Three phase line / load reactors offer an economical solution to a variety of application problems at adjustable speed motor drive installations. Harmonic compensation maximizes the reactors benefit to the ASD input circuit, while PWM / IGBT protection maximizes their performance in the drive output circuit. Among the benefits of our harmonic compensated, PWM/IGBT protected line / load reactors are:
l l l l l l l l l
Improved Motor Drive System Reliability Reduced Motor Drive System Downtime Improved True Power Factor Virtual Elimination of Inverter Nuisance Tripping Attenuation of Input Current Harmonics Extended Motor Life Reduced Motor Peak Voltage Reduced Motor dv/dt Spikes Reduced Motor Temperature and Noise
GE Industrial Systems
GE Line/Load Reactors
Line Reactor
Load ReactorL
Figur e 1: T ypical Installation Figure Typical
Without GE Load Reactor
With 5% Impedence GE Load Reactor
Figure 2: Motor Voltage from Typical PWM Inverter Output With & Without Load Reactor
General Reactor Specifications
Available in 1.5%, 3%, 5% impedance 600 Volt Class, 50/60 Hz (for 208-600 volts) Standard ratings: .75 HP through 750 HP UL, cUL, Approved Open or Nema Type 1 IGBT (PWM) Protection Fundamental Amps: 2 through 750 Max Continuous Amps: 3 through 1125 Harmonic Compensated (UL approved continuous current rating is 150% of the fundamental rating) 4000V Dielectric strength UL Class H (180 C) insulation system 115 C temperature rise, 45 C ambient 16,000 volt /sec (dv/dt rating) CE Marked
g
DEA-223
GE Industrial Systems
GE Transmission, Distribution & Industrial Systems 381 Broadway, Ft. Edward, NY, 12828 [Link]/capacitor
1999 General Electric Corporation