0% found this document useful (0 votes)
71 views3 pages

Elevator Sensor Validation & Calibration Guide

The document provides instructions to validate and calibrate a level sensor for an elevator. It involves disconnecting and reconnecting the sensor, setting a variable pointer, and using a meter to check voltage readings with the probe uncovered and covered. The calibration procedure zeroes and spans the sensor by setting the pointer, pressing buttons until indicators light permanently, and returning the pointer to validate. Diagrams show the sensor probe circuitry and connections.

Uploaded by

Balog Sunny
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
71 views3 pages

Elevator Sensor Validation & Calibration Guide

The document provides instructions to validate and calibrate a level sensor for an elevator. It involves disconnecting and reconnecting the sensor, setting a variable pointer, and using a meter to check voltage readings with the probe uncovered and covered. The calibration procedure zeroes and spans the sensor by setting the pointer, pressing buttons until indicators light permanently, and returning the pointer to validate. Diagrams show the sensor probe circuitry and connections.

Uploaded by

Balog Sunny
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd

Validation Procedure

1. Disconnect the termination and Remove the level sensor from the elevator. 2. Ensure the Variable setting pointer (A) is on 1 3. Reconnect terminal 1 and 2 and connect your meter to terminal 3 & 2. 4. 5. Probe uncovered the switch indicator led (6) remains lit, voltmeter at 3 & 2 reads 24V DC. Probe covered the switch indicator led (6) goes-off after10s delay; voltmeter at 3 & 2 reads 0V DC.

See fig 2
Calibration Procedure Zero Calibration: 1. Ensure probe is uncovered. 2. Set Variable pointer to 2, press button B until the indicator 1 becomes on permanently. Span Calibration: 1. Ensure probe is covered. 2. Set Variable pointer to 2, press button C until the indicator 5 becomes on permanently. 3. Finally return the pointer to 1 and validate.

See fig 1. fig 1

fig 2 multi-meter

Sensor Probe

24V from DCS DI input (Channel 1) port1 from DCS

0V

Return lead to DCS DI input (Channel1) port2 Note: Probe covered High capacitance Probe Uncovered Low capacitance Emitter Low Resistance High Resistance 1 +24V DC Base

Input Signal Capacitance Probe

PNP
Collector

Xc =1/wC

(Body of the bucket Elevator or sensor) Earth 3