0% found this document useful (0 votes)
491 views2 pages

Fan Schedule

The document lists the motors, control panels, and interfaces for various installations including AHU, exhaust fans, pumps, and more. It describes that the installations have motors ranging from 1.38KW to 45KW, with most having control panels and interfaces for BMS and fire alarm systems. The motors are controlled by starters like star-delta, DOL, and VFD depending on the installation and motor specifications. Duty and standby configurations are mentioned for some equipment.

Uploaded by

kkn1234
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
491 views2 pages

Fan Schedule

The document lists the motors, control panels, and interfaces for various installations including AHU, exhaust fans, pumps, and more. It describes that the installations have motors ranging from 1.38KW to 45KW, with most having control panels and interfaces for BMS and fire alarm systems. The motors are controlled by starters like star-delta, DOL, and VFD depending on the installation and motor specifications. Duty and standby configurations are mentioned for some equipment.

Uploaded by

kkn1234
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

S.

NO INSTALLATION UNIT
No of
Motors
Control
Panel inside
MCC
Interface with Remark
A FAN SCHEDULE
SMB -AHU( TO BE MADE AS MCC-AHU)
TAHU-1 Supply Motor Part =30 KW Nos 1 1 WITH SDS BMS STAR DELTA STARTER
TAHU-1 Exhaust Motor Part =15 KW Nos 1 1 WITH SDS BMS STAR DELTA STARTER
Circulating Pump Motor Part =3 KW Nos 1 1 WITH DOL BMS DOL STARTER
TAHU-2 Supply Motor Part =30 KW Nos 1 1 WITH SDS BMS STAR DELTA STARTER
TAHU-2 Exhaust Motor Part =15 KW Nos 1 1 WITH SDS BMS STAR DELTA STARTER
Circulating Pump Motor Part =3 KW Nos 1 1 WITH DOL BMS DOL STARTER
3 AHU R-01 (11KW) Nos 1 1 WITH DOL
BMS DOL STARTER
MCC-EX.F
1 HSF-1 ( 2 x 5.5 KW) Nos 2 1 WITH DOL
Firealarm&BMS 1Duty&1Standby
2 HSSF-1 (2 x 13.2 KW) Nos 2 1 WITH SDS Firealarm&BMS 1Duty&1Standby
3 EXF-1 ( 4 KW) Nos 1 1 WITH DOL
Firealarm&BMS DOL STARTER
MCC-R@ROOF
1 Booster Pump (5 KW) Nos 2 ALREADY
SUPPLIED
BMS
Feederalone
1Duty&1Standby
2 Pressurization fan -1 (18.5 KW) Nos 1 1 WITH SDS Firealarm&BMS Singlespeedmotor
3 Pressurization fan -2 (9.2 KW) Nos 1 1 WITH DOL
Firealarm&BMS Singlespeedmotor
4 Pressurization fan- 3 (9.2 KW) Nos 1 1 WITH DOL
Firealarm&BMS Singlespeedmotor
5 Pressurization fan -4 ( 6 KW) Nos 2 1 WITH DOL Firealarm&BMS
1Duty&1Standby,
singlespeedmotor
6 Cleaning equipment (5 KW) Nos 0 0 3PhaseSocketoutlet
7 Flashing Beacon control panel Nos 0 0 Feederalone
MCC-CH.W/P
1 Primary Water Pump - (4 x 30 KW) Set 4(3D+1S) 4 With 4 SDS
BMS With4SDS
2 Secondary Water Pump - (4 x 45 KW) set 4(3D+1S) 4 With 4 VFD
BMS With4VFD
MCC-B1
1 7 J etfans ( 2.53 KW each,3 phase) Nos 7 7 WITH DOL Firealarm,BMS&COsystem Low,Highspeed
2 FAF-01 (2.53 KW/0.58KW) Nos 1 1 WITH DOL
Firealarm,BMS&COsystem TwospeedMotor
3 FAF-02 (8.28 KW/ 2.07 KW) Nos 1 1 WITH DOL
Firealarm,BMS&COsystem TwospeedMotor
4 EX-01 (12.1 KW / 3.3 KW) Nos 1 1 WITH SDS
Firealarm,BMS&COsystem TwospeedMotor
1
2
5 EX-02 (12.1 KW / 3.3 KW) Nos 1 1 WITH SDS
Firealarm,BMS&COsystem TwospeedMotor
6 IRREGATION PUMP (6 KW) Nos 2 ALREADY
SUPPLIED
BMS
Feederalone,1Duty&
1standby
MCC - B2
1 7 J etfans ( 2.53 KW each,3 phase) Nos 7 7 WITH DOL Firealarm,BMS&COsystem Low,Highspeed
2 EXF-2 ( 1.38 KW /0.35 KW) Nos 1 1 WITH DOL
Firealarm&BMS TwospeedMotor
3 EXF-4 ( 1.38 KW /0.35 KW) Nos 1 1 WITH DOL
Firealarm&BMS TwospeedMotor
4 FRAF-2 (1.38 KW/ 0.35 KW) Nos 1 1 WITH DOL
Firealarm&BMS TwospeedMotor
5 FRAF-4 (1.38 KW/0.35 KW) Nos 1 1 WITH DOL
Firealarm&BMS TwospeedMotor
6 EXF-03 (12.1 KW / 3.3 KW) Nos 1 1 WITH SDS
Firealarm,BMS&COsystem TwospeedMotor
7 EXF-04 (12.1 KW / 3.3 KW) Nos 1 1 WITH SDS
Firealarm,BMS&COsystem TwospeedMotor
8 FAF-03 (8.28 KW /2.07 KW) Nos 1 1 WITH DOL
Firealarm,BMS&COsystem TwospeedMotor
9 SUMP PUMPS-1 (2.2 KW)
Nos
2 ALREADY
SUPPLIED
BMS
Feederalone,1Duty&
1standby
10 SUMP PUMPS-2 (2.2 KW)
Nos
2 ALREADY
SUPPLIED
BMS
Feederalone,1Duty&
1standby
11 SUMP PUMPS-3 (2.2 KW)
Nos
2 ALREADY
SUPPLIED
BMS
Feederalone,1Duty&
1standby
12 SUMP PUMPS-4 (2.2 KW)
Nos
2 ALREADY
SUPPLIED
BMS
Feederalone,1Duty&
1standby
SMB-G
1 ADD one FRAF-3 (1.38 KW/0.35 KW) Feeder Nos 1 1 WITH DOL
Firealarm&BMS TwospeedMotor