Time Step Simulation
Caroline Marzinzik
[email protected]
Time Step Simulation
It is often useful to assess how power system quantities vary hour by hour (or smaller time steps) due to changes in load, generation, transmission line status, etc. The Time Step Simulation (TSS) allows you to obtain power flow, OPF, and SCOPF solutions for a list of time points for which input (scenario) data has been specified. It also allows you to model actions that occur at specific times, as well as periodic actions.
2010 PowerWorld Corporation
History
Originally designed for studying optimal power flow results on an hour-by-hour basis (2001?)
Specifically for TVA
Released for general use with Simulator Version 11 (April 2005)
Power flow as well as OPF Specify time points with a resolution of minutes Patch release April 2006 specify time points with a resolution of seconds
BPA Quasi-Steady State Analysis (May 2010)
Time delays for switched shunts and transformers Time Step Actions Injection Groups time point input CSV file output
2010 PowerWorld Corporation
BPA Changes
Sequence power flow studies (quasi-steady state) Model variable MW output of a large number of wind power plants over several hours to verify proper voltage profiles can be maintained under all operating conditions Plan secondary voltage resources and controls by implementing the order of slower system characteristics (few seconds to minutes/hours)
Load characteristic changes LTC Switched shunts Remedial action schemes Equipment status changes
4
2010 PowerWorld Corporation
Switched Shunt Time Delay
Must specify that a switched shunt be allowed to use a time delay during the time step simulation run Primary and optional secondary regulation ranges with time delays for switching All parameters stored with switched shunt objects in PWB and not in TSB
Switched Shunt dialog Switched Shunt Records case information display
Only evaluated and implemented if doing a complete time step simulation run
Must click Do Run button
2010 PowerWorld Corporation
Switched Shunt Time Delay
Switched shunts not using time delays operate as usual during a Time Step Simulation study with one exception
Switched shunts not using time delays are fixed in the step where the shunts that are using time delays are processed
Switched shunts using time delays are fixed at the beginning of the time step run
Processed after all other time point inputs are applied Only allowed to switch after time delay is met while regulated value is outside regulation range
2010 PowerWorld Corporation
Switched Shunt Time Delay
Control mode for one shunt at a bus must NOT be set to Fixed
Primary Regulation Range Regulated Bus Case and area shunt control must be enabled Blocks must be defined to specify how much shunt can move at each time step 7
2010 PowerWorld Corporation
Switched Shunt Time Delay
Must be checked to model time delay
Determines maximum Mvar change per time step Delay used once regulated value first falls outside regulation range Delay used once shunt starts switching but has not met regulation range
Optional Secondary Regulation Range
2010 PowerWorld Corporation
Switched Shunt Time Delay
Time delay-specific fields
2010 PowerWorld Corporation
Using Secondary Regulation Range
Expectation is that secondary regulation range is larger and time delays are shorter for controls to act more quickly to larger deviation One range must be completely contained within the other to prevent conflicting control actions Secondary regulation range is always checked first
Primary timer is only started if the time delay for secondary range is not met or the regulated value is within secondary regulation range
2010 PowerWorld Corporation
10
Switched Shunt Time Delay
Time
12:00:00 AM 12:00:01 AM 12:00:02 AM
Bus 3 pu Volt
0.9942 0.9942 0.9942
Shunt 3 #1 Nominal Mvar
50.0 50.0 50.0
Comments
12:00:03 AM
12:00:04 AM 12:00:05 AM 12:00:06 AM 12:00:07 AM 12:00:08 AM 12:00:09 AM
0.9711
0.9711 0.9768 0.9768 0.9824 0.9824 0.9824
50.0
50.0 60.0 60.0 70.0 70.0 70.0
Start Secondary and Primary Timers, First Move Delay applicable
Secondary Move (2 sec. delay), Reset Timers, Next Move Delay applicable Start Secondary and Primary Timers Secondary Move (1 sec. delay), Reset Timers Start Primary Timer
12:00:10 AM
12:00:11 AM 12:00:12 AM 12:00:13 AM
0.9882
0.9882 0.9882 0.9939
80.0
80.0 80.0 90.0
Primary Move (2 sec. delay), Reset Timers
Start Primary Timer Primary Move (2 sec. delay), Reset Timers, First Move Delay applicable
2010 PowerWorld Corporation
11
Processing Switched Shunts
Any switched shunt meeting time delay and regulated value is outside regulation range will be processed to determine switching Each shunt meeting this condition is processed one-by-one in the order of ascending bus number
If any adjustments are made to a shunt, an estimate is made of any impact on system voltages and voltages are updated before the next switched shunt in the list is processed
2010 PowerWorld Corporation
12
Processing Switched Shunts
Only one switched shunt at a bus allowed to be on control at a time Multiple switched shunts at the same bus processed one-by-one in iterative steps Process is repeated until all shunts that are allowed to be on control for the time step have been processed
2010 PowerWorld Corporation
13
Multiple Switched Shunts on Control at Same Bus
Multiple switched shunts at the same bus are allowed to be on control when using the Time Step Simulation tool
Not currently allowed during standard power flow solution One shunt at a bus must be specified as not fixed and this dictates the Control Mode for the others using time delays at that bus
2010 PowerWorld Corporation
14
Iterative Process for Switched Shunts Example
At a given time step, 6 switched shunts meet time delay and outside regulation range Process these shunts while all other shunts are fixed At each iteration shunts are processed one-by-one in the order of Bus 1, Bus 2, Bus 3
Any switching is done and then voltage estimates are used to update the voltages before the next shunt is processed
Only one shunt at a given bus can be on control during an iteration
Iteration
1
2 3
Bus 1 Shunt A
Discrete
Fixed Fixed
Bus 2 Shunt B
Discrete
Fixed Fixed
Bus 2 Shunt C
Fixed
Discrete Fixed
Bus 3 Shunt D
Discrete
Fixed Fixed
Bus 3 Shunt E
Fixed
Discrete Fixed
Bus 3 Shunt F
Fixed
Fixed Discrete
2010 PowerWorld Corporation
15
Transformer Time Delay
Must specify that a transformer be allowed to use a time delay during the time step simulation run Primary and optional secondary regulation ranges with time delays for tap switching All parameters stored with transformer objects in PWB and not in TSB
Branch Information Dialog Transformer Control Records case information display
Only evaluated and implemented if doing a complete time step simulation run
Must click Do Run button
2010 PowerWorld Corporation
16
Transformer Time Delay
Transformers not using time delays operate as usual during a Time Step Simulation study with one exception
Transformers not using time delays are fixed in the step where the transformers that are using time delays are processed
Transformers using time delays are fixed at the beginning of the time step run
Processed after all other time point inputs are applied Only allowed to change tap/phase positions after time delay is met while regulated value is outside regulation range
2010 PowerWorld Corporation
17
Transformer Time Delay
Control must be enabled for transformer or phase shifter
Area transformer control must be enabled along with case transformer and phase shifter control
2010 PowerWorld Corporation
18
Transformer Time Delay
Primary Regulation Range (pu Voltage, Mvar, or MW) Determines how much tap or phase can move at each time step
2010 PowerWorld Corporation
19
Transformer Time Delay
Must be checked to model time delay Determines maximum tap/phase change per time step Delay used once regulated value first falls outside regulation range Delay used once transformer starts switching but has not met regulation range Optional Secondary Regulation Range (pu Voltage, Mvar, or MW)
2010 PowerWorld Corporation
20
Transformer Time Delay
Time delayspecific fields. Can also be found on the Line and Transformer Records display.
2010 PowerWorld Corporation
21
Processing Transformers
Any transformer meeting time delay and regulated value is outside regulation range will be processed to determine tap/phase switching Transformers meeting this condition will be processed in the same manner that transformers on control are processed in the regular power flow solution
Balancing parallel LTC taps Transformer Stepping Methodology Min. Sensitivity for LTC Control Model Phase Shifters as Discrete Controls
22
2010 PowerWorld Corporation
Time Step Actions
Conditional actions that can be implemented following a time delay Based off contingency elements with addition of time delay and requirement that Model Criteria be defined Can be defined from
Time Step Actions page of Time Step Simulation dialog Model Explorer under Solution Detail\Time Step Actions
Saved with PWB and not in TSB Only evaluated and implemented if doing a complete time step simulation run
Must click Do Run button
2010 PowerWorld Corporation
23
Creating/Modifying Time Step Actions
Right-click and choose Insert to create new action Right-click on existing action and choose Show Dialog to modify Can also create/modify from Model Explorer: Solution Detail\Time Step Actions
2010 PowerWorld Corporation
24
Time Step Action Dialog
Specified in the same manner as Contingency Elements
CHECK or NEVER
Model Criteria (Model Filter or Model Condition) must be specified for action to be considered
2010 PowerWorld Corporation
Minimum Time Delay is 1 second
25
Time Step Actions Example
Adjust generator voltage setpoint and open switched shunt based on Model Criteria
Action implemented
Time Delay = 1 sec. Conditions met one time step (10 seconds between time steps) prior to the implementation time step.
2010 PowerWorld Corporation
26
Time Step Actions Example
Action implemented
Time Delay = 56 sec. Conditions met 6 time steps (10 seconds between time steps) prior to the implementation time step.
2010 PowerWorld Corporation
27
Time Step Actions Example
Model Criteria: JONES_CANYON_LEANJ2 2 switch out L1 and L2 Contains 4 Model Conditions
JONES_CANYON_LEANJ2 2 34.5 kV C1 open Met for Shunt 95003 #C1 Status = Open JONES_CANYON_LEANJ2 2 34.5 kV L1 closed Met for Shunt 95003 #L1 Status = Closed
2010 PowerWorld Corporation
28
Time Step Actions Example
JONES_CANYON_VAR_CONTR_ENABLE Met for Bus 47814 227.7< kV Voltage <246
JONES_CANYON_LEANJ2W2_switch_out_L1_and_L2 Met for Generator 95005 #W3 Mvar Output > 2 Mvar
2010 PowerWorld Corporation
29
Processing Time Step Actions
Any time step action meeting time delay and Model Criteria will be implemented All actions are evaluated to determine which should be implemented without actually implementing Prevent one action from influencing another in the same time step
2010 PowerWorld Corporation
30
Flow of Time Step Run
1) Start the time step simulation by clicking the Do Run button on Time Step Simulation dialog 2) Initialize time delay objects and check for data errors If any errors result, provide user option to continue with Simulator fixing the errors or abort the run so that user can fix the errors
Transformers and switched shunts that are modeling switching delays are turned off automatic control
2010 PowerWorld Corporation
31
Flow of Time Step Run
3) Process a time point If applying pre-script command before applying input data, run pre-script command If Apply Input Data
Update loads, MW and Mvar Update generators, MW and Max MW Update line statuses Update area loads, MW and Mvar Update zone loads, MW and Mvar Update injection group injections Apply custom inputs
2010 PowerWorld Corporation
32
Flow of Time Step Run
If Apply Schedule Data
Apply schedule actions
If Input Data and Schedule Data can be applied with no errors or not applying these at all
If applying pre-script command after applying input data, run pre-script command If choosing to Apply and Solve
Solve power flow If successful power flow solution
2010 PowerWorld Corporation
33
Flow of Time Step Run
If any objects modeling time delay, check for time delay implementation Switched Shunts Transformers Time Step Actions If any system changes, solve power flow If still successful power flow solution (time delay actions implemented and power flow solves or no time delay actions implemented) If Solution Type <> Single Solution, run unconstrained OPF, OPF, or SCOPF If Run Contingencies = YES, run contingency analysis
2010 PowerWorld Corporation
34
Flow of Time Step Run
If applying post-script command before storing results, run post-script command Store results If applying post-script command after storing results, run post-script command 4) Continue processing time points until all completed go back to step 3 5) Restore time delay objects to original control modes
2010 PowerWorld Corporation
35
Injection Groups Input
Allows easy scaling of groups of generators (such as wind farms) Loads and generators can be scaled together or separately as part of injection groups The same loads and generators should not be placed in multiple injection groups that are used in the time step scaling
2010 PowerWorld Corporation
36
Specifying Injection Groups Input
2010 PowerWorld Corporation
37
Specifying Injection Groups Input
Specifies the net MW injection for loads and generators in the injection group Generator MW limits are enforced Generators scaled regardless of AGC status No Mvar adjustments Positive load is not enforced
Check this to prevent generator changes from being modified due to AGC
2010 PowerWorld Corporation
38
CSV File Output
Avoid filling up computer memory by writing results to file Separate file created for each type of object
Areas, Buses, Generators, InjectionGroups, Interfaces, Lines, Owners, SuperAreas, Zones, Transformers, Loads, and Shunts
Optionally save to memory only, CSV file only, or both
When not saving to memory, Results tables will contain zeros
2010 PowerWorld Corporation
39
CSV File Output
CSV file options contained on the Options page of the Time Step Simulation dialog
Select where the results should be stored Key field to use for identifying objects within the file File prefix - file will be named CSV File Identifier_objectname.CSV
Location where files should be written
2010 PowerWorld Corporation
40
CSV File Output
Time point identification
Object identifier based on key field selection Field identifier
Date,Time,[3] PU Volt 10/4/2010,12:00:00 AM,0.99421638250351 10/4/2010,12:00:01 AM,0.99421638250351 10/4/2010,12:00:02 AM,0.99421638250351 10/4/2010,12:00:03 AM,0.971107363700867 10/4/2010,12:00:04 AM,0.971107363700867 10/4/2010,12:00:05 AM,0.976763546466827 10/4/2010,12:00:06 AM,0.976763546466827 10/4/2010,12:00:07 AM,0.982440531253815 10/4/2010,12:00:08 AM,0.982440531253815 10/4/2010,12:00:09 AM,0.982440531253815 10/4/2010,12:00:10 AM,0.988180339336395 10/4/2010,12:00:11 AM,0.988180339336395 10/4/2010,12:00:12 AM,0.988153159618378 10/4/2010,12:00:13 AM,0.993943929672241 10/4/2010,12:00:14 AM,0.993943929672241 ... 2010 PowerWorld Corporation
41
Time Step Simulation
In this section well learn how to:
Set up and maintain a list of time points Specify time point input data Specify scheduled input data Customize the results we want to store from the solution Run continuous and timed simulations
Open the B7flat.PWB case. To access the Time Step Simulation dialog, in Run Mode, go to the Tools ribbon tab and select Time Step Simulation.
2010 PowerWorld Corporation
42
Inserting New Time Points
The first step in setting up a Time Step Simulation is to define a list of time points.
This is a list of points in time for which Simulator will obtain solutions.
In the Time Step Simulation dialog, rightclick on the grid and select Insert New Timepoint(s), or press the Insert Time Points button.
2010 PowerWorld Corporation
43
Inserting New Time Points
As an example, assume we want to simulate 24 hours, starting on May 18, 2006 at 1:00 AM
Click to select the date from a calendar component Number of time points that will be inserted
Specify the interval between time points. Maximum resolution is 1 second.
2010 PowerWorld Corporation
44
Inserting New Time Points
After Inserting the Time Points, the Time Step Simulation dialog looks like this:
By default dialog shows the Summary page
2010 PowerWorld Corporation
45
Time Step Simulation Dialog
Can specify the simulation starting and ending date and time Simulation control buttons
Summary page contains list of time points just inserted
2010 PowerWorld Corporation
Solution Type
Simulation progress
46
Summary Page: Controlling Solution
During the simulation you can skip a Time Point or you can pause at a Time Point
The Time Point Solution Type can be:
Single Solution: Same as hitting the single solution button, but would act on the corresponding time point. Unconstrained OPF Optimal Power Flow (OPF) Security Constrained Optimal Power Flow (SCOPF)
Different time points can have different solution types
2010 PowerWorld Corporation
47
Time Step Simulation Dialog
The input data and the results of the Time Step Simulation can be saved in a Time Series Binary (*.TSB) file. (Time Step Actions saved in .PWB)
.TSB file Control
Deletes results, input and scheduled input data, and the list of time points
2010 PowerWorld Corporation
48
Summary Page: Script Commands
You can specify pre- and post script commands for each time point. This allows you to perform almost every possible Simulator action before and after a time point is solved. Typical actions are running contingency analysis or saving particular set of results.
2010 PowerWorld Corporation
49
Summary Page: Script Command Tips
It is a good idea to first test the script commands in script mode, to avoid potential syntax errors. To edit the script command cell, double-click on the cell.
You can copy/paste from the cells as usual You can also copy/paste from excel or the clipboard.
To delete a script command, double-click and hit the Delete or Backspace buttons. To clear all the scripts commands in a column, right-click on the grid and select Set/Toggle/Columns Set All Values To. Then just press OK without typing anything in the dialog.
2010 PowerWorld Corporation
50
Setting up Input Data
Input data for each time point is specified in the Input pages for:
Load MW/Mvar Generation MW/Max MW Line Status Area MW Load Zone MW Load Injection Group MW
All these Input pages are matrix grids. This means that each row corresponds to a time point, and each column corresponds to the specific object for which data will be specified. Very detailed time-varying inputs may be specified on the Custom Inputs pages
2010 PowerWorld Corporation
51
Setting up Input Data
Thus we need to explicitly tell Simulator which generators, loads, etc. will have input data.
The objects that do not have input data (or scheduled input data) will keep the values from the case.
The matrix grids will have one column for the input data of each object. In the B7flat.pwb case, suppose that we want to specify Load MW data for Loads 2 and 3.
In the Input page MW Loads page, right-click and select Time Point records Insert/Scale Load Column(s)
2010 PowerWorld Corporation
52
Setting up Input Data
By default, we just want to insert new columns We just need active load
Use the selector component to select Loads 2 and 3 at the same time.
2010 PowerWorld Corporation
53
Setting up Input Data
The columns will contain zeros by default. Those will need to be filled with correct data.
In order to specify time point values, we can: 1. Enter the values manually (as shown in the Figure) 2. Read load values from Excel using the corresponding button. 3. Paste values from Excel (Copy the headers to Excel first). 4. Derive the values from another column. 5. Scale the column values.
2010 PowerWorld Corporation
54
Setting up Input Data
Example: We have specified some values for Loads 2 and 3 (as shown in the previous slide). Suppose we also need to specify input data for Loads 4 and 5, and know that those vary as Load 3, but are 90% of it.
We can derive the values for Loads 4 and 5 from Load 3.
Right-click on column for Load 3 and select Time Point records Insert/Scale Load Column(s).
Column 3 will now be the Current Column
2010 PowerWorld Corporation
55
Setting up Input Data
Column 3 becomes the current column
Loads 4 and 5 will be 90% of Load 3
Use the selector component to select Loads 4 and 5, whose values will be derived from Load 3.
2010 PowerWorld Corporation
56
Setting up Input Data
The Input Load MW page now looks like this:
Columns derived as 90% of Load 3
2010 PowerWorld Corporation
57
Setting up Input Data
We can use the column plot to check our input data. The plot column function of Case Information Displays becomes a plot versus date time when used from Time Step Simulation matrix grids.
To plot a column, rightclick on the column and select Set/Toggle/Columns Plot Column from the Local Menu. You can also drag the mouse across several columns to plot multiple columns. The Load MW for Loads 2-5 looks like this.
2010 PowerWorld Corporation
58
Setting up Input Data
Since we have spent some time defining our input data, it is probably good to save the input data in the .TSB file. Press the Save TSB File button, and save the data as B7TSS.TSB
2010 PowerWorld Corporation
59
Setting up Input Data
In the same manner as we did for load MW, hourly data for other quantities would be specified in the corresponding pages:
Mvar Loads Gen Actual MW Gen Max MW Line Status Area Loads Zone Loads Injection Groups
Recall that you can use the selector to create multiple columns at a time, and you can copy/ paste the input data from Excel.
2010 PowerWorld Corporation
60
Setting Up Results
During the time step simulation, Simulator obtains a PF/OPF/SCOPF solution for each time point. The amount of information that is generated may be significant since each time point can potentially contain the information of a solved PF, OPF, or SCOPF case.
For large systems, storing all these information may be limited by memory.
Typically, you dont need to examine all the system quantities. The Time Step Simulation requires you to explicitly define which quantities you want to explore.
2010 PowerWorld Corporation
61
Setting Up Results
Select the Results page:
Modify the Results Definitions Results Display Options
Result pages By default no objects are shown
2010 PowerWorld Corporation
62
Setting Up Results
Press the View/Modify Result Definitions button to tell Simulator the quantities you want to store. You will need to specify:
The type of object for which results must be saved (buses, generators, etc.) The individual objects whose fields will be saved (Bus 1, Bus 2, etc.) The fields that will be saved for each type of objects (Bus pu volt, etc.)
2010 PowerWorld Corporation
63
Setting Up Results
Select the Buses page Click Add/Remove Fields to modify list of fields to store
For our example, assume we want to explore per unit voltage and angle for all the buses.
Save and Close the Result Definitions
Set to YES the buses for which you want to store the fields (By default all are set to NO)
2010 PowerWorld Corporation
Result Definitions are also saved in the .TSB file.
64
Running the Simulation
Now that we have set input data and specified which results we need to store, we can run the simulation. Simulator will obtain a solution for each time point depending on the solution type. In order to start the simulation, press the Do Run button.
During the simulation, you will see how the Last Result box and the Progress Bar are updated.
2010 PowerWorld Corporation
65
Running the Simulation
Simulator will do the following at each time point:
Look at the time point skip/pause flag and act accordingly Run a pre-script command if it was specified Apply time point and scheduled input data.
Well learn how to set scheduled input data later on.
Obtain the PF/OPF/SCOPF solution Set the Processed flag in the Summary page Update the Last Result and Progress Bar indicating the status of the solution. Write the results to the Result pages Run a post-script command if it was specified
2010 PowerWorld Corporation
66
Exploring Results
For our example, the Buses page of the Results shows bus voltages and angles. The results can be grouped by objects or by fields.
BUS 1
BUS 2
2010 PowerWorld Corporation
67
Exploring Results
We can also explore the results by obtaining a column plot. This is how the bus angles look in our example.
2010 PowerWorld Corporation
68
Specifying Scheduled Input Data
Besides time point input data, the Time Step Simulation allows you to specify scheduled data. Scheduled data is used for data that more naturally spans multiple time points rather than being defined at each time point
Line statuses Generator, load, capacitor and reactor statuses MW levels of scheduled transactions Number of capacitor/reactor blocks Generator voltage set points etc.
69
2010 PowerWorld Corporation
Specifying Scheduled Input Data
Schedule input data requires a schedule and a schedule subscription. The schedule defines how a quantity varies in time (just a shape). It is a list of time points together with Numeric or Yes/No values. By subscribing an object field (Line status, Gen MW, Transaction MW level, etc.) to a schedule, we can make this object field vary according to the shape of the schedule. Schedules are implemented as sets of actions that are applied to the power flow case at the next available time point.
2010 PowerWorld Corporation
70
Specifying Scheduled Input Data
Schedule
Value
Time Point List
t
Subscription
t
Gen MW
Object Field
t
2010 PowerWorld Corporation
71
Defining a Schedule
Schedules:
Are Numeric, Yes/No, or Text Can be made periodic by specifying them to repeat the shape with a certain period. Can have start and end validity dates (used normally for periodic schedules).
To define a schedule go to the Input page Schedules page, right-click on the grid, and select Insert New Schedule.
2010 PowerWorld Corporation
72
Defining a Schedule
Schedule name must be unique Identifies main characteristics of schedule Shortcut buttons allow easy definition of the schedule date times
Settings for periodic Schedules
Date times dont need to coincide with the date times of the list of time points (Summary page)
2010 PowerWorld Corporation
Date time and numeric values define the shape of the schedule
73
Defining a Schedule Subscription
Most enterable fields from the following object types can subscribe to schedules: Generators, Loads, Line/transformers, Shunts, Areas, Transactions, and Zones Numeric fields subscribe to Numeric Schedules, Boolean fields subscribe to Yes/No schedules, and Custom Strings and Memo fields subscribe to Text schedules. To define a schedule subscription, go to the Input page Sched Subscriptions page, right-click on the grid, and select Insert New Subscription.
2010 PowerWorld Corporation
74
Defining a Schedule Subscription
1. Select the object type: Gen, Load, Line/Xfrmr, Shunt, Area, Transaction or Zone. 2. Select the particular object from the power flow case. 3. Select the field that will subscribe to the schedule 4. Select the schedule the field will subscribe to. Press to select multiple objects that subscribe to the same schedule
For instance, this means that the Gen MW output of Generator 1 at bus 1 will follow the shape of Schedule 1.
2010 PowerWorld Corporation
When you select a field, this label changes telling whether the field is Numeric or Yes/No
75
Defining a Schedule Subscription
Schedule actions are applied with the specified delay
Subscriptions to numeric schedules can modify the schedule values: Actual Value = Multiplier *Sched Value + Value Shift
2010 PowerWorld Corporation
76
Example: Scheduled Input Data
In the B7Flat.pwb case, the following input data is known for Gen 1 and line 2 to 3. The generator values occur every day.
Hour 1:00 AM 7:00 AM 1:00 PM 7:00 PM Gen 1MW 60 MW 80 MW 120 MW 100 MW Hour 4:00 AM 2:00 PM Line 2-3 Status Open Closed
We want to create the schedules and schedules subscriptions needed to model these varying quantities.
2010 PowerWorld Corporation
77
Example: Schedules
For the generator, we create a periodic schedule with period = 1 day.
The schedule is numeric. The schedule has 4 time points.
2010 PowerWorld Corporation
78
Example: Schedule Subscriptions
Then we subscribe the Gen MW output filed of generator 1, ID 1 to Sched1. There is no delay The field takes the exact values of the numeric schedule.
Note: Gen1 needs to be Off-AGC in order to keep the scheduled MW output. Manually set or use option 79
2010 PowerWorld Corporation
Example: Schedules
For the transmission line, we create a non-periodic schedule The schedule type is Yes/No. The schedule has 2 time points. Line will open at 4 AM and will close at 2 PM.
2010 PowerWorld Corporation
80
Example: Schedule Subscriptions
Then we subscribe the Status of Transmission Line 2 to 3, circuit 1 to Sched2. There is no delay
Let us go ahead and rerun the Time Step Simulation.
2010 PowerWorld Corporation
81
Example: Schedule Subscriptions
By exploring the results, we can see how bus angles changed due to load variations, the generator schedule and the outage of the transmission line.
Bus Tim epoint Custom Results Variables 5
Values
6:00 AM 1 Angle (Deg) 6 Angle (Deg) 2 Angle (Deg)
12:00 PM DateTime 3 Angle (Deg)
6:00 PM 4 Angle (Deg) 5 Angle (Deg)
12:00 AM
2010 PowerWorld Corporation
82
Schedule Subscriptions
The advantage of schedules and schedule subscriptions is that power systems tend to have many quantities that follow a similar time pattern:
Bus loads of the same type Different units of a power plant that are identically scheduled A group of devices that are disconnected/reconnected at the same time. For instance, groups of capacitor or reactors.
Using schedules, one avoids having to specify time point data for each field, which would be tedious and would require large quantities of memory.
2010 PowerWorld Corporation
83
Time Step Actions
Special conditional actions may be modeled with time delays These are typically useful only for very detailed simulations with time steps on the order of several seconds or less, where the objective is to analyze switching behavior and resulting time-domain voltage profiles (e.g. wind farm operation) Time Step Actions are only considered for complete Time Step Runs (those started using Do Run button) Actions can be applied again, following the appropriate time delay, if model criteria is met Switched shunts and transformers may also incorporate switching delays (specified with individual shunt and transformer records)
2010 PowerWorld Corporation
84
Time Step Actions
Example: Open a transmission line if it has been overloaded for at least 5 minutes
2010 PowerWorld Corporation
85
Time Step Actions
Time Step Options for AVR transformer Typical application would be detailed time-domain voltage modeling of wind farm
2010 PowerWorld Corporation
86
Custom Inputs
Custom inputs allow specification of more detailed parameters in the time domain for several object types Example: generator voltage setpoint
2010 PowerWorld Corporation
87
What is Saved in the .TSB File?
Because the amount of time information generated in the Time Step Simulation may be significant, a binary file is used to store it. This is called the Time Series Binary (.TSB) file. This file will save:
Input Data Scheduled Input Data Custom Inputs Result Definitions Results Time Simulation Options (defined in the Options page)
88
2010 PowerWorld Corporation
Continuous and Timed Simulations
By default, when you hit the Do Run button, each time step is solved immediately after the previous one. This is called a Continuous Simulation. On the other hand, the Time Step Simulation can mimic a solution in actual time by specifying a time scale. This is called a Timed Simulation. The Timed Simulation allows you to visualize the solutions on oneline diagrams as a movie.
You can see how time point and scheduled input data are applied and their effect on the system. You can also contour and animate.
2010 PowerWorld Corporation
89
Continuous and Timed Simulations
To set up a Timed Simulation go to the Options page and select Timed, in the Time Step Simulation Options under Step Control. Set the Time Scale. A time scale of 60 means that the ACTUAL time delay between the solutions of two time points with date times 1:00 AM and 2:00 AM will be 60 seconds. Thus, if the 1:00 AM point is solved now, the 2:00 AM point will be solved 60 seconds later.
2010 PowerWorld Corporation
90
Continuous and Timed Simulations
Example
Let us set the simulation to be Step Control = Timed, and set a Time Scale of 5 (1 hour runs in 5 seconds of actual time). Move the Time Step Simulation dialog so you can see the oneline, but still have access to the control buttons. Run the simulation by clicking Do Run
2010 PowerWorld Corporation
91
Continuous and Timed Simulations
System at 5 AM
60 MW OFF AGC One
1.05 pu 35 MW
A
System at 2 PM
34 MW 0 Mvar
38 MW 0 Mvar
25 MW
A
25 MW
120 MW OFF AGC One
A
41 MW
70 MW 0 Mvar
40 MW
MVA
Three
1.00 pu 13 MW 0 MW 19 MW
A A
103%
MVA
Three
1.01 pu 2 MW
A
63 MW 0 Mvar
2 MW
13 MW
1.05 pu
MVA
Four
1.00 pu
79 MW
MVA
Four
1.00 pu 27 MW
MVA
40 MW 0 Mvar
0 MW
0 MW
A
35 MW
MVA
28 MW AGC ON
80 MW 100% 0 Mvar MVA
78 MW
28 MW
A
MVA
2 MW
A
28 MW 28 MW
A
MVA
40 MW AGC ON
Two
1.04 pu 46 MW
20 MW
A
Case Hourly Cost 11155 $/hr
MVA
MVA
Two
1 MW
Case Hourly Cost 14745 $/hr
MVA
MVA
1.04 pu 55 MW 47 MW
2 MW 46 MW
29 MW
29 MW
Five
1.03 pu
Five
1.03 pu
10.8 Mvar
A
100 MW AGC ON
46 MW 3 MW
6 MW
10.8 Mvar
A
Top Area Cost 6265 $/hr
3 MW 6 MW
0 MW 0 Mvar Six
1.04 pu
MVA
MVA
34 MW 0 Mvar
160 MW AGC ON
55 MW 7 MW
15 MW
Top Area Cost 9841 $/hr
7 MW 15 MW
0 MW 0 Mvar Six
1.04 pu
MVA
MVA
63 MW 0 Mvar
MVA
Seven
3 MW 1.04 pu
MVA
Seven
7 MW 1.04 pu
3 MW
7 MW
Left Area Cost 188 $/hr
-40 MW AGC ON
MVA
200 MW AGC ON
200 MW 0 Mvar Right Area Cost 4701 $/hr
Left Area Cost 188 $/hr
-40 MW AGC ON
MVA
201 MW AGC ON
200 MW 0 Mvar Right Area Cost 4716 $/hr
Note the status of transmission line 2-3, the values of generator 1 MW output and how loads change at each time point. See how the line flows and angle contouring change (Note: Contouring should be set to continuously refresh).
2010 PowerWorld Corporation
92
Time Step Simulation Toolbar
The time step simulation toolbar is visible when the dialog is open and time points have been defined. It allows you to control the simulation (continuous or timed), without using the time step simulation dialog. Time Scale
Last Result Status Simulation Control Buttons Present Time for Timed Simulation Timed/Continuous Simulation Progress Bar used in Timed Simulation
2010 PowerWorld Corporation
93
Time Step Simulation Toolbar
Reset the Simulation
Pause a continuous or timed simulation
Solve the previous Time Point
Play the Time Step Simulation in either continuous or timed mode.
Solve the next Time Point
2010 PowerWorld Corporation
94
Summary Page Local Menu
Deletes the time point together with all the input data of that time point Applies the input data of the selected time point to the power system case (makes data available on the case information displays, oneline diagram, etc.). It does not apply scheduled input data.
Brings up a dialog to change the date/time of a time point. It sorts the list afterwards. Solves the selected time point, by first applying both time point and schedule input data. Paste (under Copy/Paste/Send) becomes enabled when the clipboard contains time step data in the correct format.
2010 PowerWorld Corporation
95
Time Step Simulation Options
When there is time point input data for area MW load and for individual load MW, always set to individual MW load value first. Then, if set to Areas, only areas are scaled. If set to Zones, only zones are scaled. Important when changing Gen Actual MW and Injection Groups OPF Pricing options Saves binding constraint results in specific results matrix grid.
2010 PowerWorld Corporation
96
Time Step Simulation Options
Time Step Simulation allows you to either Apply and Solve or just Apply Data without solving.
Sometimes you want to test only time point or schedule data
Loads the TSB automatically when the case is opened. When saving the TSB, set automatically the Default tsb to be the current tsb.
2010 PowerWorld Corporation
97
Time Step Simulation Options
Options Page
The Time Step Simulation can contour oneline diagrams as the simulation takes place. It can also save a list of the resulting images as Bitmaps or JPGs.
2010 PowerWorld Corporation
98
Time Step Simulation Options
Options Page
The Time Step Simulation can save data directly to a CSV file. This is meant to enable the time step to store data from very long runs without running out of memory.
The file identifier is used to identify the run. Individual objects have files created for them. For example, Year2010_areas.csv.
2010 PowerWorld Corporation
99
OPF and SCOPF Time Step Simulations
Users of OPF and the SCOPF add-ons can obtain time point optimal power flow and securityconstrained optimal solutions by specifying these solution types for one or more time points in the Summary page.
Make sure you become familiar with Simulator OPF and SCOPF before running a Time Step Simulation with these options.
2010 PowerWorld Corporation
100
OPF and SCOPF Time Step Simulations
Unconstrained OPF
The Time Step Simulation will remove all the constraints that would normally act in the OPF and will optimize the system to find the minimum operating cost. Simulator will change the set points of the specified controls (generators and phase shifters) to minimize the cost of all Areas and Super Areas set to OPF AGC control. Besides the power flow solution options, the Unconstrained OPF simulation will take all the options that have been defined for a regular OPF solution. Most of these options are defined in OPF Options and Results Dialog under the Add Ons ribbon tab.
2010 PowerWorld Corporation
101
OPF and SCOPF Time Step Simulations
OPF
The Time Step Simulation applies the time point and schedule input data and optimizes the control areas set to OPF to minimize cost while enforcing normal operation constraints.
This includes: transmission line thermal limits, interface limits, generator control limits, and load control limits.
The OPF algorithm detects the controls that need to be moved, the constraints that are binding at the solution point, and the unenforceable constraints, i.e., constraints that cannot be enforced with the available controls.
2010 PowerWorld Corporation
102
OPF and SCOPF Time Step Simulations
OPF
Some of the quantities that are of interest in the solution of the OPF algorithm, are displayed in the Result: Constraints Pages:
Unconstrained Generator MW Output Final generator MW Output Change in Generator MW Locational Marginal Prices: These are displayed in the Hourly Final Bus LMP Page. Average LMP prices and other LMP metrics are also available in the Results Page for Areas, Injection Groups, Super Areas, and Zones. Binding Constraints as well as Marginal Cost of Limit Enforcement for lines and interfaces.
2010 PowerWorld Corporation
103
OPF and SCOPF Time Step Simulations
SCOPF
The SCOPF combines Simulators OPF with Contingency Analysis to optimize a system for minimum cost while enforcing both normal operation and contingency constraints. The solution of an SCOPF Time Step Simulation depends on the options that have been set up for the following tools:
Power Flow Optimal Power Flow Contingency Analysis Security Constrained Optimal Power Flow Time Domain OPF Options
104
2010 PowerWorld Corporation
OPF and SCOPF Time Step Simulations
SCOPF At each time point, the SCOPF Time Step Simulation does the following:
Applies the input data and scheduled actions Solves a power flow If specified, it solves an unconstrained OPF Initializes the base case for the SCOPF by solving a power flow or an OPF Solves the contingencies for the initialized system state Solves the SCOPF optimization problem Displays the results in the matrix grids
2010 PowerWorld Corporation
105
OPF and SCOPF Time Step Simulations
SCOPF
The SCOPF often requires significant computer resources mostly because of the need to solve a large number of contingencies and to calculate their sensitivities. The size of the problem also depends on the size of the system, number of constraints (monitored elements), and number of time points considered. A mechanism to speed up the computation of the PF/OPF/SCOPF Time Step Simulation is to use DC solutions in some of the internal routines:
AC or DC power flow AC or DC contingency analysis. This one will produce the larger time savings. AC or DC SCOPF
2010 PowerWorld Corporation
106
OPF Pricing Options
Different applications of the OPF/SCOPF require special pricing options. A method for congestion pricing consist of solving first the unconstrained case to determine unconstrained LMPs, and then solve the OPF or SCOPF. The difference between these two solutions correspond to the congestion cost or congestion component of the LMP for a given hour.
Check this option to solve an unconstrained OPF (equivalent to economic dispatch) before solving the OPF or SCOPF for each time point.
2010 PowerWorld Corporation
107
OPF Pricing Options
It is also customary in LMP markets to price hydro generation at a cost equal to the unconstrained LMP. Simulator will internally modify the cost curve of the hydro generation to match the unconstrained LMP obtained during the initial unconstrained simulation. It will then solve the constrained optimization problem using this cost for the hydro units.
2010 PowerWorld Corporation
Check this option to reset the cost curve of hydro generation to the original cost after each time step. Uncheck this option to explore how Simulator changes the hydro cost to the unconstrained marginal price.
108
OPF Pricing Options
OPF and SCOPF solutions with pricing options do the following for each time step:
Apply time point and schedule input data if unconstrained then begin Solve Unconstrained OPF if price hydro then Hydro Cost = LMP end Solve OPF or SCOPF if unconstrained and price hydro and reset then Reset Price if Save then Save Binding Constraints
2010 PowerWorld Corporation
109
Time Step Simulation and Contingency Analysis
Contingency analysis will take place as part of the SCOPF.
Binding constraints will be saved in the Results: Constraints page.
Sometimes summary information of contingency analysis is required without the SCOPF
For instance, the custom results for transmission lines allows saving the Aggregate MVA Overload and Max% Loading Contingency for each transmission element.
In order to run contingency analysis for a time point, set the corresponding field to YES in the Summary page.
2010 PowerWorld Corporation
110