Midos
Type MCGG 22, 42, 52,
53, 62, 63 & 82
Overcurrent Relay for
Phase and Earth Faults
Features
Choice of 4 inverse time curves
and 3 definite time ranges by
switched selection.
Wide setting range of 0.05 x In to
2.4 x In in steps of 0.05 x In.
Time multiplier range 0.05 to 1 on
all seven characteristics.
Separate led indicators provided
on each measuring board to show
time delayed and instantaneous
operations.
Led start indicators provided to
facilitate testing.
Separate output contacts provided
for time delayed phase fault,
instantaneous phase fault, time
delayed earth fault and
instantaneous earth fault
operations.
Low ac burden.
Suitable for use with separate
direction relay.
Accurately follows time curves to
BS142 and IEC255.
High resetting ratio.
Fast resetting time.
Positive, calibrated settings by
means of switches.
Internal dc auxiliary power supply
operating over a wide input range.
Separate test mode with trip test
feature.
Indication of power to the
measuring board.
Non-volatile memory for time
delayed and instantaneous led
indicators.
Figure 1: Relay type MCGG 62 withdrawn from case.
Models available
MCGG 22
MCGG 62
Single phase overcurrent with
instantaneous element.
Three phase overcurrent with
instantaneous elements.
MCGG 42
MCGG 63
Two phase overcurrent with
instantaneous elements.
Three phase overcurrent (with
polyphase measurement), with
instantaneous element.
MCGG 52
MCGG 82
Two phase overcurrent plus earth fault
with instantaneous elements.
Three phase overcurrent plus earth
fault with instantaneous elements.
MCGG 53
Associated publications:
Two phase overcurrent (with
polyphase measurement) plus earth
fault with instantaneous elements.
3 Phase
overcurrent
inst
Model
MCGG
MCGG
MCGG
MCGG
MCGG
MCGG
MCGG
22
42
52
53
62
63
82
2 Phase
overcurrent
inst
Midos System R6001
Directional Relay R6003
Single Phase
or earthfault
inst
Measuring
boards
Case
size
1
2
3
2
3
1
4
4
6
8
8
6
6
8
Application
The relay can be used in applications
where time graded overcurrent and
earth fault protection is required.
The relay can be used to provide
selective protection for overhead and
underground distribution feeders.
Other applications include back-up
protection for transformers, generators
and HV feeder circuits and the
protection of neutral earthing resistors.
Switch position
(0)
(1)
An instantaneous element with low
transient overreach is incorporated
within each phase or earth fault
measuring board. This can be easily
disabled in applications where it is
not required.
Description
This range of MCGG relays is
designed so that versions are
available with separate measuring
boards for each phase or earth fault
input; alternatively, phase inputs may
be combined on to one board for
polyphase measurement (see table).
These boards, together with the other
circuits of the relay, are contained in
Very inverse
t=
Extremely inverse
t=
Long time earth fault
t=
Non-standard resistance values and
non-linear voltage limiting devices are
available.
t=
The total impedance of the relay and
the series stabilising resistor is usually
low enough to prevent the current
transformers developing voltages over
2kV during maximum internal faults,
but in some applications a non-linear
resistor is required to limit this voltage.
Trip test
Standard inverse
With all the current/time
characteristics available on one relay,
a standard relay can be ordered
before detailed co-ordination studies
are carried out a distinct advantage
for complex systems. Also, changes in
system configuration can be readily
accommodated.
For applications where the
instantaneous earth fault element is
required to have a sensitive setting
whilst remaining stable on heavy
through faults the use of a stabilising
resistor is recommended. The current
transformers for this application must
satisfy the criteria detailed under
Current transformer requirements in
Technical Data.
Operating
characteristic
0.14
1)
sec SI
13.5
(I 1)
sec VI
80
1)
sec EI
120
(I 1)
sec LT
(I0.02
(I2
Definite time 2 seconds
D2
Definite time 4 seconds
D4
Definite time 8 seconds
D8
Table1: Operating time characteristics with corresponding switch positions.
a single plug-in module which is
supplied in a size 4, 6 or 8 Midos
case. The case incorporates one or
two terminal blocks for external
connections. Removal of the module
automatically short circuits the current
transformer connections by means of
safety contacts within the case
terminal block. For added security,
when the module is removed, the ct
circuits are short circuited before the
connections to the output contacts and
the dc supply are broken. The relay
uses solid state techniques, each
measuring board utilising a microcomputer as a basic circuit element.
The current measurement, whether
performed on a single phase or
polyphase input, is performed via an
analogue-to-digital converter.
Application diagrams are provided in
Figures 2 to 8 (inclusive) showing
typical wiring configurations.
Each measuring board has a built-in
power off memory feature for the
time delayed and instantaneous led
indicators.
Power to each measuring board may
be tested whilst the relay is in service.
without affecting the current
measurement. A test mode is also
available to carry out a trip test on the
output relays. During this test, current
measurement is inhibited.
When required, directional control
can be exercised over the relay by
connecting an output contact from
direction relay type METI to the
terminals provided.
Separate output contacts, capable of
circuit breaker tripping, are provided
for time delayed phase faults,
instantaneous phase faults, time
delayed earth fault and instantaneous
earth fault operations.
Relay settings
Separate setting switches for each
measuring board are provided on the
relay frontplate. These are used to
select the required time/current
characteristic, current and time
multiplier settings.
Selection of time characteristics
The current/time characteristic
selection is carried out by means of
three switches (identified by
symbol on the nameplate).
Table 1 gives the basic operating
characteristic and the settings of the
switches.
Time multiplier setting
The time given by each of the
operating characteristics must be
multiplied by the time multiplier to
give the actual operating time of the
relay. This control is marked xt =
where is the sum of all the switch
positions.
The setting control of the
instantaneous element is marked
Iinst = x Is where is the sum of the
switch positions and Is is the time
delayed element setting.
When all switches are set to the left
(at zero), or when the lowest switch is
set to infinity regardless of the
positions of the other five switches, the
instantaneous feature is rendered
inoperable. The range of adjustment
of finite settings is from 1x to 31x in
unity steps.
This acts as a conventional time
multiplier on the current dependent
characteristics and gives the following
time ranges for the definite time
characteristics.
Time range
s
0.1 to 2.0 in 0.05s steps
0.2 to 4.0 in 0.1s steps
0.4 to 8.0 in 0.2s steps
Trip test
Current measurement is inhibited by
setting the curve selection switches to
111. This causes all three led to flash
once per second. If the reset push
button is then pressed for
approximately six seconds, both
output relays associated with that
measuring board will operate.
Current setting
Time delayed element
The current setting control is marked
Is = x In where Is is the current
setting in amps, is the sum of all the
switch positions and In is the relay
rated current in amps.
A
B
S2
Figure 2: Type MCGG 22 nameplate
P1
P2
If, whilst the relay is in service, the
reset button is pressed, all the leds
are iluminated, indicating that there
is power to the measuring boards.
The leds are reset on releasing the
push button. During this test, normal
current measurement is not inhibited.
Instantaneous element
The range of multiplication is from
0.05x to 1.0x in steps of 0.025.
Operating
characteristics
s
2
4
8
Power supply healthy test
Each measuring board provides a
setting range of 0.05 x In to 2.4 x In
in steps of 0.05 x In.
S1
B
Phase rotation
Directional
control
PhA
(See Note 4)
TMS
setting
24
Inst
setting
Curve
selection
23
(See Note 2)
27
IA
Is
Indicator
reset
Time delayed trip
Inst. trip
C
PhA
RL11
28
Input
circuit
Ph
Current
setting
Ph
I>Is
RL1
2
Case earth
1
10
13
14
15
16
Vx
+VE
VE
13
14
26
Output
circuits
Ph
Power
supply
circuits
RL2
2
Case earth connection
23
24
26
27
(See Note 3)
28
Module terminal block
viewed from rear
(b)
(c)
CT shorting links make
before (b) and (c) disconnect.
Short terminals break before (c).
Long terminals
2. When directional control is required the contacts
of the directional relays should be connected as shown.
Contacts must close to inhibit overcurrent relay.
3. Earthing connections (CTs) are typical only.
4. CT connections are typical only.
Figure 3: Application diagram (10 MCGG 22 02): static modular overcurent relay type MCGG 22.
Single phase with instantaneous element.
4
RL12
Phase fault
time delayed
trip output
contacts
RL21
8
10
9
RL22
16
15
MCGG 22
Notes:
1. (a)
7
6
Phase fault
instantaneous
trip output
contacts
P2
P1
S2
S1
Directional
control
PhA
C
C
B
Phase rotation (See Note 4)
TMS
setting
Inst
setting
Indicator
reset
Curve
selection
49
50
(See Note 2)
21
IA
Is
RL1
2
Time delayed trip
Inst. trip
C
PhA
Input
circuit
Ph
23
Current
setting
Ph
I>Is
45
25
29
30
33
34
35
36
10
37
38
11
12
13
14
41
42
15
16
17
18
45
46
19
20
47
48
21
22
49
50
23
24
25
26
27
28
34
RL12
IC
Inst
setting
Curve
selection
Is
RL21
Input
circuit
Ph
27
Vx
VE
28
13
C
PhC
38
RL22
Phase fault
instantaneous
trip output
contacts
I>Is
MCGG 42
CT shorting links make
before (b) and (c) disconnect.
Short terminals break before (c).
Long terminals
(b)
(c)
41
42
Current
setting
Ph
Case earth connection
Module terminal block
viewed from rear
(with integral case earth strap)
36
Power
supply
circuits
14
(See Note 3)
Notes:
1. (a)
Phase fault
time delayed
trip output
contacts
37
Time
delayed trip
Inst. trip
26
+VE
29
30
TMS
setting
46
Case earth
35
33
RL2
2
24
Directional
control
PhC
RL11
Output
circuits
Ph
22
2. When directional control is required the contacts
of the directional relays should be connected as shown.
Contacts must close to inhibit overcurrent relay.
3. Earthing connections are typical only.
4. CT connections are typical only.
Figure 4: Application diagram (10 MCGG 42 03): static modular overcurent relay type MCGG 42.
Two phase with instantaneous element.
P2
A
A
P1
S2
S1
Directional
control
PhA
TMS
setting
49
Inst
setting
Curve
selection
Indicator
reset
50
(See Note 2)
(See Note 4)
Phase rotation
21
IA
Is
22
Input
circuit
Ph
23
Directional
control
PhC
C
PhA
Current
setting
Ph
RL1
2
Time delayed trip
Inst. trip
RL11
Output
circuits
Ph
I>Is
33
RL2
2
34
RL12
TMS
setting
45
Inst
setting
Curve
selection
RL21
IC
Is
26
29
Directional
control
E/F
30
33
34
35
36
10
37
38
11
12
Input
circuit
Ph
13
14
41
42
16
43
44
17
18
45
46
19
20
47
48
21
22
49
50
23
24
25
26
27
28
Module terminal block
viewed from rear
(with integral case earth strap)
Current
setting
Ph
38
RL22
27
RL31
Inst
setting
Curve
selection
(See Note 3)
Notes:
1. (a)
(b)
(c)
VE
13
14
17
Power
supply
circuits
Input
circuit
RL32
Output
circuits
I>Is
RL41
RL4
2
Earth fault
time delayed
trip output
contacts
8
10
9
16
Earth fault
instantaneous
trip output
contacts
15
MCGG 52
2. When directional control is required the contacts
of the directional relays should be connected as shown.
Contacts must close to inhibit overcurrent relay.
2
1
Inst. trip
RL42
Case earth connection
CT shorting links make
before (b) and (c) disconnect.
Short terminals break before (c).
Long terminals
Current
setting
RL3
2
Time delayed trip
Is
28
+VE
Phase fault
instantaneous
trip output
contacts
41
I>Is
44
Vx
42
6
TMS
setting
43
E/F
15
C
PhC
36
37
Time
delayed trip
Inst. trip
25
29
Phase fault
time delayed
trip output
contacts
30
24
46
Case earth
35
3. Earthing connections are typical only.
4. CT connections are typical only.
Figure 5: Application diagram (10 MCGG 52 03): static modular overcurent relay type MCGG 52.
Two phase plus earth fault with instantaneous elements.
P2
A
A
P1
S2
Directional
control
PhA
S1
TMS
setting
49
Inst
setting
Indicator
reset
Curve
selection
50
(See Note 2)
(See Note 4)
Phase rotation
21
IA
Is
RL1
2
Time delayed trip
C
Ph
Inst. trip
22
Current
setting
Ph
23
Directional
control
PhC
RL11
Output
circuits
Ph
I>Is
33
RL2
2
34
RL12
RL21
45
26
33
34
35
36
10
37
38
11
12
13
14
41
42
15
16
43
44
18
45
46
19
20
47
48
22
23
24
25
26
27
28
49
RL31
Inst
setting
Curve
selection
27
RL3
2
Time delayed trip
Inst. trip
Is
+VE
VE
50
13
14
17
CT shorting links make
before (b) and (c) disconnect.
Short terminals break before (c).
Long terminals
(b)
(c)
Input
circuit
Current
setting
I>Is
RL41
RL4
2
Earth fault
time delayed
trip output
contacts
9
16
Earth fault
instantaneous
trip output
contacts
15
MCGG 53
2. When directional control is required the contacts
of the directional relays should be connected as shown.
Contacts must close to inhibit overcurrent relay.
10
RL42
Case earth connection
(See Note 3)
Module terminal block
viewed from rear
(with integral case earth strap
Power
supply
circuits
RL32
Output
circuits
28
Notes:
1. (a)
44
Vx
Phase fault
instantaneous
trip output
contacts
6
TMS
setting
43
E/F
17
21
Directional
control
E/F
41
42
Input
circuit
Ph
Case earth
30
36
38
RL22
IC
29
Phase fault
time delayed
trip output
contacts
37
25
29
30
24
46
35
3. Earthing connections are typical only.
4. CT connections are typical only.
Figure 6: Application diagram (10 MCGG 53 02): static modular overcurent relay type MCGG 53.
Two phase (with polyphase measurement), plus earth fault with instantaneous elements.
P2
A
A
P1
S2
S1
Directional
control
PhA
49
TMS
setting
Inst
setting
Is
C
PhA
Curve
selection
Indicator
reset
50
(See Note 2)
(See Note 4)
Phase rotation
21
IA
22
Directional
control
PhB
Input
circuit
Ph
Current
setting
Ph
TMS
setting
47
Time delayed trip
RL11
Inst. trip
33
RL1
2
I>Is
Inst
setting
Output
circuits
Ph
Curve
selection
48
23
IB
Is
24
Input
circuit
Ph
27
Case earth
1
13
14
29
30
33
34
35
36
37
38
41
Directional
control
PhC
46
47
48
49
50
TMS
setting
25
IC
Is
26
Vx
21
22
23
24
25
26
(See Note 3)
27
28
Notes:
1. (a)
Module terminal block
viewed from rear
(with integral case earth strap)
RL2
2
I>Is
Inst
setting
(b)
(c)
+VE
VE
13
14
1
Power
supply
circuits
Input
circuit
Ph
Case earth connection
Current
setting
Ph
Time delayed trip
Inst. trip
I>Is
MCGG 62
CT shorting links make
2. When directional control is required the contacts
before (b) and (c) disconnect.
of the directional relays should be connected as shown.
Short terminals break before (c).
Contacts must close to inhibit overcurrent relay.
Long terminals
3. Earthing connections are typical only.
4. CT connections are typical only.
Figure 7: Application diagram (10 MCGG 62 03): static modular overcurent relay type MCGG 62.
Three phase with instantaneous element.
41
42
Curve
selection
C
PhC
Phase fault
time delayed
trip output
contacts
36
38
RL22
28
45
29
30
RL21
46
42
45
Current
setting
Ph
34
RL12
37
Time
delayed trip
Inst. trip
C
PhB
35
Phase fault
instantaneous
trip output
contacts
P2
A
A
P1
S2
Directional
control
PhA
S1
49
TMS
setting
Inst
setting
Is
C
Ph
Indicator
reset
Curve
selection
50
(See Note 2)
(See Note 4)
Phase rotation
21
IA
RL1
2
Time delayed trip
Inst. trip
22
Directional
control
PhB
Current
setting
Ph
47
RL11
Output
circuits
Ph
I>Is
35
33
RL2
2
34
RL12
29
Phase fault
time delayed
trip output
contacts
30
48
RL21
23
38
24
Directional
control
PhC
Case earth
RL22
41
Phase fault
instantaneous
trip output
contacts
42
45
46
29
25
30
33
34
35
36
10
37
38
11
12
41
42
IC
13
14
15
16
17
18
45
46
19
20
47
48
21
22
49
50
23
24
25
26
27
36
37
IB
26
Input
circuit
27
28
Vx
+VE
VE
13
14
1
Case earth connection
(See Note 3)
Notes:
1. (a)
28
Module terminal block
viewed from rear
(with integral case earth strap)
(b)
(c)
Power
supply
circuits
CT shorting links make
before (b) and (c) disconnect.
Short terminals break before (c).
Long terminals
MCGG 63
2. When directional control is required the contacts
of the directional relays should be connected as shown.
Contacts must close to inhibit overcurrent relay.
3. Earthing connections are typical only.
4. CT connections are typical only.
Figure 8: Application diagram (10 MCGG 63 02): static modular overcurent relay type MCGG 63.
Three phase (with polyphase measurement) with instantaneous element.
A
A
B
P2
S2
P1
S1
C
C
Directional
control
PhA
TMS
setting
50
Phase rotation
Indicator
reset
49
(See Note 2) 21
(See Note 4)
IA
Is
22
Directional
control
PhB
Case earth
48
30
33
34
35
36
10
37
38
11
12
13
14
41
42
15
16
43
44
17
18
45
46
46
19
20
47
48
25
21
22
49
50
23
24
25
26
27
28
(b)
(c)
Is
C
PhB
TMS
setting
Is
43
44
2. When directional control is required the contacts
of the directional relays should be connected as shown.
Contacts must close to inhibit overcurrent relay.
Vx
(See Note 3)
VE
34
RL12
Curve
selection
29
Phase fault
time delayed
trip output
contacts
30
Time delayed trip
36
37
Inst. trip
38
13
14
17
Inst
setting
RL22
Power
supply
circuits
RL31
41
Phase fault
instantaneous
trip output
contacts
Is
C
E/F
Inst. trip
RL32
Earth fault
time delayed
trip output
contacts
Curve
selection
Time delayed trip
Inst. trip
I>Is
7
6
Time delayed trip
I>Is
Inst
setting
Input circuit Current setting
E/F
E/F
Curve
selection
C
PhC
TMS
setting
27
+VE
35
33
RL2
2
I>Is
Input circuit Current setting
Ph
Ph
28
CT shorting links make
before (b) and (c) disconnect.
Short terminals break before (c).
Long terminals.
RL11
Output
circuits
Ph
42
45
26
Notes:
1. (a)
Inst
setting
Input circuit Current setting
Ph
Ph
IC
Module terminal block
viewed from rear
(with integral case earth strap)
Inst. trip
RL21
24
Directional
control E/F
RL1
2
Time delayed trip
I>Is
TMS
setting
23
IB
Directional
control
phase PhC
Curve
selection
C
PhA
Input circuit Current setting
Ph
Ph
47
29
Inst
setting
MCGG 82
RL3
2
RL41
8
10
9
Output
circuits
E/F
RL42
RL4
2
16
Earth fault
instantaneous
trip output
contacts
15
Case earth connection
3. Earthing connections are typical only.
4. CT connections are typical only.
Figure 9: Application diagram (10 MCGG 82 03): static modular overcurent relay type MCGG 82.
Three phase plus earth fault with instantaneous elements (4 wire system).
Technical Data
Ratings
AC Current (In) 1A or 5A
Frequency
50/60Hz
DC Supply (Vx) 24/54V, 48/125V
or 110/250V
Burdens
AC Burden
Less than 0.25 VA for 1A relays and
less than 0.5VA for 5A relays, at unity
power factor and at rated current on
any setting.
The impedance of the relays over the
whole of the setting range (5% to
240% rated current) is less than
0.25 for 1A relays and less than
0.02 for 5A relays and is
independent of current.
DC Burden
Relay
rating
Relay type
MCGG MCGG MCGG MCGG
22, 63 42, 53 52, 62
24/54
82
1.5W
2.5W
3.0W 4.0W
48/125 2.0W
3.0W
3.5W 4.5W
110/250 2.5W
3.5W
4.0W 5.0W
The figures above are maxima under
quiescent conditions. With output
elements operated they are increased
by up to 2.5W per element.
Current transformer requirements
Relay and ct
secondary rating
(A)
Nominal
output
(VA)
Accuracy
class
Accuracy
Limiting lead
limit current
resistance
(X rated current) one way (ohms)
2.5
10P
20
7.5
10P
20
0.15
Note: For 5A applications with longer leads, the ct rating can be increased in
steps of 2.5VA where each step of 2.5VA is equivalent to additional
0.06 lead resistance.
Instantaneous earth fault element
For installations where the earth fault element is required to have a sensitive
setting whilst remaining stable on heavy through faults, the use of a stabilising
resistor is recommended, the value of which will vary according to the specific
application. If assistance is required in selecting the appropriate value,
please consult the Applications Department of GEC ALSTHOM T&D Protection
& Control.
Setting ranges
Time delayed settings (Is), phase/
earth fault measuring range: 5% to
240% of In in 5% steps.
Instantaneous setting (Iinst)
1 x 31 x Is in 1 x 1s steps
100
10
Operating time t (seconds)
Definite 8 seconds
Definite 4 seconds
Longtime standby
earth fault
t = 120
I1
Standard inverse
0.14
t = 0.02
I 1
Definite 2 seconds
1.0
Very inverse
t = 13.5
I1
Extremely inverse
t = 280
I 1
0.1
1
10
100
I( x Is)
Current (multiple of setting)
Figure 10: Time delayed overcurrent element operation time characteristics.
Operating time
Time delayed element
Operating characteristics
selectable to give:
Shown in Figure 10
Standard inverse IDMT
Very inverse IDMT
Extremely inverse IDMT
Long time earth fault IDMT
Definite time 2s, 4s, 8s
Time multiplier setting
0.05 to 1.0 in 0.025 steps
(applicable to all time characteristics)
Instantaneous elements
Shown in Figure 11
For settings of 5 x Is and above:
<35ms at 2x instantaneous setting
Accuracy reference conditions
Current setting (Is)
Reference range 0.05In to 2.4In for
MCGG 22, 42, 52, 62, 82 and E/F
element of MCGG53.
0.2In to 2.4In for phase fault
elements of MCGG 53 and 63.
Input current
Time characteristic Reference range
Standard inverse
Very inverse
2 x Is to 31 x Is
Long time inverse
Ambient temperature
Extremely inverse
2 x Is to 20 x Is
Definite time
1.3 x Is to 31 x Is
20C
Frequency
50Hz to 60Hz
Time multiplier setting
1x
DC auxiliary voltage
Reference ranges
24V to 54V
48V to 125V
110V to 250V
Accuracy influencing quantities
On settings 0.05 to 1.0 2% or
30ms whichever is the greater
Time multiplier
Ambient temperature
Operative range
25C to +55C
Variations over this range
Setting current
5%
Time characteristic
Time variation
Standard inverse
Very inverse
Long time inverse
5%
Extremely inverse
7.5%
Definite time
3%
Frequency
Setting current
1% over the range 47-62Hz
Operating time
2% or 30ms whichever is the
greater, over the range 4752Hz or
5762Hz.
DC auxiliary voltage
Vx dc(V)
Operative range (V)
24/54
19 60
48/125
37.5 150
110/250
87.5 300
240
220
200
180
Operating time (ms)
160
140
120
100
Iinst = 1Is
80
2Is
60
40
5-31Is
4Is
3Is
20
0
1
10
Current (multiple of instantaneous setting)
Figure 11: MCGG instantaneous operating times (various settings).
10
100
Variations over these ranges
Setting current
1%
Operating time
2% or 30ms whichever is greater
Accuracy general
Current setting
Time delayed element
1.0 x Is to 1.1 x Is
Instantaneous elements
Iinst = 1 x Is 1.0 x Iinst to 1.1 x Iinst
All other settings
Iinst 5%
Operating time
Time characteristic
Accuracy
Standard inverse
Very inverse
Long time inverse
5%
Extremely inverse
7.5% 30ms whichever is greater
Definite time
3%
Repeatability
(within basic accuracy claim)
Pick-up current
better than 1%
Operating time
better than 2% or 30ms whichever
is greater.
Overshoot time
Less than 30ms (when the input
current is reduced from any value
within the operative range to zero).
Resetting current
Time delayed and instantaneous
elements: not less than 95% of time
delayed current setting.
Resetting and disengaging times
Less than 70ms (when the input
current is reduced from any value
within the operative range to zero).
Transient overreach
System time constant up to 30ms:
5%
(instantaneous elements)
System time constant up to 100ms:
12%
Thermal withstand
Continuous withstand
2 x Is or 2.6 x In whichever is lower,
with a minimum of 1 x In
Short time withstand
For 1s: 100 x In with 400A maximum
For 3s: 57 x In with 230A maximum
Operation indicators
Each measuring board is fitted with
two red led indicators, one showing
time delayed operation and the other
showing instantaneus operation.
The reset button provided on the
frontplate resets all the operation
indicators.
The green timer start indicator
illuminates when the input current
exceeds the setting current Is to
facilitate testing of the module.
This indicator is self resetting.
Led covers are available to eliminate
any undesired led indication.
11
Contacts
MCGG 52, 53, 82
Phase fault time delayed element
Changeover Make
1
1
Phase fault instantaneous element
Earth fault time delayed element
Earth fault instantaneous element
MCGG 22, 42, 62, 63 Time delayed element
Instantaneous element
Contact ratings
Make and carry for 0.2s
7500VA subject to maxima of 30A
and 300V ac or dc
Carry continuously
5A ac or dc
Break
ac 1250VA
dc 50W resistive
25W, L/R = 0.04s
subject to
maxima of
5A and 300V
Durability
Loaded contact
10,000 operations minimum
Unloaded contact
100,000 operations minimum
Directional control
Directional control can be exercised
over each pole individually by
connecting the output contact of a
relay type METI across appropriate
case terminals.
Relay type
Direction control terminals
MCGG 22
23,24
MCGG 42
45, 46, 49, 50
MCGG 52, 53
43 to 46, 49, 50
MCGG 62, 63
45 to 50
MCGG 82
43 to 50
Note: The directional control circuits are isolated from all other circuits but are
electrically connected to the relay case. These circuits must not, therefore,
be insulation or impulse tested to the case.
High voltage withstand
Dielectric withstand
IEC 255-5: 1977
2.0kV rms for 1 minute between all
case terminals connected together and
the case earth terminal, with the
exception of the directional control
terminals.
2.0kV rms for 1 minute between
terminals of independent circuits, with
terminals on each independent circuit
connected together.
1kV rms for 1 minute across open
contacts of output relays.
High voltage impulse
IEC 255-5: 1977
12
Three positive and three negative
impulses of 5kV peak, 1.2/50s, 0.5J
between all terminals and case earth
and between adjacent terminals, with
the exception of the directional control
terminals, (see note).
Electrical environment
High frequency disturbance
IEC 255-22-1: 1988 Class III
2.5kV peak between independent
circuits and case.
1.0kV peak across terminals of the
same circuit.
Note: The directional control terminals
comply with class II and will withstand
1kV peak between all independent
circuits, and 500V peak across the
directional control terminals.
DC supply interruption
IEC 255-11: 1979
AC ripple on dc supply
IEC 255-11: 1979
Fast transient disturbance
IEC 255-22-4: 1992 Class IV
IEC 801-4: 1988 Level 4
Electrostatic discharge
IEC 255-22-2: 1989 Class II
IEC 801-2: 1991 Level 2
Surge immunity
IEC 1000-4-5: 1995 Level 4
EMC compliance
89/336/EEC
EN50081-2: 1994
EN50082-2: 1995
Product safety
73/23/EEC
EN 61010-1: 1993/A2: 1995
EN 60950: 1992/A3: 1995
The unit will withstand a 10ms
interruption in the auxiliary supply,
under normal operating conditions,
without de-energising.
The unit will witstand 12% ac ripple
on the dc supply.
4.0kV, 2.5kHz applied directly to
auxiliary supply.
4.0kV, 5.0kHz applied directly to
all inputs.
4.0kV discharge in air with cover
in place
4.0kV point contact discharge with
cover removed.
4.0kV peak, 1.2/50s between all
groups and case earth.
2.0kV peak, 1.2/50s between
terminals of each group.
Compliance with the European
Commission Directive on EMC is
claimed via the Technical Construction
File route. Generic Standards
were used to establish conformity.
Compliance with the European
Commission Low Voltage Directive.
Compliance is demonstrated by
reference to generic safety standards.
Atmospheric environment
Temperature
IEC 255-6: 1988
IEC 68-2-1: 1990
IEC 68-2-2: 1974
Storage and transit 25C to +70C
Operating 25C to +55C
Cold
Dry heat
Humidity
IEC 68-2-3: 1969
56 days at 93% RH and 40C
Enclosure protection
IEC 529: 1989
IP50 (dust protected)
13
Mechanical environment
Vibration
IEC 255-21-1: 1988
Response Class 1
Endurance Class 1
Cases
MCGG 22
Size 4
MCGG 42
Size 6
MCGG 62
Size 6
MCGG 63
Size 6
MCGG 52
Size 8
MCGG 53
Size 8
MCGG 82
Size 8
The dimensions of the cases are shown in Figures 12, 13 and 14.
52
4 holes 4.4
97
23.5
All dimensions in mm.
168
159
Push button
projection 10 max.
99
Panel cut-out:
Flush mounting fixing details.
32
Flush mounting.
Figure 12: Case outline size 4.
Information Required with Order
Relay type (see models available).
Rated current and frequency.
DC auxiliary voltage range.
Requirement for led cover part
GJ0280 001.
(These self adhesive led covers can be
supplied to cover the instantaneous
led when used in auto-reclose
applications as the leds remain on
during normal use).
14
25 min.
157 max.
177
103
212
11
103.6
4 holes 4.4
149
23.5
All dimensions in mm.
159
168
Push button
projection 10 max.
151
Panel cut-out:
Flush mounting fixing details.
32
212
25 min.
157 max.
177
155
Flush mounting.
11
Figure 13: Case outline size 6.
155.4
4 holes 4.4
200
24
159
168
Push button
projection 10 max.
203
Panel cut-out:
Flush mounting fixing details.
32
25 min.
157 max.
177
206
212
Flush mounting.
11
All dimensions in mm.
Figure 14: Case outline size 8.
15