RuggedBackbone RX1500/1501
Industrially Hardened Layer 3 Switch and Router
The RuggedBackbone RX1500 series is a cost efficient
industrially hardened layer 3 switch and router.
The RX1500s modular and field replaceable platform
allows customers to select amongst WAN, serial and
Ethernet options making it ideally suited for electric power
utilities, the industrial plant floor, and traffic control systems.
The RX1500 is hardened to the RuggedRated
specification which provides a high level of immunity to
electromagnetic interference (EMI) and heavy electrical
surges typical of the harsh environments found in many
industrial applications. An operating temperature range
of -40 to +85C (-40 to +185F) allows the RX1500 to be
placed in almost any location.
Key Features and Benefits
Security Appliance Functions
Multi-level passwords
SSH/SSL encryption
Enable/disable ports, MAC based port security
Port based network access control (802.1x)
VLAN (802.1Q) to segregate and secure network traffic
RADIUS centralized password management
SNMPv3 encrypted authentication and access security
RuggedRated for Reliability in Harsh Environments
Immunity to EMI and high voltage electrical transients
zz
Meets IEEE 1613 (electric utility substations)
zz
Exceeds IEC 61850-3 (electric utility substations)
zz
Exceeds IEC 61800-3 (variable speed drive systems)
zz
Exceeds IEC 61000-6-2 (generic industrial environment)
zz
Exceeds NEMA TS-2 (traffic control equipment)
-40C to +85C operating temperature (no fans)
Failsafe Output Relay: For critical failure or error alarming
Physical Ports
Field replaceable line modules
Up to 24-ports 100FX
Up to 36-ports 10/100TX
Up to 8-ports Gigabit Ethernet
Serial Ports*
Fully compliant EIA/TIA RS485, RS422, RS232 serial ports
(software selectable) RJ45 connectors
Raw socket mode support allows conversion of any serial
protocol
Protocols
WAN
zz
Frame Relay RFC 1490 or RFC 1294
zz
PPP RFC 1661, 1332, 1321, 1334, PAP, CHAP
Authentication
zz
Multilink PPP RFC 1990
zz
GOOSE messaging support
IP
zz
Routing: OSPF, BGP, RIPv1 and 2
zz
VRRP
zz
Traffic control, NTP Server, IP Multicast Routing
zz
DHCP Agent (Option 82 Capable)
Frame Relay Support
ISO and ITU compliant, network certified.
ANSI T1.617 Annex D, Q.933 or LMI Local Signaling
Management Tools
Web-based, SSH, CLI management interfaces
SNMP v1/v2/v3
Remote Syslog
Rich set of diagnostics with logging and alarms
Loopback diagnostic tests
Raw and interpreted real time line traces
Universal Power Supply Options
Modular
Hot-Swappable* (RX1500 only)
Fully integrated power supplies (no external adaptors)
Input voltage range of 1072VDC, 88300VDC,
and 85-264VAC for worldwide operability
CSA/UL 60950 safety approved to +85C
Warranty
5 Year Warranty
WAN Port Options:
T1/E1 (channelized/unchannelized)
E1 75 Ohms via BNC
Cellular/DDS/VDSL*
RUGGEDCOM
ISO 9001
* Coming Soon
www.RuggedCom.com
REGISTERED
RuggedBackbone RX1500/1501
RuggedBackbone RX1500/1501
Industrially Hardened Layer 3 Switch and Router
RuggedBackbone RX1500
WAN Ports
XXUp to 4 T1/E1 ports
Serial Ports*
XXUp to 18 RS232/422/485
Multiple Ethernet Ports
XXUp to 16-ports 100FX
XXUp to 24-ports 10/100TX
XXUp to 8-ports Gigabit Ethernet
XXSC, ST, LC and MTRJ
XXPluggable Optics (SFP)
Modular
XXAll modules are field replaceable
Hot Swappable Power Supply
XX24VDC (1036VDC)
48VDC (3672VDC)
HI (88300VDC/85264 VAC)
XXRedundant load sharing
power supplies
Enclosure
XXIP40
XXAluminum
Operating Temperature
XX-40C to +85C
XXNo Fans
Mounting Options
XXPanel Rail
XX19 Rack Mount
EMI Immunity
XXMeets IEEE 1613 (electric utility substations)
XXExceeds IEC 61850-3 (electric utility substations)
XXExceeds IEC 61800-3 (variable speed drive systems)
XXExceeds IEC 61000-6-2 (generic industrial environment)
XXExceeds NEMA TS-2 (traffic control equipment)
* Coming Soon
www.RuggedCom.com
RuggedBackbone RX1500/1501
RuggedBackbone RX1500/1501
Industrially Hardened Layer 3 Switch and Router
RuggedBackbone RX1501
Power Supply
XX24VDC (1036VDC)
48VDC (3672VDC)
HI (88 300VDC/85 264 VAC)
power supply options
WAN Ports
XXUp to 4 T1/E1 ports
Enclosure
XXIP40
XXAluminum
Multiple Ethernet Ports
XXUp to 4 10/100/1000 Base Tx ports or 36 10/100 Tx ports
XXUp to 24 100FX or 4 optical Gigabit ports
XXSC, ST, LC and MTRJ
XXPluggable Optics (SFP)
Serial Ports*
XXUp to 30 RS232/422/485
Modular
XXAll modules are field replaceable
Operating Temperature
XX-40C to +85C
XXNo Fans
EMI Immunity
XXMeets IEEE 1613 (electric utility substations)
XXExceeds IEC 61850-3 (electric utility substations)
XXExceeds IEC 61800-3 (variable speed drive systems)
XXExceeds IEC 61000-6-2 (generic industrial environment)
XXExceeds NEMA TS-2 (traffic control equipment)
Mounting Options
XXPanel Rail
XX19 Rack Mount
* Coming Soon
www.RuggedCom.com
RuggedBackbone RX1500/1501
RuggedBackbone RX1500/1501
Industrially Hardened Layer 3 Switch and Router
ROXII Features
ROXII Software Features
Quality of Service (IEEE 802.1p)
Enhanced Security/Reliability through Data and Control
path separation
Simple plug and play operation automatic learning,
negotiation, and crossover detection
Telecom Standard Command Line Interface (CLI)
Single File Configuration ensures easy installation &
Configuration control
Automatic Rollback in the event of configuration
errors (Configurable)
NETCONF configuration interface supports powerful
remote configuration and status features.
VLAN (802.1Q) with double tagging
Port Rate and Broadcast Storm Limiting
Port configuration, status, statistics, mirroring
SNTP time synchronization (client and server)
MSTP 802.1Q-2005 (formerly 802.1s)
RSTP (802.1w) and Enhanced Rapid Spanning Tree
(eRSTP) network fault recovery (<5ms)
Quality of Service (802.1p) for real-time traffic
Traffic Prioritization
SNMP v1, v2c and v3 Support including RMON
Stateful Firewall
RIP v1/2
OSPF
BGP
Some networking applications such as real-time control
or VoIP (voice over IP) require predictable arrival times for
Ethernet frames. Switches can introduce latency in times
of heavy network traffic due to the internal queues that
buffer frames and then transmit on a first come first serve
basis. ROXII supports Class of Service in accordance
with IEEE 802.1p that allows time critical traffic to jump
ahead to the front of the queue thus minimizing latency
and reducing jitter to allow such demanding applications to
operate correctly. ROXII allows priority classification by
port, tags, MAC address, and IP type of service (ToS). A
configurable weighted fair queuing algorithm controls how
frames are emptied from the queues.
Cyber Security
Cyber security is an urgent issue in many industries where
advanced automation and communications networks play
a crucial role in mission critical applications and where high
reliability is of paramount importance. Key ROXII features
that address security issues at the local area network level
include:
Passwords - Multi-level user passwords secures switch
against unauthorized configuration
SSH / SSL - Extends capability of password protection
to add encryption of passwords and data as they cross
the network
Enable / Disable Ports - Capability to disable ports so that
traffic can not pass
802.1Q VLAN - Provides the ability to logically segregate
traffic between predefined ports on switches
SNMPv3 - encrypted authentication and access security
HTTPS - for secure access to the web interface
Enhanced Rapid Spanning Tree Protocol (eRSTP)
RuggedCom eRSTP allows the creation of fault-tolerant
ring and mesh Ethernet networks that incorporate redundant
links that are pruned to prevent loops. eRSTP yields
worst-case fault recovery1 of 5ms times the bridge diameter
and allows rings of up to 160 switches. For example, a
ring of ten switches will have fault recovery times under
50ms. eRSTP implements both STP and RSTP to ensure
interoperability with commercial switches unlike other
proprietary ring solutions.
www.RuggedCom.com
VLAN (IEEE 802.1Q)
Virtual local area networks (VLAN) allow the segregation
of a physical network into separate logical networks with
independent broadcast domains. A measure of security
is provided since hosts can only access other hosts on
the same VLAN and traffic storms are isolated. ROXII
supports 802.1Q tagged Ethernet frames and VLAN
trunks. Port based classification allows legacy devices to
be assigned to the correct VLAN. GVRP support is also
provided to simplify the configuration of the switches on
the VLAN.
SNMP (Simple Network Management Protocol)
SNMP provides a standardized method, for network
management stations, to interrogate devices
from different vendors. SNMP versions supported by
ROXII are v1,v2c, and v3. SNMPv3 in particular
provides security features (such as authentication,
privacy, and access control) not present in earlier SNMP
versions. ROXII also supports numerous standard
MIBs (Management Information Base) allowing for easy
integration with any network management system (NMS).
A feature of SNMP supported by ROXII is the ability
to generate traps upon system events. RuggedNMS,
the RuggedCom management solution, can record traps
from multiple devices providing a powerful network
troubleshooting tool. It also provides a graphical
visualization of the network and is fully integrated with
all RuggedCom products.
NETCONF Configuration Interface
The NETCONF configuration interface will allow
administrators to set device parameters and receive device
updates through the use of XML based commands. This
standard, supported by multiple vendors, makes it possible
to greatly simplify the task of network management.
1e
RSTP fault recovery times may be approximated as follows:
For 100 Mbps, fault recovery performance is <5ms/hop
For 1,000 Mbps, fault recovery performance is <5ms/hop + 20ms
RuggedBackbone RX1500/1501
RuggedBackbone RX1500/1501
Industrially Hardened Layer 3 Switch and Router
ROXII Features
NTP (Network Time Protocol)
HTML Web Browser User Interface
NTP automatically synchronizes the internal clock of all
ROXII devices on the network. This allows for correlation
of time stamped events for troubleshooting.
ROXII provides a simple, intuitive user interface for
configuration and monitoring via a standard graphical
web browser or via standard telcom UI. All system
parameters include detailed on-line help to make setup
a breeze. ROXII presents a common look and feel and
standardized configuration process allowing easy migration
to other RuggedCom managed products.
Port Rate Limiting
ROXII supports configurable rate limiting per port to
limit unicast and multicast traffic. This can be essential to
managing precious network bandwidth for service
providers. It also provides edge security for denial of
service (DoS) attacks.
Broadcast Storm Filtering
Broadcast storms wreak havoc on a network and can
cause attached devices to malfunction. This could be
disastrous on a network with mission critical equipment.
ROXII limits this by filtering broadcast frames with a
user-defined threshold.
Port Mirroring
ROXII can be configured to duplicate all traffic on one port
to a designated mirror port. When combined with a network
analyzer, this can be a powerful troubleshooting tool.
Port Configuration and Status
ROXII allows individual ports to be hard configured for
speed, duplex, auto-negotiation, flow control and more. This
allows proper connection with devices that do not negotiate
or have unusual settings. Detailed status of ports with alarm
and SNMP trap on link problems aid greatly in system
troubleshooting.
Port Statistics and RMON (Remote Monitoring)
ROXII provides continuously updating statistics per port
that provide both ingress and egress packet and byte
counters as well as detailed error figures. Also provided is
full support for the RMON statistics, history, alarms, and
event groups. RMON allows for very sophisticated data
collection, analysis and detection of traffic patterns.
Event Logging and Alarms
ROXII records all significant events to a non-volatile
system log allowing forensic troubleshooting. Events
include link failure and recovery, unauthorized access,
broadcast storm detection, and self-test diagnostics among
others. Alarms provide a snapshot of recent events that
have yet to be acknowledged by the network administrator.
An external hardware relay is de-energized during the
presence of critical alarms allowing an external controller
to react if desired.
www.RuggedCom.com
Command Line Interface (CLI)
A command line interface used in conjunction with
remote shell to automate data retrieval, configuration
updates, and firmware upgrades. A powerful Telecom
Standard style Command Line Interface (CLI), which will
be familiar to users of Cisco XR, allows expert users the
ability to selectively retrieve or manipulate any parameters
the device has to offer.
Link Backup
Link backup provides an easily configured means of raising
a backup link upon the failure of a designated main link.
The main and backup links can be Ethernet, Cellular, T1/
E1, DDS, ADSL or T3. The feature can back up to multiple
remote locations, managing multiple main: backup link
relationships. The feature can also back up a permanent
high speed WAN link to a permanent low speed WAN link
and can be used to migrate the default route from the main
to the backup link.
OSPF (Open Shortest Path First)
OSPF is a routing protocol that determines the best path for
routing IP traffic over a TCP/IP network based on link states
between nodes and several quality parameters. OSPF is an
interior gateway protocol (IGP), which is designed to work
within an autonomous system. It is also a link state protocol,
meaning that the best route is determined by the type and
speed of the inter-router links, not by how many router
hops they are away from each other (as in Distance-Vector
routing protocols, i.e. Rip and RIP II).
BGP (Border Gateway Protocol)
BGPv4 is a path vector routing protocol where routing
decisions are made based on the policies or rules laid out
by the network administrator. It is typically used where
networks are multihomed between multiple Internet Service
Providers, or in very large internal networks where internal
gateway protocols do not scale sufficiently.
RuggedBackbone RX1500/1501
RuggedBackbone RX1500/1501
Industrially Hardened Layer 3 Switch and Router
Software Options
Layer 2
Standard Edition
Layer 3
Standard Edition
Layer 3*
Security Options
VLANs ( 802.1Q)
QoS (802.1p )
MSTP (802.1Q-2005) formerly 802.1s
RSTP
eRSTP
SNTP
Port Rate Limiting
Broadcast Storm Filtering
Port Mirroring
SNMP v1/v2/v3
RMON
CLI
HTML User Interface
Firewall
OSPF
BGP
RIP v1/v2
Traffic Prioritization*
Feature
Cyber Security Support*
Intrusion Detection*
VPN*
IPSec*
*Coming Soon
www.RuggedCom.com
RuggedBackbone RX1500/1501
RuggedBackbone RX1500/1501
Industrially Hardened Layer 3 Switch and Router
EMI and Environmental Type Tests
IEC 61850-3 EMI TYPE TESTS
TEST
Description
IEC 61000-4-2
ESD
IEC 61000-4-3
Radiated RFI
Enclosure Contact
Enclosure Air
Enclosure ports
Signal ports
IEC 61000-4-4
Burst (Fast Transient)
IEC 61000-4-6
Induced (Conducted) RFI
IEC 61000-4-8
8 Magnetic Field
A.C. Power ports
+/- 4kV
+/- 4kV
+/- 4kV line-to-earth, +/- 2kV line-to-line
+/- 2kV line-to-earth, +/- 1kV line-to-line
+/- 4kV line-to-earth, +/- 2kV line-to-line
4
3
4
Signal ports
10V
D.C Power ports
10V
A.C. Power ports
10V
Earth ground ports
10V
Enclosure ports
Voltage Dips & Interrupts
A.C. Power ports
IEC 61000-4-11
IEC 61000-4-12
Damped Oscillatory
IEC 61000-4-16
Mains Frequency Voltage
IEC 61000-4-17
Ripple on D.C. Power Supply
IEC 60255-5
Dielectric Strength
IEC 60255-5
H.V. Impulse
Note 1
4
D.C. Power ports
IEC 61000-4-29
+/- 4kV @ 2.5kHz
+/- 4kV
Signal ports
D.C. Power ports
A.C. Power ports
Surge
Severity Levels
4
4
Note 1
D.C. Power ports
Earth ground ports
IEC 61000-4-5
Test Levels
+/- 8kV
+/- 15kV
20 V/m
Signal ports
D.C. Power ports
A.C. Power ports
Signal ports
D.C. Power ports
D.C. Power ports
Signal ports
D.C. Power ports
A.C. Power ports
Signal ports
D.C. Power ports
A.C. Power ports
40 A/m continuous, 1000 A/m for 1 s
1000 A/m for 1 s
Note 1
5
30% for 0.1s, 60% for 0.1s, 100% for 0.05s
N/A
30% for 1 period, 60% for 50 periods
N/A
100% for 5 periods, 100% for 50 periods
N/A
2.5kV common, 1kV diff. mode@1MHz
2.5kV common, 1kV diff. mode@1MHz
2.5kV common, 1kV diff. mode@1MHz
30V Continuous, 300V for 1s
30V Continuous, 300V for 1s
10%
2kVac (Fail-Safe Relay output)
2kVac
2kVac
5kV (Fail-Safe Relay output)
5kV
5kV
3
3
3
4
4
3
N/A
N/A
N/A
N/A
N/A
N/A
IEEE 1613 (C37.90.x) EMI IMMUNITY TYPE TESTS 2
Test
Description
IEEE C37.90.3
ESD
IEEE C37.90.2
Radiated RFI
IEEE C37.90.1
Fast Transient
IEEE C37.90.1
Oscillatory
IEEE C37.90
H.V. Impulse
IEEE C37.90
Dielectric Strength
Enclosure Contact
Enclosure Air
Enclosure ports
Signal ports
D.C. Power ports
A.C. Power ports
Earth ground ports3
Signal ports
D.C. Power ports
A.C. Power ports
Signal ports
D.C. Power ports
A.C. Power ports
Signal ports
D.C. Power ports
A.C. Power ports
Test Levels
+/-2kV, +/-4kV, +/- 8kV
+/-4kV, +/-8kV, +/-15kV
35 V/m
+/- 4kV @ 2.5kHz
+/- 4kV
+/- 4kV
+/- 4kV
2.5kV common mode @1MHz
2.5kV common, 1kV diff. mode@1MHz
2.5kV common, 1kV diff. mode@1MHz
5kV (Fail-Safe Relay output)
5kV
5kV
2kVac
2kVac
2kVac
Environmental Type Tests
Test
IEC 60068-2-1
Cold Temperature
Test Ad
Test Levels
-40C, 16 Hours
IEC 60068-2-2
Dry Heat
Test Bd
+85C, 16 Hours
IEC 60068-2-30
Humidity (Damp Heat, Cyclic)
Test Db
95% (non-condensing), 55C , 6 cycles
IEC 60255-21-1
IEC 60255-21-2
Description
Vibration
Shock
2g @ (10 - 150) Hz
30g @ 11mS
Notes: 1. RuggedCom specified severity levels
2. Meets Class 2 requirements for an all fiber configuration. Class 1 for copper ports.
www.RuggedCom.com
RuggedBackbone RX1500/1501
RuggedBackbone RX1500/1501
Industrially Hardened Layer 3 Switch and Router
Technical Specifications
Power Supply
EMI Immunity and Environmental Compliance
24VDC (1036VDC)
IEC 61000-6-2 Industrial (Generic)
IEC 61800-3 Industrial (Variable Speed Drive Systems)
IEC 61850-3 Electric Utility Substations
IEEE 1613 Electric Utility Substations
NEMA TS 2 Traffic Control Equipment
48VDC (3672VDC)
HI Voltage AC/DC : 88-300VDC or 85-264 VAC
Power Consumption: 40W Max
Physical
Height = 1.74
Width = 17.36
Depth = 11.9
Mounting: Rack mounted
Ingress Protection: IP40 (1 mm Objects)
Weight: Dependent upon module selection
approximately 10.3 lbs
Critical Alarm Relay
Form-C contact relay: 5A@30VDC, 8A@250VAC
Switch Properties
Switching method: Store & Forward
Switching latency: 7 s
Switching bandwidth:10Gbps
MAC addresses: 8192
MAC address table size: 64kbytes
Priority Queues: 4
Frame buffer memory: 1 Mbit
VLANs: 255
IGMP multicast groups: 256
Port rate limiting
No head of line blocking
Approvals
ISO: Designed and manufactured using a
ISO9001: 2008 certified quality program
CE Marking
Emissions: FCC Part 15 (Class A),EN55022
(CISPR22 Class A)
Safety: cCSAus (Compliant with CSA C22.2 No. 60950,
UL 60950, EN60950)
Laser Eye Safety (FDA/CDRH): Complies with 21
CFR Chapter1, Subchapter J.
Warranty
5 Years - Applicable to design and manufacturing
related product defects.
Network Management
HTTPS graphical web-based
SNMP v1, v2c, v3
Telnet, VT100
Command Line Interface (CLI)
SSH
www.RuggedCom.com
IEEE Compliance
802.3-10BaseT
802.3u-100BaseTX, 100BaseFX
802.3x-Flow Control
802.3z-1000BaseLX
802.3ab-1000BaseTX
802.3ad-Link Aggregation
802.1d-MAC Bridges
802.1d-Spanning Tree Protocol
802.1p-Class of Service
802.1Q-VLAN Tagging
802.1w-Rapid Spanning Tree Protocol
802.1x-Port Based Network Access Control
802.1Q-2005 (formerly 802.1s) MSTP
IETF RFC Compliance
RFC768-UDP
RFC783-TFTP
RFC791-IP
RFC792-ICMP
RFC793-TCP
RFC826-ARP
RFC854-Telnet
RFC894-IP over Ethernet
RFC1112-IGMP v1
RFC1519-CIDR
RFC1541-DHCP (client)
RFC2030-SNTP
RFC2068-HTTP
RFC2236-IGMP v2
RFC2284-EAP
RFC2475-Differentiated Services
RFC2865-RADIUS
RFC3414-SNMPv3-USM
RFC3415-SNMPv3-VACM
IETF SNMP MIBS
RFC1493-BRIDGE-MIB
RFC1907-SNMPv2-MIB
RFC2012-TCP-MIB
RFC2013-UDP-MIB
RFC2578-SNMPv2-SMI
RFC2579-SNMPv2-TC
RFC2819-RMON-MIB
RFC2863-IF-MIB
draft-ietf-bridge-rstpmib-03-BRIDGE-MIB
draft-ietf-bridge-bridgemib-smiv2-03-RSTP-MIB
IANAifType-MIB
RuggedBackbone RX1500/1501
RuggedBackbone RX1500/1501
Industrially Hardened Layer 3 Switch and Router
RX1500 Mechanical Drawing
www.RuggedCom.com
RuggedBackbone RX1500/1501
RuggedBackbone RX1500/1501
Industrially Hardened Layer 3 Switch and Router
RX1501 Mechanical Drawing
www.RuggedCom.com
RuggedBackbone RX1500/1501
10
RuggedBackbone RX1500/1501
Industrially Hardened Layer 3 Switch and Router
Order Codes
PM1
RX1500
LM1
LM3
LM2
LM4
PM2
RX1500 ____________________________________________________________
ST
MNT PM1
PM2
SFT
LM1
LM2
LM3
LM4
MOD
RX1501
PM1
LM1
LM3
LM5
LM2
LM4
LM6
RX1501 __________________________________________________________________
ST
MNT
PM1
SFT
LM1
LM2
LM3
LM4
LM5
LM6 MOD
ST: Switch Type Hardware
L2 = Layer 2 Switch
L3 = Layer 3 Switch
MNT: Mounting Options
RM = 19 Rack Mount Kit
00 = No Mounting Option
PM1 and PM2: Power Modules
HI = 88-300 VDC or 85-264VAC, screw terminal block
HIP = 88-300 VDC or 85-264VAC, pluggable terminal block
24 = 24VDC (10-36VDC), screw terminal block(3)
48 = 48VDC (36-72VDC), screw terminal block
24P = 24VDC (10-36VDC), pluggable terminal block(3)
48P = 48VDC (36-72VDC), pluggable terminal block
XXP = No Power Supply (PM2 only)
SFT: Software
L2SE = Layer 2 Standard Edition
L3SE = Layer 3 Standard Edition
LM1 through LM6 Line Modules
Blank Module
XX = Blank Module
Copper Ethernet Modules
6TX01 = 6 x 10/100TX RJ45
CG01 = 2x 10/100/1000TX RJ45 1
100BaseFX modules with 2 Ports1
FX01 = 2 x 100FX - Multimode, 1300nm, ST connectors, 2km
FX02 = 2 x 100FX - Multimode, 1300nm, SC connectors, 2km
FX11 = 2 x 100FX - Multimode, 1300nm, LC connectors, 2km
FX03 = 2 x 100FX - Multimode, 1300nm, MTRJ connectors, 2km
FX04 = 2 x 100FX - Singlemode, 1300nm, ST connectors, 20km
FX05 = 2 x 100FX - Singlemode, 1300nm, SC connectors, 20km
FX06 = 2 x 100FX - Singlemode, 1300nm, LC connectors, 20km
FX07 = 2 x 100FX - Singlemode, 1300nm, SC connectors, 50km
FX08 = 2 x 100FX - Singlemode, 1300nm, LC connectors, 50km
FX09 = 2 x 100FX - Singlemode, 1300nm, SC connectors, 90km
FX10 = 2 x 100FX - Singlemode, 1300nm, LC connectors, 90km
www.RuggedCom.com
100BaseFX modules with 4 Ports
4FX11 = 4 x 100FX - Multimode, 1300nm, LC connectors, 2km
4FX03 = 4 x 100FX - Multimode, 1300nm, MTRJ connectors, 2km
4FX06 = 4 x 100FX - Singlemode, 1300nm, LC connectors, 20km
4FX08 = 4 x 100FX - Singlemode, 1300nm, LC connectors, 50km
4FX10 = 4 x 100FX - Singlemode, 1300nm, LC connectors, 90km
FX50 = 4 x 100FX SFP Blank (no optical transceiver)
FX51 = 4 x 100SX SFP Multimode, 1310 nm, LC, 2km
FX52 = 4 x 100LX SFP Singlemode, 1300 nm, LC, 20km
FX53 = 4 x 100LX SFP Singlemode, 1300 nm, LC, 50km
FX54 = 4 x 100LX SFP Singlemode, 1550 nm, LC, 90km
Gigabit Ethernet Modules modules with 2 Ports 1
FG01 = 2 x 1000SX Multimode, 850 nm, LC, 500m
FG02 = 2 x 1000LX Singlemode 1300 nm, SC, 10km
FG03 = 2 x 1000LX Singlemode 1300 nm, LC, 10km
FG04 = 2 x 1000LX Singlemode 1300 nm, SC, 25km
FG05 = 2 x 1000LX Singlemode 1300 nm, LC, 25km
FG50 = 2 x 1000LX SFP Blank(no optical transceiver)
FG51 = 2 x 1000SX SFP Multimode, 850 nm, LC, 500m
FG52 = 2 x 1000LX SFP Singlemode, 1310 nm, LC, 10km
FG53 = 2 x 1000LX SFP Singlemode, 1310 nm, LC, 25km
FG54 = 2 x 1000LX SFP Singlemode, 1550 nm, LC, 70km
WAN Port Options2
TC1 = Single T1/E1 via RJ45 (Channelized/Unchannelized)
TC2 = Dual T1/E1 via RJ45 (Channelized/Unchannelized)
TC4 = Quad T1/E1 via RJ45 (Channelized/Unchannelized)
E01 = Single E1 75 Ohms via BNC (Channelized/Unchannelized)
E02 = Dual E1 75 Ohms via BNC (Channelized/Unchannelized)
MOD: Hardware Modifications
XX = None
C01 = With Conformal Coating
Notes:
1. O
n the RX1501 these modules may only be selected for LM1 and LM2.
2. Only one T1/E1 module may be used per router.
3. Coming Soon.
RuggedBackbone RX1500/1501
11
RuggedBackbone RX1500/1501
Industrially Hardened Layer 3 Switch and Router
Example Order Codes:
RX1500-L3-RM-HI-HI-L3SE-FX01-FX01-6TX01-TC1-XX
One Layer 3 RX1500 unit, 19 Rack Mounted, with 2 (two)
HI power supplies, 2 (two) 2-Port 100FX Multimode line
modules, 1 (one) 6-Port 10/100TX module, one Single T1/E1
via RJ45 module, running Layer 3 Standard Edition firmware
RX1501-L3-RM-HI-L3SE-4FX01-4FX01-6TX01-6TX01-XXXX-XX
One Layer 3 RX1501 unit, 19 Rack Mounted, with a HI
power supply, 2 (two) 4-Port 100FX Multimode line modules,
2 (two) 6-Port 10/100TX modules, 2 blank modules, running
Layer 3 Standard Edition firmware
Individual Parts Order Codes
Any of the modules, Power, Control, Switch or Line Modules,
may be ordered as individual parts. An empty chassis and
brackets may also be ordered as single pieces.
RX1500PN _____ ______
PT
MOD
PT: Individual Part to be ordered
The Part may be chosen from MNT or any module from the
RX1500 order codes page. By specifying a module you are
selecting a line module that may be seated into the RX1500
unit without any cabling. By specifying a MNT option you are
selecting brackets for the RX1500
Additional Part numbers used for Software Upgrades:
SFTUP1 = Layer 2 Standard Edition to
Layer 3 Standard Edition
SFTUP2* = Layer 2 Standard Edition to
Layer 3 Security Edition
SFTUP3* = Layer 3 Standard Edition to
Layer 3 Security Edition
Example Order Codes for ordering parts
RX1500PN RMXX
This describes the 19 Rack Mount Kit
RX1500PN-HIXX
This is one HI power supply module
RX1500PN-6TX01XX
This is one 6-port 10/100BaseTX line module, for the
RX1500, with RJ45 connectors
RX1500PN- SFTUP1XX
This order code is used to request a license key to
upgrade a RX1500 from Layer 2 Standard Edition to
Layer 3 Standard Edition software
MOD: Hardware Modifications
XX = None
C01 = with Conformal Coating
* Coming Soon
www.RuggedCom.com
RuggedBackbone RX1500/1501
12
RuggedBackbone RX1500/1501
Industrially Hardened Layer 3 Switch and Router
RuggedCom Inc.
300 Applewood Crescent,
Concord, Ontario, Canada L4K 5C7
Tel: +1 (905) 856-5288 Fax: +1 (905) 856-1995
Toll Free: 1 (888) 264-0006
Technical Support Center: 1 (866) 922-7975
2010 RuggedCom Inc.
RuggedBackbone is a trademark of RuggedCom Inc.
Ethernet is a trademark of the Xerox Corporation.
Patent Pending
All specifications in this document are subject to change without notice.
Rev 1h04/06/11
For additional information on our products and
services, please visit our website at: www.RuggedCom.com
www.RuggedCom.com
RuggedBackbone RX1500/1501
13