From R&D Lattes
PACIS-C264 Presentation
24 January 2007
.
PACiS Local Expert Training
Local Expert Training : C264
General Tools
Basic Objects
Communication
Applicative features
Automation Systems R&D 11/01/07
General Tools
HELP
Action : displays the shell commands available in the
C264 software.
Parameter : none
help
Action : displays the shell commands available in the
vxworks kernel
Parameter : none
OdLogLevel x
Action : activates the IEC61850/UCA2 agency traces
Parameter : x =1 : trace activated
x=0 : trace deactivated
Automation Systems R&D 11/01/07
General Tools
SET_TRACES (task ID, msk, status)
Action : activates the debug traces for all applicative
tasks
Parameters : task_ID : task identifier. See array below.
Msk
: trace level.
Status
: 1 trace activated
0 trace deactivated
Automation Systems R&D 11/01/07
C264 Main Task Identifiers
N Task Identifier
Aim
01
T01CTRL
Autotest and watchdog management
02
T02SUPERV
Supervision
04
T04HDLDI
Digital input acquisition management
06
T04HDLAI
Analogue input acquisition management
13
T13SYNCHRO
Synchronization management
18
T18COND
Control management
20
T20GESTTS
Binary Input management
21
T21GESTCT
Binary counter management
22
T22GESTTM
Measurement management
24
T24GESTTC
Control management
25
T25ALARM
Alarm management
28
T28ISAGRAF
Isagraf feature management
Automation Systems R&D 11/01/07
C264 Main Task Identifiers
N Task Identifier
Aim
37
T37ILOCK
PSL and Interlock management
46
T46AUTREC
Auto recloser management
47
T47RED
Redundancy management
49
T49SYCHECK
Synchrocheck management
53
T53ATC
ATCC management
54
T54HMILCD
Local HMI management
62
T62TMU210
TMU210 protection feature management
63
T63MICOMS1
Micom S1 for protection feature management
Automation Systems R&D 11/01/07
C264 Communication Task Identifiers
N Task Identifier
Aim
32
T32DNP3M
DNP3 master management
35
T35IECM2
T101 and T103 master communication level 2
36
T36T103M7
T103 master communication level 7
38
T38SERMAN
IEC61850 server management
40
T40CLIMAN
IEC61850 client management
42
T42MODBM2
Modbus master level 2 management
48
T48MODBM7
Modbus master level 7 management
51
T51DNP3S
DNP3 slave management
55
T55T101S
T101 slave management
58
T58T101M7
T101 master management
59
T59T104S
T104 slave management
Automation Systems R&D 11/01/07
C264 Communication Task Identifiers
N Task Identifier
Aim
60
T60MODBS7
Modbus slave management
61
T61DNP3E
DNP3 IP slave management
Automation Systems R&D 11/01/07
Norgint Selection
S_DBTEST_print_norgint_list
Action : displays the first norgint and the number of
items by kind of datapoint.
Parameter : none
S_DBTEST_print_computer_wiring
Action : displays computer wiring.
Parameter : none
S_DBTEST_print_line_info
Action : displays serial line configuration
Parameter : none
Automation Systems R&D 11/01/07
Digital Inputs
aff_di_board_state board, type
Action : Displays all Digital Input states of a board.
Parameters : board : board address
type : 0 : DIU board, 1 : CCU board
xPS :
10
SET_TRACES 4,16,1
Automation Systems R&D 11/01/07
10
Analogue Inputs
aff_ai_board_data board
Action : Displays all Analogue Inputs values and
qualities of the specified board.
Parameter : board : board address
11
Automation Systems R&D 11/01/07
11
CTVT Analogue Inputs
CTVT_GET_MEAS
Action : Displays all CTVT Analogue Inputs values and
qualities.
aff_ctvt_data
Action : Displays CTVT data for synchrocheck feature
12
Automation Systems R&D 11/01/07
12
Digital Outputs
aff_do_data
Action : Displays the states of all Digital Outputs of DOU
and CCU boards
(# : not valid, - : DO not activated, X : DO activated)
get_state_do board
Action : Displays the states of Digital Outputs of a board
(# : not valid, - : DO not activated, X : DO
activated)
Parameter : board : board address
active_ccu board,channel,order
Action : Activate a Digital Output on a CCU board
Parameters : board : CCU board address
channel : Digital Output to activate
order : New state (0 : not activated, 1 : Activated)
13
Automation Systems R&D 11/01/07
13
Digital Outputs
active_dou board,channel,order
Action : Activate a Digital Output on a DOU board
Parameters : board : DOU board address
channel : Digital Output to activate
order : New state (0 : not activated, 1 : Activated)
14
Automation Systems R&D 11/01/07
14
Binary Inputs
aff_bi_info norgint
Action : Displays Binary Input configuration data
Parameters : norgint : Binary Input norgint
15
Automation Systems R&D 11/01/07
15
Binary Inputs
aff_bi_state2 bi_norgint
Action : Displays Binary Input state and quality
Parameter : none
get_di_norgint
Action : Displays the Binary Inputs and Digital Inputs
database relations
Parameter : none
aff_di_info board ,channel
Action : Displays Digital Input database informations
Parameters : board : board number
channel : channel number on the board
Most commonly used trace : SET_TRACES 20,16,1
16
Automation Systems R&D 11/01/07
16
Control and Setpoint Objects
aff_co_info co_norgint
Action : Displays Control database informations
Parameter : co_norgint : Control norgint
aff_sp_info sp_norgint
Action : Displays Setpoint database informations
Parameter : sp_norgint : Setpoint norgint
Most commonly used trace : SET_TRACES 24,16,1
17
Automation Systems R&D 11/01/07
17
Measurements
aff_meas_info norgint
Action : Displays Measurement database informations.
Parameter : norgint : Measurement norgint
aff_dm_info dm_norgint
Action : Displays Digital Measurement database specific
informations.
Parameter : dm_norgint : Digital Measurement norgint
aff_meas_data norgint
Action : Displays Measurement value and quality
Parameter : norgint : Measurement norgint
Most commonly used trace : SET_TRACES 22,16,1
18
Automation Systems R&D 11/01/07
18
Communication
Low level communication
Spy objects on a communication
19
Automation Systems R&D 11/01/07
19
Low level communication
traces_sccx = level
Action : Displays sent and received frames on a legacy
bus (serial line)
Parameters : x=[1,2,3,4] : communication port number
(defined in the database)
level =16 : trace activated
level =0 : trace not activated
20
Automation Systems R&D 11/01/07
20
Communication
traces_apieth
Action : Displays sent and received frames on IP
Parameter : traces_apieth =16 : trace activated
traces_apieth =0 : trace not activated
aff_104
Action : Displays informations about T104 sockets
Parameter : none
21
Automation Systems R&D 11/01/07
21
Spy objects on a communication
SET_TRACES comm task number, level, activation
Action : activates or deactivates the traces on the
specified task, with the specified trace level.
Parameters :
comm task number : see communication task identifiers
level :
1
Error level
2
Communication frame level
4
Communication data level
8
connection level
10h sent message level
20h received message level
40h Received Binary Input level
80h Received Control level
100h Received Measurement level
22
Automation Systems R&D 11/01/07
22
Spy objects on a communication
23
200h
Disturbance level (if managed by the communication task)
400h
Tunneling level (if managed by the communication task)
800h
Time synchronization level
1000h
Internal communication event level (specific to each task)
2000h
Sent Measurement level
4000h
Sent Binary Input level
8000h
Task initialization level
10000h
General interrogation level
20000h
Binary counter level
40000h
Protocol level
80000h
Generic traces level
100000h
File management level
200000h
Tap Position Indication level
400000h
SOE management level
Automation Systems R&D 11/01/07
23
Applicative Features
Control management
Autorecloser
Synchrocheck
Time synchronization
Alarms
ATCC
Fast automation and Interlock
Redundancy
Local HMI
24
Automation Systems R&D 11/01/07
24
Control Management
Trace to set before sending a control to the C264
SET_TRACES 18,4,1
Then check for ack value, or error message
SET_TRACES 24,4,1
Then check for ack value, or error message
For ack value trace only :
SET_TRACES 24,16,1
25
Automation Systems R&D 11/01/07
25
Synchrocheck
aff_sc_info index_synchrocheck
Action : displays Synchrocheck database information
Parameter : index_synchrocheck : Synchrocheck norgint
Synchrocheck first norgint
aff_sc_data index_synchrocheck
Action : displays Synchrocheck real time data
Parameter : index_synchrocheck : Synchrocheck norgint
Synchrocheck first norgint
aff_synchrocheck_info
Action : displays all Synchrochecks database
information (for internal and external synchrochecks)
26
Automation Systems R&D 11/01/07
26
ATCC
ccaCatcAff genData, group, node, voltLevel, organ,
transf
Action : displays ATCC data
Parameters : genData : donnes gnrales de lATCC
group : ATCC managed datapoint groups data
node : ATCC managed topological nodes
voltLevel : data sorted by voltage level
organ : ATCC managed organ data
transf : ATCC managed transformers data
27
Automation Systems R&D 11/01/07
27
Fast automation and Interlock
aff_eql_info
Action : displays Fast Automation and Interlock (EQL)
database information
Parameter : none
Caution : all defined Fast Automation and Interlock are
displayed
aff_eql_data
index_eql
Action : displays Fast Automation and Interlock real time
data
Parameter : index_eql : Number given by the command
above (aff_eql_info)
28
Automation Systems R&D 11/01/07
28
Redundancy
aff_red_data
Action : Display data used in C264 redundancy.
Parameters : none.
Displayed data :
Alternative values
Redundancy type
BACK UP]
: MAIN
[NO REDUNDANCY;
Computer Mode
MAINTENANCE]
: ACTIVE MODE
[STAND BY MODE;
BI change mode
: OFF
[ON]
BI network status : OFF
[ON]
CO change mode
: ON
[OFF]
CO network status : ON
[OFF]
MEAS local status : 0x0000 (valid: 0)
[0 0X003F] (valid : 1)
MEAS other status : 0x0000 (valid: 0) [0 0X003F] (valid : 1)
29
Automation Systems R&D 11/01/07
29
Redundancy
Default detected on has a value of :
CCU board
0x20
DOU board
0x10
CTVT board
0x08
DIU board
0x04
BIU board
0x02
AIU board
0x01
MEAS local and other status are the addition of the
above values in case of board failure
30
Automation Systems R&D 11/01/07
30