Textbook and
Educational Aids
ProSafe-RS
Training Manual
TE Y109JA01E-PPRS
TE Y109JA01E-PPRS
1st Edition
Introduction
The objective of the Training manual is to acquaint the user with the system layout,
operations screens and the terminologies used in the Prosafe-RS safety system.
This training module is designed to add more value to the traditional training.
The participant can acquire basic knowledge on the Prosafe-RS system.
The Training manual consists of multiple chapters
Each chapter consists of multiple topics.
Media No. TEY109JA01E-PPRS
Edition:JAN 2009
All Rights Reserved Copyright 2000, Yokogawa India
TE Y109JA01E-PPRS
1st Edition: Jan 2009
ii
TE Y109JA01E-PPRS
1st Edition: Jan 2009
iii
Safety Precautions
Safety, Protection, and Modification of the Product
-
In order to protect the system controlled by the product and the product itself
and ensure safe operation, observe the safety precautions described in this
instruction manual. We assume no liability for safety if users fail to observe
these instructions when operating the product.
If any protection or safety circuit is required for the system controlled by the
product or for the product itself, prepare it separately.
Be sure to use the spare parts approved by Yokogawa Electric Corporation
(hereafter simply referred to as YOKOGAWA) when replacing parts or
consumables.
Modification of the product is strictly prohibited.
The following symbols are used in the product and instruction manual to indicate
that there are precautions for safety:
Indicates that caution is required for operation. This symbol is placed on the
product to refer the user to the instruction manual in order to protect the
operator and the equipment. In the instruction manuals you will find precautions
to avoid physical injury or death of the operator, including electrical shocks.
Identifies a protective grounding terminal. Before using the product, ground the
terminal.
Identifies a functional grounding terminal. Before using the product, ground the
terminal.
Indicates an AC supply.
Indicates a DC supply.
Indicates that the main switch is ON.
Indicates that the main switch is OFF.
TE Y109JA01E-PPRS
1st Edition: Jan 2009
iv
Notes on Handling Manuals
-
Please read the information thoroughly before using the product.
The purpose of these manuals is not to warrant that the product is well suited to
any particular purpose but rather to describe the functional details of the
product.
No part of the manuals may be transferred or reproduced without prior written
consent from YOKOGAWA.
YOKOGAWA reserves the right to make improvements in the manuals and
product at any time, without notice or obligation.
If you have any questions, or you find mistakes or omissions in the manuals,
please contact our sales representative or your local distributor.
Warning and Disclaimer
The product is provided on an "as is" basis. YOKOGAWA shall have neither liability
nor responsibility to any person or entity with respect to any direct or indirect loss or
damage arising from using the product or any defect of the product that YOKOGAWA
cannot predict in advance.
Notes on Software
-
YOKOGAWA makes no warranties, either expressed or implied, with respect
to the software's merchantability or suitability for any particular purpose,
except as specified in the terms of warranty.
This product may be used on a one machine only. If you need to use the
product on another machine, you must purchase another product.
It is strictly prohibited to reproduce the product except for the purpose of
backup.
Store the CD-ROM (the original medium) in a safe place.
It is strictly prohibited to perform any reverse-engineering operation, such as
reverse compilation or reverse assembling on the product.
No part of the product may be transferred, converted or sublet for use by
any third party, without prior written consent from YOKOGAWA.
TE Y109JA01E-PPRS
1st Edition: Jan 2009
Documentation Conventions
Typographical Conventions
The following typographical conventions are used throughout the manuals:
Commonly used conventions throughout manuals:
Character string enclosed by a set of single angle-brackets:
Indicates a portion provided with a link. Clicking the string in angle-brackets
calls up related topics.
Example:
<Toc> <Ind>
Character string to be entered:
The characters that must be entered are shown in monospace font as follows:
Example:
FI.PV=50.0
Mark
This symbol indicates the description for an item for which you should make a
setting in the products engineering window.
While operating an engineering window, the help information for the selected
item can be accessed from Builder Definition Items in the Help menu.
Listing more than one definition item after this symbol implies that the paragraph
on the page describes more than one definition item.
Example:
Tag name, Tag importance, Window name
Mark
Indicates a space between character strings that must be entered.
Example:
.AL PIC010 -SC
Character string enclosed by brackets ({ }):
Indicates an option that can be omitted.
Example:
.PR TAG{ .sheet name}
TE Y109JA01E-PPRS
1st Edition: Jan 2009
vi
z Conventions used to show key or button operations:
Characters enclosed by brackets ([ ]):
Characters enclosed by brackets within any description on a key or button
operation, indicate either a key on the HIS (Human Interface Station) keyboard, a
key on the operation keyboard, a button name on a window, or an item displayed
on a window.
Example:
To alter the function, press the [ESC] key.
Conventions used in command syntax or program statements:
The following conventions are used within a command syntax or program
statement format:
Characters enclosed by angle-brackets:
Indicate character strings that user can specify freely according to certain
guidelines.
Example:
#define <Identifier><Character string>
... Mark
Indicates that the previous command or argument may be repeated.
Example:
Imax (arg1, arg2, ...)
Characters enclosed by brackets ([ ]):
Indicate those character strings that can be omitted.
Example:
sysalarm format_string [output_value ...]
Characters enclosed by separators ( ):
Indicate those character strings that can be selected from more than one option.
Example:
opeguide <format_character_string> [, <output_value> ...]
OG,<element number>
TE Y109JA01E-PPRS
1st Edition: Jan 2009
vii
Symbol Marks
Throughout this manual, you will find several different types of symbols are used
to identify different sections of text. This section describes these icons.
CAUTION
Identifies instructions that must be observed in order to avoid physical injury
and electric shock or death of the operator.
WARNING
Identifies instructions that must be observed in order to prevent the software
or hardware from being damaged or the system from becoming faulty.
CAUTION
Identifies additional information required to understand operations or
functions.
TIP
Identifies additional information.
SEE ALSO
Identifies a source to be referred to.
Clicking a reference displayed in green can call up its source, while clicking a
reference displayed in black cannot.
Drawing Conventions
Some drawings may be partially emphasized, simplified, or omitted, for the
convenience of description.
Some screen images depicted in the manual may have different display positions
or character types (e.g., the upper / lower case). Also note that some of the
images contained in this manual are display examples.
TE Y109JA01E-PPRS
1st Edition: Jan 2009
viii
Copyright and Trademark Notices
All Rights Reserved
The copyrights of the programs and online manual contained in the CD-ROM are
reserved.
The online manual is protected by the PDF security from modification, however, it
can be output via a printer. Printing out the online manual is only allowed for the
purpose of using the product. When using the printed information of the online
manual, check if the version is the most recent one by referring to the CD-ROM's
version.
No part of the online manual may be transferred, sold, distributed (including
delivery via a commercial PC network or the like), or registered or recorded on
videotapes.
Trademark Acknowledgments
-
CENTUM is a registered trademark of YOKOGAWA.
Microsoft, Windows, Windows NT, Excel, Visual Basic, and Internet Explorer
are registered trademarks of Microsoft Corporation.
Adobe and Acrobat are trademarks of Adobe Systems Incorporated and
registered within particular jurisdictions.
Ethernet is a registered trademark of XEROX Corporation.
Java is a registered trademark of Sun Microsystems,Inc.
Netscape Communicator is
Communications Corporation.
NetDDE is a registered trademark of Wonderware Corporation.
MELSEC-A is a registered trademark of Mitsubishi Electric Corporation.
Modicon and Modbus are registered trademarks of AEG Schneider
Automation.
Memocon-SC is a registered trademark of Yaskawa Electric Corporation.
PLC is a registered trademark of Allen-Bradley Company Inc.
SYSMAC is a registered trademark of OMRON Corporation.
SIEMENS and SIMATIC are registered trademarks of Siemens Industrial
Automation Ltd.
"FOUNDATION" in "FOUNDATION Fieldbus" is a trademark of Fieldbus
Foundation.
All other company and product names mentioned in this manual are
trademarks or registered trademarks of their respective companies.
We do not use TM or (R) mark to indicate those trademarks or registered
trademarks in this manual.
registered
trademark
TE Y109JA01E-PPRS
of
Netscape
1st Edition: Jan 2009
Prosafe-RS
Training Manual
TE Y109JA01E-PPRS 1st Edition
TOC
Table of contents
Chapter
Topic
Page Number
01.
Introduction to Safety
02.
Prosafe-RS Hardware Overview
11
03.
Introduction to Workbench
30
04.
Engineering in Prosafe-RS
42
05.
Security
60
06.
Downloading
69
07.
IEC61131-3 FBD-LD
83
08.
Integration
105
09.
Sequence of Event Recorder
122
TE Y109JA01E-PPRS
1. INTRODUCTION TO SAFETY
TE Y109JA01E-PPRS
Table of contents
Page Number
1.1 What is a Safety system?
1.2 Why Safety?
1.3 Demand for Protective Action
1.4 Function of a SIS
1.5 Safety Systems and their features
1.5.1 Applications of a safety system
1.5.2 Differences between DCS and SIS
1.6 Safety standards
1.7 Properties of a Safety System
1.7.1 System failures
1.7.2 Process safety time
1.7.3 Reliability
1.8 Safety System Architecture
1.9 Yokogawas Contribution to Industrial Safety
10
TE Y109JA01E-PPRS
1.1 What is a Safety system?
A Safety system is a system that provides an independent and predetermined emergency shutdown
path in case a process runs out of control.
A process that run out of control can cause:
Damage to People ( Both on & off site)
Damage to Environment
Loss of Equipment
Loss of Production and there by loss of money
TE Y109JA01E-PPRS
1.2 Why Safety?
Safety is defined as a "situation in which the risk is not higher than the risk limit". Safety system takes
care to keep the situation within the risk limit.
1.3 Demand for Protective Action
Sometimes things go wrong in the process and an operator takes action to keep the process within
limits and It Works!!!!
If that does not work, there may be an accident...
TE Y109JA01E-PPRS
To avoid such situation in some processes, a safety instrumented system (SIS) is also needed. It is
configured to automatically respond to certain process conditions and will perform preprogrammed
actions to mitigate the process condition.
1.4 Function of a SIS
SIS keeps the process from not crossing the safety limits.
As shown in the above figure while the process is within the range of normal behavior, the Basic
Process Control System will meet all requirements to control the process.
As the process becomes more unstable and approaches the high alarm level, the BPCS may or may not
be able to regain control of the process value in time to prevent an unsafe condition. It is expected that
the operator takes action to control the process.
If the process value continues in a unsafe direction, the trip level is reached. The SIS executes an
emergency shutdown action, preventing the process from exceeding the safe levels.
TE Y109JA01E-PPRS
1.5 Safety Systems and their features.
Safety system is a control system comprising of sensors, logic solvers and final control elements
designed to take process to a safe state when predetermined conditions are violated .
1.5.1 Applications of a safety system.
Some of the applications of the safety system are
Emergency shutdown.
Burner management.
Fire and gas detection.
1.5.2 Differences between DCS and safety system.
DCS
Highly flexible
Configuration changes can be done online.
Variety of online modifications can be done
without much complicacy
During the failure of the control system,
state of outputs are unpredictable
SIS
Fixed functionality
Complex procedures are involved in
making any change.
The possibility to repair the hardware is
limited while the plant is running
Output state is predictable during the
functional failure of a system.
Regular testing of control system is not
required.
Explicit procedures are followed to test the
system hardware.
TE Y109JA01E-PPRS
1.6 Safety standards
The two most important standards for functional safety are IEC 61508 and 61511.The first one is used to
design and manufacture safety systems.
The IEC 61511 is normally used during the design, startup and operation of a complete plant.
The standards specify all kinds of requirements for the complete life cycle of the plant. It starts with
hazards analysis and definition of safety functions, then the design and testing of the safety system,
requirements for operation and maintenance.
1.7 Properties of a Safety System
1.7.1
System failures
Failures can be divided in to
Hardware failures
Systematic Failures
Hardware failures are caused by the malfunctioning of the hardware component. Stress is the cause for
failure.
The stresses can be of different types. Below are the few examples.
Heat
Chemical Corrosion
Humidity
Vibration
Electrostatic Discharge
Operational and maintenance Errors
Systematic failures are related to errors in software design. This can be corrected by reprogramming.
1.7.2 Process safety time.
Process safety time is the maximum time between the demand and the necessary shutdown action. It is
a property of the process. Reaction time of the safety function should be with in the process safety time.
1.7.3 Reliability
Reliability is a combination of safety integrity and availability.
TE Y109JA01E-PPRS
1.8 Architecture
The simplest architecture of a safety function is shown in figure below. The input is sensed by a single
input circuitry, this input will be evaluated by the processor and the output will be placed in the output
circuit. The concept of redundancy and voting is common in SIS applications.
Input Circuit
The Prosafe-RS
Diagnostics.
Processor
is
TE Y109JA01E-PPRS
designed
with
Output Circuit
an
internal
architecture
of
out
of
with
10
1.9 Yokogawas Contribution to Industrial
Safety
Industrial automation is at the heart of Yokogawa's business. For more than five decades, we have been
developing the most comprehensive process control solutions for process industries worldwide. Deeply
ingrained in our corporate culture are the principles that reliability is a top priority, and that system
continuity and expandability are essentials.
To deliver a control platform in which our customers can have full confidence in solutions for the
evolving safety environment, Yokogawa proudly releases ProSafe-RS, a revolution in safety
instrumented systems.
TE Y109JA01E-PPRS
11
2. PROSAFE-RS HARDWARE OVERVIEW
TE Y109JA01E-PPRS
12
Table of contents
2.1
2.2
Page Number
Introduction
14
2.1.1 Overview of ProSafe-RS
14
2.1.2 Safety Application
14
System Configuration
14
2.2.1 Prosafe RS basic configuration
14
2.2.2 Prosafe RS/Centum CS 3000 Integration structure
15
2.3
Components of a Safety Control Station.
16
2.4
Components of a Safety control Unit
17
2.4.1 Standard type Safety Control Unit
17
2.4.2 Wide Range temperature type Safety Control Unit
18
2.4.3 Components of Safety Control Unit SSC10D (for Vnet)
18
2.4.4 Components of Safety Control Unit SSC50D (for Vnet/IP)
19
2.4.5 Processor module
19
2.4.6 Battery
19
2.4.7 LED display on processor module
20
2.4.8 Setting Switches on processor module
21
2.4.9 ESB coupler module
21
2.4.10 Vnet Coupler module
22
2.5
Configuration of Safety Node unit
2.5.1 Input/Output modules
2.6
22
22
2.5.1.1 Analog input module
23
2.5.1.2 Digital input/output module
23
2.5.1.3 Communication module
24
2.5.1.4 Accessories related to input/output module
25
Addressing
27
2.6.1. Setting Domain Address
27
2.6.2 Setting station address
27
2.6.3 Setting Node number on Safety node
27
TE Y109JA01E-PPRS
13
Table of contents
2.7
Redundancy
Page Number
28
2.7.1 CPU module
28
2.7.2 Input/Output module
28
2.7.3 Vnet communication
29
2.7.4 Power supply module
29
2.7.5 ESB bus
29
2.7.6 SB Bus
29
TE Y109JA01E-PPRS
14
2.1 Introduction
Prosafe-RS is a microprocessor based Safety System designed specifically for critical applications such
as: emergency shutdown systems, Burner management systems, fire and gas detection systems and
high availability process control.
This chapter provides the details of the safety considerations for building the safety system with the
ProSafe-RS.
2.1.1 Overview of ProSafe-RS
The ProSafe-RS is the safety system thatconsist of the safety controller, SCS, and an engineering and
maintenance PC, SENG. The minimum configuration includes one SCS and one SENG.
2.1.2 Safety Application
ProSafe-RS is primarily used for the following safety applications. The use of the ProSafe-RS
conforming to the standards for each application is also certified.
For the details of the requirements, refer to each standard.
ESD (Emergency Shutdown System) / PSD (Process Shutdown System)
F&G (Fire and Gas detection System: EN54, NFPA72)
BMS (Burner Management System: EN298, NFPA8501, NFPA8502, prEN50156)
2.2 System Configuration
2.2.1 ProSafe-RS Basic Configuration
ProSafe-RS consists of Safety Control Station (SCS) and Safety Engineering PC (SENG). Moreover,
ProSafe-RS can build the system connected with CS 3000 and the system connected with other systems
than CS 3000 via Modbus. The basic configuration of ProSafe-RS consists of SENG and SCS.
In the following figure, each of two SCSs has the CPU node which is connected to two I/O nodes. (I/O
module can be installed in CPU node.)
TE Y109JA01E-PPRS
15
2.2.2 ProSafe-RS/CENTUM CS 3000 Integration Structure
The structure that connects ProSafe-RS with CS 3000 projects is called ProSafe-RS/CENTUM CS 3000
Integration Configuration. The below Figure illustrates an example of the system configuration of
ProSafe-RS consisting of one SENG, two SCSs, a HIS and an FCS. SCS and SENG are connected with
the control bus called V net. Safety communication through V net allows data to be sent and received
between SCSs. In SCS, I/O can be expanded by increasing the number of I/O nodes.
For CS 3000 Integration Structure,
Both FCS and SCS can be operated and monitored from HIS.FCS can communicate with SCS via
V net. The communication has no impact on the safety functions running on SCS.
SCS engineering is performed from SENG and FCS and HIS engineering from ENG. Engineering
of the CS 3000 integration function is performed from both SENG and ENG. SENG functions,
ENG functions and HIS functions can also be installed in several PCs as well as one PC
Ethernet
Safety system Eng.
SENG
CS 3000 HIS
CS 3000 ENG.
V net
CS 3000 FCS
Safety Controller
The SENG is a general-purpose PC on which the engineering functions to build SCS applications
are installed. An SCS application created by using of FBD (Function Block Diagram) and/or LD
(Ladder Diagram) is called Application Logic. Each application logic is managed as part of the
SCS project.
TE Y109JA01E-PPRS
16
The ENG is a general-purpose PC on which the CS 3000 system generation function is installed.
Each CS 3000 application generated on the ENG is managed as part of the CS 3000 project.
The HIS is a general-purpose PC on which the CS 3000 operation function is installed.
SCS tags can be accessed from FCS. The data exchange between the SCS and the FCS will not
affect the safety communication between two SCS.
2.3 Components of a Safety Control Station
A basic system is called safety control station. A SCS can communicate with the other stations via
Vnet/Vnet/IP. SCS consists of a Safety Control Unit (CPU node) and several Safety Node Unit (I/O nodes).
Up to nine I/O nodes can be connected.
The following figure is an example of hardware configuration of SCS.
Types of safety control unit:
There are two types of the safety control unit. The standard type safety control unit (Ambient
Temperature: -20 to 50 deg.C) and wide range temperature type safety control unit (Ambient
Temperature: -20 to 70 degc).
Safety Control Units (for V net)
Standard Type Safety Control Unit (Model: SSC10S-S)
Wide Range Temperature Type Safety Control Unit (Model: SSC10S-F)
Duplexed Standard Type Safety Control Unit (Model: SSC10D-S)
Duplexed Wide Range Temperature Type Safety Control Unit (Model: SSC10D-F)
TE Y109JA01E-PPRS
17
Safety Control Units (for Vnet/IP)
Standard Type Safety Control Unit for Vnet/IP (Model: SSC50S-S)
Wide Range Temperature Type Safety Control Unit for Vnet/IP (Model: SSC50S-F)
Duplexed Standard Type Safety Control Unit for Vnet/IP (Model: SSC50D-S)
Duplexed Wide Range Temperature Type Safety Control Unit for Vnet/IP (Model:SSC50D-F)
2.4 Configuration of Safety Control Unit
2.4.1 Standard Type Safety Control Unit
The components of the standard type safety control unit are illustrated in the figure below.
In this figure, the control unit is a dual-redundantly configured unit. The power supply modules are
always paired for redundancy. For a non-redundant configuration, a single processor module will be
installed to the left-hand side slot. The slot at the right-hand side will be covered using a dummy cover. If
the safety nodes are used, the ESB bus coupler modules will be installed in a redundant configuration
Table containing the components of Standard Type Safety Control Unit
*1: For non-redundant configuration, to cover the slot at right-hand side of the single processor module.
*2: To cover the empty I/O module slot.
*3: Required if the safety nodes are used.
TE Y109JA01E-PPRS
18
2.4.2 Wide Range Temperature Type Safety Control Unit
The components of the Wide Range Temperature Type safety control unit are illustrated in the figure
below. This type of control unit consists of the standard type control unit and cooling fan unit so as to
work in a wider range of ambient environment (-20 to 70 deg. C).
Table
containing
the
components
Wide
Range
Temperature
2.4.3 Components of safety control unit SSC10D (for V net)
Power supply module (100-120 V AC): SPW481
Power supply module (220-240 V AC) :SPW482
Power supply module (24 V DC): SPW484
TE Y109JA01E-PPRS
Type
Safety
Control
Unit
19
Processor module SCP401
Dummy cover (for processor module): T9083VB
Dummy cover (for I/O module): SDCV01
ESB bus coupler module :SEC401
V net coupler unit :AIP504
External interface unit (for standard type safety control unit) :S9158FA
GPS interface unit (option): S9161FA
2.4.4 Components of safety control unit SSC50D (for Vnet/IP)
Power supply module (100-120 V AC)
SPW481 Power supply module (220-240 V AC) SPW482
Power supply module (24 V DC) SPW484
Processor module SCP451
Dummy cover (for I/O module) SDCV01
ESB bus coupler module SEC401 2ps
External interface unit (for standard type safety control unit) S9158FA 1ps
2.4.5 Processor module
Control algorithm calculations are performed in the processor modules.
Two types of processor modules are available: one for V net (Model: SCP401) and the other for
Vnet/IP (Model: SCP451).
2.4.6 Battery
In order to protect the processor module management information (in the storage memory) during
power failure, the Li batteries are used. Since the application program information is stored in the
non-volatile memories, thus battery backup is not required.
Battery Back-up Specifications
Battery life Changes according to the ambient temperature.
Three years if the average ambient temperature is 30 deg. C or less
One year and a half if the average ambient temperature is 40 deg. C or less
Nine months if the average ambient temperature is 50 deg. C or less
TE Y109JA01E-PPRS
20
2.4.7 LED display on processor module
HRDY:
The processor module performs self diagnosis. If the processor module hardware is functioning
normally, the green light turns on. If abnormality is found, the light turns off.
RDY:
The green light turns on if both the hardware and software are functioning normally. If either of them
is abnormal, the light turns off.
CTRL:
The green light turns on if the processor module is performing control. If the processor module is
standby, the light turns off. During the startup phase, the processor module installed at the righthand side performs control.
COPY:
In the dual-redundant type safety control unit, the green light turns on when program copy is
executed and turns off when program copy is completed. When a processor
module has been replaced or when the unit is stopped and then started again, the standby-side
processor module automatically copies the program of the control-side processor module. When
copy is completed, the light turns off. In the basic (single) safety control unit, the light is always off.
RCV:
Indicates the control bus communication status. 1 stands for control bus bus1 while 2 stands for
control bus bus2. When receiving communication frames, the lamp flashes in green, otherwise the
lamp is off.
SND:
Indicates the control bus communication status. 1 stands for control bus bus1 while 2 stands for
control bus bus2. When sending communication frames, the lamp flashes in green, otherwise the
lamp is off.
SYNC:
If the module is synchronizing with V net clock or IRIG-B clock, this lamp turns on green. Otherwise
it turns off. If the module is synchronizing with Vnet/IP clock, this lamp turns on green. Otherwise it
turns off.
SCTY:
The green light turns on when the security level of the SCS is online-level. If the security level of the
SCS is offline-level, the light turns off.
TE Y109JA01E-PPRS
21
2.4.8 Setting switches on processor module
START/STOP:
This maintenance switch is used for forcing the processor module CPU stop or restart. If this switch
is pressed when the processor module is still operating, the CPU will stop. If this switch is pressed
when the processor module is not operating, the CPU will restart. This switch is located inside a hole
next to the START/STOP sign. Push the switch using a non conductive slender bar of around 1 to 2
mm diameter.
Battery ON/OFF switch:
When this switch is on, battery backup is activated for protecting the processor module
management information (in the storage memory) during power failure.
ON: Enables the backup. Select this position during normal operation.
OFF: Disables the backup.
Front setting switch (6-bit DIP switch):
PORT: Port for maintenance (In usual operations, set to 0 position).
DOMN: Indicates the control bus domain number on SATUS LED when this bit is set to
1position. (In usual operations, set to 0 position).
STA: Indicates the control bus station number on SATUS LED when this bit is set to
1position. (In usual operations, set to 0 position).
ON : Force
OFF: Auto
2.4.9 ESB Bus Coupler Module
ESB bus coupler module (Model: SEC401) is installed in the safety control unit for communicating with
the ESB bus interface module (Model: SSB401) installed in the safety node unit.
The ESB bus coupler module are always dual-redundantly configured.
TE Y109JA01E-PPRS
22
2.4.10 V net Coupler Unit
The V net coupler unit is installed in the safety control unit and located between the processor module
and the V net cable so as to perform the signal isolation and signal level conversion.
2.5 Configuration of a Safety Node unit
The components of the safety node unit (Model : SNB10D) are illustrated in the figure below. The power
supply modules and ESB bus interface modules are always dual-redundantly configured.
Power supply module (100-120 V AC) SPW481
Power supply module (220-240 V AC) SPW482
Power supply module (24 V DC) SPW484
ESB bus interface module SSB401
Dummy cover (for I/O module) SDCV01 as required
Power supply
module
ESB bus interface
module
2.5.1 Input and Output Modules
The ProSafe-RS input and output modules include the following types:
Analog Input/Output Modules
Digital Input/Output Modules
Communication Modules
TE Y109JA01E-PPRS
23
2.5.1.1 Analog input modules
Analog input modules are used to read analog signal inputs and convert signals.
External View of Analog Input Module
The connections with the analog input modules vary with the types of adapters. Pressure clamp
terminals, terminal boards (with signal cable adapters) and MIL cables are used for the connections.
The ProSafe-RS analog input modules consist of the following types:
SAI143: 4 to 20 mA input, 16 Channels, Isolated.
SAV144: 1 to 5V DC/1 to 10V DC input, 16 Channels, Isolated.
SAI533 : 4 to 20 mA output, 8 Channels, Isolated.
Setup Elements
In the case of current input module, it can be set for each type of transmitter whether or not power is
supplied using the setting pins.
Setting of SAI143
The jumper and pin set of S1 to S16 can be used for setting the power supply to the field devices. The
jumper and pin set can be found on the right side of the SAI143 current input module. On factory
delivery, power supply with two-wire is the default setting for all the channels.
2.5.1.2 Digital Input/Output Modules
The input digital signals are converted into the internal data in the safety control unit and then the
converted data are output.
TE Y109JA01E-PPRS
24
External View of Digital Input/Output Module
The connections with the digital input modules vary with the types of adapters. Pressure clamp
terminals, terminal boards (with signal cable adapters) and MIL cables are used for the connections.
The ProSafe-RS digital input modules consist of the following types:
SDV144 : Non-voltage contact input, 16 Channels, Isolated
SDV531 : 24V DC output, 16 Channels, Isolated
SDV521 : 24 V DC output, 4 Channels, Isolated
SDV531-L : 24 V DC output, 8 Channels, long distance type.
SDV541 : 24 V DC output, 16 Channels, Isolated
2.5.1.3 Communication Modules
The communication module is used for linking the safety control station with external devices through
the communication lines as well as converting the communication data.
External View of Communication Module
The following types of communication modules are available.
ALR111 : RS-232C communication module
ALR121 : RS-422/RS-485 communication module
TE Y109JA01E-PPRS
25
2.5.1.4 Accessories Related to Input/Output Modules
The following accessories related to I/O modules are available:
Pressure clamp terminal blocks
Signal cable adapters
Terminal boards
Wiring Check Adapter for Digital Input
Relay boards
Pressure Clamp Terminal Blocks:
The pressure clamp terminal block is used for wiring the field devices directly to the I/O module. The
block can be used for either redundant or non-redundant wiring scheme.
Types of Pressure Clamp Terminal Blocks:
The following types of pressure clamp terminal blocks are available according to the purpose.
Signal Cable Interface Adapters:
The adapters used for linking the signal cables very with the types of I/O modules.
The signal cable adapters are used together with the terminal boards.
TE Y109JA01E-PPRS
26
Types of Signal Cable Interface Adapters:
The following models of signal cable adapters are available.
Terminal Boards:
The terminal boards are used to connect the field devices for passing the signals. The terminal boards
are used together with the signal cable adapters.
Types of Terminal Boards
Terminal boards are classified into the following types, depending on the number of input/output
channels, whether or not they are isolated, etc. Each type supports both single and dual-redundant
operation.
Wiring Check Adapter for Digital Input:
The wiring check adapter for digital input is a device for inspecting the wiring conditions between the
digital input module and the field device so as to find out the short circuit and breakage problems.
Types of Wiring Check Adapter
The following two models of wiring check adapters are available.
SCB100 : For testing OFF input loop breakage
Putting this tester in parallel with the sensor switch, the breakage of the loop for the OFF signal can be
found.
SCB110 : For testing ON input loop short circuit
Putting this tester in series with the sensor switch, the short circuit of the loop for the ON signal with the
power line can be found. The short circuit with other signals channels can also be found. When testing
the breakage or short circuits, other than using the wiring check adapters, other diagnostic features of
the input modules should also be activated.
Relay Boards:
The relay board amplifies the signals from the digital output module and outputs the amplified signals to
field devices.
TE Y109JA01E-PPRS
27
Types of Relay Boards
The following models types of relay board are available with different numbers of contact outputs
SRM53D : 8x2 dry contact outputs (M4 terminals)
SRM54D : 16x1 dry contact outputs (M4 terminals)
2.6 Addressing
2.6.1 Setting the Domain Number
A domain stands for a range of stations connected by a single train of the V net/Vnet IP. Set the domain
number to a value from 1 to 31.
To set a domain number, set the dip switches as follows. Bits 2 and 3 must always be zeros (0s).
2.6.2 Setting the Station Number
Set the station number to a value from 1 to 64. To set a station number, set the dip switches as follows.
2.6.3 Setting Node Addresses
The node addresses on the ESB bus are set using the node address setting switch. Node numbers on
the safety node unit must be designated in the range from 2 to 10. Node number 1 is reserved for the
safety control unit. It is possible to match the required node numbers by setting the DIP switches as
shown below.
TE Y109JA01E-PPRS
28
2.7 Redundancy
ProSafe-RS supports dual-redundant configurations of SCS CPU modules and input/output modules.
With the dual-redundant configuration, the continuous controllability and operating efficiency can be
improved. Moreover, with dual-redundantly configured hardware, the continuity of plant safety
monitoring will be guaranteed by swapping the control rights when an error occurs in the SCS
hardware.
2.7.1 CPU Module
The CPU module on the standby side performs the same control processing as the control side even
while it is in the standby status. For this reason, it is possible to take over outputting data immediately
after the control right is switched. Moreover, the operating mode of the SCS does not change.
Only the CPU on the control side accesses the hardware composing the SCS and the CPU on the
standby side always sets the equivalent value as the processing result. Therefore, the CPU modules on
both sides always perform processing using the same data.
In redundant configuration, if the CPU module on the standby side is not in the STBY status and the
control right cannot be switched, the same operation as single configuration CPU module is performed.
SOE data related to discrete inputs may be lost when the control right is switched between the CPU
modules.
2.7.2 Input/Output Modules
In an SCS, it is possible to mount input/output modules of the same type in two adjacent slots (*1) to
make them redundant. In the case of redundant configuration, one side becomes the control side and
the other becomes the standby side. Switching of the control right is performed by input/output
modules. The switching has no influence on the application logic.
It is not allowed to have redundant configuration across two nodes.
SOE data related to discrete inputs may be lost when the control right is switched between the input
modules even though the frequency is low
TE Y109JA01E-PPRS
29
2.7.3 V Net Communication
The SCS V net communication is redundant. The communication couplers are also redundant. The CPU
has a communication interface that supports the redundant V net. In redundant configuration, an SCS
performs communication while switching the bus to be used at regular intervals.
2.7.4 Power Supply Module
Redundant power supply modules are mounted on both the CPU nodes and I/O nodes of an SCS. The
SCS monitors the power supply status at regular intervals and, if an error occurs, it notifies the fact to
the user via the Status Display window of the SENG and HIS as well as through a diagnostic information
message.
2.7.5 ESB Bus and SSB401
The ESB bus is redundant. An SSB401 is connected to the two ESB buses, respectively.
Normally, redundant ESB buses are used in an alternating fashion.
If an error occurs in an SSB401 on one side, the error is notified to the user via a diagnostic
information message. If both modules fail, the error is treated as a node failure.
If an error occurs in one bus or SSB401, the SCS continues communication using only the normal ESB
bus on the other side.
An erroneous bus is monitored for normal recovery at regular intervals.
All errors in communication with any I/O node, except for CPU nodes, are judged to be
errors.
ESB bus
2.7.5 SB Bus
The SB bus is a backboard bus that connects the SSB401 and each input/output module. The SB buses
are redundant. Since each bus is connected to one SSB401 in a one-to-one fashion, the SB bus is
switched whenever an SSB401 is switched.
If an error occurs in one SB bus, the error is notified to the user via a diagnostic information message.
If both buses fail, the error is treated as a node failure.
In the case of one-side failure of an SB bus, only the ESB bus connected to the normal SB bus is
used.
TE Y109JA01E-PPRS
30
03. INTRODUCTION TO WORKBENCH
TE Y109JA01E-PPRS
31
Table of contents
Page Number
3.1 Introduction
32
3.2 Main Screens of workbench
32
3.2.1
Link Architecture
32
3.2.2
Hardware architecture
35
3.2.3
Dictionary
36
3.2.3.1 Variable Tree
37
3.2.3.2 Parameter Tree
38
3.2.3.3 Types Tree
38
3.2.3.4 Defined words Tree
39
3.2.4
I/O wiring
40
3.2.5
I/O Parameter Builder Setting
41
TE Y109JA01E-PPRS
32
3.1 Introduction
Prosafe-RS Workbench is the software program used to configure the Prosafe-RS system.
The workbench also provides the user with the ability to:
Transfer configuration to PLC
Edit a project.
View and update variables.
Perform system troubleshooting.
Produce documentation for a configuration.
Two languages are available for configuring the Prosafe-RS system.
Function Block Diagrams.
Ladder Diagrams.
Structured Text Language
Launching the work bench
To launch workbench software, click on start->Program-> Yokogawa Prosafe->Workbench.
3.2 Main screens of workbench
3.2.1
Link architecture Window
When a new or existing project is opened, the main window of workbench will appear. This window is
called Link Architecture window.
Creation, deletion and copying of POUs are performed in Link Architecture View of SCS Manager. Click
the Link Architecture View button on the toolbar of SCS Manager.
TE Y109JA01E-PPRS
33
Link Architecture window can be used to, Rename the resource.
The resource name is same as the project name.
Link Architecture window can also be used to, Edit SCS Resource properties.
Right click the resource on Link Architecture View and then choose [Properties] from the pop-up menu
so as to display the Resource Properties dialog box. The resource number can be defined on the
General tab.
Specify SCSddss for the resource name and ddss (dd: domain number, ss: station name) for the
resource number.
The link architecture view graphically displays the resources of a Project and the resource data links
between them. This is the default view of the Workbench providing a main entry point to all editors. In
the link architecture view, you manage many aspects of a project
defining variable groups
creating and manipulating POUs (Program Organization Units)
setting up I/O wiring
Resource Window Workspace
The Workspace displays a graphical representation of the various components of each resource.
Parameters
Variable Groups
Programs
TE Y109JA01E-PPRS
34
Functions
Function Blocks
To expand / collapse any branch of the hierarchy
Editing Resource Properties
You need to define several properties at the resource level, intimately linked to targets (and their
implementation). These properties determine the behavior of the programs and hardware, e.g., the type
of code generated, the timing, and Hardware specific properties. These properties are:
Resource Identification
Compilation Options
Run-time Settings
Resource Network Parameters
Variable Bindings
Bindings are directional links, i.e., access paths, between variables located in different resources. One
variable is referred to as the producing variable and the other as the consuming variable. The value
stored in the producing variable is transferred to the consuming variable. The Workbench enables two
types of bindings: internal bindings and external bindings. Internal bindings are between resources
within the same project. External bindings are between resources belonging to different projects.
Variable Groups
Variables Groups provide a method of managing variables and logically sorting them within a resource.
The variable groups are shown in the Variables Tree, their contents are defined within the Dictionary
Variables grid. You can perform tasks to manage variable groups:
Creating Variable Groups
Opening Variable Groups
POUs (Program Organization Units)
A POU (Program Organization Unit) is a set of instructions written in one of the following languages: ST,
FBD, and LD. POUs can be programs, functions, or function blocks.
You can perform many tasks when managing POUs:
Creating POUs
Manipulating POUs
You can create, i.e., add, POUs (programs, functions, and function blocks) in resources while in the link
architecture view. You add POUs using the main menu or a contextual menu accessed by right-clicking
the respective component (Program, Function, or Function Block) within a resource. After having
created a POU, you can drag and drop it to a new position in its section, to another section, or to
TE Y109JA01E-PPRS
35
another resource. POUs belonging to a same section must have different names. POU names must
begin with a letter.
Controlling Access to POUs
You can control access to user-defined POUs using a password. When you set a project with the readonly access control, the resources and POUs making up the project are also set to the read-only mode
except for those having individual access control. For instance, a POU having its own password remains
locked and cannot be viewed without entering its password. When moving or copying a POU using its
resources password, the POU retains this password.
The security state of a POU is indicated by its icon in the resource:
POU
Icon
Security
State
Yellow. The POU has no access control. All users have read and write access in the POU. In the
dictionary view, local variables and parameters are visible and editable.
Red. The POU is locked. Users not having the POU password cannot access the POU; these users
do not have read or write capabilities. In the dictionary view, local variables and parameters are
visible but not editable.
Cyan. The POU is in read-only mode. Users not having the resource password can view the POU;
these users do not have write capabilities. The read-only mode for the POU is inherited from the
resource to which it belongs. In the dictionary view, local variables and parameters are visible
but not editable.
Green. The POU is unlocked. User can access the POU; this user has read and writes
capabilities. In the dictionary view, local variables and parameters are visible and editable.
3.2.2 Hardware architecture
Hardware architecture window is used to,
Rename the configuration.
The configuration is same as the project name.
Right click the resource on
Hardware Architecture
View and then choose
rename configuration from
the pop-up menu so as to
display the Rename
configuration dialog box
TE Y109JA01E-PPRS
36
To set the IP address:
The IP address can be defined on Hardware Architecture View. Double click Connection so as to
display Connection - Properties dialog box. The IP address needs to be set for Value item.
In general the IP address should be 172.16.dd.ss (dd: domain number, ss: station number).
Double click
on this
connection to
enter network
parameters
3.2.3 Dictionary View
Dictionary is an editing tool using tree views and grids for the declaration of the variables, functions,
function block parameters, user types and defined words of the project.
TE Y109JA01E-PPRS
37
Click on this Icon to
enter dictionary
The various components are sorted in a tree-like hierarchy, e.g., by resource or by Type. The Tree name
is displayed on the window title bar.
The four dictionary tree views are:
Variables Tree
Parameters Tree.
Types Tree
Defined Words Tree
3.2.3.1 Variable Tree
Under the Variable tree in Dictionary it is possible to define variables in to variable groups.
Local Variables:
Variables those are unique within a POU.
Global Variables:
Variables those are unique within a resource.
Physical IO Variables:
Physical IO signal that are unique within a resource.
Producer/Consumer Variable groups:
To perform the Inter- SCS communication.
*Variables must confirm to the following rules:
Names cannot exceed 16 characters.
TE Y109JA01E-PPRS
38
The first character must be a letter.
Subsequent characters can be letters, digits or the underscore character.
Global variable names may not be duplicated within a resource.
3.2.3.2 Parameter tree
The Parameters grid defines the interface of the functions and function blocks created in the project
resources.
Display of the Parameter Tree in dictionary:
Tab in the dictionary
to enter Parameter Grid
Grid displays the
parameters of the functions
Grid displays the
Parameters of function blocks
3.2.3.3 Types Tree
This Grid is available only for viewing not for defining new types.
Display of the Types Tree in dictionary
TE Y109JA01E-PPRS
39
Tab to enter types grid
3.2.3.4 Defined words Tree
The defined word grid is used to create terms which are clearer to the user in Ladder logic or in FBD.
The term Switched_off is more meaningful than true.
The parameters in defined words tree:
Word:
Name consisting up to 16 alphabetical characters, starting with an alphabetic character.
Equivalent:
Alias name up to 16 alphanumerical characters.
Comment:
Used for more detailed information.
Display of defined words grid in dictionary.
TE Y109JA01E-PPRS
40
Tab to enter defined
words grid in Dictionary
3.2.4 I/O Wiring
I/O wiring enables you to define links between the variables defined in a project and the channels of the
devices existing on the target system. Wiring is performed at the resource level; therefore, I/O wiring is
only available when a resource is selected in either the link architecture or hardware architecture
views.
I/O wiring icon in
Link Architecture
I/O wiring option in Project
TE Y109JA01E-PPRS
41
Appearance
The I/O Wiring view is displayed in the workspace. The menus and toolbar now reflect I/O Wiring options
only.
The left of the I/O Wiring Workspace is a hierarchical 'Tree View' of defined I/O modules. The right side
of the workspace displays a grid-like table of the free (unwired) variables of the current resource. These
unwired variables are listed in alphabetical order. A Splitter is available to change the proportion of the
width of the Tree and grid windows.
3.2.5 I/O parameter builder setting.
I/O Parameter builder can be selected from Link architecture window by going to Tools->Engineering>I/O Parameter builder.
After an I/O card has been defined and the variables have been connected to the physical I/O, this
builder is used to set the various parameters related to this I/O point. The information differs for every
I/O card.
TE Y109JA01E-PPRS
42
4. ENGINEERING IN PROSAFE-RS
TE Y109JA01E-PPRS
43
Table of contents
Page Number
4.1
Procedure for Engineering
44
4.2
Classification of SCS Application
45
4.3
Restriction on System configuration
46
4.4
Restrictions on Installation of Hardware
47
4.5
Capacity of SCS Applications
48
4.6
Performance and Scan Period in SCS
49
4.7
Time Synchronization
50
4.8
Project Creation
51
4.9
Creation of Variables in Dictionary
54
4.9.1 Creation of Variable groups
54
4.9.2 Creation of Analog I/O variables in dictionary
55
4.9.3 Creation of Digital I/O variables in dictionary
56
4.9.4 Creation of internal variable in dictionary
57
4.10 Creation of I/O cards in I/O wiring view
TE Y109JA01E-PPRS
57
44
4.1 Procedure for Engineering
Prosafe-RS is the Safety Instrumented System (SIS) comprising Safety Control Station (SCS) and Safety
Engineering PC (SENG). Prosafe-RS and CENTUM CS 3000/CENTUM VP which is a Distributed Control
System made by Yokogawa, can be integrated.
The regular procedure for engineering from designs to start of operation including manufacturing,
inspecting and commissioning is shown as follows.
1. In Basic Design, the following items are decided based on users requirements and specifications.
The making of safety specification
System configuration and hardware
The number of I/Os
Safety level (SIL) of loop
Signal interface with another system
TE Y109JA01E-PPRS
45
The following documents are made as a result of these works.
Diagrams of the system structure
Hardware specifications
I/O lists
System basic design document
List of interface with other systems
2. Based on the users requirements and specification, functional specifications are
logic like shutdown logic is included in the functional specifications.
made. Detailed
3. ProSafe-RS projects and applications are created on a PC installing the SENG Function.
4. Functions of the created application are checked. After making a document about the
Specification, usually testing of functions is conducted in the following order.
Test
1) Desk test
The created applications are checked with self documents on the desk.
2) Unit test-1
Created application logics are verified. SCS simulation and Logic simulation test on SENG can be
used for this verification.
3) Unit test-2
In the target test using SCS, the overall logic etc. are verified.
4) Integration test
The integrated final test is conducted on the SCS target. Before the test, it is required
to provide
an environment, where SCS can be used, in combination with panel, console, a host computer and
other subsystems. The testing for system failure such as hardware failure is also conducted.
5. Hardware and software Factory Acceptance Test (FAT) is conducted in the presence of users.
6. Hardware and software which the user has confirmed in FAT are delivered.
7. Hardware and software which are installed in the plant are adjusted.
8. The Site Acceptance Test (SAT) is conducted to hand over the system to the user.
4.2 Classification of SCS Application
Below are the applications that are running on a SCS.
Safety Application
This is an application which executes safety functions. The safety application includes application logic
written in the language conforming to the IEC 61131-3 standards.
The following programming languages defined in IEC 61131-3 are available for SCS.
- Function Block Diagram (FBD)
- Ladder Diagram (LD)
- Structured Text (ST)
TE Y109JA01E-PPRS
46
CS 3000 Integration Application
This is an application for exchanging data with CS 3000, which is needed for the CS 3000 Integration
Structure.
Modbus Slave Communication Application
This is an application for exchanging data with other systems connected via Modbus.
4.3 Restriction on System configuration
Number of Stations
The maximum number of connectable stations within one system is shown below whether it is the
ProSafe-RS Basic Configuration or CS 3000 Integration Configuration. The systems can be extended up
to the following numbers.
Domains that can be connected: 16
Stations that can be connected in a domain: 64
Stations that can be connected: 256
Hierarchy: three-level hierarchy. The range where up to 2 BCV and 2 CGW (two pairs of CGWs) can be
used to relay is communicable for Inter-SCS communication. For CS 3000 HIS, the limit is 16
stations/domain at maximum. When using multiple domains, BCV, CGW, V net Routers and CS 3000 ENG
function are required.
Number of SENG
One SENG at least is required.
TE Y109JA01E-PPRS
47
Number of SCS
The number of stations should be within the limit. Connect Vnet/IP domains on each Bus with a Layer 3
switch (L3SW). This also requires the CS 3000/Centum VP ENG function.
Vnet/IP Domains Connection Specifications
Number of connectable domains: 16 (Total of Vnet/IP domains and V net domains)
Number of Layer 3 switches (L3SW) allowed: 15 levels
Connection Specifications in a Vnet/IP Domain
Number of connectable Vnet/IP stations: Max. 64 (Vnet/IP stations including V net
routers)
General-purpose Ethernet communication devices: Max. 124 (PCs, Routers, etc.)
Distance between stations in a Vnet/IP domain: Max. 40 km
Distance between Layer 2 switch and a station: Max. 100 m (for Unshielded Twisted Pair (UTP)); Max. 5
km (for fiber-optic cable)
Distance between Layer 2 switches: Max. 5 km (for fiber-optic cable)
Number of connectable Layer 2 switches in a domain: Max. 7 per each Bus. (Multilayer by cascade
connection allowed)
4.4 Restrictions on Installation of Hardware
There are the following restrictions on installation of hardware in SCS.
SCS can connect the CPU node to up to 9 I/O nodes.
When expanding I/O, SEC401s are installed to slots 7 and 8 of the CPU node. In the absence of
expandable I.O nodes, I/O modules can be installed to these slots.
When configuring I/O modules in redundant configuration, install them to any of the following slots in
pairs: 1 and 2, 3 and 4, 5 and 6, 7 and 8
For installation of I/O modules, there are two more limitations other than the above restrictions. One is
imposed by electric capacity and another is imposed by ambient temperature conditions (60C~70C)
for operation.
The Optical ESB Bus Repeater modules must be mounted within the specified operating temperature
range.
Up to four serial communication modules (ALR111 and ALR121) per SCS can be installed (two pairs in
redundant configuration) as subsystem communication master modules and up to two modules can be
installed as Modbus slave communication modules. Note that it is not allowed to perform both
subsystem communication and Modbus slave communication using the same serial communication
module.
TE Y109JA01E-PPRS
48
With SCS-IP, you cannot install the serial communication modules for Modbus slave communication
(that is, ALR111 and ALR121) to I/O nodes that are located further than 5 km, using the an optical ESB
bus repeater module.
Operating temperature is different between Safety Control unit for Vnet/IP and Safety Control unit for V
net.
4.5 Capacity of SCS Applications
TE Y109JA01E-PPRS
49
4.6 Performance and Scan Period in SCS
Processing Timing and Scan Period
The periodic processing for SCS falls into two types. : Application Logic Execution Function and
External Communication Function. They are executed at an individual scan period.
Application Logic Execution Function
This is the function for monitoring the safety status of a plant and performing operations specified
against a fault if it occurs. Main operations are as follows.
Input of process data from the field device
Execution of the application logic
Output of process data to the field device
Inter-SCS Safety Communication
SCS Link Transmission
Communication Data I/O (subsystem communication function)
Communication with SENG
Diagnosis
The Application Logic Execution Function has top priority among SCS functions. The External
Communication Function is executed in a part where the Application Logic Execution Function is not
executed in the CPU processing period. If the External Communication Function finishes its processing
before a scan period, the remaining time becomes the idle time on CPU.
Processing of Application Logic Execution Function
The Application Logic Execution Function is executed in the order presented as follows.
TE Y109JA01E-PPRS
50
Processing of External Communication Function
The External Communication Function is a general name for functions used for communicating the
information of SCS with external systems. CS 3000 Integration Function and Modbus Slave
Communication Function are included in this.
4.7 Time Synchronization
SCS is capable of synchronizing the time between SCSs and DI modules to make the event log accurate.
This section describes the time synchronization function on ProSafe-RS.
SCS Type and Time Synchronization
SCS for V net (also called SCS-V) synchronizes with different time synchronization methods from SCS
for Vnet/IP (also called SCS-IP).
SCS-V: V net time synchronization or IRIG-B time synchronization is selectable.
SCS-IP: Vnet/IP time synchronization is the only option.
TE Y109JA01E-PPRS
51
4.8 Project Creation
It is possible to create new RS projects in addition to the RS project created at the installation. In this
case, use file option in workbench to create a new project.
Once the workbench is launched click on file-> New Project/Library
Projects can function as library
in other projects.
Often called typicals.
If the new project has to be created the following information has to be added:
Name of the project.
Destination folder for the project.
Project comment (Optional).
Project template.
*The path of the folder must not be longer than 256 characters and should not include spaces
After the New Project/Library NEW Dialog box appears following information mode.
Folder names must not include
spaces.
The name must start
with SCS (Capitals).
The Number is the
dd.ss number i.e.
domain
number.
station number
TE Y109JA01E-PPRS
52
If this project will be included
into other
project then
select SCS library
After creation of a new project, the properties of a SCS project will be displayed. Select the suitable
Station type.
Set
the
proper
domain and station
number
IP address can
be
changed
later
The IP address is an option which is found in Hardware Architecture
Use link Architecture window to, Rename the resource.
The resource name is same as the project name.
TE Y109JA01E-PPRS
53
Right click the resource
on Link Architecture View
and then choose rename
resources from the popup menu so as to display
the Rename resource
dialog box.
Rename the configuration using hardware architecture.
Right click the resource on
Hardware Architecture View
and then choose rename
configuration from the popup menu so as to display the
Rename
configuration
dialog box.
Set the IP address using Hardware architecture
The IP address can be defined on Hardware Architecture View. Double click Connection so as to
display Connection - Properties dialog box. The IP address needs to be set for Value item.
In general the IP address should be 172.16.dd.ss (dd: domain number, ss: station number).
TE Y109JA01E-PPRS
54
In this case the IP address is
172.16.1.2
Double click
on this
connection to
enter network
parameters
4.9 Creation of variables in dictionary
4.9.1 Creation of variable groups
Right click on Variable groups in link
architecture to create new variable group
Variable groups are
Created in Link Architecture
TE Y109JA01E-PPRS
55
One can enter the dictionary by clicking on the variable groups created in link architecture
Variable groups created in Link
Architecture can be seen in
Dictionary.
4.9.2 Creation of Analog I/O variables in dictionary
Double click on the first row in dictionary .Enter the parameters.
TE Y109JA01E-PPRS
56
4.9.3 Creation of Digital I/O variables in dictionary.
Double click on the variable group DIGITALIP, to create Digital input variables. The data type
for a digital input is IO_BOOL. The attribute for the digital input is read and the direction is
Input
Double click on the variable group DIGITALOP, to create Digital output variable. The data type
for a digital output is IO_BOOL. The attribute for the digital output is write and the direction is
output
TE Y109JA01E-PPRS
57
4.9.4 Creation of internal variables in dictionary
Double click on the variable group INTERNAL, to create INTERNAL variable. The attribute for
the internal variable is free and the direction is Internal.
4.10 Creation of I/O cards in I/O wiring view.
After creating variables in the Dictionary, perform I/O wiring in the I/O wiring tool by adding I/O devices,
setting device parameters, then wiring the channel of the devices to variables in the grid. We can also
define the mapping of logical channels to physical channels.
Go to I/O wiring option either by clicking I/O wiring icon on SCS Manager or by project menu.
TE Y109JA01E-PPRS
58
I/O wiring icon in
Link Architecture
I/O wiring option in Project
In the I/O wiring view click on add device Icon to create new device (I/O card).
Add device
icon in I/O
wiring view
Select the I/O
card from the
list
A new card is added in
the list
TE Y109JA01E-PPRS
59
Set the node number and Slot number in Parameter. Assign the unwired Variable to the free channel.
Double Click on
Parameters to enter
the parameters of the
device
TE Y109JA01E-PPRS
Drag and drop the unwired
variable to the free
channel
60
5. SECURITY
TE Y109JA01E-PPRS
61
Table of contents
5.1 Overview of ProSafe-RS Security
Page Numbers
62
5.1.1 Online Level
62
5.1.2 Offline Level
62
5.2 Security of SCS
63
5.2.1 Procedure to change the Password
63
5.2.2 Changing the security level
64
5.3 Security of SCS Maintenance Support Tool
65
5.4 Security of SCS Database
66
5.4.1 Setting Password for the SCS Project
66
5.4.2 Setting Password for Each POU
67
TE Y109JA01E-PPRS
62
5.1 Overview of ProSafe-RS Security
ProSafe-RS has functions to prevent access to the system by the unauthorized users and devices, and
inadvertent changes caused by operation mistakes of users. This chapter mainly describes how to use
passwords to ensure security
There are two types of security level for an SCS: online level, which is used during normal operation of
the SCS, and offline level, which is used when the SCS is not running.
Offline download or SCS restart
Online levels
Level2
Level0
Level1
Level1 Password
check
Level0
Password
check
Level 0 Password check
5.1.1 Online Level
The online level is the security level used when the SCS is performing normal operation. Online level is
further classified into two security levels.
5.1.2 Offline Level
The offline level is used when the SCS is not performing the normal operation.In this situation the SCS
will be in security level 0.
Security Level
Security Level 2
Meaning
This is the highest security level. SCS performs
normal operation
Security Level 1
Temporarily used security level. Used
maintenance and online logic modification.
Security level0
Lowest security level. At this level One can
access to the SCS database.
TE Y109JA01E-PPRS
during
have
63
5.2 Security of SCS
The password used to change SCS security level is stored within the SCS. This password can be set or
changed from the Set SCS Security Level dialog box.
5.2.1 Procedure to change the Password
Select [Maintenance] from the [Tools] menu of SCS Manager. The Maintenance Launcher menu
appears.
Select [Set SCS Security Level] from the Maintenance Launcher menu. The Set SCS Security
Level dialog box appears.
Click [Change Password] button. The Change SCS Security Level Password dialog box appears.
Select the security level for which you wish to set the password. It is necessary to set seperate
password for each level.
Enter the current password in [Old Password:] text box, and a new password in [New Password:]
and [Confirm New Password:] text boxes. All characters you enter are displayed as asterisks (*).
For a password, up to 16 alphanumeric characters and ASCII symbols (*1) can be used. It is not
necessary to enter the current password if no password has been set before, or after executing
off-line download or master database off-line download.
TE Y109JA01E-PPRS
64
Click [OK] button. The confirmation dialog box appears.
Click [OK] button. Both new and old passwords will be sent to SCS. If the password is
successfully changed, the dialog box notifying the success appears. The new password
becomes valid. If the password change fails, a dialog box will be displayed to notify the failure.
5.2.2 Changing the Security level
Open an SCS project in SCS Manager to change the security level of the corresponding SCS.
Select [Maintenance] from the [Tools] menu of SCS Manager.The Maintenance Launcher menu
appears.
Select [Set SCS Security Level] from the Maintenance Launcher menu. The Set SCS Security
Level dialog box appears. The current security level is displayed in [Current Level:]; this item is
for display only and cannot be changed.
Select the security level of your choice in [New Level:] and enter the password for the level you
want in [Password:] text box. All characters you enter are displayed as asterisks (*). The table
below lists the combinations of levels to which the security level changes are allowed.
It is not necessary to enter a password when changing the security level from Level 1 to Level 2.
TE Y109JA01E-PPRS
65
Click [OK] button. The confirmation dialog box appears.
Click [OK] button. If the security level of SCS is changed, the message showing the result of
change is displayed. The error message is displayed if the security level could not be changed.
When changing the security level to Level 0, the following confirmation dialog box appears to
confirm the change again.
Click [OK] button. The SCS security level is changed.
5.3 Security of SCS Maintenance Support Tool
SCS Maintenance Support Tool has a security. This section describes how to set the password to the
SCS Maintenance Support Tool.
The Change Maintenance Support Password dialog box is used to specify or change the password. The
user must enter the right password when starting SCS Maintenance Support Tool. To use SCS
Maintenance Support Tool, make sure to set the password first.
Open the window related to SCS Maintenance Support Tool from SCS Manager or [Start] menu
of Windows. When the window requiring a password is opened, the Input Maintenance Support
Password dialog box appears.
TE Y109JA01E-PPRS
66
Click [Change Password] button. The Change Maintenance Support Password dialog box
appears.
Enter the passwords before and after change. All characters you enter are displayed as
asterisks (*). For the password, up to 16 alphanumeric characters and ASCII symbols (*1) can be
used. Password is case sensitive.
Click [OK] button. The password is set.
5.4 Security of SCS Database
5.4.1 Setting Password for the SCS Project
It is possible to set a password for the SCS project so that only authorized users can make changes
to the SCS project. The following settings can be made.
Password for the SCS project
If you set a password for the SCS project, users are asked to enter the password when they open
the SCS project.
Allowing read-only access without entering a password
If read-only access without entering a password is allowed, users can open the SCS project in the
read-only status. In this status, the users are not allowed to edit the application logic or generate
databases. Operations on the SCS, such as using the forcing function and downloading data, are
possible in the read-only status.
Select [Project Properties] from the [File] menu of SCS Manager; The following dialog box
appears.
TE Y109JA01E-PPRS
67
Enter the current password in the [Old:] field and a new password in the [New:] field. Enter the
password entered in the [New:] field in the [Confirm New:] field. For the password, up to 8
alphanumeric characters can be used, and case sensitive.
Select the [Read Only] check box to allow read-only access without entering a password.
Click [OK] button.
5.4.2 Setting Password for Each POU
It is possible to set a password for each POU so that only the authorized users can reference and
change important POUs. When users attempt to edit a POU for which a password is set, they are
required to enter the password. If you do not know the password, you are not allowed to reference or
print the POU.
Select a POU for which you want to set a password.
Select [Properties] from the menu displayed by clicking the right mouse button. The following
dialog box appears.
TE Y109JA01E-PPRS
68
Enter the current password in the [Old:] field and a new password in the [New:] field.Enter the
password entered in the [New:] field in the [Confirm New:] field. For the password, up to 8
alphanumeric characters can be used, and case sensitive.
Click [OK] button.
TE Y109JA01E-PPRS
69
6. DOWNLOADING
TE Y109JA01E-PPRS
70
Table of contents
Page Numbers
6.1 What is Downloading?
71
6.2 Overview and Types of Downloading
71
6.3 Downloading Functions and Databases
71
6.4 Downloading and SCS security level
72
6.5 Offline download
72
6.5.1 Downloaded Items
72
6.5.2 Procedure for offline Download
73
6.5.3 Integrity analyzer
76
6.5.4 Cross reference analyzer
76
6.6 Online change Download
6.6.1 Procedure for online change Download
6.7 Master database offline download
6.7.1 Procedure for master database offline Download
6.8 List of applicable items for online change
TE Y109JA01E-PPRS
76
76
79
80
80
71
6.1 What is Downloading?
The downloading functions transfer SCS program and database, which contains the specifications of an
application logic, to an SCS. The SCS database is saved as the master database in the SENG and the
same data as in the SCS is maintained at all times. There is no function to upload the SCS execution data
to the SENG because the SCS execution data is saved in the SENG as the master database.
6.2 Overview and Types of Downloading
Off-line Download
This function downloads a database generated from application logic created in the SENG. During the
download, the functions running on the SCS stops and resume the operation after the completion of
downloading.
On-line Change Download
This function downloads only a portion of database generated from application logic, created in the
SENG, that have been updated since the last download. The functions running on the SCS keep
operating during the download as well. Note that on-line change download may not be possible
depending on the content of the updates.
Master Database Off-line Download
This function downloads the execution data that was active in an SCS again after replacing a CPU
module. The SCS database saved in the master database on the SENG is downloaded. This download is
performed when replacing hardware. In the case of a redundant CPU module, this download is not
required if only one module is replaced.
IOM Download
This function downloads the execution data that was active in an input/output module to a new
input/output module after replacing it. The data of the input/output module (part of the SCS database)
saved in the master database on the SENG is downloaded. This download can only be performed when
replacing hardware of input/output modules.
6.3 Downloading Functions and Databases
The destination database for saving varies depending on the type of downloading. The relationship
between the different types of downloading and databases is explained below.
Off-line Download
The work database generated by building is downloaded to an SCS. The master database is overwritten
by the work database.
On-line Change Download
TE Y109JA01E-PPRS
72
Only the differences between the work database generated by building and the master database are
downloaded to an SCS. The master database is overwritten by the work database.
Master Database Off-line Download
The master database is downloaded to an SCS.
IOM Download
Only the data in the master database related to input/output modules is downloaded to an SCS.
6.4 Downloading and SCS Security Levels
Since the downloading functions attempt to write data to an SCS, the download operations may not be
allowed depending on the SCS security level. Before performing the downloading functions, it is
necessary to use the SCS security level operation function and change the security level of the SCS. The
table below shows whether or not each type of download is allowed according to the security level.
6.5 Off-line Download
During off-line download, the SCS database, which contains all the information required for operation of
an SCS, is transmitted from the SENG to the SCS; meanwhile, the SCS functions are stopped. The SCS
database is downloaded via the V net/Vnet-IP and stored in the flash memory of the SCS and the nonvolatile memory of input/output modules. The SCS database downloaded to the SCS is saved as the
master database together with the source files on the SENG.
6.5.1 Downloaded Items
Application database
The application database created by the Safety application definition function, Modbus
connection function and CENTUM CS 3000 integration function is downloaded to the CPU
module.
TE Y109JA01E-PPRS
73
I/O configuration information
The parts of the database created by the I/O definition function related to input/output modules are
downloaded to the input/output modules.
The following operations are performed if you execute off-line download.
Functions that run on the SCS stop and all the output modules output the fail-safe value
specified in I/O Parameter Builder.
Inter-SCS safety communication is disconnected.
The forcing function is cancelled.
Override from the HIS is cancelled.
SOEs and diagnostic information collected so far in the SCS are deleted (they are saved in the battery
backup memory, though).
The password for changing the SCS security level is deleted.
6.5.2 Procedure for offline Download.
Perform the building operation. An SCS database is generated based on an application.
Icons used to
perform
build
operation
Launch integrity Analyzer and analyze the database.
TE Y109JA01E-PPRS
74
Save the integrity analyzer before quitting
Click on this icon
to enter the
acknowledgement
Click on OK button
Launch cross reference Analyzer and analyze the database.
Click on this icon to
enter the
acknowledgement
TE Y109JA01E-PPRS
Save the Cross reference analyzer before quitting
75
Use SCS security level operation to set the security level to 0.
Select [download] from the [debug] menu of SCS manager. The off-line download confirmation
dialog box appears.
Click the [OK] button.
Specify the password used when changing the SCS security Level.
Use Version Control tool to save the SCS project.
TE Y109JA01E-PPRS
76
6.5.3 Integrity analyzer
Integrity Analyzer analyzes application logics, detects functions that are not allowed to be used for
the functions for safety and displays them in the window by highlighting for visual emphasis.
The user can check whether or not functions prohibited from use for safety applications are used or not.
Analysis results can be printed as well. If there is a program that intentionally makes use of functions
prohibited from use for application, the user can acknowledge their use for each program upon
examining the program based on the results of the analysis.
If functions prohibited from use for safety applications are used unintentionally, the application logic
must be modified. Make changes to the application logic, perform a build operation and then analyze the
application logic with Integrity Analyzer again.
6.5.4 Cross reference analyzer
Cross Reference Analyzer displays the differences between the previously downloaded application (the
application currently running in an SCS) and the application to be downloaded, and the extent to which
the download will affect the operation in a window by highlighting them visually, in order to limit the
range of re-testing caused by changes in an application logic. The user can check programs that
require re-testing, and print the analysis results.
Cross Reference Analyzer detects programs that depend on the changed program as programs
requiring re-testing. A list of programs requiring re-testing is displayed; they can be acknowledged
upon checking the analysis results of each program. If unintended program changes and dependencies
are detected, the application logic must be modified. Modify the application logic, perform a build
operation and then analyze the application logic with Cross Reference Analyzer again.
If no program is found for retesting, retesting will not be performed. However, since the modifications
on a certain items may not be discovered for retesting, these modified items need to be tested
accordingly.
6.6 Online Change Download
On-line change download changes a part of an application without interrupting the SCS functions. In
SCS, the data stored in the main memory of the CPU module is updated and changes are stored in
the flash memory of the CPU module as well.
When performing on-line change download of I/O definitions, changes are also reflected in the nonvolatile memory of the input/output modules. Data downloaded to an SCS is also saved in the master
database on the SENG.
6.6.1 Procedure for On-line Change Download
Perform the building operation.
TE Y109JA01E-PPRS
77
Icons used to perform
build operation
Launch integrity Analyzer and analyze the database
Save the integrity analyzer before quitting
Click on this icon to
enter the
acknowledgement
Launch cross reference Analyzer and analyze the database
TE Y109JA01E-PPRS
78
Save the Cross reference analyzer before quitting
Click on this icon to
enter the
acknowledgement
window
Use SCS security level option to set the security level to 1.
Choose [On-line Change: Download] from the [Debug] menu of SCS manager or click the Online change download button on the toolbar. The on-line change download confirmation dialog
box appears. Click OK button.
TE Y109JA01E-PPRS
79
Use the SCS security level option to return the security level to level 2.
6.7 Master database off-line Download
During master database off-line download, the master database stored in the SENG is loaded to an SCS.
Since the downloaded SCS database is identical to the master database, it is possible to download the
information downloaded previously to the SCS even while changing the work database of an SCS project.
Use this download function to download the database downloaded in the past again, for example when
the CPU module of an SCS is replaced. In the case of a redundant CPU module, this download is not
required if only one module is replaced.
TE Y109JA01E-PPRS
80
6.7.1 Procedure for Master database off-line Download
What to Do before Master Database Off-line Download
Use the SCS security level operation function to set the SCS security level to Level 0.
Start the Master Database Off-line Download
Select [Controller] from the [Tools] menu of SCS Manager. The [Controller] launcher menu appears.
Select [Master Database Off-line Download] of [Reset SCS] from the [Controller] launcher menu.
The master database off-line download confirmation dialog box appears.
6.8 List of Applicable Items for On-line Change
POU Information that is Changeable On-line
TE Y109JA01E-PPRS
81
I/O Module Information that is Changeable On-line
Constants and Network Information that are Changeable with On-line
TE Y109JA01E-PPRS
82
Builder Definitions that are Changeable with On-line
TE Y109JA01E-PPRS
83
7. IEC61131-3 FBD-LD
TE Y109JA01E-PPRS
84
Table of contents
Page Number
7.1 Introduction
85
7.2 Function and Function elements
85
7.2.1 Common elements
85
7.2.1.1
Identifiers
85
7.2.1.2
Comments
85
7.2.1.3
Functions
86
7.2.1.4 Function Blocks
7.2.2 Variable types
7.2.2.1
86
86
Local Variables
86
7.2.2.2 Global Variables
86
7.3 Function Block Diagram
86
7.3.1
Creation of FBD
86
7.3.2
Creation of logics
88
7.4 Function blocks
91
7.4.1
MUXBOOL4
91
7.4.2
MUXREAL4
92
7.4.3
SCALER
93
7.4.4
REPEATTIMER
94
7.4.5
ANLG1002D
95
7.4.6
BOOLVOTER
96
7.4.7
ANLG_S
97
7.4.8
ANLGI
99
7.4.9
VEL
99
7.4.10 CTU
100
7.4.11 CTD
100
7.5 User Defined Function blocks
TE Y109JA01E-PPRS
101
85
7.1 Introduction
IEC61131-3 deals with all aspects of PLC application to Industrial process measurement and
control.IEC61131 standard defines the following programming methods
Function block diagram
Ladder diagrams
Instruction list
Structured text
Sequence function charts
The Prosafe-RS supports Function block diagrams, ladder diagrams and Structured text.
The standard was developed to standardize the programming of PLCs available in the market. This has
several advantages:
A common language means the user need not learn different languages for different PLCs.
Portability of program across different PLCs.
Allows program to be broken in to functional elements called program organization unit.
Strong data typing
Self check to detect when wrong data type is assigned to the variable.
Can describe the complex Sequential behavior.
7.2 Function and Function elements
7.2.1 Common elements
Common elements include Identifiers, Comments and Functions.
7.2.1.1 Identifiers
Identifiers are used for naming different elements such as,
Variables
Function blocks
Programs
The identifiers can be string of letters, digits and underlines provided that:
The first character is not a digit
There are no two or more underline characters to getjer
There are no embedded spaces
7.2.1.2 Comments
Comments of various lengths can be inserted in FBDs and LD.Comments of various length can be
inserted in FBD and LD.The comment can be of single line or multi line.
TE Y109JA01E-PPRS
86
Comments can not be nested.
Ex: (*Boiler interlock logic*)
7.2.1.3 Functions
Functions are POUs with the following attributes:
They have multiple input Parameters and exactly one output parameter.
Within a function it is possible to call another function
The abbreviation for the functions is FU.
7.2.1.4 Function blocks
Multiple input / output parameters and internal memory
Within a function block it is possible to call another function block or functions.
The abbreviation for function blocks is FB.
7.2.2 Variable Types
Variables in Prosafe-RS can be either local variables or global variables.
7.2.2.1 Local Variables:
Local variables can be used only within a POU and can not be accessed else where.
7.2.2.2 Global variables:
Global variables can be accessed by all POUs.
7.3 Function Block Diagram
7.3.1 Creation of a FBD.
The path for the creation of a FBD is shown below. Click Program->Add Program->FBD in Link
architecture. A new FBD will be created.
TE Y109JA01E-PPRS
87
Rename the newly created FBD. Double click to open the newly created FBD to enter the builder
page.
TE Y109JA01E-PPRS
88
7.3.2 Creation of logics
Select Function block option from editor window.
Click on the FBD. Select Blocks dialog box appears.
TE Y109JA01E-PPRS
89
Select a suitable function block from the select blocks option for example select an AND block.
Click on the FBD page to display the AND block.
TE Y109JA01E-PPRS
90
Select variable Icon in the editor window to use the already defined variables.
Variable
icon in FBD
editor
Select the desired variable from the list.
TE Y109JA01E-PPRS
91
Select the draw link Icon in the editor window.
Draw the link from the variables to the function block.
Perform a download and test the program in debug mode.
7.4 Function blocks
7.4.1 MUXBOOL4 (BOOL-Type Multiplexer with 4 Entries)
A MUXBOOL4 function is a 4-input multiplexer for BOOL-type data. It selects one value
TE Y109JA01E-PPRS
92
Out of four input values.
Description
The MUXBOOL4 function is a 4-input multiplexer for BOOL-type data. It selects one value out of four
input values.
If a value other than 0 to 3 is specified for SELC, the output value becomes FALSE.
7.4.2 MUXREAL4 (Real-Type Multiplexer with 4 Entries)
A MUXREAL4 function is a 4-input multiplexer for real number-type data. It selects one value out of four
input values.
TE Y109JA01E-PPRS
93
Description
The MUXREAL4 function is a 4-input multiplexer for real number-type data. It selects one value out of
four input values.
If a value other than 0 to 3 is specified for SELC, the output value becomes 0.0.
7.4.3 SCALER (Scaler)
A SCALER function converts input data (0 to 100%) to the specified scale.
TE Y109JA01E-PPRS
94
Description
The SCALER function converts input data (0 to 100%) to the specified scale.
The calculation formula of OUT is as follows:
OUT = IN (SH - SL)
---------------- +SL
100.0
7.4.4 REPEATTIMER (Repeat Timer)
A REPEATTIMER is a function block of repeat timer.
Description
The REPEATTIMER function block executes a repeat timer function.
The REPEATTIMER function block outputs ON and OFF alternately as long as the output start switch
(RUN) is TRUE. It outputs TRUE as the output value (Q) during the period specified by the ON period
(ONT) and FALSE during the period specified by the OFF period (OFFT). The repeat interval is the value
obtained by adding the ON period and OFF period (ONT + OFFT). If the output start switch (RUN)
becomes FALSE, the output value (Q) is set to FALSE. If STF is TRUE, the timer starts from the OFF
period. If STF is FALSE, the timer starts from the ON period.
TE Y109JA01E-PPRS
95
7.4.5 ANLG1OO2D (1oo2D Analog Voter)
An ANLG1OO2D function block is a 2-input analog voter with diagnostics. It diagnoses the data status of
two input values and determines the output value.
Description
The ANLG1OO2D function block is a 2-input analog voter with diagnostics. It receives two inputs with
data status and determines the output value using the voting method of 1oo2D (one-out-oftwo with
diagnostics). By using the ANLG1OO2D function block, it is possible to detect not only input module
failures, but also input value errors.
TE Y109JA01E-PPRS
96
7.4.6 BOOLVOTER (IO_BOOL-Type BOOL Voter)
A BOOLVOTER function block is a 3-input BOOL voter. It receives three input values with data status
and outputs a value selected from these input values or the fail-safe value
TE Y109JA01E-PPRS
97
Description
A BOOLVOTER function block is a 3-input BOOL voter. It receives three input values with data status
and outputs one value selected as the value of at least two out of the three inputs (twoout-of three: 2oo3)
via the output (Q). By using the BOOLVOTER function block, it is possible to detect not only input
module failures, but also errors in input values INn {n = 1, 2 or 3} received from sensors.
7.4.7 ANLG_S (Analog Input Function Block with Data Status)
An ANLG_S function block converts the scale of the analog input (IN), and then outputs the converted
analog output (OUT) and data status (STS) corresponding to the analog input (IN).
TE Y109JA01E-PPRS
98
Description
An ANLG_S function block converts the scale of the analog input (IN), and then outputs the converted
analog output (OUT) and data status (STS) corresponding to the analog input (IN). It compares this
output value (OUT) with four types of threshold values (HH, PH, PL and LL) and outputs an alarm status
TE Y109JA01E-PPRS
99
(NHTR, NHHH, NLLL or NLTR). Each alarm condition is only set as having occurred (FALSE) if the alarm
condition continues for a specified period of time (TRDT or PADT) or longer. If TRUE is specified for
SOER, an SOE event is generated when a trip/prealarm occurs or the system recovers from it.
It can be referenced using a tag name from CS 3000 by defining the tag name for the instance of the
ANLG_S function block. If the data status (STS) becomes FALSE (BAD), an IOP process alarm is
generated, which can be confirmed on an HIS.
7.4.8 ANLGI (Analog Input)
An ANLGI function block converts the scale of the input value (IN) and calculates the output value OUT).
Since the ANLG_S function block consists of the feature of this function block and other capabilities
such as outputting data status, it is recommended to use ANLG_S instead of this function block.
7.4.9 VEL (Velocity Limit Alarm)
A VEL function block monitors the rate of change of the input value and judges whether or not the
specified rate of change is exceeded.
Description
The VEL function block monitors the rate of change of the input value and judges whether or not the
specified rate of change is exceeded. Moreover, it can be referenced using a mapping block from CS
3000 by defining a tag name for the instance in question.
TE Y109JA01E-PPRS
100
7.4.10 CTU (Count Up Counter)
A CTU function block counts up from 0 to the maximum counter value (PV) in increments of 1 as long as
the count input (CU) is TRUE.
Description
The CTU function block counts up in increments of 1 at each scan from 0 to the maximum counter
value (PV) as long as the count input (CU) is TRUE. The count result is output for CV and the default
value is 0.
When the counter reaches the maximum value (CV PV), the CTU function block stops counting up and
outputs TRUE for Q.
RESET is a reset command. If RESET becomes TRUE, the counter is reset, Q becomes FALSE and CV
becomes 0. As long as RESET is TRUE, the CTU function block does not count up even if CU becomes
TRUE.
7.4.11 CTD (Count Down Counter)
A CTD function block counts down in decrements of 1 at each scan from the initial counter value
(PV) to 0 as long as the count input (CD) is TRUE.
TE Y109JA01E-PPRS
101
Description
The CTD function block counts down in decrements of 1 at each scan from the initial counter value
(PV) to 0 as long as the count input (CD) is TRUE. The count result is output for CV and the default value
is the initial counter value (PV).
When the counter reaches 0 (CV 0), CTD stops counting down and outputs TRUE for Q.
LOAD is a load command. If LOAD becomes TRUE, the counter is loaded, Q becomes FALSE and CV is
reset to PV. As long as LOAD is TRUE, the CTD function block does not count down even if CD becomes
TRUE.
7.5 User Defined Function block
Prosafe-RS allows user to define unique FUs and FBs. These FUs and FBs are called User defined FUs
and User defined FBs, respectively. Frequently used FUs and FBs such as AND,OR, TON etc can be
used by the user to write logics used commonly in applications as well. User defined FUs and FBs can
be used in any programs.
Creation of a user defined function block.
To Create a user defined function block, Right click Function blocks on the link architecture
view, then select Add function block option and the language FBD. Then name it as ESD_VALVE.
TE Y109JA01E-PPRS
102
To define the parameters of the user defined function blocks, Open the Dictionary View . Then
select the parameters tree and click (+) on the tree view to select ESD_VALVE.
TE Y109JA01E-PPRS
103
Define the following parameters in Dictionary.
Double click on the ESD_VALVE of a function block on the link architecture view. Edit the logic
as shown in the following figure.
Execute the build program and save'. Then close the multi-language editor.
Creation of a program using User Defined function block.
Create a program for Valve-2 using ESD_VALVE which is a User defined function block.
Define I/O variables on the Dictionary view and wire them with I/O channels on the I/O wiring
builder.
1.Digital inputs:
ESD switch signal from operator console:
DIP101 NC input
Open operation for Valve-2 from local operation box: DIP102 NO input.
Close operation for Valve-2 from local operation box: DIP103 NC input.
2. Digital outputs:
Open command for Valve-2
: DOP303 DTS output
Create new program choosing FBD as the language, and then name it Valve2 on the link
architecture view.
Double-click the Valve2 to open the editor and edit the logic as shown in the following figure.
TE Y109JA01E-PPRS
104
Execute Save and Build Program'. Then close the multi-Language editor.
TE Y109JA01E-PPRS
105
8. INTEGRATION
TE Y109JA01E-PPRS
106
Table of contents
Page Number
8.1 Introduction
107
8.2 Overview of Operation and Monitoring from HIS.
107
8.3 Engineering on the SENG Side
107
8.4 Engineering on the CS 3000 Side
109
8.5 Integration of ANLG_S with CS3000
109
8.6 Function blocks for integration with CS3000
114
8.6.1 Override Function Blocks
114
8.6.2 PASSWD (Password)
115
8.6.3 ANN
116
8.7 Inter SCS communication
8.7.1 Function Blocks details for Inter-SCS Communication
TE Y109JA01E-PPRS
116
120
107
8.1 Overview of CS 3000 Integration
The CS 3000 Integration Function of the ProSafe-RS provides a communication interface for accessing
SCS of ProSafe-RS from HIS and FCS of CENTUM CS 3000 system (hereinafter referred to as CS 3000).
By this function, you can operate and monitor SCS from HIS using the same interfaces (windows) for
operating and monitoring FCS. You can also access SCS data from FCS using the same interface (tag
names) used by an FCS to access other FCS.
8.2 Overview of Operation and Monitoring from
HIS.
In the CS 3000 integration, the following operations are possible from HIS to SCS:
To use tag names to operate and monitor SCS data via the same interface used to monitor FCS data.
To monitor the status of process alarms and annunciators generated on SCSs in HISs Process Alarm
window.
To monitor the system alarms generated on SCS in HISs System Alarm window.
To display the status of each SCS in HISs SCS Status Display window.
To override the application logic variables.
To set output of the application logics.
8.3 Engineering on the SENG Side
This section describes the engineering tasks performed on the SENG side, among the tasks required to
connect an SCS project and a CS 3000 project.
Setting of SCS Project Property
An SCS project and a CS 3000 project can be connected using SCS Project Properties in SCS manager.
In SCS Project Properties, specify the folder of the CS 3000 project you want to connect to the SCS
project. The information for CS 3000 integration that has been set in the SCS project can be copied to
the CS 3000 project folder.
The connection of an SCS project and a CS 3000 project is set only in one direction: from the SCS
project to the CS 3000 project.
TE Y109JA01E-PPRS
108
TE Y109JA01E-PPRS
109
8.4 Engineering on the CS 3000 Side
This section describes engineering tasks performed on the CS 3000 side, among those tasks required
to connect an SCS project and a CS 3000 project.
SCS Creation
To connect each SCS project to a CS 3000 project, a corresponding SCS must be created in CS 3000
System View first.
Creating an SCS
SCSs are created in CS 3000 System View. The procedure is explained below:
Select [File] - [Create New] - [SCS (E)] in System View. The New Station dialog box appears.
8.5 Integration of ANLG_S with CS3000
There are number of function blocks that makes the integration with Centum CS3000 an easy job. By
using these block in Prosafe-RS and exporting them to CS3000 configuration, Faceplates on the HIS are
generated automatically.
The blocks are mentioned below.
It is necessary to assign instance name to the blocks. This should be done in dictionary.
TE Y109JA01E-PPRS
110
After the instance names are set the blocks can be placed in the drawing or if the blocks where
already drawn instance name should be attached.
TE Y109JA01E-PPRS
111
TE Y109JA01E-PPRS
112
Set the right input output variable.
Once the tags and instances are assigned in the dictionary it is necessary to start the tag list
generation and assign the tag names as they should appear in HIS. This should be done by the
tag name builder.
TE Y109JA01E-PPRS
113
Use Tag name builder to assign Centum CS3000 tag names to SCS Tags. Double click on the
SCS tag name in the left panel. By doing this name will move to the list on right. The different
types of SCS tags will show up under the tabs with the same name, e.g. the tags assigned to
ANLG_S block will show up under the tab.
Assign a centum CS3000 tag name in the Tag Name Column.
The next step is to make the data available for Centum CS3000. Therefore make sure where that
workbench software is provided with the path for centum CS3000 project.
As mentioned earlier each SCS must be created in CS3000 system view.
Launch Taglist builder from System view. In System view, select the SCS you want to generate a
taglist for.
Select the [TOOLS]-[SCS Taglist import] from the menu. An HIS tag list will be generated.
TE Y109JA01E-PPRS
114
8.6 Function blocks for integration with
CS3000
8.6.1 Override Function Blocks
Override function blocks (override FBs) override variables of an application logic. Blocks vary
according to the data type of the overridden variables.
OVR_B (BOOL-Type Data Override)
OVR_I (INTEGER-Type Data Override)
OVR_R (REAL-Type Data Override)
OVR_IB (IO_BOOL-Type Data Override)
OVR_IR (IO_REAL-Type Data Override)
Types of Override Function Blocks
There are five types of override function blocks, one for each data type, as shown in the table below.
Arguments other than input parameter IN, output parameter OUT and input parameter VAL are common
for all of the function blocks regardless of the data type.
TE Y109JA01E-PPRS
115
Arguments
Description
The override function blocks output the data input from input parameter IN as is via output parameter
OUT as long as no overriding operation is performed. If an override instruction is set from an HIS, on the
other hand, the override function blocks output the data specified in input parameter VAL via output
parameter OUT. In short, data is fixed to the value defined in input parameter VAL in advance. If the
override operation is canceled from the HIS, the override function blocks resume outputting data input
from input parameter IN via output parameter OUT.
8.6.2 PASSWD (Password)
The PASSWD function block sets the output value to either TRUE or FALSE upon examination of the
password character string sent from an HIS.
Description
TE Y109JA01E-PPRS
116
A password character string entered on the faceplate of an HIS is transmitted to the PASSWD function
block via a mapping block. If this character string matches with the character string specified for the
input parameter PSWD, a data value set to TRUE, the PASSWD function block outputs the same value to
its output parameter OUT.
The default value of output parameter OUT of the PASSWD function block is FALSE. Make sure to
configure the PASSWD function block such that it outputs FALSE under normal circumstances and
TRUE when data requiring password authentication is set from an HIS.
8.6.3 ANN (Annunciator)
An ANN function blockis used to generate annunciator messages if a CS 3000 HIS is connected.
Description
ANN block generates an annunciator message notifying that an alarm has been generated if the input
value (IN) changes from FALSE to TRUE. If the input value (IN) changes from TRUE to FALSE, it
generates an annunciator message notifying that the function block has recovered from the alarm.
Message character strings are specified in Tag Name Builder. The default value for IN when starting an
SCS is FALSE.
8.7 Inter SCS communication
An SCS is able to perform Safety Communication with another SCS in same domain and in different
domains.i.e an user can create a safety loops covering two SCS.
The specifications of inter-SCS safety Communication are discussed below:
One SCS can Communicate with 16 SCS.
One SCS can send up to 200 data values.
One SCs can receive up to 200 data values.
Communication data sent at the same time is never divided into multiple scans and received.
An application logic that shows the fail safe communication between SCS0101 and SCS0102.
TE Y109JA01E-PPRS
117
SCS0101 sends a variable called P0101001 (P=Producer Variable, 0101=ddss, 001=index of the
variable) to the SCS0102.Last SCS will put this variable called C0101001(C=Consumer Variable,
0101=ddss, 001=index number).
Creation of the producer variable.
Enter the producer variable in SCS0101 dictionary. The type should be COM_BOOL
Select from Link Architecture the external binding list.
Icon for
External
binding list
Select new binding option from this Form
TE Y109JA01E-PPRS
118
After you have selected the option new binding the next figure appears. Select New binding
option to select the variables. Select the variable P0101001.
If everything has been defined the right way, the result should look like the next figure.
Define the right variable into the right function block for producer variable.
Perform Offline download.
Creation of the Consumer variable.
Enter a consumer variable in SCS0102 dictionary. The type should be COM_BOOL.
TE Y109JA01E-PPRS
119
Select from Link Architecture the external binding list.
Icon for
External
binding list
Select new binding option from this Form.
In this form one can enter the variables by selecting the new binding symbol. At that moment
external binding form appears.
Now one can only select the producer variable from the sending side if the communication is
available and the definition of the producer variable has been already defined. Select the
producing and consuming variable from the external binding form.
TE Y109JA01E-PPRS
120
Define the right variable into the right function block for consumer variable.
Perform Offline download. Also perform Output enable operation on the producer side.
8.7.1 Function Blocks details for Inter-SCS Communication:
The Following function Blocks are provided for Inter-SCS Communication:
Production function blocks.
Consumer function blocks.
Production function blocks:
The function blocks have same input and output parameters, but the data type corresponds with the
type of function blocks.
Consumer function blocks:
TE Y109JA01E-PPRS
121
Consumer function block receives the data sent from the production function block in other SCS and, if
there is no error, outputs the data.
The consumer function blocks have input and output with the same name, but the data type
corresponds to the type of the function block.
TE Y109JA01E-PPRS
122
9. SEQUENCE OF EVENT
RECORDER
TE Y109JA01E-PPRS
123
Table of contents
Page Number
9.1 SOER Collection Definition
124
9.2 Event Collection
124
9.2.1 Objects of Event Collection
124
9.2.2 Event Saving
124
9.2.3 Event Targets
125
9.2.3.1 Events of Discrete Inputs (DI)
125
9.2.3.2 Events of Discrete Outputs (DO)
125
9.2.3.3 Events of Analog Inputs (AI)
125
9.2.3.4 Events of internal variables
126
9.3 Event Storage
128
9.3.1 Saving Event Data
128
9.3.2 Flow of Event Storage
128
9.3.3 Specification of Event Log Files
129
9.3.4 Trip Signal
129
9.3.5 Specification of Trip Signal Files
129
9.4 Management of Event Information when SCS is Unsteady
130
9.4.1 Protection of Event Information at Power Failure
130
9.4.2 SCS Startup Operation
130
9.4.3 Lock Status by the Forcing Function
130
9.5 SOE Viewer
131
9.5.1 SOE Viewer Window
131
9.5.2 Displaying SOE Viewer
131
9.5.3 Event Mode Operation
132
9.5.4 Activating the Event Mode
132
9.5.5 Data Source Query
132
9.5.6 Trip Mode Operation
133
9.5.7 Activating the Trip Mode
133
TE Y109JA01E-PPRS
124
9.1 SOER Collection Definition
Sequence of Events Recorder (SOER) is a function that collects and stores events occurred in an SCS.
The SOER collection definition defines which events to collect. It also specifies the time synchronization
method related to event collection time (time stamp). By using SOE Viewer, it is possible to analyze
collected events and save them in files.
9.2 Event Collection
The setting method of event collection definition varies depending on the object. Events can be
collected either from a discrete input/output module or an application logic.
9.2.1 Objects of Event Collection
The following types of events can be collected for SCSs.
Signal changes of discrete input modules.
It is possible to collect events from discrete input modules according to the changes of data input from
individual channels. Specify whether or not to collect events for each channel.
Signal changes of discrete output data
It is possible to collect events according to the changes of data output to individual discrete output
channels. Specify whether or not to collect events for each channel.
Alarms on Analog input data and Recovery
It is possible to collect events by comparing the output values with the settings of alarm level set to the
analog input block.
Variation of Analog output data
It is possible to collect events based on the variation of output variable. Take the settings of the output
variable into SOE_R, and specify the conditions of event generation.
Changes of internal variable of an application logic
It is possible to collect events according to the changes of an internal variable of an application
logic. Specify the object internal variable and conditions of event generation.
9.2.2 Event Saving
There is no need to prepare a PC for saving events or keep the power supply to an SENG on at all times,
because event information is saved in the SCS.
The maximum number of event information records that can be saved in an SCS is 15,000.
It is possible to ensure that particularly important event information, i.e., records acquired before and
after a trip signal was generated, can be notified to users without fail by separating the storage location.
TE Y109JA01E-PPRS
125
9.2.3 Event Targets
An SCS can save the following data as event information by user specification. Events related to
discrete inputs (DI) are collected by the input modules; other events are collectedby the CPU.
9.2.3.1 Events of Discrete Inputs (DI)
Discrete input modules detect changes in the input signals input to each channel (FALSE to TRUE or
TRUE to FALSE) and collect events.
Users can specify whether or not to collect SOE event information for each channel.
If discrete input modules are placed in redundant configuration, the active module collects events.
The each comment text applied to the variable corresponding to DI is added to the event (acharacter
string of up to 32 single-byte characters or 16 double-byte characters). The user needs to define the
variables corresponding to the contact inputs on the Workbench Dictionary View as the comments so as
to identify the whereabouts of the occurred events.
9.2.3.2 Events of Discrete Outputs (DO)
The CPU detects changes in the output value set to a discrete output module and collects events.
Users can specify whether or not to collect SOE event information for each channel.
For dual-redundantly configured contact output modules, the signals output from the active module
are gathered as the events.
If the output channel is abnormal (data status is BAD), the events will not be gathered.
Each event is attached with a comment text assigned as a variable to the contact output (a character
string of up to 32 single-byte characters or 16 double-byte characters). The user needs to define the
variables corresponding to the contact outputs on the Workbench Dictionary View as the comments so
as to identify the events.
9.2.3.3 Events of Analog Inputs (AI)
The ANLG_S function block outputs alarms by judging analog input values, so it is able to collect
events by making appropriate application. It performs magnitude correlation comparison of set values
and analog output values (OUT) and collects events by using a change in OUT as a trigger.
Events are collected when the SOER input terminal is set to TRUE.
At event collection, a character string set to the ID input (a character string of up to 32 singlebyte characters or 16 double-byte characters) is stored along with the event data.
TE Y109JA01E-PPRS
126
An ANLG_S function block collects events when the following outputs change their status from FALSE
to TRUE, or from TRUE to FALSE
NHTR (HI trip flag)
NHHH (HI pre-alarm flag)
NLLL (LO pre-alarm flag)
NLTR (LO trip flag)
When the event occurred can be checked in the ID field of the SOE Viewer.
9.2.3.4 Events of internal variables
SOE_B (BOOL-Type Data SOER)
An SOE_B function block collects SOE data of BOOL type.
TE Y109JA01E-PPRS
127
Description
The SOE_B function block collects SOE data of BOOL type.
The SOE_B function block collects events at the timing when input value IN changes. If the trip signal
specification is set to a value other than TRIP_NONE, events collected with the SOE_B function block
are treated as trip signals. ID is event identification information and displayed in SOE Viewer. Specify a
character string (up to 32 single-byte or 16 double-byte characters) in order to identify the event.
SOE_I (INTEGER-Type Data SOER)
An SOE_I function block collects SOE data of integer type.
Description
The SOE_I function block collects SOE data of integer type.
The SOE_I function block collects events at the timing when the trigger signal value changes. If the trip
signal specification is set to TRIP_ON or TRIP_OFF, events collected with the SOE_I function block are
treated as trip signals. ID is event identification information and displayed on SOE Viewer. Specify a
character string (up to 32 single-byte or 16 double-byte characters) in order to identify the event.
SOE_R (REAL-Type Data SOER)
An SOE_R function block collects SOE data of real number type.
TE Y109JA01E-PPRS
128
Description
The SOE_R function block collects SOE data of real number type.
The SOE_R function block collects events at the timing when the trigger signal value changes. If the trip
signal specification is set to TRIP_ON or TRIP_OFF, events collected with the SOE_R function block are
treated as trip signals. ID is event identification information and displayed on SOE Viewer. Specify a
character string (up to 32 single-byte or 16 double-byte characters) in order to identify the event.
9.3 Event Storage
Event information is stored in the SOER event information storage memory of an SCS. There are two
types of files in which event information can be stored: an event log file and trip signal files. An event log
file stores the latest event information. In the trip signal file, events before and after each trip signal are
saved.
9.3.1 Saving Event Data
An SCS saves event data using two types of files: an event log file, which stores event information in
the order of data collection, and trip signal files, which store events generated before and after the trip
signal specified by the user. There are two trip signal files.
Event information saved in an SCS is not deleted when read by an SENG and HIS. It is thus possible to
reference the information from multiple SOE Viewers.
9.3.2 Flow of Event Storage
TE Y109JA01E-PPRS
129
The figure below illustrates the flow according to which event information is stored in an SCS.
Since event information from a discrete input (DI) module is automatically stored in the DI event
temporary storage memory of the CPU, both the DI event in this memory and event information collected
in the application logic are stored in the SOER event information storage memory.
9.3.3 Specification of Event Log Files
An event log file stores the latest event information and one event log file is saved per SCS.
Up to 15,000 events can be saved in the event log file.
If the number of events saved exceeds the maximum number, events are deleted and overwritten by
new events from the oldest one.
Whenever an SCS has saved 12,000 events in the event log file, it sends a diagnostic information
message to prompt the user to upload to the SENG.
9.3.4 Trip Signal
Trip signals are particularly important events in the plant. Since they are key events when engineers
attempt to analyze the causes of tripping, they must be securely stored in the SCS together with the
events generated before and after them.
Either ON edge or OFF edge can be specified as the trip signal. However, both edges can be specified
as ignored.
Users can specify trip signals in input/output definitions or in function blocks for SOE. There is no
restriction on the number of trip signals that can be specified, but it is necessary to examine trip signal
settings thoroughly in order to record useful event information.
9.3.5 Specification of Trip Signal Files
Trip signal files store events generated before and after a trip signal specified by the user.
An SCS stores events generated before and after the trip signal in a trip signal file.
TE Y109JA01E-PPRS
130
A trip signal file stores 1,500 events in total: the last 500 events generated before tripping including the
trip signal and the 1,000 events generated after tripping.
Up to two trip signal files can be stored in an SCS. No more trip signal files are saved even if more trip
signals are generated. If two trips occur in a short period of time, the data in the two trip signal files may
overlap.
If less than 500 events are collected prior a trip event occurs, the number of the events before the trip
event will be less than 500.
The file will be closed when 1000 events are collected after the trip event. However,if the number of
events after 30 minutes of the trip event is less than 1000, the file will be closed anyway with less events.
An SCS sends a diagnostic information message when saving of a trip signal file is completed.
Trip signal files are not automatically initialized by the system. These files can be initialized only via
operation from the SENG.
9.4 Management of Event Information when
SCS is Unsteady
An SCS is considered to be unsteady if it is in one of the following conditions:
A power failure occurs in the SCS
During startup of the SCS
Input/output variables are locked
If a power failure occurs in an SCS, event information is saved in a memory backed up by a battery. The
SCS restores the event information at startup; it is thus possible to check the event information before
the SCS was stopped.
9.4.1 Protection of Event Information at Power Failure
Under normal circumstances, event information is stored in the main memory of an SCS. If a power
failure occurs in the CPU, the data saved in the main memory is lost. Therefore, the SCS saves the most
recent events recorded immediately before the power failure to a different memory backed up by a
battery. Although all the events cannot be protected, it is possible to analyze events that occurred
immediately before the power failure by protecting them in this way.
9.4.2 SCS Startup Operation
An SCS restores the event information that was saved before it was stopped when it starts up at
restarting or after off-line download.
9.4.3 Lock Status by the Forcing Function
If input/output variables are locked by the forcing function, event collection is performed in the following
ways when the values of the input/output variables change.
TE Y109JA01E-PPRS
131
9.5 SOE Viewer
SOE Viewer allows the user to analyze events detected by SCS. It uploads event logs from the specified
SCS and displays them as event messages.
9.5.1 SOE Viewer Window
The information managed by SOE Viewer is displayed in either the event mode or the trip mode. The
window structure used in the event and trip modes is the same.
9.5.2 Displaying SOE Viewer
Select [All Programs], [YOKOGAWA ProSafe] and [SOE Viewer] from the [Start] menu of Windows. SOE
Viewer is displayed in the event mode.
After starting the SOE Viewer, no event message is displayed in the message record list since no
data source is specified. The event messages are displayed only after specifying the data source
and running the query.
TE Y109JA01E-PPRS
132
9.5.3 Event Mode Operation
In this mode, SOE Viewer displays event messages of an SCS in a list format. This allows analyzing
events from relevant information using filtering.
9.5.4 Activating the Event Mode
When you start SOE Viewer, the event mode is automatically activated. When you start up SOE Viewer
for the first time, no data source is setup. Specify one or more data sources in the SOE Viewer
Properties dialog box.
9.5.5 Data Source Query
If a query is executed, event messages matching the date/time and the data source parameters
specified in the SOE Viewer Properties dialog box are acquired, up to the maximum number of records.
The event messages are displayed in the message record list of SOE Viewer.
TE Y109JA01E-PPRS
133
9.5.6 Trip Mode Operation
In this mode, SOE Viewer displays only trip trigger events specified as trip signals in a list format. It also
displays detailed information generated near a specified trip trigger event for analysis. This section
provides an overview of the trip mode of SOE Viewer and information displayed in the trip detail display.
9.5.7 Activating the Trip Mode
Click Trip Mode button on the toolbar or select [Trip Mode] in the [View] menu. SOE Viewer switches
to the trip mode.
The trip trigger event list is blank until a query is executed. Once a query is executed, trip signals in the
specified date range are uploaded from the specified data source and the trip trigger events are
displayed in the trip trigger event list. This data is displayed again when the trip mode is activated again.
TE Y109JA01E-PPRS
Ind-1
Prosafe-RS Training
Manual
TE Y109JA01E-PPRS 1st Edition
INDEX
A
Accessories 25
Addressing 27
Analog input modules 22
ANLG_S.. 97
ANLG1oo2D.. 95
ANLGI.. 99
ANN.. 116
Application logic execution function. 49
Front setting switch. 21
B
Battery.. 19
Battery ON/OFF Switch 21
BCV. 46
BOOLVOTER 96
C
CGW 46
Communication modules. 24
COPY.. 20
Creation of Analog I/O variables.. 55
Creation of Digital I/O variables 56
Cross reference analyzer... 76
CTD.100
CTRL.. .. 20
CTU... 99
D
Data source Query... .. 132
Defined words tree. 39
Desk test 45
Dictionary view 36
DOMN. 21
E
Event Collection. 124
Event messages. 131
Event mode operation. 132
Event saving 124
Event storage. 128
Event Targets 125
External communication function 49
G
Global variables37
H
Hardware architecture.35
HRDY 20
I
I/O parameter building setting. 41
I/O wiring 40
Input and Output modules. 22
Integrity analyzer. 76
Inter SCS Communication.. 116
IOM download 71
L
Link Architecture window. 32
Local variables...... 37
M
MIL cables........
Modbus slave communication.
MUXBOOL4.
MUXREAL4........
23
46
91
92
N
Node Address. 27
O
Offline download61
Offline level..62
Online change download.76
Online level..62
Optical ESB bus repeater47
Override function block114
TE Y109JA01E-PPRS
Edition: Jan 2009
Ind-2
Parameter Tree 38
Passwd..115
PORT.21
Pressure clamp terminals.. .24
Processor module19
Programming languages.. 85
Project creation51
Project template51
Variable bindings..34
Variable groups 34
Variable tree. 37
VEL... 99
V-net coupler unit....19
W
Wiring check adapter.....26
R
RCV20
RDY20
Reaction time.08
Redundancy..28
Relay boards. 26
Reliability 08
Repeat Timer. 94
S
SAI143. 23
SAI533. 23
SAV144 23
SB bus. 29
Scaler.. 93
Scan period 49
SCS database 66
SCS Maintenance support tool 65
SCTY. 20
SEC401 19
Serial communication modules.... 47
Signal cable interface adapter 25
SNB10D22
SND.. 20
SOE_B .........126
SOE_I..127
SOE_R.127
SOER Collection Definition.124
SSC10D16
STA21
Standard Type Safety control unit.17
START/STOP..21
STBY. 21
SYNC...... 20
T
Tagname builder.112
Time synchronization..50
Trip mode..133
Trip trigger event133
U
User defined function block101
TE Y109JA01E-PPRS
1st Edition: Jan 2009
i
Revision Information
Title
Manual No.
: PROSAFE-RS Training manual
: TE Y109JA01E-PPRS
JAN 2009 /1st Edition/R2.01 or later
Newly published
Written by
Training centre
Customer Service Division
Yokogawa India Limited
TE Y109JA01E-PPRS
1st Edition: Jan 2009