100%(2)100% found this document useful (2 votes) 1K views4 pagesTube Rupture Relief Sizing Method
DIERS method for Two-phase equation
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content,
claim it here.
Available Formats
Download as PDF or read online on Scribd
. this purpose are receiv-
Using DIERS two-phase
equations to estimate tube
rupture flowrates
The method is more accurate than
the traditional ‘separate’ phase approach
B. Elliott, Stone & Webster Engineering Corp.,
Houston, Texas
SME Section VIII and API 521 discuss the
A need to design and protect heat exchangers
against overpressure due to a tube rupture,
API 521 specifically addresses requirements and
approaches to solve this problem. The first solution
is to raise design presture ofthe low-pressure side
toa minimum of two-thirds of the design pressure
ofthe high-pressure side, Howover, this may not be
desirable due to economics or other design reasorie,
"The second solution s
toad a relieving device,
like a relief valve or @
rupture dise. To size this
relieving device, flow
through the tabe rapture
from the high-pressure
side to the low-pressure
side of the heat ex.
changer must be calew.
lated (Fig. D. Equations
developed by the Ameri=
can Institute of Chemical
Engineers (AIChE) for
ing widespread support.
In many instances,
high-pressure liquid
flashes to a much lower
pressure through the tube rupture, thereby requiring
a method for calculating two-phase flashing flow.
Equations that have been developed in the past two
decades for two-phase flashing flow in relief valves
and flare header piping can be used for determining
flowrate through the tube rupture.
Historically, the process industry has sized relief
valves whose inlet and/or discharge is two-phase by
separating out the phases into pure liquid and pure
vapor phases, determining a required area for each
phase, and adding the two areas together for a total
required relief valve area. While this has no theo-
retical basis, it was seen as giving a reasonable “ball.
Fig. 1. Tube rupture diagram,
—___ —
park” estimate, without going into complicated math-
ematical and semiempirical techniques. There is evi-
dence that using this method can lead to incorrectly
sizing relief valves
Over the past 15 years, The Design Institute for
Emergency Relief Systems (DIERS), an arm of
AIChE, has been looking into the area of two-phaso
flow in relief valves and flare headers. It has devel-
oped various caleulation methods to deal with these
problems. These methods are receiving widespread
support and use within the industry. Since a tube
rupture, as defined in API 521, is just flow through
a tube (one side of the
break) and flow through
an orifice (tubesheet
side of the break), the
| DIERS two-phase mass
flux methods can easily
be applied to these prob-
lems when there are
two-phase or flashing
fluids,
DIERS equations for
physical properties of
the fluid. A generalized
equation for nozzle dis-
charge is used for sizing
the relief valves for two-phase flashing flow. Hence,
it can be used to approximate flowrate through the
DIERS mass flux equations have also been devel-
oped for pipe flow with choked discharge. These
equations can be used for the tube side of the tube
twice the flow through the tubesheet, assuming that
the flowrates will be reasonably close. This would
Jess accurate) than the other method.
HYDROCARBON PROCESSING /AUGUST2001 49
Bad FEequations assume steady-state and equilibrium condi-
ons, and they do not account for transients. An esti-
nation of peak pressures caused by shock waves that
boeur immediately after the tube rupture would have to
be evaluated using a different method.
‘The method for estimating tube rupture flowrate is
as follows:
@ Determine mass flux through the tubesheet side
of the broken tube.
‘© Determine mass flux through the tube side of the
broken tube.
‘ Calculate tube discharge area.
@ Calculate flowrate through the tube rupture.
‘To determine inlet composition of the relief valve on
the low-pressure side, calculate any additional flashing
and mixing that occurs after the rupture.
Methodology using DIERS HEM equations. There
are various specific DIERS methodologies for calcu-
Jating two-phase flashing flow. The specific equations
presented here were developed by Leung.! Their
Strength is ease of use and that they only require inlet
conditions, However, they are not necessarily as accu
tate with fluids close to the critical point. An alterna-
tive sot of equations was developed by Simpson? These
equations are stronger when dealing with critical flu-
ids, but require more physical data.*
‘Determine mass flux through the tubesheet
side of the broken tube.
‘Stop 1: Calculate the compressible flow parameter, o:
‘The DIERS methods treat the two-phase fluid as a
single homogeneous “compressible” fluid. Leung's
method does this by calculating a compressible flow
parameter, o. This parameter is a measure of the flu-
Jas “compressibility.” The larger the value of «, the
‘more the fluid behaves like a compressible fluid. Values
for o fall into these categories:
Flashing flow: worl
Gas/vapor flow: onl
Nonflashing flow: O 0.6.8 At values < 0.6, Eq. 3 should be
solved numerically.
Step 3: Calculate the dimensionless mass flux, 0*:
If the flow is critical:
G=n/ot ©
If the flow is not critical:
Gra fsfotan+(o-0e-nlf hoon 2}+1] ©
and
n= Ps/Po oO
where
'P; =low-pressure side “relieving pressure”, psia
P)= high-pressure side pressure, psia
Step 4: Caleulate actual mass flux, G (b/hr/in ?):
Gy =17006* (oo) ©
inlet pressure (psia)
overall density of the two-phase fluid at inlet,
Thin?
Continued
etDetermine the mass flux through the tube side
cof the broken tube. Flow through the tube side can be
/ approximated by using the DIERS mass flux equations
for horizontal pipes (or vertical pipe, ifthe exchanger is
vertical) For consistency, we have continued to use
Leung's methods.
Use the samo w as was calculated in the previous
Step 1. The method consists of three equations, one
for tube inlet, one for the flow through the tube and
one for tube discharge. If an exchanger doesn't comply
with the API 2/3 rule, discharge from the tube will
almost certainly be choked, therefore, the discharge
nozzle equation can be assumed to be critical flow.
‘Step 1: Inlet “nozzle”
©
where: n, = the ratio of the pipe inlet pressure to the
“high-pressure side” pressure.
n= Pal Po ao
Step 2: Pipe
coca _o _,(-e)y+e
WO Ge wo er
-softcopere( a] as
(Q-a)ny +002 J
where: nz =the rato ofthe outlet pressure to the “high-
pressure side” pressure.
ny Bi a2
where:
f= friction factor
= tube length
D=tube diameter
Step 3: Outlet nozzle:
of = Te. as)
‘These equations are combined and then solved
numerically to obtain a G*.
Step 4: Calculate actual mass flux, G (Ib/hr/in.),
Gq = 1,7006* (Pyp)# aay
where: *
Po = inlet pressure, psia
wwerall density of the two-phase fluid, Ib/ft?
Calculate tube discharge area, A, (in.*)
Ay = nD? ap
where: Dy = tube inner diameter, in,
Or use a cross-sectional area cited in a reference.
Caleulate flowrate through the tube rupture:
We 4,(41+G3) as)
At this point, total flowrate through the rupture
has been calculated. The flow then needs to be eval-
uated at the low-pressure side pressure (presumably
relieving pressure) to determine if there is any addi-
tional flashing. This will determine inlet conditions of
the relief valve being used to relieve the tube rupture
flowrate.
Sample calculation. As an example, consider a
slurry/HP steam generator in an FCC unit. The high-
pressure (boiler feed water) side has a design pres-
sure of 600 psig. The low-pressure (FCC slurry) has a
design pressure of 200 psig (PSV relieving pressure =
220 psig). The tubes are 1-in. 10 BWG tubing (length
= 16 ft, inside diameter = 0.782 in, inside cross-section
= 0.4208 in, friction factor = 0.00575). Calculate
flowrate through a fall rupture of e single tube.
xo =0
p= 49.599 Ibyn?
py = 1.992 Ibn?
pr =49.599 1hjn?
Cy =117 Beu/lbF
1) =9488R
Fy =614.7 psia
L=7283 Bey/lb
Continued
THE GENUINE
INTELLIGENT STEAM TRAP
REDUCE COSTS...
of maintenance and
inspection,
Up to 15% eneroy
saving.
STOP LEAKS...!!
Continuous leak and
failure detection on
steam traps and valves.
“BiTherm SmartWatch™™"
A New Concept of Intelligent Valves
Visit us in CHEM SHOW 2001 - New York
23 - 25 October / Booth # 2473
INTELLISENT CONTROL SYSTEMS (1.C.5.)
Web: [Link] Email: purgesa@[Link]|
Distributers in: Argentine, Australia, Eaypt, Tly, Korea, USA,
Portugal, Singapore, Brazil, India.
Circle 78
saflow parameter, w:(Eq. 1):
= (0 49.809/1.302/1- 614.7/0.7728.* 1.992) +
0.28505° 1.17" 948.8 614.7" 49.539
[[v1.ss2- y49.539)/728.3)"
= 6.29
Since w > 1, the flow is flashing (which is as
expected)
‘Step 1: Caleulate compressible.
(Eg. 4):
Step 2: Calculate the pressure ratio,
Tig = 0.6055 + 0.1356(In6.29) ~ 0.0131{1n6.29)”
ag =0811
Check with Ba, 3:
sit? +(.20?~2+625)1-0s14)? +2*625%In(0812)+
2*6.29%(1- 0811)
Song = 0.811 is acurat
Step 3: Calculate dimensionless mass flux through
the tubesheet rupture, G;* (Eq. 5):
Since the actual pressure ratio is 234.7/614.7
0.382 and the critical pressure ratio is 0.811, the flow
is critical. Hence,
of =081y(6.29)8
Gf =0823
Step 4: Calculate actual mass flux through the
tubesheet, G (Ib/br/in.?) (Eq. 8
og
G, = 95,820 Ib/hr/in.? :
So total mass flowrate through the tubesheet would
be (Eq. 16):
W; = 95,820 Ib/hr/in.? + 0.4208 in.”
W, = 40,821 Ijin,
700* 9.329(614.7* 49.539)?
Determine mass flux through the tube side of
the broken tube. The compressible flow parameter
is the same:
= 629
Step 1 9):
[e.29ian, +(6.29)
ea
ay
Step 2: Pipe (Bq, 10):
1+
523 | 280 "629-529;
fese-sfu (a
> (seem a]
—f}
29, 629- zn
‘54 HYDROCARBON PROGESSING/ AUGUST 2001
Step 3: Outlet Nozzle (Bq. 11):
Substitute Eq. 11 into Hgs. 9 and 11 to eliminate Gz,
and solve numerically (e.g., on a spreadsheet):
78
nzs0art
Gj «0390
Step 4: Calculate actual mass flux, G (Ib/hr/in.”) (Eq. 14):
Gy = 1,700" 0,190 (614.7" 49.539)
g = 56,422 Ihfhe/in?
So total mass flowrate through the broken tube
would be (Eq. 16):
Wp = 86,421 lb br/in® +0.4208 in?
We = 28,742 lyr
‘The total mass flowrate is :
W = 40,821 + 23,742 = 64,063 Ib/hr
Ifflow was estimated by just doubling the tubesheet
flow, the total would be 80,642 Ib/hr, which is an addi-
tional 25%. This would be a conservative answer while
still remaining in the ballpark, and most probably not
affecting the size of the relief valve that would need to
bbe purchased.
‘To determine the vapor/liquid split for the relief
valve inlet, flash the mixture at the relief valve reliev-
ing pressure (220 psig). In this example, the mass,
fraction of flashed steam would be about 13%, and x,
for the relief valve sizing calculation would be 0.13
except that in this example, the hot slurry side will
vaporize some of the remaining water, giving a higher
x, (perhaps as high as 1.0). This will need to be eval-
uated separately. 7
“tee. tone cd PpAiit Ae ar
Sj “etn ve Paseo is Salty Devine Chil Brinn,
age i oto.
* Late 61 enon Corin Onegin Honsgscnus Bulan
tig Chats Hon ATCAE Jura Oc 1588
“Lung 6, “Dashy Sas Rea Bre ad ipog he Tro Foae Flom” Chena
Regiirg Prgms Deca 8. 280
1 AS ices ii ests a
1 De te epee Sey Rae le Sf wo Phase Fr” a ne.
Signa con, rane le Send re
sence nnnnennteesrernninmcrtiee