API Std 650 Storage Tank
Data Sheet PAGE 1
* For boxes marked with *, if blank, Mfr. Shall determine and submit as per Appendix L. For all lines, see Appendix L for line-by-line instructions.
GENERAL Special Documentation Package Requirements:
Measurement Units to be used in API Std 650: SI US Customary
1. Manufacturer* Contract No.*
Address*
Mfg. Serial No.* Year Built* Edition & Addendum to API 650* 12th Edition-Latest
2. Purchaser Contract No.
Address
Tank Designation
3. Owner/Operator Location Kuwait
4. Size Limitations* Tank Diameter* 15m Shell Height*
Capacity: Maximum* Net Working* 1193 m 3
Criteria*
5. Products Stored:
Liquid Crude Oil Max. S.G.: 1.02 at 15.56 ° C
Blanketing Gas Vapor Pressure 13 PSIA at Max. Operating Temp.
% Aromatic Suppl. Spec. H2S Service? Yes No Suppl. Spec.
Other Special Service Conditions? Yes No Suppl. Spec.
DESIGN AND TESTING Purchaser to Review Design Prior to Ordering Material? Yes No
6. Applicable API Standard 650 Appendices:* A B C F G H I J L M O P S U V
7. Max. Design. Temp. ° Design Metal Temp.* ° Design Liquid Level* 8.4 m
Design Pressure 6.89 kPa External Pressure -3.44 kPa Maximum Fill Rate 120 m /Hr3
Maximum Emptying Rate
Floatation Considerations? Yes No Flot. Suppl. Spec:* Applied Supplemental Load Spec.
8. Seismic Design? Yes No Appendix E Alternate Seismic Criteria Seismic Use Group
MBE Site Class D Vertical Seismic Design? Yes No Vertical Ground Motion Accelerator AV:
Basis of Lateral Acceleration (Select one): Mapped Seismic Parameters? Ss S1 S0 ; Site-Specific Procedures: MCE
Design Required? Yes No ; Other (Non-ASCE) Methods Sp = 0.075
Freeboard Required for SUG I Design Roof Tie Rods @ Outer Ring?* Yes No
9. Wind Velocity for non-U.S. sites, 50-yr. wind speed (3-sec. Gust)* 162 km/Hr
Top Wind Girder Style* Detail - 'I' Dimensions* Use Top Wind Girder as Walkway? Yes
Intermediate Wind Girders?* Yes No Intermediate Wind Girder Style* Dimensions*
Check Buckling in Corroded Cond.? Yes No
10. Shell Design: 1-Ft Mthd?* Yes No ; Variable-Des-Pt Mthd?* Yes No Alternate ; Elastic Anal. Mthd?* Yes No
Plate Stacking Criteria* Centerline-Stacked? Yes No Flush-Stacked? Yes No Inside Outside
Plate Widths (Shell course heights) and Thicknesses * Numbers below Indicate Course Number.
1. 2400 x 8 2. 2000 x 8 3. 2000 x 8 4. 2000 x 8 5.
6. 7. 8. 9. 10.
11. 12. 13. 14. 15.
Joint Efficiency* % Shell-to-Bottom Weld Type* Shell-to-Bottom Weld Insp. Mthd*
Approvals: Revisions: Title:
By: Ck'd:
Drawing No.: Sheet
OF 7
12th Edition-Latest
Kuwait
8.4m
Maximum Emptying Rate 120 m3/Hr
Seismic Use Group 1
Site-Specific Procedures: MCE
No
Alternate
Date:
Sheet of
API Std 650 Storage Tank
AMETANK Data Sheet PAGE 2
* If box is blank, Manufacturer shall determine and submit as per Appendix L.
11. Open-Top and Fixed Roofs: (See Sheet 6 for Floating Roofs) Open Top?* Yes No
Fixed Roof Type* Cone Roof Support Columns*: Pipe Or Structural Shape
Cone Slope* 1:6 Dome or Umbrella Radius* Weld Joints* Lap
(Lap, Butt, Other)
Seal Weld Underside of: Lap Joints? Yes No ; Seal Weld Underside of Wind Girder Joints? Yes No
Gas-tight? Yes No Joint Efficiency* %
Thickness* 7 mm In. Snow Load* App. Suppl. Load Spec.* Column Lateral Load
Normal Venting Devices* Emergency Venting Devices*
For Non-Frangible Roofs: Seal Weld Roof Plates to Top Angle on the Inside? Yes No ; Weld Rafters to Roof Plates?
Roof-to-Shell Detail* Detai 'I' of Annex -F - Fig F-2 Radial Projection of Horizontal Component of Top Angle* Inward Outward
12. Bottom: Thickness* 10 Style* Cone - Up Slope* 1 : 35 Weld Joint Type* Lap
Provide Drip Ring? Yes No Alternate Spec.
Annular Ring? Yes No Annular Ring: Minimum Radial Width* 750 (min) Thickness* 10 mm
13. Foundation: Furnished by* Type* Ring Wall
Soil Allow: Bearing Pressure* Per Spec.* Anchors: Size* VTC Qty.*
Foundation Design Loads: Base Shear Force: Wind* Seismic* Overturning Moment: Wind* VTC Seismic*
Ring Forces: Weight of Shell + Roof New* Corroded* Roof Live Load* 1.2 kPa Internal Pressure*
Partial Vacuum* Wind* Seismic*
Bottom Forces: Floor Wt. New* Corroded* Product Wt.* Water Wt.* Internal Pressure*
Partial Vacuum* Other Foundation Loads* Min. Projection of Fdn. Above Grade:
14. Responsibility for Heating Water, if Required: Purchaser Manufacturer
Hydro-Test Fill Height* 8.4 m Settlement Measurements Required? Yes No Extended Duration of Hydro-Test:
Predicted Settlement Profile is Attached
Responsibility for Setting Water Quality: Purchaser Manufacturer Supplemental Test Water Quality Spec.
Test Water Source & Disposal Tie-In Locations Hydro-Test Appendix J Tank?
Post-Pressure-Test Activities Required of the Manufacturer: Broom Clean Potable Water Rinse Dry Interior
Other
15. Inspection by in Shop;
Supplemental NDE Responsibility Supplemental NDE Spec.
(Purch., Mfg., Other)
Positive Material Identification? Yes No PMI Requirements:
Max. Plate Thickness for Shearing
Must Welds not exceeding 6 mm (1/4 in.) Be Multi-Pass? Yes No Must Welds greater than 6 mm (1/4 in.) Be Multi-Pass? Yes
Leak Test Mthd: Roof* Shell* As per API 650 Shell Noz./Manhole Reinf. Plt*
Bottom* As per API 650 Floating Roof Components*
Modify or Waive API Dimensional Tolerances (see 7.5)? No Yes Specify:
Specify Additional Tolerances, if any, and Circumferential and Vertical Measurement Locations:
- Allowable Plumbness: Measure and Record at a Minimum of Locations or Every m (ft) around the Tank, at
the Following Shell Heights: (select one box): 1
/3 H, 2/3 H and H Top of Each Shell Course Other:
- Allowable Roundness:** Measure Radius and Record at a Minimum of Locations or Every
around the Tank, at the Following Shell Heights (select one box):
Top of Tank, H 1
/3 H, 2/3 H and H Top of Each Shell Course Other:
**See Data Sheet Instructions for the Maximum Allowable Additional Radial Tolerance.
Approvals: Revisions: Title:
By: Ck'd:
Drawing No.: Sheet
2 OF 7
Lap
Weld Rafters to Roof Plates? Yes No
Outward
Lap
Ring Wall
Qty.* VTC
Seismic* VTC
Internal Pressure* 6.89 kPa
Internal Pressure*
Min. Projection of Fdn. Above Grade:
Extended Duration of Hydro-Test:
Supplemental Test Water Quality Spec.
Yes No
in Field
Yes No
m (ft) around the Tank, at
m (ft)
Date:
Sheet of
API Std 650 Storage Tank
AMETANK Data Sheet PAGE 3
16. Coatings:
Internal Coatings by: Per Spec.* As Per Spec
(Not Req'd., Others, Tank Mfg.)
External Coating by: Per Spec.* As Per Spec
(Not Req'd., Others, Tank Mfg.)
Under-Bottom Coating by: Per Spec.* As per Spec
(Not Req'd., Others, Tank Mfg.)
17. Cathodic Protection System? Yes No Per Spec.*
18. Leak Detection System? Yes No Per Spec.*
19. Release Prevention Barrier? Yes No Per Spec.*
20. Tank Measurement System: Required? Yes No Remote Capability Required? Yes No
By:* Per Spec.*
21. Weight of Tank: Full of Water* Empty* Shipping* Brace/Lift Spec.*
22. References:* API Std 650, Appendix L
23. Remarks:*
1. Nozzle Elevation and Orientation to be confirmed after site visit on contract award
2. the T
Approvals: Revisions: Title:
By: Ck'd:
Drawing No.: Sheet
OF 7
Date:
Sheet of
API Std 650 Storage Tank
AMETANK Data Sheet PAGE 4
* If box is blank, Manufacturer shall determine and submit as per Appendix L.
Table 1 MATERIALS OF CONSTRUCTION
Component Material*/Thickness* C.A. Component Material*
Shell, Course _1__ to _4__ A 283 Gr C - 8 mm 1.6 Reinforcing Pads A 283 Gr C
Shell, Course ___ to ___ Manhole/Nozzle Necks A 283 Gr C / A 106 Gr B
Shell, Course ___ to ___ Manhole/Nozzle Flanges A 283 Gr C / A 105
Shell, Course ___ to ___ Flange Covers A 283 Gr C
Shell, Course ___ to ___ Anchor Attachments A 283 Gr C
Roof A 283 Gr C 1.6 Submerged Piping A 106 Gr B
Bottom A 283 Gr C 3.2 Wetted Structurals A 36 / S275 JR
Annular Ring A 283 Gr C 3.2 Non-wetted Structurals A 36 / S275 JR
+ Check here if C.A. is to apply to each exposed sur
Table 2 BOLTS and ANCHORS
Component Head Type* Bolt or Anchor Material* Nut Material* Thread Series*
Flange Bolting HEX A 193 Gr B7 A 194 Gr 2H UN
Structural Bolting HEX A 327 A563 UN
Anchor Bolts HEX A 307 / BS4190 A 563 UN
UN
++ Total C.A., on the nominal diameter.
Table 3 NOZZLE and MANHOLE SCHEDULE* (for Fixed Roof, Shell, and Bottom)
Neck Sch Full Pen. Proj. to FF or CL Remaks
Size, NPS, or Wall Reinf. Plate On Open. Flange Flange Class or from Datum Gasket Thick.
Mark Service or Dia. (in.) Thick. Dimensions (Y/N) Type or Thick. Lines and Dimen.
Shell Nozzles
N1 Inlet 8" WNRF 150# Note-4
N2 Outlet 8" WNRF 150# Note -5
N3 Level 3" WNRF 150#
N4 Level 3" WNRF 150#
N5 Level 3" WNRF 150#
N6 Level 3" WNRF 150#
N7 Spare 4" WNRF 150# W/ Blind
N8 Drain 3" WNRF 150#
N9 Foam 4" WNRF 150# VTC
Sample
N10 Connection. 1" WNRF 150#
Recirculatio
N11 n Line 3" WNRF 150#
N12 Heating Coil 3" WNRF 150#
N13 Heating Coil 3" WNRF 150#
N14 Spare 3" WNRF 150# W/ Blind
N15 Spare 3" WNRF 150# W/ Blind
N16 Spare 3" WNRF 150# W/ Blind
M1 Clean Out 24" As per API 650 W/ Cover+D
Approvals: Revisions: Title:
By: Ckd:
Drawing No.: Sheet
4 OF 7
MATERIALS OF CONSTRUCTION
Material* C.A.
A 283 Gr C 1.6
A 283 Gr C / A 106 Gr B 1.6
A 283 Gr C / A 105
A 283 Gr C
A 283 Gr C 1.6
A 106 Gr B 1.6
A 36 / S275 JR 1.6 +
A 36 / S275 JR 1.6 +
+ Check here if C.A. is to apply to each exposed surface
e 2 BOLTS and ANCHORS
Thread Series* C.A.
UN ++
UN ++
UN ++
UN
OLE SCHEDULE* (for Fixed Roof, Shell, and Bottom)
Remaks
Note-4
Note -5
W/ Blind
VTC
W/ Blind
W/ Blind
W/ Blind
W/ Cover+Davit
Date:
Sheet of
API Std 650 Storage Tank
AMETANK Data Sheet PAGE 5
* If box is blank, Manufacturer shall determine and submit as per Appendix L.
Table 3 NOZZLE and MANHOLE SCHEDULE* (for Fixed Roof, Shell, and Bottom)
Neck Sch Full Pen. Proj. to FF or CL Remaks
Size, NPS, or Wall Reinf. Plate On Open. Flange Flange Class or from Datum Gasket Thick.
Mark Service or Dia. (in.) Thick. Dimensions (Y/N) Type or Thick. Lines and Dimen.
ROOF Nozzles
N17 VENT 2" WNRF 150# GAS
BLANKET
N18 GAAS 4" WNRF 150# Note -5
Emergenc
N19 y Vent 24" WNRF 150# W/ Emergency
N20 PVSV 6" WNRF 150#
M2 Manhole 24" As per API 650 W / Cover + D
N21 MTG LVL 2" WNRF 150#
N22 Spare 2" WNRF 150# W/ Blind
N23 Spare 2" WNRF 150# W/ Blind
Clean Out 24" As per API 650 W/ Cover+D
Approvals: Revisions: Title:
By: Ckd:
Drawing No.: Sheet
OF 7
OLE SCHEDULE* (for Fixed Roof, Shell, and Bottom)
Remaks
GAS
Note -5
W/ Emergency Vent
W / Cover + Davit
W/ Blind
W/ Blind
W/ Cover+Davit
Date:
Sheet of
API Std 650 Storage Tank
AMETANK Data Sheet PAGE 6
* If box is blank, Manufacturer shall determine and submit as per Appendix L.
OTHER TANK APPURTENANCES
24. Platform, Stairway, and Railing: Galvanizing Req'd?* Yes No Stairway Style* Spiral Walk Surf. Type*
(Straight or Helical)
Stair and Walkway Clear Width* 1000 mm National Safety Standards*
Architectural/Structural Specification*
Gauger's Platform Req'd? Yes No Qty. Req'd* 1 Per Spec.*
25. Jacket Required?* Yes No Other Heaters/Coolers Required?* Yes No
Supplemental Jacket, Heater, or Cooler Specifications*
26. Mixer/Agitator: Quantity Size* Per Spec.*
27. Insulation: Required? Yes No Thickness* Material*
Per Specs* Responsibility for Insulation and Installation
(Purchaser, Manufacturer, Others)
28. Structural Attachments: Lift Lugs?* Yes No Desc.*
Shell Anchorage?* Yes No Type* Scaffold Cable Support?
29. Various Other Items: Welded Flush-Type: Shell Connection Cleanout Fitting Waive Application of Appendix P?
Miscellany #1 Heating Coil Miscellany #2
Miscellany #3 Miscellany #4
Miscellany #5 Miscellany #6
Table 4 OTHER TANK APPURTENANCES*
Service or
Mark Quantity Description Size Orientation Height from Datum Material
Approvals: Revisions: Title:
By: Ck'd:
Drawing No.: Sheet
OF 7
Greating
(Purchaser, Manufacturer, Others)
Yes No
Yes No
THER TANK APPURTENANCES*
Material Remarks
Date:
Sheet of
API Std 650 Storage Tank
AMETANK Data Sheet PAGE 7
* If box is blank, Manufacturer shall determine and submit as per Appendix L.
Tank Plan and Sketches:
Notes:
Approvals: Revisions: Title:
By: Ck'd:
Drawing No.: Sheet
OF 7
Date:
Sheet of