Example Problems for Compression Members
1) Determine the maximum allowable load that can be carried by a compression member of a
braced building frame made of W530x167 section if section made of A-36 steel. Assume the
statical systems for member as shown below.
y
Pa ? Pa ?
x x
y
lx 7m l y 7m W-530x167
For buckling For buckling
in x-direction in y-direction
-Using recommended design value of effective length factors given by AISC table, effective
length factors for column given are
k x 1.0 & k y 0 .8
From table of W-section, section properties for W530x167:
A 21290 mm 2 , rx 226 mm, ry 78.7 mm
-then, slenderness ratio of compression member,
k x .lx 1.0 7000 mm
31.0
rx 226 mm
k y .l y 0.8 7000 mm
71.2
ry 78.7 mm
k .l
-The largest value of control allowable compressive stress. Thus,
r
k .l
71.2
r
-Using tables of allowable compressive stress, interpolating between slenderness ratios of 70
k .l
and 75 for 71.2 Fa 112.4 N mm 2
r
-then, the maximum allowable compressive load that can be carried by the member
Pa Fa . A 112.4 21290 2392.996 103 N 2392.996 kN
1
2) Select the lightest W-section that can carry a service design axial compression of 700kN for
compression member of length 5m. The member may be assumed pinned at top and bottom.
In addition, it has weak direction support at mid height. The column (compression member)
is part of a braced building structure. W-sections are made of A36 steel.
P 700 kN P 700 kN y
x x
2.5 m
Cross-beam
y
5 m
W-section
2.5 m
For buckling For buckling
in y-direction in x-direction
-unsupported lengths of member in both directions are
l x 5000 mm & l y 2500mm
-Effective length factors if ends of column hinged,
k x 1.0 & k y 1.0
-Assuming allowable compressive stress Fa 100 N mm 2 , trial area of section is
obtained as
P 700 103
Areq 7000 mm 2
Fa 100
-then, select trial section from table of W-section with A 7000 mm 2 ,
1st trial : W460x67
A 8520 mm 2 , rx 186 mm, ry 41.2mm
-then, slenderness ratio of trial section,
k x . lx 1.0 5000 mm
26.9
rx 186 mm
k y .ly 1.0 2500 mm
60.7
ry 41.2 mm
k .l
-The largest value of control allowable compressive stress. Thus,
r
k .l
60.7
r
-Using tables of allowable compressive stress, interpolating between slenderness ratios of 60
k .l
and 65 for 60.7 Fa 119.7 N mm 2
r
-then, checking adequacy of trial section
Pa Fa . A 119 .7 8520 1019.844 103 N 1019.844 kN 700 kN
2
therefore, 1st trial is adequate. But, it is not the lightest section. You have to check next lower
trial section.
2st trial : W460x52
A 6640 mm 2 , rx 179 mm, ry 31.2mm
-then, slenderness ratio of trial section,
k x . lx 1.0 5000 mm
27.9
rx 179 mm
k y .ly 1.0 2500 mm
80.1
ry 31.2 mm
k .l
-The largest value of control allowable compressive stress. Thus,
r
k .l
80.1
r
-Using tables of allowable compressive stress, interpolating between slenderness ratios of 80
k .l
and 85 for 80.1 Fa 105.8 N mm 2
r
-then, checking adequacy of trial section
Pa Fa . A 105.8 6640 702.512 103 N 702.512 kN 700 kN
2st trial is adequate. Therefore, W460x52 can be selected as the lightest section for
compression member
3) Determine the maximum allowable load that can be carried by a compression member made
of built-up section as shown below. Both components of built-up section are made of A-36
steel. Assume the column is pin-ended in both directions having a length of 5.25m.
_
y y
C-310x45
x x
y
S-380x74 y
-Section properties of one C-310x45:
A 5690 mm 2 , t w 13 mm,
_
y 17.1mm x x d
I x 2.14 10 mm 6 4
I y 67.4 10 mm
6 4
-Section properties of one S-380x74:
A 9480 mm 2 , d 381 mm
y y
I x 202 10 mm 4 6
I y 6.53 10 6 mm 4
_
-Section properties of built-up section: a
A 5690 9480 15170 mm 2 x x
I y 67.4 6.53 10 73.93 10 mm
6 6 4
_
A. y 5690 17.1 9480 13 381 / 2
a 133.6 mm
A 5690 9480 y
3
I x 2.14 202 106 5690 133.6 17.1 9480 381/ 2 13 133.6 327.69 106 mm
2 2
Iy 73.93 10 6
ry 69.8 mm
A 15170
Ix 327.69 10 6
rx 147 mm
A 15170
-Effective length factors if ends of column hinged,
k x 1.0 & k y 1.0
-then, slenderness ratio of member,
k x .lx 1.0 5250 mm
35.7
rx 147 mm
k y .ly 1.0 5250 mm
75.2
ry 69.8 mm
k .l
-The largest value of control allowable compressive stress. Thus,
r
k .l
75.2
r
-Using tables of allowable compressive stress, interpolating between slenderness ratios of 75
k .l
and 80 for 75.2 Fa 109.45 N mm 2
r
-then, the maximum allowable compressive load that can be carried by the member
Pa Fa . A 109.45 15170 1660.356103 N 1660.356 kN
4) Determine the maximum allowable load that can be carried by a compression member made
of double angles sections, 2L76x51x6.4 with longer legs back to back connected to opposite
sides of 10mm thick gusset-plate by bolts as shown below. The effective length of column is
equal to 3.4m, and they are the same in both directions. Assume sufficient tacking bolts with
spacer-plates have been provided along the length of member. Section is made of A-36 steel.
y t gusset 10 mm
plate
y'
76 mm
x x
y'
_
x
y
-Section properties of one L76x51x6.4:
_
A 768 mm 2 , rx 24.3 mm, x 12.5mm, I y 0.163 10 6 mm 4
-Section properties of double angles 2 L76x51x6.4:
A 2 768 1536 mm 2
rx 24.3 mm (the same as for single angle)
4
I y I y0 A . d x2 2 0.163 106 2 768 12.5 10 / 2 796.4 103 mm 4
2
Iy 796.4 103
ry 22.77 mm
A 1536
-effective length factors if ends of column hinged,
k x 1.0 & k y 1.0
-then, slenderness ratio of member,
k x . lx 1.0 3400 mm
139.9
rx 24.3 mm
k y .ly 1.0 3400 mm
149.3
ry 22.77 mm
k .l
-The largest value of control allowable compressive stress. Thus,
r
k .l
149.3
r
-Using tables of allowable compressive stress, interpolating between slenderness ratios of 145
k .l
and 150 for 149.3 Fa 46.248 N mm 2
r
-then, the maximum allowable compressive load that can be carried by the member
Pa Fa . A 46.248 1536 71.037 103 N 71.037 kN
5) a) Design a built-up section for column to supports a service design axial compressive load of
1250kN using double channel section placed back to back spaced at desired distance. The
channel sections are effectively held at desired position using adequate lacing system. The
effective length of column is equal to 6.4m. Channel section is made of A-36 steel.
b) Design also the lacing system for built-up section.
Solution
a) Design of built-up section using double channels placed back to back
V (transverse shear )
40 mm 40 mm
y F (t )
F (c )
x x lC
leL
y 450
bf s b f 80 mm
40 mm s 40 mm
5
-Assuming allowable comp. stress Fa 120 N mm 2 , trial area of built-up section is,
P 1250 103
Areq 10416.7 mm 2
Fa 120
and, required area of one channel section is
Ag (one channel ) 10416.7 2 5208.35 mm 2
-then, select trial channel section from table with, A 5208.35 mm 2
1st trial : 2C-310x45 section placed back to back at desired spacing
For one C-310x45 section:
_
Ag 5690 mm 2 , x 17.1 mm, rx 109 mm, ry 19.4 mm,
I x 67.4 106 mm 4 , I y 2.14 106 mm 4 , b f 80mm
For double channels A 2 5690 11380 mm ,
2
-for efficient section of compression member made of built-up, section may be
proportioned using rx ry I x I y
then, rmin rx 109 mm (the same as for single channel section)
-effective length factors if ends of column hinged,
k x 1.0 & k y 1.0
-then, slenderness ratio of trial section,
k .l 1.0 6400 mm
58.7
r 109 mm
-Using tables of allowable compressive stress, interpolating between slenderness ratios of 55
k .l
and 60 for 58.7 Fa 121 N mm 2
r
-then, checking adequacy of trial section
Pa Fa . A 121 11380 1376.98 103 N 1376.98 kN 1250 kN
therefore, trial section is adequate if channels are spaced at desired position.
-To locate spacing between channels for efficient built-up section may be determined using,
Ix Iy
where I x 2 I x0 2 67.4 106 134.8 106 mm 4
I y 2 I y0 2 Ag0 . s 2 x 2 2.14 106 2 5690 s 2 17.1
2 2
Equating the two moment of inertias
134.8 10 6 4.28 10 6 11380 s 2 17.1
2
simplifying, s 2 17.1 11469 .244
2
s 2 17.1 107.09
s 179.989 mm 180 mm
therefore, 2C-310x45 spaced 180mm between back of the channels may be used for column
b) Design of lacing system
-assuming a single lacing system inclined at 450 , spacing of lacing bars connection if edge
distance from line of bolts is 40mm,
l C 2 s 2 40 / tan 450 2180 80 / tan 450 520 mm
C
C
rmin of each channel section = ry 19.4 mm
-then, checking slenderness ratio of each channel section between lacings connection (IS:800)
6
lC 520 50
26.8
rmin 19.4 0.7l r comp. member 0.7 58.7 41.09
ok!
C
-effective length of lacing bars,
leL s 2 40 sin 450 180 80 sin 450 367.7 mm
-minimum thickness of lacing bar (IS:800 & AISC),
lL 367.7
tL e 9.2 mm use t L 10 mm
40 40
-minimum width of lacing bar if 20mm diameter bolts are used (IS:800 & AISC),
b L 3b 3 20 60 mm
-Try 60mm x 10mm flat solid bars for lacing connected by 20mm diameter bolts:
Checking slenderness ratio of trial lacing bar section,
leL 12 leL 12 267.7
127.4 145 0k!
rmin t 10
-allowable compressive stress of lacing bar for l r 127.4
FaL 63.5 N mm 2
-transverse shear force to be resisted by lacing bars (IS:800),
V 0.025 P 0.025 1250 kN 31.25 kN
-then, axial tensile and compressive forces developed in lacing bars due to transverse shear
from force equilibrium,
V 31.25
F 22.1 kN
2 sin 2 sin 450
-then, checking tensile and compressive stresses in the lacing bars:
F 22.1 103
ft 57.4 N mm 2 Ft 0.6 Fy 0.6 250 150 N mm 2
An 60 21.5 10
ok!
F 22.1 103
and, fc 36.83 N mm 2 FaL 63.5 N mm 2
Ag 60 10
ok!
Therefore, use single lacing system made of 60mm x 10mm flat solid bars placed 450 from
vertical at the two faces of the double channel section.
End tie-plate required:
-tie-plate shall have a thickness at least equal to 1/50 of the distance between lines of bolts,
t = (180+2x40)/50 = 5.2mm take t = 6mm
-length of tie-plate is equal to the distance between lines of bolts,
l = (180+2x40) = 260mm take l = 260mm
-width of tie-plate, b = (180+2bf) = (180+2x80) = 340 mm take b = 340mm
-therefore, use end tie-plate 6mm x 260mm x 340mm
7
Exercise Problems
1) It is desired to design a column for compression member to support a service design axial
compression of 6490kN using A-36 steel with effective length of 3.65m and they are the
same in both direction. A W360x202 is on hand with a good supply of 25mm thick plates.
Design cover-plates to be connected to the flanges of W-section to enable the column to
support the required load. Ans: PL-445mm x 25mm
y
PL b p 25 mm
W 360 202
x x
PL b p 25 mm
y
2) Assuming axial loads only, select W-section for an interior column of the laterally braced
2
frame as shown below. Use A-50 steel ( Fy 345 N mm ). Each column section can be
used for one or two stories before it is spliced, whichever seems advisable. Select among
W360 depth group.
Miscellaneous Data:
-Weight of reinforced concrete = 24 kN m 3
-Live load on roof = 1.5 kN m 2
-Weight of roof finishes = 0.3 kN m 2
-Live load on interior floors = 4.0 kN m 2
-Weight of floor finishes & partition load = 0.7 kN m 2
All joints are assumed to be pinned so as to simplify calculations. Spacing of frames are 9m
on centers. Neglect weight of beams and columns.
100mm re inf orced concrete slab
150mm re inf orced 3.6 m
concrete slab
3.6 m
3.6 m
3.6 m
12 m 12 m 12 m
9m
column beam
9m
8