Technical Data Sheet

This document provides specifications for 31 fans used for exhaust in various locations of a building. For each fan, it lists the air volume and static pressure, outlet velocity and power output, total efficiency and noise level, motor specifications including location. The fans include backward curved centrifugal, cabinet, circular inline and rectangular inline types ranging from 150 to 24900 CFM and 25 to 65 mmWG static pressure.

Uploaded by

Aamir Shaikh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
268 views6 pages

Technical Data Sheet

This document provides specifications for 31 fans used for exhaust in various locations of a building. For each fan, it lists the air volume and static pressure, outlet velocity and power output, total efficiency and noise level, motor specifications including location. The fans include backward curved centrifugal, cabinet, circular inline and rectangular inline types ranging from 150 to 24900 CFM and 25 to 65 mmWG static pressure.

Uploaded by

Aamir Shaikh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd

Outlet Vel. Abs.

Power (Bkw) Noise Level Motor


Air Volume St. Pr. m/s Total Eff. dB(A)
Location- Application @ 3m Fan RPM
(CFM) (MMWG) % KW Pole
Sr. No Fan Type
1 12500 65 SISW Backward Curved belt driven Basement Plant 11.01 5.75 72.9 71 963 7.5 6
Centrifugal Fan Room- Exhaust air

2 12620 65 SISW Backward curved belt driven Terrace- Kitchen 11.11 5.84 72.6 71 968 7.5 6
centrifugal fan. (Bearing outside the Airflow Exhaust
path)
3 24900 65 SISW Backward Curved belt driven Terrace- Loundry- 11.11 11.5 73 73 697 15 6
Centrifugal Fan Exhaust air

4 10000 40 Cabinet type Belt driven Backward curved Basement- Exhaust 9.26 3.33 62.9 69 1156 5.5 4
centrifugal Fan Air

5 13000 35 Cabinet type Belt driven Backward curved Basement- Exhaust 9.59 3.67 66.7 69 993 5.5 6
centrifugal Fan Air

6 3900 35 Cabinet type Belt driven Backward curved Basement- Exhaust 9.01 1.15 62.7 65 1733 1.5 4
centrifugal Fan Air

7 650 30 Circular type Inline Fans Basement- Exhaust Available sp= 24 mmwg 60 2600 0.24 2
Air

7A 650 30 Rectangular type Direct driven Inline Fans Basement- Exhaust Available sp= 34 mmwg 57 1200 0.245 4
Air

8 550 30 Circular type Inline Fans Basement- Exhaust Available sp= 31 mmwg 60 2600 0.24 2
Air

9 1100 32 Cabinet type Belt driven Backward curved Lower Ground- 6.26 0.27 65.4 59 2283 0.37 2
centrifugal Fan Exhaust Air

10 1800 32 Cabinet type Belt driven Backward curved Lower Ground- 8.17 0.48 63.7 61 2275 0.75 2
centrifugal Fan Exhaust Air

11 1650 40 Cabinet type Belt driven Backward curved Lower Ground- 7.49 0.5 67.5 61 2326 0.75 2
centrifugal Fan Exhaust Air

12 1350 35 Cabinet type Belt driven Backward curved Lower Ground- 7.69 0.39 63.3 62 2549 0.55 2
centrifugal Fan Exhaust Air

13 1000 35 Cabinet type Belt driven Backward curved Lower Ground- 7.15 0.29 61.4 61 2810 0.55 2
centrifugal Fan Exhaust Air

14 10500 35 Cabinet type Belt driven Backward curved Lower Ground- 9.72 3.37 58.9 69 1158 5.5 4
centrifugal Fan Exhaust Air

15 4300 35 Cabinet type Belt driven Backward curved Lower Ground- 7.93 1.15 67.2 63 1439 1.5 4
centrifugal Fan Exhaust Air

16 750 35 Cabinet type Belt driven Backward curved Lower Ground- 5.37 0.2 64.2 57 2513 0.37 2
centrifugal Fan Exhaust Air

17 450 32 Circular type Inline Fans Lower Ground- Available sp= 40 mmwg 60 2600 0.24 2
Exhaust Air

18 400 32 Circular type Inline Fans Lower Ground- Available sp= 44 mmwg 60 2600 0.24 2
Exhaust Air

19 2650 35 Cabinet type Belt driven Backward curved Lower Ground- 9.65 0.79 63.8 65 2236 1.1 2
centrifugal Fan Exhaust Air

20 700 32 Cabinet type Belt driven Backward curved Lower Ground- 5.01 0.17 64 56 2386 0.37 2
centrifugal Fan Exhaust Air

21 620 32 Circular type Inline Fans Lower Ground- Available sp= 26 mmwg 60 2600 0.24 2
Exhaust Air

21A 620 32 Rectangular type Direct driven Inline Fans Lower Ground- Available sp= 34 mmwg 57 1200 0.245 4
Exhaust Air

22 4900 40 Cabinet type Belt driven Backward curved Lower Ground- 9.04 1.56 65.6 66 1591 2.2 4
centrifugal Fan Exhaust Air

23 300 25 Circular type Inline Fans Upper Ground- Available sp= 27 mmwg 57 2500 0.141 2
Exhaust Air

24 150 25 Circular type Inline Fans Upper Ground- Available sp= 30 mmwg 59 2650 0.121 2
Exhaust Air

25 250 25 Circular type Inline Fans Upper Ground- Available sp= 33 mmwg 57 2500 0.141 2
Exhaust Air

26 900 25 Cabinet type Belt driven Backward curved Upper Ground- 6.44 0.19 60.3 57 2449 0.37 2
centrifugal Fan Exhaust Air

27 9320 35 Cabinet type Belt driven Backward curved Upper Ground- 8.63 2.71 63 66 1079 3.7 4
centrifugal Fan Exhaust Air

28 750 30 Cabinet type Belt driven Backward curved Upper Ground- 5.37 0.17 64.2 56 2385 0.37 2
centrifugal Fan Exhaust Air

29 1100 40 Cabinet type Belt driven Backward curved First Floor- Exhaust 6.26 0.33 66.1 61 2455 0.55 2
centrifugal Fan Air
30 950 40 Cabinet type Belt driven Backward curved First Floor- Exhaust 6.8 0.3 63.3 61 2851 0.55 2
centrifugal Fan Air

31 2000 32 Cabinet type Belt driven Backward curved Second Floor- 7.29 0.47 70.1 59 1898 0.75 4
centrifugal Fan Exhaust Air

32 400 32 Circular type Inline Fans Second Floor- Available sp= 44 mmwg 60 2600 0.24 2
Exhaust Air

33 400 32 Circular type Inline Fans Third Floor- Exhaust Available sp= 44 mmwg 60 2600 0.24 2
Air

34 600 32 Circular type Inline Fans Third Floor- Exhaust Available sp= 27 mmwg 60 2600 0.24 2
Air

34A 600 32 Rectangular type Direct driven Inline Fans Third Floor- Exhaust Available sp= 35 mmwg 57 1200 0.245 4
Air

35 350 32 Circular type Inline Fans Third Floor- Exhaust Available sp= 49 mmwg 60 2600 0.24 2
Air

36 300 32 Circular type Inline Fans Third Floor- Exhaust Available sp= 34 mmwg 59 2600 0.14 2
Air

37 800 40 Cabinet type Belt driven Backward curved Fourth Floor- Exhaust 5.72 0.25 64.2 59 2684 0.37 2
centrifugal Fan Air

38 600 32 Circular type Inline Fans sixth Floor- Exhaust Available sp= 27 mmwg 60 2600 0.24 2
Air

39 700 40 Cabinet type Belt driven Backward curved sixth Floor- Exhaust 5.01 0.22 62.3 57 2596 0.37 2
centrifugal Fan Air

40 200 25 Circular type Inline Fans sixth Floor- Exhaust Available sp= 26 mmwg 59 2650 0.121 2
Air

41 400 32 Circular type Inline Fans Seventh Floor- Available sp= 44 mmwg 60 2600 0.24 2
Exhaust Air

42 300 32 Circular type Inline Fans Seventh Floor- Available sp= 34 mmwg 59 2600 0.14 2
Exhaust Air

43 200 25 Circular type Inline Fans Seventh Floor- Available sp= 26 mmwg 59 2650 0.121 2
Exhaust Air

44 100 25 Circular type Inline Fans Eighth Floor- Exhaust Available sp= 33 mmwg 59 2650 0.121 2
Air

45 450 25 Circular type Inline Fans Eighth Floor- Exhaust Available sp= 40 mmwg 60 2600 0.24 2
Air

46 950 25 Cabinet type Belt driven Backward curved Eighth Floor- Exhaust 6.8 0.21 59.2 58 2517 0.37 2
centrifugal Fan Air

47 100 25 Circular type Inline Fans Nineth Floor- Available sp= 33 mmwg 59 2650 0.121 2
Exhaust Air

48 500 25 Circular type Inline Fans Tenth Floor- Exhaust Available sp= 36 mmwg 60 2600 0.24 2
Air

49 9100 45 Cabinet type Belt driven Backward curved Basement- Fresh Air 10.56 3.66 59.6 72 1434 5.5 4
centrifugal Fan

50 11250 65 Cabinet type Belt driven Backward curved Basement- Fresh Air 10.41 5.58 67 74 1379 7.5 4
centrifugal Fan

51 11700 40 Cabinet type Belt driven Backward curved Basement- Fresh Air 8.63 3.37 71.7 67 971 5.5 6
centrifugal Fan

52 3500 40 Cabinet type Belt driven Backward curved Basement- Fresh Air 8.09 1.06 67.3 62 1688 1.5 4
centrifugal Fan

53 1650 40 Cabinet type Belt driven Backward curved Lower Ground- Fresh 7.49 0.5 67.5 61 2326 0.75 2
centrifugal Fan Air

54 1500 40 Cabinet type Belt driven Backward curved Lower Ground- Fresh 6.81 0.44 68.3 60 2248 0.75 2
centrifugal Fan Air

55 1200 40 Cabinet type Belt driven Backward curved Lower Ground- Fresh 6.83 0.37 65.6 62 2529 0.55 2
centrifugal Fan Air

56 900 40 Cabinet type Belt driven Backward curved Lower Ground- Fresh 6.44 0.28 63.9 60 2792 0.55 2
centrifugal Fan Air

57 3900 40 Cabinet type Belt driven Backward curved Lower Ground- Fresh 9.01 1.26 64.7 65 1784 1.5 4
centrifugal Fan Air

58 11400 45 Cabinet type Belt driven Backward curved Lower Ground- Fresh 8.41 3.52 73.9 67 990 5.5 6
centrifugal Fan Air

59 2400 40 Cabinet type Belt driven Backward curved Lower Ground- Fresh 8.74 0.74 68.5 64 2193 1.1 2
centrifugal Fan Air

60 22400 45 Cabinet type Belt driven Backward curved Lower Ground- Fresh 10.45 7.73 69.4 72 867 11 6
centrifugal Fan Air
61 4410 40 Cabinet type Belt driven Backward curved Lower Ground- Fresh 8.13 1.32 68.2 64 1507 2.2 4
centrifugal Fan Air

62 8388 35 Cabinet type Belt driven Backward curved upper Ground- Fresh 9.73 2.73 58.1 70 1299 5.5 4
centrifugal Fan Air

63 1800 32 Cabinet type Belt driven Backward curved Second Floor- fresh 8.17 0.48 63.7 61 2275 0.75 2
centrifugal Fan Air

64 1000 32 DIDW Backward curved Belt driven Smoke Smoke Evacuation & 5.7 0.24 66 58 2208 0.37 2
spill Centrifugal fan with Cabinet Defumigation

65 23270 32 Vane Axial fans Lift well 17.53 8.02 70.7 81 1450 11 4
pressurization

66 20250 32 Vane Axial fans Lift well 19.23 8.82 59.6 82 1450 11 4
pressurization

67 16500 35 Vane Axial fans Basement- 10.08 4.82 68.4 71 950 5.5 6
Smokespill

68 42900 35 Vane Axial fans Basement- 13.32 12.6 74.5 78 950 15 6


Smokespill

69 27100 35 Vane Axial fans Basement- 10.67 8.76 64 78 950 11 6


Smokespill

70 6480/3240 - Jet fans rated at 300 Deg. C. for 2 Hrs. - 18.2/9.1 1.33/0.1 - 58/43 2850/1 1.50/0.30 2/4
CMH 7 450

70A 4500/2250 - Jet fans rated at 300 Deg. C. for 2 Hrs. - 16.0/8.0 0.74/0.1 - 54/38 2850/1 0.90/0.18 2/4
CMH 0 450

71 - - CO Sensors (without display)

72 - - Steady state CFD Analysis

73 450 - Wall Mounted Propeller fans Exhaust Air for toilets Free Flow 48 1300 0.03 4
& Pantry Area

74 350 - Wall Mounted Propeller fans Exhaust Air for toilets Free Flow 42 1300 0.022 4
& Pantry Area

75 300 - Wall Mounted Propeller fans Exhaust Air for toilets Free Flow 42 1300 0.022 4
& Pantry Area

76 250 - Wall Mounted Propeller fans Exhaust Air for toilets Free Flow 42 1300 0.022 4
& Pantry Area

77 200 - Wall Mounted Propeller fans Exhaust Air for toilets Free Flow 36 1300 0.016 4
& Pantry Area

78 150 - Wall Mounted Propeller fans Exhaust Air for toilets Free Flow 36 1300 0.016 4
& Pantry Area

79 100 - Slimline axial fan Exhaust Air for toilets Free Flow 47 2200 0.035 2
& Pantry Area

80 16500 35 Vane Axial fans Basement (Normal + 10.08 4.82 68.4 71 950 5.5 6
Fire)

81 42900 35 Vane Axial fans Basement (Normal + 13.32 12.6 74.5 78 950 15 6
Fire)

82 27100 35 Vane Axial fans Basement (Normal + 10.67 8.76 64 78 950 11 6


Fire)
Motor

Prot Phase Ins


Qty
IP55 III F 1

IP55 III F 1

IP55 III F 1

IP55 III F 1

IP55 III F 1

IP55 III F 1

IP44 I B 2

IP21 I F RO

IP44 I B 1

IP55 III F 1

IP55 III F 1

IP55 III F 1

IP55 III F 1

IP55 III F 1

IP55 III F 1

IP55 III F 1

IP55 III F 1

IP44 I B 2

IP44 I B 1

IP55 III F 1

IP55 III F 1

IP44 I B 1

IP21 I F RO

IP55 III F 1

IP44 I B 1

IP44 I B 2

IP44 I B 2

IP55 III F 1

IP55 III F 1

IP55 III F 1

IP55 III F 1
IP55 III F 1

IP55 III F 1

IP44 I B 1

IP44 I B 2

IP44 I B 1

IP21 I F RO

IP44 I B 1

IP44 I B 1

IP55 III F 1

IP44 I B 1

IP55 III F 1

IP44 I B 1

IP44 I B 1

IP44 I B 1

IP44 I B 1

IP44 I B 1

IP44 I B 1

IP55 III F 1

IP44 I B 1

IP44 I B 1

IP55 III F 1

IP55 III F 1

IP55 III F 1

IP55 III F 1

IP55 III F 1

IP55 III F 1

IP55 III F 1

IP55 III F 1

IP55 III F 1

IP55 III F 1

IP55 III F 1

IP55 III F 1
IP55 III F 1

IP55 III F 1

IP55 III F 1

IP55 III F 12

IP55 III F 10

IP55 III F 2

IP55 III H 2

IP55 III H 2

IP55 III H 2

IP55 III H 9

IP55 III H RO

20

IP44 I B 1

IP44 I B 2

IP44 I B 3

IP44 I B 8

IP44 I B 11

IP44 I B 72

- I - 209

IP55 III H 2

IP55 III H 2

IP55 III H 2