RC Elevated Water Tank Design Guide

This document provides design data and calculations for the reinforcement of a rectangular elevated water tank without a key beam. The tank has dimensions of 6m x 6m x 2m. Reinforcement is designed for the wall, roof slab, and base slab to resist water pressure, bending moments, and tensile forces. Horizontal and vertical reinforcement quantities are calculated and spacing requirements are checked to code standards.

Uploaded by

Chhour CE
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
100% found this document useful (3 votes)
2K views10 pages

RC Elevated Water Tank Design Guide

This document provides design data and calculations for the reinforcement of a rectangular elevated water tank without a key beam. The tank has dimensions of 6m x 6m x 2m. Reinforcement is designed for the wall, roof slab, and base slab to resist water pressure, bending moments, and tensile forces. Horizontal and vertical reinforcement quantities are calculated and spacing requirements are checked to code standards.

Uploaded by

Chhour CE
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
  • Water Tank Design Parameters: Details the design input data and geometry of the water tank, specifying material properties and tank dimensions.
  • Reinforcement Design: Explains external and vertical forces in the design, including key beam requirements and reinforcement details according to standards.
  • Base Slab Design Analysis: Covers analyses such as shear force, bending moment, and slab reinforcement designs for stability and strength calculations.
  • Material Specifications: Lists specifications for materials including types of tanks and reinforcement bars required for various conditions.

RC Water Tank Design Ref.

ACI31

Design Data Input

Type of Water Tanks = Elevated or overhead Tank Without Key beam

Material Property L
Concrete strength, f'c = 30 Mpa
Unit-weight of concrete, ϒb = 25 kN/m3
Top View B
Reinf. Yeild strength, fy = 390 Mpa
Unit-weight of water, ϒw = 10 kN/m3
Hinge supported at the top of the Wall
Tank Geometry
Width of Tank, B = 6 m Slab Slab
Length of Tank, L = 6 m Elevation View H
Height of Tank, H = 2 m
Thickness of Wall, tw = 0.25 m LxB
Wall Thickness, tw,min = 0.25 m Fixe supported at the base of the Wall
Width of strip considered, Strip = 1 m, Fixed
Effective depth, d = 0.174 m
Cover, Cc = 0.04 m

Elastic modulus of steel, Es = 200000 Mpa Vertical Reinforcement, DB = 22


Elastic modulus of concrete, Ec = 25743.0 Mpa Horizontal Reinforcement, DB = 25

RC Water Tank Design [Link]


sv sv
Horizontal Reinforcement Design sh
sh
In the direction L sh
e= 0.074 m Eccentricity sh
Mn = 47.073 kN.m per 1m sh
Rn = 1.55479588 Mpa per 1m sh
ρ = 0.00459 per 1m B
As,L = 798.80 mm2 Arr. Horizontal [Link] Long Dir DB25 @

Mn = 47.073 kN.m per 1m


Rn = 1.55479588 Mpa per 1m
ρ = 0.00459078 per 1m
As,B = 798.796028 mm2 Arr. Horizontal [Link] Short Dir DB25 @
Ref. ACI318M-14 RC Water Tank Design Re

External Forces Design NOTE: KEY BEAM IS REQUIRED WHEN

P_w = 15 kN/m2 Water Pressure.


M_c,H = -45 kN.m Horizontal bending moment at support
M_L,H = 22.5 kN.m Horizontal bending moment at Mid-span in Dir
Support Type M_B,H = 22.5 kN.m Horizontal bending moment at Mid-span in Dir

Hinged/Pinned M_u,pos = 2.388 kN.m Vertical positve bending moment


Roof slab M_u,neg = 5.333 kN.m Vertical negative bending moment

[Link] T_L = 45.000 kN Tensile Force in Dir. L


T_B = 45.000 kN Tensile Force in Dir. B

Vertical Reinforcement Desig ACI350M-06 + AC318M-14


Fixed base
Cs = 1.3 Flexrure Sanitary Coefficient
Mn = 13.0963 kN.m φ = 0.9
Ru = 0.432564 Mpa per 1m
ρ = 0.001244 per 1m
As,trial = 216.4931 mm2 [Link] required per 1m
T As,min = 825 mm2 Minimum Reinf. Per 1m
T As,req = 825 mm2 Reinf. Required per 1m
As,pro = 1140.398 mm2 per 1m
S,max = 0.31 m Arr. Of Vertical Reinf. In L&B

Ref.ACI318M-14 RC Water Tank Design


sv sv
Base Slab Reinforcement Design
Thk Slab = 0.35 m
Load Applied
Finishing = 1.10 kN/m2
Self-weight = 8.75 kN/m2
Weight of side Wall = 6.25 kN/m2
B
960 Total DeadLoad = 16.10 kN/m2

Live Load = 20.00 kN/m2 Water DownWard Pressure


Wu = 53.32 kN/m2 Total DownWard .Pressure
309.2308
Ref. ACI318M-14 RC Water Tank Design Ref. ACI318M-14

IS REQUIRED WHEN ρ IS NEGATIVE. Shear Design & Check at the base of Base Slab

Vu = 183.954 kN Shear Force of Base Slab


moment at support φVc = 203.6843 OK!
moment at Mid-span in Direction of L
moment at Mid-span in Direction of B

ing moment
nding moment

DB22 @ 300

Ref.ACI318M-14

Bending Moment of the base slab

Mu,neg = 191.952 kN.m Fixed end moments Mn,pos = 152.3429


Mu,pos = 137.1086 kN.m Positive at midspan Ru,pos = 1.721267
β = 0.835714 ρ = 0.005103
ρ,min = 0.00359 minimum [Link] Fixed end moment As, req = 1518.151 mm2 For [Link]
d = 0.2975 m n =3
Mn,neg = 213.28 kN.m Resist. of Mu,neg DB25 @ 460 [Link] Reinf.
Ru,neg = 2.409773 Mpa
ρ = 0.00727 ρ,sh = 0.0018
As,req = 2162.698 mm2 [Link] of Fixed end moment As,sh = 630 mm2
n4 PCs S,max = 0.7 m
DB25 @ 307 Arr. Of Fixed end moment DB25 @ 200 Shrinkage Reinf.
Ref. ACI318M-14

Force of Base Slab

Ref.ACI318M-14

For [Link]

[Link] Reinf.
Shrinkage Reinf.
Resting on ground Tank Without Key beam 10 M10
Elevated or overhead Tank Without Key beam 15 M15
Underground Tank Without Key Beam 20 M20
25 M25
30 M30
35 M35
Hinged/Pinned 40 M40
45 M45
50 M50
3 250 130 Flexrure 1.3
5 415 230 Direct Tension 1.65
7 500 275 Shear 1.3
8.5
10
11.5
13
14.5