Ferrocement Cut Off Trench Design for Dams

The document discusses using ferrocement technology for cut-off trenches in earthen dams as a more environmentally friendly alternative to using black cotton soil. It presents a case study of Bham Dam in India where ferrocement panels could save approximately 2.78 lakh tons of fertile soil. Seepage analysis was conducted using GeoStudio 2012 to analyze the dam's behavior and determine pressure conditions of 29m total head and 6.112kg/cm^2 saturated soil pressure.

Uploaded by

Priyanka Soni
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
168 views5 pages

Ferrocement Cut Off Trench Design for Dams

The document discusses using ferrocement technology for cut-off trenches in earthen dams as a more environmentally friendly alternative to using black cotton soil. It presents a case study of Bham Dam in India where ferrocement panels could save approximately 2.78 lakh tons of fertile soil. Seepage analysis was conducted using GeoStudio 2012 to analyze the dam's behavior and determine pressure conditions of 29m total head and 6.112kg/cm^2 saturated soil pressure.

Uploaded by

Priyanka Soni
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

Long-Term Behaviour and Environmentally Friendly Rehabilitation Technologies of Dams (LTBD 2017) DOI:10.

3217/978-3-85125-564-5-062

Analysis and Design of Ferrocement Cut Off Trench in Earthen


Dam: A Case Study of Bham Dam

Sunil Kute1, Patil N. P.2, Ebrahim Farajpour Bonab3, Susmit Kute4


1- Professor, Department of Civil Engineering, K.K.W. Institute of Engg. Edu. and Res. Nashik, India
2- Assistant Professor, S.N.D.T. College of Engg. Yeola, Dist. Nashik, Maharashtra, India
3- Road and Building Expert, East Azerbaijan State, Bonab City, Governor-ate, Iran
4-Student, K.B.T. College of Engg., Nashik, Maharashtra, India

Email: [email protected].

Abstract
Cut off trench (COT) in the section of earthen dam is made up with impervious layer of black cotton soil.
Large amount of fertile land is invested to maintain the impervious layer in cut off zone. This paper presents
analyis and design of ferrocement cut off trench. Geo Studio 2012 software is used for analytical studies of
cut off trench and various soil investigations are done with experimental investigation. A case study of Bham
Dam located in Igatpuri, Nashik (India) is analyzed for investigations and design of ferrocement cut off
trench. By designing the cutoff trench with ferrocement, thousands of tons of black cotton soil can be saved.
It takes thousands of years to form the black cotton soil. The result shows that in case of Bham Dam,
approximately 2.78 lakh ton of fertile soil can be saved by adopting ferrocement COT in earthen dam.
Keywords: Cut off Trench, Earthen Dam, Seepage Analysis, Geostudio.

1. INTRODUCTION
Cut off trench which is an underground seepage barrier is a conventional method for reducing the
seepage through earthen dam foundation. The selection of material of COT is based impervious properties
and black cotton soil is preferred as most suitable material since it has very low permeability
Black cotton soil is the earth’s fragile skin that anchors all life on Earth. It is comprised of countless species
that create a dynamic and complex ecosystem and is among the most precious resources to humans. Half
of the topsoil on the planet has been lost in the last 150 years. To serve the agriculture needs, solution on
the loss of fertile land has to find out.
Approximately 2.78 lakh ton of fertile soil is required for Bham Dam located in Igatpuri, Nashik
(India) only in cut off trench zone. The solution of this problem can be explored by using the innovative
technology. To have the impervious layer in foundation of the earthen dam cut off trench, Ferrocement
technology is tried. Ferrocement is a composite of rich cement mortar and mesh reinforcement. Since the
wire mesh is stronger in tension and makes the matrix of mortar as perfectly homogenous, the cut off trench
with ferrocement is best solution to make the impervious layer in dam foundation.
In present study, the case of Bham dam is considered. It is an earthen dam and is under
construction. It is situated in the catchment of Bham river located in Kaluste village of Igatpuri in Nasik
district (India). The dam is 1500 m in the length and 31.78 m in height with average depth 13 m of cut off
trench in dam foundation.
The hydraulic study of Bham dam at Chainage of 700 m along the length of dam is carried out,
which includes soil studies and permeability studies for hearting and casing of the dam. This chainage is
approximate mid chainage of the dam in the length of 1500 m. With the input of experimental works,
detailed study of seepage analysis is carried out in GeoStudio 2012 software to get various pressure heads
and total head for knowing the behavior of phreatic line.

2. SOIL INVESTIGATION
For the detailed study of seepage analysis and to know the behavior of phreatic line in the
GeoStudio 2012 software, inputs of coefficient of permeability and Grain size analysis (D60 and D10) are
required. Hence, in this study coefficient of permeability and Grain size analysis are calculated at CH700
m by constant head test and sieve analysis, respectively. The coefficient of permeability and grain size are
calculated for both casing and hearting zone. For this experimental investigation, the different soil samples

474
Long-Term Behaviour and Environmentally Friendly Rehabilitation Technologies of Dams (LTBD 2017) DOI:10.3217/978-3-85125-564-5-062

are taken from CH700 m in the casing and hearting zone of Bham Dam. The coefficients of permeability
for these samples are 6.145 X 10-3 and 3.781 X 10-4 for casing and hearting, respectively. The grain size
analysis shows that the Particle size in mm for Casing and Hearting are 0.55(D10), 4.15(D60), 0.4(D10)
and 5.5(D60), respectively. Moisture content of soil samples is also calculated in soil investigation. The
samples were taken from actual Dam site. The moisture content was used as one of the input parameters
for the Geo Studio 2012 software to perform seepage analysis. The moisture content for samples at
Chainage700 m was 36.76 % for casing and that of for hearting was 14.45%.

3. HYDRAULIC ANALYSIS BY GEOSTUDIO 2012


GeoStudio 2012 is the analysis software used to perform various analyses related to earthen dam
like seepage analysis, stability analysis, stress and deformation analysis, earthquake analysis, thermal
analysis, contaminant analysis and air flow analysis. GeoStudio SEEP/W 2012 is used for the seepage
analysis of Bham dam. The cross-section of dam at Chainage 700 m is considered for the analysis and soil
properties at this Chainage are provided as input to the software. Parameters of Bham Dam used for the
analysis are as follows:
Type of Dam: Earthen
Height: 31.78 m Width: 263.16 m
Length: 1500 m Free board: 2.55 m
Average depth of Foundation: 6.65m
Average depth of Cut off Trench: 6 m
The cross-sectional profile of Bham Dam modeled in Geo Studio software at CH700, is shown in
Figure 1

Figure 1: Total Head variation at CH130 (Total Head: 29m)


From this modeling of Bham dam in GeoStudio 2012, various results are obtained which include the
Total Head, Pressure Head and Hydraulic conductivity through earthen dam. Table1 given below shows the
various results of Bham dam at CH700 m.

Table 1 Results of seepage analysis at Ch.700 m


Results from
Sr. No. Parameters
GeoStudio
1 Water Flux (m³/sec) 9.561341e-005
2 X-Velocity Magnitude (m/sec) 1.4628577e-007
3 Y-Velocity Magnitude (m/sec) 1.4349074e-007
4 Total Head (m) 39
5 Pore-Water Pressure (kPa) 284.403
6 Pressure Head (m) 29

Figures 2, 3, and 4 show Total Head, Pressure Head and Hydraulic conductivity, respectively.

475
Long-Term Behaviour and Environmentally Friendly Rehabilitation Technologies of Dams (LTBD 2017) DOI:10.3217/978-3-85125-564-5-062

Figure 2: Total head variation at Ch.700 m (Total head :39m)

Figure 3: Pressure head variation at Ch.700 m (Total head :29m)

Figure 4: Hydraulic Conductivity at CH700 (Conductivity: 1.4628577e-007)

From the seepage analysis, the worst pressure conditions were determined. The results of pressures are
29 m total head of water and 6.112 kg/cm2 as saturated soil pressure.

4. FERROCEMENT PANELCASTING
Ferrocement cut off trench panels were cast using the matrix of 1: 2 cement mortar and welded and
chicken mesh reinforcement. The number of mesh layers were calculated using ACI Code of ferrocement, ACI
549R.The details of design data of ferrocement COT panels is shown in Table 2.

476
Long-Term Behaviour and Environmentally Friendly Rehabilitation Technologies of Dams (LTBD 2017) DOI:10.3217/978-3-85125-564-5-062

Table 2: Design data of ferrocement COT panels.


Sr. No. Parameters Specification
1. Cut-off trench panels size 1mx 1m
2 Skeletal steel 8 mm @ 300 mm c/c
3 Type of Wire mesh Welded mesh and Chicken mesh
4 Mortar proportions 1:2
5 Water to cement ratio 0.5
6 Thickness of panels 25 mm
7 No of wire mesh layers 2 (min.)
8 No. of panels 6 no’s

The panels were cast, cured and tested in loading frame for the flexural loading. Table 3 shows the results
of flexural test.
It is clearly seen from the results of flexural strength test results that, the average flexural strength of cut
off trench panels with welded mesh have more strength than that of panels with the chicken mesh. But results can
be carefully noted as both of panels have flexural strength more than the total pressure obtained from the analytical
calculations and worst loading cases. The average flexural strength of both of the panels is compared with the
total pressure of 0.6 N/mm2 which is obtained from analytical solution of case II. Total pressure of second worst
loading case is calculated by considering saturated unit weight of soil for the overall depth of 32 m from the
foundation of the dam. The obtained flexural strength of the welded mesh panels is more than the chicken mesh
wire because the strength of the ferrocement material depends on the specific surface area of the wire mesh and
welded wire mesh provides more specific surface area than the chicken wire mesh.

Table 3: Flexural tests results of ferrocement cut off trench panels


Maximum Avg. flexural
Sr. No. Sample Designation pressure from Flexural strength strength
(N/mm2)
worst loading cases (N/mm2)

1 Panel 1 (Chicken mesh) 1.47

2 Panel 2 (Chicken mesh) Total pressure = 0.6 0.92 1.28

3 Panel 3 (Chicken mesh) N/mm2(Case II: 1.45


Saturated soil
4 Panel 4 (Welded mesh) 1.90
pressure for depth
5 Panel 5 (Welded mesh) of 32 m) 1.45 1.68

6 Panel 6 (Welded mesh) 1.71

5. COEFFICIENT OF PERMEABILITY:

The coefficient of permeability for ferrocement cutoff trench panel core for welded mesh core and
chicken mesh core is determined by falling head test. Coefficient of permeability of the ferrocement panel core is
calculated by measuring the discharge per unit time. The homogenous nature of mortar and wire mesh together is
not allowing any flow of water to seep through it. Hence no flow of water is obtained in the 24 hours.

477
Long-Term Behaviour and Environmentally Friendly Rehabilitation Technologies of Dams (LTBD 2017) DOI:10.3217/978-3-85125-564-5-062

6. CONCLUSIONS
From the obtained results it is clear that the ferrocement cut off trench is the possible solution for the cut
off trench in earthen dam. Ferrocement cut off trench panels can be provided instead of traditional cut off trenches,
as it has passed for flexural as well as permeability test. This will facilitate to avoid the use of black cotton soil in
COT portion of an earthen dam in the quest of preserving the natural resources for sustainable development.

7. REFRENCES
1. B. Shadravan, A. A. Miraghasemi, M. Pakzad, Karkhek Storage Dam Cutoff Wall Analysis and Design, Fifth
2. International Conference on Case Histories in Geotechnical Engineering, New York, April 2004, pp. 1-10.
3. B. Mansuri, F. Salmasi, Effect of Horizontal Drain Length and Cutoff Wall on Seepage and Uplift Pressure
in.
4. Hetergenous Earth Dam with Numerical Simulation, Journal of Civil Engineering and Urban, pp 114-121.
5. Kute, S. Y., et.al.., “An investigation for scope of fly as in dam construction for sustainable development of
6. natural resources” 4th International R&D conference of CBIP, Aurangabad, 2003, pp. CP-36.
7. I.S.8417-2007: Guidelines for Design of Under-Seepage Control Measures for Earth and Rockfill Dams.
8. IS 8826-1978 (Reaffirmed 2002). “Guidelines for Design of Large Earth and rockfill dams” BIS, New Delhi.
9. ACI 549R-97,” State-of-the-Art Report on Ferrocement” 1997
10. ACI 549R1-93, “Guide for the Design, Construction, and Repair of Ferrocement” 1993
11. IS 2720 (Part 4) -1985 (Reaffirmed 2006), “Method of test for soils - Grain size analysis” BIS, New Delhi
12. IS 2720 (Part 17) - 1986 (Reaffirmed 2002), “Method of test for soils - Laboratory determination of
permeability”
13. BIS, New Delhi.
14. IS 2720 (Part 7) - 1980 (Reaffirmed 2011), “Method of test for soils - Determination of water content - dry
15. density relation using light compaction” BIS, New Delhi.
16. IS 2720 (Part 2) - 1973 (Reaffirmed 2010), “Method of test for soils - Determination of water content” BIS,
17. New Delhi
18. Divekar, B. N., (2012), “Ferrocement technology - A construction manual”
19. Garg, S. K., (2014), “Irrigation Engineering and Hydraulic Structures” Khanna publishers,New Delhi