SEQUENCE OF OPERATION
WHEN DUST COLLECTOR DC-5 IS OFF, EXHAUST FAN EF-4 IS OPEN
MOTORIZED DAMPER M17 IS CLOSED, MOTORIZED DAMPER M-18 IS OPEN
WHEN DUST COLLECTOR DC-5 IS ON, EXHAUST FAN EF-4
IS OFF, MOTORIZED DAMPER M17 IS OPEN, MOTORIZED
DAMPER M18 IS CLOSED
DEDICATED AIR HANDLING UNIT AHU-5 IS CONTINUOUS RUNNING
AHU 5 - 7.5 TONS
MERV 14 FILTER ACCESS DOOR SECTION
MERV 8 FILTER COOLING COIL SECTION
FAN SECTION
0 CFM
2703 CFM
0 CFM
CLOSED
M
M17
2703 CFM
393 CFM
OPEN
M18
M
2477 CFM 226 CFM
2640 CFM 393 CFM 63 CFM
0 CFM
UNITIZED PACKING ANTE ROOM
Area (sq. m.) 54.7 Area (sq. m.) 5.0
Height (m.) 3.5 Height (m.) 3.5
MIN. ACH 20 MIN. ACH 20
Conditions (°C, % RH) NMT 24/NA Conditions (°C, % RH)
Cleanliness ISO 8 Cleanliness ISO 8
Diff. Pressure (Pa) NLT 5 Diff. Pressure (Pa) NLT 5
393 CFM
556 CFM
HALLWAY
SEQUENCE OF OPERATION
WHEN DUST COLLECTOR DC-4 IS OFF, MAHU-4 IS ALSO OFF,
MOTORIZED DAMPER M14 AND M16 ARE CLOSED, MOTORIZED
DAMPER M ADD, M15 ARE OPEN
WHEN DUST COLLECTOR DC-4 IS ON, MAHU-4 ALSO ON,
MOTORIZED DAMPER M14 &M16 ARE OPEN,
MOTORIZED DAMPER MADD & M15 WERE OPEN
DEDICATED AIR HANDLING UNIT AHU-4 IS CONTINUOUS RUNNING
AHU 4 - 6.5 TONS
MERV 14 FILTER ACCESS DOOR SECTION
MERV 8 FILTER COOLING COIL SECTION
FAN SECTION
0 CFM
2833 CFM
425 CFM
2408 CFM
M
OPEN 425 CFM
M
M16
M
ADDITIONAL M15 CLOSED
OPEN
CLOSED
M
M14
MAHU 4 - 7.5 TONS
895 CFM 1177 CFM 761 CFM
0 CFM 1430 CFM 0 CFM 978 CFM
0 CFM
ANTE ROOM DISPENSING ROOM DISPENSED RM
Area (sq. m.) 11.55 Area (sq. m.) 26.0 Area (sq. m.) 16.8
Height (m.) 3.5 Height (m.) 3.5 Height (m.) 3.5
MIN. ACH 20 MIN. ACH 20 MIN. ACH 20
Conditions (°C, % RH) NMT 24/NA Conditions (°C, % RH) Conditions (°C, % RH)
Cleanliness ISO 8 Cleanliness ISO 8 Cleanliness ISO 8
Diff. Pressure (Pa) NLT 5 Diff. Pressure (Pa) NLT 5 Diff. Pressure (Pa) NLT 5
556 CFM
339 CFM 339 CFM
556 CFM 425 CFM
GOWNING ROOM HALLWAY
SEQUENCE OF OPERATION
WHEN DUST COLLECTOR DC-3 IS OFF, MAHU-3 IS ALSO OFF, EXHAUST
FAN EF-3A & 3B IS ON, MOTORIZED DAMPER M9 IS CLOSED, MOTORIZED
DAMPER M10, M11, M12 AND M13 WERE OPEN
WHEN DUST COLLECTOR DC-3 IS ON, MAHU-3 ALSO ON,
EXHAUST FAN EF-3A & 3B OFF MOTORIZED DAMPER M9 IS OPEN,
AHU 3 - 7.5 TONS MOTORIZED DAMPER M10,M11,M12 & M13 WERE CLOSED
MERV 14 FILTER ACCESS DOOR SECTION
MERV 8 FILTER COOLING COIL SECTION DEDICATED AIR HANDLING UNIT AHU-3 IS CONTINUOUS RUNNING
FAN SECTION
0 CFM
CLOSED 3242 CFM
M M9
0 CFM
3242 CFM
681 CFM
M
M11
OPEN
MAHU 3 - 7.5 TONS
M
M12 M13
OPEN OPEN
0 CFM
1269 CFM 1000 CFM 973 CFM
1269 CFM 0 CFM 1000 CFM 973 CFM 681 CFM
M10
OPEN M 681 CFM 0 CFM 0 CFM
681 CFM
MIXING ROOM 3 FILLING ROOM 3 LABELING ROOM 3
Area (sq. m.) 19.9 Area (sq. m.) 20.28 Area (sq. m.) 21.5
Height (m.) 3.5 Height (m.) 3.5 Height (m.) 3.5
MIN. ACH 20 MIN. ACH 20 MIN. ACH 20
Conditions (°C, % RH) NMT 24/NA Conditions (°C, % RH) Conditions (°C, % RH) NMT 24/NA
Cleanliness ISO 8 Cleanliness ISO 8 Cleanliness ISO 8
TO AHU-3 Diff. Pressure (Pa) NLT 5 Diff. Pressure (Pa) NLT 5 Diff. Pressure (Pa) NLT 5
681 CFM 681 CFM
HALLWAY HALLWAY
SEQUENCE OF OPERATION
WHEN DUST COLLECTOR DC-2 IS OFF, MAHU-2 IS ALSO OFF, EXHAUST
FAN EF-2A & 2B IS ON, MOTORIZED DAMPER M4 IS CLOSED, MOTORIZED
DAMPER M5, M6, M7 AND M8 WERE OPEN
WHEN DUST COLLECTOR DC-2 IS ON, MAHU-2 ALSO ON,
EXHAUST FAN EF-2A & 2B OFF MOTORIZED DAMPER M4 IS OPEN,
AHU 2 - 7.5 TONS
MOTORIZED DAMPER M5,M6,M7 & M8 WERE CLOSED
ACCESS DOOR SECTION
MERV 14 FILTER
DEDICATED AIR HANDLING UNIT AHU-2 IS CONTINUOUS RUNNING
MERV 8 FILTER COOLING COIL SECTION
FAN SECTION
0 CFM
CLOSED 3347 CFM
M4M
0 CFM
3347 CFM
681 CFM
M
M6 M7 M8
MAHU 2 - 7.5 TONS OPEN OPEN OPEN
0 CFM
1269 CFM 1000 CFM 1078 CFM
1269 CFM 1000 CFM 0 CFM 1078 CFM 681 CFM
M5
OPEN M 681 CFM 0 CFM 0 CFM
681 CFM
MIXING ROOM 2 FILLING ROOM 2 LABELING ROOM 2
Area (sq. m.) 22.1 Area (sq. m.) 22.47 Area (sq. m.) 23.82
Height (m.) 3.5 Height (m.) 3.5 Height (m.) 3.5
MIN. ACH 20 MIN. ACH 20 MIN. ACH 20
Conditions (°C, % RH) NMT 24/NA Conditions (°C, % RH) Conditions (°C, % RH) NMT 24/NA
Cleanliness ISO 8 Cleanliness ISO 8 Cleanliness ISO 8
Diff. Pressure (Pa) NLT 5 Diff. Pressure (Pa) NLT 5 Diff. Pressure (Pa) NLT 5
681 CFM 681 CFM
HALLWAY HALLWAY
TO AHU-2
AHU 1 - 22.5 TONS
MERV 14 FILTER ACCESS DOOR SECTION
MERV 8 FILTER COOLING COIL SECTION
FAN SECTION
0 CFM
CLOSED 8567 CFM
0 CFM MM1 219 CFM
0 CFM
8567 CFM
681 CFM
M
M2
M
OPEN M3
OPEN
MAHU 1 - 7.5 TONS
1362 CFM 1596 CFM 1719 CFM 2706 CFM 1184 CFM
0 CFM 2277 CFM 2400 CFM 2706 CFM 1184 CFM 681 CFM
0 CFM
ANTE ROOM DIS ROOM RM MIXING ROOM 1 FILLING ROOM 1 LABELING ROOM 1
Area (sq. m.) 19.8 Area (sq. m.) 19.8 Area (sq. m.) 13.64/10.54 Area (sq. m.) 24.61 Area (sq. m.) 18.6/7.56
TO AHU-1
Height (m.) 3.0 Height (m.) 3.0 Height (m.) 3.5/8.5 Height (m.) 8.5 Height (m.) 8.5/3.5
MIN. ACH 20 MIN. ACH 20 MIN. ACH 20 MIN. ACH 20 MIN. ACH 20
Conditions (°C, % RH) NMT 24/NA Conditions (°C, % RH) NMT 24/NA Conditions (°C, % RH) NMT 24/NA Conditions (°C, % RH) Conditions (°C, % RH) NMT 24/NA
Cleanliness ISO 8 Cleanliness ISO 8 Cleanliness ISO 8 Cleanliness ISO 8 Cleanliness ISO 8
Diff. Pressure (Pa) NLT 5 Diff. Pressure (Pa) NLT 5 Diff. Pressure (Pa) NLT 5 Diff. Pressure (Pa) NLT 5 Diff. Pressure (Pa) NLT 5
681 CFM 681 CFM
681 CFM 681 CFM
HALLWAY HALLWAY
SECOND FLOOR
SEQUENCE OF OPERATION
WHEN DUST COLLECTOR DC-1 IS OFF, MAHU-1 IS ALSO OFF, EXHAUST
FAN EF-1 IS ON, MOTORIZED DAMPER M2 AND M3 ARE OPEN AND
MOTORIZED DAMPER M1 IS CLOSED
LINE 1
WHEN DUST COLLECTOR DC-1 IS ON, MAHU-1 ALSO ON,
EXHAUST FAN IS OFF MOTORIZED DAMPER M2 AND M3 ARE CLOSED
AND MOTORIZED DAMPER M1 IS OPEN
DEDICATED AIR HANDLING UNIT AHU-1 IS CONTINUOUS RUNNING