Electrical Design for Two-Storey House

The document provides materials and computations for the electrical design of a two-storey house. It lists materials used such as lighting outlets, convenience outlets, special purpose outlets, utility boxes, junction boxes, and various sizes of wires. It also includes computations for the total ampere load, main circuit breaker size, wire sizes, and conduit size. Wire sizes and lengths are computed for three circuits based on outlet locations and ratings.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
90 views4 pages

Electrical Design for Two-Storey House

The document provides materials and computations for the electrical design of a two-storey house. It lists materials used such as lighting outlets, convenience outlets, special purpose outlets, utility boxes, junction boxes, and various sizes of wires. It also includes computations for the total ampere load, main circuit breaker size, wire sizes, and conduit size. Wire sizes and lengths are computed for three circuits based on outlet locations and ratings.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd

Emilio Aguinaldo College – Cavite

COLLEGE OF ENGINEERING
Congressional East Avenue, Burol Main, City of Dasmarinas, Cavite 4114

ELECTRICAL DESIGN OF A TWO -


STOREY HOUSE
(Materials and Computation)

Submitted to;

Engr. Levita Castañeda P.E.E.

Submitted by:

Esta, Leorenz Marc A.

September 17, 2019


MATERIALS USED:

Description Pieces

Lighting Outlet 41

Convenience Outlet 50

Special Purpose Outlet 2

Utility Box 93

Junction Box 41

Electrical Tape 20

S 23

S2 4

S2W 1

PVC 177 @ 10 ft.

PVC Solvent 1½ L (2)

Ground Rod 4

Entrance cap 1

Main Distribution Panel 1

PVC-T 28

2.0mm2(1.6mmØ) wire 1 box

3.5mm² (2.0mmØ) wire 1 box

5.5mm² (2.6mmØ) wire 1 box

15A Circuit Breaker 2

20A Circuit Breaker 7

30A Circuit Breaker 10

125 Main Circuit Breaker 1


Computation:

Data of Schedule of loads

Total Ampere = 1.1870 + 1.2783 + (6.5217 x 8) + (8 x 9) = 126.64 Amps

Main Circuit Breaker:

Formula: MCB = Total Ampere + (0.25 + Highest Motor Rating)

MCB = 133.02 Amps + (0.25 + 12.9 Amps)

MCB = 136.25 Amps

Standard Ampere Rating in PEC = 150 Amperes

Main Circuit Breaker: 125 Amperes MCCB

Size of wire: 38 mm^2 THHN WIRE

Size of N wire: 22 mm^2 THHN WIRE

Size of Conduit: 32 mm ∅ RSC

Wire Computation:

CKT #1

63.53(2) + 1.43(11)(2) +1 + 1.43(3)(3) +1.5 + 1.43(1)(4) +2 = 181.61 m @ 2.0mm2


(1.6mmØ) @ 2.0mm2 (1.6mmØ)

CKT #2

39.83(2) + 1.43(15)(2) + 1 +1.43(2)(3) + 1.5 = 133.64 m @ 2.0mm2 (1.6mmØ) @ 2.0mm2


(1.6mmØ)
CKT #3