6-Level Measurement
6-Level Measurement
CONTROL
LEARNING
SYSTEMS ACTIVITY
PACKET
LEVEL MEASUREMENT
BB270-XD06XEN
LEARNING ACTIVITY PACKET 6
LEVEL MEASUREMENT
INTRODUCTION
Level is one of the most commonly measured process variables. Some processes
require precise measurement and control of level. One example is a chemical process
which requires that the level in the reaction tank be maintained at a specific level so the
chemicals are properly mixed.
This LAP covers how a number of level sensing devices operate and how to interpret
their electrical signals in physical units of the level, such as feet or meters.
The last segment covers how to use a process meter to display the output of a level
sensor. Process meters are commonly used to provide a visual indication of the status of a
process variable.
ITEMS NEEDED
Amatrol Supplied
1 T5552 Process Control Learning System
School Supplied
1 Water (10 gallons)
1 Compressed Air Supply
1 Digital Multimeter
A sensor is a device that responds to some type of physical input (e.g. pressure,
thermal energy, magnetism, motion, etc.) by producing an output signal, usually
electrical, as shown in figure 1.
PHYSICAL ELECTRICAL
INPUT OUTPUT
SENSOR
The two main parts of a sensor are the transducer and the transmitter, as figure
2 shows. The transducer converts the physical input into a variable electrical
measurement (e.g. variable resistance, variable capacitance, etc.). The transmitter
then creates an electrical output signal that is sent to a controller or some other
device.
SENSOR
VARIABLE
PHYSICAL ELECTRICAL ELECTRICAL
INPUT MEASUREMENT OUTPUT
TRANSDUCER TRANSMITTER
ELECTRONICS
FOR TRANSMITTER
TRANSDUCER
INPUT
PRESSURE
In other cases, the transducer and transmitter are packaged separately. Figure 4
shows an example of a flow transducer with an external transmitter. As liquid flows
over the blades, the paddle wheel rotates. This generates a frequency output that is
sent to an external transmitter and converted to an analog output.
ANALOG CURRENT
OUTPUT 4-20 mA
TRANSMITTER
PULSE
FLOW
FLOW
TRANSDUCER
FLOW
Voltage producing transmitters most often produce a 0 volt output when the
physical input signal (i.e. pressure, temperature, etc.) is also at zero. As the phys-
ical input signal increases, the voltage also increases in a proportional or straight
line manner. For example, the graph in figure 5 shows the output of a 0-10 V pres-
sure transmitter. The transmitter produces 0 volts at 0 psi and 10 volts at 1 psi.
10
8
(OUTPUT)
6
VOLTS
0
0 0.5 1
PRESSURE (psi)
(INPUT)
20
16
CURRENT (mA)
(OUTPUT)
12
OFFSET 0
0 0.5 1
PRESSURE (psi)
(INPUT)
There are a variety of sensors used to measure level. The type used depends on
the application. Four methods of sensing level are:
• Pressure
• Electrical Resistance
• Electrical Capacitance
• Ultrasonic
Pressure
Pressure-type level sensors measure level by measuring the pressure of the
liquid at the bottom of a container. This pressure is then converted to an analog
electrical signal that is proportional to the liquid level in the tank. Figure 7 shows
an example of a pressure-type level sensor. This type of level sensor has an internal
transmitter that produces a 4-20 mA electrical current output.
PRESSURE-TYPE 4-20mA
LEVEL SENSOR
W/ INTERNAL TRANSMITTER
WIRE WINDING
BASE STRIP
LIQUID PRESSURE
Resistance tape level sensors are often used to measure raw sewage, sludge,
and gasoline levels.
4-20 mA
OUTPUT
CAPACITANCE
PROBE
PROBE
TIP
(PLATE)
TANK
WALL
LIQUID (PLATE)
(DIELECTRIC)
4-20mA ULTRASONIC
OUTPUT LEVEL SENSOR
TRANSMITTED
WAVES
REFLECTED
WAVES
Applications for ultrasonic level sensors include measuring the level of chemi-
cals that can become contaminated through any type of contact. Ultrasonic sensors
are also used to measure the level of combustible fluids.
A volume of liquid in a tank exerts pressure on the bottom of the tank due to
its weight. This pressure is referred to as hydrostatic pressure, which is commonly
measured in pounds per square inch (psi).
Pressure can also be expressed in terms of the height of the liquid. In this
case, it is referred to as hydrostatic head and is measured in feet/inches or meters/
centimeters.
Figure 11 shows an example of the pressure on the bottom of a tank expressed
in terms of hydrostatic pressure and hydrostatic head. The amount of pressure or
head depends on the height and the density of the liquid. Increasing the liquid level
in the tank increases the pressure at the bottom of the liquid column. Decreasing
the liquid level in the tank decreases the pressure.
HYDROSTATIC HYDROSTATIC
PRESSURE HEAD
5 psi 11.6 ft
5 lbs
WATER
11.6 ft
1 SQUARE
INCH SURFACE
5 POUNDS
PRESSURE =
1 SQ. IN.
OPEN
CONTAINER
ATMOSPHERIC
PRESSURE
P1 = 14.7 psia
ABSOLUTE
PRESSURE
HYDROSTATIC HEAD Pabs = 16.86 +14.7
5 FEET = 16.86 psia CONTROLLER
= 31.56 psia
5.00
GAUGE PRESSURE
Pgage = 31.56 - 14.7 = 16.86 psia
Figure 12. Open Tank Level Measurement Using Pressure-Type Level Sensor
AIR PRESSURE=
30 psia
HYDROSTATIC HEAD
5ft = 16.86 psia
CONTROLLER
74.44
PRESSURE
TAP
P1 = 30 psia
NET (DIFFERENTIAL)
PRESSURE SIGNAL
16.86 psia
5.00
DIFFERENTIAL
PRESSURE
TRANSMITTER
PRESSURE
TAP
P2 = 46.86 psia
Pressure type level sensors are used in various industries including oil and gas,
marine, medical, and space. Differential pressure measurement is commonly used
when measuring the level of potentially volatile liquids such as liquid oxygen or
hydrogen.
A bubbler system is a type of level measuring device that determines the level
of a liquid by measuring the pressure of a gas that is forced out of a tube into the
liquid in the tank. This type of system is often used for measurement but seldom
for control because its accuracy is not as high as other methods.
Bubbler systems consist of a tube, regulator, gas supply (usually air or
nitrogen), and pressure gauge, as shown in figure 15. The tube is placed inside the
tank or vessel so that it extends near the bottom of the tank or just below the lowest
point of desired level measurement. The gas supply and regulator force a regulated
volume of air or nitrogen through the tube until it bubbles out the open end. The
pressure gauge measures the pressure required to force the gas out of the tube.
PRESSURE
GAUGE
REGULATOR
0
PSIG
GAS BUBBLER
SUPPLY TUBE
PRESSURE
GAUGE
REGULATOR VENT
0
GAS
PSIG
SUPPLY BUBBLER
PIPE
PIPE FITTING
TUBULAR BODY
ELECTRICAL
CONNECTION
+ -
FLEXIBLE FLEXIBLE
DIAPHRAGM DIAPHRAGM
STATIONARY STATIONARY
ELECTRODE OSCILLATOR OSCILLATOR ELECTRODE
CIRCUIT WITH CIRCUIT WITH
VARIABLE FIXED
CAPACITANCE CAPACITANCE
TRANSMITTER
COMPARATOR
TRANSMITTER
CIRCUIT
COMPONENTS
GENERATES
4-20mA OUTPUT
4 - 20 mA
- +
When fluid pressure acts on the diaphragm, it flexes causing the capacitance
to change.
To detect the change in capacitance, this sensor uses two oscillator circuits one
connected to a fixed capacitance and the other connected to available capacitance
created by the diaphragm. When pressure increases, the frequency of the oscil-
lator circuit connected to the flexible diaphragm changes. A comparator circuit
compares the difference in frequency between the oscillator circuit connected to
the flexible diaphragm to the frequency of a fixed capacitor oscillation circuit and
produces a proportional analog output signal, usually 4-20 mA.
20
16
CURRENT (mA)
(OUTPUT)
12
OFFSET 0
0 0.5 1
PRESSURE (psi)
(INPUT)
MULTIMETER
7mA
+ -
-
+ CONTROLLER
INPUT
+ -
DC POWER
SUPPLY
2-WIRE + -
PRESSURE SENSOR
MULTIMETER
3V
+ -
-
+ CONTROLLER
INPUT
+ -
DC POWER
2-WIRE SUPPLY
PRESSURE SENSOR + -
MULTIMETER
3V
+ -
CONTROLLER
INPUT INPUT
+ -
COMMON
EXCITATION +
DC POWER
SUPPLY
+ -
3-WIRE
PRESSURE SENSOR
Procedure Overview
In this procedure, you will connect a 2-wire variable capacitance pressure
sensor to an external power supply on the T5552 process control system. You
will then place a digital multimeter (DMM) in the circuit to determine if the
sensor produces an output signal.
1. Perform a lockout/tagout.
2. Perform the following substeps to set up the T5552, as shown in figure 23.
NOTE
The appearance of the electrical outlet will differ based on the electrical
power supplied at your location.
ELECTRICAL
PID CONTROLLER FLOW TRANSMITTER
FT1
4-20mA
FLOW SENSORS
FT2
4-20mA TEST
FLOWPVALVE
FV1
4-20mA
PL1 PL2 PL3 PL4
ALM1
ALM2
ALM3
PROCESS METER
UDI1700
MAX
MIN
OUTLET
SS1 SS2 SS3 SS4
ALM4
ALM5
ALM 1234 MAN FC
LEVEL SENSORS
0
DI 1234 SET SETUP
PV LT1 LT2
OUT 1234
-sp 0.0
OUTPUT RELAY 1
CURRENT INPUT
SP NO COM NC
mA
CR2
4-20mA
AL2
DISCRETE
9 10 11 12 13 14 15 16
DL1
AUX. POWER
ALARM
AL1 CR3
DISCRETE
DC POWER SUPPLY PLC ANALOG I/O
DL2 4-20mA
24 VDC 24 VDC 24VDC 24VDC 24VDC
AL2 OPEN COLLECTOR
SOLENOID VALVES
1 2 3 4 5 6 7 8
SV1 SV2 SV3
GND
9 10 11 12 13 14 15 16
PRESSURE
REGULATOR
HV2 SET TO ZERO
MANUAL DRAIN
VALVES CLOSED
AIR SUPPLY
CONNECTION
HAND VALVES HV1
OPEN MANUAL FLOW
CONTROL VALVE
OPEN
LEVEL SENSORS
LT1 LT2
LS1 LS2
LT1
10
9
CONTROL RELAYS ALARM HORN CIRC. PUMP
8
AH1 P1
7 CR1
5 CR2
4
CR3
3
DC POWER SUPPLY
2
24VDC 24VDC 24VDC
1
SOLENOID VALVES
0 SV1 SV2 SV3
GND
SET TO MEASURE DC
TO LT1 mA mA (TEST PROBES
WAVETEK
CONNECTED TO
DM15XL
PRESSURE
20
2 2
SENSOR 2000
M
20M
20m
200m
A
2000k 10A
200k 10A
20k 200m
2k 20m
200 200 2m
l A
V COM mA 10A
FUSED
MAX
1000V FUSED
750V
DMM
7. The pressure exerted on the bottom of a tank depends on the height and
__________ of the liquid in the tank.
Specific Gravity (SG) is the ratio of the weight of a liquid to an equal amount
of water. There is no unit of measure for specific gravity because it is a ratio.
The formula below shows how to calculate the specific gravity of a material.
Where:
SG = Specific Gravity
Mmaterial = Mass of the material
Mwater = Mass of an equal volume of water
231 ft. SG SG SG
1.0 0.74 0.79
100 74 79
psi psi psi
A liquid that has a specific gravity greater than 1 (the specific gravity of fresh
water) exerts more pressure on the bottom of a tank than water, or any fluid with a
specific gravity less than 1.
Liquid level units can be converted to fluid pressure units if the level in the
tank and the specific gravity of the liquid in the tank are known. Converting liquid
level units to pressure units is useful in determining the proper components for the
system.
The following formula converts liquid level units to pressure units.
P = L × SG × k
Where:
P = Pressure (psi, kPa)
L = Level (inches, feet, meters)
SG = Specific Gravity
k = Conversion Factor = 0.036 psi/in
= 0.432 psi/ft
= 9.772 kPa/m
Example: Determine the range needed for a pressure sensor for a tank. The
maximum level is 25 feet of water, as shown in figure 27.
LEVEL = 25 ft.
PRESSURE = ?
Procedure Overview
In this procedure, you will be given the height of a liquid and asked to
calculate the pressure that will be detected by the level sensor. Or, you may
be given the pressure and asked to calculate the height of the liquid. This
information would then be used to select a level sensor for that application.
GLUCOSE
MAXIMUM HEIGHT =
18.35 ft (5.59m)
You should find that the maximum pressure is 22.29 psi (153.69 kPa).
3. Determine the maximum pressure exerted by a column of liquid given the
following scenario.
Scenario: You have a tank that contains seawater at a maximum height of
98.5 in (2.5 m) and you want to select the proper level sensor for this tank.
Maximum Pressure = ___________________________________ (psi/kPa)
You should find that the maximum pressure is 3.65 psi (25.16 kPa).
4. Determine the height of the column of liquid given the following scenario.
Scenario: You have a tank that contains molasses exerting a pressure of 32.80
psi (226.15 kPa) as shown in figure 29 and you want to determine the column
height (level) of the molasses.
Column Height (Level) = __________________________________ (ft/m)
MOLASSES
COLUMN
HEIGHT
(LEVEL)=?
You should find that the column height (level) is 52.36 ft (15.96 m).
SENSITIVITY FORMULA
OElec
S
I Phys
where
S = Sensitivity
D = Amount of Change
OElec = Electrical Output Signal
IPhys = Physical Input Signal
Example: If a pressure sensor increases its electrical signal 0.001 volt for
every 1 psi increase in pressure, as shown in figure 30, its sensitivity is 0.001 volts
per 1 psi (0.001 volt/1 psi).
PRESSURE =
0.5V
Example: Calculate the pressure that the sensor in figure 32 senses using the
following information:
Electrical Output Signal Range = 1-5 V
Pressure Input Signal Range = 0-20 psi
Measured Output = 1.5 V
CONTROLLER
PRESSURE =
1.5V
To calculate the pressure sensor output signal value given the measured pres-
sure input signal value, the previous formula can be rearranged as follows:
Om = (Pm × S) + Omin
Where:
Om = Measured Output Signal Value
Pm = Measured Pressure
S = Sensitivity
Omin = Minimum Output Signal Value
To solve the problem, first determine the sensitivity. Then use the sensitivity to
determine the measured output.
Determine the sensitivity:
5V 1V
S
20 psi 0 psi
4V
20 psi
0.2 V/psi
Procedure Overview
In this procedure, you will convert pressure sensor output signals to
pressure units and vice versa given the pressure and output ranges of the sensor
and either the measured output signal or the measured input pressure.
15 mA
PRESSURE = 3 psi
(20.68 kPa)
Liquid level units are converted to sensor output signal units by first converting
the liquid level units to pressure units and then converting the pressure units to
sensor output signal units. This calculation is useful in troubleshooting and allows
the technician to determine if the pressure sensor is providing the correct output.
Substituting the expression relating liquid level to pressure into the equa-
tion that converts pressure units to sensor output signal units gives the following
equation:
Om = (S × L × SG × k) + Omin
Where:
Om = Measured Output Signal
S = Sensitivity
L = Level (inches, feet, meters)
SG = Specific Gravity
Omin = Minimum Output Signal Value
k = Conversion Factor
= 0.036 psi/in
= 0.432 psi/ft
= 9.772 kPa/m
Example: Calculate the measured output of a pressure sensor with a 0-3 psi
range and a 1-5 V output signal range if the level of crude oil (SG = 0.85) in the
tank is 26 inches. Figure 36 shows this system.
26 INCHES
CRUDE OIL
OUTPUT = ?V
PRESSURE
SENSOR
(0-3 psi)
L = ( Om − Omin )
( S × SG × k)
Where:
L = Level (inches, feet, meters)
Om = Measured Output Signal
Omin = Minimum Output Signal Value
S = Sensitivity
SG = Specific Gravity
k = Conversion Factor
= 0.036 psi/in
= 0.432 psi/ft
= 9.772 kPa/m
Example: Calculate the level (in inches) of soybean oil (SG = 0.93) in a tank
if the measured output from a 6 psi sensor with a pressure range of 0-5 psi is 8 mA.
The sensor has a 0-20 mA output signal range.
Using the equation:
(8 − 0)
L=
( ( )
20
5
× 0.93 × 0.036)
8
L=
( 4 × 0.93 × 0.036)
8
L=
0.134
L = 59.74 inches
Procedure Overview
In this procedure, you will convert liquid level units to sensor output signal
units using the equations to convert liquid level to pressure and pressure to
sensor output signal. Refer to Appendix A for the specific gravity of the liquids.
1. Calculate the current output signal from a pressure-type sensor that has a 0-2
psi (0-13.79 kPa) input signal range if it measures a water level of 21 inches
(0.53 m).
The sensor has a 4-20mA output signal range.
Electrical Output Signal ____________________________________ (mA)
21 INCHES
(0.53m)
WATER
OUTPUT = ?mA
PRESSURE
SENSOR
LEVEL = 70 in
(1.78m)
FRESH
WATER
PRESSURE
SENSOR
LEVEL = ?
CORN OIL
4.5V
PRESSURE
SENSOR
Procedure Overview
In this procedure, you will check the output of a pressure sensor using a
digital multimeter (DMM). The sensor should produce an analog electrical
signal (current) that is proportional to the fluid level in the process tank. As the
level in the tank increases, so should the output signal of the sensor. You will
verify this relationship in this procedure.
This is a procedure commonly used to troubleshoot a suspected bad sensor.
1. Perform a lockout/tagout.
2. Perform the following substeps to set up the T5552, as shown in figure 40.
NOTE
The appearance of the electrical outlet will differ based on the electrical
power supplied at your location.
ELECTRICAL
PID CONTROLLER FLOW TRANSMITTER
FT1
4-20mA
FLOW SENSORS
FT2
4-20mA TEST
FLOWPVALVE
FV1
4-20mA
PL1 PL2 PL3 PL4
ALM1
ALM2
PROCESS METER
UDI1700
MAX
MIN
OUTLET
SS1 SS2 SS3 SS4 ALM3
ALM4
ALM5
ALM 1234 MAN FC
LEVEL SENSORS
0
DI 1234 SET SETUP
PV LT1 LT2
OUT 1234
-sp 0.0
OUTPUT RELAY 1
SP CURRENT INPUT
mA NO COM NC
CR2
4-20mA
AL2
DISCRETE
9 10 11 12 13 14 15 16
DL1
AUX. POWER
ALARM
AL1 CR3
DISCRETE
DC POWER SUPPLY PLC ANALOG I/O
DL2 4-20mA
24 VDC 24 VDC 24VDC 24VDC 24VDC
AL2 OPEN COLLECTOR
SOLENOID VALVES
1 2 3 4 5 6 7 8
SV1 SV2 SV3
GND
9 10 11 12 13 14 15 16
PRESSURE
REGULATOR
HV2 SET TO ZERO
MANUAL DRAIN
VALVES CLOSED
AIR SUPPLY
CONNECTION
HAND VALVES HV1
OPEN MANUAL FLOW
CONTROL VALVE
OPEN
LEVEL SENSORS
LT1 LT2
LS1 LS2
CR1
CR2
CR3
DC POWER SUPPLY
SOLENOID VALVES
SV1 SV2 SV3
GND
SET TO MEASURE DC
mA mA (TEST PROBES
WAVETEK DM15XL
V
2
20
200
1000 OFF 750
200
20
2
V
CONNECTED TO
200m
V COM mA 10A
FUSED
MAX
1000V FUSED
750V
DMM
NOTE
Actual measurements depend on how well the sensor is calibrated.
You should find the readings to be close (typically within ± 0.5 mA) of the
theoretical values (from the graph in figure 43). If your recorded values
vary from theoretical values by more than ±1 mA, inform your instructor.
The sensor may be out of calibration.
D. When the level in the tank reaches 10 inches, turn off the circulation
pump.
6. Make a plot of the sensor output versus the level using the data you recorded
in substep 5C.
20
19
18
17
16
15
14
13
12
11
OUTPUT
10
(mA)
9
8
7
6
5
4
3
2
1
0
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28
LEVEL
(INCHES)
20
19
18
17
16
15
14
13
12
11
OUTPUT
10 10" ≈ 10.75mA
(mA)
9
8
7
6
5
4
3
2
1
0
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28
LEVEL
(INCHES)
1. To convert liquid level units to pressure units, you need to know the
level and the _______________________ of the fluid.
6. When converting liquid level units to sensor output signal units, you
should first convert the liquid level units to ___________ units.
SCALED
DISPLAY
2.0
2m
5mA
LEVEL
SENSOR
UDI1700
ALM1 MAX
ALM2 MIN
ALM3
ALM4
ALM5
SET SETUP
PROCESS
METER
UDI1700
2.0
ALM1 MAX
ALM2 MIN
ALM3
ALM4
ALM5
SET SETUP
2M
5mA
Process meters are often scaled to display the electrical input signal in terms of
the physical units (i.e. display scaling). For example, although the process meter in
figure 46 receives a 5 mA input signal, it displays 2.0 (the level in meters).
Process meters can be mounted almost anywhere. In some applications, it is
necessary to mount the process meter near the actual process. Some applications
require the process meter to be installed in a central location such as a control panel
or a control room.
DISPLAY
CONNECTION TERMINALS
(ON BACK)
UDI1700
ALM1 MAX
ALM2 MIN
ALM3
ALM4
ALM5
SET SETUP
PROGRAMMING
KEYS
UDI1700
ALM1 MAX
ALM2 MIN
ALM3
ALM4
ALM5
SET SETUP
DOWN UP SETUP
ARROW ARROW KEY
KEY KEY
OPTION A
OPTION 3 C C 11 23 C C OPTION 2
- + LINEAR (V/mV)
LINEAR (mA)
+ -
UNIVERSAL INPUT
PROCESS METER
13 14 15 16 17 18 19 20 21
12 22
CONTROLLER
11 23
+ -
INPUT
10 24
9 8 7 6 5 4 3 2 1
- +
LEVEL
SENSOR
(1-5VDC)
Figure 51. Process Meter Wired to a Level Sensor and Remotely Located Controller
PROCESS METER
DISPLAY
ANALOG
INPUT ANALOG-TO-
DIGITAL (A/D)
CONVERSION
DIGITAL
SIGNAL
MICROPROCESSOR
ADJUSTED
DATA
PARAMETERS
MEMORY
PROCESS METER
13 14 15 16 17 18 19 20 21
12 22
11 23
10 24
9 8 7 6 5 4 3 2 1
+ -
DC POWER
SUPPLY
LEVEL + -
SENSOR
(4-20mA)
UDI1700
ALM1 MAX
ALM2 MIN
ALM3
ALM4
ALM5
SET SETUP
UDI1700
ALM1 MAX
ALM2 MIN
ALM3
ALM4
ALM5
SET SETUP
UDI1700
ALM1 MAX
ALM2 MIN
ALM3
ALM4
ALM5
SET SETUP
Procedure Overview
In this procedure, you will connect and configure the process meter on the
T5552 to measure the level of water in the process tank. To do this, you must
first determine the output of the level sensor/transmitter for a level of zero
inches and a level of 10 inches. You will then use this information to configure
the meter.
1. Perform a lockout/tagout.
2. Perform the following substeps to set up the T5552, as shown in figure 57.
NOTE
The appearance of the electrical outlet will differ based on the electrical
power supplied at your location.
ELECTRICAL
PID CONTROLLER FLOW TRANSMITTER
FT1
4-20mA
FLOW SENSORS
FT2
4-20mA TEST
FLOWPVALVE
FV1
4-20mA
PL1 PL2 PL3 PL4
ALM1
ALM2
PROCESS METER
UDI1700
MAX
MIN
OUTLET
SS1 SS2 SS3 SS4 ALM3
ALM4
ALM5
ALM 1234 MAN FC
LEVEL SENSORS
0
DI 1234 SET SETUP
PV LT1 LT2
OUT 1234
-sp 0.0
OUTPUT RELAY 1
SP CURRENT INPUT
mA NO COM NC
CR2
4-20mA
AL2
DISCRETE
9 10 11 12 13 14 15 16
DL1
AUX. POWER
ALARM
AL1 CR3
DISCRETE
DC POWER SUPPLY PLC ANALOG I/O
DL2 4-20mA
24 VDC 24 VDC 24VDC 24VDC 24VDC
AL2 OPEN COLLECTOR
SOLENOID VALVES
1 2 3 4 5 6 7 8
SV1 SV2 SV3
GND
9 10 11 12 13 14 15 16
PRESSURE
REGULATOR
HV2 SET TO ZERO
MANUAL DRAIN
VALVES CLOSED
AIR SUPPLY
CONNECTION
HAND VALVES HV1
OPEN MANUAL FLOW
CONTROL VALVE
OPEN
NOTE
You must set several parameters to properly configure the process meter on
the T5552. The relevant parameters will be explained as you progress through
the remaining steps.
4. Perform the following substeps to set up the process meter on the T5552 for
configuration.
A. Connect the circuit shown in figure 58.
Make sure the current input terminals are used.
This circuit allows you to measure the level of water in the process tank
with the process meter.
ALM1 MAX
ALM4
ALM5
OUTPUT RELAY 1
CURRENT INPUT
mA NO COM NC
LS1 LS2
OUTPUT RELAY 2
VOLTAGE INPUT NO COM NC
mV/V
CR1
1 2 3 4 5 6 7 8
CR2
9 10 11 12 13 14 15 16
CR3
SOLENOID VALVES
1 2 3 4 5 6 7 8
SV1 SV2 SV3
GND
9 10 11 12 13 14 15 16
DC POWER
SUPPLY LT1 PROCESS METER
PRESSURE SENSOR CURRENT INPUT
+
+ - + -
-
24
VDC
CIRC. PUMP
P1
SS1
+
-
Figure 59. Wiring Diagram for Level Sensor Connected to the Process Meter
B. Use the up and down arrow keys to scroll through the menus until
the Configuration Menu (ConF) appears on the display.
“ConF” should now appear on the display.
C. Press the SETUP key to open the Configuration Menu.
Since the Configuration Menu is locked, “ULoc” appears on the display
briefly, followed by 0. The unlock code must be entered before you can
continue.
D. Use the up and down arrow keys to change the displayed value to
20, which is the unlock code for the Configuration Menu.
UDI1700
ALM1 MAX
ALM2 MIN
ALM3
ALM4
ALM5
SET SETUP
NOTE
The longer you hold a key, either up or down, the faster the value scrolls.
UDI1700
ALM1 MAX
ALM2 MIN
ALM3
ALM4
ALM5
SET SETUP
C. Press the up arrow key to accept the new value for the input parameter.
NOTE
If you do not press the up arrow key in response to a Yes prompt, the
value of the selected parameter reverts to the previous setting.
With the correct input selected, the next step is to set the scale range limits
for the process variable.
7. Perform the following substeps to set the scale range limit parameters.
NOTE
In order to scroll through the parameters using the SETUP key, the name
of a parameter (i.e. inPt) must appear on the display. If a value is displayed (i.e.
4_20), pressing the SETUP key displays the parameter name. The parameter
name will appear for about one second before returning to the value. You can
only scroll with the SETUP key when a parameter name is displayed.
The scale range limit parameters are also located in the Configuration Menu.
5. To configure a process meter, you must program the input signal range
and the _______________ range parameters.