Presentation, Variable speed drives
characteristics Altivar 71: reduction of current harmonics
Option: passive filters
Passive filters
A passive filter is used to reduce current harmonics with total harmonic distortion
L1
factors of less than 16% or 10%. These ratios may be reduced to 10% or 5% if the
filter is used with a DC choke, see pages 152 to 155.
L2
L3
The reactive power increases at no load or low load. To eliminate this reactive power,
the filter capacitors can be disconnected via the drive, see page 233. To do this, the
ATV 71ppppN4 contactor must be controlled by one of the relay outputs on the drive, at a value lower
ATV 71PpppN4Z
than 10% of the nominal drive current (In) (please refer to the programming manual).
For ATV 71HpppY drives, use of a line choke is recommended or mandatory,
Passive filter depending on the rating.
Application
Reduction of current harmonics in order to use drives in the first environment.
General characteristics
Degree of protection IP 20
Maximum relative humidity Class F humidity without condensation 5%…85%
Ambient air temperature Operation °C 5…+ 40 without derating
around the device
Storage °C - 25…+ 55
Maximum operating altitude m 1000 without derating
Electrical characteristics
Range 400 V 460 V
Nominal voltage ± 10% V 380…415 a 440…480 a
Operating frequency 50 ± 5 % 60 ± 5 %
Overload capacity 1.5 x In (A)
Efficiency 98% (2% thermal losses)
THDI (1) % ≤ 16
Cos ϕ At 75 % of the line current: 0.85
At 100 % of the line current: 0.99
At 150% of the line current: 1
Connection characteristics
Maximum wire size VW3 A4 601…604 16 mm2
VW3 A4 605…609 50 mm2
VW3 A4 610, 611 Connected on a bar, Ø 12.5
VW3 A4 612, 613, 619 Connected on a bar, Ø 16.5
VW3 A4 621, 622 16 mm2
VW3 A4 623…627 50 mm2
VW3 A4 628, 629 Connected on a bar, Ø 12.5
VW3 A4 630…633, 639 Connected on a bar, Ø 16.5
VW3 A4 641…644 16 mm2
VW3 A4 645…648 50 mm2
VW3 A4 649 Connected on a bar, Ø 12.5
VW3 A4 650, 651, 656, 657 Connected on a bar, Ø 16.5
VW3 A4 661…663 16 mm2
VW3 A4 664…666 50 mm2
VW3 A4 667, 668 Connected on a bar, Ø 12.5
VW3 A4 669…671, 676, 677 Connected on a bar, Ø 16.5
(1) The total current harmonic distortion (THDI) is indicated for a total voltage harmonic distortion (THDU) < 2% and a short-circuit ratio (RSCE) > 66%, and only for
the nominal current of the passive filter. If these conditions are not adhered to, the total current harmonics will be reduced without any guarantee of level.
References: Dimensions: Schemes:
pages 162 to 165 pages 210 and 211 pages 232 and 233
161
References Variable speed drives
Altivar 71: reduction of current harmonics
Option: passive filters
Passive filters: three-phase power supply 400 V 50 Hz
Motor rating For drives Network Filter Quantity Reference Weight
Line current ln (2) per drive
kW HP A A kg
THDI 16% (1)
0.75 1 ATV 71H075N4 2.5 6 1 VW3 A4 601 15.000
ATV 71W075N4
ATV 71P075N4Z
1.5 2 ATV 71HU15N4 3.6 6 1 VW3 A4 601 15.000
ATV 71WU15N4
ATV 71PU15N4Z
2.2 3 ATV 71HU22N4 5 6 1 VW3 A4 601 15.000
ATV 71WU22N4
ATV 71PU22N4Z
3 – ATV 71HU30N4 6 6 1 VW3 A4 601 15.000
ATV 71WU30N4
ATV 71PU30N4Z
4 5 ATV 71HU40N4 7.8 10 1 VW3 A4 602 19.000
ATV 71WU40N4
ATV 71PU40N4Z
5.5 7.5 ATV 71HU55N4 10 10 1 VW3 A4 602 19.000
ATV 71WU55N4
ATV 71PU55N4Z
7.5 10 ATV 71HU75N4 14 19 1 VW3 A4 603 21.000
ATV 71WU75N4
ATV 71PU75N4Z
11 15 ATV 71HD11N4 19 19 1 VW3 A4 603 21.000
ATV 71WD11N4
ATV 71PD11N4Z
15 20 ATV 71HD15N4 26 26 1 VW3 A4 604 22.000
ATV 71WD15N4
18.5 25 ATV 71HD18N4 32 35 1 VW3 A4 605 34.000
ATV 71WD18N4
22 30 ATV 71HD22N4 38 43 1 VW3 A4 606 38.000
ATV 71WD22N4
30 40 ATV 71HD30N4 52 72 1 VW3 A4 607 56.000
ATV 71WD30N4
37 50 ATV 71HD37N4 63 72 1 VW3 A4 607 56.000
ATV 71WD37N4
45 60 ATV 71HD45N4 77 101 1 VW3 A4 608 69.000
ATV 71WD45N4
55 75 ATV 71HD55N4 91 101 1 VW3 A4 608 69.000
ATV 71WD55N4
75 100 ATV 71HD75N4 126 144 1 VW3 A4 609 97.000
ATV 71WD75N4
THDI 10%
90 125 ATV 71HD90N4 149 144 1 VW3 A4 609 97.000
110 150 ATV 71HC11N4 182 180 1 VW3 A4 610 103.000
132 200 ATV 71HC13N4 218 216 1 VW3 A4 611 112.000
160 250 ATV 71HC16N4 287 289 1 VW3 A4 612 135.000
200 300 ATV 71HC20N4 353.5 370 1 VW3 A4 613 155.000
220 350 ATV 71HC25N4 364 370 1 VW3 A4 613 155.000
250 400 ATV 71HC25N4 415 216 2 VW3 A4 611 112.000
280 450 ATV 71HC28N4 485 289 2 VW3 A4 612 135.000
315 500 ATV 71HC31N4 543 289 2 VW3 A4 612 135.000
355 – ATV 71HC40N4 588 289 2 VW3 A4 612 135.000
400 600 ATV 71HC40N4 664 325 2 VW3 A4 619 155.000
500 700 ATV 71HC50N4 840 289 3 VW3 A4 612 135.000
(1) By adding a DC choke (see page 152) to ATV 71p075N4…pD75N4 and ATV 71PpppN4Z drives, a THD y 10% is obtained.
This DC choke is supplied as standard with ATV 71HD90N4…HC50N4 drives.
These reduced current harmonics are obtained, only for the nominal filter current, on condition that the THDU is < 2% and
the RSCE > 66%.
(2) In: nominal filter current.
Presentation: Characteristics: Dimensions: Schemes:
page 161 page 161 pages 210 and 211 pages 232 and 233
162
References (continued) 1
Variable speed drives
Altivar 71: reduction of current harmonics
Option: passive filters
Passive filters: three-phase power supply 400 V 50 Hz
Motor rating For drives Network Filter Quantity Reference Weight
Line current ln (2) per drive
kW HP A A kg
THDI 10 % (1)
0.75 1 ATV 71H075N4 2.5 6 1 VW3 A4 621 21.000
ATV 71W075N4
ATV 71P075N4Z
1.5 2 ATV 71HU15N4 3.6 6 1 VW3 A4 621 21.000
ATV 71WU15N4
ATV 71PU15N4Z
2.2 3 ATV 71HU22N4 5 6 1 VW3 A4 621 21.000
ATV 71WU22N4
ATV 71PU22N4Z
3 – ATV 71HU30N4 6 6 1 VW3 A4 621 21.000
ATV 71WU30N4
ATV 71PU30N4Z
4 5 ATV 71HU40N4 7.8 10 1 VW3 A4 622 27.000
ATV 71WU40N4
ATV 71PU40N4Z
5.5 7.5 ATV 71HU55N4 10 10 1 VW3 A4 622 27.000
ATV 71WU55N4
ATV 71PU55N4Z
7.5 10 ATV 71HU75N4 14 19 1 VW3 A4 623 28.000
ATV 71WU75N4
ATV 71PU75N4Z
11 15 ATV 71HD11N4 19 19 1 VW3 A4 623 28.000
ATV 71WD11N4
ATV 71PD11N4Z
15 20 ATV 71HD15N4 26 26 1 VW3 A4 624 40.000
ATV 71WD15N4
18.5 25 ATV 71HD18N4 32 35 1 VW3 A4 625 49.000
ATV 71WD18N4
22 30 ATV 71HD22N4 38 43 1 VW3 A4 626 52.000
ATV 71WD22N4
30 40 ATV 71HD30N4 52 72 1 VW3 A4 627 88.000
ATV 71WD30N4
37 50 ATV 71HD37N4 63 72 1 VW3 A4 627 88.000
ATV 71WD37N4
45 60 ATV 71HD45N4 77 101 1 VW3 A4 628 150.000
ATV 71WD45N4
55 75 ATV 71HD55N4 91 101 1 VW3 A4 628 150.000
ATV 71WD55N4
75 100 ATV 71HD75N4 126 144 1 VW3 A4 629 167.000
ATV 71WD75N4
THDI 5 %
90 125 ATV 71HD90N4 149 144 1 VW3 A4 629 167.000
110 150 ATV 71HC11N4 182 180 1 VW3 A4 630 178.000
132 200 ATV 71HC13N4 218 216 1 VW3 A4 631 224.000
160 250 ATV 71HC16N4 287 289 1 VW3 A4 632 271.000
200 300 ATV 71HC20N4 353.5 370 1 VW3 A4 633 320.000
220 350 ATV 71HC25N4 364 370 1 VW3 A4 633 320.000
250 400 ATV 71HC25N4 415 216 2 VW3 A4 631 224.000
280 450 ATV 71HC28N4 485 289 2 VW3 A4 632 271.000
315 500 ATV 71HC31N4 543 289 2 VW3 A4 632 271.000
355 – ATV 71HC40N4 588 289 2 VW3 A4 632 271.000
400 600 ATV 71HC40N4 664 325 2 VW3 A4 639 284.000
500 700 ATV 71HC50N4 840 289 3 VW3 A4 632 271.000
(1) By adding a DC choke (see page 152) to ATV 71p075N4…pD75N4 and ATV 71PpppN4Z drives, a THD y 5% is [Link]
DC choke is supplied as standard with ATV 71HD90N4…HC50N4 drives.
These reduced current harmonics are obtained, only for the nominal filter current, on condition that the THDU is < 2% and
the RSCE > 66%.
(2) In: nominal filter current.
Presentation: Characteristics: Dimensions: Schemes:
page 161 page 161 pages 210 and 211 pages 232 and 233
163
References (continued) 1
Variable speed drives
Altivar 71: reduction of current harmonics
Option: passive filters
Passive filters: three-phase power supply 460 V 60 Hz
Motor rating For drives Network Filter Quantity Reference Weight
Line current ln (2) per drive
kW HP A A kg
THDI 16% (1)
0.75 1 ATV 71H075N4 2.5 6 1 VW3 A4 641 15.000
ATV 71W075N4
ATV 71P075N4Z
1.5 2 ATV 71HU15N4 3 6 1 VW3 A4 641 15.000
ATV 71WU15N4
ATV 71PU15N4Z
2.2 3 ATV 71HU22N4 5 6 1 VW3 A4 641 15.000
ATV 71WU22N4
ATV 71PU22N4Z
3 – ATV 71HU30N4 6 6 1 VW3 A4 641 15.000
ATV 71WU30N4
ATV 71PU30N4Z
4 5 ATV 71HU40N4 7 10 1 VW3 A4 642 19.000
ATV 71WU40N4
ATV 71PU40N4Z
5.5 7.5 ATV 71HU55N4 10 10 1 VW3 A4 642 19.000
ATV 71WU55N4
ATV 71PU55N4Z
7.5 10 ATV 71HU75N4 13 19 1 VW3 A4 643 23.000
ATV 71WU75N4
ATV 71PU75N4Z
11 15 ATV 71HD11N4 19 19 1 VW3 A4 643 23.000
ATV 71WD11N4
ATV 71PD11N4Z
15 20 ATV 71HD15N4 24 26 1 VW3 A4 644 34.000
ATV 71WD15N4
18.5 25 ATV 71HD18N4 32 35 1 VW3 A4 645 42.000
ATV 71WD18N4
22 30 ATV 71HD22N4 35 35 1 VW3 A4 645 42.000
ATV 71WD22N4
30 40 ATV 71HD30N4 44 43 1 VW3 A4 646 45.000
ATV 71WD30N4
37 50 ATV 71HD37N4 58.7 72 1 VW3 A4 647 61.000
ATV 71WD37N4
45 60 ATV 71HD45N4 68 72 1 VW3 A4 647 61.000
ATV 71WD45N4
55 75 ATV 71HD55N4 82.6 101 1 VW3 A4 648 75.000
ATV 71WD55N4
75 100 ATV 71 HD75N4 108 101 1 VW3 A4 648 75.000
ATV 71 WD75N4
THDI 10%
90 125 ATV 71HD90N4 134 180 1 VW3 A4 649 107.000
110 150 ATV 71HC11N4 163 180 1 VW3 A4 649 107.000
132 200 ATV 71HC13N4 192 217 1 VW3 A4 656 119.000
160 250 ATV 71HC16N4 235 289 1 VW3 A4 650 145.000
200 300 ATV 71HC20N4 300 370 1 VW3 A4 651 185.000
220 350 ATV 71HC25N4 330 370 1 VW3 A4 651 185.000
250 400 ATV 71HC25N4 400 217 2 VW3 A4 656 119.000
280 450 ATV 71HC28N4 440 289 2 VW3 A4 650 145.000
315 500 ATV 71HC31N4 470 289 2 VW3 A4 650 145.000
355 – ATV 71HC40N4 530 289 2 VW3 A4 650 145.000
400 600 ATV 71HC40N4 590 325 2 VW3 A4 657 165.000
500 700 ATV 71HC50N4 730 370 2 VW3 A4 651 185.000
(1) By adding a DC choke (see page 152) to ATV 71p075N4…pD75N4 and ATV 71PpppN4Zdrives, a THD y 10% is [Link]
DC choke is supplied as standard with ATV 71HD90N4…HC50N4 drives.
These reduced current harmonics are obtained, only for the nominal filter current, on condition that the THDU is < 2% and
the RSCE > 66%.
(2) In: nominal filter current.
Presentation: Characteristics: Dimensions: Schemes:
page 161 page 161 pages 210 and 211 pages 232 and 233
164
References (continued) 1
Variable speed drives
Altivar 71: reduction of current harmonics
Option: passive filters
Passive filters: three-phase power supply 460 V 60 Hz
Motor rating For drives Network Filter Quantity Reference Weight
Line current ln (2) per drive
kW HP A A kg
THDI 10% (1)
0.75 1 ATV 71H075N4 2.5 6 1 VW3 A4 661 21.000
ATV 71W075N4
ATV 71P075N4Z
1.5 2 ATV 71HU15N4 3 6 1 VW3 A4 661 21.000
ATV 71WU15N4
ATV 71PU15N4Z
2.2 3 ATV 71HU22N4 4.2 6 1 VW3 A4 661 21.000
ATV 71WU22N4
ATV 71PU22N4Z
3 – ATV 71HU30N4 6 6 1 VW3 A4 661 21.000
ATV 71WU30N4
ATV 71PU30N4Z
4 5 ATV 71HU40N4 7 10 1 VW3 A4 662 27.000
ATV 71WU40N4
ATV 71PU40N4Z
5.5 7.5 ATV 71HU55N4 10 10 1 VW3 A4 662 27.000
ATV 71HU55N4
ATV 71PU55N4Z
7.5 10 ATV 71HU75N4 13 19 1 VW3 A4 663 28.000
ATV 71WU75N4
ATV 71PU75N4Z
11 15 ATV 71HD11N4 19 19 1 VW3 A4 663 28.000
ATV 71WD11N4
ATV 71PD11N4Z
15 20 ATV 71HD15N4 24 26 1 VW3 A4 664 41.000
ATV 71WD15N4
18.5 25 ATV 71HD18N4 32 35 1 VW3 A4 665 49.000
ATV 71WD18N4
22 30 ATV 71HD22N4 35 35 1 VW3 A4 665 49.000
ATV 71WD22N4
30 40 ATV 71HD30N4 44 43 1 VW3 A4 666 56.000
ATV 71WD30N4
37 50 ATV 71HD37N4 58.7 72 1 VW3 A4 667 80.000
ATV 71WD37N4
45 60 ATV 71HD45N4 68 72 1 VW3 A4 668 98.000
ATV 71WD45N4
55 75 ATV 71HD55N4 82.6 101 1 VW3 A4 668 98.000
ATV 71WD55N4
75 100 ATV 71HD75N4 108 101 1 VW3 A4 668 98.000
ATV 71WD75N4
THDI 5 %
90 125 ATV 71HD90N4 134 180 1 VW3 A4 669 151.000
110 150 ATV 71HC11N4 163 180 1 VW3 A4 669 151.000
132 200 ATV 71HC13N4 192 217 1 VW3 A4 676 171.000
160 250 ATV 71HC16N4 235 289 1 VW3 A4 670 215.000
200 300 ATV 71HC20N4 300 370 1 VW3 A4 671 250.000
220 350 ATV 71HC25N4 330 370 1 VW3 A4 671 250.000
250 400 ATV 71HC25N4 400 217 2 VW3 A4 676 171.000
280 450 ATV 71HC28N4 440 289 2 VW3 A4 670 215.000
315 500 ATV 71HC31N4 470 289 2 VW3 A4 670 215.000
355 – ATV 71HC40N4 530 289 2 VW3 A4 670 215.000
400 600 ATV 71HC40N4 590 325 2 VW3 A4 677 240.000
500 700 ATV 71HC50N4 730 370 2 VW3 A4 671 250.000
(1) By adding a DC choke (see page 152) to ATV 71p075N4…pD75N4 and ATV 71PpppN4Z drives, a THD y 5% is [Link]
DC choke is supplied as standard with ATV 71HD90N4…HC50N4 drives.
These reduced current harmonics are obtained, only for the nominal filter current, on condition that the THDU is < 2% and
the RSCE > 66%.
(2) In: nominal filter current.
Presentation: Characteristics: Dimensions: Schemes:
page 161 page 161 pages 210 and 211 pages 232 and 233