Foundation and Roof Design Details
Foundation and Roof Design Details
23625
A B C D E No. NOTES
5800 5800 5800 1800 1680 2745
23625 1. The Structural Engineer to inspect all the reinforcement
5800 5800 5800 6225 5800 5800 5800 1800 1680 2745 cages before concreting
5800 5800 5800 6225
3 2. All dimensions are in millimetres ( mm ) unless otherwise
shown or stated.
1800
1800
Columns 40mm
1575
Beams 25mm
6375
450
Slabs 20mm
1575
4. Reinforced concrete to be class 25 / 20 (1:1.5 : 3) for
1550
6375
Columns and other structural concrete to be class 20/(20)
Blinding concrete to be class 15 / 20 (1: 3 : 6 )
1550
fall fall fall fall 5. Reinforcement steel to be : -
1450
1450
6. This drawing is to be read inconjuction with all other
14375
14375
before proceeding.
TRUSS
TRUSS
TRUSS
TRUSS
TRUSS
7. Timber to be second grade, treated cypress(GS) celcured
2550
seasoned to the Equilbrium Moisture Content (EMC).
4000
8000
8000
8. Abbreviations :-
1 1 T1 - Means the first topmost layer of reinforcement
8000
8000
T2 - Means the second topmost layer of reinforcement
fall fall fall fall 6D16 - 01 B1 - Means the bottommost layer of reinforcement
B2 - Means the second bottommost layer of reinforcement
HTS - Means High Tensile Stress
20D8 - 01-175
DPC - Damp Proof Course
DPM - Damp Proof Membrane
9. Coarse aggregate to be machine crushed graded
1 03 03 aggregate or equivalent and fine aggregate to be river
300
200
02 sand to engineer's approval.
1 10. Maximum allowable Soil Bearing Capacity (SBC) to be
FOUNDATION LAYOUT 1 : 100 03 03
450 350 Kn/m2. Foundation details to be confirmed on site
- Floor Slab to be casted with D10 @ 250 both ways
ROOF LAYOUT 1:100 8-8 by the Engineer.
700
- All joints are contraction joints 150 x 150 x 6mm angle bracing
ZS 10 Purlins @ 1059mm c/c Roof member No. 1 11. Fabrication drawings to be done by the contractor and to
unless otherwise shown
( 125.8 x 50 x 2mm ) be approved by the Engineer.
- Foundation details to be confirmed on site
Roof member No. 2
75
by the Engineer. Ground Floor
12. All fabrication works to be carried out under engineer's
- All portal frame columns bases are Type 01 unless supervision.
otherwise shown 13. Steel works to BS449 and BS 5950.
6D16 - 01
14. All dimensions to be confirmed on site.
500 500
1000 1000 15. All welding to be 6mm fillet weld.
2 No. 16mm J Bolts embedded in
1000 1000
1000 1000
ring beam.
Type C1 (13 No.) 16. Two coats of red oxide to be applied on all fabricated
50
1000 1000 metal surfaces. One coat after fabrication and the other
R.C. Column Details 1:25
200
1000 1000
1000 after erection on site.
1000 15mm Thick Mild Steel
50
500 500 Bearing Plate 75 x 75 x 4mm angle
450
1285
R8 - 24 - 200
3 6D16 - 27
Eave Truss connection Details 1:10
( Plan )
10°
300
Roof Pitch = 10 deg
KEY
4000
50
Member No. 6 200 200
7Y16 - 21 -250 B
2 2. D10@250mm both ways reinforcement (top). 1000
3 3. 150mm thick ground floor slab (class 15/20). PROPOSED GODOWN PLOT L. R. NO.
4. 1000 gauge polythene sheet d.p.m
4
(damp-proof membrane).
Section 3 - 3 52171 MATASIA NGONG.
5. 50mm thick murram blinding. 1000
6. 300mm thick hardcore handpacked and
5
well compacted in layers not exceeding
Ground Floor Slab
6 150mm thick. 7D16 -21 -250B2
7. 50mm thick concrete blinding.
NOTE.
1000
200
unless otherwise shown. 02
200
200
D12 - 02 - 250 B1 150 03 03 & foundation Details
7 7 3 450 3
Foundation Footing 4 D12 - 01 B2 4 D12 - 01 B2
700 800
DEVELOPER
CARE TO LEARN INTERNATIONAL,
T1 (10No.) 1 : 50 External
125
Internal P.O. Box 1424,
250
TYPICAL SECTION THROUGH ROOF
200
600 600 600 600 NAIVASHA.
125
Purlins to be 125.8 x 50 x 2mm Z - Purlins 8
FOUNDATION FOOTING DETAILS 1:20 125 125 Plan
8
150 150
ARCHITECTS
Z- Purlins at maximum spacing of 1000mm centres No Initial Gap Initial Gap Type 01 Arch. JOEL [Link]
Maximum portal frame spacing to be 6225mm centres
150
150
DRG No.
Revision Suffix
ST.01/0819/01