FCU Submittal Part 3 of 3
FCU Submittal Part 3 of 3
DESCRIPTIONS PAGE
FEATURES & SPECIFICATIONS 2
FAN PERFORMANCE 12 - 13
ELECTRICAL DATA 15
GUIDE SPECIFICATIONS 16
FEATURES & SPECIFICATIONS
GENERAL
Type Chilled Water Fan Coil
Model 040 050 060 070 090 100
Nominal Capacity kW 12.2 14.7 17.6 20.9 26.5 29.9
Btu/hr 41,580 50,251 60,218 71,467 90,367 102
Air Quantity (Range)l/s 430 - 657 421 - 659 563 - 780 784 - 1283 825 - 1232 1271 - 1813
Power Supply V/Ph/Hz 230/1/50
FAN
Type Centrifugal Forward Curved Blades
Drive Direct Drive
Quantity pcs 1 2
Max Rev rpm 1500
Diameter mm 241
MOTOR
Type Permanent Split Capacitor, 3 Speeds
Quantity pcs 1
Power Input kW 0.47 0.47 0.83 1.01 1.01 1.41
Power Output kW 0.32 0.32 0.46 0.75 0.75 0.80
Full Load Amps A 2.46 2.46 4.40 4.55 4.55 7.40
Rev rpm 1350 1350 1200 1360 1360 1405
COIL
Type Copper Tube, Aluminium Plate Fins
Row - Fins/in 2 - 15 3 - 15 4 - 15 3 - 15 4 - 15 3 - 15
Face Area m2 0.343 0.343 0.343 0.437 0.437 0.613
FILTER
Type Washable / Throw Away
Size (H x W x D) mm 398 x 744 x 12 398 x 944 x 12 398 x 1344 x 12
Quantity pcs 1
CONNECTIONS
Supply Inch 1" BSPT MPT
Return Inch 1" BSPT MPT
Drain Pipe Inch 3/4" NPT MPT
Net weight Kg 66.00 67.00 69.00 92.00 97.00 115.00
DIMENSIONS
Height mm 480
Width mm 1000 1200 1600
Length mm 680
FLA: FULL LOAD AMPS
2
PHYSICAL DIMENSION – UNIT SIZE 40LM 040
20.0 960.0
109.1 748.9
53.7
680.7
420.0
130.7
23.2
235.0 382.5
WATER OUT
1000.0 1 INCH BSP GRADE B (MPT)
1012.0 53.8
WATER IN
1 INCH BSP GRADE B (MPT)
102.1
54.9
260.0
183.9
112.8
188.8 16.4
237.9
120.7
FRONT VIEW
3/4 INCH NPT (MPT) DRAIN TUBE
3
PHYSICAL DIMENSION – UNIT SIZE 40LM 050
20.0 960.0
109.1 748.9
53.7
680.7 420.0
130.7 23.2
WATER OUT
235.0 382.5
1 INCH BSP GRADE B (MPT)
1000.0 53.8
WATER IN
1012.0 1 INCH BSP GRADE B (MPT) 101.7
CONTROL BOX
54.9
260.0
183.9
112.8
189.3
16.4
237.9
120.7
3/4 INCH NPT (MPT) DRAIN TUBE
FRONT VIEW
4
PHYSICAL DIMENSION – UNIT SIZE 40LM 060
20.0 960.0
109.1 748.3
53.7
680.7 420.0
130.7
1012.8
WATER IN
1 INCH BSP GRADE B (MPT) 53.8
TOP VIEW 101.7
CONTROL BOX
20.2
54.9
260.0
183.9
112.8
16.4
188.8 237.9
120.7
FRONT VIEW
5
PHYSICAL DIMENSION – UNIT SIZE 40LM 070
20.0 1160.0
109.1 948.9
53.0
680.0 420.0
130.0
54.9
260.0
183.5
91.0
120.7
FRONT VIEW
3/4 INCH NPT (MPT) DRAIN TUBE
6
PHYSICAL DIMENSION – UNIT SIZE 40LM 090
20.0 1160.0
109.1 948.9
680.0 420.0
130.0
23.8
189.5 303.0 215.0 303.0
54.9
260.0
183.5
91.0
16.4
188.4 237.9 120.7
FRONT VIEW
RIGHT SIDE VIEW
7
PHYSICAL DIMENSION – UNIT SIZE 40LM 100
20.0 1560.0
109.1 1348.9
54.0
680.0 420.0
130.4
23.4
389.5 303.0 215.0 303.0
1600.0
WATER OUT
1612.0
1 INCH BSP GRADE B (MPT)
WATER IN
47.7
TOP VIEW 1 INCH BSP GRADE B (MPT)
23.8
23.8
54.9
260.0
182.3 16.4
94.4
190.2 237.9
8
PERFORMANCE DATA COOLING CAPACITIES
9
PERFORMANCE DATA PRESSURE DROP
40LM040
250
Water Pressure Drop (kPA)
200
150
100
50
0
0 10 20 30 40 50 60
Water Flow (l /min)
40LM050
120
Water Pressure Drop (kPA)
100
80
60
40
20
0
0 10 20 30 40 50 60 70
Water Flow (l /min)
40LM060
60
Water Pressure Drop (kPA)
50
40
30
20
10
0
0 10 20 30 40 50 60 70 80 90
Water Flow (l /min)
10
PERFORMANCE DATA COIL PRESSURE DROP
40LM070
250
Water Pressure Drop (kPA)
200
150
100
50
0
0 10 20 30 40 50 60 70 80 90
Water Flow (l /min)
40LM090
350
Water Pressure Drop (kPA)
300
250
200
150
100
50
0
0 20 40 60 80 100 120
Water Flow (l /min)
40LM100
140
Water Pressure Drop (kPA)
120
100
80
60
40
20
0
0 20 40 60 80 100 120 140
Water Flow (l /min
11
FAN PERFORMANCE
40LM040
40LM050
40LM060
12
FAN PERFORMANCE
40LM070
40LM090
40LM100
13
SOUND PRESSURE LEVEL DATA
Note: Sound measurement in accordance with standard JIS B8616-2006 (1.5 Meter below the unit bottom) at 8mm ESP
14
ELECTRICAL DATA
Medium 315 587 1029 2.46 Medium 315 600 1022 2.46
Medium 462 617 1278 4.4 Medium 750 859 1348 4.55
Medium 750 919 1326 4.55 Medium 800 1290 1259 7.4
15
GUIDE SPECIFICATIONS
Part 1 – GENERAL
1.1 System Description 2.4 Fan
Horizontal, furred-in, above ceiling for ducting Direct driven, double width fan wheel with forward
room fan coil unit. curved blades shall be statically and dynamically
balanced. Fan wheels shall be constructed of high
density reinforced polypropylene.
1.2 Quality Assurance
Unit shall be tested in accordance with ARI
Standard 440. Each coil shall be factory tested for 2.5 Coils
leakage at 400 psig air pressure with coil Drain pan covers entire length and width of coil till
submerged in water. Factory is ISO-9001 certified. the headers. Drain pan inside coated and outside
insulated. Standard base unit shall be equipped with
a 4-row coil for installation in a 2-pipe system. Coils
1.3 Delivery Storage and Handling shall have 9.5mm copper tubes, aluminum fins
bonded to the tubes by mechanical expansion.
Each unit shall be individually packaged from point
Each coil shall have a manual air vent and threaded
of manufacture. Units shall be handled and stored
connections field piping. Working pressure 1.72
in accordance with the manufacturer’s instructions.
Mpa, 0.105mm fin thickness and 0.24mm tube wall
thickness.
Part 2 – PRODUCTS
Equipment 2.6 Operating Characteristics
2.1 General A one coil unit installed in a 2-pipe system shall be
Factory assembled, horizontal draw through type
capable of providing cooling as determined by the
fan coil for furred-in ducted installations. Units
operating mode of the central water supply system.
shall be completed with water coil(s), fan(s),
motor(s), drain pan, filters and all required wiring,
collars for ducted units. Unit insulation and unit’s
drain pan insulation are UL94 compliance. 2.7 Electrical Requirements
Standard unit shall operate on 230V±10%, single
phase, 50Hz electric power.
2.2 40LM Furred-in Units
Base 40LM unit with factory installed plenum
section and cleanable filter as shown on 2.8 Motor(s)
equipment drawings. The plenum shall be rear air Fan motors shall be 3-speed, 230V, single phase,
return. Shall enclose the fan/motor assemblies, 50Hz permanent split capacitor type, with ball type
and shall be lined with 12.7mm thick PU insulation bearings and over-sized oil reservoirs to ensure
20kg/m³ density and 6.0mm PE insulation lubrication. The fan motor(s) shall be equipped with
28.6kg/m³ density on the drain pan. Unit shall integral automatic temperature reset for motor
have a removable panel to provide access to protection. Motor insulation is Class E and motor is
fan/motor assemblies and unit identification label. open drip proof type.
16
Carrier International Sdn. Bhd. (3385-T)
Lot 4, Jalan P/6, 43650 Bandar Baru Bangi,
Selangor Darul Ehsan, Malaysia.
Tel: 03-8913 7600
40LM1 REV-6
01 2015
40LM1-A15-7PD
42C/D SERIES
Ducted Chilled Water Fan Coil Unit
With District Cooling Application
(300 to 2000 CFM)
42DF
42CGT
42DE
42CET
42DC
MODEL : 42CET/CED
4 2 C E T 0 0 3 4 - - 7 2 1 2 5
CISB Code
42 series 25 — AC Motor
Fan Coil Unit E5 — EC Motor
Packing Method
Model 1 — Standard Packing
CE — Furred-in Ceiling
model with plenum Development Series
0 — 42CET/CED (EC motor)
2 — 42CET/CED (AC motor)
T — Standard application
D — District Cooling application Electrical Characteristics
7 — 220/240V-1PH-50Hz
Piping Handling
Unit Size (Airflow, cfm) - — Left
003 — 300 R — Right
004 — 400
005 — 500 - — Opposite end connection
006 — 600 K — Same end connection
008 — 800
010 — 1000 Coil
012 — 1200 3 — 3 row coil
* 014 — 1400 4 — 4 row coil
Note:
* Not applicable for EC motor.
COMPUTER SELECTION
We have made available a computer program to finalize your selections.
Please contact your Carrier representative for a computer selection based on
your “Quick Selection” plus the design parameters of your application.
TABLE OF CONTENTS
Page
Model Number Nomenclature………………………………………..……………………..……...... 2 - 3
Product Features………………………………………………………….………………………………. 4
Technical Data…………………………………………………………………………………….…. 5 - 15
Unit Dimension and Weight………………………………………………………………...….…... 16 - 20
Performance Rating………………………………………………………………………….….…..
g 21 - 26
Electrical Data……………………………………………………………………………….………. 27 - 28
Wiring Diagram……………………………………………………………………………….………29 - 31
Guide Specifications…………………………………………………………….………………….. 32 - 33
2
MODEL NUMBER NOMENCLATURE
MODEL : 42CGT/CGD
4 2 C G T 0 0 3 4 - - 7 0 1 2 5
Packing Method
Model 1
CG — Cabinet model
Development Series
0 — 42CGT, 42CGD
T — Standard Application
D — District Cooling Application Electrical Characteristics
7 — 220/240V-1Ph-50Hz
Note:
* Not aplicable for EC motor.
** Applicable for 42DC/DCD model only.
3
PRODUCT FEATURES
If fan coil terminals are the answer to your job requirements, you can’t afford to pass
over Carrier’s versatile and extensive range of fan coil units.
With Carrier’s 42 series fan coil units, you can select furred-in or cabinet style, in capacities from 300 to 2,000
cfm. Units are ideal for installations in residential, hotels, motels, apartments, offices, hospitals, schools and
other multi-room buildings.
Carrier room fan coil terminals provide unsurpassed year round comfort, with high cooling performance.
Carrier 42 series terminal requires very little space and is easy to install. Piping, drain and wiring connections
are readily accessible to save installation time and field labor expense.
Forget about expensive ductwork, forget about complex system controls, forget the aggravation and choose
Carrier’s easy to install room fan coil units – in pipe systems. Opt for quiet. Carrier room fan coil units
operate at exceptionally low sound levels. Generous amount of insulation absorbs operating sound and
rugged, rigid construction ensures vibration free operation at all fan speeds.
Carrier room fan coil units are economical. Three speed fans deliver just the right amount of conditioned air
for your comfort needs at any load. And each individual unit can be shut off when not in use. Permanent Split
Capacitor motors deliver peak operating efficiency. In choosing Carrier units, you can match your application
with a wide range of custom-designed options and accessories.
When you go for Carrier 42 series, the advantages to owner, installer and the room occupants are too great to
ignore.
Carrier 42 series fan coils give you design and Save operating costs with Carrier fan coils
equipment location flexibility • Higher efficiency & reliability Electronically
• Wide range of popular capacities, 300 – 2000 cfm Commuted Motor (42CET/CED, DC/DCD) -
• Available up to 11 sizes. optional.
• Cabinet or furred-in units • Individual unit shut-off when not in use
• Choose from numerous control systems • Efficient, 3 speed centrifugal fans
• Select 3 row coils (42CET), 4 row coils (42CET, • Permanent Split Capacitor motors
CGT, DC, DE & DF) • High efficiency heat transfer surface
• Accommodates 2 pipe systems
• Fully insulated/low fan speed means quiet operation Carrier fan coils save your service and
• Draw outside air for odor dilution maintenance expense
• Uses only minimal space • Nationwide Carrier service
• Insulated drain pan
Select Carrier fan coils for easy, low cost installation • Easy access to components
• Easy wiring, piping connections • Rugged construction
• Mounting holes, slots speed hanging • Factory leak test for coil
• Requires
R i no expensive
i d ductwork
k • Cleanable
C f
filters
• Ideal for new construction or renovation • Long life, heavy duty bearings
4
TECHNICAL DATA
NOTE:
* Based on motor at high speed, standard air and dry coil operation; 5.6˚C water temperature rise; entering air temperature 26.7˚C DB;
19.4˚C WB; Entering water temperature 7.2˚C.
** Sound measurement in accordance with Standard JIS8616-2006 (1.5m below the unit bottom).
Electronically Commuted Motor (ECM) is available for unit size 003 to 012 - optional.
LT101
Controller
- - For other design conditions, please apply the selection program to finalize your applications - -
Performance Assurance
Rated in accordance with
ARI Standard 440-2008
5
TECHNICAL DATA (cont’)
MODEL: 42CET
PERFORMANCE
003 004 005 006 008 010 012 014
Nominal CFM 300 400 500 600 800 1000 1200 1400
High
Air Volume ℓ/s 142 189 236 283 378 472 566 661
kW 3.38 4.25 4.58 4.99 7.55 8.58 11.5 13.53
Cooling Capacity (Fluid)*
Btu/hr 11,530 14,486 15,637 17,009 25,758 29,270 39,232 46,157
Motor nominal power output W 32 45 70 72 55 (x2) 70 (x2) 72 (x2) 70 (x3)
Motor current Amp - Refer to page 27 -
High 37.1 37.4 39.1 40.4 41.3 43.1 43.4 43.6
Sound
Med dB(A) 34.6 34.9 35.7 38.8 38.8 40.8 39.9 41.8
Pressure **
Low 33.0 32.1 32.4 35.4 34.6 37.2 37.6 39.9
Water Flow ℓ/s 0.14 0.18 0.20 0.21 0.32 0.37 0.49 0.58
Water Pressure Drop kPa 13.5 23.8 17.6 9.3 17.4 24.5 30.8 46.4
yp
Fan Type Centrifugal
g Forward-curved blades
Motor Type Permanent Split Capacitor
No. of Row 4
Coil
Working Pressure 1.72 MPa
In-Out (Thread) / Material ¾” FPT (BSP) / Brass
Connections
Condensate Drain / Material ¾” MPT (BSP) / GI Steel
Height mm 241 4
241.4
Cabinet Size Width mm 556.8
Length mm 770 890 970 1,170 1,410 1,530 1,770 2,010
Casing Material / Thickness Galvanized Steel / 0.8 & 1.0mm
Casing Treatment / External Finish Non-painted / -
Net Weight kg 17.8 20.5 21.7 23.7 33.0 36.7 42.0 49.1
NOTE:
* Based on motor at high speed, standard air and dry coil operation; 5.6˚C water temperature rise; entering air temperature 26.7˚C DB;
19.4˚C WB; Entering water temperature 7.2˚C.
** Sound measurement in accordance with Standard JIS8616-2006 (1.5m below the unit bottom).
Electronically Commuted Motor (ECM) is available for unit size 003 to 012 - optional.
LT101
Controller
- - For other design conditions, please apply the selection program to finalize your applications - -
Performance Assurance
Rated in accordance with
ARI Standard 440-2008
6
TECHNICAL DATA (cont’)
Electronically Commuted Motor (ECM) is available for unit size 003 to 012 - optional.
LT101
Controller
- - For other design conditions, please apply the selection program to finalize your applications - -
Performance Assurance
Rated in accordance with
ARI Standard 440-2008
7
TECHNICAL DATA (cont’)
MODEL: 42CGT
PERFORMANCE
003 004 005 006 008 010 012
Nominal CFM 300 400 500 600 800 1000 1200
High
Air Volume ℓ/s 142 182 236 283 378 472 566
kW 3.34 4.64 5.64 5.91 8.38 11.47 13.04
Cooling Capacity (Fluid)*
Btu/hr 11,388 15,842 19,242 20,153 28,585 39,151 44,487
Motor nominal power output W 35 48 68 75 58 (x2) 75 (x2) 78 (x3)
Motor current Amp - Refer to page 27 -
High 44.3 43.6 44.5 46.0 49.1 49.5 50.1
Sound
Med dB(A) 42.3 41.5 41.7 41.0 45.5 45.6 48.4
Pressure **
Low 40.2 39.0 38.6 40.5 41.8 40.2 44.3
Water Flow ℓ/s 0.14 0.20 0.24 0.25 0.36 0.49 0.56
Water Pressure Drop kPa 12.7 22.6 46.9 8.8 21.6 47.3 48.1
yp
Fan Type Centrifugal
g Forward-curved blades
Motor Type Permanent Split Capacitor
No. of Row 4
Coil
Working Pressure 1.6MPa
In-Out (Sweat) / Material 3/4” / Copper
Connections
Condensate Drain / Material 7/8” / GI Steel
Height mm 310
Cabinet Size Width mm 582
Length mm 1,030 1,150 1,230 1,350 1,670 2,030 2,270
Casing Material / Thickness Galvanized Steel / 0.9 & 1.0 mm
Casing Treatment / External Finish Powder Painted / Morning Mist
Net Weight kg 39.7 44.6 46.9 50.9 65.0 79.8 90.7
NOTE:
* Based on motor at high speed, standard air and dry coil operation; 5.6˚C water temperature rise; entering air temperature
23.89˚C DB; 17.2˚C WB; Entering water temperature 7.2˚C.
** Sound measurement in accordance with Standard JIS8616-2006 (1.5m below the unit bottom).
- - For other design conditions, please apply the selection program to finalize your applications - -
Performance Assurance
Rated in accordance with
ARI Standard 440-2008
8
TECHNICAL DATA (cont’)
- - For other design conditions, please apply the selection program to finalize your applications - -
Performance Assurance
Rated in accordance with
ARI Standard 440-2008
9
TECHNICAL DATA (cont’)
MODEL: 42DC
PERFORMANCE
006 008 010 012 014 016 018 020
Nominal
N i l CFM 600 800 1000 1200 1400 1600 1800 2000
High
Air Volume ℓ/s 283 378 472 566 661 755 852 943
kW 6.57 7.88 9.94 12.39 14.10 17.71 19.03 20.42
Cooling Capacity (Fluid)*
Btu/hr 22,404 26,890 33,900 42,291 48,106 60,427 64,924 69,688
Motor nominal power output W 120 200 120 (x2) 300 450
Motor current Amp - Refer to page 27 -
High 40.3 42.0 48.4 47.2 49.2 48.6 48.9 49.7
Sound
Med dB(A) 38.3 38.9 44.8 43.1 46.4 46.9 47.6 48.1
Pressure **
Low 35.5 36.5 38.6 39.8 44.6 44.8 44.7 45.6
Water Flow ℓ/s 0.28 0.34 0.42 0.53 0.60 0.76 0.81 0.87
Water Pressure Drop kPa 25.6 33.3 52.7 85.7 82.0 114.6 96.6 117.6
Fan Type Centrifugal Forward-curved blades
Motor Type Permanent Split Capacitor
No. of Row 4
Coil
Working Pressure 1.72 MPa
In-Out (Sweat) / Material 5/8” / Copper 1” / Copper
Connections
Condensate Drain / Material 7/8” / GI Steel
Height mm 416 3
416.3
Cabinet Size Width mm 762.4
Length mm 641 768 870 997 1,124 1,251 1,378 1,479
Casing Material / Thickness Galvanized Steel / 1.0 mm
Casing Treatment / External Finish Non-painted / -
Net Weight kg 39 44 63 72 75 76 83 95
NOTE:
* Based on motor at high speed, standard air and dry coil operation; 5.6˚C water temperature rise; entering air temperature 26.7˚C DB;
19.4˚C WB; Entering water temperature 7.2˚C.
** Sound measurement in accordance with Standard JIS8616-2006 (1.5m below the unit bottom).
LT101
Controller
- - For other design conditions, please apply the selection program to finalize your applications - -
Performance Assurance
Rated in accordance with
ARI Standard 440-2008
10
TECHNICAL DATA (cont’)
LT101
Controller
- - For other design conditions, please apply the selection program to finalize your applications - -
Performance Assurance
Rated in accordance with
ARI Standard 440-2008
11
TECHNICAL DATA (cont’)
MODEL: 42DE
PERFORMANCE
006 008 010 012 014 016 018 020
Nominal
N i l CFM 600 800 1000 1200 1400 1600 1800 2000
High
Air Volume ℓ/s 283 378 472 566 661 755 852 943
kW 6.53 7.85 9.78 12.03 15.23 17.03 19.62 20.51
Cooling Capacity (Fluid)*
Btu/hr 22,286 26,769 33,367 41,063 51,963 58,118 66,954 69,969
Motor nominal power output W 120 200 120 (x2) 300 450
Motor current Amp - Refer to page 28 -
High 44.1 41.1 47.6 47.6 47.6 54.3 51.8 52.1
Sound
Med dB(A) 41.2 38.5 45.5 44.5 44.8 52.8 49.5 49.4
Pressure **
Low 37.6 34.8 40.6 42.4 41.0 47.6 45.3 45.2
Water Flow ℓ/s 0.28 0.33 0.42 0.51 0.65 0.73 0.84 0.88
Water Pressure Drop kPa 17.5 23.9 30.1 38.7 34.9 46.8 29.7 33.5
Fan Type Centrifugal Forward-curved blades
Motor Type Permanent Split Capacitor
No. of Row 4
Coil
Working Pressure 1.72 MPa
In-Out (Sweat) / Material 5/8” / Copper 7/8” / Copper 1 1/8” / Copper
Connections
Condensate Drain / Material 7/8” / GI Steel
Height mm 479
Cabinet Size Width mm 965
Length mm 787 914 1,016 1,143 1,270 1,397 1,524 1,626
Casing Material / Thickness Galvanized Steel / 1.0 mm
Casing Treatment / External Finish Powder Painted / Morning Mist
Net Weight kg 62 71 78 89 95 101 110 114
NOTE:
* Based on motor at high speed, standard air and dry coil operation; 5.6˚C water temperature rise; entering air temperature 26.7˚C DB;
19.4°C WB; Entering water temperature 7.2˚C.
** Sound measurement in accordance with Standard JIS8616-2006 (1.5m below the unit bottom).
- - For other design conditions, please apply the selection program to finalize your applications - -
Performance Assurance
Rated in accordance with
ARI Standard 440-2008
12
TECHNICAL DATA (cont’)
- - For other design conditions, please apply the selection program to finalize your applications - -
Performance Assurance
Rated in accordance with
ARI Standard 440-2008
13
TECHNICAL DATA (cont’)
MODEL: 42DF
PERFORMANCE
006 008 010 012 014 016 018 020
Nominal
N i l CFM 600 800 1000 1200 1400 1600 1800 2000
High
Air Volume ℓ/s 283 378 472 566 661 755 852 943
kW 5.07 7.20 8.82 10.62 12.67 14.49 17.48 19.59
Cooling Capacity (Fluid)*
Btu/hr 17,282 24,577 30,102 36,235 43,227 49,450 59,635 66,856
Motor nominal power output W 80 120 80 (x2) 120 (x2) 200 (x2)
Motor current Amp - Refer to page 28 -
High 44.1 41.1 47.6 47.6 47.6 54.3 51.8 52.1
Sound
Med dB(A) 41.2 38.5 45.5 44.5 44.8 52.8 49.5 49.4
Pressure **
Low 37.6 34.8 40.6 42.4 41.0 47.6 45.3 45.2
Water Flow ℓ/s 0.22 0.31 0.38 0.45 0.54 0.62 0.75 0.84
Water Pressure Drop kPa 10.6 20.9 24.6 31.3 25.7 35.0 24.2 30.8
Fan Type Centrifugal Forward-curved blades
Motor Type Permanent Split Capacitor
No. of Row 4
Coil
Working Pressure 1.72 MPa
In-Out (Sweat) / Material 5/8” / Copper 7/8” / Copper 1 1/8” / Copper
Connections
Condensate Drain / Material 7/8” / GI Steel
Height mm 479
Cabinet Size Width mm 965
Length mm 787 914 1,016 1,143 1,270 1,397 1,524 1,626
Casing Material / Thickness Galvanized Steel / 1.0 mm
Casing Treatment / External Finish Powder Painted / Morning Mist
Net Weight kg 59 66 73 82 88 96 103 108
NOTE:
* Based on motor at high speed, standard air and dry coil operation; 5.6˚C water temperature rise; entering air temperature 26.7˚C DB;
19.4˚C WB; Entering water temperature 7.2˚C.
** Sound measurement in accordance with Standard JIS8616-2006 (1.5m below the unit bottom).
- - For other design conditions, please apply the selection program to finalize your applications - -
Performance Assurance
Rated in accordance with
ARI Standard 440-2008
14
TECHNICAL DATA (cont’)
- - For other design conditions, please apply the selection program to finalize your applications - -
Performance Assurance
Rated in accordance with
ARI Standard 440-2008
15
UNIT DIMENSIONS AND WEIGHT
335 4-12 x 22 mm
27.4
164.0
55
128.4
223 118.5 241.5
272 23
16
UNIT DIMENSIONS AND WEIGHT (cont’)
A
101
C B C
582
422
FRONT VIEW
59
49 47
TOP PANEL
30
110
310
BACK PANEL
RIGHT SIDE VIEW
104
71
61
257 259
218
220.0
165
141
85 82
79.0
D 40
E E BACK PANEL DETAIL
17
UNIT DIMENSIONS AND WEIGHT (cont’)
F
F
D
D
683 683
C C
183.4 183.4
114 B 114
32 32 114 B 114
A
A
36
13 142
64
104
134
268
306
402 356
MTG
HOLE
CONTROL
BOX
683
183.4 C
32 114 B 114
18
UNIT DIMENSIONS AND WEIGHT (cont’)
76
65
C F
CONTROL
BOX
A B D E
C F
813
965
TOP VIEW
20
FILTER (Dimension shown are all in mm)
33
67
66 197
322 64
460 356 391
22mm DIA KO 64
E 64
38mm DIA KO
66
98
44
57 77 77
49 RIGHT SIDE VIEW REAR PANEL ELEVATION
19
UNIT DIMENSIONS AND WEIGHT (cont’)
76
65
C F
CONTROL BOX
A B D E
C F
812 76
965
TOP VIEW
67
66
322 64
460 356
22mm DIA KO 64
64
38mm DIA KO
66
98
FILTER 36
76.9
RIGHT SIDE VIEW REAR PANEL ELEVATION
(TYP)
20
PERFORMANCE RATING
- - For other design conditions, please apply the selection program to finalize your applications - -
21
PERFORMANCE RATING (cont’)
- - For other design conditions, please apply the selection program to finalize your applications - -
22
PERFORMANCE RATING (cont’)
- - For other design conditions, please apply the selection program to finalize your applications - -
23
PERFORMANCE RATING (cont’)
42DCD Furred
Furred-in
in Cabinet Model (4
(4-Rows)
Rows) – District Cooling Applications
Model ESP Air Flow Capacity (kW) Air off FCU (°C) Water Flow Water Pressure
Speed
42DCD Pa (ℓ/s) Total Sensible DB WB (ℓ/s) (kPa)
High 313 4.89 4.14 13.6 12.5 0.13 26.8
006 Medium 50 262 4.35 3.62 13.1 12.1 0.12 21.5
Low 205 3.76 3.01 12.4 11.5 0.10 16.0
High 361 6.68 5.08 12.9 11.5 0.18 55.2
008 Medium 50 282 5.73 4.20 12.2 10.9 0.15 43.9
L
Low 200 4 57
4.57 3 20
3.20 11 3
11.3 10 0
10.0 0 12
0.12 28 0
28.0
High 512 8.02 6.94 13.3 12.4 0.22 53.5
010 Medium 50 441 7.29 6.21 12.9 12.1 0.20 45.6
Low 327 6.09 4.93 12.1 11.4 0.16 33.4
High 572 9.50 8.05 12.9 12.1 0.26 47.4
012 Medium 50 495 8.64 7.21 12.5 11.8 0.23 39.1
Low 396 7.58 6.07 11.9 11.3 0.20 32.2
High 755 11.20 9.87 13.7 12.7 0.30 41.7
014 Medium 50 605 9.72 8.37 13.1 12.3 0.26 32.8
Low 550 9.14 7.79 12.8 12.1 0.25 29.2
High 858 14.26 12.06 12.9 12.1 0.38 55.1
016 Medium 50 767 13.29 11.11 12.6 11.9 0.36 48.6
Low 687 12.37 10.22 12.3 11.7 0.33 42.7
High 937 15.15 12.65 13.4 12.3 0.41 62.6
018 Medium 50 875 14.51 12.03 13.2 12.1 0.39 59.1
Low 692 12.46 10.07 12.5 11.6 0.33 44.6
High 970 15.76 13.23 13.3 12.2 0.42 55.5
020 Medium 50 890 14.90 12.40 13.0 12.1 0.40 51.6
Low 693 12.77 10.23 12.3 11.5 0.34 38.8
NOTE: Air Conditions: EDB/EWB 24.4/17.2°C Water Conditions: EWT/LWT 5.5/14.4˚C ∆T: 8.9˚C
- - For other design conditions, please apply the selection program to finalize your applications - -
24
PERFORMANCE RATING (cont’)
- - For other design conditions, please apply the selection program to finalize your applications - -
25
PERFORMANCE RATING (cont’)
- - For other design conditions, please apply the selection program to finalize your applications - -
26
ELECTRICAL DATA (cont’)
27
ELECTRICAL DATA (cont’)
28
WIRING DIAGRAM
OFF L M H TB
(H) RED H
1
(M) BLUE M
2 FM cap
B (L) WHITE L
3
(C)
4 CDM
YEL H
SS 5
M FM cap
6
L
CDM
POWER H
M FM cap
L
FM MOTOR
SS SWITCH CDM
TB TERMINAL BLOCK
cap CAPACITOR
TB
L BLUE
1
N GRAY
POWER 2
E GREEN/YELLOW
3
WHITE WHITE PWM1 L
4
BLACK BLACK FG1 FM with N
5 Driver 1
E
RED RED COM
6
L
CONTROLLER WHITE
N WHITE PWM2 L
7
BLACK BLACK FG2 FM with N
8
Driver 2 E
RED RED COM
9
LEGEND:
FIELD WIRING
FACTORY WIRING IF REQUIRED FM MOTOR
FACTORY WIRING TB TERMINAL BLOCK
29
WIRING DIAGRAM
BLK
BRN
BLU
RED FAN
MOTOR 2 CAPACITOR
YEL OR WHT
BRN
TERMINAL
OFF L M H BLOCK
HIGH BLK
H
1 BRN
M MEDIUM BLU
2 FAN
B L LOW RED
MOTOR 1 CAPACITOR
3
C BRN
COMMON YEL OR WHT
4
3 SPEED SWITCH
L1 EQUIP. GND.
L2 OR N
GROUND
42DC UNIT WIRING
M RED
OFF L H TB BLK
HIGH
TO TABLE
H YEL
REFER
1
M MEDIUM BRN
2 CAP
B L LOW ORA
3
C COMMON BLU BLK
4
LEGEND:
FIELD WIRING
FACTORY WIRING IF REQUIRED
FACTORY WIRING
30
WIRING DIAGRAM
GREEN/YELLOW E
GROUND 1
L1 BLUE L
2
L2 or N GREY N
3
WHT WHT PWM1
4
BLK BLK FG1 DRIVER FAN
5 1 MTR 1
CONTROLLER
TB
LEGEND:
FIELD WIRING
FACTORY WIRING IF REQUIRED
FACTORY WIRING
NOTE: 1. Caution – disconnect power before servicing, wait for at least 20 sec to allow current completely drain off from driver.
2. Use 14 AWG, 75˚C MIN, copper conductor.
3. Motor(s) thermally protected.
4. Provide disconnect means & over-current protection as required.
5. All models use 6 pole terminal block except 42DC-012 with 2 fan motors uses 9 pole terminal block.
6. Use cable wire “UL2464”specification to ensure transmission reliability for motor to FCU controller.
31
GUIDE SPECIFICATIONS
HVAC Guide Specifications 2.5 42DE/DED Horizontal Painted Cabinet unit for
Size range: 300 to 2000 Nominal Cfm concealed installation
Unit shall be constructed of galvanized steel with
Part 1 – GENERAL removable panels for access to internal components.
Units have 12.7mm PU insulation 20kg/m³ density on
1.1 System Description chassis and plenum box and 6.0mm PE insulation
Horizontal room fan coil unit with furred-in,
Horizontal, furred in above 28.6kg/m³
g densityy on the drain p pan. Filter track with
ceiling for ducting, or with cabinet for exposed ceiling one-in permanent filter, one-in supply collar and 64mm
installations. return air collar on rear of unit for duct connection.
1.2 Quality Assurance 2.6 42DF/DFD Horizontal Cabinet Unit for Exposed
Unit shall be tested in accordance with ARI Standard Installation
440. Each coil shall be factory tested for leakage at Unit shall be constructed of steel with morning mist re-
400 psig air pressure with coil submerged in water. coatable baked enamel finish. Cabinet shall be lined
Factoryy is ISO-9001 certified. with 12.7mm PU insulation 20kg/m³ g densityy on chassis
and plenum box and 6.0mm PE insulation 28.6kg/m³
1.3 Delivery storage and handling
density on the drain pan and have removable bottom
Each unit shall be individually packaged from point of
access panel. Unit shall include hinged bar type return
manufacture. Unit shall be handled and stored in
air grille on rear of unit with one-in permanent filter and
accordance with the manufacturer’s instructions.
integral double deflection supply grille.
Part 2 - PRODUCTS 2.7 Fan
Direct driven, double width fan wheels with forward
Equipment curved d blades
bl d shall
h ll be
b statically
t ti ll andd dynamically
d i ll
2.1 General balanced. Scrolls shall be constructed of galvanized
Factory assembled, horizontal, blow-thru type fan coil steel. Fan wheels shall be constructed of galvanized
for furred-in, exposed ceiling or ducted installations. steel.
Unit shall be complete with water coil(s), fan(s), 2.8 Coils
motor(s), drain pan, filters and all required wiring, Galvanized drain pan covers entire length & width of
collars for ducted units. Unit insulation are UL94 coil till the headers. Drain pan inside powder coated
compliance, whereas drain pan insulation are UL94 & and outside insulated.
NFPA-90A compliance.
2.2 42CET, CED Furred-in Units 42CET/CED & DC/DCD models
Base 42CET, CED unit with factory installed plenum Standard base unit shall be equipped with a 3-row or
section and cleanable filter as shown on equipment 4-row coil for installation in a 2-pipe system. Coils
drawings. The plenum shall be rear air return. Shall shall have 7mm copper tubes, aluminium fins bonded
enclose the fan/motor assemblies, and shall be lined to the tubes by mechanical expansion. Each coil shall
with 10mm thick PU insulation 20kg/m³ density and have a manual air vent and threaded or sweat
6 0mm PE insulation 28.6kg/m
6.0mm 28 6kg/m³ density on the drain connections
co ect o s field
ed p piping
p g ((refer
e e to Technical
ec ca Data).
ata)
pan. Unit shall have a removable panel to provide Working pressure 1.72 MPa, 0.105mm fin thickness
access to fan/motor assemblies and unit identification and 0.24mm tube wall thickness.
label.
42CGT/CGD, DE/DED & DF/DFD models
2.3 42CGT/CGD Decorative Ceiling Fan Coil Unit Standard base unit shall be equipped with 4-row coil
Unit with stamped discharge grille, removable bottom for installation in a 2-pipe system. Coils shall have
access panel with stamped return air grille, filter track 9.5mm copper tubes, aluminium fins bonded to the
and filter. The panel shall be fastened with slotted tubes byy mechanical expansion.
p Each coil shall have
head, positive-locking quarter-turn fasteners. a manual air vent and threaded or sweat connections
Units have 12.7mm PU insulation on chassis and field piping (refer to Technical Data). Working
10mm PU insulation on coil top panel with 20kg/m³, pressure 1.72 MPa, 0.105mm fin thickness and
and 6.0mm PE insulation 28.6kg/m³ density on the 0.28mm tube wall thickness.
drain pan.
2.4 42DC/DCD Horizontal Base Unit with Plenum for 2.9 Operating Characteristics
Concealed Installation A one coil unit installed in a 2-pipe system shall be
Unit have a factory installed,
installed galvanized steel plenum capable
bl off providing
idi cooling
li as determined
d t i d byb the
th
section and one-in permanent filter. The plenum shall operating mode of the central water supply system.
be rear return, lined with 12.7mm PU insulation
20kg/m³ density and plenum box and 6.0mm PE
insulation 28.6kg/m³ density on the drain pan, and
include a removable panel to provide access to the
fan/motor assembly.
32
GUIDE SPECIFICATIONS
LT101
Controller
3 2 Filter
3.2
Permanently washable aluminium filters with 21mm
thick and 70% gravimetric efficiency as per European
Union EN779 class.
33
Carrier International Sdn Bhd, Malaysia
Manufacturer reserves the right to discontinue, or change at anytime, specifications or designs without notice and without incurring obligations.
42CD-E13-7PD
INSTALLATION, START-UP AND
Carrier
International SERVICE INSTRUCTIONS
42C
Sdn. Bhd.
Malaysia FAN COIL AIR CONDITIONERS
M k Piping
Make Pi i C
Connections
ti - Refer
R f tot Table
T bl 1 for
f piping
i i
CONTENTS:
connection physical dimensions.
INSTALLATION 1
DRAIN CONNECTIONS - Install drain line in accordance
PHYSICAL DATA 2 with all applicable codes. Slope drain away from unit.
Insulate the drain line to prevent sweating.
POWER ON 2
START-UP 3 WATER SUPPLY/RETURN CONNETIONS - Install
piping in accordance with all applicable codes. Position
SERVICE 3 valves over the drain pan. Be sure valves are in proper
operating position and are easily accessible for adjustment.
If coil and valve package connections will be made with a
INSTALLATION
solder joint, care should be taken to ensure that
components in the valve package are not subjected to high
Unpack and Inspect Units - Remove shipping wraps temperatures which may damage seals or other materials.
from all units. Check the shipment against shipping order. if Many 2-position electric control valves are provided with a
shipment is damaged or incomplete, file claim with manual operating level. This level should be in the OPEN
transportation company and advise Carrier immediately. position during all soldering operations.
If coil connection is made with a union, the coil side of the
Protect Units Form Damage -To maintain warranty, union must be prevented from turning (it must be backed
protect units against adverse weather, theft or vandalism on up) during tightening. Do not over tighten! Over tightening
jobsite. will distort (egg shape) the union seal surface and destroy
the union.
Prepare Jobsite for Unit Installation - To save time
and to reduce the possibility of costly errors, set a complete Steam Connections - On units with steam heating coils, the
sample installation in a typical room at jobsite. Check all maximum steam pressure applied to the unit should never
critical dimensions such as pipe, wire and duct connection exceed 10 psig.
requirements. Refer to job drawings and product dimension
drawings as required. Instruct all trades in their part of the TEST AND INSULATE -When all joints are complete,
installation. perform hydrostatic test for leaks. Vent all coils at this time.
Check interior unit piping for signs of leakage from shipping
Identify and Prepare Units damage or mishandling. If leaks are found, notify a Carrier
Be sure power requirements match available power source. representative before initiating any repairs. Release
Refer to unit nameplate and wiring diagram. trapped air from system (refer to Make Final Preparations
section).
Place Unit in Position
1
1. Be sure unit is level or pitched towards drain to ensure
proper drainage and operation. Pitch of suspended unit
can change after coil is filled; recheck after filling coil. All water coils must be protected from freezing after
2. When installing ceiling units, use factory-provided initial filling with water. Even if system is drained, unit
mounting holes. Units are not balanced on mounting coils may still have enough water to cause damage
holes. Select suitable vibration isolators at installation. If when exposed to temperatures below freezing
used, adjust isolators so unit is uniformly suspended and
pitched. Following the hydrostatic test, insulate all piping to prevent
3. Models 42CE with bottom inlet may be installed in sweating.
noncombustible areas only.
only To ensure compliance with building codes, restore the
4. Protect units from damage caused by jobsite debris. Do structure’s original fire resistance rating by sealing all holes
not allow foreign material to fall into drain pan. Prevent with materials carrying the same fire rating as the structure.
dust and debris from being deposited on motor or fan
wheels. Make Electrical Connections - Refer to unit serial plate
for required supply voltage, fan and heater amperage and
Table 1 – Physical Data required circuit ampacities. Refer to unit wiring diagram for
Dimension (inch) unit and field wiring.
COIL OUTLET,, INLET 5/8 OD The fan motor(s) should never be controlled by any wiring
or device other than the factory-supplied switch or
DRAIN CONNECTION 42C 7/8 OD thermostat/ switch combination unless prior factory
SUPPLY DUCT authorization is obtained. Fan motor(s) may be temporarily
1
Flange Connection wired for use during construction only with prior factory
approval and only in strict accordance with the instructions
issued at that time
42CGT/CGD
42CET/CED
To Clean Coil
1. Be sure electrical disconnect is open, locked and
tagged while working on unit.
2 Remove return air grille access panel and brush
2.
between coil fins with stiff wire brush. Follow up by
cleaning with vacuum cleaner. If coil is cleaned with air
hose and nozzle, take care not to drive dirt and dust
into other components.
3. Install clean filter as described in the section Clean or
Replace Air Filters.
Carrier
International
Sdn. Bhd.
Malaysia
CONTENTS:
INSTALLATION 1
PHYSICAL DATA 2
POWER ON 3
START-UP 3
SERVICE 3-4
Fig. 1 – Drain Line Details, Typical
INSTALLATION
Step 6 - Make Piping Connections
Step 1 - Unpack and Inspect Units DRAIN LINE - Install a trapped drain line in accordance with
Remove shipping
R hi i wraps from
f allll units.
it Check
Ch k the
th shipment
hi t all applicable codes.
codes Slope drain line away from unit.
unit Insulate
against shipping order. Check for concealed shipping drain line to prevent sweating. Drain connections are shown
damage. If shipment is damaged or incomplete, file claim in Fig. 1 and 2.
with transportation company and advise Carrier immediately.
WATER SUPPLY/RETURN CONNECTIONS - Maximum
Step 2 - Protect Units from Damage allowable entering hot water temperature is 190°F. Install
To maintain warranty, protect unit against adverse weather, piping in accordance with all applicable codes. See Table 1.
theft or vandalism at jobsite. Position valves over the drain pan. Be sure valves are in
proper operating position and are easily accessible for
adjustment.
Step 3 - Prepare Jobsite for Unit Installation
To save time and reduce the possibility of costly errors, set
If valves cannot be installed over drain pan, insulate valves
up a complete sample installation in a typical room at jobsite.
to prevent sweating.
Check all critical dimensions such as pipe, wire and duct
connection requirements. Refer to job drawings and product
If coil and valve package connections are to be made with a
dimension drawings as required. Instruct all trades in their
solder joint, care should be taken to ensure that no
part of the installation
components in the valve package are subjected to a
Step 4 - Identify and Prepare Units temperature high enough to damage seals or other
1. Be sure unit power requirements match available power materials. Many 2- position electric control valves have a
source. Refer to unit nameplate and wiring diagram. manual operating lever. This lever should be in the OPEN
2. Units are designed for chilled water or hot water (190°F position during all soldering operations.
maximum) only. Unit may be equipped with optional
electric heater. Be sure that the required control If coil connection is made with a union, the coil side of the
packages for the unit have been supplied. union must be prevented from twisting (i.e., it should be
3. Check all tags on unit to determine if shipping screws “backed
backed up up”)) during tightening.
tightening Do NOT over-tighten!
over tighten!
are to be removed. Remove screws as directed. Over-tightening distorts the union seal surface and destroys
the union.
Step 5 - Place Unit in Position
1. Be sure unit is level or pitched towards drain to ensure Steam Connections - On units with steam-heating coils,
proper drainage and operation. (see Fig. 1 and 2.) Pitch the maximum steam pressure applied to the unit should
of suspended unit can change after coil is filled; recheck never exceed 10 psig.
after filling coil.
Unit weight distribution is not uniform at mounting points. Test And Insulate - When Wh allll joints
j i t are completed,
l t d
Suspend unit at factory-provided holes (Fig. 2). If used, perform hydrostatic test for leaks. Vent all coils at this time.
select and adjust vibration isolators so that unit is Check interior unit piping for signs of leakage from shipping
uniformly suspended and pitched. damage or mishandling. If leaks are found, notify a Carrier
2. Models, with bottom inlet, may be installed in representative before initiating any repair. Release trapped
noncombustible return air spaces only. air from system (see Step 9-6).
3. Protect units from damage caused by jobsite debris. Do
not allow foreign material to fall in unit drain pan.
Prevent dust and debris from being deposited on motor All water coils must be protected from freezing after
or fan wheels. initial filling with water. Even if system is drained, unit
coils may still have enough water to cause damage
when exposed to temperatures below freezing
42DF/DFD
42DF 42DE/DED
42DC/DCD
LEGEND:
1 - Coil
2 - Drain, 7/8” O.D.
3 - Hanger Mounting Holes diameter, 7/8”
4 - Junction Box (or power K.O.)
5 - Supply Air Duct Collar, 1”
Note: 6 - Coil Outlet
42DE & DF are supplied complete with the casing and 7 - Coil Inlet
the legend for internal parts are as per 42DC diagram. 8 - Access Panel
42DC/DCD 42DE/DED, DF/DFD Units with aquastats furnished and installed at the factory
Unit may be shipped with the aquastats mounted on a coil
Inlet Outlet Inlet Outlet
Size stubout. If so, remove the aquastat before installing a valve
(in. OD) (in. OD) (in. OD) (in. OD) package.
p g When re-installing
g the aquastats,
q , consult the
006 7/8 7/8 factory piping diagram in the submittals for proper location. If
008 7/8 7/8 the valve package is field supplied, the aquastat must be
installed in a location where it will sense the water
010 7/8 7/8
temperature regardless of the position of the control valve. A
012 7/8 7/8 bleed bypass may be required to ensure proper aquastat
7/8 7/8
014 1 1/8 1 1/8 operation.
016 1 1/8 1 1/8
All field wiring
g should be done in accordance with g governing
g
018 1 1/8 1 1/8 codes and ordinances. Any modification of unit wiring without
020 1 1/8 1 1/8 factory authorization will void all factory warranties and will
nullify any agency listings.
Following the hydrostatic test, insulate all piping, controls Step 8 - Make Duct Connections
and valves to unit to prevent sweating. Install all ductwork to and from unit in accordance with all
applicable codes. Duct construction must allow unit to
To ensure compliance with building codes, restore the operate without duct external static pressure limits as shown
structure’s original fire resistance rating by sealing all holes on job submittals. Units designed to operate with ductwork
with material carrying the same fire rating as the structure. may be damaged if operated without the intended ductwork
attached. Units configured to bring in outside air should have
Step 7 - Make Electrical Connections some method of low temperature protection to prevent coil
See unit serial plate for required supply voltage, fan and freeze-up.
heater amperage, and required circuit ampacities. See unit
wiring diagram for unit wiring and field wiring. Insulate all ductwork as required. Use flexible connections to
minimizee duct
duct-to-unit
to u t aalignment
g e t p problems
ob e s a and
d noise
o se
The fan motor(s) should never be controlled by any wiring or transmission where specified.
device other than the factory-supplied switch or thermostat/
switch combination unless factory authorization has been Install ductwork, accessory grills and plenums so that they
obtained. Fan motor(s) may be wired for temporary use do not restrict access to filter. (See Fig. 2 and Table 2.)
during construction only if: (1) prior factory approval has
been obtained, and (2) wiring and operation are done in strict
accordance with the instructions issued by the factory.
2
Prevent dust and debris from setting in unit. If wall finish or START-UP
color is to be spray applied, cover all openings to prevent Start-up procedures vary depending upon the time of year
spray from entering unit. (summer or winter) and building characteristics (new building
or old building, occupied or unoccupied, etc.).
Table 2 - Filter Data (One-in. thick)
Start up in the cooling mode requires that proper care be
Start-up
Unit Size L x H (inch) given to avoid condensation problems. Condensation forms
Size 42DC/DCD 42DE/DED 42DF/DFD on surfaces that are colder than the dew point of the
surrounding air. If a unit is started and is fed low-temperature
006 14 x 21 14 x 13 ¾
chilled water in a hot, humid setting, condensation will form
008 14 x 26 14 x 19 ¾ on many parts of the unit. In order to avoid excessive
010 14 x 30 14 x 23 ¾ condensation, water of a higher temperature should be used
-approximately 65-70°F. Also, the building should be as
012 14 x 35 14 x 27 ¾ completely
p y enclosed as p possible and outside air supply
pp y fans
014 14 x 40 14 x 33 ¾ and bathroom and kitchen exhaust fans should be off.
016 14 x 45 14 x 37 ¾
As the building temperature drops, the chilled water
018 14 x 50 14 x 43 ¾ temperature can gradually be reduced until it reaches 50°F.
020 14 x 54 14 x 47 ¾ At this point, the outside air fans can be turned on. When the
chilled water temperature is reduced to its design point the
Note: Filter sizes for models 42DC/DCD and DF/DFD are exhaust fans can be turned on.
factory supplied cleanable filters.
Clean Electric Heater -Lock open and tag heater and unit
di
disconnects.
t Check
Ch k that
th t airflow
i fl th
through
h heater
h t elements
l t is
i PERMANENT FILTER (Fiber Type)
unobstructed. Clean heater elements with soft brush or 1. Tap on solid surface to dislodge heavy particles.
vacuum cleaner as necessary. 2. Wash in hot water. If needed, use mild solution of
commercial solvent such as sal soda or trisodium
Clean or Replace Air Filters -Lock open and tag unit phosphate.
electrical disconnect. At the start of each cooling season and 3. Set filter on end so that water drains out through slots in
after each month of operation (more or less depending on frame. Allow filter to dry thoroughly.
operating conditions) replace throwaway filter or clean 4. Recharge filter with Film-Cor or similar recharging oil.
permanent filter. Three ounces is sufficient for medium-size
medium size filter.
filter Oil may
be applied by insect spray gun. For easier spraying, the
To remove filter, remove unit front panel and slip filter oil can be warmed. If filter is dipped in recharging oil,
forward out of filter rack. remove it immediately and allow to drain through slots in
frame.
5. Replace filter in unit. Replace unit front panel. If another
type of filter is used, follow filter manufacturer’s
instruction.
Carrier
International
Sdn. Bhd.
Malaysia
42D Rev-2
04 2012
Manufacturer reserves the right to discontinue,
or change at any time, specifications or designs
without notice and without incurring obligations.