Reference Conditions: 100m (100kPA) A.s.l., T 25°C, 30% H.R

This document summarizes the specifications of a 1250 kVA/1000 kWe prime power and 1375 kVA/1100 kWe limited-time running power generator set. It is powered by an 18 cylinder MTU 18V2000G26F diesel engine and includes a MECC ALTE ECO43-2L/4 alternator. The generator set meets various industry standards and directives and includes standard equipment such as starting batteries, exhaust silencers, and an automatic control panel.

Uploaded by

Rakib Hasan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
83 views5 pages

Reference Conditions: 100m (100kPA) A.s.l., T 25°C, 30% H.R

This document summarizes the specifications of a 1250 kVA/1000 kWe prime power and 1375 kVA/1100 kWe limited-time running power generator set. It is powered by an 18 cylinder MTU 18V2000G26F diesel engine and includes a MECC ALTE ECO43-2L/4 alternator. The generator set meets various industry standards and directives and includes standard equipment such as starting batteries, exhaust silencers, and an automatic control panel.

Uploaded by

Rakib Hasan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

GENSET MODEL GCW1375M

POWER RATING

kVA kWe
PRP - Prime Power 1250 1000
LTP - Limited-Time running Power 1375 1100

Reference conditions: 100m (100kPA) a.s.l., T 25°C, 30% H.R.

Ratings definitions (according to the standard ISO8528.1:2005)

PRP - Prime Power:


It is defined as being the maximum power which a generating set is capable of delivering continuously whilst
supplying a variable electrical load when operated for an unlimited number of hours per year under the
agreed operating conditions with the maintenance intervals and procedures being carried out as prescribed
by the manufacturer. The permissible average power output over 24 h of operation shall not exceed 70 % of
the prime power. .

LTP - Limited-Time running Power:


It is defined as the maximum power available, under the agreed operating conditions, for which the
generating set is capable of delivering for up to 500 h of operation per year (whose no more than 300 for
continuative use) with the maintenance intervals and procedures being carried out as prescribed by the
manufacturers.
No overload capability is available.

GENSET DATA

Nominal voltage: 400/230V Three phases.


Nominal frequency: 50 Hz.
Nominal speed: 1500 rpm
Power factor: 0,8.

The generating set will be manufactured in accordance with the following rules and directives:
- IEC 60034, IEC 60947, IEC 60255
- ISO 3046-1 & 2, ISO 8528
- 2006/42/EC, 2004/108/EC, 2006/95/EC.

STATIONARY RANGE
CUSTOMIZED SOLUTIONS
GENSET MODEL GCW1375M

DIESEL ENGINE FEATURES

General data
Manufacturer MTU
Model 18V2000G26F
Optimization Fuel consumption
N° cylinders / disposition 18 in “V” angle
Bore and Stroke 130 / 150 mm
Total displacement 35820 cc
Compression ratio 16 :1
Fuel injection Direct
Aspiration system Turbocharged
Cooling system Water

Operating data
Engine speed 1500 rpm
Net PRP Power 1049 kWm
Rating conditions: 25°C air inlet temperature, barometric pressure 100 kPa, relative humidity 30%
Fuel consumption at 75% PRP 189 g/kWh, 165 Liter/kWh
Fuel consumption at 100% PRP 189 g/kWh, 220 Liter/kWh

Engine equipment
Electric starter 24V DC / 9,5 kW
Set of dry-type air filters with contamination indicator
Fuel delivery pump
Fuel main filter
Fuel priming pump for initial system filling and venting
Closed fuel system
Lube oil circulation pump with safety valve
Lube oil multi-stage filter
Lube oil heat exchanger
Oil filter neck and oil dipstick for measurement on non-running engine
Electronic engine management system "ADEC"
Front-type radiator for jacket water and charge air cooling circuit with integrated expansion tank.

STATIONARY RANGE
CUSTOMIZED SOLUTIONS
GENSET MODEL GCW1375M

ALTERNATOR FEATURES

General data
Manufacturer MECC ALTE
Model ECO43-2L/4
Synchronous, self-regulated, self-excited, brushless,
Design
4 poles, 12 winding leads, pitch 2/3

Electrical characteristics

Stand-by power at 40°C 1358 kVA


Stand-by power at 27°C 1420 kVA
Nominal frequency 50Hz
Output voltage 400/230V
Power factor 0.8
Efficiency 96%
Voltage regulator DER1
Steady-state voltage deviation 1%
Short circuit current capacity >300%
Insulation class H

Mechanical characteristics
Degree of protection 23
Type of construction Single bearing
Air flow 90 m³/min
Standard CEI 2-3, EN 60034-1, IEC 34-1, VDE 0530, BS 4999-5000

Alternator equipment
Current transformer for parallel running

STATIONARY RANGE
CUSTOMIZED SOLUTIONS
GENSET MODEL GCW1375M

GENSET EQUIPMENT

• Lead acid starting batteries


• Fully bounded baseframe made of welded steel profiles, complete of anti-vibration mountings properly
sized.
• Industrial exhaust silencers made of carbon steel and designed for 15dB(A) noise reduction;
exhaust compensator and counter-flange included. Delivered loose.
• Manual oil draining pump
• Automatic modular synchronizing control panel for multiple genset in parallel. It allows the
following genset working operations:
Automatic mains failure start as single genset.
Multiple sets (up to 32 units) running in island-parallel (communication between genset trough
control cable) as production or emergency plant.
Complete with:
NTC
Comap InteliGen BaseBox control unit including devices for generator’s control, protection and
setting.
Intelivision 5 as color display unit
Main features:

o Display that shows measurements, alarms and settings.


Commands:
√ Genset START/STOP.
√ Manual open/close genset circuit breaker.
√ Manual open/close Mains circuit breaker.
√ Horn deactivation.
√ Fault reset.
√ Control unit programming.
Measurements:
√ Generator frequency.
√ Generator voltage.
√ Genset Act / React Power and P.F per phase.
√ Genset Active and Reactive Energy counter..
√ Mains frequency.
√ Mains voltage.
√ Synchronoscope
Protections and alarms:
√ Over/Under frequency
√ Over/Under voltage
√ Current/Voltage asymmetry
√ Overcurrent/Overload.
√ Oil pressure.
√ Engine temperature.
√ Fuel level.
√ Battery voltage.
√ Start failure.
LEDs for visual indication of:
√ Mains present.
√ Mains failure.
√ Genset voltage present.
√ Genset failure.
√ Genset Circuit breaker ON.
√ Mains circuit breaker ON.
√ Bus voltage present.
RS232/RS485 interfaces for remote control.
Audible horn alarm.

STATIONARY RANGE
CUSTOMIZED SOLUTIONS
GENSET MODEL GCW1375M

Automatic battery charger.


Moulded-case motor operated circuit breaker as protection for the generator against overloads
and short-circuits. Main features are:
o N° of poles: 4.
o Nominal current: 2000 A
o Type: fixed.
Emergency-Stop button.
Multi-pin connectors for CAN BUS control cable.
Robust metal frame casing. Mechanical degree of protection IP40. Built according to: EN 60439-1, EN
60204-1, CEI 64/8, CEE 73/23, EMC CEE 89/336, CEE 89/392. Gen-set Mounted.