ECE 5984: Power Distribution System Analysis
Lecture 1: Introduction to Power Distribution Systems
Reference: Textbook, Chapter 1
Instructor: V. Kekatos
1
The big picture
2
Distribution substations and feeders
• Switching
• Protection
• Voltage transformation
• Voltage regulation
• Metering
§ analog current recordings
§ meters on substation and/or feeder
§ digital meters record min/max/avg of
current, voltage, power, power factor
over 15 min, 30 min, or 1 hr
3
Switching and protective devices
• Switching devices
§ manual switches
§ remote controlled switches
• Protective devices
§ circuit breakers
§ fuses
§ overcurrent relays
§ reclosers
§ sectionalizers
Photo courtesy of K. Schneider (PNNL)
4
Switches
• Simple devices; no control/communication
• Located at substation or feeder
• Isolate equipment for maintenance at
substation, or reconfigure feeders
• Cannot interrupt fault currents and lack
synchronization equipment
• Manual control, or remote control via
SCADA signals Photo courtesy of K. Schneider (PNNL)
• Control equipment located at bottom of supporting structure or utility pole
5
Circuit breakers
• Similar to switches, but can break fault currents
• Used to protect rather than disconnect
• Located at substation due to size (rating)
• They can be operated remotely
• Classified based on material used to quench arc
(air, oil, vacuum, SF6)
Photo courtesy of K. Schneider (PNNL)
6
Detailed structure
• sub-transmission is optional
e.g., 115:4 kV [IEEE 123-bus]
138:69 kV
69:14 kV
Distribution substation
• Typical distribution feeders 15-200 MVA @ 2-46 kV
4 MVA @ 4 kV
12 MVA @ 12.47 kV
20 MVA @ 23 kV
30 MVA @ 34 kV
14:480/208 kV
• Inline transformers 14:4 kV
[Glover, Sarma, Overbye]
7
Breaker-and-a-half scheme
8
Voltage transformers
On-Load Tap-Changing (OLTC) transformer
§ a.k.a. Tap Changing Under-Load Transf. (TCUL)
§ located at the substation; can serve multiple feeders
§ maintains constant low-voltage side under varying
distribution load or transmission-side conditions
§ can be substituted with transformer & regulator
In-line transformer and regulators
Distribution transformers
9
Primary and secondary distribution
Distribution transformers (pole/pad-mounted) form the boundaries
Classes change: IEEE 1547 defines MV as 1-35 kV …
10
Distribution lines
three-phase four-wire multi-grounded Y
three-phase Delta (under replacement)
[Blume]
11
240/120 V single-phase distribution transformers
[Blume]
12
208/120 V three-phase distribution transformers
[Blume]
13
480/277 V three-phase distribution transformers
[Blume]
Small single-phase transformers provide 120 V from 480 V for lighting/office
14
Voltage regulation
• Voltage magnitude should lie within ±5% of nominal (114-126 for 120 V)
• Voltage regulators: induction devices in shunt or series with regulated circuit for the
control of its voltage
• Capacitors: power factor correction (include switching and protective elements)
15
Radial feeders
primary ‘main’ feeder:
2-30 MVA @ 2-46 kV
secondaries:
5-500 kVA @ 120-480 V
3, V, single-phase laterals
in-line transformers
distribution transformers
240/120 V 1-phase (split-phase)
208/120 V 3-phase
480/277/120 V 3-phase
400/230 V 3-phase (Europe)
regulators and cap banks
protection devices
16
Distribution feeder map
• Transformers (kVA rating, connection)
• Shunt capacitors (kVAR rating, phase)
• Voltage regulators (phase, ratios, compensator
settings)
• Lines (OH/UG, distance, conductor, phase)
• Switches (NO/NC)
• Geographical distances
• Conductors (radius, diameter, resistance)
See e.g., the actual IEEE 123-bus benchmark…
17
Fuses
• Low-cost devices used to interrupt fault currents
• Once fuse interrupts overcurrent, it has to be
manually replaced by a line crew
• Fuse coordination: the practice of selecting fuse sizes
so that fuse closest to the fault blows first
• Fuse coordination requires knowledge of system
load and gets complicated with distributed resources
Photo courtesy of K. Schneider
• Operate on an inverse time curve:
the higher the fault current, the quicker the fuse will blow
18
Example: fuse protection
• Permanent line to ground fault on line 705-712
• Fuse blows due to overcurrent, thus isolating single-
phase lateral
• Customers at node 712 and 742 call in to report power
outage
• Utility dispatches a line crew to investigate
• Line crew locates fault and repairs condition
• Line crew replaces blown fuse with a new one
• Single-phase lateral us back to service Photo courtesy of K. Schneider
19
Protection relays
• Use local measurements to generate control signals
• Fuses measure only current; relays measure
voltage and current so can also estimate
- real and reactive power
- sequence components
- phasor measurements
• They can be accessed remotely for maintenance
and updates
Photo courtesy of K. Schneider
20
Reclosers
• Designed to minimize number of
customers affected by momentary fault
• Not needed in transmission or underground
distribution systems
Operation
1. Fault occurs
2. Recloser interrupts fault current and remains
open for a time period (1-2 sec) to allow
Photo courtesy of K. Schneider
momentary faults to clear
3. Recloser closes back into fault and sees if fault
has cleared
4. If fault has cleared, recloser stays closed;
otherwise, recloser reopens
5. Number of tries to reconnect is user-configurable
(usually 3)
6. After final ‘shot’, recloser locks open
7. Utility crew must locally reset the unit
21
Sectionalizers
• Operate on local measurements and with
proper coordination of upstream reclosers
• Combination of reclosers and sectionalizers
is ideal for system with permanent and Recloser
temporary faults
Operation
1. Sectionalizer detects overcurrent but cannot
Sectionalizer #1
Sectionalizer #2
Sectionalizer #3
interrupt fault
2. It starts counting recloser shots
3. During the second/third recloser shots, the
sectionalizer opens under no load
Photo courtesy of K. Schneider
22
Example: sectionalizer protection
• Permanent line to ground fault on line 710-735
• Overcurrent causes recloser 730-709 to open
• Sect. 708-733 detects overcurrent and prepares to open
• Sect.738-711 does not detect overcurrent
• Recloser waits and closes back in; repeats 2-3 times
• Sect. 708-733 opens after 2nd or 3rd shot during no load
• Recloser closes back in, sees no fault, and remains closed
• Customers downstream of 708 report power outage and
utility dispatches line crew
• Line crew locates fault; repairs condition; and recloses sect.
Photo courtesy of K. Schneider
• Lateral back to service
23