Clarifier Tank Structural PDF

This document is a construction plan for a clarifier tank. It includes notes on general construction details, concrete specifications requiring a minimum compressive strength of 2500-3000 psi depending on the element, and reinforcement bar requirements. Reinforcement bars smaller than 20mm diameter must meet ASTM A615 Grade 40 specifications, while bars 25mm and larger must be Grade 60. The head of the structural section and building official have approved the plan.

Uploaded by

Benderlip Cortez
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
917 views3 pages

Clarifier Tank Structural PDF

This document is a construction plan for a clarifier tank. It includes notes on general construction details, concrete specifications requiring a minimum compressive strength of 2500-3000 psi depending on the element, and reinforcement bar requirements. Reinforcement bars smaller than 20mm diameter must meet ASTM A615 Grade 40 specifications, while bars 25mm and larger must be Grade 60. The head of the structural section and building official have approved the plan.

Uploaded by

Benderlip Cortez
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

REPUBLIC OF THE PHILIPPINES

OFFICE OF THE BUILDING OFFICIAL


MUNICIPALITY IN THE PROVINCE OF LEYTE
16.00
0.80

14.40 0.80

CONSTRUCTION NOTES: b RECOMMENDING APPROVAL:

APPROVED BY:

A. GENERAL
1. CONSTRUCTION NOTES AND TYPICAL DETAILS APPLY TO ALL DRAWINGS UNLESS HEAD STRUCTURAL SEC. DATE
OTHERWISE SHOWN OR NOTED, MODIFY TYPICAL DETAILS AS DIRECTED TO MEET SPECIAL

3.50
CONDITIONS.
BLDG. OFFICIAL DATE
2. SHOP DRAWINGS WITH ERECTION & PLACING DIAGRAMS OF ALL STRUCTURAL STEEL,
MISCELLANEOUS IRON, PRE-CAST CONCRETE ETC. SHALL BE SUBMITTED FOR ENGINEER'S
APPROVAL BEFORE FABRICATION.

5.30
3. CONTRACTOR SHALL VERIFY ALL DIMENSIONS BEFORE ALL WORK IS TO BEGIN, CHECK
WITH MECHANICAL OR ELECTRICAL CONTRACTORS FOR CONDUITS, PIPE SLEEVES, ETC, TO
BE EMBEDDED IN CONCRETE.
SHORING & BRACINGS OF THE STRUCTURE FOR ALL LOADS THAT MAYBE IMPOSED DURING

12.20

10.60

12.20
5.20
CONSTRACTION.

B. CONCRTE AND REINFORCEMENT


1. ALL MATERIALS & WORKMANSHIP SHALL CONFIRM WITH THE LATEST BUILDING CODE OF
AMERICAN CONCRETE INSTITUTE (ACI - 318)

5.30
2. ALL CONCRETE SHALL DEVELOP A MINIMUM COMPRESSIVE STRENGTH AT THE END OF
TWENTY EIGHT (28) DAYS WITH CORRESPONDING MAXIMUM SIZE AGGREGATE AND SLUMP
AS FOLLOWS: a a

3.50
LOCATION 28 DAYS STRENGTH MAX. SIZE AGGREGATE MAX SLUMP
CURBS & SLAB 2500 PSI 1 IN. (25MM) 4 IN. (100MM)
ON GRADE
EXCEPT FOUND.

FOUNDATION AND b
3000 PSI 3 4 IN. (100MM)
RETAINING WALL 4 IN. (19MM)

ALL OTHERS
INCLUDING BEAMS, 3000 PSI 3
IN. (19MM) 4 IN. (100MM)
4 CLARIFIER TANK
SUSPENDED SLABS &
COLUMNS
L A Y O U T
S C A L E 1 : 1 0 0 M T S

3. ALL REINFORCING BARS SHALL CONFORM TO ASTM A615 GRADE 40 FOR DIA.20MM &
SMALLER BARS & GRADE 60 FOR DAI. 25MM & LARGER BARS. COLUMN HOOPS ARE ALL
GRADE 40 BARS.
12.20
4. IN GENERAL, THE LATEST EDITION OF ACI - 315, MANUAL OF STANDARD PRACTICE 16.00

DETAILING REINFORCED CONCRETE STRUCTURES SHALL BE ADHERED TO UNLESS 1.00 0.80 0.70 5.80 5.70 1.20 0.80 1.00 5.00 5.00 1.00
OTHERWISE SHOWN OR NOTED. 0.25 0.25 0.25
5. MAINTAIN MINIMUM CONCRTE COVER FOR REINFORCING STEEL AS FOLLOWS: 0.80

SUSPENDED SLABS......................................................3/4 IN. (19MM.)


SEE DETAIL A
SLAB ON GRADE.........................................................1 1/2 IN. (38MM.)
WALLS ABOVE GRADE.....................................................1 IN. (25MM.)
BEAM STIRRUPS AND COLUMN TIES.......................1 1/2 IN. (38MM.)
WHERE CONCRETE IS EXPOSED

0.75
TO EARTH BUT POURED AGAINST FORMS...................2 IN. (50MM.)

2.20
2.50
WHERE CONCRETE IS DEPOSITED 2.00
3.20

DIRECTLY AGAINST EARTH.............................................2 IN. (50MM.)


4.20

4.50

4.50
6. SPLICES SHALL BE SECURELY WIRED TOGETHER & SHALL LAP OR EXTEND IN

1.00
ACCORDANCE WITH TABLE 1 (TABLE OF LAP SLICE & ANCHORAGE LENGTH) UNLESS

1.50
OTHERWISE SHOWN ON DRAWINGS, SPLICES SHALL BE STAGGERED WHENEVER POSSIBLE.
1.00

0.50

1.30
D. FOUNDATION
1. FOUNDATION IS DESIGNED FOR ASSUMED ALLOWABLE SOIL BEARING CAPACITY OF :
BU - 5,000 PSI; BA - 2,000 PSI CLARIFIER TANK

2. FOUNDATION SHALL REST ON NATURAL SOIL. UNLESS OTHERWISE NOTED BY THE CLARIFIER TANK
SECTION AT B
S C A L E 1 : 1 0 0 M T S
ENGINEER, NO PART OF THE FOUNDATION SHALL REST ON FILL. SECTION AT A
S C A L E 1 : 1 0 0 M T S
3.THE CONTRACTOR SHALL NOTIFY THE ENGINEER AFTER FOOTING EXCAVATION HAVE
BEEN COMPLETED & PRIOR TO CONCRETING TO CONFIRM THE DESIGN SOIL BEARING
CAPACITY.

CLARIFIER TANK (CONCRETE)

SEAL PROJECT TITLE: APPROVED AS TO PLAN AND SPECS: SHEET CONTENT: SHEET NUMBER:

CONSTRUCTION NOTES

PRC NO : VALIDITY : WATER TREATMENT PLANT METRO CARIGARA WATER DISTRICT


LAYOUT

SECTION AT A S
PTR NO : DATE :
OWNER SECTION AT B
01 03
PLACE : LOCATION: CARIGARA, LEYTE LOCATION: CARIGARA, LEYTE
REPUBLIC OF THE PHILIPPINES

OFFICE OF THE BUILDING OFFICIAL


MUNICIPALITY IN THE PROVINCE OF LEYTE

RECOMMENDING APPROVAL:

APPROVED BY:

HEAD STRUCTURAL SEC. DATE

BLDG. OFFICIAL DATE

16.00

0.80 14.40 0.80

SLAB ON GRADE
16mmØ- G40 TOP BAR SPACED AT 16.00
200mm ON CENTER BOTHWAYS 0.80

20mmØ - G40 BOTTOM BAR SPACED AT 14.40 0.80


200mm ON CENTER BOTHWAYS 0.20
1.60 5.80 6.60

B1 B1

3.50
3.50

C1F1 C1F1 C1F1 C1F1 C1F1

5.30
5.20
5.30
B1 B1 B1 B1 B1

B1 B1

12.20

10.60

12.20
5.20
12.20

10.60

12.20
5.20

C1F1 C1F1 C1F1 C1F1 C1F1

5.20

5.30
B1 B1 B1 B1 B1

5.30
1
0
L

3.50
L
3.50

A
W

B1 B1

C1F1 C1F1 C1F1 C1F1 C1F1

CLARIFIER TANK
CLARIFIER TANK
FOUNDATION PLAN BEAM FRMG. PLAN
S C A L E 1 : 1 0 0 M T S
S C A L E 1 : 1 0 0 M T S

CLARIFIER TANK (CONCRETE)

SEAL PROJECT TITLE: APPROVED AS TO PLAN AND SPECS: SHEET CONTENT: SHEET NUMBER:

FOUNDATION PLAN

PRC NO : VALIDITY : WATER TREATMENT PLANT METRO CARIGARA WATER DISTRICT


BEAM FRAMING PLAN
S
PTR NO : DATE :
OWNER
02 03
PLACE : LOCATION: CARIGARA, LEYTE LOCATION: CARIGARA, LEYTE
REPUBLIC OF THE PHILIPPINES

OFFICE OF THE BUILDING OFFICIAL


1.30 MUNICIPALITY IN THE PROVINCE OF LEYTE

L/4 L/2 L/4


RECOMMENDING APPROVAL:
EXTRA TOP BAR @ SUPPORTS
APPROVED BY:

0.25
1.30
HEAD STRUCTURAL SEC. DATE

BLDG. OFFICIAL DATE


EXTRA BOTTOM BAR @ MIDSPAN
0.40
L/5 3L/5 L/5

LATERAL TIES
TYPICAL BEAM DETAIL
5- 10mm Ø AT 0.05M ON CENTER 1.00
5- 10mm Ø AT 0.10M ON CENTER
REST AT 0.15M ON CENTER
BEAM DESIGN 0.70 0.30

0.20

SUPPORT MIDSPAN
BEAM NO. REINFORCEMENTS REINFORCEMENTS NUMBER OF TIES

COLUMN REBARS B1 12 - 20MMØ 2 - 20MMØ USE 10MM Ø STIRRUPS SPACED 1 @ 0.025M., 5 @ 0.05M.,
8 - 20mm Ø REBARS
2 - 20MMØ 12 - 20MMØ 5 @ 0.10M., REST AT 0.15M., ON CENTER
0.3 X 0.50

0.50
TOP BAR
10mm Ø REBAR SPACED
AT 200mm ON CENTER

NGL BOTTOM BAR


16mm Ø REBAR SPACED
AT 200mm ON CENTER

HEIGHT IN METERS
0.90

0.20
1.20

HORIZONTAL BAR
0.30

16mmØ - G40 REBAR SPACED


AT 200mm ON CENTER

G R A V E L B E D D I N G
VERTICAL BAR
20mmØ - G40 REBAR SPACED
AT 200mm ON CENTER

1.00
0.20 5mm THICK GRAVEL BED
0.70 0.30
CLARIFIER TANK (CONCRETE)

COLUMN-FOOTING DETAIL
S C A L E 1 : 3 0 M T S HORIZONTAL BAR

0.25
16mmØ - G40 REBAR SPACED

0.10
AT 200mm ON CENTER

VERTICAL BAR
20mmØ - G40 REBAR SPACED
AT 200mm ON CENTER

0.50
TOP BARS

COLUMN DESIGN 16mmØ - G40 REBAR SPACED AT


200mm ON CENTER BOTHWAYS

SLAB ON FILL
TOP BAR
10mm Ø REBAR SPACED
AT 200mm ON CENTER
BOTTOM BARS
COLUMN NO. NUMBER OF TIES 20mmØ - G40 REBAR SPACED AT
MAIN BARS 20mm ON CENTER BOTH WAYS

BOTTOM BAR
C1 8 - 20MMØ
USE 10MM Ø TIES (2 SETS) SPACED 5 @ 0.05M., 16mm Ø REBAR SPACED
VERTICAL BAR
WALL 01
5 @ 0.10M., REST AT 0.15M., ON CENTER AT 200mm ON CENTER S C A L E 1 : 2 0 M T S

20mm Ø - G40 REBAR SPACED AT

0.25
0.25 X 0.40 20mm ON CENTER, BOTHWAYS

HORIZONTAL BAR

COLUMN FOOTING DESIGN GRAVEL BED


16mm Ø - G40 REBAR SPACED AT
20mm ON CENTER, BOTHWAYS
CLARIFIER TANK (CONCRETE)
MIDSPAN
BEAM NO. REINFORCEMENTS NUMBER OF TIES DETAIL B
S C A L E 1 : 1 5 M T S

SHORT DIRECTION : USE 6 - 20MMØ BARS LENGTH OF SLAB


F1C1 1.30M X 1.30M X 0.30M
LONG DIRECTION : USE 6 - 20MMØ BARS
CLARIFIER TANK (CONCRETE)

DETAIL A
S C A L E 1 : 1 5 M T S

TOP BARS
16mmØ - G40 REBAR SPACED AT
200mm ON CENTER BOTHWAYS

NOTE:
SLAB :
PROVIDE SPACER EVERY 1.00

0.25
MTRS; BOTHWAYS

WALLS:
GRAVEL BED PROVIDE HOOK EVERY 1.00
METERS; BOTHWAYS
BOTTOM BARS
20mmØ - G40 REBAR SPACED AT
200mm ON CENTER BOTHWAYS

CLARIFIER TANK (CONCRETE) CLARIFIER TANK (CONCRETE)

SLAB DETAIL
S C A L E 1 : 1 5 M T S

SEAL PROJECT TITLE: APPROVED AS TO PLAN AND SPECS: SHEET CONTENT: SHEET NUMBER:

COLUMN DETAILS WALL DETAIL

PRC NO : VALIDITY : WATER TREATMENT PLANT METRO CARIGARA WATER DISTRICT


FOOTING DETAILS

BEAM DETAILS S
PTR NO : DATE :
OWNER DETAIL AT A

DETAIL AT B
03 03
PLACE : LOCATION: CARIGARA, LEYTE LOCATION: CARIGARA, LEYTE
SLAB DETAIL