0% found this document useful (0 votes)
542 views6 pages

Nader NDB6AZ 63H Products Specification

1. The document provides the product specification for the NDB6AZ-63H molded case circuit breaker. It describes the product name, type, date, and intended applications. 2. The main technical parameters of the circuit breaker are outlined, including the model, rated voltage and current, wiring area, and time-current curves. 3. Installation dimensions, method, and packaging are specified. The document also lists notices for safe use and an accessory derating ratio table.

Uploaded by

Mesfin Mamo
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
542 views6 pages

Nader NDB6AZ 63H Products Specification

1. The document provides the product specification for the NDB6AZ-63H molded case circuit breaker. It describes the product name, type, date, and intended applications. 2. The main technical parameters of the circuit breaker are outlined, including the model, rated voltage and current, wiring area, and time-current curves. 3. Installation dimensions, method, and packaging are specified. The document also lists notices for safe use and an accessory derating ratio table.

Uploaded by

Mesfin Mamo
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

File No.

:NDT2930580 Version:0

Product Specification of NDB6AZ-63H


(IPD-ENG-DEV-T22 A1 2016-09-23)

Product Name: Moulded Case Circuit Breaker


Product type: NDB6AZ-63H
Date: 20190825

Prepared Yang Yanqun Date 2019-8-25

Reviewed Zhang Yang Date 2019-8-26

Approved Yang Hairong Date 2019-8-27

https://www.nader-circuit-breaker.com Page 1 of 6
File No.:NDT2930580 Version:0

Revision information

Version Revised contents and reasons Date Prepared Reviewed Approved


Yang Yang
0 Initial release 20190827 Zhang Yang
Yanqun Hairong

Page 2 of 6
File No.:NDT2930580 Version:0

1、Application
 Short -circuit protection
 Over-load protection
 Isolation
NDB6AZ-63H series products are mainly used in telecommunications equipment rooms or communication
cabinets,as isolation,short circuit and overload protection for cabinets,equipment rooms or downstream
subscriber lines.

2、Product Pictures

NDB6AZ-63H breaker

3、Model and implication

ND B 6A Z - 63 H / 50 B / 1PN

Bre- Design DC Shelf black Rated current Battery:B Number of poles


Low aker number rank 6,10,16,20,25, Load:none N pole straight through
voltage 63A 32,40,50,63
electrical
appliance

Page 3 of 6
File No.:NDT2930580 Version:0

4、Main technical parameters


Specific parameter
Parameter name Specific parameter description Parameter name
description

Model NDB6AZ-63H Rated voltage(V) DC80,AC230/240

Rated limit breaking 10(DC80V),6(6-16A,AC230/240V),


Electrical endurance(times) 4000
capacity(kA) 4.5(20-63A,AC230/240V)

Bare wire:0.75~16

ferrule with plastic sleeve:0.75~10

ferrule without plastic sleeve:16


the schematic diagram of the ferrule’s
cross-sectional area is as follows:

Wiring area(mm2) Mechanical life(times) 6000

cross-sectional area of ferrule:

1.3 mm≤L≤6mm, 1.3 mm≤W≤6mm.

insulation sleeve or heat shrinkable tube diameter

≤9.5mm when ferrul is inserted into 25mm depth.

0.75~6mm²:12~18
Plug depth(mm) 23~25 Stripping length(mm) 10mm²:14~18
16mm²:18±1
Insertion frame force
≤80 Pull out frame force (N) ≤75
(N)
0.75~6mm²:10~16
circuit breaker insertion
200 cold pressed end Length (mm) 10mm²:12~16
and removal times
16mm²:16±1

5、Working conditions
● Height :≤2000m,provoid derating parameters at more than 2000 meters(derating ratio table see

attachment)
● ambient temperature:-40℃~+70℃

● Can withstand the effects of humid air(Temperature @+40℃ and above,air relative humidity does not
exceed 50%,allows greater relative humidity at lower temperatures,for example,95% @+20℃)
● Can withstand salt spray for 48 hours
● In a medium without explosion hazard,and the medium does not have enough gas and conductive dust to
corrode metal and destroy insulation

Page 4 of 6
File No.:NDT2930580 Version:0

● In places where there is no rain or snow


6、Time-Current curves
● Direct-current
○ Protect conventional and distribution cables
○ Specify ampere rating:6A、10A、16A、20A、25A、32A、40A、50A、63A
○Tripping characteristics:instantaneous trip range 11In(1±20%)

DC Ii=11In(1±20%)

7、Outline and installation dimensions

NDB6AZ-63H Outline and installation dimensions

8、Installation method
Plug-in type, the thickness of the rear-end plug in copper row is 2±0.1mm,signal port copper row thickness

Page 5 of 6
File No.:NDT2930580 Version:0

is 1±0.1mm.

Signal terminal wiring schematic diagram:

9、Packaging and storage


Maximum number of packages:8/box,packed in boxes:24 boxes/box,it should stored in a warehouse where
air circulation and relative humidity is not more than 80%,temperature is not lower than -40℃ but not higer than
80℃.Store in the warehouse without acid,alkaline or other corrosive gases in the surrounding air.
Under the above conditions,the storage period shall not exceed 1 year from the date of manufacture.
10、Environment
Product design meets ROHS requirements.
11、Accessory list and installation
Annex1:derating ratio table of Moulded Case Circuit Breaker with altitude greater than 2000m.

12、Notices
1、Take responsibility for yourself if product quality problems caused by unpacking products privately;
2、Do not touch the exposed part of the non-insulated part of the circuit breaker when the work is energized;
3、Please do not arbitrarily debug the characteristics of the circuit breaker.The manufacturer will not be
responsible for the product quality problems caused by this;
4、The wiring should be reliable to prevent the breaker from circuit breaker malfunction and terminal burned
caused by abnormal heat at the terminals.

Page 6 of 6