File No.
:NDT2930580 Version:0
Product Specification of NDB6AZ-63H
(IPD-ENG-DEV-T22 A1 2016-09-23)
Product Name: Moulded Case Circuit Breaker
Product type: NDB6AZ-63H
Date: 20190825
Prepared Yang Yanqun Date 2019-8-25
Reviewed Zhang Yang Date 2019-8-26
Approved Yang Hairong Date 2019-8-27
https://www.nader-circuit-breaker.com Page 1 of 6
File No.:NDT2930580 Version:0
Revision information
Version Revised contents and reasons Date Prepared Reviewed Approved
Yang Yang
0 Initial release 20190827 Zhang Yang
Yanqun Hairong
Page 2 of 6
File No.:NDT2930580 Version:0
1、Application
Short -circuit protection
Over-load protection
Isolation
NDB6AZ-63H series products are mainly used in telecommunications equipment rooms or communication
cabinets,as isolation,short circuit and overload protection for cabinets,equipment rooms or downstream
subscriber lines.
2、Product Pictures
NDB6AZ-63H breaker
3、Model and implication
ND B 6A Z - 63 H / 50 B / 1PN
Bre- Design DC Shelf black Rated current Battery:B Number of poles
Low aker number rank 6,10,16,20,25, Load:none N pole straight through
voltage 63A 32,40,50,63
electrical
appliance
Page 3 of 6
File No.:NDT2930580 Version:0
4、Main technical parameters
Specific parameter
Parameter name Specific parameter description Parameter name
description
Model NDB6AZ-63H Rated voltage(V) DC80,AC230/240
Rated limit breaking 10(DC80V),6(6-16A,AC230/240V),
Electrical endurance(times) 4000
capacity(kA) 4.5(20-63A,AC230/240V)
Bare wire:0.75~16
ferrule with plastic sleeve:0.75~10
ferrule without plastic sleeve:16
the schematic diagram of the ferrule’s
cross-sectional area is as follows:
Wiring area(mm2) Mechanical life(times) 6000
cross-sectional area of ferrule:
1.3 mm≤L≤6mm, 1.3 mm≤W≤6mm.
insulation sleeve or heat shrinkable tube diameter
≤9.5mm when ferrul is inserted into 25mm depth.
0.75~6mm²:12~18
Plug depth(mm) 23~25 Stripping length(mm) 10mm²:14~18
16mm²:18±1
Insertion frame force
≤80 Pull out frame force (N) ≤75
(N)
0.75~6mm²:10~16
circuit breaker insertion
200 cold pressed end Length (mm) 10mm²:12~16
and removal times
16mm²:16±1
5、Working conditions
● Height :≤2000m,provoid derating parameters at more than 2000 meters(derating ratio table see
attachment)
● ambient temperature:-40℃~+70℃
● Can withstand the effects of humid air(Temperature @+40℃ and above,air relative humidity does not
exceed 50%,allows greater relative humidity at lower temperatures,for example,95% @+20℃)
● Can withstand salt spray for 48 hours
● In a medium without explosion hazard,and the medium does not have enough gas and conductive dust to
corrode metal and destroy insulation
Page 4 of 6
File No.:NDT2930580 Version:0
● In places where there is no rain or snow
6、Time-Current curves
● Direct-current
○ Protect conventional and distribution cables
○ Specify ampere rating:6A、10A、16A、20A、25A、32A、40A、50A、63A
○Tripping characteristics:instantaneous trip range 11In(1±20%)
DC Ii=11In(1±20%)
7、Outline and installation dimensions
NDB6AZ-63H Outline and installation dimensions
8、Installation method
Plug-in type, the thickness of the rear-end plug in copper row is 2±0.1mm,signal port copper row thickness
Page 5 of 6
File No.:NDT2930580 Version:0
is 1±0.1mm.
Signal terminal wiring schematic diagram:
9、Packaging and storage
Maximum number of packages:8/box,packed in boxes:24 boxes/box,it should stored in a warehouse where
air circulation and relative humidity is not more than 80%,temperature is not lower than -40℃ but not higer than
80℃.Store in the warehouse without acid,alkaline or other corrosive gases in the surrounding air.
Under the above conditions,the storage period shall not exceed 1 year from the date of manufacture.
10、Environment
Product design meets ROHS requirements.
11、Accessory list and installation
Annex1:derating ratio table of Moulded Case Circuit Breaker with altitude greater than 2000m.
12、Notices
1、Take responsibility for yourself if product quality problems caused by unpacking products privately;
2、Do not touch the exposed part of the non-insulated part of the circuit breaker when the work is energized;
3、Please do not arbitrarily debug the characteristics of the circuit breaker.The manufacturer will not be
responsible for the product quality problems caused by this;
4、The wiring should be reliable to prevent the breaker from circuit breaker malfunction and terminal burned
caused by abnormal heat at the terminals.
Page 6 of 6