Drawing1 Layout1

The document outlines the electrical layout plans for a building, including details on panel boards, circuit homeruns, load specifications, and conductor sizes. It includes general notes on compliance with the Philippines Electrical Code, grounding requirements, and installation standards. The layout features various outlets, switches, and lighting arrangements across different floors, with a total load of 11,980 watts and 54.453 amps.

Uploaded by

Benmark Jabay
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
60 views1 page

Drawing1 Layout1

The document outlines the electrical layout plans for a building, including details on panel boards, circuit homeruns, load specifications, and conductor sizes. It includes general notes on compliance with the Philippines Electrical Code, grounding requirements, and installation standards. The layout features various outlets, switches, and lighting arrangements across different floors, with a total load of 11,980 watts and 54.453 amps.

Uploaded by

Benmark Jabay
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

ELECTRICAL

LEGEND:

PANEL BOARD

CIRCUIT HOMERUN NO. OF LOAD NO. OF


NO. OF
SWITCHES VOLTS WATTS AMPERE SIZES OF CONDUCTOR SIZES OF CONDUITS ACB
CIRCUITS DESCRIPTION OUTLETS
S1 S2 S3
FUSE GENERAL NOTES:
LIGHTING OUTLET LINE
C1 220 1080 watts 2-3.5 mm2 ø TW COPPER WIRE 13.00 mm ø PVC PIPE
POWER OUTLET 6 240 volts 4. 909 amp 25 amp
SWITCH LINE 220
volts 2-3.5 mm2 ø TW COPPER WIRE
1. ALL ELECTRICAL WORKS AND INSTALLATIONS HEREIN SHALL CONFORM WITH THE LATEST
C2 POWER OUTLET 6 240 1080 watts 4. 909 amp 13.00 mm ø PVC PIPE 25 amp
APPROVED EDITION OF THE PHILIPPINES ELECTRICAL CODE, RULES AND REGULATIONS OF THE
10w 10w 10w
CONVENIENCE OUTLET LINE C3 POWER OUTLET 6 220
240 volts 1080 watts 4. 909 amp 2-3.5 mm2 ø TW COPPER WIRE 13.00 mm ø PVC PIPE 25 amp LOCAL AND NATIONAL AUTHORITIES CONCERNED IN THE ENFORCEMENT OF ELECTRICAL LAWS
S1 S1 ONE GANG SWITCH C4 POWER OUTLET 6
220
240 volts 1080 watts 4. 909 amp 2-3.5 mm2 ø TW COPPER WIRE 13.00 mm ø PVC PIPE 25 amp AND ORDINANCES.
20w
10w 10w 10w 10w
10w 10w S1 10w 220 4. 909 amp 13.00 mm ø PVC PIPE
2. ADEQUATE AND EFFECTIVE GROUNDING SHALL BE PROVIDED TO ALL METALLIC CONDUITS,
10w C5 POWER OUTLET 6 volts 1080 watts 2-3.5 mm2 ø TW COPPER WIRE 25 amp
S1
10w
S1 20w S2 TWO GANG SWITCH 240
CABINETS, ENCLOSURES AND EQUIPMENT BY MEANS OF COPPER CLAD GROUNDING RODS.
20w 20w 220 13.00 mm ø PVC PIPE 10 amp
20w 20w 20w
C6 LIGHTING OUTLET 12 2 2 0 240 volts 190 watts 0. 864 amp 2-2.0 mm2 ø TW COPPER WIRE 3. NO BRANCH CIRCUIT SHALL HAVE A LOAD OF MORE THAN 80% OF ITS RATING.
20w S1
10w 10w 10w 10w 10w 10w S3 THREE GANG SWITCH 220 4. ELECTRICAL SERVICE REQUIREMENTS SHALL BE 220 VOLTS, 3- PHASE AND 60 HERTZ.
C7 LIGHTING OUTLET 11 5 1 0 240 volts 160 watts 0.727 amp 2-2.0 mm2 ø TW COPPER WIRE 13.00 mm ø PVC PIPE 10 amp
10w
10w
20w
S2
S2 S2
10w CONVENIENCE OUTLET 220
5. ALL SINGLE PHASE LOADS SHALL BE SO CONNECTED TO EFFECT A BALANCED THREE PHASE
10w 10w C8 LIGHTING OUTLET 15 2 3 0 volts 200 watts 0. 909 amp 2-2.0 mm2 ø TW COPPER WIRE 13.00 mm ø PVC PIPE 20 amp
10w 10w 10w
240
SYSTEM.
10w S1 S2
SPECIAL PURPOSE OUTLET FOR ACU C9 LIGHTING OUTLET 8 1 0 0
220
240 volts 80 watts 0. 364 amp 2-2.0 mm2 ø TW COPPER WIRE 13.00 mm ø PVC PIPE 10 amp 6. ALL MATERIALS TO BE USED SHALL BE NEW AND APPROVED TYPE FOR BOTH PURPOSE AND
S2 10w S1
10w
S1
10w 10w
S1
ACU AIR CONDITIONING UNIT C10 LIGHTING OUTLET 16 3 2 0
220
240 volts 200 watts
0. 909 amp 2-2.0 mm2 ø TW COPPER WIRE 13.00 mm ø PVC PIPE 20 amp LOCATION INTENDED. ALL WIRES INSULATED FOR 600 VOLTS, TYPE THW OR TW AND SHALLBE
10w 10w
S2 40w C10 INSIDE RIGID UPVC PIPES FOR EMBEDDED PIPE. EMT/IMC FOR EXPOSE PIPES.
C7 C11 ACU OUTLET 1
220
volts 1150 watts 5. 227 amp 2-5.0 mm2 ø TW COPPER WIRE 13.00 mm ø PVC PIPE 30 amp
40w 20w
C8
20w 10w CFL PIN LIGHT 240
7. CIRCUIT BREAKER PANELBOARD SHALL STANDARD FACTORY PRODUCTS. ALL CIRCUIT
C6 20w C12 ACU OUTLET 1
220
240 volts 1150 watts 5. 227 amp 2-5.0 mm2 ø TW COPPER WIRE 13.00 mm ø PVC PIPE 30 amp BREAKERS SHALL BE BOLT- ON TYPE.
40w S1
10w 10w S1 S1 C9 10w 10w 20w CFL
10w 10w 10w 10w C13 ACU OUTLET 1 220
240 volts 1150 watts 5. 227 amp 2-5.0 mm2 ø TW COPPER WIRE 13.00 mm ø PVC PIPE 30 amp 8. WORKMANSHIP SHALL BE EQUAL TO THE BEST STANDARD PRACTICE RECOGNIZED AND
S2 S1 S1 ADOPTED FOR THIS TRADE.
CHANDELIER C14 ACU OUTLET 1 220
240 volts 1150 watts 5. 227 amp 2-5.0 mm2 ø TW COPPER WIRE 13.00 mm ø PVC PIPE 30 amp
9. ALL ELECTRICAL WORKS AND INSTALLATIONS HERE IN SHALL BE DONE UNDER THE DIRECT
10w 10w
C15 ACU OUTLET 1 220
240 volts 1150 watts 5. 227 amp 2-5.0 mm2 ø TW COPPER WIRE 13.00 mm ø PVC PIPE 30 amp SUPERVISION OF A DULY LICENSED ELECTRICAL ENGINEER OR HIS REPRESENTATIVE.
10w 10w Ref REFRIGERATOR OUTLET
C16 SPARE
GROUND
C17 SPARE
M

E SECOND FLOOR LIGHTING LAYOUT PLAN KILOWATTHOUR METER C18 SPARE


E GROUND FLOOR LIGHTING LAYOUT PLAN SCALE: 1:100 MT
SCALE: 1:100 MT
PEDESTAL POST TOTAL 97 13 8 0 11, 980 watts 54. 453 amp 2-8.0 mm2 ø TW COPPER WIRE 25.00 mm ø PVC TYPE 60 amp

SERVICE ENTRANCE DROP WIRE

20w CFL (ROUND)


E SCHEDULE OF LOADS
NOT TO SCALE

Toilet
Room Toilet
Room
Service Area
Girls Masters
Bedroom Shower Bedroom
Guest Room Room Bathtub
Kitchen Area
T&B
Room Bathtub

Ref Stairs

Stairs

Family Hall C5
C14
C4 Girls
Boys C13
C11 C15 Bedroom
Living Area Bedroom
Dining Area
C2 Carport
C12
C3

C1

Balcony

Balcony

SERVICE ENTRANCE
CAP

C9
C10 C8

CONCRETE
E GROUND FLOOR POWER LAYOUT PLAN E SECOND FLOOR POWER LAYOUT PLAN PEDESTAL POST
C3 C5 C13 C15 C14 C12 C4
SCALE: 1:100 MT SCALE: 1:100 MT

KILOWATT- HOUR
M C7 C6
METER
POWER PANEL BOARD

C1 C11 S S S C2

GROUND

NO. 8.0 PVC TW COPPER WIRE

UNDERGROUND 1' ø PVC CONDUIT TYPE


KILOWATT- HOUR METER

SURNECO M
E RISER DIAGRAM M
CONCRETE PEDESTAL POST
SCALE: 1:100 MT

18- SLOT ELECT'L


60 amp

PANEL BOARD
ROAD
ACB

KILOWATT- HOUR METER


SERVICE ENTRANCE DROP WIRE 25 amp 25 amp
SERVICE ENTRANCE CAP
PEDESTAL POST C1
25 amp C2
25 amp
SURNECO LINE POST
C3
10 amp C4
I = V/R
25 amp

C6
C5
10 amp 20 amp
C1+C2+C3+C4+C5....................+C15 E SERVICE ENTRANCE ELECTRICAL LAYOUT PLAN
C8
C7
10 amp 20 amp
SCALE: 1:100 MT

C9
30 amp 30 amp C10
=11,980 watts
C12
C11
30 amp 30 amp

C14
C13
30 amp Spare

C15
Spare Spare
S

I = V/R
S
S

11980
= 220

=54. 45 amp x .80 D.F


= 43. 563 amp : 60 amp
No. 8 AWG COPPER WIRE
GROUND

E CIRCUIT BREAKER DIAGRAM E SAMPLE COMPUTATIONS


SCALE: 1:100 MT
NOT TO SCALE