PT3: three phase
single-function transducers Accurate
class 0.2, 0.5 & 1
USB
programming
Response time
~100-220 ms
Modbus RTU
Compact, long range
site configurable transducers
PT3 is a range of compact, configurable single measured
transducers designed to meet the demanding needs of supply
utilities and industrial applications. It offers accurate true RMS
measurements for high efficiency with quick response time. It
is equipped with up to four load-independent, galvanically-
isolated analogue outputs that can be configured for desired
input range and output curves. PT3 transducers comply with IEC
60688.
Ÿ Best in class response time
Ÿ Long range, site-configurable inputs and outputs
Ÿ Load-independent accuracy on all outputs
Ÿ Diagnostic LEDs
Ÿ Compact footprint
Measurement functions Output range No. of Accuracy class
(Measurands) outputs
Current, active power, frequency, 0-1 mA*, 0-2 mA**, 0-5 mA**, 0-10 mA, 2 or 4 0.2, 0.5, 1.0
reactive power, power factor, 0-20 mA, 4-20 mA, -20 -(+20) mA, -10-(+10) mA,
apparent power -5-(+5) mA**, -2-(+2) mA**, -1-(+1) mA*,
0-5 V, 0-10 V, -10-(+10) V, -5-(+5) V
Voltage 0-1 mA*, 0-2 mA**, 0-5 mA**, 0-10 mA, 2 or 4 0.2, 0.5, 1.0
0-20 mA, 4-20 mA
0-5 V, 0-10 V
*available in accuracy class 1.0
**available in accuracy class 0.5 and class 1.0
Power factor accuracy ± 0.2 degree at nominal input range
PT3: three phase
single-function transducers
Output cuves
Curve A Curve B Curve F
Linear Linear with live zero Compressed upper region
Output Output Output
Input Input Input
Curve F Curve C Curve D
Compressed lower region Bipolar bipolar with live zero
Output Output Output
Input Input Input
Bipolar Zero displacement
Mechanical dimensions
75 mm
100 mm 105 mm
Front view Side view Isometric view
PT3: three phase
single-function transducers
Technical specifications
Variants
AC voltage
Nominal input (Un) 3 x 100 to 415 V L-L (3-phase 3-wire system)
3 x 57.5 to 240V L-N (3-phase 4-wire system)
Measuring range 0 to 130 % of Vn (500 V max.)
Measurement frequency 50/60 Hz (±5 %)
Burden ≤0.2 VA
Maximum overload voltage 1.3 x Un continuously (500 V max.)
2 x Un for 1 s, with up to 10 repetitions at 10 s intervals
Scale factor 0.8 to 1.5 Un
AC current
Nominal input (In) 1A to 5A
Measuring current range 0 to 150 % In
Scale factor 0.6 to 1.5 In
Burden ≤0.2 VA
Maximum overload current 2 x In continuously
20 x In for 1 s, with up to 10 repetitions at 100 s intervals
Active power /reactive power/ apparent power
Nominal input voltage (Un) 3 x 100 to 415 V L-L (3-phase 3-wire system)
3 x 57.5 to 240V L-N (3 -phase 4-wire system)
Input voltage range 0 to 130 % Un (up to 500 V)
Nominal input current (In) 1A to 5A
Input current range 0 to 150 % In
Measurement frequency 50/60 Hz (±5 %)
Scale factor 0.5 to 1.5 of Un x In primary (active power, at unity power factor)
0.3 to 1 Un x In primary (reactive power, at reactive power factor>0.8 or unity)
Un x In primary (apparent power)
Active power factor / load power factor
Nominal input voltage (Un) 3 x 100 to 415 V L-L (3 phase 3 wire system)
3 x 57.5 to 240V L-N (3 phase 4 wire system)
Input voltage range 0 to 130 % Un (up to 500 V)
Nominal input current (In) 1A to 5A
Input current range 0 to 150 % In
Measurement frequency 50/60 Hz (±5 %)
Measurement range -1...0...1
Resolution (phase angle) ±0.2 degree (at nominal range)
Frequency
Nominal input voltage (Un) 3 x 100 to 415 V L-L (3 phase 3 wire system)
3 x 57.5 to 240V L-N (3 phase 4 wire system)
Nominal input current (In) 1A to 5A
Measurement range 45Hz to 55Hz or 55Hz to 65Hz
Accuracy + 0.2%
Auxiliary supply
High auxiliary
Nominal voltage range 80-276 V AC/DC (±10 %)
Frequency 50/60 Hz
Maximum burden ≤11 VA, 6 W with two outputs at 750 Ω each
≤12 VA, 7 W with four outputs at 750 Ω each
Low auxiliary
Nominal voltage range 24-80 V DC (±10 %)
Maximum burden ≤6 W with two outputs at 750 Ω each
≤8 W with four outputs at 750 Ω each
PT3: three phase
single-function transducers
Technical specifications
Analogue outputs
Type Current & Voltage (bipolar)
Maximum load resistance ≤750 Ω for 20 mA, ≥ 2 k Ω for 10 V (for each output)
Response time 5 cycles measurement (≤100-250 ms)
Ripple <0.4 % peak to peak
Temperature range
Operating temperature -5 °C to +55 °C
Storage temperature -25 °C to +70 °C
Usage group 1
Physical
Dimension (W x H x D) 100 x 75 x 105 (mm)
Weight 0.7 kg (approx.)
Material Fire-retardant polycarbonate (PC-FR, UL 94 V-0)
Mounting DIN (EN 50022)
Connector type Screw terminals
Conductor size for terminals ≤4 mm2
Environmental
Protection class II (double insulation) EN 61010-1
Pollution degree 2
Installation category CAT III for < 300V AC and CAT II for < 600V AC
Protection degree Protection housing: IP 40, terminals: IP 20
Standards compliance
Standards IEC 60688, IEC 61010-1, IEC 61010-2-30, IEC 61326-1, DIN 50022
Communication ports
Micro USB For configuration
Can be configured without auxiliary power
RS-485 Modbus RTU enabled (suitable for integration with SCADA/PLC)
Baud rate 1200-38400 baud
Configuration software- Configview ConfigView
For on-site configuration of measurement inputs, measurands, output curve
and online parameter reading. It can be freely downloaded from
www.securemeters.com
Ordering key
PT XX3-1YY X X 3 - 1 Y Y
Example
Specifications are subject to change without prior notice
PT 623-126
where high auxiliary (6), Output Accuracy
output nos. (2), accuracy class (2) 2: 2 nos. 1: Cl 1.0
Function
function active power(6) 4: 4 nos. 2: Cl 0.2
1: Voltage
Aux supply 5: Cl 0.5
3: Frequency
6: High 7: Accuracy
5: Current
7: Low as per
6: Active Power
configuration
7: Reactive Power
8: Power Factor
9: Apparent power