Typical Full-Load Motor
Current Chart for Three
Phase Alternating-
Current Motors
The following values of full-load currents are typical for
motors running at speeds usual for belted motors and
motors with normal torque characteristics. Motors built
for low speeds (1200 RPM or less) or high torques may
require more running current, and multispeed motors
will have a full-load current varying with speed. In these
cases the nameplate current ratings shall be used
230
HP 208 Volts Volt 460 Volts
s
1/2 2.4 2.2 1.1
3/4 3.5 3.2 1.6
1 4.6 4.2 2.1
1 1/2 6.6 6.0 3.0
2 7.5 6.8 3.4
3 10.6 9.6 4.8
5 16.7 15.2 7.6
7 1/2 24.2 22 11
10 30.8 28 14
15 46.2 42 21
20 59.4 54 27
25 74.8 68 34
30 88 80 40
40 114 104 52
50 143 130 65
60 169 154 77
75 211 192 96
100 273 248 124
125 343 312 156
150 396 360 180
200 528 480 240
250 -- -- 302
300 -- -- 361
350 -- -- 414
400 -- -- 477
450 -- -- 515
500 -- -- 590