TRANSFORMER TEST REPORT IF
APPLICABLE
LA DOC. NO: LA-R-TR-003
Details & Location M/s. Northern Railway, Lucknow Equipment Sr. No. 2048355
Tested by Jaydeep and Kapil Testing Date 07/05/2020
Report Prepared by Mayur Report No.
End User Details & Location: M/s Northern Railway, Lucknow
Client / Contractor Name: M/s Vishwas Power
Customer Reference PO No: PO Dated:
Details of Unit Under Test
Serial Number 2048355
Manufacturer BHEL
Year of Manufacture 2019
No. of Phases 1
Rated Capacity (MVA) HV LV
ONAN 21.60 21.60
ONAF 30.24 30.24
HV LV
Rated Voltage (KV)
132 27
HV LV
Rated Current (Amp)
229 1120
Rated Frequency (Hz) 50
Vector Group Ii0
%Impedance 12.37
Type of Tap Changer OCTC
Total Number of Taps 6
Reference Standard IS 2026 / IEC 60076
Information of Testing Instruments:
Date of Last Due Date of
Instrument Make Model Serial Number
Calibration Calibration
MULTIPURPOSE TEST KIT OMICRON CPC 100 SE639Y 21/05/2019 20/05/2020
IR TESTER FLUKE 3616028
SFRA KIT MEGGAR FRAX-101
Tested By Report Reviewed/Authorized By Witnessed By
Schedule of Tests Performed
No. Details of Test Page No.
1 Measurement of Tanδ And Capacitance of Winding 3
2 Measurement of Tanδ And Capacitance of Bushing 4
Page 1 of 8
NABL LOGO
TRANSFORMER TEST REPORT IF
APPLICABLE
LA DOC. NO: LA-R-TR-003
Details & Location M/s. Northern Railway, Lucknow Equipment Sr. No. 2048355
Tested by Jaydeep and Kapil Testing Date 07/05/2020
Report Prepared by Mayur Report No.
3 Measurement of Insulation Resistance Test of Winding 5
4 Measurement of Sweep Frequency Response Analysis 5
1. Measurement of Tanδ And Capacitance of Winding:
OTI: 35 °C WTI: 35 °C
Combination Mode Test Capacitance Capacitance Tanδ Tanδ
Page 2 of 8
NABL LOGO
TRANSFORMER TEST REPORT IF
APPLICABLE
LA DOC. NO: LA-R-TR-003
Details & Location M/s. Northern Railway, Lucknow Equipment Sr. No. 2048355
Tested by Jaydeep and Kapil Testing Date 07/05/2020
Report Prepared by Mayur Report No.
Voltage (nF) (nF) (%) (%)
(kV) Site Factory Site Factory
2 8.05011 ---- 0.3249 ----
HV/LV UST 5 8.05046 8.03900 0.3268 0.246
10 8.05052 ---- 0.3275 ----
2 1.45845 ---- 0.3886 ----
HV/ground with
GST-g 5 1.45847 1.45045 0.3891 0.377
LV Guard
10 1.45849 ---- 0.3905 ----
2 9.50868 ---- 0.3340 ----
HV/LV+Ground GST 5 9.50886 9.48949 0.3365 0.264
10 9.50936 ---- 0.3436 ----
2 8.05089 ---- 0.3243 ----
LV/HV UST 5 8.05110 ---- 0.3260 ----
10 8.05105 ---- 0.3271 ----
2 8.54295 ---- 0.3969 ----
LV/ground with
GST-g 5 8.54386 8.50952 0.3964 0.335
HV Guard
10 8.54425 ---- 0.3973 ----
2 16.5956 ---- 0.3613 ----
LV/HV+Ground GST 5 16.5952 16.5486 0.3622 0.265
10 16.5958 ---- 0.3622 ----
Acceptance Criteria: Measured Tan Delta value should be <0.5%
Results: Pass
2. Measurement of Tanδ And Capacitance of Bushings
OTI: 35 °C WTI: 35 °C
Test Capacitance Capacitance Tanδ Tanδ
Combination Mode
Voltage (kV) (pF) Site (pF) Factory (%) Site (%) Factory
Page 3 of 8
NABL LOGO
TRANSFORMER TEST REPORT IF
APPLICABLE
LA DOC. NO: LA-R-TR-003
Details & Location M/s. Northern Railway, Lucknow Equipment Sr. No. 2048355
Tested by Jaydeep and Kapil Testing Date 07/05/2020
Report Prepared by Mayur Report No.
Sr. No:1920704 2 345.851 ---- 0.1602 ----
Make:BHEL UST 5 345.845 ---- 0.1603 ----
kV: 145 10 348.851 ---- 0.1602 ----
Type: OIP ---- ----
GST-g 1 1287.16 0.4161
Identification: 1.1
Sr. No:1920706 2 345.381 ---- 0.1599 ----
Make: BHEL UST 5 345.374 ---- 0.1606 ----
kV: 145 10 345.378 ---- 0.1608 ----
Type: OIP ---- ----
GST-g 1 1268.00 0.2526
Identification: 1.2
Sr. No:1911035 2 229.544 ---- 0.2865 ----
Make: BHEL UST 5 229.585 ---- 0.2878 ----
kV: 52 10 229.485 ---- 0.2754 ----
Type: OIP ---- ----
GST-g 1 645.335 0.3268
Identification: 2.1
Sr. No:1941093 2 233.704 ---- 0.2798 ----
Make: BHEL UST 5 233.656 ---- 0.2817 ----
kV: 52 10 233.655 ---- 0.2816 ----
Type: OIP ---- ----
GST-g 1 681.199 0.6012
Identification: 2.2
Acceptance Criteria: Measured Tan Delta value should be <0.4%
Results: Pass
3. Measurement of Insulation Resistance of Winding:
OTI: 35 °C WTI: 35°C
Page 4 of 8
NABL LOGO
TRANSFORMER TEST REPORT IF
APPLICABLE
LA DOC. NO: LA-R-TR-003
Details & Location M/s. Northern Railway, Lucknow Equipment Sr. No. 2048355
Tested by Jaydeep and Kapil Testing Date 07/05/2020
Report Prepared by Mayur Report No.
Applied D.C. IR Value(in GΩ) PI
Connection
Voltage 15 Sec 60 Sec 600 Sec (600 Sec / 60 Sec)
HV/LV 5000 Volts 0.673 4.950 22.90 4.62
HV – E 5000 Volts 1.140 3.87 15.40 3.98
LV – E 5000 Volts 0.657 1.48 2.04 1.38
Acceptance Criteria: Polarization Index should be ≥ 1.5
Results: Pass
4. SFRA Test Signatures
Listing of Measurement combinations:
COMBINATION: OPEN OR SHORTED OR GROUND TAP
No.
MEASURED BETWEEN TERMINALS (if any) POSITION
1 1.1-1.2 All Open 6
2 1.1-1.2 2.1 & 2.2 Shorted Together 6
3 2.1-2.2 All Open 1
4 2.1-2.2 All Open 4
5 2.1-2.2 All Open 6
1. HV 1.1-1.2 (All Open) Tap-6
Page 5 of 8
NABL LOGO
TRANSFORMER TEST REPORT IF
APPLICABLE
LA DOC. NO: LA-R-TR-003
Details & Location M/s. Northern Railway, Lucknow Equipment Sr. No. 2048355
Tested by Jaydeep and Kapil Testing Date 07/05/2020
Report Prepared by Mayur Report No.
2. HV 1.1-1.2 (LV Short) Tap-6
3. LV 2.1-2.2 (All Open) Tap-1
Page 6 of 8
NABL LOGO
TRANSFORMER TEST REPORT IF
APPLICABLE
LA DOC. NO: LA-R-TR-003
Details & Location M/s. Northern Railway, Lucknow Equipment Sr. No. 2048355
Tested by Jaydeep and Kapil Testing Date 07/05/2020
Report Prepared by Mayur Report No.
4. LV 2.1-2.2 (All Open) Tap-4
5. LV 2.1-2.2 (All Open) Tap-6
Page 7 of 8
NABL LOGO
TRANSFORMER TEST REPORT IF
APPLICABLE
LA DOC. NO: LA-R-TR-003
Details & Location M/s. Northern Railway, Lucknow Equipment Sr. No. 2048355
Tested by Jaydeep and Kapil Testing Date 07/05/2020
Report Prepared by Mayur Report No.
--- END OF REPORT ---