technical data

air conditioning systems


Ceiling Mounted Corner Cassette

FXKQ-MAVE
technical data

air conditioning systems


Ceiling Mounted Corner Cassette

FXKQ-MAVE
• Indoor Units • CEILING MOUNTED CORNER CASSETTE • FXKQ-MAVE

TABLE OF CONTENTS
FXKQ-MAVE

1 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Electrical Specifications (50Hz) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Electrical Specifications (60Hz) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

2 Safety device settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

3 Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

4 Control systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

5 Capacity tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Cooling capacity tables .............................................. 6
Heating capacity tables .............................................. 7

6 Dimensional drawing & centre of gravity . . . . . . . . . . . . . . . . . . . . . . . . 8


Dimensional drawing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Centre of gravity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

7 Piping diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

8 Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

9 Sound data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Sound level data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Sound pressure spectrum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

10 Air flow pattern . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

11 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Drainage instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Suspension bolt pitch position . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Service space . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

• VRV® Systems • Indoor Units 1


• Indoor Units • CEILING MOUNTED CORNER CASSETTE • FXKQ-MAVE

1 Specifications

m ut e oi tMn sUE Vgy AnSr M io - ®lo Q Vdi K nReX CFIV


1-1 TECHNICAL SPECIFICATIONS FXKQ25MAVE FXKQ32MAVE FXKQ40MAVE FXKQ63MAVE
Capacity Cooling kW 2.80 3.60 4.50 7.10
Heating kW 3.20 4.00 5.00 8.00
Power Input (50Hz) Cooling kW 0.066 0.066 0.076 0.105
Heating kW 0.046 0.046 0.056 0.085
Power Input (60Hz) Cooling kW 0.069 0.069 0.092 0.120
Heating kW 0.049 0.049 0.072 0.100
Casing Material Galvanised steel
Dimensions Unit Height mm 215 215 215 215
Width mm 1110 1110 1110 1310
Depth mm 710 710 710 710
Weight Unit kg 31 31 31 34
Heat Exchanger Dimensions Nr of Rows 2 2 2 3
Fin Pitch mm 1.75 1.75 1.75 1.75
Face Area m² 0.180 0.180 0.180 0.226
Nr of Stages 11 11 11 11
Fan Type Sirocco fan
Quantity 1 1 1 1
Air Flow Rate Cooling High m³/min 11.00 11.00 13.00 18.00
Low m³/min 9.00 9.00 10.00 15.00
Fan Motor Quantity 1 1 1 1
Model 3D12H1AN1V1 3D12H1AN1V1 3D12H1AP1V1 4D12H1AJ1V1
Output (high) W 15 15 20 45
Drive Direct drive
Refrigerant Name R-410A
Cooling Sound Pressure High dBA 38.0 38.0 40.0 42.0
Low dBA 33.0 33.0 34.0 37.0
Piping connections Liquid (OD) Type Flare connection
Diameter mm 6.35 6.35 6.35 9.52
Gas Type Flare connection
Diameter mm 12.7 12.7 12.7 15.9
Drain Diameter mm 32 32 32 32
Heat Insulation Foamed Polyethylene
Decoration Panel Model BYK45FJW1 BYK45FJW1 BYK45FJW1 BYK71FJW1
Colour White
Dimensions Height mm 70 70 70 70
Width mm 1240 1240 1240 1440
Depth mm 800 800 800 800
Weight kg 8.5 8.5 8.5 9.5
Air Filter Resin net with mold resistance
Refrigerant control Electronic expansion valve
Temperature control Microprocessor thermostat for cooling and heating
Safety devices PC board fuse
Drain pump fuse
Fan motor thermal fuse Fan motor thermal fuse Fan motor thermal Fan motor thermal
protector protector
Standard Accessories Installation and operation manual
Metal clamp for drain hose
Clamps
Insulation for hanger bracket
Positioning jig for installation
Paper pattern for installation
Drain hose
Insulation for fitting
Sealing pads
Screws
Washer
Air outlet blocking pad

2 • VRV® Systems • Indoor Units


• Indoor Units • CEILING MOUNTED CORNER CASSETTE • FXKQ-MAVE

1 Specifications

1-1 TECHNICAL SPECIFICATIONS FXKQ25MAVE FXKQ32MAVE FXKQ40MAVE FXKQ63MAVE


Notes Nominal cooling capacities are based on : indoor temperature : 27°CDB, 19°CWB, outdoor temperature
: 35°CDB, equivalent refrigerant piping : 7.5m (horizontal)
Nominal heating capacities are based on : indoor temperature : 20°CDB, outdoor temperature : 7°CDB,
6°CWB, equivalent refrigerant piping : 7.5m (horizontal)
Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
Sound pressure levels are measured at 220V

1-2 ELECTRICAL SPECIFICATIONS (50HZ) FXKQ25MAVE FXKQ32MAVE FXKQ40MAVE FXKQ63MAVE


Power Supply Name VE
Phase 1~
Frequency Hz 50
Voltage V 220-240
Current Minimum circuit amps (MCA) A 0.3 0.3 0.3 0.5
Maximum fuse amps (MFA) A 15 15 15 15
Full load amps (FLA) A 0.2 0.2 0.2 0.4
Voltage range Minimum V -10%
Maximum V +10%
Notes Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminals
is not below or above listed range limits.
Maximum allowable voltage range variation between phases is 2%.
MCA/MFA : MCA = 1.25 x FLA
MFA is smaller than or equal to 4 x FLA
Next lower standard fuse rating minimum 15A
Select wire size based on the MCA
Instead of a fuse, use a circuit breaker

1-3 ELECTRICAL SPECIFICATIONS (60HZ) FXKQ25MAVE FXKQ32MAVE FXKQ40MAVE FXKQ63MAVE


Power Supply Name VE
Phase 1~
Frequency Hz 60
Voltage V 220
Current Minimum circuit amps (MCA) A 0.4 0.4 0.5 0.6
Maximum fuse amps (MFA) A 15 15 15 15
Full load amps (FLA) A 0.3 0.3 0.4 0.5
Voltage range Minimum V -10%
Maximum V +10%
Notes Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminals
is not below or above listed range limits.
Maximum allowable voltage range variation between phases is 2%.
MCA/MFA : MCA = 1.25 x FLA
MFA is smaller than or equal to 4 x FLA
Next lower standard fuse rating minimum 15A
Select wire size based on the MCA
Instead of a fuse, use a circuit breaker

• VRV® Systems • Indoor Units 3


• Indoor Units • CEILING MOUNTED CORNER CASSETTE • FXKQ-MAVE

2 Safety device settings

FXKQ25MA FXKQ32MA FXKQ40MA FXKQ63MA


PC BOARD FUSE 250V 5A
FAN MOTOR THERMAL FUSE °C 146±3 -
FAN MOTOR THERMAL PROTECTOR °C - OFF: 120±5 / ON: 105 or less
DRAIN PUMP THERMAL FUSE °C 145
3D006691K

3 Options

FXKQ25MA FXKQ32MA FXKQ40MA FXKQ63MA


DECORATION PANEL BYK45FJW1 BYK71FJW1
PANEL SPACER KPBJ52F56W KPBJ52F80W
LONG LIFE REPLACEMENT FILTER KAFJ521F56 KAFJ521F80
AIR DISCHARGE GRILL K-HV7AW K-HV9AW
AIR DISCHARGE BLIND PANEL KDBJ52F56W KDBJ52F80W
FLEXIBLE DUCT (WITH SHUTTER) KFDJ52F56 KFDJ52F80
3D037081A

Shutter

Flexible duct (with shutter)

Fresh air intake position

Air discharge grill

Decoration panel Long life filter Panel spacer


(For front discharge)

4 • VRV® Systems • Indoor Units


• Indoor Units • CEILING MOUNTED CORNER CASSETTE • FXKQ-MAVE

4 Control systems

Individual control systems

FXKQ25MA FXKQ32MA FXKQ40MA FXKQ63MA


WIRED REMOTE CONTROL BRC1D52
INFRARED REMOTE CONTROL Heat pump BRC4C61
Cooling only BRC4C63

Centralised control systems

FXKQ25MA FXKQ32MA FXKQ40MA FXKQ63MA


CENTRALISED REMOTE CONTROL DCS302C51
UNIFIED ON/OFF CONTROL DCS301B51
SCHEDULE TIMER DST301B51

Others

FXKQ25MA FXKQ32MA FXKQ40MA FXKQ63MA


WIRING ADAPTER KRP1B61
WIRING ADAPTER FOR ELECTRICAL APPENDICES (1) KRP2A61
WIRING ADAPTER FOR ELECTRICAL APPENDICES (2) KRP4A51
REMOTE SENSOR KRCS01-1
ELECTRICAL BOX WITH EARTH TERMINAL (3 BLOCKS) KJB311A
ELECTRICAL BOX WITH EARTH TERMINAL (2 BLOCKS) KJB212A
NOISE FILTER (FOR ELECTROMAGNETIC INTERFACE USE ONLY) KEK26-1A
EXTERNAL CONTROL ADAPTER FOR OUTDOOR UNITS (INSTALLATION ON INDOOR UNIT) DTA104A61
3D034600C

• VRV® Systems • Indoor Units 5


• Indoor Units • CEILING MOUNTED CORNER CASSETTE • FXKQ-MAVE

5 Capacity tables
5-1 Cooling capacity tables
FXKQ-MA
TC: Total capacity;kW – SHC: Sensible capacity;kW
Unit size Nominal Outdoor Indoor air temperature
capacity air temp. 14.0WB 16.0WB 18.0WB 19.0WB 20.0WB 22.0WB 24.0WB
20.0DB 23.0DB 26.0DB 27.0DB 28.0DB 30.0DB 32.0DB
°CDB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
25 2.8 10.0 1.9 1.9 2.3 2.2 2.6 2.3 2.8 2.4 3.0 2.5 3.4 2.5 3.7 2.5
12.0 1.9 1.9 2.3 2.2 2.6 2.3 2.8 2.4 3.0 2.5 3.4 2.5 3.6 2.5
14.0 1.9 1.9 2.3 2.2 2.6 2.3 2.8 2.4 3.0 2.5 3.4 2.5 3.6 2.5
16.0 1.9 1.9 2.3 2.2 2.6 2.3 2.8 2.4 3.0 2.5 3.4 2.5 3.5 2.4
18.0 1.9 1.9 2.3 2.2 2.6 2.3 2.8 2.4 3.0 2.5 3.4 2.5 3.5 2.4
20.0 1.9 1.9 2.3 2.2 2.6 2.3 2.8 2.4 3.0 2.5 3.4 2.5 3.4 2.4
21.0 1.9 1.9 2.3 2.2 2.6 2.3 2.8 2.4 3.0 2.5 3.4 2.5 3.4 2.4
23.0 1.9 1.9 2.3 2.2 2.6 2.3 2.8 2.4 3.0 2.5 3.3 2.5 3.4 2.3
25.0 1.9 1.9 2.3 2.2 2.6 2.3 2.8 2.4 3.0 2.5 3.3 2.5 3.3 2.3
27.0 1.9 1.9 2.3 2.2 2.6 2.3 2.8 2.4 3.0 2.5 3.2 2.4 3.3 2.3
29.0 1.9 1.9 2.3 2.2 2.6 2.3 2.8 2.4 3.0 2.5 3.2 2.4 3.2 2.3
31.0 1.9 1.9 2.3 2.2 2.6 2.3 2.8 2.4 3.0 2.5 3.1 2.4 3.2 2.3
33.0 1.9 1.9 2.3 2.2 2.6 2.3 2.8 2.4 3.0 2.5 3.1 2.4 3.1 2.3
35.0 1.9 1.9 2.3 2.2 2.6 2.3 2.8 2.4 3.0 2.5 3.0 2.4 3.1 2.3
37.0 1.9 1.9 2.3 2.2 2.6 2.3 2.8 2.4 2.9 2.5 3.0 2.4 3.0 2.3
39.0 1.9 1.9 2.3 2.2 2.6 2.3 2.8 2.4 2.9 2.5 2.9 2.3 3.0 2.2
32 3.6 10.0 2.4 2.2 2.9 2.5 3.4 2.6 3.6 2.7 3.8 2.9 4.3 2.9 4.7 2.9
12.0 2.4 2.2 2.9 2.5 3.4 2.6 3.6 2.7 3.8 2.9 4.3 2.9 4.7 2.9
14.0 2.4 2.2 2.9 2.5 3.4 2.6 3.6 2.7 3.8 2.9 4.3 2.9 4.6 2.9
16.0 2.4 2.2 2.9 2.5 3.4 2.6 3.6 2.7 3.8 2.9 4.3 2.9 4.6 2.8
18.0 2.4 2.2 2.9 2.5 3.4 2.6 3.6 2.7 3.8 2.9 4.3 2.9 4.5 2.8
20.0 2.4 2.2 2.9 2.5 3.4 2.6 3.6 2.7 3.8 2.9 4.3 2.9 4.4 2.8
21.0 2.4 2.2 2.9 2.5 3.4 2.6 3.6 2.7 3.8 2.9 4.3 2.9 4.4 2.7
23.0 2.4 2.2 2.9 2.5 3.4 2.6 3.6 2.7 3.8 2.9 4.2 2.9 4.3 2.7
25.0 2.4 2.2 2.9 2.5 3.4 2.6 3.6 2.7 3.8 2.9 4.2 2.8 4.3 2.7
27.0 2.4 2.2 2.9 2.5 3.4 2.6 3.6 2.7 3.8 2.9 4.1 2.8 4.2 2.7
29.0 2.4 2.2 2.9 2.5 3.4 2.6 3.6 2.7 3.8 2.9 4.1 2.8 4.2 2.6
31.0 2.4 2.2 2.9 2.5 3.4 2.6 3.6 2.7 3.8 2.9 4.0 2.7 4.1 2.6
33.0 2.4 2.2 2.9 2.5 3.4 2.6 3.6 2.7 3.8 2.9 3.9 2.7 4.0 2.6
35.0 2.4 2.2 2.9 2.5 3.4 2.6 3.6 2.7 3.8 2.9 3.9 2.7 4.0 2.6
37.0 2.4 2.2 2.9 2.5 3.4 2.6 3.6 2.7 3.7 2.8 3.8 2.7 3.9 2.6
39.0 2.4 2.2 2.9 2.5 3.4 2.6 3.6 2.7 3.7 2.8 3.8 2.7 3.8 2.6
40 4.5 10.0 3.0 2.6 3.6 2.8 4.2 3.2 4.5 3.2 4.8 3.3 5.4 3.5 5.9 3.5
12.0 3.0 2.6 3.6 2.8 4.2 3.2 4.5 3.2 4.8 3.3 5.4 3.5 5.8 3.5
14.0 3.0 2.6 3.6 2.8 4.2 3.2 4.5 3.2 4.8 3.3 5.4 3.5 5.8 3.4
16.0 3.0 2.6 3.6 2.8 4.2 3.2 4.5 3.2 4.8 3.3 5.4 3.5 5.7 3.4
18.0 3.0 2.6 3.6 2.8 4.2 3.2 4.5 3.2 4.8 3.3 5.4 3.5 5.6 3.3
20.0 3.0 2.6 3.6 2.8 4.2 3.2 4.5 3.2 4.8 3.3 5.4 3.5 5.5 3.3
21.0 3.0 2.6 3.6 2.8 4.2 3.2 4.5 3.2 4.8 3.3 5.4 3.5 5.5 3.3
23.0 3.0 2.6 3.6 2.8 4.2 3.2 4.5 3.2 4.8 3.3 5.3 3.4 5.4 3.2
25.0 3.0 2.6 3.6 2.8 4.2 3.2 4.5 3.2 4.8 3.3 5.2 3.4 5.3 3.2
27.0 3.0 2.6 3.6 2.8 4.2 3.2 4.5 3.2 4.8 3.3 5.2 3.3 5.3 3.2
29.0 3.0 2.6 3.6 2.8 4.2 3.2 4.5 3.2 4.8 3.3 5.1 3.3 5.2 3.1
31.0 3.0 2.6 3.6 2.8 4.2 3.2 4.5 3.2 4.8 3.3 5.0 3.2 5.1 3.1
33.0 3.0 2.6 3.6 2.8 4.2 3.2 4.5 3.2 4.8 3.3 4.9 3.2 5.0 3.1
35.0 3.0 2.6 3.6 2.8 4.2 3.2 4.5 3.2 4.7 3.3 4.9 3.2 5.0 3.0
37.0 3.0 2.6 3.6 2.8 4.2 3.2 4.5 3.2 4.7 3.3 4.8 3.1 4.9 3.0
39.0 3.0 2.6 3.6 2.8 4.2 3.2 4.5 3.2 4.6 3.2 4.7 3.1 4.8 3.0
63 7.1 10.0 4.8 4.0 5.7 4.5 6.6 5.0 7.1 5.1 7.6 5.2 8.5 5.4 9.3 5.6
12.0 4.8 4.0 5.7 4.5 6.6 5.0 7.1 5.1 7.6 5.2 8.5 5.4 9.2 5.5
14.0 4.8 4.0 5.7 4.5 6.6 5.0 7.1 5.1 7.6 5.2 8.5 5.4 9.1 5.4
16.0 4.8 4.0 5.7 4.5 6.6 5.0 7.1 5.1 7.6 5.2 8.5 5.4 9.0 5.3
18.0 4.8 4.0 5.7 4.5 6.6 5.0 7.1 5.1 7.6 5.2 8.5 5.4 8.8 5.3
20.0 4.8 4.0 5.7 4.5 6.6 5.0 7.1 5.1 7.6 5.2 8.5 5.4 8.7 5.2
21.0 4.8 4.0 5.7 4.5 6.6 5.0 7.1 5.1 7.6 5.2 8.5 5.4 8.7 5.2
23.0 4.8 4.0 5.7 4.5 6.6 5.0 7.1 5.1 7.6 5.2 8.4 5.3 8.5 5.1
25.0 4.8 4.0 5.7 4.5 6.6 5.0 7.1 5.1 7.6 5.2 8.3 5.3 8.4 5.0
27.0 4.8 4.0 5.7 4.5 6.6 5.0 7.1 5.1 7.6 5.2 8.1 5.2 8.3 5.0
29.0 4.8 4.0 5.7 4.5 6.6 5.0 7.1 5.1 7.6 5.2 8.0 5.1 8.2 4.9
31.0 4.8 4.0 5.7 4.5 6.6 5.0 7.1 5.1 7.6 5.2 7.9 5.1 8.1 4.9
33.0 4.8 4.0 5.7 4.5 6.6 5.0 7.1 5.1 7.6 5.2 7.8 5.0 7.9 4.8
35.0 4.8 4.0 5.7 4.5 6.6 5.0 7.1 5.1 7.5 5.2 7.7 5.0 7.8 4.8
37.0 4.8 4.0 5.7 4.5 6.6 5.0 7.1 5.1 7.4 5.1 7.5 4.9 7.7 4.8
39.0 4.8 4.0 5.7 4.5 6.6 5.0 7.1 5.1 7.2 5.0 7.4 4.9 7.6 4.7
CA03A095

6 • VRV® Systems • Indoor Units


• Indoor Units • CEILING MOUNTED CORNER CASSETTE • FXKQ-MAVE

5 Capacity tables
5-2 Heating capacity tables
FXKQ-MA

Outdoor Indoor air temperature °CDB


Unit Size Nominal capacity air temperature 16.0 18.0 20.0 21.0 22.0 24.0
°CDB °CWB kW kW kW kW kW kW
25 3.2 -19.8 -20.0 1.9 1.9 1.9 1.9 1.9 1.9
-18.8 -19.0 1.9 1.9 1.9 1.9 1.9 1.9
-16.7 -17.0 2.1 2.1 2.0 2.0 2.0 2.0
-14.7 -15.0 2.2 2.2 2.2 2.2 2.2 2.1
-12.6 -13.0 2.3 2.3 2.3 2.3 2.3 2.3
-10.5 -11.0 2.4 2.4 2.4 2.4 2.4 2.4
-9.5 -10.0 2.5 2.4 2.4 2.4 2.4 2.4
-8.5 -9.1 2.5 2.5 2.5 2.5 2.5 2.5
-7.0 -7.6 2.6 2.6 2.6 2.6 2.6 2.6
-5.0 -5.6 2.7 2.7 2.7 2.7 2.7 2.7
-3.0 -3.7 2.8 2.8 2.8 2.8 2.8 2.8
0.0 -0.7 3.0 3.0 3.0 3.0 3.0 2.8
3.0 2.2 3.1 3.1 3.1 3.1 3.0 2.8
5.0 4.1 3.3 3.2 3.2 3.1 3.0 2.8
7.0 6.0 3.4 3.4 3.2 3.1 3.0 2.8
9.0 7.9 3.5 3.4 3.2 3.1 3.0 2.8
11.0 9.8 3.6 3.4 3.2 3.1 3.0 2.8
13.0 11.8 3.6 3.4 3.2 3.1 3.0 2.8
15.0 13.7 3.6 3.4 3.2 3.1 3.0 2.8
32 4.0 -19.8 -20.0 2.4 2.4 2.3 2.3 2.3 2.3
-18.8 -19.0 2.4 2.4 2.4 2.4 2.4 2.4
-16.7 -17.0 2.6 2.6 2.6 2.6 2.6 2.5
-14.7 -15.0 2.7 2.7 2.7 2.7 2.7 2.7
-12.6 -13.0 2.9 2.8 2.8 2.8 2.8 2.8
-10.5 -11.0 3.0 3.0 3.0 3.0 3.0 3.0
-9.5 -10.0 3.1 3.1 3.1 3.1 3.0 3.0
-8.5 -9.1 3.1 3.1 3.1 3.1 3.1 3.1
-7.0 -7.6 3.2 3.2 3.2 3.2 3.2 3.2
-5.0 -5.6 3.4 3.4 3.4 3.4 3.4 3.4
-3.0 -3.7 3.5 3.5 3.5 3.5 3.5 3.5
0.0 -0.7 3.7 3.7 3.7 3.7 3.7 3.5
3.0 2.2 3.9 3.9 3.9 3.9 3.7 3.5
5.0 4.1 4.1 4.1 4.0 3.9 3.7 3.5
7.0 6.0 4.2 4.2 4.0 3.9 3.7 3.5
9.0 7.9 4.3 4.3 4.0 3.9 3.7 3.5
11.0 9.8 4.5 4.3 4.0 3.9 3.7 3.5
13.0 11.8 4.5 4.3 4.0 3.9 3.7 3.5
15.0 13.7 4.5 4.3 4.0 3.9 3.7 3.5
40 5.0 -19.8 -20.0 3.0 2.9 2.9 2.9 2.9 2.9
-18.8 -19.0 3.0 3.0 3.0 3.0 3.0 3.0
-16.7 -17.0 3.2 3.2 3.2 3.2 3.2 3.2
-14.7 -15.0 3.4 3.4 3.4 3.4 3.4 3.4
-12.6 -13.0 3.6 3.6 3.6 3.5 3.5 3.5
-10.5 -11.0 3.7 3.7 3.7 3.7 3.7 3.7
-9.5 -10.0 3.8 3.8 3.8 3.8 3.8 3.8
-8.5 -9.1 3.9 3.9 3.9 3.9 3.9 3.9
-7.0 -7.6 4.0 4.0 4.0 4.0 4.0 4.0
-5.0 -5.6 4.2 4.2 4.2 4.2 4.2 4.2
-3.0 -3.7 4.4 4.4 4.4 4.4 4.4 4.4
0.0 -0.7 4.7 4.6 4.6 4.6 4.6 4.4
3.0 2.2 4.9 4.9 4.9 4.8 4.7 4.4
5.0 4.1 5.1 5.1 5.0 4.8 4.7 4.4
7.0 6.0 5.2 5.2 5.0 4.8 4.7 4.4
9.0 7.9 5.4 5.3 5.0 4.8 4.7 4.4
11.0 9.8 5.6 5.3 5.0 4.8 4.7 4.4
13.0 11.8 5.6 5.3 5.0 4.8 4.7 4.4
15.0 13.7 5.6 5.3 5.0 4.8 4.7 4.4
63 8.0 -19.8 -20.0 4.7 4.7 4.7 4.7 4.7 4.7
-18.8 -19.0 4.9 4.9 4.8 4.8 4.8 4.8
-16.7 -17.0 5.1 5.1 5.1 5.1 5.1 5.1
-14.7 -15.0 5.4 5.4 5.4 5.4 5.4 5.4
-12.6 -13.0 5.7 5.7 5.7 5.7 5.7 5.7
-10.5 -11.0 6.0 6.0 6.0 6.0 6.0 5.9
-9.5 -10.0 6.1 6.1 6.1 6.1 6.1 6.1
-8.5 -9.1 6.3 6.3 6.2 6.2 6.2 6.2
-7.0 -7.6 6.5 6.5 6.4 6.4 6.4 6.4
-5.0 -5.6 6.8 6.7 6.7 6.7 6.7 6.7
-3.0 -3.7 7.0 7.0 7.0 7.0 7.0 7.0
0.0 -0.7 7.5 7.4 7.4 7.4 7.4 7.0
3.0 2.2 7.9 7.8 7.8 7.7 7.5 7.0
5.0 4.1 8.1 8.1 8.0 7.7 7.5 7.0
7.0 6.0 8.4 8.4 8.0 7.7 7.5 7.0
9.0 7.9 8.7 8.5 8.0 7.7 7.5 7.0
11.0 9.8 8.9 8.5 8.0 7.7 7.5 7.0
13.0 11.8 9.0 8.5 8.0 7.7 7.5 7.0
15.0 13.7 9.0 8.5 8.0 7.7 7.5 7.0
CA03A095

• VRV® Systems • Indoor Units 7


• Indoor Units • CEILING MOUNTED CORNER CASSETTE • FXKQ-MAVE

6 Dimensional drawing & centre of gravity


6-1 Dimensional drawing
FXKQ25,32,40MA

Required installation space

1,500 mm or 200 mm or more


more 200 mm or more
20 mm or more
350 (Suspension position)
760 (Ceiling opening)

Nr. Name Description


1 Liquid pipe connection ø 6.4 Flare connection
2 Gas pipe connection ø 12.7 Flare connection
3 Drain pipe connection VP25 (O.D. ø 32)
1,150 (Suspension position) 4 Wire intake
1,200 (Ceiling opening) 5 Interunit wiring connection
6 Grounding terminal Inside switch box (M4)
Front discharge duct position 7 Discharge
4-M4 hole Suspension bolt 8 Air suction grille
9 Long life filter
10 Suspension bolt
Required installation space
1,000 or more

NOTES

1 Location of unit’s name plate:


• For main body: Bottom part of fan housing inside of air suction grille.
• For decoration panel: Service lid face inside of air suction grille.
2 When installing an optional accessory, refer to the installation drawings.

3D038840

FXKQ63MA

Required installation space


1,500 mm or 200 mm or more
more 200 mm or more
20 mm or more
350 (Suspension position)

Nr. Name Description


760 (Ceiling opening)

1 Liquid pipe connection ø 9.5 Flare connection


2 Gas pipe connection ø 15.9 Flare connection
3 Drain pipe connection VP25 (O.D. ø 32)
4 Wire intake
5 Interunit wiring connection
1,350 (Suspension position)
1,400 (Ceiling opening)
6 Grounding terminal Inside switch box (M4)
7 Discharge
Front discharge duct position 8 Air suction grille
6-M4 hole Suspension bolt 9 Long life filter
10 Suspension bolt
installation space)
1,000 or more

NOTES
(Required

1 Location of unit’s name plate:


• For main body: Bottom part of fan housing inside of air suction grille.
• For decoration panel: Service lid face inside of air suction grille.
2 When installing an optional accessory, refer to the installation drawings.

3D038841

8 • VRV® Systems • Indoor Units


• Indoor Units • CEILING MOUNTED CORNER CASSETTE • FXKQ-MAVE

6 Dimensional drawing & centre of gravity


6-2 Centre of gravity
FXKQ-MA

Model A
FXKQ25,32,40MA 1,110
FXKQ63MA 1,310

4D037079A

• VRV® Systems • Indoor Units 9


• Indoor Units • CEILING MOUNTED CORNER CASSETTE • FXKQ-MAVE

7 Piping diagram

FXKQ-MA

Gas pipe connection port


Heat exchanger

Fan

Liquid pipe connection port

Filter Filter

Electronic expansion
valve

Piping connection diameters

Model Gas Liquid


FXKQ25,32,40MA ø12.7 ø6.4
FXKQ63MA ø15.9 ø9.5

4D034245A

10 • VRV® Systems • Indoor Units


• Indoor Units • CEILING MOUNTED CORNER CASSETTE • FXKQ-MAVE

8 Wiring diagram
8-1 Wiring diagram

FXKQ-MA

Power supply
220-240V 220V Electric parts box
~ ~
50Hz 60Hz

Note 2
Input from outside
Note 1
Note 3 Transmission wiring central
remote control

Wired remote control


(Optional accessory)

Indoor Unit R1T Thermistor (Air)


A1P Printed circuit board R2T•R3T Thermistor (Coil)
A2P Terminal board S1Q Limit switch (Swing flap)
C1R Capacitor (M1F) T1R Transformer (220-240V/22V)
F1U Fuse (훾, 5A, 250V) X1M Terminal block (Power)
HAP Light emitting diode (Service monitor-green) X2M Terminal block (Control)
K1R-K3R Magnetic relay (M1F) Y1E Electronic expansion valve
KAR Magnetic relay (M1S) Wired remote control
KPR Magnetic relay (M1P) R1T Thermistor (Air)
M1F Motor (Indoor fan) SS1 Selector Switch (Main/Sub)
M1P Motor (Drain pump) Connector for optional parts
M1S Motor (Swing flap) X16A Connector (Adapter for wiring)
Q1M Thermo switch (M1F embedded) X18A Connector (Wiring adapter for electorical appendices)

: Terminal block COLORS : BLK : Black PNK : Pink


, : Connector BLU : Blue RED : Red
: Terminal BRN : Brown WHT : White
: Field wiring GRY : Gray YLW : Yellow
ORG : Orange

NOTES
1 In case using central remote control, connect it to the unit in accordance with the attached instruction manual.
2 When connecting the input wires from outside, forced off or on/off control operation can be selected by remote control.
In details, refer to the installation manual attached the unit.
3 In case high E.S.P. operation, change over the wiring connection from X2A to X3A.
4 Use copper conductors only.

3D039564B

• VRV® Systems • Indoor Units 11


• Indoor Units • CEILING MOUNTED CORNER CASSETTE • FXKQ-MAVE

9 Sound data
9-1 Sound level data
FXKQ-MA

Sound pressure level - 220 V Sound pressure level - 240 V


Model Sound power level
H L H L
FXKQ25MA 38 33 40 35 *
FXKQ32MA 38 33 40 35 *
FXKQ40MA 40 34 42 36 *
FXKQ63MA 42 37 44 39 *
* data were not available at the time of publication

NOTES

1 Reference acoustic pressure 0dB=0.0002μbar


2 Operation noise differs with operation and ambient conditions
3 Measuring place: anechoic chamber

12 • VRV® Systems • Indoor Units


• Indoor Units • CEILING MOUNTED CORNER CASSETTE • FXKQ-MAVE

9 Sound data
9-2 Sound pressure spectrum

FXKQ25,32MA 4D037071 FXKQ40MA 4D037072

Octave band sound pressure level dB (0dB=0.0002 μbar)


Sound pressure level dB (0dB=0.0002 m bar)

Approximate
threshold
hearing for
continuous noise

Octave band center frequency (Hz)


Approximate
threshold
hearing for
continuous noise

Octave band center frequency (Hz)

FXKQ63MA 4D037073
Octave band sound pressure level dB (0dB=0.0002 μbar)

Approximate
threshold
hearing for
continuous noise

Octave band center frequency (Hz)

• VRV® Systems • Indoor Units 13


• Indoor Units • CEILING MOUNTED CORNER CASSETTE • FXKQ-MAVE

10 Air flow pattern

FXKQ63MA
Heating air velocity distribution
Lower air blow
3m

1.5 m/sec 2m

1.0 m/sec
1m
0.5 m/sec

0m
0m 1m 2m 3m 4m 5m 6m 7m 8m

Heating temperature distribution


Lower air blow
3m

33°C
2m
30°C

27°C 1m
25°C
22°C
0m
0m 1m 2m 3m 4m 5m 6m 7m 8m

NOTES

1 The corner type is applicable on a high ceiling. The standard set-up height is 3 m. Shown here is the measurement distribution at the ceiling
height of 3 m.

14 • VRV® Systems • Indoor Units


• Indoor Units • CEILING MOUNTED CORNER CASSETTE • FXKQ-MAVE

11 Installation
11 - 1 Drainage instructions
Rig the drain pipe as shown below and take measures against
condensation. Improperly rigged piping could lead to leaks and
eventually wet furniture and belongings.

Install the drain pipes.

• Keep piping as short as possible and slope it downwards so that


the air does not remain trapped inside the pipe.
• The diameter of the drain pipe should be larger than or equal to
the diameter of the connecting pipe (Vinyl tube; pipe size: 25 mm; Clamp metal
outer dimension: 32 mm).
• Use the attached drain hose and clamp metal. Insert the drain hose
into the drain socket, up to the white tape. Tighten the clamp until
the screw head is less than 4 mm from the hose.

Tape (white) Drain hose


CAUTION
Clamp metal Large sealing pad
1 Installing the unit at an angle opposite to the drain piping might
(attached) (attached)
cause leaks.

• Wrap the attached sealing pad over the clamp and drain hose to
insulate.
• Insulate the drain hose inside the building.
< 4 mm
• Insulate the clamp and drain hose with the attached large sealing
pad. If the drain hose cannot be sufficiently set on a slope, execute
the drain raising piping. Secure a downward gradient of 1/100 or
more for the drain pipe. To accomplish this, mount supporting
brackets at an interval of 1 - 1.5 m.

Precautions when installing drain-up piping.


• Make sure the drain-up piping is maximum 330 mm high. Install
the drain-up piping horizontally, and make sure it is not further
than 300 mm from the base of the drain socket.

Ceiling slab

< 300 1-1.5 m Support bracket

Adjustable (< 330)


Drain-up piping
< 500
170

Riser

Clamp metal (attached) Drain hose (attached)

• Use the following outline if installing concentrated drain piping. If


converging multiple drain pipes, install according to the procedure
shown on the right.
> 100 mm

T-joint converging drain pipes

Select converging drain pipes whose gauge is suitable for the operating capacity of the unit.

• VRV® Systems • Indoor Units 15


• Indoor Units • CEILING MOUNTED CORNER CASSETTE • FXKQ-MAVE

11 Installation
11 - 1 Drainage instructions
When piping work is finished

• Check if drainage flows smoothly. Open the inspection opening,


add approximately 1,000 cc of water slowly into the drain pan and Inspection opening
check drainage flow.
Portable pump

NOTE

1 Use the drain outlet for maintenance to drain water from the
drain pan.
Drain outlet for maintenance (with rubber plug)
Bucket

When electric wiring work is finished

• Check drainage flow during COOL running, explained under “TEST


OPERATION”

When electric wiring work is not finished

• Remove the electric parts box lid, connect power supply and
remote control to the terminals.
Next, press the inspection/test operation button on the
remote control. The unit will engage the test operation mode.
Press the operation mode selector button until selection
FAN OPERATION . Then, press the ON/OFF button . Power supply
The indoor unit fan and drain pump will start up. Check that the KV1 type 1 ~ 220-240V
water has drained from the unit. Press to go back to the
PC board Power supply terminal
first mode.

CAUTION

1 Do not connect the drain piping directly to sewage pipes that


smell of ammonia. The ammonia in the sewage might enter the
indoor unit through the drain pipes and corrode the heat
exchanger.

Copper wire

Electric parts box lid.

16 • VRV® Systems • Indoor Units


• Indoor Units • CEILING MOUNTED CORNER CASSETTE • FXKQ-MAVE

11 Installation
11 - 2 Suspension bolt pitch position
FXKQ-MA

Decoration panel
Ceiling opening port

Indoor unit

Suspension bolt (4 pc.)

Model A B C D
FXKQ25,32,40MA 1,110 1,150 1,200 1,240
FXKQ63MA 1,310 1,350 1,400 1,440

• VRV® Systems • Indoor Units 17


• Indoor Units • CEILING MOUNTED CORNER CASSETTE • FXKQ-MAVE

11 Installation
11 - 3 Service space
FXKQ-MA

220 or more
1,000 or more

200 or more 200 or more


1,500 or more 20 or more

(Discharge side) (Suction side)

NOTES

1 Above figures mean minimum values

18 • VRV® Systems • Indoor Units


Daikin’s unique position as a manufacturer of air Daikin Europe N.V. is approved by LRQA for its Quality The present publication is drawn up by way of information only and does not
conditioning equipment, compressors and Management System in accordance with the ISO9001 constitute an offer binding upon Daikin Europe N.V.. Daikin Europe N.V. has
refrigerants has led to its close involvement in standard. ISO9001 pertains to quality assurance regarding compiled the content of this publication to the best of its knowledge. No
environmental issues. For several years Daikin has design, development, manufacturing as well as to services express or implied warranty is given for the completeness, accuracy,
had the intension to become a leader in the provision related to the product. reliability or fitness for particular purpose of its content and the products and
of products that have limited impact on the services presented therein. Specifications are subject to change without
environment. This challenge demands the eco design prior notice. Daikin Europe N.V. explicitly rejects any liability for any direct or
and development of a wide range of products and an indirect damage, in the broadest sense, arising from or related to the use
energy management system, resulting in energy and/or interpretation of this publication. All content is copyrighted by Daikin
conservation and a reduction of waste. Europe N.V..
Prepared in Belgium by Lannoo (www.lannooprint.be), a company whose concern for

Responsible Editor: Daikin Europe N.V., Zandvoordestraat 300, B- 8400 Oostende

ISO14001 assures an effective environmental


management system in order to help protect human health
and the environment from the potential impact of our
activities, products and services and to assist in
maintaining and improving the quality of the environment.
the environmont is set in the EMAS and ISO 14001 systems.

Daikin units comply with the European regulations that


guarantee the safety of the product.

Naamloze Vennootschap
Zandvoordestraat 300
B-8400 Oostende, Belgium
VRV®products are not within the scope of the Eurovent
www.daikin.eu certification programme.
BTW: BE 0412 120 336
RPR Oostende

You might also like