PT.
REKAYASA INDUSTRI
Date : Nov 11th 2021
Rev :B
CATHODIC PROTECTION SACRIFICIAL SYSTEM FOR JETTY & RWI PILE
LOMBOK CFSPP FTP-2 2X50 MW
PT. REKAYASA INDUSTRI
DATA :
CALCULATED LIFE TIME (Y) 25 Years
CURRENT DENSITY
- CURRENT DENSITY FOR RIVER MUD 20.00 mA/sq.m
COATING BREAKDOWN 22 %
CURRENT DENSITY BY CALC
- CURRENT DENSITY FOR RIVER MUD (CD1) 4.40 mA/sq.m
- CURRENT DENSITY FOR RIVER WATER 54 mA/sq.m
COATING BREAKDOWN 32 %
CURRENT DENSITY BY CALC
- CURRENT DENSITY FOR RIVER WATER (CD2) 17.22 mA/sq.m
CONSUMPTION RATE OF MAGNESIUM(CON) 7.5 [Link]/Y
UTILIZATION FACTOR (U) 0.60
PROPOSED ANODE WEIGHT (N) 30.0 Kg
NOTES AND FORMULAS :
Dia = Diameter of Pipe
L = Length of Pipe
Ap = Surface Area to be protected = (3.14 x Dia x L)
Ip = Required Protection current (Current Demand) = Ap x CD
Wt = Required Weight of Anode = Ip x Y x Con : U
Nos = Number of anodes required by Weight = Wt : N
N = Proposed Anode Weight
Length Length Nos per Proposed Total Weight of
Dia
SECTION Buried Exposed Number pile Anode Anode proposed
of Piles
(m) (m) (m) (pcs) Qty (kg)
[Link] 0.711 48.0 0.2 53 20.00 1,060.00 31800.00
[Link] 0.711 37.0 8.2 22 16.00 352.00 10560.00
[Link] 0.711 45.0 8.2 34 19.00 646.00 19380.00
[Link] 0.250 35.0 8.2 10 6.00 60.00 1800.00
[Link] 0.610 40.0 8.2 24 15.00 360.00 10800.00
[Link] 0.610 29.0 0.2 48 10.00 480.00 14400.00
[Link] 0.610 30.1 2.2 36 11.00 396.00 11880.00
[Link] 0.610 30.3 0.2 28 11.00 308.00 9240.00
TOTAL 100,620.00