Fire Pump Submittal Ramdan Scope - 2014 (1250 GPM)
Fire Pump Submittal Ramdan Scope - 2014 (1250 GPM)
4 CATALOG
AC FIRE PUMP
LOWARA JOCKEY PUMP
5 COUNTRY OF ORIGIN
6 WARRANTY CERTIFICATE
7 COMPANY PROFILE
UL LISTED / FM APPROVED / NFPA-20
REF # XYLEM A-C ELECTRIC MOTOR-FIRE PUMPS)
DOUBLE SUCTION HORIZONTAL SPLIT CASE FIRE PUMP DATA
PUMP DATA:
FLOW : 1250 GPM
HEAD : 185 PSI
MANUFACTURER : XYLEM A-C – U.S.A.
SERIES : 8100
MODEL : 8 X 6 X 12F-M
SUCTION SIZE : 8”
DISCHARGE SIZE : 6”
MOTOR DATA:
HORSE POWER : 250 HP
RPM : 3555
START : WYE DELTA START
ENCLOSURE : ODP
INSULATION : CLASS – F
AMBIENT : 40°C AMBIENT
POWER SUPPLY : 400V/3/60
FRAME SIZE : 445T
SERVICE FACTOR : 1.15
CONSTRUCTION MATERIAL:
ASTM A48 CLASS 35A CAST IRON CASING ASSEMBLY WITH SUCTION & DISCHARGE GAUGE PORTS,
ENEWABLE BRONZE CASING WEAR RINGS, COPPER SEAL FLUSH CONNECTION, DRAIN PLUG,
FLANGED SUCTION & DISCHARGE ENDS.
ASTM B584-875 BRONZE IMPELLER, FULLY ENCLOSED, DOUBLE SUCTION, DYNAMICALLY
BALANCED & KEYED TO SHAFT.
ALLOY STEEL SAE 1045 SHAFT.
BRONZE ASTM B584-932 SHAFT SLEEVES.
BRONZE ASTM B584-932 CASING RINGS.
CAST IRON STUFFING BOX.
STEEL IMPELLER KEY.
BRONZE (ASTM B584-932) PACKING GLANDWITH FIVE (5) RINGS OF GRAPHITE IMPREGNATED
ACRYLIC YARN PACKING (RINGS).
ASTM A48 CLASS 25A CAST IRON BEARING HOUSING.
GREASE LUBRICATED STEEL BEARINGS – REPLACEABLE.
FLEXIBLE COUPLED WITH ANSI/OSHA COMPLIANT COUPLER GUARD.
FABRICATED HEAVY DUTY RUGGED STEEL BASEPLATE.
1
SPECIFICATIONS:
XYLEM A-C SERIES: 8100, MADE IN U.S.A, UL-LISTED, FM-APPROVED FIRE PUMPS, MANUFACTURED
IN COMPLIANCE WITH NFPA-20 WITH THE FOLLOWING FEATURES:
HORIZONTAL SPLIT CASE, BASEMOUNTED, DOUBLE SUCTION, SINGLE STAGE CENTRIFUGAL
PUMP.
HEAVY DUTY FLEXIBLE COUPLER EMPLOYED BETWEEN PUMP & MOTOR.
ANSI / OSHA COMPLIANT HEAVY DUTY STEEL COUPLING GUARD
DYNAMICALLY BALANCED ENCLOSED TYPE IMPELLER.
THE PUMP SHALL DELIVER NOT LESS THAN 150% OF THE RATED CAPACITY AT A PRESSURE NOT
LESS THAN 65% OF THE RATED PRESSURE, THE SHUT-OFF PRESSURE SHALL NOT EXCEED 120% OF
THE RATED PRESSURE.
HORIZONTAL SUCTION & DISCHARGE.
THE CASING MAXIMUM WORKING PRESSURE: 225 PSIG.
MAXIMUM HYDROSTATIC TEST PRESSURE: 375 PSIG
STUFFING BOX DESIGN
HEAVY DUTY, RUGGED, FACTORY BUILT COMMON BASE PLATE WITH HEAVY DUTY MOTOR
SADDLE ASSEMBLY, BOLTS HOLES AND ACCESS FOR GROUTING.
PUMP ACCESSORIES:
SUCTION AND DISCHARGE GAUGES, DIAL SIZE: 3-1/2”
AUTOMATIC AIR RELEASE VALVE, ¾”.
CASING RELIEF VALVE, ¾”.
CUTTLER HAMMER ELECTRIC FIRE PUMP CONTROLLER MODEL: FD70 WITH THE FOLLOWING FEATURES:
MICROPROCESSOR CONTROL
PRESSURE VOLTAGE AND CURRENT DISPLAY
ALARM & STATUS LED INDICATION
LCD MESSAGE RETRIEVAL
PRESSURE TRANSDUCER- 600 PSI MAX.
ELAPSED TIME METER
NUMBER OF OPERATION COUNTER
RUN PERIOD TIMER
SEQUENTIAL START TIMER
WEEKLY TEST TIMER
COMMON ALARM RELAY & CONTACTS
NEMA-2 ENCLOSURE
NEMA RATED CONTACTORS
EMERGENCY START OPERATOR
PREWIRED TERMINALS FOR REMOTE START, DELUGE VALVE, RELIEF VALVE DISCHARGE, LOW
SUCTION PRESURE & INTERLOCK.
2
STATUS LEDS:
- POWER ON
- PUMP RUNNING
- RPT TIMER
- SEQUENCE TIMER
- LOCAL START
- REMOTE START
- DELUGE VALVE
- INTERLOCK ON
- LOW PRESSURE
ALARM LEDS:
- PHASE REVERSAL
- PHASE FAILURE
- FAIL TO START
- UNDER VOLTAGE
- OVER VOLTAGE
- RELIEF VALVE DISCHARGE
- LOCKED ROTOR TRIP
- LOW SUCTION PRESSURE
- EMERGENCY START
* * * * * * * * * * * * * * * * * * * *
3
FP 2.1
HORIZONTAL MOTOR DRIVEN FIRE PUMPS
PAGE 143
PERFORMANCE RATINGS
JAN 2014
WHEN SHUT OFF HEAD PLUS SUCTION PRESSURE EXCEEDS MAXIMUM ALLOWABLE DISCHARGE PRESSURE PLEASE SPECIFY (H)
INDICATING DUCTILE IRON CONSTRUCTION AND OR 250# FLANGES WHERE APPLICABLE.
ALL PRICES ARE SUBJECT TO PROVISIONS SET FORTH IN OUR LATEST PRICES SUBJECT TO CHANGE WITHOUT NOTICE.
BUSINESS & PRICE POLICY, FP0.1, PAGES 11 THROUGH 14.
PERFORMANCE CURVES FP 2.0
1250 GPM
OCTOBER 2012
Curves show performance with clear water at 85°F. If specific gravity is other than 1.0, BHP must be corrected.
© 2012 Xylem Inc. A-C Fire Pump is a trademark of Xylem Inc. or one of its subsidiaries.
FP 2.1 A-C FIRE PUMP SYSTEMS
Page 312 Dimensions – Horizontal Electric
Motor Driven Fire Pumps
March 08
MOTOR
C MO HB HF HF1 HD HG
FRAME
404 36.40 [925] 10.40 64.00 52.00 26.00 21.25 4.00
405 37.90 [963] [265] [1626] [1321] [661] [540] [102]
444 42.20 [1072] 11.80 76.00 64.00 32.00 23.25 6.00
445 44.20 [1123] [300] [1931] [1626] [813] [591] [153]
NOTES:
1. ALL DIMENSIONS ARE INCHES [mm].
2. SUCTION AND DISCHARGE CONNECTIONS ARE DRILLED PER 125# ANSI B16.1. PUMPS WITH “H” PREFIX HAVE DISCHARGE CONNECTION
DRILLED PER 250# ANSI B16.1. FLANGE HOLES STRADDLE CENTERLINE.
3. BASE PLATE SETTING (BEFORE PIPING), GROUTING PROCEDURES, AND FINAL ALIGNMENT MUST BE IN ACCORDANCE WITH AC FIRE
PUMPS SYSTEMS RECOMMENDED PROCEDURES OUTLINED IN THE INSTRUCTION MANUAL ASSOCIATED WITH THIS PUMP TYPE.
4. MOTOR DIMENSIONS ARE APPROXIMATE FOR A GIVEN NEMA FRAME. CONSULT FACTORY IF SPACE IS LIMITED.
5. BOTH SUCTION AND DISCHARGE PIPES MUST BE SUPPORTED INDEPENDENTLY NEAR THE PUMP TO REDUCE STRAIN ON THE PUMP CASING.
ALSO EXPANSION JOINTS, IF USED, MUST NOT EXERT FORCE ON CASING.
6. COUPLING GUARD MEETS ANSI/OSHA REQUIREMENTS.
7. CONSULT FACTORY FOR BASE MOUNTED CONTROLLER.
LMR PLUS Electric Fire Pump Controllers 1-2
Features
FD70 Reduced Voltage - Wye Delta (Star-Delta) Open Transition June 2010
DATA
PRINT
LAMP
TEST MENU
RESET
SAVE/EXIT
ACK.
99-5816-01
NOTES:
1. Refer to the LMR Plus technical manual for detail and setup
information, as well as programming and custom labelling for
Programmable LED # 1 and Programmable LED # 2.
N. Y. C.
APPROVED
NOTE: As of January 1, 2009 - All Limited Service Controllers will not carry FM Approval.
MD05805096K/C For more information visit: [Link]
LMR PLUS Electric Fire Pump Controllers
Dimensions
FD70 Wye Delta (Star-Delta) Open March 2010
Dimensions
Standard Enclosure - Type NEMA 2, 3R, 4, 4X, 12
LMR
PLU
S
A
17.65 [448] B
3A13357H01
3A13357H01
START
STOP
62.00 [1575]
74.00 [1880]
5.00 [127]
16.00 [406]
PIPING ENTRANCE
1/4" NPT - FEMALE
PIPING ENTRANCE
1/2" NPT - FEMALE
6
1 - START PUSHBUTTON
2 - STOP PUSHBUTTON 14.00
3 - MAIN POWER SWITCH 11.26 [286]
[356]
4 - MSH (EMERGENCY START HANDLE) 1.11 [28]
5 - MAIN LMR PLUS DISPLAY
6 - RECOMMENDED CABLE ACCESS (BOTTOM ONLY)
1.37 [35]
C 1.13 [29]
3.35 [85]
50 - 100 200 - 208V 100,000 Consult Consult 315 41.83 30.25 21.30
60 - 125 220 - 240V Factory Factory (143) (1062) (768) (541)
100 - 200 * 380 - 415V
125 - 250 440 - 480V
125 - 300 550 - 600V 25,000 35,000
125 - 150 200 - 208V 100,000 Consult 420 54.83 43.25 34.30
Factory (190) (1393) (1099) (871)
150 - 200 220 - 240V
250 - 300 * 380 - 415V
300 - 400 440 - 480V
350 - 500 550 - 600V 25,000 35,000
* Coils Available: 380V-50Hz, 380V-60Hz, 415V-50Hz, 415V-60Hz
NOTES:
1. All enclosures finished in FirePump red.
N. Y. C. 2. Cable Entrance bottom only.
APPROVED 3. Standard Enclosure type NEMA 2.
INTERLOCK ON
LOW SUCTION
PUMP START
INPUT #1
INPUT #2
INPUT #3
INPUT #4
INPUT #5
INPUT #6
INPUT #7
INPUT #8
INPUT #9
CUSTOMER INPUTS
COMMON ALARM
(NORMALLY ENERGIZED)
INTERNAL CONNECTIONS
COMMON ALARM
(NORMALLY ENERGIZED)
PHASE FAILURE
(NORMALLY ENERGIZED)
ALARM CONTACTS
PHASE FAILURE
(NORMALLY ENERGIZED)
PHASE REVERSAL
PHASE REVERSAL
FUTURE #1
FUTURE #1
PUMP RUN
PUMP RUN
N. Y. C.
APPROVED
Field Connections
LMR
PLU
S
COMMON ALARM
(NORMALLY ENERGIZED)
COMMON ALARM
(NORMALLY ENERGIZED)
PHASE FAILURE
(NORMALLY ENERGIZED)
ALARM CONTACTS
PHASE FAILURE
(NORMALLY ENERGIZED)
PHASE REVERSAL
PHASE REVERSAL
FUTURE #1 NOTE:
1. MOTOR CONNECTIONS VARY, PLEASE
REFER TO SPECIFIC MOTOR CONNECTION
FUTURE #1 DIAGRAM.
2. PLEASE OBSERVE PROPER PHASE
ROTATION, A,B,C-L1,L2,L3 AS CONTROLLER
IS PHASE SENSITIVE.
PUMP RUN 3. CABLE SIZE TO BE 125% OF FULL LOAD
CURRENT. REFER TO WIRE SIZE TABLE IN
NFPA 70.
PUMP RUN
N. Y. C.
APPROVED
The Silence Alarm button on the membrane will Inputs seven (7) and eight (8) are directly
silence all active alarms when pressed, but has connected to two LED’s on the bottom right on the
no effect on the associated alarm LED(s). If membrane. As well as LED indication and labeling
another alarm condition occurs after the silence area on the membrane, they will each provide an
button has been pressed, the alarm buzzer will output signal from a corresponding SPDT, 8Amp
re-sound until the button is pressed again, or relay.
the alarm condition is satisfied.
Electric Remote
Alarm Panel
LAMP SILENCE
TEST ALARM
N. Y. C.
APPROVED
Dimensions
Standard Enclosure - Type NEMA 1 - Electric Remote Alarm Panel
11.56 [294]
15.49 [393]
9.75 [248]
C US C US
C US LISTED C US LISTED
LR66765 4M95 LR66765 4M95
n 0.27 [n7]x4
WALL MTG. HOLES
4.74 [120]
Approx. Weight
Lbs. (Kg)
10 (4.5)
NOTES:
1. All enclosures finished in FirePump red.
N. Y. C. 2. Cable Entrance either top or bottom.
APPROVED 3. Standard Enclosure type NEMA 1.
N. Y. C.
APPROVED
Typical Specifications
1. Approvals 3. Enclosure
A. The Remote Alarm Panel shall meet the require- A. The panel shall be housed in a NEMA Type-1
ments of the latest edition of NFPA 20 and shall enclosure provided with means for wall mounting.
be listed by [Underwriters Laboratories (UL)]
[Underwriters Laboratories of Canada (ULC)] 4. Input Contacts
approved by [Canadian Standards Association A. Contact inputs shall be dry contact (non pow-
(CSA)] and have MEA approval for New York ered). Each input shall be capable of being se-
City. lected as either normally open (N.O.) or normally
closed (N.C.).
2. Construction
A. The remote alarm panel shall be equipped with a 5. Output Contacts
Lamp Test button which, when operated, fully A. Electric alarm panels shall provide six (6) alarm
tests all LED’s. The Lamp Test Button shall not outputs to indicate Normal Power ON, Supervi-
change the state of internal relays. sory Power ON, Pump Running, Phase Reversal,
B. The panel shall accept both 120 volt 50/60Hz and Phase Failure and Common Alarm.
240 volt 50/60Hz power supply on either of the Diesel alarm panels shall provide six (6) alarm
primary and backup source inputs. The panel outputs to indicate Normal Power ON, Supervi-
shall operate such that if the primary source of sory Power ON, Engine Running, Not in Auto
supply is lost, the panel will automatically switch Mode, Low Fuel, and Common Alarm.
to the backup source. Both the primary and B. (All outputs shall be printed circuit board relay
backup sources shall be independent of each style rated for 8amps / 250VAC. The relays shall
other. be de-energized under normal conditions regard-
C. An audible buzzer shall sound when any alarm less of input status selected.
conditions are present. It shall continue to sound
until either the silence button is pressed, or the 6. Manufacturer
alarm condition is satisfied. A. The panel manufacturer shall manufacture the
D. A silence alarm button shall be provided to si- enclosure and provide completely assembled
lence all active alarms when pressed. It shall units.
have no effect on the associated alarm LED’s. B. The remote alarm panel shall be manufactured
Should a second alarm condition occur after the by Eaton Corporation.
silence button has been pressed, the audible
alarm shall re-sound until the silence button is
pressed again, or the alarm condition has been
satisfied.
E. A Normal Power On LED shall indicate when
normal power is available and shall turn off when
the controller switches to the Supervisory
(backup) power source. An audible alarm shall
sound when normal power is not available and
shall remain ON until normal power is restored,
or the silence button is pressed.
ITEM DESCRIPTION
SUCTION PRESSURE GAUGE, 3.5 DIAL, 3-2-3% ACCURACY,
A
RANGE -30-0-200
DISCARGE PRESSURE GAUGE, 3.5 DIAL, 3-2-3% ACCURACY,
B
RANGE 0-300 PSI
C 1/4" NPT TWO WAY BALL VALVE
4
2 7
6
3
8.375
8 3/8
(212.725)
”
13 34
12 1
10
6.00
11 6 "
(152.400)
17 5
LISTED
28WL
FM
MAX WORKING PRESSURE = 300 PSI APPROVED
WEIGHT = 5 LBS
INLET
1 B O DY 11 O R I FIC E B U TTON
2 CO V E R 12 PIV OT P IN NOTE: 1.00 NPT INLET.
3 LE V E R F RA M E 13 PIN R E TA IN E R (N OT S H OW N )
4 S E AT 14 PIP E P LU G THREADED BUSHINGS
5 F LO AT 17 F L O AT R E TA IN E R PROVIDED FOR SMALLER
6 GASKET 21 L O C ATOR SIZES.
7 CO V E R B O LT 23 SC RE E N E D H OOD
10 F LO AT A RM 34 L O C K WA S H E R
0 to 75 8.5 psi
7.44
20 to 200 28.0 psi
WEIGHT = 6 LBS
1.75
3.50
4.50
FP 2.7 A-C FIRE PUMP SYSTEMS
Page 316 Dimensions - Fire Pump Fittings &
Accessories
August 07
SIZE A B WT
FLOWMETER
A B
VENTURI SYSTEM PIPE METER RANGE MIN.
GPM VENTURI LENGTH
MODEL NO. SIZE & MAX. GPM 150 # (RF) 300 # (RF)
GROOVED BUTT WELD
25 K-25-1-1/4(616) 1-1/4" 12.5-50 Threaded only 3-3/4 (92.25) --- ---
50 K-50-2(685) 2" 25-100 Threaded only 4-1/4 (120.65) --- ---
100 K-100-2-1/2(746) 2-1/2" 50-200 3.00 (76.2) 4.00 (101.6) 9.50 (241.3) 10.00 (254)
150 K-150-3(766) 3" 75-300 3.50 (88.9) 4.38 (111.125) 9.00 (228.6) 10.25 (260.35)
200 K-200-3(766) 3" 100-400 3.50 (88.9) 4.38 (111.125) 9.00 (228.6) 10.25 (260.35)
250 K-250-4(744) 4" 125-500 3.50 (88.9) 3.75 (95.25) 9.50 (241.3) 10.75 (273.05)
300 K-300-4(744) 4" 150-600 3.50 (88.9) 3.75 (95.25) 9.50 (241.3) 10.75 (273.05)
450 K-450-4(744) 4" 225-900 3.50 (88.9) 3.75 (95.25) 9.50 (241.3) 10.75 (273.05)
500 K-500-5(715) 5" 250-1000 5.00 (127) 12.00 (304.8) 13.25 (336.55)
500 K-500-6(743) 6" 250-1000 6.00 (152.4) 13.00 (330.2) 14.25 (361.95)
750 K-750-6(743) 6" 375-1500 6.00 (152.4) 13.00 (330.2) 14.25 (361.95)
1000 K-1000-6(743) 6" 500-2000 6.00 (152.4) 13.00 (330.2) 14.25 (361.95)
1250 K-1250-6(743) 6" 625-2500 6.00 (152.4) 13.00 (330.2) 14.25 (361.95)
1500 K-1500-8(750) 8" 750-3000 7.00 (177.8) 15.00 (381) 16.25 (412.75)
2000 K-2000-8(750) 8" 1000-4000 7.00 (177.8) 15.00 (381) 16.25 (412.75)
2500 K-2500-8(750) 8" 1250-5000 7.00 (177.8) 15.00 (381) 16.25 (412.75)
3000 K-3000-8(750) 8" 1500-6000 7.00 (177.8) 15.00 (381) 16.25 (412.75)
3500 K-3500-10(755) 10" 1750-7000 8.00 (203.2) 16.00 (406.4) 17.75 (450.85)
4000 K-4000-10(755) 10" 2000-8000 8.00 (203.2) 16.00 (406.4) 17.75 (450.85)
4500 K-4500-10(755) 10" 2250-9000 8.00 (203.2) 16.00 (406.4) 17.75 (450.85)
5000 K-2000-12(750) 12" 2500-9000 12.00 (304.8) 21.00 (533.4) 22.75 (577.85)
Factory Mutal Approved.
2" 2-1/2" 3 4 6 8
WEIGHT (lbs) 50 50 80 130 210 270
B-1
3-11
O.S.&Y. RESILIENT WEDGE
GATE VALVES UL / FM
FLANGED ENDS
FIRE PROTECTION PRODUCTS
R-2365-6: O.S.&Y. RESILIENT WEDGE GATE VALVE WITH FLANGE ENDS
• 2-1/2", 3", 4", 6" AND 8" SIZES • RUBBER ENCAPSULATED IRON WEDGE
• MEETS OR EXCEEDS ALL APPLICABLE • ADJUSTABLE PACKING
REQUIREMENTS OF UL 262 AND FM 1120/1130 • HANDWHEEL – OPEN LEFT OR OPEN RIGHT
SPECIFICATIONS AND COMPLIES WITH NSF-61 • 250 PSIG (1379KPA) MAXIMUM WORKING
• DUCTILE IRON BODY WITH MUELLER® PRO-GARD™ PRESSURE - 500 PSIG (2758 KPA) STATIC TEST
FUSION EPOXY COATED INTERIOR & EXTERIOR • EPOXY COATING MEETS OR EXCEEDS ANSI/AWWA
SURFACES C550 AND COMPLIES WITH NSF-61
• OUTSIDE SCREW AND YOKE (O.S.&Y.)
• FLANGED END DIMENSIONS AND DRILLING
Options
Y-5
• STAINLESS STEEL FASTENERS: TYPE 316
• PN10/PN16 DRILLING Y-3
• STAINLESS STEEL STEM: TYPE 304 & 316 Y-4 (not shown)
Y-1
Y-214
Catalog Y-8
Y-3 Hand Wheel Ductile Iron ASTM A536 Grade 65-45-12 Y-23
Y-16 Bonnet Bolts & Nuts Stainless Steel Type 304 Y-218
DIMENSIONS
Size
Dimension* 2-1/2" 3" 4" 6" 8"
A 20.33" 20.16" 23.63" 30.00" 37.37"
AA 16.53" 16.32" 18.94" 23.22" 28.60"
E 7.00" 7.00" 10.00" 12.00" 14.00" A(open)
R 7.00" 7.50" 9.00" 11.00" 13.50" AA(closed)
FF 7.50" 8.00" 9.00" 10.50" 11.50"
UU 5.50" 6.00" 7.50" 9.50" 11.75"
FFF (number and size of holes) 4--.75" 4--.75" 8--.75" 8--.88" 8--.88"
Turns to open 11 11 14 20.5 26.5
Weight (lbs.)* 50 52 76 119 182 FFF
FF
Page B-1-14.2
10SV SERIES
DIMENSIONS AND WEIGHTS AT 60Hz
AT 60Hz,, 2 POLES
10SV01 0,75 80 357 226 263 - - 357 367 121 129 140 155 120 14,3 25,3
10SV02 1,5 90 367 263 268 - - 367 377 137 137 155 178 140 15,6 30
10SV03 2,2 90 399 298 268 - - 399 409 151 137 174 178 140 16,6 33
10SV04 3 100 441 - 288 - - 441 451 - 137 - 178 160 18,4 38
10SV05 4 112 473 - 319 473 259 473 483 - 154 - 197 160 19,3 45,7
10SV06 4 112 505 - 319 505 291 505 515 - 154 - 197 160 20,3 46,6
10SV07 5,5 132 604 - 375 604 323 604 614 - 168 - 214 300 26 63,5
10SV08 5,5 132 636 - 375 636 355 636 646 - 168 - 214 300 26,9 64,5
10SV09 7,5 132 668 - 367 668 387 668 678 - 191 - 256 300 27,9 83,6
10SV10 7,5 132 700 - 367 700 419 - 710 - 191 - 256 300 28,8 84,5
10SV11 7,5 132 732 - 367 732 451 - 742 - 191 - 256 300 29,7 85,5
10SV13 11 160 826 - 428 826 515 - 836 - 191 - 256 350 34,4 105
10SV15 11 160 890 - 428 890 579 - 900 - 191 - 256 350 36,3 107
10sv-2p60_b_td
34
10SV SERIES
OPERA TING CHARACTERISTIC
OPERATING CHARACTERISTICSS AT 60Hz, 2 POLES
AT
10SV ∼ 3500 [rpm] ISO 9906 - Annex A
0 10 20 30 40 50 60 Q [Imp
70gpm]
0 10 20 30 40 50 60 70 Q
80[US gpm]
280
900
H [m]
H [ft]
260 15
800
240
13
220
700
200
11
180 600
10
160
09 500
140 08
120 07 400
100 06
300
05
80
04
60 200
03
40
02 100
20 01
0 0
1.0 80
Pp [kW]
η
η [%]
0.8 60
0.6 40
kW/stage
0.4 20
4
NPSH [m]
NPSH [ft]
10
2
5
0 0
05943_B_CH
3
0 2 4 6 8 10 12 14 16 18 Q [m20
/h]
35
XT SERIES Jockey Pump Controllers 1-1
Features
XT Series Jockey Pump Controllers March 2012
The XT Series of Jockey Pump Controllers Eaton's XTJP and XTJY series of jockey pump
incorporate Eaton’s XT Power Controls which controllers are supplied standard with an 1/8 DIN,
are designed for the global marketplace. The NEMA 4X digital panel meter that displays current
XT controls carry global ratings, are small in pressure and hi and low setpoints on a 4-digit,
size and are available in a wide variety of superbright LED display. Pressure input is
operating voltages. They are easy to install provided by a 4-20mA pressure sensor.
and maintain, due to their modular, plug-in
design.
All jockey pump controllers are wired with a Enclosures have an oven baked powder paint
120V control power transformer as standard. finish and are supplied with NEMA 2 rating,
unless otherwise ordered. Available options
include: NEMA 3R, 4, 4X, 12.
Technical Data
Product Description
ACROSS-THE-LINE (Direct On Line) JOCKEY PUMP CONTROLLERS
ACROSS THE LINE
Line Voltage
JOCKEY PUMP CONTROLLERS
200 - 208V 220 - 240V 380 - 415V 440 - 480V 550 - 600V 120V 1 ph 240V 1 ph
The XTJP jockey pump controllers operate
across-the-line. Full voltage is applied to the
motor for starting by the use of a single motor Motor Horsepower
starter. Starting inrush current is approximately
600% of rated full load amperes. 1/3 - 15Hp 1/3 - 40Hp 1/3 - 50Hp 1/3 - 50Hp 1/3 - 50Hp 1/3 - 5Hp 1/3 - 10Hp
WYE-DELTA (Star-Delta)
JOCKEY PUMP CONTROLLERS
When six or twelve-lead delta connected WYE-DELTA (Star-Delta) JOCKEY PUMP CONTROLLERS
jockey pump motors are started wye (star)
connected, approximately 58% of line voltage Line Voltage
is applied to each winding. The motor
develops 33% of full-voltage starting torque 200 - 208V 220 - 240V 380 - 415V 440 - 480V 550 - 600V
and draws 33% of normal locked-rotor current
from the line. After an adjustable time delay
(during which the motor accelerates), it is Motor Horsepower
reconnected for normal operation. 1/3 - 15Hp 1/3 - 40Hp 1/3 - 50Hp 1/3 - 50Hp 1/3 - 50Hp
(0.74 - 11.03KW) (0.74 - 29.42KW) (0.74 - 36.78KW) (0.74 - 36.78KW) (0.74 - 36.78KW)
Product Features
Combination Motor Controllers
N. Y. C.
APPROVED
Sealed Rotary Handle Mechanism
Dimensions
Standard Enclosure - Type NEMA 2 - Jockey Pump Controller
10.75
[273]
16.13 8.00
[410] [203]
Ø 0.27 [Ø7] x4
WALL MTG. HOLES
1
2
3
13.00 16.35
4
[330] [415]
NOTES:
1 - ISOLATION SWITCH
2 - HAND/OFF/AUTO SWITCH PIPING ENTRANCE 8.59
3 - DOOR LATCH 8.08 1/4" NPT - FEMALE [218]
4 - DIGITAL DISPLAY [205]
2.13
[54]
Dimensions in inches and [millimeters] 4.03
[102]
200 - 208V 220 - 240V 380 - 415V 440 - 480V 550 - 600V
Motor Hp Withstand Motor Hp Withstand Motor Hp Withstand Motor Hp Withstand Motor Hp Withstand
Rating (kA) Rating (kA) Rating (kA) Rating (kA) Rating (kA)
0.33 - 3 65 0.33 - 3 65 0.33 - 5 65 0.33 - 7.5 65 0.33 - 10 18
4 50 4 50 7.5 - 10 18 10 50
5 - 10 18 5 - 10 18 15 - 20 18
N. Y. C.
Pending
APPROVED
Dimensions
Standard Enclosure - Type NEMA 2 - Jockey Pump Controller with Options
16.38
21.76 [416]
[553]
13.00
[330]
Ø 0.27 [Ø7] x4
WALL MTG. HOLES
1
2
3
16.00 21.15
[406] [537]
4
NOTES:
1 - ISOLATION SWITCH
2 - HAND/OFF/AUTO SWITCH PIPING ENTRANCE 8.60
8.08 1/4" NPT - FEMALE
3 - DOOR LATCH [218]
[205]
4 - DIGITAL DISPLAY
2.63
Dimensions in inches and [millimeters] [67] 3.96
[101]
200 - 208V 220 - 240V 380 - 415V 440 - 480V 550 - 600V
Motor Hp Withstand Motor Hp Withstand Motor Hp Withstand Motor Hp Withstand Motor Hp Withstand
Rating (kA) Rating (kA) Rating (kA) Rating (kA) Rating (kA)
0.33 - 3 65 0.33 - 3 65 0.33 - 5 65 0.33 - 7.5 65 0.33 - 10 18
4 50 4 50 7.5 - 10 18 10 50
5 - 10 18 5 - 10 18 15 - 20 18
N. Y. C.
Pending
APPROVED
N. Y. C.
APPROVED
N. Y. C.
APPROVED
XTJP
XTJY
N. Y. C.
APPROVED
Optional Enclosures
1. NEMA 3R (IEC IP14) rain-tight enclosure.
2. NEMA 4 (IEC IP66) watertight enclosure.
3. NEMA 4X (IEC IP66) watertight 304 stainless steel
enclosure.
4. NEMA 4X (IEC IP66) watertight 316 stainless steel
enclosure.
5. NEMA 4X (IEC IP66) watertight corrosion resistant
enclosure.
6. NEMA 12 (IEC IP52) dust-tight enclosure.
Fire Pumps
Series 8100
ACFP 8100-05
Series 8100
Basic Construction
Part Name Cast Iron, Bronze Fitted
Pipe Plugs (Casing) Brass
Flush Piping Copper
Pins (Sleeves) 302 Stainless Steel
Packing Glands Bronze (ASTM B584-932)
Packing (Rings) Graphite Impregnated Acrylic Yarn
Casing Assembly Cast Iron (ASTM a48 Class 35A)*
Casing Joint Gasket (Suction) Paper (Vellumoid 505)
Casing Joint Gasket (Discharge) Paper (Vellumoid 505)
Casing Joint Bolts Steel (Grade 5)
Dowel Pins (Casing) Steel
Casing rings Bronze (ASTM B584-932)
Shaft Steel (SAE 1045)
Pump Size
Shaft Sleeves Bronze (ASTM B584-932)
3x2x11F-S
Shaft Sleeve Nuts Bronze (ASTM B584-932)
6x4x9F
Bearing Housing (Inboard) Cast Iron (ASTM a48 Class 25A)
6x4x10F-M
Bearing Housing (Outboard) Cast Iron (ASTM a48 Class 25A)
6x4x11F
Ball Bearing (Inboard) Steel
6x4x12F-M
Ball Bearing (Outboard) Steel
6x6x9F
Stuffing Boxes (Packing) Cast Iron (ASTM a48 Class 25A)
8x6x9F
Deflectors Rubber (Buna “N”)
8x6x10F
Lip Seals (Bearing) Rubber (Buna “N”)
8x6x12F-S
Locknut (Bearing) Steel
8x6x12F-M
Lockwasher (Bearing) Steel
8x6x13F
Set Screws 316 Stainless Steel
8x6x18F
Cap Screw (Bearing Housing) Steel (Grade 2)
8x8x12F
Cap Screw (Gland) Steel (Grade 2)
8x8x17F
Grease Fittings (Bearing) Steel
10x8x17F-S
Pipe Plugs (Bearing Housing) Steel
10x8x17F-L
Key (Impeller) Steel
10x8x20F-S
Key (Coupling) Steel
10x8x20F-L
O-ring (Stuffing Box) Rubber (Buna “N”)
12x10x18F
O-ring (Casing) Rubber (Buna “N”)
O-ring (Shaft Sleeve) Rubber (Buna “N”)
= Pumps that use Steel (SAE 4140) shafts. Spirol Pins (Stuffing Box) 304 Stainless Steel
= Pumps that use TFE Impregnated
Spirol Pins (Casing Ring) 304 Stainless Steel
Acrylic Yarn
* = Casings for pump sizes with “H” prefix Impeller Bronze (ASTM B584-876)
will be made from Ductile Iron (ASTM Seal Cage Teflon
A536 Grade 65-45-12) & Casing Joint
Bolts will be Steel (Grade 8).
Xylem, Inc.
8200 N. Austin Avenue
Morton Grove, Illinois 60053
Phone: (847) 966-3700
Fax: (847) 965-8379
[Link]/brands/acfirepump
e-SV Series
TM
800
200
600
400
100
200
0 0
06052_B_CH
1 10 100 Q [m3/h]
extra efficient
The e-SVTM’s newly-designed hydraulics, combined with a high-efficiency motor (IE2)
deliver maximum efficiency.
energy saving
Pumps are among the largest users of industrial energy. Do your part to reduce CO2
emissions and your impact on the environment - and improve your bottom line - by
taking advantage of the new e-SVTM’s lower energy requirement. Use a new e-SVTM pump
along with a variable speed drive such as ITT’s Hydrovar®, and save even more energy
and money.
easy to maintain
The e-SVTM’s new design allows removal of the mechanical seal without having to remove
the motor, reducing repair time by up to 50%.
A standard DIN mechanical seal, wearing components, service tools and standard IEC
motors enable faster and easier maintenance and servicing.
Lowa
Benefits
The e-SVTM range of pumps features 11 models, and can be specially confi
for a wider range of applications. The line is interchangeable with Lowar
series of vertical multi-stage pumps for added flexibility in meeting pu
requirements. Additionally, five e-SVTM manufacturing facilities arou
world provide shorter lead times and faster service.
Applications
Water supply and pressure boosting
Water treatment
Light industry
Head up to 330 m
Specifications
Maximum operating pressure PN25-40 for sizes 1-22SV; PN16, PN25, PN40 for sizes 33-125
Temperature of pumped liquid -30°C to +120°C standard version / up to 150°C in “hot water design”
Protection IP55
Insulation class F
Combination with Hydrovar® and other VFDs (on pumps and Booster Packages)
Lowara
e-SV Series
TM
From:
George El-Hani
International Sales & Marketing
EMEA
This is to certify that ITT A-C Products are under warranty for 12 months
from the date of testing & commissioning.
We thank you for your understanding and for choosing ITT A-C products.
From:
George El-Hani
International Sales & Marketing
EMEA
This is to certify that ITT A-C Products are produced in the United States of
America by ITT A-C Company. The ITT A-C Company does hereby certify that
the ITT A-C product (s) are of our manufacture and in full compliance with all
test, calibration, and inspection specifications of the ITT A-C company quality
assurance program.
We thank you for your understanding and for choosing ITT A-C products.
Locations
Head Office ……………………………………………………… 4
Branches and Managed Operations………………………………. 4-6
Agents …………………………………………………………... 6
Products
HVAC Equipment ………………………………………………. 7-8
Fire Fighting Equipment ………………………………………... 9-10
Industrial Equipment ……………………………………………. 11-12
Marketing
Exhibitions ……………………………………………………… 13
Seminars ………………………………………………………… 13
Awards Received ………………………………………………… 14
Services
At Tendering ……………………………………………………. 15
When Order is Placed …………………………………………... 15
After Delivery to Site …………………………………………… 15
Software
In - House Developed Software ………………………………… 16
2
Morex, Inc. Overview
Introduction
Morex, Inc.’s expertise is in international marketing and its service the Middle
East region.
Mission Statement
Our commitment is to supply the best Engineered products in the industry. Our
goal is to continuously expand our market coverage while maintaining the quality
of service we provide our suppliers and customers. Our facilities and staff of
multilingual professionals, together with our managed operations and agents in the
Middle East, maintain our reputation as one of the leading companies in our field.
3
Locations
Head Office
Our head office and 10,000 square foot warehouse are located in Charlotte, North
Carolina:
Morex, Inc. achieves effective Middle East coverage in high business volume
markets by establishing branches or managed operations under the sponsorship of
prominent local companies. These operations are located as follows:
x Amman, Jordan
Morex, Inc. - Jordan
P.O. Box 142531
Amman 11844, Jordan
Tel :(011)-962-6582-2740
Fax:(011)-962-6582-2742
E-Mail: jordanoffice@[Link]
Mr. Subhi Souri, branch manager
x Riyadh
A.S.E.M. / Morex, Inc.
P.O. Box 235
Riyadh 11371, Saudi Arabia
Tel :(011)-966-1-473-0030
Fax:(011)-966-1-472-2875
E-Mail: asemryd@[Link]
Mr. Majdi Hakim, branch manager
4
Locations (Cont’d)
x Jeddah
A.S.E.M./ Morex, Inc
P.O. Box 118189
Jeddah 21312, Saudi Arabia
Tel:(011)-966-2-6510124
Fax:(011)-966-2-6516445
E-Mail: asemjed@[Link]
Mr. Fuad Hussein, branch manager
x Al Khobar
A.S.E.M./ Morex, Inc
P.O. Box 20843
Al-Khobar 31952, Saudi Arabia
Tel :(011)-966-3-864-5357
Fax:(011)-966-3-897-0602
E-Mail: asemkbr@[Link]
Mr. Ali Haidar, branch manager
x Kuwait
Atlas Blue General Trading & Cont. Est /Morex, Inc
P.O. Box 2914
Safat 13030, Kuwait
Tel :(011)-965-241-8547
Fax:(011)-965-240-7910
E-Mail: atlas@[Link]
Mr. Hussam Bashir, branch manager
x Iraq
Morex International
P.O. Box 3054, Al-Ilweiya
Baghdad, Iraq
Tel:(011)-964-718-1194
Fax:(011)-964-717-5591 E-Mail: iraqoffice@[Link]
Mr. Shlimon Zaya, branch manager
5
x Pakistan
Morex Inc. - Pakistan
Suite:707 Anum Blessing, Block 7/8 [Link], KCHS
Shahrah-e-faisal, Karachi - Pakistan
Tel:(011)-92-21-432-5270
Fax:(011)-92-21-432-5271 E-Mail: karachioffice@[Link]
Mr. Junaid Alam, branch manager
Agents
Locations in the Middle East where we have not established branch offices or our
own managed operations are covered through agents that distribute some of our
products in specific regions. These companies were selected for their excellent
market penetration and their involvement with the HVAC and fire fighting
business for many years and are well connected with the business community and
local Government.
These agents are located in Egypt, Lebanon, United Arab Emirates and Bahrain. A
list of their names and addresses is available upon request.
6
Products
HVAC Equipment
x Ormandy
Storage type Water Calorifiers – Copper Lining.
x Vent-Axia
Twin Fans, Plastic Propeller Wall and Ceiling
Fans.
7
Products (HVAC Equipment Cont’d)
x Anemostat
Grille, Registers and Diffusers, VAV Boxes.
8
Products
x Mueller Co.
x United Brass Co.
x Sure-Test
UL Listed and FM approved all types of Fire
Protection Valves, Fire Hydrants, Gate Valves,
IBBM Gate Valves, Check Valves, Tapping
Material and Post Indicators, Inspectors Test
& Drain, “Y” Strainers.
9
Products (Fire Fighting Cont’d)
x Potter Electric
UL Listed and FM approved Sprinkler
Monitoring Devices, Flow Switches, Pressure
Switches, Bells, Tamper and Supervisory
Switches and Releasing Panels.
10
Products
Industrial Equipment
x Pennram Diversified
Manufacturing Corp.
Incinerators for Municipal, Medical, Liquid
Waste, Pathological and Industrial
Applications.
x LFG&E International
Specializing in Design Solutions for Landfill
Gases and Manufacturing of Landfill Gas
Power Generation.
11
Marketing
Seminars
We conduct seminars for engineers
and contractors to introduce new
products and/or technology.
(Picture of seminar
conducted in joint
participation with ITT Bell &
Gossett to introduce the
Variable Speed Pumps in
Riyadh, Saudi Arabia)
Exhibitions
Morex, Inc. regularly Participates in
exhibitions in the Middle East
jointly with our sponsors and agents.
(Picture of exhibition in
Riyadh, Saudi Arabia)
13
Marketing (Cont’d)
Awards
As a result of our successful
marketing, Morex, Inc has earned
numerous awards through the years
for highest sales achievement from
our vendors.
List of Awards
14
Services
At Tendering:
x Prompt handling of all
quotations requests.
x Complete technical
submittals.
x Storage of equipment at no
additional charge.
x Equipment consolidation to
minimize shipping costs.
x Export crating.
x Equipment inspection.
x Export documentation.
x Product warranty.
15
Software
In - House Developed
Software
16
Projects
Morex, Inc has supplied Engineered Products to a very large number of projects.
Following is a partial list of the projects supplied.
17
Projects (Cont’d)
18
Projects (Cont’d)
19
The use of a jockey pump alongside the main fire pump provides several advantages in fire pump systems. It helps maintain the system's pressure, compensating for small leaks and ensuring the main fire pump is not unnecessarily activated. A jockey pump's presence ensures the main fire pump operates efficiently and prolongs its lifespan by reducing unnecessary wear. It is vital for maintaining steady pressure in the fire protection system, readying the system for high-demand scenarios without triggering the main pump .
LED indicators are essential in fire pump systems for real-time monitoring and diagnostics. They visually alert operators to conditions such as phase reversal, phase failure, common alarms, and pump operation states. LEDs provide instant feedback, enabling quick response to malfunctions or issues that require attention. This immediate visibility contributes significantly to operational safety by ensuring any anomalies can be swiftly identified and addressed, minimizing risks associated with system failures .
The Xylem A-C Series 8100 fire pump is designed with a dynamically balanced, enclosed double-suction impeller made of bronze, a cast iron casing with a suction and discharge gauge ports, and heavy-duty base mounts for stability. It uses grease-lubricated steel bearings and features a stuffing box design, ensuring efficient performance under exigent conditions. The use of materials like ASTM A48 Class 25A and ASTM B584 for different components adds to the pump's robustness and reliability in fire safety applications .
The fire pump components are constructed from durable materials such as ASTM A48 Class 35A cast iron for the casing assembly, ASTM B584-875 bronze for the impeller, and alloy steel SAE 1045 for the shaft. These materials are chosen for their strength and corrosion resistance, ensuring long operational life and adherence to safety standards such as NFPA-20, UL, and FM. They provide the necessary balance between structural integrity and the ability to withstand high-pressure conditions .
The inclusion of a pressure transducer in a jockey pump controller enhances its functionality by allowing precise control over the start and stop pressures. It provides solid-state accuracy in pressure readings, directly influencing the system to maintain the desired pressure levels more efficiently. This real-time adaptability is crucial for pressure adjustments in increments as fine as 1 PSI, ensuring the entire fire suppression system consistently operates at optimal levels .
Remote alarm panels play a critical role in maintaining fire pump safety by providing audible and visual alerts for various conditions, such as power failure and common alarms. These panels are microprocessor-controlled and allow for real-time monitoring and response to the pump system's operational status. Features like the lamp test button and the silence alarm button ensure the ongoing functionality of alarms without altering their configurations, ensuring that any operational anomalies are promptly reported even if not under constant supervision .
The fire pump control system uses a Cutler Hammer Electric Motor Driven Controller equipped with interlock and shutdown circuits managed by a digital display system. It includes features such as automatic or manual reset, LED functionality testing, and pressure sensor adjustments via a 4-20mA sensor with increments of 1 PSI. The system supports three standard languages and provides customizable future inputs/outputs, enhancing operational efficiency and safety by accommodating various alarm scenarios and user-selected settings .
The fire pump controller offers both manual and automatic system resets to ensure that the pump can be adjusted quickly to safe operating conditions. Automatic resets allow for uninterrupted operation when transient conditions normalize, reducing downtime. Manual resets provide a safeguard by requiring human intervention to verify and resolve persistent issues, ensuring safety through deliberate oversight. These provisions are important as they balance operational efficiency with safety concerns, enabling quick recovery and the ability to address any underlying issues .
Key construction elements that ensure the robustness and reliability of the fire pump include the use of ASTM A48 Class 35A cast iron for casing assembly, interconnected by dynamically balanced impellers, bronze ASTM B584 for important components like the impeller and sleeve, and grease-lubricated steel bearings. The solid construction allows it to withstand high pressures, minimize wear, and facilitate easier maintenance .
The Xylem A-C Series 8100 fire pump has a flow capacity of 1250 GPM and a head of 185 PSI. It is manufactured from materials such as cast iron, bronze, and steel, ensuring durability and performance. This series is UL-listed, FM-approved and meets NFPA-20 standards, supporting not less than 150% of rated capacity at a pressure not less than 65% of rated pressure. The pump's shut-off pressure does not exceed 120% of rated pressure, and it has a maximum working pressure of 225 PSIG, with a hydrostatic test pressure of up to 375 PSIG .