15-May-14

PROJECT: THE EXTENSION OF THE HARAM


AND SURROUNDING ELEMENTS

SUBMITTAL FOR FIRE PUMP FOR SHAMIYAH


TEMPORARY WORKS RAMADAN SCOPE(1435)

CONTRACTOR: SBG - ABCD SUBMITTED BY: ASEM (MOREX)


INDEX
S# Summary

1 REF # ElECTRIC MOTOR DRIVEN FIRE PUMP


A) Pump Selection Table & Performance Curve
B) Dimensional Drawing & Engineering Data
C) General Information and Pump Controller
D) Pump Controller Information

2 FIRE PUMP ACCESSORIES

3 TAG # (JOCKEY PUMP)


A) Pump Submittal sheet &Performance Curve
B) Pump Details & Dimensional Details
C) Jockey Pump Controller

4 CATALOG
AC FIRE PUMP
LOWARA JOCKEY PUMP 

5 COUNTRY OF ORIGIN

6 WARRANTY CERTIFICATE

7 COMPANY PROFILE
UL LISTED / FM APPROVED / NFPA-20
REF # XYLEM A-C ELECTRIC MOTOR-FIRE PUMPS)
DOUBLE SUCTION HORIZONTAL SPLIT CASE FIRE PUMP DATA
PUMP DATA:
FLOW : 1250 GPM
HEAD : 185 PSI
MANUFACTURER : XYLEM A-C – U.S.A.
SERIES : 8100
MODEL : 8 X 6 X 12F-M
SUCTION SIZE : 8”
DISCHARGE SIZE : 6”

MOTOR DATA:
HORSE POWER : 250 HP
RPM : 3555
START : WYE DELTA START
ENCLOSURE : ODP
INSULATION : CLASS – F
AMBIENT : 40°C AMBIENT
POWER SUPPLY : 400V/3/60
FRAME SIZE : 445T
SERVICE FACTOR : 1.15

CONSTRUCTION MATERIAL:
 ASTM A48 CLASS 35A CAST IRON CASING ASSEMBLY WITH SUCTION & DISCHARGE GAUGE PORTS,
ENEWABLE BRONZE CASING WEAR RINGS, COPPER SEAL FLUSH CONNECTION, DRAIN PLUG,
FLANGED SUCTION & DISCHARGE ENDS.
 ASTM B584-875 BRONZE IMPELLER, FULLY ENCLOSED, DOUBLE SUCTION, DYNAMICALLY
BALANCED & KEYED TO SHAFT.
 ALLOY STEEL SAE 1045 SHAFT.
 BRONZE ASTM B584-932 SHAFT SLEEVES.
 BRONZE ASTM B584-932 CASING RINGS.
 CAST IRON STUFFING BOX.
 STEEL IMPELLER KEY.
 BRONZE (ASTM B584-932) PACKING GLANDWITH FIVE (5) RINGS OF GRAPHITE IMPREGNATED
ACRYLIC YARN PACKING (RINGS).
 ASTM A48 CLASS 25A CAST IRON BEARING HOUSING.
 GREASE LUBRICATED STEEL BEARINGS – REPLACEABLE.
 FLEXIBLE COUPLED WITH ANSI/OSHA COMPLIANT COUPLER GUARD.
 FABRICATED HEAVY DUTY RUGGED STEEL BASEPLATE.

1
SPECIFICATIONS:
XYLEM A-C SERIES: 8100, MADE IN U.S.A, UL-LISTED, FM-APPROVED FIRE PUMPS, MANUFACTURED
IN COMPLIANCE WITH NFPA-20 WITH THE FOLLOWING FEATURES:
 HORIZONTAL SPLIT CASE, BASEMOUNTED, DOUBLE SUCTION, SINGLE STAGE CENTRIFUGAL
PUMP.
 HEAVY DUTY FLEXIBLE COUPLER EMPLOYED BETWEEN PUMP & MOTOR.
 ANSI / OSHA COMPLIANT HEAVY DUTY STEEL COUPLING GUARD
 DYNAMICALLY BALANCED ENCLOSED TYPE IMPELLER.
 THE PUMP SHALL DELIVER NOT LESS THAN 150% OF THE RATED CAPACITY AT A PRESSURE NOT
LESS THAN 65% OF THE RATED PRESSURE, THE SHUT-OFF PRESSURE SHALL NOT EXCEED 120% OF
THE RATED PRESSURE.
 HORIZONTAL SUCTION & DISCHARGE.
 THE CASING MAXIMUM WORKING PRESSURE: 225 PSIG.
 MAXIMUM HYDROSTATIC TEST PRESSURE: 375 PSIG
 STUFFING BOX DESIGN
 HEAVY DUTY, RUGGED, FACTORY BUILT COMMON BASE PLATE WITH HEAVY DUTY MOTOR
SADDLE ASSEMBLY, BOLTS HOLES AND ACCESS FOR GROUTING.

PUMP ACCESSORIES:
 SUCTION AND DISCHARGE GAUGES, DIAL SIZE: 3-1/2”
 AUTOMATIC AIR RELEASE VALVE, ¾”.
 CASING RELIEF VALVE, ¾”.

ELECTRIC MOTOR DRIVEN FIRE PUMP CONTROL PANEL:


“CUTLER HAMMER” ELECTRIC MOTOR DRIVEN FIRE PUMP CONTROLLER,
UL-LISTED, FM-APPROVED, MODEL FD-70, USES A METHOD OF CONNECTING
THE PUMP MOTOR WINDINGS INTO WYE CONFIGURATION TO START, THEN
SWITCHING TO A DELTA CONFIGURATION TO RUN, THIS REDUCES THE
STARTING CURRENT OF THE MOTOR SIGNIFICANTLY, WYE-DELTA STARTING
IS THE ONLY METHOD THAT HAS A STARTING TORQUE EFFICIENCY OF
100%. THE FD70 CAN BE PROGRAMMED FOR EITHER FULLY AUTOMATIC OR
SEMI-AUTOMATIC OPERATION

CUTTLER HAMMER ELECTRIC FIRE PUMP CONTROLLER MODEL: FD70 WITH THE FOLLOWING FEATURES:
 MICROPROCESSOR CONTROL
 PRESSURE VOLTAGE AND CURRENT DISPLAY
 ALARM & STATUS LED INDICATION
 LCD MESSAGE RETRIEVAL
 PRESSURE TRANSDUCER- 600 PSI MAX.
 ELAPSED TIME METER
 NUMBER OF OPERATION COUNTER
 RUN PERIOD TIMER
 SEQUENTIAL START TIMER
 WEEKLY TEST TIMER
 COMMON ALARM RELAY & CONTACTS
 NEMA-2 ENCLOSURE
 NEMA RATED CONTACTORS
 EMERGENCY START OPERATOR
 PREWIRED TERMINALS FOR REMOTE START, DELUGE VALVE, RELIEF VALVE DISCHARGE, LOW
SUCTION PRESURE & INTERLOCK.

2
STATUS LEDS:
- POWER ON
- PUMP RUNNING
- RPT TIMER
- SEQUENCE TIMER
- LOCAL START
- REMOTE START
- DELUGE VALVE
- INTERLOCK ON
- LOW PRESSURE

ALARM LEDS:
- PHASE REVERSAL
- PHASE FAILURE
- FAIL TO START
- UNDER VOLTAGE
- OVER VOLTAGE
- RELIEF VALVE DISCHARGE
- LOCKED ROTOR TRIP
- LOW SUCTION PRESSURE
- EMERGENCY START

 MANUFACTURER’S FACTORY PUMP TEST CURVES FOR EACH PUMP SHALL BE


PROVIDED ALONG WITH THE PUMPS.

* * * * * * * * * * * * * * * * * * * *

3

FP 2.1
HORIZONTAL MOTOR DRIVEN FIRE PUMPS
PAGE 143
PERFORMANCE RATINGS

JAN 2014

SUPERSEDES ALL PREVIOUS ISSUES


1250 GPM

RATED PSI PUMP SIZE SERIES RPM MOTOR HP MAX HP UL FM
125 8x6x12F-M 8100 3555 150 147 x x
8x6x10F 8100 3550 150 156 x x
130 8x6x12F-M 8100 3555 150 157 x x
8x6x10F 8100 3550 150 160 x x
135 8x6x12F-M 8100 3555 150 168 x x
8x6x10F 8100 3550 150 165 x x
140 8x6x12F-M 8100 3555 200 178 x x
8x6x10F 8100 3550 200 177 x x
145 8x6x12F-M 8100 3555 200 189 x x
150 8x6x12F-M 8100 3555 200 200 x x
155 8x6x12F-M 8100 3555 200 211 x x
160 8x6x12F-M 8100 3555 200 222 x x
165 8x6x12F-M 8100 3555 250 233 x x
170 8x6x12F-M 8100 3555 250 255 x x
175 8x6x12F-M 8100 3555 250 255 x x
180 8x6x12F-M 8100 3555 250 267 x x
185 8x6x12F-M 8100 3555 250 278 x x
190 8x6x12F-M 8100 3555 300 290 x x
195 8x6x12F-M 8100 3555 300 302 x x
200 8x6x12F-M 8100 3555 300 314 x x
205 8x6x12F-M 8100 3555 300 326 x

 WHEN SHUT OFF HEAD PLUS SUCTION PRESSURE EXCEEDS MAXIMUM ALLOWABLE DISCHARGE PRESSURE PLEASE SPECIFY (H)
INDICATING DUCTILE IRON CONSTRUCTION AND OR 250# FLANGES WHERE APPLICABLE.

ALL PRICES ARE SUBJECT TO PROVISIONS SET FORTH IN OUR LATEST PRICES SUBJECT TO CHANGE WITHOUT NOTICE.
BUSINESS & PRICE POLICY, FP0.1, PAGES 11 THROUGH 14.
PERFORMANCE CURVES FP 2.0

1250 GPM
OCTOBER 2012

SUPERSEDES ALL PREVIOUS ISSUES

Curves show performance with clear water at 85°F. If specific gravity is other than 1.0, BHP must be corrected.

© 2012 Xylem Inc. A-C Fire Pump is a trademark of Xylem Inc. or one of its subsidiaries.
FP 2.1 A-C FIRE PUMP SYSTEMS
Page 312 Dimensions – Horizontal Electric
Motor Driven Fire Pumps
March 08

Supersedes all previous issues

(H)8x6x12F-M – 8100 SERIES

MOTOR
C MO HB HF HF1 HD HG
FRAME
404 36.40 [925] 10.40 64.00 52.00 26.00 21.25 4.00
405 37.90 [963] [265] [1626] [1321] [661] [540] [102]
444 42.20 [1072] 11.80 76.00 64.00 32.00 23.25 6.00
445 44.20 [1123] [300] [1931] [1626] [813] [591] [153]

447 47.60 [1210]

NOTES:
1. ALL DIMENSIONS ARE INCHES [mm].
2. SUCTION AND DISCHARGE CONNECTIONS ARE DRILLED PER 125# ANSI B16.1. PUMPS WITH “H” PREFIX HAVE DISCHARGE CONNECTION
DRILLED PER 250# ANSI B16.1. FLANGE HOLES STRADDLE CENTERLINE.
3. BASE PLATE SETTING (BEFORE PIPING), GROUTING PROCEDURES, AND FINAL ALIGNMENT MUST BE IN ACCORDANCE WITH AC FIRE
PUMPS SYSTEMS RECOMMENDED PROCEDURES OUTLINED IN THE INSTRUCTION MANUAL ASSOCIATED WITH THIS PUMP TYPE.
4. MOTOR DIMENSIONS ARE APPROXIMATE FOR A GIVEN NEMA FRAME. CONSULT FACTORY IF SPACE IS LIMITED.
5. BOTH SUCTION AND DISCHARGE PIPES MUST BE SUPPORTED INDEPENDENTLY NEAR THE PUMP TO REDUCE STRAIN ON THE PUMP CASING.
ALSO EXPANSION JOINTS, IF USED, MUST NOT EXERT FORCE ON CASING.
6. COUPLING GUARD MEETS ANSI/OSHA REQUIREMENTS.
7. CONSULT FACTORY FOR BASE MOUNTED CONTROLLER.
LMR PLUS Electric Fire Pump Controllers 1-2
Features
FD70 Reduced Voltage - Wye Delta (Star-Delta) Open Transition June 2010

Product Features Firmware Update Language


Firmware revisions are updated from an The language sub-menu allows the user to select
Main Display external USB drive. All previously programmed English, French, Spanish or Other languages to
General settings will remain intact when updating is be viewed on the LCD Display. Several other
The main display will show the current system completed. Should there be an update failure, languages can be uploaded into the controller.
pressure, time and date, voltage and amps the controller will automatically revert back to Contact the factory for details.
reading for all three phases, the system the previous version of firmware.
frequency and any custom messages, alarms Regional
or timers. Embedded Webpage Regional settings include the ability to program
General the date by adjusting the Month, Day, Year and
The embedded webpage is a multifunction tool Day of Week. As well, the Current Time can be
that will allow the user to view the current status adjusted on the 24 hour clock.
of the controller as well as display all current
readings, set points, Pressure
and history. An external A variety of pressure settings can be
computer can be programmed in the pressure sub-menu. These
connected via the settings include disabling the pressure
Programmed Set-Point Ethernet port to transmitter; setting of the start point, stop point,
The set-point display will show programmed access the page. low pressure alarm, high pressure alarm, stop
pressure start point, pressure stop point and When connected, mode, proof pressure switch (for foam units), low
weekly test timer setting. the controller set suction shutdown (low foam interlock), pressure
points can be deviation and hourly pressure recording. Refer to
Statistics programmed the LMR Plus operation manual IM05805020K
The statistics display will allow the user to via the webpage. for details.
scroll through all of the measured statistics
stored in memory. Refer to LMR Plus operation Timers
manual IM05805020K for specific details. Multiple Pages Timers in the LMR Plus that can be programmed
There are 5 viewable pages that show the Main include: Run Period Timer (RPT), RPT Start
Diagnostics Display, Statistics, Diagnostics, History and Mode, Acceleration Timer (AT), Weekly Test
The diagnostics display allows the user to Programmed Set Points. Timer, Fail to Start Timer (FST) and Sequential
scroll through various diagnostic points to Start Timer (SST). Refer to the LMR Plus
assist with troubleshooting the system. Pressure Points operation manual IM05805020K for details.
The pressure reports recorded in memory can
be graphed and/or sorted based on date and Alarm Set Points
Message History
time. There are five settable alarm points that can be
The user will be able to scroll through all of the
programmed by the user. They include: Phase
messages stored in the memory of the
Programmed Set Points Rotation, Over Voltage (OV), Under Voltage
controller with the most recent message being
All of the programmed set points and their (UV), Over Frequency (OF) and Under
displayed first. Frequency (UF). Refer to the LMR Plus operation
current status can be viewed via the webpage.
manual IM05805020K for details.
PRINT Menu
Custom Messages Custom Inputs / Outputs
Description
Users can create custom messages on a There is provision on the Power I/O Board to
All fault and alarm information is sent to the
computer and upload to the controller using a accept up to 9 additional inputs and 9 additional
USB and Printer ports on demand, as well as
USB Drive (memory stick). Up to 10 custom outputs. Each of the inputs can be labeled using
the status of each output. The LMR Plus will
messages of up to 100 characters each, will one of 11 pre-set input descriptions or assigned a
store up to 10K events which are time and date
continuously scroll across the fourth line of the custom description that is programmed by the
stamped. All information can also be retrieved
LCD display once uploaded. user. The optional outputs can be programmed to
and displayed on the LCD display.
indicate up to 25 output conditions. As well, two
Saving to USB Drive optional alarm LED’s can be programmed for up
The controller will save four separate text files, to 12 alarm conditions.
one CSV file and the embedded webpage to the All optional inputs, outputs and LED’s can be
USB external drive. The files, at maximum size, linked, as required.
can be saved multiple times on one 128MB Inputs can be programmed to energize the
USB drive. common alarm output, link to relays and optional
Trigger Points LED’s and latch until reset by the user.
Files to be saved are: Status Report,
The message can be programmed to appear at Outputs can be programmed for fail safe and
Diagnostics Report, Statistics Report,
specific trigger points such as specific date and latch until reset by the user.
Configuration File and Last 5K Messages.
time, specific number of operations, specific Optional inputs and outputs can be programmed
number of hours run or at any individual alarm with time delay functions.
Print Menu
point.
The printer menu is accessed in order to select
All of the trigger points can be selected as
the desired print function. System Configuration Menu
And/Or values.
Functions include: Print Messages, Last XX The system configuration menu section is
Messages, Date & Time, Status Report, password protected and contains settings such
Diagnostics Report and Statistics Report. Programming Menu as system voltage, frequency, CT ratio etc. Refer
General to Technical Bulletin PU05805035K/D
Custom Messages The LMR Plus programming menu is divided for details.
When this item is selected, custom messages into 8 different sub-menus. Each sub-menu
can be cleared from memory or downloaded contains information relative to it’s particular Main Menu Password
from the USB external drive. function. Following is a brief description of each A password can be programmed by the user to
sub-menu. protect access to the Main Menu. Refer to the
LMR Plus Operation Manual IM05805020K for
details.

For more information visit: [Link] BR05805051K/F


Pump and Plumbing for Fire Pump Controllers

Pump and Plumbing March 2010

Pump and Plumbing LMR


PLU
S

MD05805005K/B For more information visit: [Link]


LMR PLUS Electric Fire Pump Controllers
Main Display
Main Display - LMR Plus Fire Pump Controllers March 2010

Main Display LMR


PLU
S

POWER ON PHASE REVERSAL LMR


PLU
S
PUMP RUNNING PHASE FAILURE
LOCAL START FAIL TO START
REMOTE START UNDERVOLTAGE
DELUGE VALVE OVERVOLTAGE
EMERGENCY START LOW ROOM TEMPERATURE
SILENCE
INTERLOCK ON LOCKED ROTOR TRIP
ALARM
LOW PRESSURE LOW SUCTION PRESSURE
MOTOR AUTO SHUTDOWN ENABLED SOURCE 2 DISCONNECTED
TEST

DATA
PRINT

LAMP
TEST MENU

RESET
SAVE/EXIT

ACK.
99-5816-01

NOTES:
1. Refer to the LMR Plus technical manual for detail and setup
information, as well as programming and custom labelling for
Programmable LED # 1 and Programmable LED # 2.

N. Y. C.
APPROVED

NOTE: As of January 1, 2009 - All Limited Service Controllers will not carry FM Approval.
MD05805096K/C For more information visit: [Link]
LMR PLUS Electric Fire Pump Controllers
Dimensions
FD70 Wye Delta (Star-Delta) Open March 2010

Dimensions
Standard Enclosure - Type NEMA 2, 3R, 4, 4X, 12
LMR
PLU
S

A
17.65 [448] B

3A13357H01
3A13357H01

START

STOP

62.00 [1575]

74.00 [1880]

12.24 [311] Ø1.75 [Ø44]


1.88 [48]
12.00 [305]
6.00 [152]

5.00 [127]
16.00 [406]

PIPING ENTRANCE
1/4" NPT - FEMALE
PIPING ENTRANCE
1/2" NPT - FEMALE
6

1 - START PUSHBUTTON
2 - STOP PUSHBUTTON 14.00
3 - MAIN POWER SWITCH 11.26 [286]
[356]
4 - MSH (EMERGENCY START HANDLE) 1.11 [28]
5 - MAIN LMR PLUS DISPLAY
6 - RECOMMENDED CABLE ACCESS (BOTTOM ONLY)
1.37 [35]
C 1.13 [29]
3.35 [85]

Motor Hp Line Withstand Rating Approx.


Voltage Standard Intermediate High
Weight A B C
Lbs. (Kg)

50 - 100 200 - 208V 100,000 Consult Consult 315 41.83 30.25 21.30
60 - 125 220 - 240V Factory Factory (143) (1062) (768) (541)
100 - 200 * 380 - 415V
125 - 250 440 - 480V
125 - 300 550 - 600V 25,000 35,000
125 - 150 200 - 208V 100,000 Consult 420 54.83 43.25 34.30
Factory (190) (1393) (1099) (871)
150 - 200 220 - 240V
250 - 300 * 380 - 415V
300 - 400 440 - 480V
350 - 500 550 - 600V 25,000 35,000
* Coils Available: 380V-50Hz, 380V-60Hz, 415V-50Hz, 415V-60Hz
NOTES:
1. All enclosures finished in FirePump red.
N. Y. C. 2. Cable Entrance bottom only.
APPROVED 3. Standard Enclosure type NEMA 2.

MD05805085K/B For more information visit: [Link]


LMR PLUS Electric Fire Pump Controllers
Electrical Wiring Schematic
FD70 Wye Delta (Star-Delta) Open March 2010

Electrical Wiring Schematic


LMR
PLU
S

DELUGE VALVE (REMOVE JUMPER IF USED)

LOW ROOM TEMPERATURE


REMOTE START

INTERLOCK ON
LOW SUCTION
PUMP START

INPUT #1
INPUT #2
INPUT #3
INPUT #4
INPUT #5
INPUT #6
INPUT #7
INPUT #8
INPUT #9
CUSTOMER INPUTS

OPTION RELAY #1 OPTION RELAY #5


(2 SETS FORM-C) (2 SETS FORM-C)

OPTION RELAY #2 OPTION RELAY #6


(2 SETS FORM-C) (2 SETS FORM-C)

OPTION RELAY #3 OPTION RELAY #7


(2 SETS FORM-C) (2 SETS FORM-C)

OPTION RELAY #4 OPTION RELAY #8


(2 SETS FORM-C) (2 SETS FORM-C)

COMMON ALARM
(NORMALLY ENERGIZED)
INTERNAL CONNECTIONS

COMMON ALARM
(NORMALLY ENERGIZED)

PHASE FAILURE
(NORMALLY ENERGIZED)
ALARM CONTACTS

PHASE FAILURE
(NORMALLY ENERGIZED)

PHASE REVERSAL

PHASE REVERSAL

FUTURE #1

FUTURE #1

PUMP RUN

PUMP RUN

N. Y. C.
APPROVED

ES05805096K/C For more information visit: [Link]


LMR PLUS Electric Fire Pump Controllers
Field Connections
FD70 Wye Delta (Star-Delta) Open March 2010

Field Connections
LMR
PLU
S

Line Terminals (Incoming Cables)


Line Te r m inals on M ain Is olation Sw itch (Incom ing Cable s )
LINE V OLTA GE Qty. & Cable Sizes Service Entrance GND. LUG
200 - 208 220 - 240 *380 - 415 440 - 480 550 - 600 Qty. & Cable Sizes
Max HP 25 30 40 60 75 (1)#14-1/0 PER Ø (CU/A L) (1)#14-2/0 (CU/A L)
40 50 75 100 100 (1)#4-4/0 PER Ø (CU) (1)#4-350MCM (CU/A L)
75 75 150 200 200 (1)#3-350MCM PER Ø (CU/A L) (1)#4-350MCM (CU/A L)
100 125 200 250 300 (2)3/0-250MCM PER Ø (CU/A L) (2)1/0-750MCM (CU/A L)
150 200 300 400 400 (2)250-350MCM PER Ø (CU/A L) (2)1/0-750MCM (CU/A L)
200 - 350 450 550 (2)#1-500MCM PER Ø (CU/A L) (2)1/0-750MCM (CU/A L)
250 300 500 600 700 (3)3/0-400MCM PER Ø (CU/A L) (2)1/0-750MCM (CU/A L)
* Coils available: 380V -50Hz, 380V -60Hz, 415V -50Hz, 415V -60Hz.

Load Terminals (To Motor)


Load Terminals (To Motor)
LINE VOLTAGE Qty. & Cable Sizes
200 - 208 220 - 240 380 - 415 440 - 480 550 - 600
Max HP 20 25 30 40 40 (1)#14-#3 PER Ø (CU)
40 50 75 100 100 (1)#14-1/0 PER Ø (CU/AL)
60 75 100 150 150 (1)#6-250MCM PER Ø (CU/AL)
150 150 250 300 300 (2)1/0-250MCM PER Ø (CU/AL)
250 300 500 600 700 (2)2/0-500MCM PER Ø (CU/AL)
* For Proper Cable Size Refer to National Electrical Code NFPA-70

External Inputs Alarm / Relay Outputs Typical Controller Connection

COMMON ALARM
(NORMALLY ENERGIZED)

COMMON ALARM
(NORMALLY ENERGIZED)

PHASE FAILURE
(NORMALLY ENERGIZED)
ALARM CONTACTS

PHASE FAILURE
(NORMALLY ENERGIZED)

PHASE REVERSAL

PHASE REVERSAL

FUTURE #1 NOTE:
1. MOTOR CONNECTIONS VARY, PLEASE
REFER TO SPECIFIC MOTOR CONNECTION
FUTURE #1 DIAGRAM.
2. PLEASE OBSERVE PROPER PHASE
ROTATION, A,B,C-L1,L2,L3 AS CONTROLLER
IS PHASE SENSITIVE.
PUMP RUN 3. CABLE SIZE TO BE 125% OF FULL LOAD
CURRENT. REFER TO WIRE SIZE TABLE IN
NFPA 70.

PUMP RUN

N. Y. C.
APPROVED

ES05805097K/D For more information visit: [Link]


Fire Pump Controllers 1-1
Features

LMR Plus Electric Fire Pump Controllers

Typical Specifications A. The controller shall come complete with a 4 line by


40 character LCD display mounted on a panel open-
1. Approvals ing in the front door. The LCD display shall indicate
A. The Fire Pump Controller shall meet the require- the following:
ments of the latest edition of NFPA 20 and shall be 1. Main screen displaying system pressure, three-
listed by [Underwriters Laboratories (UL)]and ap- phase voltage and amperage readings, system
proved by [Factory Mutual Research (FM)] [Cana- frequency, date, and time.
dian Standards Association (CSA)] [New York De- 2. Set point review screen displaying the pro-
partment of Buildings (NYSB)] and carry the CE grammed pressure start and stop points, and
marking for fire pump service. weekly test time.
2. Starting Type 3. Controller statistics screen, including:
A. The controller shall be of the combined manual and a. Powered Time
automatic type designed for [Full Voltage Starting] b. Motor Run Time
[Part Winding Starting] [Primary Resistor Starting] c. Number of Calls to Start
[Autotransformer Starting] [Wye-Delta (Star-Delta) d. Number of Starts
Open Transition Starting] [Wye-Delta (Star-Delta) e. Last Motor Start Time
Closed Transition Starting] [Solid State Soft Start f. Last Motor Run Time
Starting] g. Last Low Pressure Start
3. Ratings h. Minimum System Voltage
A. The Controller shall have a withstand rating of i. Maximum System Voltage
100,000 RMS symmetrical amperes @ [208V] [240V] j. Minimum System Frequency
[380V] [400V] [415V] [480V] [25,000 @ 600VAC]. k. Maximum System Frequency
4. Construction l. Minimum System Pressure
A. The controller shall include a motor rated combina- m. Maximum System Pressure
tion isolating switch and circuit breaker, mechanically n. Last System Startup
interlocked and operated with a single externally o. Last Phase Failure
mounted handle. p. Last Phase Reversal
B. The isolating switch shall be rated to disconnect the q. Last Locked Rotor Trip
motor load. r. Maximum Run Current
C. The isolating switch/circuit breaker combination shall s. Last Locked Rotor Current
be mechanically interlocked such that the enclosure 4. Controller diagnostics screen, including:
door cannot be opened when the handle is in the on a. Date & Time
position except by a tool operated defeater mecha- b. Firmware Version
nism. c. Shop Order Number
D. The controller manufacturer shall manufacture the d. Customer Order Number
contactor, isolating switch, circuit breaker, pushbut- e. Transformer Output Voltage
tons, and enclosures. Brand-labeled components f. Current Transformer Outputs
will not be accepted. g. Pressure Transducer Calibrated Settings
5. Enclosure h. Input Status
A. The controller shall be housed in a NEMA Type 2 i. Output Status
(IEC IP11) drip-proof, powder baked finish, free- 5. Display last messages screen that will display
standing enclosure. up to 10,000 alarms/messages stored in the
B. Optional Enclosures: controllers' memory.
1. NEMA 3R (IEC IP14) rain-tight enclosure. 6. Display up to ten (10) custom messages of up to
2. NEMA 4 (IEC IP56) watertight enclosure. 100 characters each, which will continually scroll
3. NEMA 4X (IEC IP56) watertight 304 stainless across the fourth line of the display.
steel enclosure. 7. Remaining time left on active timers.
4. NEMA 4X (IEC IP56) watertight 316 stainless B. The controller shall be supplied with ten (10) green
steel enclosure. status LED’s for the following:
5. NEMA 4X (IEC IP56) watertight corrosion resis- 1. Power On
tant enclosure. 2. Pump Running
6. NEMA 12 (IEC IP52) dust-tight enclosure. 3. Local Start
4. Remote Start
5. Deluge Valve
6. Emergency Start
6. Microprocessor Control 7. Interlock On

June 2010 For more information visit: [Link] PS05805008K/C


Fire Pump Controllers 1-2
Features

LMR Plus Electric Fire Pump Controllers

8. Low Pressure 7. Programming Menu


9. Auto Shutdown Enabled A. The programming menu shall have the ability to en-
10. Programmable LED #1 able an entry password.
C. The controller shall be supplied with ten (10) red B. The programming menu shall be limited to two (2)
alarm LED’s to indicate the following: levels of password protection.
1. Phase Reversal C. The controller shall have three (3) languages as a
2. Phase Failure standard, English, French, and Spanish, with the
3. Fail to Start ability to add a fourth language.
4. Undervoltage D. The programming menu shall be grouped into 6 main
5. Overvoltage menu headings as follows:
6. Low Room Temperature 1. Regional Settings
7. Locked Rotor Trip 2. Pressure Settings
8. Low Suction Pressure 3. Timer Values
9. Source 2 Disconnected 4. Alarm Set points
10. Programmable LED #2 5. Input/Output Menu
D. The microprocessor logic board shall be equipped 6. System Configuration (password protected)
with: 8. Pressure Sensor
1. A USB port for transference of message history, A. A solid-state 4-20mA pressure sensor shall be pro-
controller status, diagnostics, and statistics and vided. The pressure Start and Stop points shall be
the ability to update firmware. adjustable in increments of one (1) PSI. A low pres-
2. An Ethernet port for direct connection to a com- sure pre-alarm, indicated with a flashing green LED,
puter for data transfer. shall denote a potential pump starting condition and
3. An RS485 Serial port for communication to vari- will remain lit once the pump has started to indicate
ous external software programs. the starting cause.
E. The controller shall come complete with an embed- 9. Custom Inputs/Outputs
ded web page which allows viewing of the control- A. The controller shall come standard with nine (9) fu-
lers' current status, data values, programmed set ture inputs, two (2) future LED indicators, and one (1)
points, and history. future output, with the ability to add up to another 8
F. A Fail-to-Start alarm shall occur if the motor control- outputs via optional relay boards.
ler sees less than 20% of the motor full load amps af- B. The user shall be able to program the future in-
ter an adjustable time delay of 1-90 seconds. puts/outputs through the main programming menu.
G. Locked rotor protection shall be provided. After a trip C. The inputs shall be selectable based on the following
condition and restoration of power, the LCD display criteria:
shall indicate “LOCKED ROTOR TRIP”. 1. User selected message or thirteen (13) prede-
H. A sequential start timer and weekly test timer shall termined messages.
be provided as standard. 2. Energize the common alarm relay when the in-
I. A restart time delay of two (2) seconds shall be pro- put is received.
vided to allow the residual voltage of the motor to 3. Link to a future relay and/or LED indicator.
decay prior to re-starting the motor. In the event that 4. Alarm latched until reset.
the pump motor continues to run after a request to 5. Normally open or closed input.
stop, then the controller must display a fail to stop 6. On-delay timer.
message to indicate this condition. D. The LED indicators shall be selectable based on the
J. Overvoltage (5-20%) and undervoltage (5-30%) following criteria:
sensing and alarming shall be provided as standard. 1. Indication based on a minimum of twelve (12)
K. The controller shall be supplied with interlock and predetermined alarms or a custom input.
shutdown circuits as standard. A flashing green LED E. The future relays shall be selectable based on the
shall indicate an interlock on condition. following criteria:
L. Where shutdown of the pump(s) due to low suction 1. Output based on a minimum of twenty-seven
pressure is required, it shall be accomplished without (27) predetermined alarms, controller status or a
the addition of a separate panel or enclosure. The custom input.
LCD display shall indicate low suction shutdown. 2. Latched until reset.
Resetting of the condition shall be automatic or man- 3. Energized under normal conditions.
ual as selected by the user. 4. On or off delay timer on the output.
M. Means shall be provided to test the operation of all
LED’s to ensure their functionality.

June 2010 For more information visit: [Link] PS05805008K/C


Fire Pump Controllers 1-3
Features

LMR Plus Electric Fire Pump Controllers

10. Alarm Relays


A. All relays shall be of the plug-in type. An LED on the
relay panel shall indicate the energized state of the
relay. All relay contacts shall be rated @ 8A,
277VAC/30VDC. Two (2) sets of Form-C contacts
shall be provided for each of the following:
1. Phase Reversal
2. Phase Failure
3. Common Alarm
4. Future #1
5. Pump Run.
B. The Common Alarm and Phase Failure relays shall
be energized under normal conditions.
11. Audible Alarm Buzzer
An audible alarm buzzer, capable of being heard
while the motor is operating, shall operate if Fail to
Start, Hardware Malfunction or any Common Alarm
condition exists.
12. Manufacturer
A. The controller shall be of the LMR Plus type as
manufactured by Eaton Corporation.

June 2010 For more information visit: [Link] PS05805008K/C


Remote Alarm Panels 1-1
Features
DFDAP-M / FDAP-M Remote Alarm Panel March 2011

Lamp Test Button Membrane Indication


The lamp test button on the membrane will Inputs five (5) and six (6) are directly connected to
simultaneously test all LED’s. two LED’s on the bottom left on the membrane. A
space is provided beside each LED for labeling
Silence Alarm Button purposes.

The Silence Alarm button on the membrane will Inputs seven (7) and eight (8) are directly
silence all active alarms when pressed, but has connected to two LED’s on the bottom right on the
no effect on the associated alarm LED(s). If membrane. As well as LED indication and labeling
another alarm condition occurs after the silence area on the membrane, they will each provide an
button has been pressed, the alarm buzzer will output signal from a corresponding SPDT, 8Amp
re-sound until the button is pressed again, or relay.
the alarm condition is satisfied.

User Selectable Alarm Inputs Electric Remote


Alarm Panel

NORMAL POWER ON SUPERVISORY POWER ON


Each panel accepts up to eight (8) inputs. Each PUMP RUNNING PHASE FAILURE
PHASE REVERSAL COMMON ALARM
input can be selected as either normally open
or normally closed by use of jumpers on the
Product Description microprocessor board.
LAMP SILENCE
TEST ALARM
Eaton’s Remote Alarm Panels are designed to
provide audible and visual alarms for Electric
and Diesel Fire Pump Controllers. 99-5814-01

These remote panels are located at a point of


constant attendance when the pump room is
Electric
not constantly supervised.
Normal Power On
Supervisory Power On
Product Features Pump Running
Phase Failure
Microprocessor Control Phase Reversal
Common Alarm
All DFDAP-M and FDAP-M Remote Alarm Custom - (2)
Panels are microprocessor based. Custom with SPDT, 8Amp relay Output - (2)
The same microprocessor board is used for “Normal Power On” Indication
both Electric and Diesel units.
The Normal Power On LED will turn ON when
the normal power is available and will turn OFF
Power Supply Voltages when the controller switches to the Supervisory Diesel Remote
Alarm Panel

(backup) power source. NORMAL POWER ON SUPERVISORY POWER ON


Both Normal and Supervisory (backup) power ENGINE RUNNING NOT IN AUTO MODE
The alarm buzzer will sound when the normal LOW FUEL COMMON ALARM
supply voltages can be supplied from 110 to
power is not available and will remain ON until
240Vac, 50-60 Hz. Both Normal and
the normal power is restored, or the Silence
Supervisory power is supplied by customer.
Alarm button is pressed. LAMP SILENCE
TEST ALARM

Normal / Supervisory (backup) Output Relays


Power Source 99-5815-01

Output relays are PCB style - rated for


If the Normal power source is not available,
8A/250VAC. Diesel
the controller will automatically switch to the
Supervisory (backup) source. When normal Normal Power On
power is restored, the controller will switch Supervisory Power On
back to the normal source. Engine Running
Not In Auto Mode
Audible Alarm NEMA 1 Enclosures Low Fuel
An audible buzzer will sound when any alarm Common Alarm
All remote alarm panels come standard with Custom - (2)
condition occurs. It will continue to sound until
NEMA 1 enclosures. Custom with SPDT, 8 Amp relay Output - (2)
either the Silence Alarm button is pressed, or
the alarm condition is satisfied.

Technical Data and Specifications Standards & Certification


Line Terminals (Incoming Cables) The DFDAP-M / FDAP-M Remote Alarm Panels
meet or exceed the requirements of Underwriters
Laboratories, Underwriters Laboratories Canada,
Recommended Wire Size Distance the Canadian Standards Association, the New York
Number of feet (meters) from the controller to the remote
alarm panel.
City building code, and are built to NFPA 20
standards.
Stranded # 16 3000 (914.4)
Stranded # 14 4500 (1371.6) N. Y. C.
APPROVED
Stranded # 12 7000 (2133.6)

For more information visit: [Link] BR05805024K/G


Remote Alarm Panels
Main Display
Main Display - FDAP-M Electric Remote Alarm Panel March 2011

Main Display LMR


PLU
S

Electric Remote
Alarm Panel

NORMAL POWER ON SUPERVISORY POWER ON


PUMP RUNNING PHASE FAILURE
PHASE REVERSAL COMMON ALARM

LAMP SILENCE
TEST ALARM

N. Y. C.
APPROVED

MD05805157K/B For more information visit: [Link]


Remote Alarm Panels
Dimensions
FDAP-M Electric Remote Alarm Panel June 2010

Dimensions
Standard Enclosure - Type NEMA 1 - Electric Remote Alarm Panel

11.56 [294]
15.49 [393]
9.75 [248]

9.55 [243] 8.00 [203]

C US C US
C US LISTED C US LISTED
LR66765 4M95 LR66765 4M95

CAT. NO. FDAP-M CAT. NO. FDAP-M


VOLTS 120 AMPS 2 HERTZ 60 VOLTS 120 AMPS 2 HERTZ 60
CONTROL CIRCUIT VOLTS 24VDC CONTROL CIRCUIT VOLTS 24VDC
SERIAL NO. 16BJ709E ENCL. TYPE 1 SERIAL NO. 16BJ709E ENCL. TYPE 1

MADE IN CANADA 4A55079H01 MADE IN CANADA 4A55079H01

n 0.27 [n7]x4
WALL MTG. HOLES

4.74 [120]

Approx. Weight
Lbs. (Kg)

10 (4.5)

NOTES:
1. All enclosures finished in FirePump red.
N. Y. C. 2. Cable Entrance either top or bottom.
APPROVED 3. Standard Enclosure type NEMA 1.

MD05805054K/B For more information visit: [Link]


Remote Alarm Panels
Electrical Wiring Schematic
FDAP- M Electric Remote Alarm Panel March 2011

Electrical Wiring Schematic

N. Y. C.
APPROVED

ES05805132K/D For more information visit: [Link]


Remote Alarm Panels
Features
DFDAP-M / FDAP-M Remote Alarm Panels
June 2010

Typical Specifications

1. Approvals 3. Enclosure
A. The Remote Alarm Panel shall meet the require- A. The panel shall be housed in a NEMA Type-1
ments of the latest edition of NFPA 20 and shall enclosure provided with means for wall mounting.
be listed by [Underwriters Laboratories (UL)]
[Underwriters Laboratories of Canada (ULC)] 4. Input Contacts
approved by [Canadian Standards Association A. Contact inputs shall be dry contact (non pow-
(CSA)] and have MEA approval for New York ered). Each input shall be capable of being se-
City. lected as either normally open (N.O.) or normally
closed (N.C.).
2. Construction
A. The remote alarm panel shall be equipped with a 5. Output Contacts
Lamp Test button which, when operated, fully A. Electric alarm panels shall provide six (6) alarm
tests all LED’s. The Lamp Test Button shall not outputs to indicate Normal Power ON, Supervi-
change the state of internal relays. sory Power ON, Pump Running, Phase Reversal,
B. The panel shall accept both 120 volt 50/60Hz and Phase Failure and Common Alarm.
240 volt 50/60Hz power supply on either of the Diesel alarm panels shall provide six (6) alarm
primary and backup source inputs. The panel outputs to indicate Normal Power ON, Supervi-
shall operate such that if the primary source of sory Power ON, Engine Running, Not in Auto
supply is lost, the panel will automatically switch Mode, Low Fuel, and Common Alarm.
to the backup source. Both the primary and B. (All outputs shall be printed circuit board relay
backup sources shall be independent of each style rated for 8amps / 250VAC. The relays shall
other. be de-energized under normal conditions regard-
C. An audible buzzer shall sound when any alarm less of input status selected.
conditions are present. It shall continue to sound
until either the silence button is pressed, or the 6. Manufacturer
alarm condition is satisfied. A. The panel manufacturer shall manufacture the
D. A silence alarm button shall be provided to si- enclosure and provide completely assembled
lence all active alarms when pressed. It shall units.
have no effect on the associated alarm LED’s. B. The remote alarm panel shall be manufactured
Should a second alarm condition occur after the by Eaton Corporation.
silence button has been pressed, the audible
alarm shall re-sound until the silence button is
pressed again, or the alarm condition has been
satisfied.
E. A Normal Power On LED shall indicate when
normal power is available and shall turn off when
the controller switches to the Supervisory
(backup) power source. An audible alarm shall
sound when normal power is not available and
shall remain ON until normal power is restored,
or the silence button is pressed.

For more information visit: [Link] PS05805007K/C


FP 2.7 A-C FIRE PUMP SYSTEMS
Page 302 List Prices Fire Pump Fittings &
Accessories
August 07

Supersedes all previous issues

SUCTION AND DISCHARGE GAUGE ASSEMBLY

ITEM DESCRIPTION
SUCTION PRESSURE GAUGE, 3.5 DIAL, 3-2-3% ACCURACY,
A
RANGE -30-0-200
DISCARGE PRESSURE GAUGE, 3.5 DIAL, 3-2-3% ACCURACY,
B
RANGE 0-300 PSI
C 1/4" NPT TWO WAY BALL VALVE

D 1/4" NPT STREET ELBOW


A-C FIRE PUMP SYSTEMS FP 2.7
Dimensions - Fire Pump Fittings & Page 301
Accessories
August 07

Supersedes all previous issues

AUTOMATIC AIR RELEASE VALVE


5.125
5 1/8 ”
(130.175)
OPTIONAL
23
14
21 OUTLET

4
2 7

6
3
8.375
8 3/8
(212.725)

13 34
12 1
10
6.00
11 6 "
(152.400)

17 5

LISTED
28WL
FM
MAX WORKING PRESSURE = 300 PSI APPROVED

WEIGHT = 5 LBS

INLET

1 B O DY 11 O R I FIC E B U TTON
2 CO V E R 12 PIV OT P IN NOTE: 1.00 NPT INLET.
3 LE V E R F RA M E 13 PIN R E TA IN E R (N OT S H OW N )
4 S E AT 14 PIP E P LU G THREADED BUSHINGS
5 F LO AT 17 F L O AT R E TA IN E R PROVIDED FOR SMALLER
6 GASKET 21 L O C ATOR SIZES.
7 CO V E R B O LT 23 SC RE E N E D H OOD
10 F LO AT A RM 34 L O C K WA S H E R

DIMENSIONS IN INCHES (mm)


A-C FIRE PUMP SYSTEMS FP 2.7
Dimensions - Fire Pump Fittings & Page 303
Accessories
August 07

Supersedes all previous issues

CASING RELIEF VALVE


p
Size 3/4" Threaded
Temperature Range Water, Air: to 180°F Max.
Materials 1.75
Body & Cover: Cast Bronze ASTM B62
Stainless Steel ASTM A743-CF-16Fa
Trim: Brass & Stainless Steel 303
Rubber: Buna-N® Synthetic Rubber

Flow Range: < 2500 GPM


1.75
UL Listed Approximate Increase
55L Range for Each Clockwise Turn
psi of Adjusting Screw Pressure
20 to 175 28.0 psi Setting
Adjustment
Screw
(Turn Clockwise
FM Approved Approximate Increase To Increase Setting)
55L Range for Each Clockwise Turn
psi of Adjusting Screw

0 to 75 8.5 psi
7.44
20 to 200 28.0 psi

100 to 300 18.0 psi

Pressure Ratings Cast Bronze 400 psi Max.


Stainless Steel 400 psi Max.
Other Materials Available on special order
Adjustment Ranges 0 to 75 psi INLET
20 to 200 psi
100 to 300 psi .71

WEIGHT = 6 LBS
1.75

3.50
4.50
FP 2.7 A-C FIRE PUMP SYSTEMS
Page 316 Dimensions - Fire Pump Fittings &
Accessories
August 07

Supersedes all previous issues

CLOSED WASTE CONE


INLET CONNECTION 150# R.F. ANSI B16.5
OUTLET CONNECTION 150# R.F. ANSI B16.5
BODY MATERIAL CAST STEEL
MAX W.P. 175 PSI

SIZE A B WT

2 x 2-1/2 8.00 (203.2) 1.00 (25.4) 18

2-1/2 x 3-1/2 7.50 (190.5) 1.00 (25.4) 27

3x5 8.50 (215.9) 2.00 (50.8) 37

4x6 9.03 (229.362) 2.00 (50.8) 48

4x8 10.25 (260.35) 2.00 (50.8) 68

6x8 10.25 (260.35) 2.00 (50.8) 77

6 x 10 11.50 (292.1) 2.00 (50.8) 98

8 x 12 13.00 (330.2) 2.00 (50.8) 151

8 x 14 14.00 (355.6) 2.00 (50.8) 197

DIMENSIONS IN INCHES (mm)


FP 2.7 A-C FIRE PUMP SYSTEMS
Page 320 Dimensions - Fire Pump Fittings &
Accessories
August 07

Supersedes all previous issues

FLOWMETER

A B
VENTURI SYSTEM PIPE METER RANGE MIN.
GPM VENTURI LENGTH
MODEL NO. SIZE & MAX. GPM 150 # (RF) 300 # (RF)
GROOVED BUTT WELD
25 K-25-1-1/4(616) 1-1/4" 12.5-50 Threaded only 3-3/4 (92.25) --- ---
50 K-50-2(685) 2" 25-100 Threaded only 4-1/4 (120.65) --- ---
100 K-100-2-1/2(746) 2-1/2" 50-200 3.00 (76.2) 4.00 (101.6) 9.50 (241.3) 10.00 (254)
150 K-150-3(766) 3" 75-300 3.50 (88.9) 4.38 (111.125) 9.00 (228.6) 10.25 (260.35)
200 K-200-3(766) 3" 100-400 3.50 (88.9) 4.38 (111.125) 9.00 (228.6) 10.25 (260.35)
250 K-250-4(744) 4" 125-500 3.50 (88.9) 3.75 (95.25) 9.50 (241.3) 10.75 (273.05)
300 K-300-4(744) 4" 150-600 3.50 (88.9) 3.75 (95.25) 9.50 (241.3) 10.75 (273.05)
450 K-450-4(744) 4" 225-900 3.50 (88.9) 3.75 (95.25) 9.50 (241.3) 10.75 (273.05)
500 K-500-5(715) 5" 250-1000 5.00 (127) 12.00 (304.8) 13.25 (336.55)
500 K-500-6(743) 6" 250-1000 6.00 (152.4) 13.00 (330.2) 14.25 (361.95)
750 K-750-6(743) 6" 375-1500 6.00 (152.4) 13.00 (330.2) 14.25 (361.95)
1000 K-1000-6(743) 6" 500-2000 6.00 (152.4) 13.00 (330.2) 14.25 (361.95)
1250 K-1250-6(743) 6" 625-2500 6.00 (152.4) 13.00 (330.2) 14.25 (361.95)
1500 K-1500-8(750) 8" 750-3000 7.00 (177.8) 15.00 (381) 16.25 (412.75)
2000 K-2000-8(750) 8" 1000-4000 7.00 (177.8) 15.00 (381) 16.25 (412.75)
2500 K-2500-8(750) 8" 1250-5000 7.00 (177.8) 15.00 (381) 16.25 (412.75)
3000 K-3000-8(750) 8" 1500-6000 7.00 (177.8) 15.00 (381) 16.25 (412.75)
3500 K-3500-10(755) 10" 1750-7000 8.00 (203.2) 16.00 (406.4) 17.75 (450.85)
4000 K-4000-10(755) 10" 2000-8000 8.00 (203.2) 16.00 (406.4) 17.75 (450.85)
4500 K-4500-10(755) 10" 2250-9000 8.00 (203.2) 16.00 (406.4) 17.75 (450.85)
5000 K-2000-12(750) 12" 2500-9000 12.00 (304.8) 21.00 (533.4) 22.75 (577.85)
Factory Mutal Approved.

DIMENSIONS IN INCHES (mm)


FP 2.7 A-C FIRE PUMP SYSTEMS
Page 314 Dimensions - Fire Pump Fittings &
Accessories
August 07

Supersedes all previous issues

MAIN RELIEF VALVE


PILOT CONTROLLED

Sizes Angle 2" - 8" flanged

End Details 150 and 300 ANSI B16.42


Pressure Ratings class - 175 psi Max.
class - 300 psi Max
Water, to 180°F Max.
Materials Main Valve Body & Cover
Ductile Iron ASTM A-536
Naval Bronze ASTM B61
Other Material Available
Standard Main Valve Trim:
Bronze Seat, Teflon Coated
Stainless Steel Stem, Delrin Sleeved
Standard Pilot Control System:
Cast Bronze with
Stainless Steel trim
Adjustment Range Available in the following relief
pressure ranges:
20-200 psi (150 Class)
100-300 psi (300 Class)

UL Listed / FM Approved (Sizes 3" - 8")

2" 2-1/2" 3 4 6 8
WEIGHT (lbs) 50 50 80 130 210 270

VALVE SIZE (INCHES)


2 2 1/2 3 4 6 8
THREADED 3.250 (82.55) 4.000 (101.6)
150# FLANGED A 3.250 (82.55) 4.000 (101.6) 4.000 (101.6) 5.000 (127) 6.000 (152.4) 8.000 (203.2)
300# FLANGED 3.500 (88.9) 4.310 (109.474) 4.380 (111.252) 5.310 (134.874) 6.500 (165.1) 8.500 (215.9)
B 12.000 (304.8) 12.250 (311.15) 12.500 (317.5) 13.000 (330.2) 14.310 (363.474) 16.310 (414.274)
THREADED 4.750 (120.65) 5.500 (139.7)
150# FLANGED C 4.750 (120.65) 5.500 (139.7) 6.000 (152.4) 7.500 (190.5) 10.000 (254) 12.750 (323.85)
300# FLANGED 5.000 (127) 5.880 (149.352) 6.380 (162.052) 7.880 (200.152) 10.500 (266.7) 13.250 (336.55)
E 6.000 (152.4) 6.690 (169.926) 7.750 (196.85) 7.880 (200.152) 8.500 (215.9) 9.750 (247.65)
G 3.310 (84.074) 4.000 (101.6) 4.560 (115.824) 5.750 (146.05) 7.880 (200.152) 10.000 (254)

DIMENSIONS IN INCHES (mm)


SECTION

B-1
3-11
O.S.&Y. RESILIENT WEDGE
GATE VALVES UL / FM
FLANGED ENDS
FIRE PROTECTION PRODUCTS
R-2365-6: O.S.&Y. RESILIENT WEDGE GATE VALVE WITH FLANGE ENDS

• 2-1/2", 3", 4", 6" AND 8" SIZES • RUBBER ENCAPSULATED IRON WEDGE
• MEETS OR EXCEEDS ALL APPLICABLE • ADJUSTABLE PACKING
REQUIREMENTS OF UL 262 AND FM 1120/1130 • HANDWHEEL – OPEN LEFT OR OPEN RIGHT
SPECIFICATIONS AND COMPLIES WITH NSF-61 • 250 PSIG (1379KPA) MAXIMUM WORKING
• DUCTILE IRON BODY WITH MUELLER® PRO-GARD™ PRESSURE - 500 PSIG (2758 KPA) STATIC TEST
FUSION EPOXY COATED INTERIOR & EXTERIOR • EPOXY COATING MEETS OR EXCEEDS ANSI/AWWA
SURFACES C550 AND COMPLIES WITH NSF-61
• OUTSIDE SCREW AND YOKE (O.S.&Y.)
• FLANGED END DIMENSIONS AND DRILLING

Options
Y-5
• STAINLESS STEEL FASTENERS: TYPE 316
• PN10/PN16 DRILLING Y-3
• STAINLESS STEEL STEM: TYPE 304 & 316 Y-4 (not shown)
Y-1
Y-214

PARTS LIST Y-213

Catalog Y-8

Part No. Description Material Material Standard Y-7

Y-1 Retaining Nut Carbon Steel E Coated ASTM A36 Y-10

Y-3 Hand Wheel Ductile Iron ASTM A536 Grade 65-45-12 Y-23

Y-4 Washer Brass ASTM B36


Y-5 Bush Nut Brass ASTM B16
Y-16

Y-7 Gland Nut Silicon Bronze ASTM B98


Y-8 Packing Gland Ductile Iron ASTM A536 Grade 65-45-12 Y-211
Y-217
Y-10 Gland Bolt Stainless Steel Type 304 Y-219

Y-16 Bonnet Bolts & Nuts Stainless Steel Type 304 Y-218

Y-23 Stem Packing Lubricated Flax


Y-212

Y-206 Guide Cap Bearings Acetyl Y-209


Y-209 Wedge, Rubber Encapsulated Cast Iron** ASTM A126 CL.B
Y-211 Bonnet O-ring SBR ASTM D2000 Y-206 (not shown)

Y-212 Body Ductile Iron ASTM A536 Grade 65-45-12


Y-213 Stem Stainless Steel Type 431
Y-214 Bonnet & Yoke Ductile Iron ASTM A536 Grade 65-45-12
Y-217 O-ring Nitrile ASTM D2000
Y-218 Disc Nut Ductile Iron E Coated ASTM A536 Grade 65-45-12 E
Y-219 Stem Nut Pin Stainless Steel Type 303

DIMENSIONS
Size
Dimension* 2-1/2" 3" 4" 6" 8"
A 20.33" 20.16" 23.63" 30.00" 37.37"
AA 16.53" 16.32" 18.94" 23.22" 28.60"
E 7.00" 7.00" 10.00" 12.00" 14.00" A(open)
R 7.00" 7.50" 9.00" 11.00" 13.50" AA(closed)
FF 7.50" 8.00" 9.00" 10.50" 11.50"
UU 5.50" 6.00" 7.50" 9.50" 11.75"
FFF (number and size of holes) 4--.75" 4--.75" 8--.75" 8--.88" 8--.88"
Turns to open 11 11 14 20.5 26.5
Weight (lbs.)* 50 52 76 119 182 FFF

See page B-1-22 for ordering insturctions.


NOTE: Flanged ends have 125lb. American Standard End Flange Drilling, ANSI B16.1.
*All dimensions are in inches. All weights are in pounds and are approximate. R
** Fully encapsulated in molded rubber with no iron exposed. UU

FF

Page B-1-14.2
10SV SERIES
DIMENSIONS AND WEIGHTS AT 60Hz
AT 60Hz,, 2 POLES

DIMENSIONI E PESI SERIE 10SV 2 poli 60 Hz

PUMP MOTOR DIMENSIONS (mm) WEIGHT kg


TYPE L2 M D1 ELECTRIC

kW SIZE L1 1~ 3~ L3 L4 L5 L6 1~ 3~ 1~ 3~ D2 PUMP PUMP

10SV01 0,75 80 357 226 263 - - 357 367 121 129 140 155 120 14,3 25,3
10SV02 1,5 90 367 263 268 - - 367 377 137 137 155 178 140 15,6 30
10SV03 2,2 90 399 298 268 - - 399 409 151 137 174 178 140 16,6 33
10SV04 3 100 441 - 288 - - 441 451 - 137 - 178 160 18,4 38
10SV05 4 112 473 - 319 473 259 473 483 - 154 - 197 160 19,3 45,7
10SV06 4 112 505 - 319 505 291 505 515 - 154 - 197 160 20,3 46,6
10SV07 5,5 132 604 - 375 604 323 604 614 - 168 - 214 300 26 63,5
10SV08 5,5 132 636 - 375 636 355 636 646 - 168 - 214 300 26,9 64,5
10SV09 7,5 132 668 - 367 668 387 668 678 - 191 - 256 300 27,9 83,6
10SV10 7,5 132 700 - 367 700 419 - 710 - 191 - 256 300 28,8 84,5
10SV11 7,5 132 732 - 367 732 451 - 742 - 191 - 256 300 29,7 85,5
10SV13 11 160 826 - 428 826 515 - 836 - 191 - 256 350 34,4 105
10SV15 11 160 890 - 428 890 579 - 900 - 191 - 256 350 36,3 107

10sv-2p60_b_td

34
10SV SERIES
OPERA TING CHARACTERISTIC
OPERATING CHARACTERISTICSS AT 60Hz, 2 POLES
AT
10SV ∼ 3500 [rpm] ISO 9906 - Annex A

0 10 20 30 40 50 60 Q [Imp
70gpm]

0 10 20 30 40 50 60 70 Q
80[US gpm]
280
900
H [m]

H [ft]
260 15

800
240
13
220
700
200
11
180 600
10
160
09 500
140 08

120 07 400

100 06
300
05
80
04
60 200
03
40
02 100
20 01

0 0
1.0 80
Pp [kW]

η
η [%]

0.8 60
0.6 40
kW/stage
0.4 20
4
NPSH [m]

NPSH [ft]

10
2
5

0 0
05943_B_CH

3
0 2 4 6 8 10 12 14 16 18 Q [m20
/h]

0 50 100 150 200 250 300 Q [l/min]


These performances are valid for liquids with density ρ = 1.0 Kg/dm3 and kinematic viscosity ν = 1 mm2/sec.

35
XT SERIES Jockey Pump Controllers 1-1
Features
XT Series Jockey Pump Controllers March 2012

XT Power Controls Digital Display

The XT Series of Jockey Pump Controllers Eaton's XTJP and XTJY series of jockey pump
incorporate Eaton’s XT Power Controls which controllers are supplied standard with an 1/8 DIN,
are designed for the global marketplace. The NEMA 4X digital panel meter that displays current
XT controls carry global ratings, are small in pressure and hi and low setpoints on a 4-digit,
size and are available in a wide variety of superbright LED display. Pressure input is
operating voltages. They are easy to install provided by a 4-20mA pressure sensor.
and maintain, due to their modular, plug-in
design.

120V Control Power Transformer NEMA 2 Enclosures

All jockey pump controllers are wired with a Enclosures have an oven baked powder paint
120V control power transformer as standard. finish and are supplied with NEMA 2 rating,
unless otherwise ordered. Available options
include: NEMA 3R, 4, 4X, 12.

Technical Data
Product Description
ACROSS-THE-LINE (Direct On Line) JOCKEY PUMP CONTROLLERS
ACROSS THE LINE
Line Voltage
JOCKEY PUMP CONTROLLERS
200 - 208V 220 - 240V 380 - 415V 440 - 480V 550 - 600V 120V 1 ph 240V 1 ph
The XTJP jockey pump controllers operate
across-the-line. Full voltage is applied to the
motor for starting by the use of a single motor Motor Horsepower
starter. Starting inrush current is approximately
600% of rated full load amperes. 1/3 - 15Hp 1/3 - 40Hp 1/3 - 50Hp 1/3 - 50Hp 1/3 - 50Hp 1/3 - 5Hp 1/3 - 10Hp

WYE-DELTA (Star-Delta)
JOCKEY PUMP CONTROLLERS

When six or twelve-lead delta connected WYE-DELTA (Star-Delta) JOCKEY PUMP CONTROLLERS
jockey pump motors are started wye (star)
connected, approximately 58% of line voltage Line Voltage
is applied to each winding. The motor
develops 33% of full-voltage starting torque 200 - 208V 220 - 240V 380 - 415V 440 - 480V 550 - 600V
and draws 33% of normal locked-rotor current
from the line. After an adjustable time delay
(during which the motor accelerates), it is Motor Horsepower
reconnected for normal operation. 1/3 - 15Hp 1/3 - 40Hp 1/3 - 50Hp 1/3 - 50Hp 1/3 - 50Hp
(0.74 - 11.03KW) (0.74 - 29.42KW) (0.74 - 36.78KW) (0.74 - 36.78KW) (0.74 - 36.78KW)
Product Features
Combination Motor Controllers

All jockey pump controllers are supplied with


EATON combination motor controllers, which
combine the circuit breaker and overload in
one device.

Standards & Certification


The XT Series of Jockey Pump Controllers
meet or exceed the requirements of
Underwriters Laboratories, Underwriters
Laboratories Canada, the Canadian Standards
Association and the New York City Building
Code.

N. Y. C.
APPROVED
Sealed Rotary Handle Mechanism

The rotary handle mechanism can be


padlocked in the OFF position.

For more information visit: [Link] BR05805077K


Jockey Pump Controllers
Dimensions
XTJP Jockey Pump Controllers May 2012

Dimensions
Standard Enclosure - Type NEMA 2 - Jockey Pump Controller
10.75
[273]

16.13 8.00
[410] [203]

Ø 0.27 [Ø7] x4
WALL MTG. HOLES

1
2

3
13.00 16.35
4
[330] [415]

NOTES:
1 - ISOLATION SWITCH
2 - HAND/OFF/AUTO SWITCH PIPING ENTRANCE 8.59
3 - DOOR LATCH 8.08 1/4" NPT - FEMALE [218]
4 - DIGITAL DISPLAY [205]
2.13
[54]
Dimensions in inches and [millimeters] 4.03
[102]

Dimensions in inches and [millimeters].

200 - 208V 220 - 240V 380 - 415V 440 - 480V 550 - 600V
Motor Hp Withstand Motor Hp Withstand Motor Hp Withstand Motor Hp Withstand Motor Hp Withstand
Rating (kA) Rating (kA) Rating (kA) Rating (kA) Rating (kA)
0.33 - 3 65 0.33 - 3 65 0.33 - 5 65 0.33 - 7.5 65 0.33 - 10 18
4 50 4 50 7.5 - 10 18 10 50
5 - 10 18 5 - 10 18 15 - 20 18

120V 1 240V 1 Approx. Weight


Motor Hp Withstand Motor Hp Withstand Lbs (Kg)
Rating (kA) Rating (kA)
NOTES:
0.33 - 0.5 65 0.33 - 2 65 22 1. All enclosures finished in Red.
50 2. Cable Entrance either top or bottom.
0.75 3-5 18 (10) 3. Standard Enclosure type NEMA 2.
1-2 18

N. Y. C.
Pending
APPROVED

MD05805161K/B For more information visit: [Link]


Jockey Pump Controllers
Dimensions
XTJP Jockey Pump Controllers May 2012

Dimensions
Standard Enclosure - Type NEMA 2 - Jockey Pump Controller with Options
16.38
21.76 [416]
[553]
13.00
[330]

Ø 0.27 [Ø7] x4
WALL MTG. HOLES

1
2

3
16.00 21.15
[406] [537]
4

NOTES:
1 - ISOLATION SWITCH
2 - HAND/OFF/AUTO SWITCH PIPING ENTRANCE 8.60
8.08 1/4" NPT - FEMALE
3 - DOOR LATCH [218]
[205]
4 - DIGITAL DISPLAY
2.63
Dimensions in inches and [millimeters] [67] 3.96
[101]

Dimensions in inches and [millimeters].

200 - 208V 220 - 240V 380 - 415V 440 - 480V 550 - 600V
Motor Hp Withstand Motor Hp Withstand Motor Hp Withstand Motor Hp Withstand Motor Hp Withstand
Rating (kA) Rating (kA) Rating (kA) Rating (kA) Rating (kA)
0.33 - 3 65 0.33 - 3 65 0.33 - 5 65 0.33 - 7.5 65 0.33 - 10 18
4 50 4 50 7.5 - 10 18 10 50
5 - 10 18 5 - 10 18 15 - 20 18

120V 1 240V 1 Approx. Weight


Motor Hp Withstand Motor Hp Withstand Lbs (Kg)
Rating (kA) Rating (kA)
NOTES:
0.33 - 0.5 65 0.33 - 2 65 22 1. All enclosures finished in Red.
50 2. Cable Entrance either top or bottom.
0.75 3-5 18 (10) 3. Standard Enclosure type NEMA 2.
1-2 18

N. Y. C.
Pending
APPROVED

MD05805166K/B For more information visit: [Link]


Jockey Pump Controllers
Electrical Wiring Schematic
XTJP Jockey Pump Controllers - 3 Phase May 2012

Electrical Wiring Schematic - 3 Phase

N. Y. C.
APPROVED

ES05805176K/B For more information visit: [Link]


Jockey Pump Controllers
Electrical Wiring Schematic
XTJP Jockey Pump Controllers March 2012

Electrical Wiring - Options

N. Y. C.
APPROVED

ES05805177K For more information visit: [Link]


Jockey Pump Controllers
Part Number / Options Selection Guide
XTJP / XTJY Jockey Pump Controllers March 2014

Part Number / Options Selection Guide


XTJP / XTJY Jockey Pump Controllers

XTJP
XTJY

Horsepower (KW) Options


1/3 (0.25) C1 Extra Contacts "Pump Run"
1/2 (0.373) C2 Extra Contacts "AC Power Failure"
3/4 (0.56) E1 NEMA 3R - Raintight Enclosure
1 (0.75) E2 NEMA 4 - Watertight Enclosure
1.5 (1.1) E3 NEMA 12 - Industrial Dust Tight Enclosure
2 (1.5) E5 NEMA 4X - 304 Stainless Steel Enclosure
3 (2.25) E8 Tropicalization
4 (2.94) E9 NEMA 4X - Painted Steel
5 (3.75) E10 NEMA 4X - 316 Stainless Steel Enclosure
7.5 (5.6) EX Export Crating
10 (7.5) POL "Power-On" Light
15 (11) PRL "Pump Run" Light
20 (15) P7 Low Suction Pressure Switch and Alarm Pilot Light
25 (18.6) P8 Low Suction Shutdown (Requires P7)
30 (22) P10 Pressure Transducer - Sea Water Rated
40 (30) R1 Space Heater (120 / 220V)
50 (37) R2 Space Heater c/w Thermostat
R3 Space Heater c/w Humidistat
Voltage S Sequential Start
A = 208V - 60HZ T Running Period Timer
B = 240V - 60HZ Z Elapsed Run Time Meter
C = 380V - 50HZ
D = 480V - 60HZ Languages
E = 600V - 60HZ L1 = English
F = 415V - 50HZ L2 = French
H = 380V - 60HZ L4 = Italian
J = 400V - 50HZ L5 = Spanish
K = 400V - 60HZ L6 = Portuguese
G1 = 120V Single Phase (XTJP only) L7 = Chinese
G2 = 240V Single Phase (XTJP only) L8 = Polish
L9 = Dutch
L11 = Turkish

N. Y. C.
APPROVED

PA05805027K/B For more information visit: [Link]


Fire Pump Controllers 1-1
Features

XTJP / XTJY Jockey Pump Controllers

Typical Jockey Pump Controller Specifications


Languages
Approvals The controller shall be available in a variety of languages
The Jockey Pump Controller shall meet the requirements of including, but not limited to:
UL 508 [Underwriters Laboratories (UL)] and approved by English, French, Spanish, Turkish.
[Canadian Standards Association (CSA)] [New York Depart-
ment of Buildings (NYSB). Digital Indication
The controller shall be supplied with a digital display that shall
Starting Type indicate the following: System Pressure, Start Pressure, Stop
The controller shall be Across-the-Line or Wye-Delta (Star Del- Pressure.
ta) type designed for full voltage starting.
The digital display shall be supplied with a solid-state 4-20mA
Ratings pressure sensor. The pressure Start and Stop points shall be
The Controller shall have a minimum withstand rating of 18,000 adjustable in increments of one (1) PSI.
symmetrical amperes @ [208V] [240V] [380V] [415V] [480V]
[600V] [120V Single Phase] [240V Single Phase]. The digital display shall be a door-mount type that permits
exterior programming with the controller door secured.
The horsepower rating of the controller shall not exceed 50Hp
for three (3) phase units or 10Hp on single phase units. Options
The jockey pump controller shall have provision to be supplied
Construction with the following options:
The controller shall include a combination Circuit
Breaker / Overload Motor Protector. C1 Extra Contacts “ Pump Run”
C2 Extra Contacts “AC Power Failure”
The circuit breaker shall be mechanically interlocked such that E1 NEMA 3R – Raintight Enclosure
the enclosure door cannot be opened when the handle is in the E2 NEMA 4 – Watertight Enclosure
on position except by a tool operated defeater mechanism. E3 NEMA 12 – Industrial Dust Tight Enclosure
E5 NEMA 4X – Stainless Steel Enclosure
The controller manufacturer shall manufacture the contactor, E8 Tropicalization
circuit breaker, pushbuttons, and enclosures. Brand-labeled E9 NEMA 4X - Painted Steel
components will not be accepted. E10 NEMA 4X - 316 Stainless Steel Enclosure
EX Export Crating
Supply Voltage POL “Power On” Light
The jockey pump controller shall be available with the following PRL “Pump Run” Light
supply voltages: P7 Low Suction Pressure Switch and Alarm Pilot Light
P8 Low Suction Shutdown (Requires P7)
A 200-208V 60 Hz P10 Pressure Switch (0-500psi) – Sea Water
B 220-240V 60 Hz R1 Space Heater (120 / 220V)
C 380V 50 / 60 Hz R2 Space Heater c/w Thermostat
D 440-480V 60 Hz R3 Space Heater c/w Humidistat
E 550-600V 60 Hz S Sequential Start
F 415V 50 / 60 Hz T Run Period Timer
G1 120V Single Phase Z Elapsed Run Time Meter
G2 240V Single Phase
Manufacturer
Enclosure The controller shall be of the XTJP Across-the-Line or
The controller shall be housed in a NEMA Type 2 (IEC IP11) XTJY Wye Delta (Star-Delta) type as manufactured by
drip-proof, powder baked finish, freestanding enclosure. EATON Corporation.

Optional Enclosures
1. NEMA 3R (IEC IP14) rain-tight enclosure.
2. NEMA 4 (IEC IP66) watertight enclosure.
3. NEMA 4X (IEC IP66) watertight 304 stainless steel
enclosure.
4. NEMA 4X (IEC IP66) watertight 316 stainless steel
enclosure.
5. NEMA 4X (IEC IP66) watertight corrosion resistant
enclosure.
6. NEMA 12 (IEC IP52) dust-tight enclosure.

Run Period Timer


An optional Run Period Timer shall be available.

March 2012 For more information visit: [Link] PS05805010K


The 8100 Series Fire Pump is designed to provide water to
stand pipe, sprinkler, chemical mitigation and hydrant systems
for fire supression in industrial and commercial facilities.

Features & Benefits


• Available in capacities up to 3,000 GPM (681 m3/hr).
• Pressures up to 255 PSI (179 m)
• In compliance with NFPA #20, UL, ULC, FM and ANSI.
• Performance and hydrostatic tests.
• Dynamic balance impellers.
• Space saving design.
• Easy maintenance and upkeep.
• Available in electric or diesel engine driven models.
• Standard construction: cast iron, bronze fitted.
• Clockwise or counterclockwise rotation is available to
simplify pump room layout.
• Packed stuff box.
• Grease lubrication.
• Available in 50 or 60 cycle.
• Suction and discharge flanges are on a common
centerline.

NOTE: This product is not intended for potable water applications

Fire Pumps
Series 8100

ACFP 8100-05
Series 8100

Basic Construction
Part Name Cast Iron, Bronze Fitted
Pipe Plugs (Casing) Brass
Flush Piping Copper
Pins (Sleeves) 302 Stainless Steel
Packing Glands Bronze (ASTM B584-932)
Packing (Rings) Graphite Impregnated Acrylic Yarn
Casing Assembly Cast Iron (ASTM a48 Class 35A)*
Casing Joint Gasket (Suction) Paper (Vellumoid 505)
Casing Joint Gasket (Discharge) Paper (Vellumoid 505)
Casing Joint Bolts Steel (Grade 5)
Dowel Pins (Casing) Steel
Casing rings Bronze (ASTM B584-932)
Shaft Steel (SAE 1045)
Pump Size
Shaft Sleeves Bronze (ASTM B584-932)
3x2x11F-S
Shaft Sleeve Nuts Bronze (ASTM B584-932)
6x4x9F
Bearing Housing (Inboard) Cast Iron (ASTM a48 Class 25A)
6x4x10F-M
Bearing Housing (Outboard) Cast Iron (ASTM a48 Class 25A)
6x4x11F
Ball Bearing (Inboard) Steel
6x4x12F-M
Ball Bearing (Outboard) Steel
6x6x9F
Stuffing Boxes (Packing) Cast Iron (ASTM a48 Class 25A)
8x6x9F
Deflectors Rubber (Buna “N”)
8x6x10F
Lip Seals (Bearing) Rubber (Buna “N”)
8x6x12F-S
Locknut (Bearing) Steel
8x6x12F-M
Lockwasher (Bearing) Steel
8x6x13F
Set Screws 316 Stainless Steel
8x6x18F
Cap Screw (Bearing Housing) Steel (Grade 2)
8x8x12F
Cap Screw (Gland) Steel (Grade 2)
8x8x17F
Grease Fittings (Bearing) Steel
10x8x17F-S
Pipe Plugs (Bearing Housing) Steel
10x8x17F-L
Key (Impeller) Steel
10x8x20F-S
Key (Coupling) Steel
10x8x20F-L
O-ring (Stuffing Box) Rubber (Buna “N”)
12x10x18F
O-ring (Casing) Rubber (Buna “N”)
O-ring (Shaft Sleeve) Rubber (Buna “N”)
= Pumps that use Steel (SAE 4140) shafts. Spirol Pins (Stuffing Box) 304 Stainless Steel
= Pumps that use TFE Impregnated
Spirol Pins (Casing Ring) 304 Stainless Steel
Acrylic Yarn
* = Casings for pump sizes with “H” prefix Impeller Bronze (ASTM B584-876)
will be made from Ductile Iron (ASTM Seal Cage Teflon
A536 Grade 65-45-12) & Casing Joint
Bolts will be Steel (Grade 8).

Xylem, Inc.
8200 N. Austin Avenue
Morton Grove, Illinois 60053
Phone: (847) 966-3700
Fax: (847) 965-8379
[Link]/brands/acfirepump

Xylem Residential & Commercial Water


a division of Xylem Canada Company
55 Royal Road, Guelph, Ontario
N1H 1T1, Canada
Phone: (519) 821-1900
Fax: (519) 821-5316
A-C Fire Pump is a trademark of Xylem Inc. or one of its subsidiaries.
© 2012 Xylem Inc. ACFP 8100-05 March 2012
Lowara

e-SV Series
TM

stainless steel vertical


multi-stage pumps
Hydraulic performance range
10 100 Q [Imp gpm]

10 100 Q [US gpm]


H [m] H [ft]
300 1000

800

200
600

400
100

200

0 0

06052_B_CH
1 10 100 Q [m3/h]

100 1000 Q [l/min]

extra efficient
The e-SVTM’s newly-designed hydraulics, combined with a high-efficiency motor (IE2)
deliver maximum efficiency.

energy saving
Pumps are among the largest users of industrial energy. Do your part to reduce CO2
emissions and your impact on the environment - and improve your bottom line - by
taking advantage of the new e-SVTM’s lower energy requirement. Use a new e-SVTM pump
along with a variable speed drive such as ITT’s Hydrovar®, and save even more energy
and money.

easy to maintain
The e-SVTM’s new design allows removal of the mechanical seal without having to remove
the motor, reducing repair time by up to 50%.
A standard DIN mechanical seal, wearing components, service tools and standard IEC
motors enable faster and easier maintenance and servicing.
Lowa

Benefits
The e-SVTM range of pumps features 11 models, and can be specially confi
for a wider range of applications. The line is interchangeable with Lowar
series of vertical multi-stage pumps for added flexibility in meeting pu
requirements. Additionally, five e-SVTM manufacturing facilities arou
world provide shorter lead times and faster service.

Applications
Water supply and pressure boosting

Water treatment

Light industry

Irrigation and farming

Heating, ventilation and air-conditioning

Delivery up to 160 m3/h

Head up to 330 m
Specifications

Power supply three-phase and single-phase 50 and 60 Hz

Power standard motors from 0.37 kW to 55 kW

Maximum operating pressure PN25-40 for sizes 1-22SV; PN16, PN25, PN40 for sizes 33-125

Temperature of pumped liquid -30°C to +120°C standard version / up to 150°C in “hot water design”

Protection IP55

Insulation class F

Combination with Hydrovar® and other VFDs (on pumps and Booster Packages)
Lowara

e-SV Series
TM

stainless steel vertical


multi-stage pumps
Why “e”-SVTM? “e” stands for the ultimate in energy efficiency, easy installation and economical operation - a new generation
of vertical, multi-stage pumps that deliver outstanding performance and reliability.
Developed based on intensive research into user needs, the new e-SVTM pumps are designed to extend uptime and help
reduce lifecycle costs in a wide variety of demanding applications.
Superior efficiency
rules the water.
Think about ITT.
Lowara
ITT-Lowara ([Link]), headquarters of "Residential and Commercial
Water - EMEA" part of the ITT Corporation and located in Montecchio Maggiore,
Vicenza - Italy, is a leading manufacturer of hydraulic pumps and water handling
and control systems. It has 1.819 employees in Europe, 675 operating in Italy. In
2009 its consolidated sales totalled about 286 million €, or over 396 million $.
ITT Corporation is a high-technology engineering and manufacturing company
operating on all seven continents in three vital markets: water and fluids
management, global defense and security, and motion and flow control. With a
heritage of innovation, ITT partners with its customers to deliver extraordinary
solutions that create more livable environments, provide protection and safety and
connect our world. Headquartered in White Plains, N.Y., the company generated
2009 revenue of $10.9 billion.

ITT RESIDENTIAL AND COMMERCIAL WATER DIVISION - EMEA


Headquarters
LOWARA S.r.l. Unipersonale
Via Dott. Lombardi, 14
36075 Montecchio Maggiore
Vicenza - Italy
Tel. (+39) 0444 707111
Fax (+39) 0444 492166
e-mail: [Link]@[Link]
http: //[Link]

AUSTRIA IRELAND PORTUGAL


ITT AUSTRIA GmbH ITT IRELAND ITT PORTUGAL, Lda
A-2000 STOCKERAU 50 Broomhill Close Praçeta da Castanheira, 38
Ernst Vogel-Straße 2 Airton Road 4475-019 Barca
Tel. (+43) 02266 604 Tallaght Tel. (+351) 22 9478550
Fax (+43) 02266 65311 DUBLIN 24 Fax (+351) 22 9478570
e-mail: [Link]@[Link] Tel. (+353) 01 4524444 e-mail: [Link]@[Link]
[Link] Fax (+353) 01 4524795 [Link]
e-mail: [Link]@[Link] -
FRANCE [Link] RUSSIA
ITT FRANCE LOWARA RUSSIA
Parc de l'ile NEDERLAND Kalanchevskaya st. 11 b.2, off. 334
29 rue du Port LOWARA NEDERLAND B.V. 107078 Moscow
92022 Nanterre Cedex Zandweistraat 22 Tel. (+7) 495 631 55 15
Tel. (+33) 02 47 88 17 17 4181 CG Waardenburg Fax (+7) 495 631 59 72
Fax (+33) 02 47 88 17 00 Tel. (+31) 0418 65 50 60 [Link]@[Link] - [Link]
e-mail: [Link]@[Link] Fax (+31) 0418 65 50 61
[Link] e-mail: [Link]@[Link] UK
[Link] LOWARA UK LTD.
GERMANY Millwey Rise, Industrial Estate
ITT LOWARA DEUTSCHLAND GmbH POLAND Axminster - Devon EX13 5HU UK
Biebigheimer Straße 12 LOWARA VOGEL POLSKA Sp. z o.o. Tel. (+44) 01297 630200
D-63762 Großostheim PL 57-100 Strzelin Fax (+44) 01297 630270
Tel. (+49) 0 60 26 9 43 - 0 ul. Kazimierza Wielkiego 5 e-mail: lowaraukenquiries@[Link]
Fax (+49) 0 60 26 9 43 - 2 10 Tel. (+48) 071 769 3900 - Fax (+48) 071 769 3909 [Link]
e-mail: [Link]@[Link] e-mail: [Link]@[Link] -
[Link] [Link]

For additional addresses, please visit


[Link]

cod. 191002051 P 07/10

Lowara reserves the right to make modifications


without prior notice.
8200 N. Austin Avenue
Morton Grove, Illinois 60053
Telephone (847) 966-3700
Fax (847) 966-8366
E-mail: Gelhani@[Link]

INTERNATIONAL SALES & MARKETING

From:
George El-Hani
International Sales & Marketing
EMEA

Date: August 15, 2010

MANUFACTURER’S WARRANTY CERTIFICATE

This is to certify that ITT A-C Products are under warranty for 12 months
from the date of testing & commissioning.

The A-C company is certified to ISO 9001:2000 Quality management system


by LPC-B of United States on Certification # 125.

We thank you for your understanding and for choosing ITT A-C products.

Thank you & Best Regards,


GeorgeElHani
Regional Sales Manager
EMEA
8200 N. Austin Avenue
Morton Grove, Illinois 60053
Telephone (847) 966-3700
Fax (847) 966-8366
E-mail: Gelhani@[Link]

INTERNATIONAL SALES & MARKETING

From:
George El-Hani
International Sales & Marketing
EMEA

Date: Jun 27, 2012

MANUFACTURER’S CERTIFICATE OF ORIGIN

This is to certify that ITT A-C Products are produced in the United States of
America by ITT A-C Company. The ITT A-C Company does hereby certify that
the ITT A-C product (s) are of our manufacture and in full compliance with all
test, calibration, and inspection specifications of the ITT A-C company quality
assurance program.

The A-C company is certified to ISO 9001:2000 Quality management system by


LPC-B of United States on Certification # 125.

We thank you for your understanding and for choosing ITT A-C products.

Thank you & Best Regards,


GeorgeElHani
Regional Sales Manager
EMEA
TABLE OF CONTENTS

Morex, Inc. Overview


Introduction ………………………………………………………….. 3
Mission Statement ………………………………………………. 3

Locations
Head Office ……………………………………………………… 4
Branches and Managed Operations………………………………. 4-6
Agents …………………………………………………………... 6

Products
HVAC Equipment ………………………………………………. 7-8
Fire Fighting Equipment ………………………………………... 9-10
Industrial Equipment ……………………………………………. 11-12

Marketing
Exhibitions ……………………………………………………… 13
Seminars ………………………………………………………… 13
Awards Received ………………………………………………… 14

Services
At Tendering ……………………………………………………. 15
When Order is Placed …………………………………………... 15
After Delivery to Site …………………………………………… 15

Software
In - House Developed Software ………………………………… 16

Projects ……………………………………………………………….. 17-19

2
Morex, Inc. Overview

Introduction

Founded in 1986 by Rudolph Mazigi in Brookfield, Connecticut and relocated to


Charlotte, North Carolina in September 1996, Morex, Inc., is a full service
manufacturer representative company for heating, ventilating, air conditioning
(HVAC), fire fighting products and industrial equipment.

Morex, Inc.’s expertise is in international marketing and its service the Middle
East region.

Mission Statement
Our commitment is to supply the best Engineered products in the industry. Our
goal is to continuously expand our market coverage while maintaining the quality
of service we provide our suppliers and customers. Our facilities and staff of
multilingual professionals, together with our managed operations and agents in the
Middle East, maintain our reputation as one of the leading companies in our field.

3
Locations

Head Office

Our head office and 10,000 square foot warehouse are located in Charlotte, North
Carolina:

1609 Cross Beam Drive


Charlotte, NC 28217
U.S.A

Telephone #: (704) 423 - 0102


Fax #: (704) 423 - 0320
E-Mail: sales@[Link]
Web Site: [Link]

Branches and Managed Operations

Morex, Inc. achieves effective Middle East coverage in high business volume
markets by establishing branches or managed operations under the sponsorship of
prominent local companies. These operations are located as follows:

x Amman, Jordan
Morex, Inc. - Jordan
P.O. Box 142531
Amman 11844, Jordan
Tel :(011)-962-6582-2740
Fax:(011)-962-6582-2742
E-Mail: jordanoffice@[Link]
Mr. Subhi Souri, branch manager

x Riyadh
A.S.E.M. / Morex, Inc.
P.O. Box 235
Riyadh 11371, Saudi Arabia
Tel :(011)-966-1-473-0030
Fax:(011)-966-1-472-2875
E-Mail: asemryd@[Link]
Mr. Majdi Hakim, branch manager

4
Locations (Cont’d)
x Jeddah
A.S.E.M./ Morex, Inc
P.O. Box 118189
Jeddah 21312, Saudi Arabia
Tel:(011)-966-2-6510124
Fax:(011)-966-2-6516445
E-Mail: asemjed@[Link]
Mr. Fuad Hussein, branch manager

x Al Khobar
A.S.E.M./ Morex, Inc
P.O. Box 20843
Al-Khobar 31952, Saudi Arabia
Tel :(011)-966-3-864-5357
Fax:(011)-966-3-897-0602
E-Mail: asemkbr@[Link]
Mr. Ali Haidar, branch manager

x Kuwait
Atlas Blue General Trading & Cont. Est /Morex, Inc
P.O. Box 2914
Safat 13030, Kuwait
Tel :(011)-965-241-8547
Fax:(011)-965-240-7910
E-Mail: atlas@[Link]
Mr. Hussam Bashir, branch manager

x Iraq
Morex International
P.O. Box 3054, Al-Ilweiya
Baghdad, Iraq
Tel:(011)-964-718-1194
Fax:(011)-964-717-5591 E-Mail: iraqoffice@[Link]
Mr. Shlimon Zaya, branch manager

x United Arab Emirates


Morex Inc. – UAE Branch
Dubai Airport Free Zone
P.O. Box 54751 Dubai, U.A.E.
Tel:(011)-971-4-214-9622
Fax:(011)-971-4-214-9720 E-Mail: dubaioffice@[Link]
Mr. Muhammad Abu Safieh, branch manager

5
x Pakistan
Morex Inc. - Pakistan
Suite:707 Anum Blessing, Block 7/8 [Link], KCHS
Shahrah-e-faisal, Karachi - Pakistan
Tel:(011)-92-21-432-5270
Fax:(011)-92-21-432-5271 E-Mail: karachioffice@[Link]
Mr. Junaid Alam, branch manager

Agents
Locations in the Middle East where we have not established branch offices or our
own managed operations are covered through agents that distribute some of our
products in specific regions. These companies were selected for their excellent
market penetration and their involvement with the HVAC and fire fighting
business for many years and are well connected with the business community and
local Government.
These agents are located in Egypt, Lebanon, United Arab Emirates and Bahrain. A
list of their names and addresses is available upon request.

6
Products

HVAC Equipment

x ITT Bell & Gossett


x ITT McDonnell & Miller
Centrifugal Pumps: In-Line, End-Suction,
Split Case, Single and Double Suction,
Pressure Boosters, Variable Speed.
Hydronic Specialties: Expansion Tanks,
Balancing Valves, Air Vents, Relief Valves,
Suction Diffusers.
Heat Exchangers: Liquid to Liquid, Steam to
Liquid, Plate Type, Straight and “U” Design.
Controls:. Steam Traps & Regulators, Flow
Switches, Boiler Controls.

x Hurst Boiler & Welding Co., Inc.


Steam and Hot Water Boilers, Gas, Oil and
Combination Fired, Feedwater Units, Controls
and Accessories.

x Hubbell Electric Heater Co.


Residential , Commercial and Industrial
Electric Hot Water Heaters, Instantaneous and
Storage type, Cement and Copper Lining.

x Ormandy
Storage type Water Calorifiers – Copper Lining.

x Acme Engineering & Mfg Corp.


Commercial and Industrial Fans, Ceiling and
Cabinet type, Industrial Process Fans, Heavy
Duty Industrial Fans, Air Handling Fans, Wall
Fans, Roof Exhaust and Supply Fans, Roof
Curbs, Intake & Relief Hoods.

x Vent-Axia
Twin Fans, Plastic Propeller Wall and Ceiling
Fans.

7
Products (HVAC Equipment Cont’d)

x Camfil – Farr Company


Air Filters, High Efficiency Hepa Type, Bag
Filters, Disposable and Washable Prefilters,
Activated Carbon Filters for Gas and Odor
Adsorption, Filter Holding Frames and Side-
Servicing Housings, Self-Cleaning Inertial
Separators, Air Filter Gauges.

x Anemostat
Grille, Registers and Diffusers, VAV Boxes.

x PCI Industries - Pottorff


Control Dampers, Backdraft Dampers, Fire
and Smoke Dampers, Architectural, Acoustical
Louvers and Penthouses.

x Other HVAC Equipment


- Herrmidifier:
Commercial and Industrial Humidifiers.
- Brasch Mfg. Co.:
Electric Duct Heaters.
- Dynasonics:
Sound Attenuators and Duct Silencers.
- Hammond Valves:
Valves.
- H.O. Trerice Co.:
Pressure and Temperature Gauges.
- Vibration Eliminator Co.:
Vibration Isolators, Seismic Controls.

8
Products

Fire Fighting Equipment

x ITT A-C Pumps


Fire Pumps, U.L. Listed and FM approved,
Horizontal Split Case, Vertical Fire Pump
Systems, Electric and Diesel Driven, Vertical
Turbine and In-Line Fire Pumps, Jockey
Pumps, Fire Pump Controls, Fittings and
Accessories.

x Mueller Co.
x United Brass Co.
x Sure-Test
UL Listed and FM approved all types of Fire
Protection Valves, Fire Hydrants, Gate Valves,
IBBM Gate Valves, Check Valves, Tapping
Material and Post Indicators, Inspectors Test
& Drain, “Y” Strainers.

x National Fittings Co.


Complete line of UL Listed and FM approved
Grooved Couplings, Cast Iron and Ductile Iron
for Fire Sprinkler System.

9
Products (Fire Fighting Cont’d)

x OCV Control Valves


UL Listed and FM approved Fire Fighting
Control Valves, PRV’s and Deluge Valves.

x Potter Electric
UL Listed and FM approved Sprinkler
Monitoring Devices, Flow Switches, Pressure
Switches, Bells, Tamper and Supervisory
Switches and Releasing Panels.

x Other Fire Fighting


Equipment
Pipe Hangers, Bulb Type Sprinklers, Alarm
Check Valves, Dry Pipe Valves, Grooved
Check Valves, Fire & Smoke Dampers.

10
Products

Industrial Equipment

x Hyspan Precision Products


x Barco
Metallic Expansion and Ball Joints for
Building Heating and Cooling Systems,
Power, Process, Industrial and Petrochemical
Applications.

x Pennram Diversified
Manufacturing Corp.
Incinerators for Municipal, Medical, Liquid
Waste, Pathological and Industrial
Applications.

x LFG&E International
Specializing in Design Solutions for Landfill
Gases and Manufacturing of Landfill Gas
Power Generation.

11


     

      
Marketing

Our marketing approach is multi-faceted. By establishing our own branches and


managed operations we achieve the control needed to maximize our market
coverage. We maintain close contacts with engineers and contractors, promptly
handle all inquiries and technical data requests, participate in exhibitions and
conducts seminars, and our engineers visit the area on a regular basis.

Seminars
We conduct seminars for engineers
and contractors to introduce new
products and/or technology.

(Picture of seminar
conducted in joint
participation with ITT Bell &
Gossett to introduce the
Variable Speed Pumps in
Riyadh, Saudi Arabia)

Exhibitions
Morex, Inc. regularly Participates in
exhibitions in the Middle East
jointly with our sponsors and agents.

(Picture of exhibition in
Riyadh, Saudi Arabia)

13
Marketing (Cont’d)

Awards
As a result of our successful
marketing, Morex, Inc has earned
numerous awards through the years
for highest sales achievement from
our vendors.

(Picture of Mr. Lee Buddrus


of Acme Engineering & Mfg.
Corp delivering the award to
the Morex Staff )

List of Awards

1991 Sales Representative of the Year – Herrmidifier


1992 Sales Representative of the Year – Herrmidifier
1996 Outstanding Sales – Acme Engineering & Mfg Corp.
1996 Quota Buster – ITT A-C Pump
1996 Quota Buster – Farr Co.
1997 Top Gun – Acme Engineering & Mfg Corp.
1998 Outstanding Sales Achievement – Acme Engineering & Mfg Corp.
1999 Top Sales – Acme Engineering & Mfg Corp.
2000 Top Sales – Acme Engineering & Mfg Corp.
2000 Goal Breaking Sales – Wessels
2001 Fire Pump Quota Buster – ITT A-C Pump.
2002 Marketing Excellence – Eriez Manufacturing Co.
2002 Outstanding International Sales Achievement – Hurst Boiler

14
Services

At Tendering:
x Prompt handling of all
quotations requests.

x Bill of material take - off.

x Complete technical
submittals.

When Order is Placed:

x Storage of equipment at no
additional charge.

x Equipment consolidation to
minimize shipping costs.

x Export crating.

x Equipment inspection.

x Export documentation.

x Financing for qualified


buyers.

After Delivery to Site:

x Commissioning and start - up services available.

x Product warranty.

15
Software

In - House Developed
Software

Morex, Inc. has developed its


own software, Morex HVAC
Works, in order to
expedite quotation and
product information to the
customer and save employee
time. This, in turn, allows us
to lower our costs and be
very competitive.
Morex HVAC Works will do
equipment selection, pricing
and submittals. In Addition, the program will track projects,
automate quotation follow-up, provide expedient order entry and
export documentation, monitor order progress and profitability, and
alarm management in case of problems. E-mail has been integrated
so that generated quotations can be transmitted directly to the
customer without leaving the software.
Morex HVAC Works is also made available to our agents and is
customized to handle their particular needs.
The same program is also available on line over the Internet so that our engineers
can access their work from any location and quotations and orders can be
transmitted directly via the Internet.

16
Projects

Morex, Inc has supplied Engineered Products to a very large number of projects.
Following is a partial list of the projects supplied.

100-BED Hospital Aramco Medical Dental Clinic


40 Grand Hotel Jeddah Arcent Zone I, II & III
870 Room Hotel at Le Meridien As-Samra Wastewater
Abqaiq Support Facilities Stabilization
Acacia Taba Resort Aswan Hospital
Aden International Airport Ataka Pumping Station-Cairo
Adnoc Borouge Pe Project Awqaf Tower
Ajyad Car Park - Makkah Bank of Housing
Al Attar Tower Bank of Jordan
Al Haram Hotel, Madinah Bayan Palace
Al Haram-Ii-Sub-Station Beach Palace
Al Hodaifi Tower Bidah Plaza
Al Salamah Hospital - Jeddah Boubyan Factory
Al-Ahram Adm BLDG. Buraydah Maternity Hospital
Al-Diyafah Shopping Mall Burgan Bank
Al-Faisaliah Centre for King F Cairo Airport
Al-Hamrani Commercial Center Casino Du Liban Phase 2
Al-Haram Shopping Mall Central Plant in Kuwait Univ.
Al-Hasa Hospital Coast Guard Headquarters
Al-Jazzara Factory College of Legal Studies/Kuwait
Al-Jizan Project College of Technical Studies
Al-Khereiji Bldg. - Jeddah Colleges of Social Sciences
Al-Khozama Tower - Jeddah Commercial Dev. Ctr - Jumeirah
Al-Mada Health Club Conference Center
Al-Marai HQ Bldg Conoco Gas Plant
Al-Nakheel Village Country Lodge II
Al-Rashid Towers Jeddah Dammam Girl's College
Al-Razi Pharmaceutical Complex Dar Al Fikr College
Al-Safi Towers (Site-C) Darualaman Battalion Kandak 14
Al-Salama Hospital - Jeddah & 15, Kabul
Al-Sharq Waterfront Doha Campus Headquarters
Al-Tameer Center Edible Oil Factory
Amiri Diwan Package 19 Kuwait El Ahram Administration Bldg
Amoc Project El Gouna Golf, Red Sea
Aqaba Bridge Hotel Enlisted Men Housing
Arabian Printing Press European Egyptian Parmaceutical
Aramco Core Area Annex Bldg F-16 Depot Facilities
Aramco Head Office Retrofit Fahaheel Towers

17
Projects (Cont’d)

Four Seasons Hotel-Amman Madina Hilton Hotel


Four Seasons Hotel-Sharm El Madinah and Yanbu Water
Sheikh Transmission
FY00/01 Navy Milcon, Operations Makkah Hotel
FY97 Mca Phase II - Qatar Mercedes Showroom
FY98 Army Milcon Meridian Hotel, Egypt
FY98 Mca Phase III - Qatar Middle East Battery Co
G100 Hospitals - Khafji/Rafha Mina Project
Ghazlan II Power Plant Ministry of Education
Gizan Airport Mobile Telecom Co.
Golden Pyramids Plaza Ph-I Moda
Gulf Packaging - Bopp Film Plant Modern Products Factory
Hadeed Fire Protection System Movenpick Hotel
Hail Power Plant MSO-Building-Aramco
Haram Fire Fighting Navy Milcon Pro Adm Support
Hasa Factory New US Embassy Nairobi, Kenya
Hasa Hospital New US Embassy DES, Tanzania
Hawiyah Gas Plant Support Facility New US Embassy Zagreb, Croatia
Hayel Hospital New US Embassy Istanbul,
Hilton Resort Turkey
Hilton Taba New US Embassy Dubai, UAE
Institute of Public Admin. New US Embassy Yerev, Armenia
Jamjoom Pharmacutical Factory New US Embassy Sofia, Bulgaria
Jeddah Continental School New US Embassy Ivory Coast
Jeddah Sheraton Hotel Peace Shield Project
King Abdul Aziz Hospital Alhasa Peace Vector Projects, Ph4 & Ph6
King Abdul Aziz Specialized Paper Mill, Khobar- Saudi Arabia
Hospital Petrokemya Olefins III Project
King Faisal University - College Pharma House - Kuwait
King Khalid University Hospital Pharmaceutical Plant, Riyadh
King Saud Hospital Phoenicia Hotel-Lebanon
Kingdom Trade Center Plot 168 - Medinah
KKMC Airport Plot 130 - Hotel & Complex
KOC-Utility Building Plot 131 & 136 Hotels & Complex
KU-College of Health Plot 145 - Medina
Kuwait University Central Plan Plot 169
Kuwait-Central Plant University Police Officers Club
Lab R&D Center Phases I & II Power Plant PP-8
Landmark Project Prince Salman Handicap Children
Qaseem Power Plant Extension

18
Projects (Cont’d)

Qassim Imara Palace Taba and Zefta Hospitals


Qatar Flour Mills Taba Beach Resort
Qahi Ext’n./Jordan Armed Forces Tabouk Power Plant
Qibla, FWF and GMC Tabuk Cement Plant
Showrooms Taif Hospital
QVC Qatar Vinyl Project TD 196 Dubai International Air
Rabigh Steam Power Plant Tunnel Dampers-Makkah
Rafha Power Plant U.S. Embassy Warehouse, Cairo
Ras Laffan Common Cooling Umm Al-Qura University – Phase
Systems USAID Annex Lima, Peru
Rastanura Refinery Upgrade US Embassy Jordan
Riyadh Power Plant PP-9 US Embassy Staff Housing-Kuwait
Riyadh Refinery - Aramco US Embassy-Kuwait
Riyadh Refinery Extension US Aid Water Transfer Project
Royal Commission Schools Warehouse Contruction FY96 Mca
Royal Plaza at Al Sadd Water Treatment Plant
Saad Oasis Hospital BLK-B Western Ammunition Workshop
Sabah Adult Psychiatric Hospital Women's Medical College
Sabg Girls & Boys Schools- Dam Yanbu-Madina Pipe Line
Sabic R&D LAB2 Yanpet Expansion
Sabiya Power Station Yanpet Housing
Safco Ammonia - Urea Project Zam Zam Cooling /Water Prophet
Safi Towers, Madinah Zara 1 Tower, Amman
Saudi Yanbu Petrochemical
Comp
Saudi-Aramco General
Sceco H.Q. Office Bldg.
Sea Water Cooling Expansion
Sheikh Ibrahim Bldg in Makkah
Shoaibah Power Plant
Shohada Hotel, Mekka
Social Security Project
STC-Makkah (Al-Shara
Warehse)
Stores/Us Forces Ammunition
Swiss Hotel Sharm El-Sheikh

19

Common questions

Powered by AI

The use of a jockey pump alongside the main fire pump provides several advantages in fire pump systems. It helps maintain the system's pressure, compensating for small leaks and ensuring the main fire pump is not unnecessarily activated. A jockey pump's presence ensures the main fire pump operates efficiently and prolongs its lifespan by reducing unnecessary wear. It is vital for maintaining steady pressure in the fire protection system, readying the system for high-demand scenarios without triggering the main pump .

LED indicators are essential in fire pump systems for real-time monitoring and diagnostics. They visually alert operators to conditions such as phase reversal, phase failure, common alarms, and pump operation states. LEDs provide instant feedback, enabling quick response to malfunctions or issues that require attention. This immediate visibility contributes significantly to operational safety by ensuring any anomalies can be swiftly identified and addressed, minimizing risks associated with system failures .

The Xylem A-C Series 8100 fire pump is designed with a dynamically balanced, enclosed double-suction impeller made of bronze, a cast iron casing with a suction and discharge gauge ports, and heavy-duty base mounts for stability. It uses grease-lubricated steel bearings and features a stuffing box design, ensuring efficient performance under exigent conditions. The use of materials like ASTM A48 Class 25A and ASTM B584 for different components adds to the pump's robustness and reliability in fire safety applications .

The fire pump components are constructed from durable materials such as ASTM A48 Class 35A cast iron for the casing assembly, ASTM B584-875 bronze for the impeller, and alloy steel SAE 1045 for the shaft. These materials are chosen for their strength and corrosion resistance, ensuring long operational life and adherence to safety standards such as NFPA-20, UL, and FM. They provide the necessary balance between structural integrity and the ability to withstand high-pressure conditions .

The inclusion of a pressure transducer in a jockey pump controller enhances its functionality by allowing precise control over the start and stop pressures. It provides solid-state accuracy in pressure readings, directly influencing the system to maintain the desired pressure levels more efficiently. This real-time adaptability is crucial for pressure adjustments in increments as fine as 1 PSI, ensuring the entire fire suppression system consistently operates at optimal levels .

Remote alarm panels play a critical role in maintaining fire pump safety by providing audible and visual alerts for various conditions, such as power failure and common alarms. These panels are microprocessor-controlled and allow for real-time monitoring and response to the pump system's operational status. Features like the lamp test button and the silence alarm button ensure the ongoing functionality of alarms without altering their configurations, ensuring that any operational anomalies are promptly reported even if not under constant supervision .

The fire pump control system uses a Cutler Hammer Electric Motor Driven Controller equipped with interlock and shutdown circuits managed by a digital display system. It includes features such as automatic or manual reset, LED functionality testing, and pressure sensor adjustments via a 4-20mA sensor with increments of 1 PSI. The system supports three standard languages and provides customizable future inputs/outputs, enhancing operational efficiency and safety by accommodating various alarm scenarios and user-selected settings .

The fire pump controller offers both manual and automatic system resets to ensure that the pump can be adjusted quickly to safe operating conditions. Automatic resets allow for uninterrupted operation when transient conditions normalize, reducing downtime. Manual resets provide a safeguard by requiring human intervention to verify and resolve persistent issues, ensuring safety through deliberate oversight. These provisions are important as they balance operational efficiency with safety concerns, enabling quick recovery and the ability to address any underlying issues .

Key construction elements that ensure the robustness and reliability of the fire pump include the use of ASTM A48 Class 35A cast iron for casing assembly, interconnected by dynamically balanced impellers, bronze ASTM B584 for important components like the impeller and sleeve, and grease-lubricated steel bearings. The solid construction allows it to withstand high pressures, minimize wear, and facilitate easier maintenance .

The Xylem A-C Series 8100 fire pump has a flow capacity of 1250 GPM and a head of 185 PSI. It is manufactured from materials such as cast iron, bronze, and steel, ensuring durability and performance. This series is UL-listed, FM-approved and meets NFPA-20 standards, supporting not less than 150% of rated capacity at a pressure not less than 65% of rated pressure. The pump's shut-off pressure does not exceed 120% of rated pressure, and it has a maximum working pressure of 225 PSIG, with a hydrostatic test pressure of up to 375 PSIG .