ENGINEERING
DATA
CONTENT
Introduction 1
Features & Benefits 2
How It Works 3
Nomenclature 3
Typical Installation 4
Overall Dimension 5
Electrical Wiring 6
Technical Data 8
INTRODUCTION
The Company
Citec International is one of the global leaders in designing and manufacturing
precision air-conditioning system. Citec International places great emphasis on
achieving the highest standards and incorporates stringent quality controls throughout
its operations. Every CITEC product is designed and built within a Quality
Management System ISO9001 and Environmental Management System ISO14001,
using our unrivalled experience in Precision Air Conditioning, with extensive testing
of components and complete systems. Every aspect is engineered to ensure maximum
reliability, economy of operation and long working life, together with ease of
installation and maintenance.
The Product
The Citec Assist Flow CAF fan tile units are the latest innovative product from Citec
International that designed to assist in airflow management of data center with raised
flooring. The CAF units consist of one or multiple fans that draw cold air from the
underfloor and provide adequate airflow to the high density racks. Thus with CAF
units installed, airflow required is guaranteed and hot spot can be eliminated.
The Citec CAF unit is to be installed on the raised floor structure replacing perforated
tile. The unit can be placed directly on the 4 columns and stringers. Citec CAF
comprises of eight models with up to 4 fans per unit and two types of fan. Nominal air
flow ranged from 850m³/hr to 3,400m³/hr.
~1~
FEATURES AND BENEFITS
Fans: The unit can be fitted with AC fans or EC fans. EC Fan Cartridge: Can fit in 2 fans per
fans are highly energy efficient with variable speed feature cartridge and up to 2 cartridges per
while AC fans are cost effective and to be coupled with fan unit. Both cartridges have separate
speed controller to enable airflow control. Maximum up to power supply connection, thus one of
4 fans can be fitted to the unit for large airflow application the cartridges can be removed without
as well as for great redundancy. affecting the other cartridge.
Controller and Fan
On/Off Switch: The
controller will
intelligently control
the fan speed
according to the
Control MCB:
measurement of the
Control circuit is
temperature sensor
protected by a MCB
at the rack. Alarms
which accessible
will be triggered to
from the top by
alert the users In the
removing the cover.
event of abnormal
operation. The
operation of fan
cartridge can be turn
on/off with the Grille: Solid and
switches next to the rigid heavy duty
controller. aluminium grille
with > 60% free area
ensure minimum
airflow restriction.
IEC C13 Socket: The
Casing: 18 gauge unit is fitted with IEC
galvanised steel casing C13 socket for easy
with high quality power connection.
powder coating.
~2~
HOW IT WORKS
CAF unit shall be placed in front
of equipment rack. A
temperature sensor connected to
the CAF controller shall be
placed at the top of the rack.
During operation, CAF
controller will regulate the fan
speed to ensure there is enough
cold air delivered to the top of
the rack. If the temperature
sensor sense higher temperature,
the fan speed will be increased to
draw more cold air from under
floor. While if the temperature
sensor senses lower temperature,
the fan speed will be decreased
to preserve energy usage.
NOMENCLATURE
CAF 4 A
A ± AC Fan(s)
E ± EC Fan(s)
CAF ± Citec Assist Flow
No. of fans ± from 1 to 4
~3~
TYPICAL INSTALLATION
min. 150mm
~4~
OVERALL DIMENSION
EC Fan Version
569
573
133
164
14 5
246
516 54
AC Fan Version
569
573
133
516
~5~
ELECTRICAL WIRING
EC Fan Version
L
N
E
0.75mm2 Q1
A1
F1
230V 0V G0 Y2 B1 GND
6 7 14 13 8 10
2 2
RED 0.75mm
2
BLK 0.75mm
RED 0.75mm
2
2 CORE 1.5mm 2
BK 0.75mm
N BLK
L
T1
S1
WH
V+ V+ V- V-
2C 13
BR BR WH WH
1A 2C 1B 2D
2 CORE 1.5mm 2
2 CORE 1.5mm 2
1A 1B 2C 2D
SW1 SW1 SW2 SW2
BR WH BR WH
13 13 13 13
2
2
2
2
BL 0.75mm
BL 0.75mm
BL 0.75mm
BL 0.75mm
RD BL YE RD BL YE RD BL YE RD BL YE
0-10V
0-10V
0-10V
0-10V
GND
GND
GND
GND
+
+
+
+
M1 M2 M3 M4
Item Description
Q1 Main System MCB, SP, 6A
F1 Control Fuse, 3A
S1 Temperature Sensor, NTC
A1 Controller
T1 DC Power Supply
SW1 Fan 1 On/Off Switch, DPST
SW2 Fan 2 On/Off Switch, DPST
M1 Fan Motor Interface 1
M2 Fan Motor Interface 2
M3 Fan Motor Interface 3
M4 Fan Motor Interface 4
~6~
AC Fan Version
L
N
E
0.75mm2
A1
F1
Q1 230V 0V G0 Y2 B1 GND
6 7 14 13 8 10
2
RED 0.75mm
2
BK 0.75mm
BLK
B1
2
2 CORE 0.75mm
S1
BR WH
WH
BR
50 51 WH
50 51
BR WH BR WH
2
2
2 CORE 0.75mm
2 CORE 0.75mm
SW1 SW2
BK1 BK2 G/Y BK1 BK2 G/Y BK1 BK2 G/Y BK1 BK2 G/Y
M1A M1B M1C M2A M2B M2C M3A M3B M3C M4A M4B M4C
2
2
2
2
3 CORE 0.75mm
3 CORE 0.75mm
3 CORE 0.75mm
3 CORE 0.75mm
BK1 BK2 G/Y BK1 BK2 G/Y BK1 BK2 G/Y BK1 BK2 G/Y
L N PE L N PE L N PE L N PE
M1 M2 M3 M4
Item Description
Q1 Main System MCB, SP, 6A
F1 Control Fuse, 3A
S1 Temperature Sensor, NTC
A1 Controller
B1 Fan Speed Controller
SW1 Fan 1 On/Off Switch, DPST
SW2 Fan 2 On/Off Switch, DPST
M1 Fan Motor Interface 1
M2 Fan Motor Interface 2
M3 Fan Motor Interface 3
M4 Fan Motor Interface 4
~7~
TECHNICAL DATA
EC Fan Version
Unit Model CAF1E CAF2E CAF3E CAF4E
Maximum Airflow m³/h 850 1700 2550 3400
Fan Type EC Axial EC Axial EC Axial EC Axial
No. of fan(s) 1 2 3 4
Max. Power Consumption W 110 180 270 360
Rated Current A 0.6 1.0 1.5 2.0
Weight kg 21 23 25 27
AC Fan Version
Unit Model CAF1A CAF2A CAF3A CAF4A
Maximum Airflow m³/h 735 1470 2205 2940
Fan Type AC Axial AC Axial AC Axial AC Axial
No. of fan(s) 1 2 3 4
Max. Power Consumption W 127 208 312 416
Rated Current A 0.7 1.3 2.0 2.6
Weight kg 20 22 24 26
Note:
1. Data is based on 230V/1Ph/50Hz.
'XHWRRXUSROLF\RIFRQWLQXHVGHYHORSPHQWDQGLPSURYHPHQWWKHVSHFL¿FDWLRQVDQGGDWDKHUHLQDUHVXEMHFWWRFKDQJHZLWKRXWSrior
notice. We must therefore reserve the right to supply equipment that may differ from that described and illustrated herein. All
information, including illustrations, contained in this brochure, is believed to be accurate and reliable. Users, however, should
independently evaluate the suitability of each product for their own application. CITEC makes no warranties as to the accuracy or
completeness of the information, and disclaims any liability regarding its use.
~8~
~9~
Version 2.1/2016/CAF