Understanding Transformer Core Saturation

Core saturation occurs when a transformer's magnetic core reaches its maximum flux density and can no longer support additional magnetic field increases. This causes distortions in the voltage waveforms from primary to secondary windings. Special transformers called peaking transformers exploit core saturation to produce voltage pulses. Operating a transformer designed for 60 Hz at a lower 50 Hz frequency or having DC current in the primary winding can also cause the core to saturate by pushing the flux closer to or beyond its limits. Proper transformer design aims to keep flux densities well below saturation levels to avoid these issues.

Uploaded by

HRM, BAPEX
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
550 views3 pages

Understanding Transformer Core Saturation

Core saturation occurs when a transformer's magnetic core reaches its maximum flux density and can no longer support additional magnetic field increases. This causes distortions in the voltage waveforms from primary to secondary windings. Special transformers called peaking transformers exploit core saturation to produce voltage pulses. Operating a transformer designed for 60 Hz at a lower 50 Hz frequency or having DC current in the primary winding can also cause the core to saturate by pushing the flux closer to or beyond its limits. Proper transformer design aims to keep flux densities well below saturation levels to avoid these issues.

Uploaded by

HRM, BAPEX
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd

Core saturation

Transformers are also constrained in their performance by the magnetic flux limitations of the core. For
ferromagnetic core transformers, we must be mindful of the saturation limits of the core. Remember that
ferromagnetic materials cannot support infinite magnetic flux densities: they tend to "saturate" at a certain
level (dictated by the material and core dimensions), meaning that further increases in magnetic field
force (mmf) do not result in proportional increases in magnetic field flux (Φ).

When a transformer's primary winding is overloaded from excessive applied voltage, the core flux may
reach saturation levels during peak moments of the AC sinewave cycle. If this happens, the voltage
induced in the secondary winding will no longer match the wave-shape as the voltage powering the
primary coil. In other words, the overloaded transformer will distort the waveshape from primary to
secondary windings, creating harmonics in the secondary winding's output. As we discussed before,
harmonic content in AC power systems typically causes problems.

Special transformers known as peaking transformers exploit this principle to produce brief voltage pulses
near the peaks of the source voltage waveform. The core is designed to saturate quickly and sharply, at
voltage levels well below peak. This results in a severely cropped sine-wave flux waveform, and
secondary voltage pulses only when the flux is changing (below saturation levels):

Another cause of abnormal transformer core saturation is operation at frequencies lower than normal. For
example, if a power transformer designed to operate at 60 Hz is forced to operate at 50 Hz instead, the
flux must reach greater peak levels than before in order to produce the same opposing voltage needed to
balance against the source voltage. This is true even if the source voltage is the same as before.
Since instantaneous winding voltage is proportional to the instantaneous magnetic flux's rate of change in
a transformer, a voltage waveform reaching the same peak value, but taking a longer amount of time to
complete each half-cycle, demands that the flux maintain the same rate of change as before, but for
longer periods of time. Thus, if the flux has to climb at the same rate as before, but for longer periods of
time, it will climb to a greater peak value.

Mathematically, this is another example of calculus in action. Because the voltage is proportional to the
flux's rate-of-change, we say that the voltage waveform is the derivative of the flux waveform, "derivative"
being that calculus operation defining one mathematical function (waveform) in terms of the rate-of-
change of another. If we take the opposite perspective, though, and relate the original waveform to its
derivative, we may call the original waveform the integral of the derivative waveform. In this case, the
voltage waveform is the derivative of the flux waveform, and the flux waveform is the integral of the
voltage waveform.

The integral of any mathematical function is proportional to the area accumulated underneath the curve of
that function. Since each half-cycle of the 50 Hz waveform accumulates more area between it and the
zero line of the graph than the 60 Hz waveform will -- and we know that the magnetic flux is the integral of
the voltage -- the flux will attain higher values:
Yet another cause of transformer saturation is the presence of DC current in the primary winding. Any
amount of DC voltage dropped across the primary winding of a transformer will cause additional magnetic
flux in the core. This additional flux "bias" or "offset" will push the alternating flux waveform closer to
saturation in one half-cycle than the other:

For most transformers, core saturation is a very undesirable effect, and it is avoided through good design:
engineering the windings and core so that magnetic flux densities remain well below the saturation levels.
This ensures that the relationship between mmf and Φ is more linear throughout the flux cycle, which is
good because it makes for less distortion in the magnetization current waveform. Also, engineering the
core for low flux densities provides a safe margin between the normal flux peaks and the core saturation
limits to accommodate occasional, abnormal conditions such as frequency variation and DC offset.