HT Meter Setting
HT Meter Setting
Features
damage caused by incorrect or non-application of any of the · Accuracy class 1 as per IEC 62053-21, class 0.5, 0.5S, 0.2, 0.2S as per IEC 62053-22
instructions attached herein. Under no circumstance shall · True RMS measurement
Larsen & Toubro be liable for any consequential or resulting
injury or for loss, damage or expense directly or indirectly from · Password protection provision
the use of this product. Sufficient care is taken to provide all · OLD registers to store the previously cleared energy value and Load hours
information regarding the product but Larsen & Toubro does · High / Low V, A, Hz, W, VA, VAr, PF
not claim any responsibility for the damage caused by using the
product directly or indirectly. Use according to the operating · Auto-scaling of Kilo, Mega & Giga value
instructions, professional practices, wiring rules, codes, safety · THD for Voltage and Current
regulations applicable to the given installation. · Site selectable for 3 phase 4 wire, 3 phase 3 wire, 1 phase
Digital Panel Meter · Site programmable CT/PT ratio
During normal operation of this instrument ,hazardous voltages · Maximum demand measurement with real time clock in 4440 series
Multifunction Meter are present at the rear terminals, which can cause injury or · Direct access key for Basic parameters, Power and Energy parameters
Installation ,disconnection or removal of the meter should be
44XX Series LED Type carried out only by qualified, trained personnel, after de-
· Autoscrolling & freeze mode provision is available
energizing connected circuits. Improper installation , including · Terminals with sealing provision (optional)
improper grounding will void warranty. Product warranty void if
seal is broken.
2. Technical Specification
3 Ph 4 W, 3 Ph 3 W, 1 Ph Fast transients burst test ±4 kV as per IEC 61000-4-4
Type of Type Immunity to ±8 kV air discharge, ±6 kV contact
measurement True RMS, 128 samples per cycle,
1 sec update time electrostatic discharge discharge as per IEC 61000-4-2
K I/O 4
Baud rate 2400, 4800, 9600, 19200, 38400 bps (site selectable) M
4. Display Of Parameters
4.1 Display of Parameters for multifunction meter
Preventive Measures :
· Fuse : To avoid the possibility of short circuit, use a slow blow fuse that has a voltage rating VAC : 250V, Fuse current : 200 mA, Breaking capacity : 10kA@ 125 VAC When replacing a fuse,
turn OFF the power and unplug the power cord. Never short the fuse holder
5.1 Programming Mode 5.2 General Programming Guide 5.3 Setting or Configuration of Parameter If customer enters wrong password
Programming keys · Press UP + E to enter Programming Mode · Press E to enter Edit Mode then pass error will be displayed (Meter
· Press Down to enter Password (Default Value · Blinking of parameter/value indicates Edit Mode is ON will display next parameter
0000) · Press UP or DOWN to increment/decrement values but cannot be edited.) If customer
ENTER - to enter Edit Mode and save parameter
· Digit blinking indicates Edit Mode is ON or to select from available options forgets the set password, Kindly
DOWN - to decrement value or parameter · Press E to accept the value of the parameter contact L&T Customer Interaction Center.
· Press UP or DOWN to increment and
UP - to increment value or parameter · Press DOWN to move to next parameters till end
decrement
after configuration of last parameter display screen
value 0/1/2/3/4/5/6/7/8/9
will prompt “save”, Display reads “y” (YES)
· Press E to edit the next digit till 4th digit · Press Down if changes are not to be saved, display
· If Password is correct, meter displays next reads “ ” (no)
parameter in editable mode · Press E to save the option
5.4 Display : High Limit 1* 1800 1% to 100% of Full scale 5.5. Enabling & Disabling Auto Scrolling
M Press DOWN for 6 secs
Row 1: Parameter -
High Limit 2* 1700 50% to 99% of High Limit 1 Display Shows: EnAbLE Auto.sc
Row 2: Options/Set Option K
Low Limit* 1300 50% to 99% of High limit 2 Again press DOWN for 6 sec
M Display Shows: diSAbL Auto.sc
Eg. Row 1: ConFIG -
Baud rate 9600 2400, 4800, 9600, 19.2k 5.6.Clearing Parameter
K
Row 2: 3P 4W Parity · Press UP + DOWN to enter Clear Mode
Even Even/Odd/none
· Press DOWN to enter Password (0000 Default)
Slave Id 1.000 1 to 247 · Press E to clear
Programming Option/Range · Select :
Default No of Poles (For rpm) - CLR. int to clear integrator (all energy parameter)
Parameter 4.000 1 to 28
- CLR. Hi. L clear max or min value
Yes/No
Reverse lock*** REV.LOC No - CLR. Md clear max demand
ConFIG 3P 4W If YES it blocks energy accumulation
in case the CT polarity reverse. · Once parameter to be cleared is selected it will prompt for
(Defines the power 3P 4W 3P 3W to “Y” (YES) or “ ” (no) for conformation
system configuration.) 1 Phase PASSWORD 0000 0000 to 9999
Energy Resolution Resolution/Counter 5.7. Energy Resolution
100V-999kV
To set 33kV Set first four digits Starting current 0.400 0.4 to 20% of Full Scale Active energy display is available in resolution mode (default) or counter
(3300) as explained above press
PT Primary 415 UP/DOWN key to place decimal point mode.
at appropriate location. Display update time 1.000 1 to 5 seconds
Letter K/M will indicate the Kilo/Mega.
M & K both LED will glow for Giga In Resolution mode when energy reading reaches 9999.xx Wh it will
Display autoscroll time 5.000 1 to 10 seconds
next scale to 10.xxxx kWh, once it reaches 9999.xxkWh it scales to
PT Secondary 415.0 50V to 550V Pulse output on time 250.0 50 to 500 msec 10.xxxxMWh, once it reaches to 9999.xx MWh it scales to 10.xxxx
CT Primary 5.000 0.5A - 99kA GWh.
Analog output 1 VLL/A/Freq/Watts /PF/VA
parameter diSAbL In Counter mode, the energy reading will be fixed at kWh or MWh or
CT Secondary 5.000 0.5A - 6A GWh. It primarily depends on the CT primary and PT primary values.
Method of VA Selection: Analog Output 1 Following table denotes the same:
VA selection VEC.Har Arithmetic /Vector harmonics 0 to 20mA 0 to 20mA/4 to 20mA Full scale
Offset
/Vector ( 3 X PT pri X CT pri ) / 1000 Fixed unit of display
Analog Output 2 VLL/A/Freq/Watts/PF/VA
YEAr** x Range: 2012 to 2052 parameter diSAbL 0.4 - 400 kWh
40111 VAR R Ph float 40131 VA B Ph float 40171* VARh Ind. Delivered* float
3
Relay 2
2
Relay 1
40113 VAR Y Ph float 40133 VLL Avg float 40153 I Y Ph float 40173* VARh Cap. Delivered* float
COM 1
AMF IP
240V AC
AMF IP
240V AC Common
40115 VAR B Ph float 40135 VRY Ph float 40155 I B Ph float 40175 PF Avg. Received float
40117 PF Avg (inst) float 40137 VYB Ph float 40157 Frequency float 40177 Amps hour Received float
3 Phase 4 Wire System 3 Phase 3 Wire System For 4420 and 4430 with 2 relay output
40119 PF R Ph float 40139 VBR Ph float 40159 Wh EB Received float 40179* PF Avg. Delivered* float
40181* Amps hour Delivered* float 40217 Load Hours Received Unsigned long 40265 I Unbal R Ph float 40301 Watts Max. float 40489 I B Har. float
40183 Neutral I float 40219* Load Hours Delivered* Unsigned long 40267 I Unbal Y Ph float 40303 Watts Min. float 40491 K factor V R Ph float
40185 V R Har. float 40221 No of interruptions Unsigned long 40269 I Unbal B Ph float 40305 VAR Max. (absolute max.) float 40493 K factor V Y Ph float
40187 V Y Har. float 40223 MD Occurrence time Unsigned long 40273 Analog input 1 float 40307 VAR Min. (absolute min) float 40495 K factor V B Ph float
40189 V B Har. float 40233 V R Ph angle float 40275 Analog input 2 float 40309 VA Max. float 40497 K factor I R Ph float
40191 I R Har. float 40235 V Y Ph angle float 40285 VLL Max. float 40311 VA Min. float 40499 K factor I Y Ph float
40193 I Y Har. float 40237 V B Ph angle float 40287 VLL Min. float 40313 PF Max. (absolute max.) float 40501 K factor I B Ph float
40195 I B Har. float 40239 I R Ph angle float 40289 VLN Max. float 40315 PF Min. (absolute min.) float *Applicable for 4430 Model
40197 Rising Demand float 40241 I Y Ph angle float 40291 VLN Min. float 40479 V R Har. float
40201 Max. Demand float 40243 I B Ph angle float 40293 Amps Max. float 40481 V Y Har. float
40203* Rising Demand Delivered* float 40259 V Unbal R Ph float 40295 Amps Min. float 40483 V B Har. float
40207* Max. Demand Delivered* float 40261 V Unbal Y Ph float 40297 Frequency Max. float 40485 I R Har. float
40215 RPM float 40263 V Unbal B Ph float 40299 Frequency Min. float 40487 I Y Har. float
2. Technical Specification
3 P 4 W, 3 P 3 W, 1 P Impulse voltage test ±6 kV as per IEC 62052-11
Insulation
Type of Type AC voltage test 4 kV double insulation as per IEC 62053-21
measurement True RMS, 128 samples per cycle, properties
1 sec update time Insulation resistance 500 V DC as per IS 13779
Operating temperature -10O C to +55O C
Class 1 as per IEC 62053-21
Measurement Operating Storage temperature -25O C to +70O C
Accuracy Class 0.5, 0.5s as per IEC 62053-22
conditions Humidity 5% to 95% relative humidity non-condensing
Class 0.2, 0.2s as per IEC 62053-22
Recommended wire 2.5 sq mm
Display type LCD 4 digit for instantaneous and 6 digits
and resolution for cumulative Shock As per standard IEC 60068-2
Mechanical
50 - 520 VLL Vibration 10 to 55 Hz, 0.15 mm amplitude
conditions
PT Primary and Secondary user programmable Casing Plastic mould protected to IP51 from front side
Input voltage for LT and HT applications Measurement category CAT III
Burden: 0.2VA max per phase Safety Pollution degree 2
-/5A and -/1A site selectable Protection IP20 at terminals, IP51 on front
Measuring circuit 300 gms
Current range from 50mA - 5A with overload Product weight
Input current capacity upto 120% In (i.e., 6A) Weight & Bezel dimension (W x H x D) 96 x 96 x 58 mm
dimensions
CT Primary and Secondary user Panel cutout 92 x 92 mm +0.8
-0.0
programmable for LT and HT applications Outputs Meter constant: 10000/(external CT ratio x PT ratio)
Frequency 40 - 70 Hz Type RS485 port Modbus RTU
Aux voltage 80 - 300VAC/DC Baud rate 2400, 4800, 9600, 19200, 38400 bps (site selectable)
Auxiliary circuit Aux burden <5VA Parity Odd, Even, None
Communication
Freq range 40 - 70 Hz Slave id 1 to 247 (programmable)
Test of power consumption as per IEC 62053-21 2 kVAC isolation for 1 minute between
Electrical Isolation
Voltage dips and interrupts as per IEC 62053-21 communication and other circuits
requirements
Short time over current protection 10A max continuous, 20 times of In for 3 sec Certifications CE, RoHS
Fast transients burst test ±4 kV as per IEC 61000-4-4
B P E B P E B P E
To view parameters CLR PRG CLR PRG CLR PRG
To select and to accept the
MULTIFUNCTION METER value/Parameter in setup MULTIFUNCTION METER MULTIFUNCTION METER
To edit the value/ mode and scroll through
system type downward To edit the value/system the Energy parameters
in edit mode & scroll type upward in edit mode
through the basic & scroll through the
parameters Power parameters
4. Display Of Parameters
4.1 Display of Parameters for multifunction meter
Preventive Measures :
· Fuse : To avoid the possibility of short circuit, use a slow blow fuse that has a voltage rating
VAC : 250V, Fuse current : 200 mA, Breaking capacity : 10kA@ 125 VAC When replacing a fuse,
turn OFF the power and unplug the power cord. Never short the fuse holder
5.1 Programming Mode 5.2 General Programming Guide 5.3 Setting or Configuration of Parameter If customer enters wrong password
Programming keys · Press UP + E to enter Programming Mode · Press E to enter Edit Mode then pass error will be displayed (Meter
· Press Down to enter Password (Default Value · Blinking of parameter/value indicates Edit Mode is ON will display next parameter
0000) · Press UP or DOWN to increment/decrement values but cannot be edited.) If customer
ENTER - to enter Edit Mode and save parameter or to select from available options forgets the set password, Kindly
DOWN - to decrement value or parameter · Digit blinking indicates Edit Mode is ON
· Press E to accept the value of the parameter contact L&T Customer Interaction Center.
UP - to increment value or parameter · Press UP or DOWN to increment and · Press DOWN to move to next parameters till end
decrement after configuration of last parameter display screen
value 0/1/2/3/4/5/6/7/8/9 will prompt “save”, Display reads “y” (YES)
· Press E to edit the next digit till 4th digit · Press Down if changes are not to be saved, display
· If Password is correct, meter displays next reads “ ” (no)
parameter in editable mode · Press E to save the option
4
Following table denotes the same:
3
Relay 2
2
Relay 1
Full scale
COM 1
AMF IP AMF IP AMF IP
Common
( 3 X PT pri X CT pri ) / 1000 Fixed unit of display
240V AC 240V AC 240V AC
7. Memory Map
Address Parameter Data type Address Parameter Data type Address Parameter Data type Address Parameter Data type
40101 Watts Total float 40157 Frequency float 40223 MD Occurrence time Unsigned long 40315 PF Min. (absolute min.) float
40103 Watts R Ph float 40159 Wh Received float 40233 V R Ph angle float 40479 V R Har. float
40105 Watts Y Ph float 40161 VAh Received float 40235 V Y Ph angle float 40481 V Y Har. float
40107 Watts B Ph float 40163 VARh Ind. Received float 40237 V B Ph angle float 40483 V B Har. float
40109 VAR Total float 40165 VARh Cap. Received float 40239 I R Ph angle float 40485 I R Har. float
40111 VAR R Ph float 40167** Wh Delivered float 40241 I Y Ph angle float 40487 I Y Har. float
40113 VAR Y Ph float 40169** Vah Delivered float 40243 I B Ph angle float 40489 I B Har. float
40115 VAR B Ph float 40171** VARh Ind. Delivered float 40259 V Unbal R Ph float 40491 K factor V R Ph float
40117 PF Avg (inst) float 40173** VARh Cap. Delivered float 40261 V Unbal Y Ph float 40493 K factor V Y Ph float
40119 PF R Ph float 40175 PF Avg. Received float 40263 V Unbal B Ph float 40495 K factor V B Ph float
40121 PF Y Ph float 40177 Ampere Hour float 40265 I Unbal R Ph float 40497 K factor I R Ph float
40123 PF B Ph float 40179** PF Avg. Delivered float 40267 I Unbal Y Ph float 40499 K factor I Y Ph float
40125 VA Total float 40181** Ampere Hour Delivered float 40269 I Unbal B Ph float 40501 K factor I B Ph float
40127 VA R Ph float 40183 Neutral Current float 40285 VLL Max. float ** Applicable for 4430 Model
1) Meter display does not turn ON. In case of complaint please contact
+2.0 Steps for Mounting
90 - 0.0
Insert meter to panel
a) Check that there is power supply applied on Aux supply terminals. CUSTOMER INTERACTION CENTRE (CIC)
1
without clamps b) Check fuse connection (Use fuse connection of specified ratings). TOLL-Free: 1800 233 5858, 1800 200 5858
2) Data displayed / reading incorrect. Telephone : 022 6774 5858
2 Insert both clamps
1
a) Check that CT /PT ratios are properly set. email: [email protected]
2 3
b) Check if proper configuration mode 3P4W, 3P3W, 1Phase is correctly set.
90 +2.0 3) Pt reading are incorrect / Active Power reading is negative.
- 0.0
a) CT connections may be reversed, check and correct CT connection.
b) Check voltage and current phases are connected in proper sequence.
4) RS485 communication does not work. L&T Electrical & Automation
a) Check baud rate & parity maintained in the connected computers is same as Meter. Electrical Standard Products
b) Memory mapping in software is correct. L&T Business Park, Tower 'B' / 3rd Floor
54mm
3 c) Check Slave ID of meter is Unique & properly maintained. Saki Vihar Road, Powai Mumbai 400 072
4mm
d) Check converter is working properly. Website: www.Lntebg.com
e)Ensure termination resistor (120Ω 0.5W)is connected