Fire Protection Solutions in Arabia
Fire Protection Solutions in Arabia
COMPANY PROFILE
Fire Fighting & Safety Equipment and Systems
REDA
Trading & Development Co. Ltd.
…………………………….List of Contents
PROFILE IN BRIEF 3
COMPANY AIM 3
POTENTIAL OF COMPANY 4
MISSION 4
QUALITY 5
SAFETY 5
ENVIRONMENTAL 5
INTERNAL RELATIONSHIP 5
SERVICES 6
AREAS OF SPECIALIZATION 7
ACTIVITIES 7/8
CAPABILITIES 9
PRODUCTS 9/10/11
PARTNERS 12 / 13
OFFICE LOCATIONS 14
Page 2 of 14
Fire Fighting & Safety Equipment and Systems
PROFILE IN BRIEF
RREEDDAA Fire Protection division is one of the leading fire-protection, design, supply,
construction and servicing companies. Its technicians assess fire risks, evaluate
owner's needs, conduct fire-hazard analyses and develop conceptual solutions. RREEDDAA
specializes in system design, supplying complete detection and suppression systems
and provides top-quality installation, service, training and other services.
For more than 15 years, RREEDDAA has protected against every type of hazard due to fire.
The company provides an unparalleled, complete range of capabilities and total
service that its customers will not find elsewhere.
With the ability to evaluate a broad range of solutions for any fire-protection
problem -- large or small -- RREEDDAA brings together the scientific and technological
expertise of leading manufacturers with its contracting, installation and service
experience.
RREEDDAA proudly incorporates the most advanced technologies available for any type of
work. Regardless of the challenge, RREEDDAA has the people, the products, the financial
resources and the expertise to handle the project from star t to finish -- complete
turnkey construction of fire protection systems.
COMPANY AIM
Our mandate is to protect you and your property from fire. RREEDDAA is dedicated to
finding the suitable solution for any fire protection problem. We offer total fire
protection capabilities with quality products and trained, experienced technicians.
RREEDDAA is aligned with the leading manufacturers who select only very qualified
representation. We have a working knowledge of worldwide fire protection rules and
regulations to ensure complete safety and compliance anywhere. On time, reliable,
accurate, and on budget.
RREEDDAA - FIRST For Fire Protection.
As you can see our experience covers the complete range of Fire Protection, from
fire sprinklers and special hazards protection to alarms and detection we can handle
YOUR fire challenge. Understanding our customer’s needs, concerns and business is
our number one priority.
RREEDDAA - your first call for Fire Protection!
Page 3 of 14
Fire Fighting & Safety Equipment and Systems
POTENTIAL OF COMPANY
Our Services are genuinely innovative, comprehensive and represent an excellent
value. We consider our customers as our partners ensuring their objective are met as
efficiently and economically as possible.
REDA, believes in a team approach for creating a safer facility. We work closely with
our clients to formulate and implement high-quality, comprehensive programs that
exceed their expectations.
MISSION
The key to the success of any Fire & Safety equipment or system is its suitability for
the site and workforce it protects.
Fires and toxic spillage especially threaten the oil and petrochemical industries. Many
other industries such as plastics, paints or paper are facing similar hazards. Offices,
shops, hospitals and hotels are all at risk in different ways.
At REDA we not only supply the entire Saudi Arabian market with fire fighting and
safety equipment produced by many of the US and Europe’s leading manufacturers,
we also provide technical advisory services and comprehensive testing, servicing and
maintenance program which ensure the safety of working people in oil fields,
petrochemical plants, electrical companies, desalination plants, industrial
installations, airports, militaries, civil defense, hospitals, schools, university, offices,
building and other location throughout the region.
REDA Fire & Safety operates from 4 offices and logistics centres and serves the
countries of Saudi Arabia and Kuwait.
All senior members of staff have significant experience with the Oil, Gas, Water,
Chemical, Iron & Steel Industries and Civil Engineering Industries commensurate with
the high standard of services required and provided for activities in the KSA. In
addition a register is maintained of qualified personnel who may be used to
supplement staffing levels on large contracts or specialized projects.
It is the policy of the organization to invest in its staff both at degree and vocational
levels with appropriate training and development programs for the long-term benefit
of the company and the services provided.
This is endorsed by the recognition and certification under the Investors in People
initiative.
Page 4 of 14
Fire Fighting & Safety Equipment and Systems
QUALITY
SAFETY
The company operates a safety policy in compliance with internally set objectives of
recognized standard. Safety consultants are retained to advise on all safety matters
related to company activities.
Safety awareness is highlighted for all projects and risk assessment is prepared to
recognized standards to control hazards.
The safety policies followed are aimed at working together with clients to achieve
the objective of zero safety related incidents.
ENVIRONMENTAL
INTERNAL RELATIONSHIP
It is our firm conviction that our employees are our “Best Assets” and we wish to be
recognized as a “Great Place to Work” our personal shall be guided by this desire and
our approach to our employees shall be governed by the principles of “Mutual
Respect” and “Trust”.
We recognize the need to nurture team spirit. For this purpose we shall provide an
environment of friendliness and mutual support within the organization at the same
time encourage individual initiative and creative skills.
Page 5 of 14
Fire Fighting & Safety Equipment and Systems
As Saudi Arabia’s leading fire and safety experts, we put a high priority on a
complete understanding of our suppliers’ products and our customers’ real needs.
We have experience and understanding of the fire risk and hazardous accidents
facing oil and petrochemical companies. Our services, which include recommending,
supplying, servicing and maintaining safety equipment, will help protect our clients’
costly installations, and ultimately will save lives.
SERVICES
Working closely with reliable and highly technical suppliers gives us the benefit of
the knowledge and experience gained over many years. Our engineers assess and
evaluate each of our customer’s fire protection & safety needs, advice them on the
correct systems required for their individual sites, supervise materials installation
and subsequently offer a planned program of continuous service & maintenance
specifically created for each individual customers according to the manufacturer’s
recommendation and the international standards.
REDA operates three service centers in Saudi Arabia: Al Khobar, Jubail and Yanbu.
SERVICES PERFORMED
Page 6 of 14
Fire Fighting & Safety Equipment and Systems
AREAS OF SPECIALIZATION
• Industrial Safety Supplies
A
ACCT
T II V
V II T
T II E
E SS
• Consultancy
• Risk Analysis and Risk Control
• Loss Prevention Planning
• Site Inspection
• Periodic Inspection
• Preventive Maintenance
Page 8 of 14
Fire Fighting & Safety Equipment and Systems
C
CAA PP A
ABB II L
L II T
T II E
E SS
PP R
ROOD
DUUC
CTT SS
In line with the comprehensive scope of our advisory services, materials supply,
repair & maintenance services, REDA carries a large inventory of specialized fire
protection and safety items.
We keep for ready-supply various types of Self Contained Breathing Apparatus (SCBA)
with all accessories.
All type and sizes of fire extinguishers, portable, mobile and fixed fire monitors,
wide range of effective fire nozzles, a range of fire & safety valves, various
diameters of industrial and municipal fire hoses.
All types of fire-fighting fire entry suits and fire retardant station uniforms including
fire helmets, fire gloves and fire boots.
A large selection of chemical suits against all type of chemicals at various
concentrations.
Safety equipment such stretchers, burn kits, flashlights, various types of safety
shower personal protection, gas masks and accessories.
Fire alarm and extinguishing systems and a range of specialized equipment to be
installed and used on fire trucks.
REDA has an established firefighting and safety equipment business which is also
involved in marketing and distribution of a wide range materials, services and
equipments for many industrial activities.
Page 9 of 14
Fire Fighting & Safety Equipment and Systems
Fire Fighting
Fire Extinguishers
Cartridge-Operated
Cartridge-Operated
Portable Fire Extinguishers
Stored Pressure Portable Fire Extinguishers
Firefighting Agents
Foam Fire Extinguishing
Carbon Dioxide Fire Extinguishing
Alternative Fire Extinguishing Systems
Dry Chemical/Powder Fire Extinguishing
Page 10 of 14
Fire Fighting & Safety Equipment and Systems
Page 11 of 14
Fire Fighting & Safety Equipment and Systems
Partners
REDA ‘‘ss partners include the following:
Page 12 of 14
Fire Fighting & Safety Equipment and Systems
Page 13 of 14
Fire Fighting & Safety Equipment and Systems
O
O FF FF II C
CEE L
LOOC
CAAT
T II O
ONN SS
AL KHOBAR, SAUDI ARABIA YANBU, SAUDI ARABIA
TRADING & DEVELOPMENT P.O. Box 2077
Co. For MACHINERY & Jeddah 21451
EQUIPMENT (REDA) Ltd. Kingdom of Saudi Arabia
Khobar-Dammam Tel : (966 4) 391 3702
Expressway Fax : (966 4) 391 3702
P.O. Box 2923 Contacts:
Al Khobar 31952 sales@[Link]
Kingdom of Saudi Arabia
Tel : (966 3) 857 0079
Fax : (966 3) 857 0087
Contacts:
sales@[Link]
Page 14 of 14
TRADING & DEVELOPMENT CO. FOR MACHINERY & EQUIPMENT LTD.
FIRE & SAFETY DIVISION
Al Khobar : Tel (9663) 857-0079 - Fax (9663) 857-0087
Email: sales@[Link]
Al Khobar-Dammam Road, P.O. Box 2923, 31952 Al Khobar, Saudi Arabia
MAJOR REDA
PROJECTS
REFERENCE
LIST
TRADING & DEVELOPMENT CO. FOR MACHINERY & EQUIPMENT LTD.
FIRE & SAFETY DIVISION
Al Khobar : Tel (9663) 857-0079 - Fax (9663) 857-0087
Email: sales@[Link]
Al Khobar-Dammam Road, P.O. Box 2923, 31952 Al Khobar, Saudi Arabia
Page 1 of 4
TRADING & DEVELOPMENT CO. FOR MACHINERY & EQUIPMENT LTD.
FIRE & SAFETY DIVISION
Al Khobar : Tel (9663) 857-0079 - Fax (9663) 857-0087
Email: sales@[Link]
Al Khobar-Dammam Road, P.O. Box 2923, 31952 Al Khobar, Saudi Arabia
33. Saline Water Conversion Pumping Station Generator room High Pressure CO2 Systems
Page 3 of 4
Aramco Overseas Company King Abdullah Sports City
MEP Specification
PART 1 - GENERAL
A. Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
A. Section Includes:
B. Related Sections:
1. Section 283111 "Digital, Addressable Fire-Alarm System" for alarm devices not
specified in this Section.
A. The specifications and standards listed below form a part of this section of the
specifications. The system shall fully comply with the latest issue, with all updates, of these
standards as applicable.
1.4 REQUIREMENTS
A. The NOVEC 1230 Suppression System installation shall be made in accordance with the
drawings, specifications and applicable standards.
1.5 EXCLUSIONS
A. The work listed below shall be provided by others, or under other sections of this
specification
A. Manufacturer
B. Installer
1. The installing contractor shall be trained by the supplier to design, install, test and
maintain Suppression Systems
2. When possible, the installing contractor shall employ a NICET certified special
hazard designer, level 2 or above, who will be responsible for this project.
3. The installing contractor shall be an experienced firm regularly engaged in the
installation of automatic Clean Agent, or similar, fire suppression systems in strict
accordance with all applicable standards.
4. The installing contractor must have a minimum of five (5) years experience in the
design, installation and testing of Clean Agent, or similar, fire suppression systems. A
list of systems of a similar nature and scope shall be provided on request.
1.7 SUBMITTALS
A. The installing contractor shall submit the following design information and drawings for
approval prior to starting work on this project.
1. Field installation layout drawings having a scale of not less than 1/8” = 1’-0” or
1:1000m detailing the location of all agent storage tanks, pipe runs including pipe
sizes and lengths, control panel(s), detectors, manual pull stations, abort stations,
audible and visual alarms, etc.
2. Auxiliary details and information such as maintenance panels, door holders, special
sealing requirements and equipment shutdowns
3. Separate layouts, or drawings, shall be provided for each level, ( i.e.; room,
underfloor, and above ceiling) and for mechanical and electrical work.
4. A separate layout or drawing shall show isometric details of agent storage containers,
mounting details and proposed pipe runs and sizes.
5. Electrical layout drawings shall show the location of all devices and include point-to-
point conduit runs and a description of the method(s) used for detector mounting
6. Provide an internal control panel wiring diagram which shall include power supply
requirements and field wiring termination points.
7. Complete hydraulic flow calculations, from a U.L. listed computer program, shall be
provided for all engineered Clean Agent systems. Calculation sheet(s) must include
the manufacturers name and U.L. listing number for verification. The individual
sections of pipe and each fitting to be used, as shown on the isometrics, must be
identified and included in the calculation. Total agent discharge time must be shown
and detailed by zone.
8. Provide calculations for the battery stand-by power supply taking into consideration
the power requirements of all alarms, initiating devices and auxiliary components
under full load conditions.
9. A complete sequence of operation shall be submitted detailing all alarm devices,
shutdown functions, remote signaling, damper operation, time delay and agent
discharge for each zone or system
B. Submit drawings, calculations and system component data sheets for approval to the local
Fire Prevention Agency, Company Representatives Insurance Underwriter and all other
Authorities Having Jurisdiction before starting installation. Submit approved plans to the
Architect/Engineer for record.
3. After completion of the time-delay sequence, the NOVEC Clean Agent system shall
discharge and the following shall occur:
a. Illuminate a "SYSTEM FIRED" lamp on the control panel face
b. Shutdown of all power to high-voltage equipment
c. Energize a visual indicator(s) outside the hazard in which the discharge
occurred
d. Energize a "System Fired" audible device
4. The system shall be capable of being actuated by manual discharge devices located at
each hazard exit. Operation of a manual device shall duplicate the sequence
description above except that the time-delay and abort functions shall be bypassed.
The manual discharge station shall be of the electrical actuation type and shall be
supervised at the main control panel.
A. The NOVEC 1230 Clean Agent System materials and equipment shall be standard products
of the supplier's latest design and suitable to perform the functions intended. When one or
more pieces of equipment must perform the same function(s), they shall be duplicates
produced by one manufacturer.
1. All devices and equipment shall be U.L. Listed and/or FM approved
C. CONTROL PANEL
1. Three (3) Class “B” Style Y notification appliance circuits rated for 2.0 amps @ 24
VDC
2. Up to two (2) Style B initiating device circuits capable of sequential alarm, cross-
zone, or single detector release operation.
Page 1 of 9
TRADING & DEVELOPMENT CO. FOR MACHINERY & EQUIPMENT LTD.
FIRE & SAFETY DIVISION
Al Khobar : Tel (9663) 857-0079 - Fax (9663) 857-0087
Email: sales@[Link]
Al Khobar-Dammam Road, P.O. Box 2923, 31952 Al Khobar, Saudi Arabia
Page 2 of 9
TRADING & DEVELOPMENT CO. FOR MACHINERY & EQUIPMENT LTD.
FIRE & SAFETY DIVISION
Al Khobar : Tel (9663) 857-0079 - Fax (9663) 857-0087
Email: sales@[Link]
Al Khobar-Dammam Road, P.O. Box 2923, 31952 Al Khobar, Saudi Arabia
Page 3 of 9
TRADING & DEVELOPMENT CO. FOR MACHINERY & EQUIPMENT LTD.
FIRE & SAFETY DIVISION
Al Khobar : Tel (9663) 857-0079 - Fax (9663) 857-0087
Email: sales@[Link]
Al Khobar-Dammam Road, P.O. Box 2923, 31952 Al Khobar, Saudi Arabia
19. AIR PRODUCTS SABIC – GAS FM 200, Alarm System and Fire Fighting
Yanbu 22.06.2006 22.12.2007 Equipment
Page 4 of 9
TRADING & DEVELOPMENT CO. FOR MACHINERY & EQUIPMENT LTD.
FIRE & SAFETY DIVISION
Al Khobar : Tel (9663) 857-0079 - Fax (9663) 857-0087
Email: sales@[Link]
Al Khobar-Dammam Road, P.O. Box 2923, 31952 Al Khobar, Saudi Arabia
Page 5 of 9
TRADING & DEVELOPMENT CO. FOR MACHINERY & EQUIPMENT LTD.
FIRE & SAFETY DIVISION
Al Khobar : Tel (9663) 857-0079 - Fax (9663) 857-0087
Email: sales@[Link]
Al Khobar-Dammam Road, P.O. Box 2923, 31952 Al Khobar, Saudi Arabia
Page 6 of 9
TRADING & DEVELOPMENT CO. FOR MACHINERY & EQUIPMENT LTD.
FIRE & SAFETY DIVISION
Al Khobar : Tel (9663) 857-0079 - Fax (9663) 857-0087
Email: sales@[Link]
Al Khobar-Dammam Road, P.O. Box 2923, 31952 Al Khobar, Saudi Arabia
Page 7 of 9
TRADING & DEVELOPMENT CO. FOR MACHINERY & EQUIPMENT LTD.
FIRE & SAFETY DIVISION
Al Khobar : Tel (9663) 857-0079 - Fax (9663) 857-0087
Email: sales@[Link]
Al Khobar-Dammam Road, P.O. Box 2923, 31952 Al Khobar, Saudi Arabia
Page 8 of 9
TRADING & DEVELOPMENT CO. FOR MACHINERY & EQUIPMENT LTD.
FIRE & SAFETY DIVISION
Al Khobar : Tel (9663) 857-0079 - Fax (9663) 857-0087
Email: sales@[Link]
Al Khobar-Dammam Road, P.O. Box 2923, 31952 Al Khobar, Saudi Arabia
61. HADEED CSD Workshop Design supply supervision installation and testing
12.09.2009 27.10.2010 & commissioning of CO2 fire suppression system
for new switchgear room.
62. HADEED Elevator 11.12.2010 27.04.2011 Supply fire alarm system for Elevator Project
63. SUMITOMO KAUST 19.02.2009 Design, Engineering, supply and Installation of
12.11.2010
Novec 1230 system
Page 9 of 9
FM200 FIRE SUPPRESSION SYSTEM & FIRE DETECTION SYSTEM
RAWDHAT AL-KHURAIM
Vendor Document
Client : EMPOWER
NFS-320(E)
Intelligent Addressable
Fire Alarm System
Intelligent Fire Alarm Control Panels
General
The NFS-320 intelligent Fire Alarm Control Panel is part of the
ONYX® Series of Fire Alarm Controls from NOTIFIER.
In stand-alone or network configurations, ONYX Series products
meet virtually every application requirement.
Designed with modularity and ease of system planning, the
NFS-320 can be configured with just a few devices for small
building applications, or for a large campus or high-rise applica-
tion. Simply add additional peripheral equipment to suit the
application.
NOTE: Unless called out with a version-specific “R” or “E” at the
end of the part number, “NFS-320” refers to models NFS-320,
[Link]
NFS-320R, and NFS-320E; similarly, “CPU-320” refers to the main
circuit board for CPU-320, and CPU-320E.
Features
• Listed to UL Standard 864, 9th edition. NFS-320
• One isolated intelligent Signaling Line Circuit (SLC) Style 4, 6
or 7.
• Field-programmable on panel or on PC, with VeriFire Tools
• Up to 159 detectors (any mix of ion, photo, thermal, or multi- program check, compare, simulate.
sensor) and 159 modules (Addressable pull stations, nor-
• Full QWERTY keypad.
mally open contact devices, two-wire smoke, notification, or
relay). 318 devices maximum. • Battery charger supports 18 – 200 amp hour batteries
• Standard 80-character display. • Non-alarm points for lower priority functions.
• Network options: • Remote ACK/Signal Silence/System Reset/Drill via monitor
modules.
– High-speed network for up to 200 nodes (NFS2-3030,
NFS2-640, NFS-320(C), NCA-2, DVC, ONYXWorks, • Automatic time control functions, with holiday exceptions.
NCS, NFS-3030, NFS-640, and NCA). • Surface Mount Technology (SMT) electronics.
– Standard network for up to 103 nodes (NFS2-3030, • Extensive, built-in transient protection.
NFS2-640, NFS-320(C), NCA-2, DVC, ONYXWorks, • Powerful Boolean logic equations.
NCS, NFS-3030, NFS-640, NCA, AFP-200, AFP-300/
400, AFP-1010, and AM2020). Up to 54 nodes when DVC FLASHSCAN® INTELLIGENT FEATURES:
is used in network paging. • Poll up to 318 devices in less than two seconds.
• 6.0 amp power supply with four Class A/B built-in Notification • Activate up to 159 outputs in less than five seconds.
Appliance Circuits (NAC). Selectable System Sensor, Whee- • Multicolor LEDs blink device address during Walk Test.
lock, or Gentex strobe synchronization.
• Fully digital, high-precision protocol (U.S. Patent 5,539,389).
• Built-in Alarm, Trouble, Security, and Supervisory relays.
• Manual sensitivity adjustment — nine levels.
• VeriFire® Tools online or offline programming utility. Upload/
Download, save, store, check, compare, and simulate panel • Pre-alarm ONYX intelligent sensing — nine levels.
databases. Upgrade panel firmware. • Day/Night automatic sensitivity adjustment.
• Autoprogramming and Walk Test reports. • Sensitivity windows:
• Optional universal 318-point DACT. – Ion – 0.5 to 2.5%/foot obscuration.
• 80-character remote annunciators (up to 32). – Photo – 0.5 to 2.35%/foot obscuration.
• EIA-485 annunciators, including custom graphics. – Laser (VIEW®) – 0.02 to 2.0%/foot obscuration.
• Printer interface (80-column and 40-column printers). – Acclimate Plus™ – 0.5 to 4.0%/foot obscuration.
• History file with 800-event capacity in nonvolatile memory, – IntelliQuad – 1.0 to 4.0%/foot obscuration.
plus separate 200-event alarm-only file. • Drift compensation (U.S. Patent 5,764,142).
• Alarm Verification selection per point, with tally. • Degraded mode — in the unlikely event that the CPU-320
• Autoprogramming and Walk Test reports. microprocessor fails, FlashScan detectors revert to degraded
• Presignal/Positive Alarm Sequence (PAS). operation and can activate the CPU-320 NAC circuits and
alarm relay. Each of the four built-in panel circuits includes a
• Silence inhibit and Auto Silence timer options. Disable/Enable switch for this feature.
• NAC coding functions: • Multi-detector algorithm involves nearby detectors in alarm
– March time. decision (U.S. Patent 5,627,515).
– Temporal. • Automatic detector sensitivity testing (NFPA-72 compliant).
– California two-stage coding. • Maintenance alert (two levels).
– Canadian two-stage. • Self-optimizing pre-alarm.
– Strobe synchronization.
NFS-320
Sample
System
Options
[Link]
General
[Link]
Notifier 851 Series intelligent plug-in smoke detectors with
integral communication provide features that surpass conven-
tional detectors. Detector sensitivity can be programmed in
the control panel software. Sensitivity is continuously moni-
tored and reported to the panel. Point ID capability allows
each detector’s address to be set with decade address
switches, providing exact detector location for selective main-
tenance when chamber contamination reaches an unaccept-
able level. The FSP-851 photoelectric detector’s unique
optical sensing chamber is engineered to sense smoke pro- FSP-851 with B710LP base
duced by a wide range of combustion sources. Dual electronic
thermistors add 135°F (57°C) fixed-temperature thermal sens-
ing on the FSP-851T. The FSP-851R is a remote test capable
[Link]
detector for use with DNR(W) duct detector housings.
FSP-851 series detectors are compatible with all ONYX
series Notifier intelligent Fire Alarm Control Panels (FACP).
FlashScan® (U.S. Patent 5,539,389) is a communication pro-
tocol developed by Notifier that greatly increases the speed of
communication between analog intelligent devices. Intelligent
devices communicate in a grouped fashion. If one of the
devices in the group has new information, the panel’s CPU
stops the group poll and concentrates on single points. The
FSP-851T with B710LP base
net effect is response speed greater than five times that of ear-
lier designs.
Features Specifications
• Sleek, low-profile design.
Size: 2.1” (5.3cm) high x 4.1” (10.4cm) diameter installed in
• Addressable-analog communication. B501 base, 6.1” (15.5cm) diameter installed in B710LPbase.
• Stable communication technique with noise immunity. Shipping Weight: 5.2oz. (147g).
• Low standby current. Operating Temperature: FSP-851, 0°C to 49°C (32°F to
• Two-wire SLC connection. 120°F); FSP-851T, 0°C to 38°C (32°F to 100°F). Low temper-
• FlashScan (NFS-320, NFS-640, NFS2-640, NFS-3030, ature signal for FSP-851T at 45°F +/- 10°F (7.22°C +/-
NFS2-3030) and classic CLIP systems (AFP-100, AFP- 5.54°C). FSP-851R installed in a DNR(W), -20°C to 70°C (-4°F
200, AFP-300, AFP-400, NFS-640, AM2020/AFP1010, to 158°F).
NFS-3030) compatible. UL/ULC Listed Velocity Range: 0-4000 ft/min. (1219.2 m/
• Rotary, decimal addressing (1-99 on CLIP systems, 1-159 min.), suitable for installation in ducts.
on FlashScan systems). Relative Humidity: 10%-93% noncondensing.
• Optional remote, single-gang LED accessory.
Thermal Ratings: Fixed-temperature setpoint 135°F (57°C).
• Dual LED design provides 360° viewing angle.
• Visible bi-color LEDs blink green every time the detector is DETECTOR SPACING AND APPLICATIONS
addressed, and illuminate steady red on alarm (FlashScan Notifier recommends spacing detectors in compliance with
systems only). NFPA 72. In low airflow applications with smooth ceiling,
• Remote test feature from the panel. space detectors 30 feet (9.144m) for ceiling heights 10 feet
• Walk test with address display (an address on 121 will blink (3.148m) and higher. For specific information regarding
the detector LED: 12-[pause]-1(FlashScan systems only). detector spacing, placement, and special applications refer to
NFPA 72. System Smoke Detector Application Guide,
• Built-in functional test switch activated by external magnet. document A05-1003, is available at [Link]
• Built-in tamper-resistant feature.
ELECTRICAL SPECIFICATIONS
• Sealed against back pressure.
• Constructed of off-white Bayblend®, designed to commer- Voltage Range: 15-32 volts DC peak.
cial standards, and offers an attractive appearance. Standby Current (max. avg.): 300μA @ 24VDC (one com-
• 94-5V plastic flammability rating. munication every five seconds with LED enabled).
• SEMS screws for wiring of the separate base. LED Current (max.): 6.5mA @ 24VDC (‘ON’).
• Optional relay, isolator, and sounder bases. BASES AVAILABLE
NOTE: “A” suffix indicates ULC Listed model.
B200SR(A): Intelligent sounder base, configurable for temp-3 FSP-851TA:Same as FSP-851T but with ULC listing.
or steady sound. FSP-851R: Low-profile intelligent photoelectric sensor,
B224RB(A) Relay Base: Screw Terminals, up to 14AWG remote test capable. For use with DNRW.
(2.0mm2); Relay Type, Form-C; Rating, 2.0A @ 30VDC resis- FSP-851RA: Same as FSP-851R but with ULC listing.
tive, 0.3A @ 110VDC inductive, 1.0A @ 30VDC inductive;
Dimensions, 6.2” (15.748cm) x 1.2” (3.048cm) x 1.2” BASES
(3.048cm). B710LP: Standard U.S. low-profile base.
B224BI(A) Isolator Base: Dimensions, 6.2” (15.748cm) x 1.2” B710LPBP:Standard U.S. low-profile base, pkg. of 10.
(3.048cm) x 1.2” (3.048cm); Maximum, 25 devices between B710LPA:Standard U.S. low-profile base, ULC listing.
isolator bases.
B501BP:Standard European flangeless base, pkg. of 10.
Installation B501A:Standard European flangeless base, ULC listing.
FSP-851 plug-in detectors use a separate base to simplify B200SR(A): Intelligent sounder base, configurable for temp-3
installation, service, and maintenance. A special tool allows or steady sound.
maintenance personnel to plug in and remove detectors with- B224RB(A):Intelligent relay base.
out using a ladder.
B224BI(A):Intelligent isolator base. Isolates SLC from loop
Mount base on an electrical backbox which is at least 1.5” shorts.
(3.81cm) deep. Suitable mounting base boxes include:
• 4.0” (10.16cm) square box. ACCESSORIES
• 3.5” (8.89cm) or 4.0” (10.16cm) octagonal box. F110:Retrofit replacement flange for older style bases. Con-
verts older high profile base for use with FlashScan detectors.
• Single-gang box (except relay or isolator base).
• With B200SR base, use an appropriate junction box. RA100Z(A):Remote LED annunciator. 3-32VDC. Fits U.S.
single-gang electrical box. Supported by B710LP(A) and
• With B224RB or B224BI base, use a 3.5” (8.89cm) octago- B501(A) bases only.
nal box, or a 4.0” (10.16cm) octagonal or square box.
SMK400E:Surface mounting kit provides for entry of surface
NOTE: 1) Because of inherent supervision provided by the SLC
loop, end-of-line resistors are not required. Wiring “T-taps” or
wiring conduit. For use with B501(A) base only.
branches are permitted for style 4 (Class “B”) wiring. 2) When RMK400:Recessed mounting kit. For use with B501(A) base
using relay or sounder bases, consult data sheet DN-2243 (ISO-X) only.
for device limitations between isolator modules and isolator bases.
SMB600:Surface mounting kit for use with B710LP(A).
Agency Listings and Approvals BCK-200B:Black detector covers, box of 10. For use with
FSP-851 only.
These listings and approvals apply to the modules specified in
this document. In some cases, certain modules or applications WCK-200B: White detector covers, box of 10. For use with
may not be listed by certain approval agencies, or listing may FSP-851 only.
be in process. Consult factory for latest listing status. M02-04-00:Test magnet.
• UL Listed: S1115 M02-09-00:Test magnet with telescope stick.
• ULC Listed: S1115 (FSP-851A, FSP-851TA) XR2B:Detector removal tool. Allows installation and/or
• MEA Listed: 225-02-E removal of FlashScan Series detector heads from base in high
• FM Approved ceiling installations.
• CSFM: 7272-0028:206 T55-127-010:Detector removal tool without pole.
• Maryland State Fire Marshal: Permit # 2122 XP-4:Extension pole for XR2B. Comes in three 5-ft. sections.
• BSMI: CI313066760036
• CCCF: Certif. # 2004081801000017 (FSP-851T)
Certif. # 2004081801000016 (FSP-851)
• Lloyd’s Register: 03/60011
Addressable Devices
General
[Link]
Intelligent FlashScan® and CLIP mounting bases and kits pro-
vide a variety of ways to install NOTIFIER detectors in any appli-
cation. Intelligent detectors can be mounted in either flanged or
[Link]
flangeless bases depending on junction box selection (see
Junction Box Selection Guide). Across this product line, detec-
tors plug in easily to the base with SEMS screws; and models Relay Base
employ various 12 to 24 AWG wire ranges. Flangeless Mounting Base
Relay, isolator, and sounder bases can be used to meet local
[Link]
code requirements. Relay bases provide one Form-C contact
relay for control of auxiliary functions such as door closure and
elevator recall. Isolator bases allow loops to continue to operate
under fault conditions and automatically restore when the fault is
[Link]
removed. Sounder bases are available in temporal and non-tem-
poral pattern versions depending on whether the signal is to be
used for evacuation purposes. Recessed Mounting
Flanged Mounting Base
The RMK400 recessed mounting kit provides the most aes-
thetically pleasing installation. Surface mounting boxes are
[Link]
available when flush mounting isn’t possible.
Specifications
[Link]
Diameter: For B501: 4.1" (104 mm). For B224BI, B224RB,
B710LP: 6.1" (155 mm). For B501BH-2, B501BHT-2: 6.0" (152
mm). Standard Sounder Base Flangeless Surface Mounting
Wire gauge: for B224BI, B224RB: 14 to 24 AWG. For
B710LP,B501, B501BH-2, B501BHT-2: 12 to 24 AWG.
Temperature range: For B224BI, B224RB, B501BH-2, Startup capacitance: 200 μF.
B501BHT-2: 32°F to 120°F (0°C to 49°C). For B501 and
Sounder delay time: For B501BH-2 and B501BHT-2, 0.75 to
B710LP, -4°F to 150°F (0°C to 66°C).
5.7 seconds.
Humidity range: 10% to 93% RH, non-condensing.
Sound output: greater than 90 dBA measured in anechoic
System temperature and humidity ranges: This system room at 10 feet (3.048 m), 24 volts. 85 dBA minimum in UL
meets NFPA requirements for operation at 0°C to 49°C (32°F to reverberant room.
120°F); and at a relative humidity (noncondensing) of 85% at
30°C (86°F) per NFPA, and 93% ± 2% at 32°C ± 2°C (89.6°F ±
1.1°F) per ULC. However, the useful life of the system’s standby
Recessed Mounting Kit
batteries and the electronic components may be adversely The RMK400 can be used with drywall or suspended ceilings.
affected by extreme temperature ranges and humidity. There- The aesthetically pleasing design can be used with standard
fore, it is recommended that this system and all peripherals be junction boxes — suitable for use with 4.0” (10.16 cm) octago-
installed in an environment with a nominal room temperature of nal, 50 mm, and 60 mm junction boxes connected to flexible
15°C to 27°C (60°F to 80°F). conduit. Note that junction boxes are not included in the kit. As
an application example, with the B501 base, the RMK400 pro-
Electrical Ratings vides a simple installation solution in applications that demand a
lower-profile smoke detector.
FOR B224RB, B224BI:
Operating voltage: 15 to 32 VDC (powered by SLC). Product Line Information
Standby ratings: <500 μA maximum @ 24 VDC. INTELLIGENT BASES
Set time (B224RB only): short delay 55 to 90 msec; long delay B501: Flangeless mounting base.
6 to 9 seconds.
B501A: Flangeless mounting base, ULC Listed.
Reset time (B224RB only): 20 msec maximum.
B501BP: Flangeless mounting base, ULC Listed.
Relay characteristics (B224RB only): two-coil latching relay;
one Form-C contact; ratings (UL/CSA): 0.9 A @ 125 VAC, 0.9 A B710LP: Flanged mounting base.
@ 110 VDC, and 3.0 A @ 30 VDC. B710LPA: Flanged mounting base, ULC Listed.
FOR B501BH-2, B501BHT-2: B710LPBP: Flanged mounting base.
External supply voltage: 17 to 32 VDC. B501BH-2: Plug-in System Sensor standard sounder detec-tor
base, steady tone. Includes B501 base.
Standby current: 1.0 mA maximum.
B501BHT-2: Plug-in System Sensor temporal tone sounder
Alarm current: 15 mA maximum. base.
Maximum ripple voltage: 10% of supply voltage.
California
GENERAL State Fire
Marshal
The NBG-12LR and NBG-12LRA are Agent Release Sta-
tions designed for use with NOTIFIER Fire Alarm Control 7150-0028:199
Panels with releasing capabilities and RP Series Releas-
ing Systems.
S692
FEATURES Approved
Non-coded, dual action operation.
Made with durable polycarbonate.
Optional surface backbox.
NBG-12LRA includes:
" Abort switch.
" Power-on indication.
" Released indication.
" Manual release (dual-action).
NBG-12LR includes:
" Dual-action release only.
APPLICATIONS
The NBG-12LRA and NBG-12LR are ideal for areas such
as clean rooms and computer rooms where a chemical
agent is used to extinguish a fire.
[Link]
NOTIFIER
Dual-Action NBG-12LRA
(shown activated)
This document is not intended to be used for installation purposes. We try to keep our
product information up-to-date and accurate. We cannot cover all specific applications or
anticipate all requirements. All specifications are subject to change without notice.
For more information, contact NOTIFIER. Phone: (203) 484-7161 FAX: (203) 484-7118
[Link]
Dual-Action NBG-12LR
NOTIFIER
[Link]
DIMENSIONS, BACKBOXES
12345678901234
12345678901234
12345678901234
12345678901234
Normally Open
12345678901234
12345678901234
12345678901234
Abort Switch
12345678901234
12345678901234
[Link]
[Link]
General
FCM-1(A) Control Module: The FCM-1(A) Addressable Con-
trol Module provides Notifier intelligent fire alarm control pan-
els a circuit for Notification Appliances (horns, strobes,
speakers, etc.) Addressability allows the FCM-1(A) to be acti-
vated, either manually or through panel programming, on a
select (zone or area of coverage) basis.
FRM-1(A) Relay Module: The FRM-1(A) Addressable Relay
Module provides the system with a dry-contact output for acti-
vating a variety of auxiliary devices, such as fans, dampers,
control equipment, etc. Addressability allows the dry contact to
be activated, either manually or through panel programming,
on a select basis.
FlashScan® (U.S. Patent 5,539,389) is a communication pro-
tocol developed by NOTIFIER Engineering that greatly
enhances the speed of communication between analog intelli-
[Link]
gent devices. Intelligent devices communicate in a grouped
fashion. If one of the devices within the group has new infor-
mation, the panel CPU stops the group poll and concentrates
on single points. The net effect is response speed greater than
five times that of other designs.
FCM-1(A)
Features
• Built-in type identification automatically identifies these • The FCM-1(A) is configured for a single Class B (Style Y) or
devices to the control panel. Class A (Style Z) Notification Appliance Circuit.
• Internal circuitry and relay powered directly by two-wire • The FRM-1(A) provides two Form-C dry contacts that
SLC loop. The FCM-1(A) module requires power (for horns, switch together.
strobes, etc.), or audio (for speakers).
• Integral LED “blinks” green each time a communication is Operation
received from the control panel and turns on in steady red Each FCM-1(A) or FRM-1(A) uses one of 159 possible module
when activated. addresses on a SLC loop (99 on CLIP loops). It responds to
• LED blink may be deselected globally (affects all devices). regular polls from the control panel and reports its type and
• High noise immunity (EMF/RFI). status, including the open/normal/short status of its Notifica-
tion Appliance Circuit (NAC). The LED blinks with each poll
• The FCM-1(A) may be used to switch 24-volt NAC power, received. On command, it activates its internal relay. The
audio (up to 70.7 Vrms). FCM-1(A) supervises Class B (Style Y) or Class A (Style Z)
• Wide viewing angle of LED. notification or control circuits.
• SEMS screws with clamping plates for wiring ease. Upon code command from the panel, the FCM-1(A) will dis-
• Direct-dial entry of address 01– 159 for FlashScan loops, connect the supervision and connect the external power sup-
01 – 99 for CLIP mode loops. ply in the proper polarity across the load device. The
• Speaker, and audible/visual applications may be wired for disconnection of the supervision provides a positive indication
Class B or A (Style Y or Z). to the panel that the control relay actually turned ON. The
external power supply is always relay isolated from the com-
munication loop so that a trouble condition on the external
Applications power supply will never interfere with the rest of the system.
The FCM-1(A) is used to switch 24 VDC audible/visual power, Rotary switches set a unique address for each module. The
high-level audio (speakers), or control telephone devices. The address may be set before or after mounting. The built-in
FRM-1(A) may be programmed to operate dry contacts for
TYPE CODE (not settable) will identify the module to the con-
applications such as door holders or Air Handling Unit shut- trol panel, so as to differentiate between a module and a sen-
down, and to reset four-wire smoke detector power. sor address.
NOTE: Refer to the SLC Manual (PN 51253) for details regarding
releasing applications with the FCM-1(A). Refer to the FCM-1-REL
datasheet (DN-60390) for new FlashScan® releasing applications.
Specifications for FCM-1(A)
Normal operating voltage: 15 to 32 VDC.
Construction Maximum current draw: 6.5 mA (LED on).
• The face plate is made of off-white heat-resistant plastic. Average operating current: 350 μA direct poll, 375 μA group
• Controls include two rotary switches for direct-dial entry of poll with LED flashing, 485 μA Max. (LED flashing, NAC
address (01-159). shorted.)
FMM-1, FMM-101,
FZM-1 & FDM-1
Monitor Modules with FlashScan®
Intelligent/Addressable Devices
General
Four different monitor modules are available for Notifier’s intel-
ligent control panels for a variety of applications. Monitor mod-
ules supervise a circuit of dry-contact input devices, such as
conventional heat detectors and pull stations, or monitor and
power a circuit of two-wire smoke detectors (FZM-1).
FMM-1 is a standard-sized module (typically mounts to a 4"
[10.16 cm] square box) that supervises either a Class A (Style
D) or Class B (Style B) circuit of dry-contact input devices.
FMM-101 is a miniature monitor module (a mere 1.3" (3.302
cm) H x 2.75" (6.985 cm) W x 0.5" (1.270 cm) D) that super-
vises a Class B (Style B) circuit of dry-contact input devices.
Its compact design allows the FMM-101 to often be mounted
in a single-gang box behind the device it monitors.
FZM-1 is a standard-sized module that monitors and super-
[Link]
vises compatible two-wire, 24 volt, smoke detectors on a
Class A (Style D) or Class B (Style B) circuit.
FDM-1 is a standard-sized dual monitor module that monitors
and supervises two independent two-wire Style B (Class B)
dry-contact initiating device circuits (IDCs) at two separate, FMM-1 (Type H)
consecutive addresses in intelligent, two-wire systems.
A) Initiating Device Circuit. A 47K ohm End-of-Line Resistor
FlashScan® (U.S. Patent 5,539,389) is a communication pro- (provided) terminates the Style B circuit. No resistor is
tocol developed by NOTIFIER that greatly increases the speed required for supervision of the Style D circuit.
of communication between analog intelligent devices. Intelli-
gent devices communicate in a grouped fashion. If one of the FMM-1 OPERATION
devices within the group has new information, the panel CPU Each FMM-1 uses one of the available module addresses on
stops the group poll and concentrates on single points. The an SLC loop. It responds to regular polls from the control panel
net effect is response speed greater than five times that of and reports its type and the status (open/normal/short) of its
other designs. protocols. Initiating Device Circuit (IDC). A flashing LED indicates that
the module is in communication with the control panel. The
FMM-1 Monitor Module LED latches steady on alarm (subject to current limitations on
the loop).
• Built-in type identification automatically identifies this device
as a monitor module to the control panel. FMM-1 SPECIFICATIONS
• Powered directly by two-wire SLC loop. No additional power Nominal operating voltage: 15 to 32 VDC.
required.
Maximum current draw: 5.0 mA (LED on).
• High noise (EMF/RFI) immunity.
Maximum operating current: 375 µA (LED flashing).
• SEMS screws with clamping plates for ease of wiring.
Maximum IDC wiring resistance: 1,500 ohms.
• Direct-dial entry of address: 01 – 159 on FlashScan sys-
tems; 01 – 99 on CLIP systems. , 01 – 99 on . EOL resistance: 47K ohms.
• LED flashes green during normal operation (this is a pro- Temperature range: 32°F to 120°F (0°C to 49°C).
grammable option) and latches on steady red to indicate
Humidity range: 10% to 93% noncondensing.
alarm.
The FMM-1 Monitor Module is intended for use in intelligent, Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x
two-wire systems, where the individual address of each mod- 1.25" (3.175 cm) deep. Mounts to a 4" (10.16 cm) square x
ule is selected using the built-in rotary switches. It provides 2.125" (5.398 cm) deep box.
either a two-wire or four-wire fault-tolerant Initiating Device Cir-
cuit (IDC) for normally-open-contact fire alarm and supervisory FMM-101 Mini Monitor Module
devices. The module has a panel-controlled LED indicator.
• Built-in type identification automatically identifies this device
The FMM-1 can be used to replace MMX-1 modules in
as a monitor module to the panel.
existing systems.
• Powered directly by two-wire SLC loop. No additional power
FMM-1 APPLICATIONS required.
Use to monitor a zone of four-wire smoke detectors, manual • High noise (EMF/RFI) immunity.
fire alarm pull stations, waterflow devices, or other normally- • Tinned, stripped leads for ease of wiring.
open dry-contact alarm activation devices. May also be used
• Direct-dial entry of address: 01 – 159 on FlashScan sys-
to monitor normally-open supervisory devices with special
tems; 01 – 99 on CLIP systems. , 01 – 99 on .
supervisory indication at the control panel. Monitored circuit
may be wired as an NFPA Style B (Class B) or Style D (Class
[Link]
ble option.
• LED latches steady to indicate alarm on command from
control panel.
The FZM-1 Interface Module is intended for use in intelligent,
addressable systems, where the individual address of each
module is selected using built-in rotary switches. This module
allows intelligent panels to interface and monitor two-wire con-
ventional smoke detectors. It transmits the status (normal,
open, or alarm) of one full zone of conventional detectors back
to the control panel. All two-wire detectors being monitored
must be UL compatible with the module. The FZM-1 can be
used to replace MMX-2 modules in existing systems.
FZM-1 APPLICATIONS
Use the FZM-1 to monitor a zone of two-wire smoke detectors.
The monitored circuit may be wired as an NFPA Style B (Class
B) or Style D (Class A) Initiating Device Circuit. A 3.9 K ohm
End-of-Line Resistor (provided) terminates the end of the Style
The FMM-101 Mini Monitor Module can be installed in a sin- B or D (class B or A) circuit (maximum IDC loop resistance is
gle-gang junction directly behind the monitored unit. Its small 25 ohms). Install ELR across terminals 8 and 9 for Style D
size and light weight allow it to be installed without rigid mount- application.
ing. The FMM-101 is intended for use in intelligent, two-wire FZM-1 OPERATION
systems where the individual address of each module is
selected using rotary switches. It provides a two-wire initiating Each FZM-1 uses one of the available module addresses on
device circuit for normally-open-contact fire alarm and security an SLC loop. It responds to regular polls from the control panel
devices. The FMM-101 can be used to replace MMX-101 and reports its type and the status (open/normal/short) of its
modules in existing systems. Initiating Device Circuit (IDC). A flashing LED indicates that
the module is in communication with the control panel. The
FMM-101 APPLICATIONS LED latches steady on alarm (subject to current limitations on
Use to monitor a single device or a zone of four-wire smoke the loop).
detectors, manual fire alarm pull stations, waterflow devices, or FZM-1 SPECIFICATIONS
other normally-open dry-contact devices. May also be used to
monitor normally-open supervisory devices with special super- Nominal operating voltage: 15 to 32 VDC.
visory indication at the control panel. Monitored circuit/device Maximum current draw: 5.1 mA (LED on).
is wired as an NFPA Style B (Class B) Initiating Device Circuit.
Maximum IDC wiring resistance: 25 ohms.
A 47K ohm End-of-Line Resistor (provided) terminates the cir-
cuit. Maximum operating current: 270 µA (LED flashing).
EOL resistance: 3.9K ohms.
FMM-101 OPERATION
Each FMM-101 uses one of the available module addresses External supply voltage (between Terminals T3 and T4):
on an SLC loop. It responds to regular polls from the control DC voltage: 24 volts power limited. Ripple voltage: 0.1 Vrms
panel and reports its type and the status (open/normal/short) maximum. Current: 90 mA per module maximum.
of its Initiating Device Circuit (IDC). Temperature range: 32°F to 120°F (0°C to 49°C).
FMM-101 SPECIFICATIONS Humidity range: 10% to 93% noncondensing.
Nominal operating voltage: 15 to 32 VDC. Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x
1.25" (3.175 cm) deep. Mounts to a 4" (10.16 cm) square x
Maximum operating current: 375 µA.
2.125" (5.398 cm) deep box.
Maximum IDC wiring resistance: 1,500 ohms.
EOL resistance: 47K ohms. FDM-1 Dual Monitor Module
Temperature range: 32°F to 120°F (0°C to 49°C). The FDM-1 Dual Monitor Module is intended for use in intelli-
Humidity range: 10% to 93% noncondensing. gent, two-wire systems. It provides two independent two-wire
initiating device circuits (IDCs) at two separate, consecutive
Dimensions: 1.3" (3.302 cm) high x 2.75" (6.985 cm) wide x addresses. It is capable of monitoring normally open contact
0.65" (1.651 cm) deep. fire alarm and supervisory devices; or either normally open or
Wire length: 6" (15.24 cm) minimum. normally closed security devices. The module has a single
panel-controlled LED.
FZM-1 Interface Module NOTE: The FDM-1 provides two Class B (Style B) IDC circuits
ONLY. Class A (Style D) IDC circuits are NOT supported in any
• Supports compatible two-wire smoke detectors. application.
• Supervises IDC wiring and connection of external power
source. FDM-1 SPECIFICATIONS
• High noise (EMF/RFI) immunity. Normal operating voltage range: 15 to 32 VDC.
• SEMS screws with clamping plates for ease of wiring. Maximum current draw: 6.4 mA (LED on).
• Direct-dial entry of address: 01 – 159 on FlashScan sys- Maximum operating current: 750 µA (LED flashing).
tems, 01 – 99 on CLIP systems. Maximum IDC wiring resistance: 1,500 ohms.
CAUTION:
! Avoid duplicating addresses on the system.
Installation
FMM-1, FZM-1, and FDM-1 modules mount directly to a stan-
dard 4" (10.16 cm) square, 2.125" (5.398 cm) deep, electrical
box. They may also be mounted to the SMB500 surface-mount
box. Mounting hardware and installation instructions are pro-
vided with each module. All wiring must conform to applicable
local codes, ordinances, and regulations. These modules are
intended for power-limited wiring only.
The FMM-101 module is intended to be wired and mounted
without rigid connections inside a standard electrical box. All
wiring must conform to applicable local codes, ordinances, and
regulations.
FCM-1-REL(A)
Releasing Control Module
Intelligent/Addressable Devices
General
The FCM-1-REL Releasing Control Module is specifically
designed for fire suppression releasing applications in Flash-
Scan® systems. Power to the release agent solenoid(s) runs
through the module for full-time monitoring and supervision.
The FCM-1-REL Releasing Control Module uses a redun-
dant protocol; the module must be armed with a pair of sig-
nals in order to activate. It will then enter a 3-second window
awaiting a pair of confirmation signals. If no confirmation is
received, the module will automatically reset. It also super-
vises the wiring to the connected load and reports the status
to the panel as NORMAL, OPEN, or SHORT CIRCUIT. The
module has two pairs of output termination points available
for fault-tolerant wiring and a panel-controlled LED indicator.
The module may be connected to either one 24VDC solenoid
or up to two 12VDC solenoids (in series). To ensure proper
operation, this module shall be connected to a compatible
Notifier system control panel only (list available from Notifier).
[Link]
In addition, please refer to Notifier Device Compatibility Doc-
ument PN 15378 for the list of compatible solenoids.
NOTE: FCM-1-REL is required for all new FlashScan-mode
releasing applications with NFS2-3030 (version 14.0 or higher),
NFS2-640 (version 12.0 or higher) and NFS-320(E)(C) (version
FCM-1-REL
12.0 or higher) panels. Use FCM-1 for releasing applications on
NFS-640, NFS-3030, and all CLIP mode panels.
EXTERNAL SUPPLY
Features • Normal Operating Voltage: 24 VDC Nominal
• Redundant protocol for added protection • Maximum Line Loss: 2.3 VDC (total allowable loss from
• Configurable for Class A or Class B operation power supply to module and from module to solenoid)
• External supply voltage monitoring • Minimum Operating Voltage to Activate Solenoid:
• Can power one 24V or two 12V solenoids 18 VDC (at solenoid)
• SEMS screws for easing wiring • Standby Current: 6.4 mA
• Panel controlled status LED • Activation Current: 10 mA
• Analog communications SOLENOID
• Rotary address switches • Supervisory Loop Voltage: 3.3 V
• Low standby current • Supervisory Loop Current (Normal): 30 mA
• Mounts in standard 4" (10.16 cm) junction box • Maximum Activation Current: 2 A
• FlashScan operation
Product Line Information
Specifications NOTE: “A” suffix indicates ULC Listed model.
FCM-1-REL(A): Releasing Control Module.
GENERAL SPECIFICATIONS
• Operating Voltage: 15 to 32 VDC SMB500: Optional Surface-Mount Backbox.
• Communication Line Loop Impedance: 40 Ohm max. CB500: Control Module Barrier — required by UL for sepa-
• Temperature Range: 14°F to 140°F (-10° to 60°C) rating power-limited and non-power limited wiring in the
same junction box as FCM-1-REL.
• Relative Humidity: 10% to 95% noncondensing
• Shipping Weight: 5.5 oz (156 g)
• Dimensions: 4.275" W × 4.675" H × 1.400" D
(10.86 cm W × 11.87 cm H × 3.56 cm D)
SLC
• Average Operating Current: 700 µA max @ 24 VDC
(one communication every 5 sec. with LED enabled)
• Maximum Activation Current: 9.0 mA (LED on)
SpectrAlert® Advance
Selectable Output
Notification Appliances
Audio/Visual Devices
DC Input 135 150 177 185 FWR Input 135 150 177 185
DC, Temporal, High 245 259 290 297 FWR, Temporal, High 215 231 258 265
DC, Temporal, Medium 235 253 288 297 FWR, Temporal, Medium 209 224 250 258
DC, Temporal, Low 232 251 282 292 FWR, Temporal, Low 207 221 248 256
DC, Non-temporal, High 255 270 303 309 FWR, Non-temporal, High 233 248 275 281
DC, Non-temporal, Medium 242 259 293 299 FWR, Non-temporal, Medium 219 232 262 267
DC, Non-temporal, Low 238 254 291 295 FWR, Non-temporal, Low 214 229 256 262
[Link]
For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118.
[Link]
SSM Series
Alarm Bells
Audio/Visual Appliances
General
System Sensor’s SSM Series alarm bells are low-current,
high-decibel notification appliances for use in fire and burglary
systems or other signaling applications. They come pre-wired
to reduce installation time, and also incorporate a polarized
electrical design for use with supervision circuitry.
With reliable performance, SSM Series alarm bells provide
loud, resonant tones. They operate on 24 VDC and are motor-
driven.
SSM Series alarm bells offer simplified installation. For indoor
use, SSM Series alarm bells mount to a standard 4" (10.16
cm) square electrical box. For outdoor applications, a WBB
weatherproof backbox is used.
[Link]
Features
• Approved for indoor or outdoor (with WBB backbox) use.
• Low current draw.
• High dB output.
• Three sizes available: 6" (15.24 cm), 8" (20.32 cm), and Agency Listings and Approvals
10" (25.40 cm) diameter. These listings and approvals apply to the modules specified in
• 24 VDC models; polarized for use with supervision circuitry. this document. In some cases, certain modules or applications
• Bells mount directly to standard 4" (10.16 cm) square elec- may not be listed by certain approval agencies, or listing may
trical box. be in process. Consult factory for latest listing status.
• UL Listed: S4011
Specifications • ULC Listed: S7539 (SSM24-6A, SSM24-8A, SSM24-10A)
Nominal voltage: 24 VDC. • MEA Listed: 331-01-E
Operating voltage range: 19.2 to 26.4 VDC. • FM Approved
Average current draw: 0.03 A. • CSFM: 7135-1653:125
Termination: provided with two sets of leads for in/out wiring. SSM24-6A: Canadian model of 6" bell above.
Service use: Fire Alarm, General Signaling, Burglar Alarm. SSM24-8: 8" (20.32 cm) bell, 24 VDC, polarized, 85 dBA.
SSM24-8A: Canadian model of 8" bell above.
Engineering and Architectural SSM24-10: 10" (25.40 cm) bell, 24 VDC, polarized, 85 dBA.
Specifications SSM24-10A: Canadian model of 10" above.
Model shall be a SSM Series alarm bell. Bells shall have WBB: Weatherproof backbox.
underdome strikers and operating mechanisms. Gongs on
said bell shall be no smaller than nominal 6" (15.24 cm), 8"
(20.32 cm), or 10" (25.40 cm) (specify size) with an operating
voltage of 24 VDC. Bells shall be suitable for surface or semi-
flush mounting. Outdoor surface-mounted installations shall
be weatherproof (using optional WBB weatherproof backbox);
otherwise, bells shall mount to a standard 4" (10.16 cm)
square electrical box having a minimum projection of 2.5"
(6.35 cm). Bells shall be located as shown on the installation
drawings or as determined by the Authority Having Jurisdic-
tion. Bells shall be Listed for indoor/outdoor use by Underwrit-
ers Laboratories, ULC (Canada), and the California State Fire
Marshal, and approved by Factory Mutual and MEA.
ISO-X
Fault Isolator Module
Intelligent/Addressable Devices
General
The Notifier ISO-X Fault Isolator Module is used with the NFS-
3030, NFS2-3030, NFS-640, NFS2-640, NFS-320, and AFP-
200 to protect the system against wire-to-wire short circuits on
the SLC loops.
Features
• Powered by SLC loop directly, no external power required.
• Mount in standard 4.0" (10.16 cm) square (2.125" [5.398
cm] deep) junction boxes.
• Integral LED blinks to indicate normal condition. Illuminates
steady when short circuit condition is detected.
• High noise (EMF/RFI) immunity.
[Link]
• Wide viewing angle of LED.
• SEMS screws with clamping plates for ease of wiring.
• Opens SLC loop automatically on detection of short, pre-
venting the short from causing failure of the entire loop.
• Automatically resets on correction of short.
• Supports Style 4, 6, or 7 wiring.
Applications ISO-X
The Fault Isolator Modules should be spaced between groups
of sensors in a loop to protect the rest of the loop. Use to iso-
late short circuit problems within a section of a loop so that
other sections can continue to operate normally. The ISO-X
Construction
supports a maximum of 25 devices in-between isolators, The face plate is made of off-white plastic. Includes yellow
except when using relay bases or IPX multisensors. LED indicator that pulses when normal and illuminates steady
NOTE: ON LOADS PER RELAY BASE AND MULTI-SENSOR when a short is detected.
DETECTORS/ISOLATORS/ISOLATOR BASES: the maximum
number of addressable devices between isolators (or B224BI iso- Operation
lator bases) is 25 devices.
Automatically opens circuit when the line voltage drops below
four volts. Fault Isolator Modules should be spaced between
groups of addressable devices (maximum 25, see notes on
page 1) in a loop to protect the rest of the loop. If a short
occurs between any two isolators, then both isolators immedi-
[Link]
ately switch to an open circuit state and isolate the groups of
sensors between them. The remaining units on the loop con-
B224RB relay bases and IPX-751 multisensor detectors draw tinue to fully operate.
more current than all other intelligent devices. When calculat-
ing the 25-device maximum: In Style 4 loops, the ISO-X is generally used at each T-tap
branch, to limit the effect of short circuits on a branch to the
• B224RB represents 2.5 devices. devices on that branch. The LED indicator is on continuously
• IPX-751 in a standard base represents 12 devices. during a short circuit condition.
• IPX-751 in a relay base represents 14.5 devices. The ISO-X Fault Isolator Module automatically restores the
• All other addressable devices represent 1 device. shorted portion of the communications loop to normal condi-
See examples on page 2. tion when the short circuit condition is removed.
Example 1
[Link]
Example 2
[Link]
Example 3
ordering.
TYCO FIRE SUPPRESSION & BUILDING PRODUCTS Copyright ©2010 Tyco Fire Suppression & Building Products
ONE STANTON STREET All rights reserved.
MARINETTE, WI 54143-2542 715-735-7411 Form No. F-2003184-3
ANSUL ®
System Components
UL EX-4510 12-1-03 Page 1-1
ANSUL INCORPORATED, ONE STANTON STREET, MARINETTE, WI 54143-2542 715-735-7411 Form No. F-2003183 © 2003 Ansul Incorporated Litho in U.S.A.
ANSUL ®
System Components
UL EX-4510 12-1-03 Page 1-7
Shipping “A”
Assembly Dimension
Part No. Description in. (cm)
570085 Bracket Assembly for 15.7 (40)
20, 50, and 90 lb. tanks
(10 in. diameter)
570092 Bracket Assembly for 23.6 (60)
140, 280, 390, and
450 lb. tanks
(16 in. diameter)
570336 Bracket Assembly for 27.3 (69)
850 lb. tank
(24 in. diameter)
ANSUL INCORPORATED, ONE STANTON STREET, MARINETTE, WI 54143-2542 715-735-7411 Form No. F-2003189 © 2003 Ansul Incorporated Litho in U.S.A.
ANSUL ®
System Components
UL EX-4510 12-1-03 Page 1-19
006255
Shipping Assembly
Part No. Description
570277 Liquid Level Indicator for
280 lb. Tank
570278 Liquid Level Indicator for
390 and 850 lb. Tanks
570589 Liquid Level Indicator for
450 lb. Tank
ANSUL INCORPORATED, ONE STANTON STREET, MARINETTE, WI 54143-2542 715-735-7411 Form No. F-2003203 © 2003 Ansul Incorporated Litho in U.S.A.
ANSUL ®
System Components
UL EX-4510 12-1-03 Page 1-10
Shipping Assembly
Part No. Description
69841 3 in. Discharge Hose/
Check Valve Assembly
ANSUL INCORPORATED, ONE STANTON STREET, MARINETTE, WI 54143-2542 715-735-7411 Form No. F-2003191 © 2003 Ansul Incorporated Litho in U.S.A.
ANSUL ®
System Components
UL EX-4510 12-1-03 Page 1-9
Thread
Component Material Type Approvals
Check Body: 1 in. NPT UL Listed 006889
Valve Brass and ULC Listed
Stem and 2 in. NPT FM Approved
Seal:
Stainless
Steel
Shipping Assembly
Part No. Description
570566 1 in. Manifold Check Valve
570568 2 in. Manifold Check Valve
ANSUL INCORPORATED, ONE STANTON STREET, MARINETTE, WI 54143-2542 715-735-7411 Form No. F-2003192 © 2003 Ansul Incorporated Litho in U.S.A.
ANSUL ®
System Components
UL EX-4510 12-1-03 Page 1-4
Thread
Component Material Type Approvals
Electric Body: Steel 1 in. UL Listed
Actuator Swivel Nut: BSPP ULC Listed
Brass FM Approved
Actuation Pin:
1.8 IN.
Stainless (45 mm)
Steel
Shipping Assembly
Part No. Description
570537 Electric Actuator
ANSUL INCORPORATED, ONE STANTON STREET, MARINETTE, WI 54143-2542 715-735-7411 Form No. F-2003186 © 2003 Ansul Incorporated Litho in U.S.A.
System Components
UL EX-4510 12-1-03 Page 1-13
Shipping Assembly
Part No. Description
570549 Local Manual Actuator
ANSUL INCORPORATED, MARINETTE, WI 54143-2542 715-735-7411 Form No. F-2003195 Copyright © 2008 Ansul Incorporated
ANSUL ®
System Components
UL EX-4510 12-1-03 Page 1-12
Pneumatic Actuator
006764
Shipping Assembly
Part No. Description
570550 Pneumatic Actuator
ANSUL INCORPORATED, ONE STANTON STREET, MARINETTE, WI 54143-2542 715-735-7411 Form No. F-2003194 © 2003 Ansul Incorporated Litho in U.S.A.
System Components
UL EX-4510 4-1-05 Page 1-20
REV. 1
1/4 in. Actuation Hose Male Actuation Tee – Part No. 31811
The 1/4 in. stainless steel actuation hose is used to connect The male actuation tee is used to connect multiple actua-
the 1/4 in. actuation line to the pneumatic actuator located tion hoses together. The actuation tee has a 7/16-20 thread
on the tank valve. The hose is used when the actuation line for connecting to the female actuation hose and a NPT
is rigid 1/4 in. pipe and fittings. The hose has a 1/4 in. NPT thread for connecting to the pneumatic actuator on the tank
male thread on one end and a 7/16-20 female thread on the valve.
other end. A male straight adaptor, Part No. 32338, is 7/16 – 20
required with this hose. Three lengths of hoses are
available.
SEE CHART
000435
000432
Part No.
______ Description
_________
73597 16 in. (40.6 cm) Hose Male Actuation Elbow – Part No. 31810
415142 32 in. (81.3 cm) Hose The male actuation elbow is used to connect the actuation
430815 42 in. (106.7 cm) Hose hose to a single or last tank in a multiple tank system. The
elbow connects between the hose and the pneumatic actu-
1/4 in. Female Actuation Hose – Part No. 32336 ator on the valve. The elbow has a 7/16-20 thread for con-
The 1/4 in. stainless steel, female actuation hose is used to necting to the hose and a 1/4 in. NPT thread for connecting
connect the actuation line compression tees between each to the pneumatic actuator on the tank valve.
agent tank. The hose has the same thread, 7/16-20, as the
7/16 – 20
compression tees.
24 IN.
(61 cm)
000433
000436
Male Actuation Connector – Part No. 32338 Male Adaptor – Part No. 570342
The male connector is used to connect the 1/4 in. female The male adaptor is required to attach the 1/4 in. actuation
actuation hose to rigid 1/4 in. actuation fittings and also the hose to the master tank pilot port. When using the male
pneumatic actuator. The connector has a 7/16-20 thread for adaptor on the master tank pilot port, a 1/4 in. pipe coupling
connecting to the actuation hose and a 1/4 in. NPT thread must be used between the adaptor and the male hose
for connecting to the actuation piping and pneumatic thread.
actuator.
1/4 – 18 NPT
1/4 IN. MALE 1/4 IN.
BSP MALE NPT
004820
000434
7/16 – 20
ANSUL INCORPORATED, MARINETTE, WI 54143-2542 715-735-7411 Form No. F-2003200-1 Copyright © 2008 Ansul Incorporated
ANSUL ®
System Components
UL EX-4510 12-1-03 Page 1-15
below 290 psi (20 bar), the switch operates, enabling the
condition to be signaled at the control panel.
The low pressure switch is optional and must be ordered
separately when ordering the SAPPHIRE tank.
Shipping Assembly
Part No. Description
570585 Low Pressure Switch
Switch Electrical
Component Material Point/Type Rating Approvals
Low Pressure Hermetically Sealed Opens on fall at Maximum Current: UL Listed
Switch Stainless Steel Body 290 psi +/- 10 psi 2.9A ULC Listed
(20 bar +/- .7 bar) Voltage Range: FM Approved
5-28 VDC
6 ft. (1.8 m) Wire Leads Closes on rise at
350 psi +/- 10 psi
(24 bar +/- .7 bar)
ANSUL INCORPORATED, ONE STANTON STREET, MARINETTE, WI 54143-2542 715-735-7411 Form No. F-2003197 © 2003 Ansul Incorporated Litho in U.S.A.
System Components
UL EX-4986 4-1-10 Page 2-16
Shipping Assembly
Part No. Description
46250 Pressure Switch – DPST
Thread Electrical
Component Material Size/Type Rating Approvals
Pressure Switch Switch: BAKELITE Conduit Inlet: 2 HP – 240 UL Listed
DPST 3/4 in. NPT Female VAC/480 VAC ULC Listed
Housing: Malleable Iron Pressure Inlet: 2 HP – 250 VDC FM Approved
Piston: Brass 1/4 in. NPT Female 30A – 250V AC/DC
Cover: Brass 5A – 480V AC/DC
PYRO-CHEM is a trademark of Tyco Fire Suppression & Building Products or its affiliates. PC2009037
System Components
UL EX-4510 12-1-03 Page 1-17
Warning Signs
Shipping Assembly
Part No. Description
570580 Warning Sign
570581 Agent Discharge Warning Sign LABEL NO. 570580
006894
006895
ANSUL INCORPORATED, MARINETTE, WI 54143-2542 715-735-7411 Form No. F-2003199 Copyright © 2008 Ansul Incorporated
ANSUL
Detection and Control Components
Applications POLARITY IS
SHOWN
The Key Maintenance Switch is used to interrupt the release IN ALARM
24 VDC POWER CONDITION
circuit signal to the fire suppression system. It is key-operat- SOURCE
ed to allow authorized personnel to deactivate the release
circuit during service or maintenance. An indicator lamp, 24 VDC
INDICATOR LAMP
located on the switch plate, will light when the switch is in the
* SEE CONTROL UNIT MANUAL FOR SPECIFIC WIRING REQUIREMENTS.
“lock-out” mode to serve as a reminder that the release cir-
cuit has been disconnected.
MOUNTING DIMENSIONS
SURFACE-MOUNT FLUSH-MOUNT
4 11/16 IN. 3 1/8 IN. 2 3/4 IN.
(119 mm) (79 mm) (70 mm)
NORMAL
LOCK-OUT
4 5/8 IN.
(117 mm)
ANSUL
FIRE SUPPRESSION SYSTEM ABORT
3-33
ANSUL INCORPORATED, ONE STANTON STREET, MARINETTE, WI 54143-2542 715-735-7411 Form No. F-95110-1 2003 Ansul Incorporated Litho in U.S.A.
ANSUL ®
System Components
UL EX-4510 12-1-03 Page 1-11
Discharge Nozzles
Shipping Assembly
Part No. Description
570515 1/2 in Nozzle – 180°
570516 3/4 in. Nozzle – 180°
570517 1 in. Nozzle – 180°
004840
570518 1 1/4 in. Nozzle – 180° 180° NOZZLE 360° NOZZLE
PATTERN PATTERN
570519 1 1/2 in. Nozzle – 180°
570520 2 in. Nozzle – 180°
570602 1/2 in. Nozzle – 360°
570603 3/4 in. Nozzle – 360°
570604 1 in. Nozzle – 360°
570605 1 1/4 in. Nozzle – 360°
570606 1 1/2 in. Nozzle – 360°
570607 2 in. Nozzle – 360°
ANSUL INCORPORATED, ONE STANTON STREET, MARINETTE, WI 54143-2542 715-735-7411 Form No. F-2003193 © 2003 Ansul Incorporated Litho in U.S.A.
() () () ()
.
()
()
-4: "
>"Ic-
>> ." -4:-'" -....-
.~
~I I I§-4:
-
J> J>
< -< ~
;:~
.... ....
. -< ....
- -
~
- J>
J>
~
~ "
"
()
~
-' > " -' ~::1-,~
-' J>
<" <-'-' -'-'
J> () J> J>
< .... <
-4:
-'
.... . -" -....
-"
-<
-4:-'
, <
~
.
.~
-'
~
.
-<
>>>>>>>>>>>
-A.,z~~,.6:>,..A>J;I-«,..[Link]\"
~::::~~~~~:;5::£
• .~ _ < J ~ _ ~ ~ ~ ~
r > > > > > > > > > > > > > >.> > > >
o .-If .,..b J>
:;~~~~:<;:~o~~~-;;:::rl-;;£
o > ~ 1 ~ > -A .-If 0
~ "J ...". -A
< _ ~ . - ,~ .. -
"s -A 0 .,J ,... J> .,..0. ...... ~ -
r
r'41 t..
-4:-[Link].-t. .. o ..... < .. ~\ < > .. 0 ~ _ -'4. .....c: .-b < ~ _ 0 ..... ..~, -
.-..,z. c, -<>L -"--" .... ". '-'J>"J><-_ -,,<--<L Ii=:
~
t' .f
t
[.
,<;;
L
1::
.i,C
c
>
F -< L
f
~ ~
-I ~
-=< (;:
..?£
-<
~:t ~~. ~Yo :~ <e.~ ~• ~f ~f r It- 1.~ . : ~~ t."= t."= it ~.~ 1.?~- ~t ;F~,{~ "'~,,-: F
-< ---
l
il:
fu·~ - ~;
~. \.- f ~ Efu "= ~ t· ~. .~. t·I'!:.'
i
r
0'
t'
t
[. t'
'f.
t'
r f
r:,
tt:
~
- ,~, t'
--.
IS'"
'~ ~- t' ~
L
- t
§~fr
0' t
r ;j L c,t' r:~ ...,t: _ 'l-!-t' r ~,
[,
~_ r. [ rf f
---- r;,..
/:' ,t'
, ~,~, -',.r;; ,t' - t, [,- i
L '-'
,t' ,t ,f. f .t' .r;;
~ ... ,(;, c !:= t' t ... y. ... - ~ c ~
,--'
~
r- >., [- [
' - c 1I
0'
'f> _
[Link]'t~ ~C> 'tIi" ~~'1'['~ ~ r t ~, ~'t ,~..~ i ~ ~ r- ~
[,c 'v> ' .. L
v·
~ 1:=: 'r. ,I;. .1:." -[ L. n '1:: !:=
-'<;; c
;-.' '&- ~ - - /: ~ -e. I" \r. - ~,c. ~ ~,c
,I;.
- '1 ,. - 'e: t - 'I). !E:. .. t"<;; t.. ~ l ~ "'-: ~ [, . r;,.. ~ g 't: &' .)., ("' -:- '~I
~'t f' -'!f. t;' t;' t .~: '[ \,; r, ( .- 1:,'\ 't' f t' ~. ,t'
.1-' R
t~. 'J;'~ t: ,r.L.
f f' t;' f' 't" G; f'~' (
't.
f' 1,. \.. Q. !f:,- f'. ,:,~ 't.f 't ~t;' I,.t; t'f
f> -- 1. ,I (..
f. 't' f
''t' 'f,. 't' f _ 't ~' ~ 't.
\,. r·' ~ f 't ~ I,. 't'
't
.
t~:~ 1
~ 'f' ~t'
[ 't' 't 't'
t;' ~'
't' f I,·
f.
~'
1,.f
'ct.. t' !; ~
t' I,., I
[, tEo, _
~ - -t-'f:L
'~~. ['
- I=..~
Tyco Safety Products Ltd. Reda Fire & Hazard Control Division
Burlington House, Hewett Road 2nd Industrial Area
Gapton Hall Industrial Estate Dammam 31482
Great Yarmouth, Norfolk NR31 0NN Saudi Arabia
United Kingdom
Said Approval is subject to satisfactory field performance, continuing follow-up Facilities and Procedures Audits, and strict
conformity to the constructions as shown in the Approval Guide, an online resource of FM Approvals.
For more than 160 years FM Approvals has partnered with business and industry
to reduce property losses.
March 8, 2011
1 Stanton St
Marinette, WI 54143
®
Have been investigated by Underwriters Laboratories Inc. (UL) or any authorized
licensee of UL in accordance with the Standard(s) indicated on this Certificate.
Standard(s) for Safety: UL 2166, "Halocarbon Clean Agent Extinguishing System Units,"
NFPA 2001, "National Fire Protection Association Standard on Clean Agent Fire
Extinguishing Systems"
Additional Information: See UL On-Line Certification Directory at [Link] for additional information.
Only those products bearing the UL Listing Mark should be considered as being covered by UL's Listing and Follow-
Up Service.
The UL Listing Mark generally includes the following elements: the symbol UL in a circle: with the word “LISTED”; a
control number (may be alphanumeric) assigned by UL; and the product category name (product identifier) as indicated in the
appropriate UL Directory.
William R. Carney
Director, North American Certification Programs
Underwriters Laboratories Inc.
Any information and documentation involving UL Mark services are provided on behalf of Underwriters Laboratories Inc. (UL) or any authorized licensee of UL
For questions, please contact a local UL Customer Service Representative at [Link]
Certificate Number 20110804-EX4510 Page 2 of 2
Report Reference 2011 August 4
Issue Date 2011 August 4
This is to verify that representative samples of the product as specified on this certificate were tested
according to the current UL requirements.
Hygood Models 16926, 9180, 9190, 9200, 14692, 9210, 14693, 14694, 9220, 9230, 9240 and 14798,
containing FM-200 (HFC-227ea) clean agent.
Fireater Models 16946, 9180, 9190, 9200, 14692, 9210, 14693, 14694, 9220, 9230, 9240 and 14798,
containing FM-200 (HFC-227ea) clean agent.
Ansul Sapphire Models 570635, 570633, 570634, 570638, 570639, 570640, 570641, and 570586,
containing NovecTM 1230 Fire Protection Fluid (FK-5-1-12) clean agent.
William R. Carney
Director, North American Certification Programs
Underwriters Laboratories Inc.
Any information and documentation involving UL Mark services are provided on behalf of Underwriters Laboratories Inc. (UL) or any authorized licensee of UL
For questions, please contact a local UL Customer Service Representative at [Link]