REDA

FIRE & HAZARD CONTROL


TRADING & DEVELOPMENT CO.
FOR MACHINERY AND EQUIPMENT LTD.

COMPANY PROFILE
Fire Fighting & Safety Equipment and Systems

REDA
Trading & Development Co. Ltd.

Specialists In Fire Protection And


Safety Equipment & Systems In
The Arabian Peninsula

P.O. Box 2923


Al-Khobar - 31952
Tel: 03-857-0079 / 814-2591 / 814-2602 Fax: 03-8142463
Email:[Link]@[Link] Website: [Link]
Fire Fighting & Safety Equipment and Systems

…………………………….List of Contents
PROFILE IN BRIEF 3

COMPANY AIM 3

POTENTIAL OF COMPANY 4

MISSION 4

COMPANY ORGANIZATION& STAFF PROFILE 4

QUALITY 5

SAFETY 5

ENVIRONMENTAL 5

INTERNAL RELATIONSHIP 5

EXPERIENCE AND UNDERSTANDING 6

OTHER DIVISIONS OF REDA 6

SERVICES 6

AREAS OF SPECIALIZATION 7

ACTIVITIES 7/8

CAPABILITIES 9

PRODUCTS 9/10/11

PARTNERS 12 / 13

OFFICE LOCATIONS 14

Page 2 of 14
Fire Fighting & Safety Equipment and Systems

PROFILE IN BRIEF

RREEDDAA Fire Protection division is one of the leading fire-protection, design, supply,
construction and servicing companies. Its technicians assess fire risks, evaluate
owner's needs, conduct fire-hazard analyses and develop conceptual solutions. RREEDDAA
specializes in system design, supplying complete detection and suppression systems
and provides top-quality installation, service, training and other services.

For more than 15 years, RREEDDAA has protected against every type of hazard due to fire.
The company provides an unparalleled, complete range of capabilities and total
service that its customers will not find elsewhere.

With the ability to evaluate a broad range of solutions for any fire-protection
problem -- large or small -- RREEDDAA brings together the scientific and technological
expertise of leading manufacturers with its contracting, installation and service
experience.

RREEDDAA proudly incorporates the most advanced technologies available for any type of
work. Regardless of the challenge, RREEDDAA has the people, the products, the financial
resources and the expertise to handle the project from star t to finish -- complete
turnkey construction of fire protection systems.

COMPANY AIM

Our mandate is to protect you and your property from fire. RREEDDAA is dedicated to
finding the suitable solution for any fire protection problem. We offer total fire
protection capabilities with quality products and trained, experienced technicians.
RREEDDAA is aligned with the leading manufacturers who select only very qualified
representation. We have a working knowledge of worldwide fire protection rules and
regulations to ensure complete safety and compliance anywhere. On time, reliable,
accurate, and on budget.
RREEDDAA - FIRST For Fire Protection.

As you can see our experience covers the complete range of Fire Protection, from
fire sprinklers and special hazards protection to alarms and detection we can handle
YOUR fire challenge. Understanding our customer’s needs, concerns and business is
our number one priority.
RREEDDAA - your first call for Fire Protection!

Page 3 of 14
Fire Fighting & Safety Equipment and Systems

POTENTIAL OF COMPANY
Our Services are genuinely innovative, comprehensive and represent an excellent
value. We consider our customers as our partners ensuring their objective are met as
efficiently and economically as possible.

REDA, believes in a team approach for creating a safer facility. We work closely with
our clients to formulate and implement high-quality, comprehensive programs that
exceed their expectations.

MISSION
The key to the success of any Fire & Safety equipment or system is its suitability for
the site and workforce it protects.
Fires and toxic spillage especially threaten the oil and petrochemical industries. Many
other industries such as plastics, paints or paper are facing similar hazards. Offices,
shops, hospitals and hotels are all at risk in different ways.

At REDA we not only supply the entire Saudi Arabian market with fire fighting and
safety equipment produced by many of the US and Europe’s leading manufacturers,
we also provide technical advisory services and comprehensive testing, servicing and
maintenance program which ensure the safety of working people in oil fields,
petrochemical plants, electrical companies, desalination plants, industrial
installations, airports, militaries, civil defense, hospitals, schools, university, offices,
building and other location throughout the region.
REDA Fire & Safety operates from 4 offices and logistics centres and serves the
countries of Saudi Arabia and Kuwait.

COMPANY ORGANIZATION & STAFF PROFILE

All senior members of staff have significant experience with the Oil, Gas, Water,
Chemical, Iron & Steel Industries and Civil Engineering Industries commensurate with
the high standard of services required and provided for activities in the KSA. In
addition a register is maintained of qualified personnel who may be used to
supplement staffing levels on large contracts or specialized projects.

It is the policy of the organization to invest in its staff both at degree and vocational
levels with appropriate training and development programs for the long-term benefit
of the company and the services provided.

This is endorsed by the recognition and certification under the Investors in People
initiative.

Page 4 of 14
Fire Fighting & Safety Equipment and Systems

QUALITY

The company operates a quality policy in accordance with the provisions of


internationally recognized requirements.

SAFETY

The company operates a safety policy in compliance with internally set objectives of
recognized standard. Safety consultants are retained to advise on all safety matters
related to company activities.

Safety awareness is highlighted for all projects and risk assessment is prepared to
recognized standards to control hazards.

The safety policies followed are aimed at working together with clients to achieve
the objective of zero safety related incidents.

ENVIRONMENTAL

Environmental policies are operated to ensure safeguards in respect of the


environment and society in connection with all of its activities. The company
additionally complies with all client requirements regarding environmental policies,
which are in force at its sites or operating locations. The company policy is aimed
reducing environmental impact to a minimum and ensuring that all related activities
are carried out in accordance with recognized approved procedures.

INTERNAL RELATIONSHIP

It is our firm conviction that our employees are our “Best Assets” and we wish to be
recognized as a “Great Place to Work” our personal shall be guided by this desire and
our approach to our employees shall be governed by the principles of “Mutual
Respect” and “Trust”.

We recognize the need to nurture team spirit. For this purpose we shall provide an
environment of friendliness and mutual support within the organization at the same
time encourage individual initiative and creative skills.

Page 5 of 14
Fire Fighting & Safety Equipment and Systems

EXPERIENCE AND UNDERSTANDING

As Saudi Arabia’s leading fire and safety experts, we put a high priority on a
complete understanding of our suppliers’ products and our customers’ real needs.
We have experience and understanding of the fire risk and hazardous accidents
facing oil and petrochemical companies. Our services, which include recommending,
supplying, servicing and maintaining safety equipment, will help protect our clients’
costly installations, and ultimately will save lives.

OTHER DIVISIONS OF REDA


In addition to our well established fire fighting and safety equipment business
division, REDA Group is also involved in the marketing and distribution of a range of
industrial and specialty chemicals, as well as specialized process equipment. (For
more details, see [Link], [Link] )

SERVICES

Working closely with reliable and highly technical suppliers gives us the benefit of
the knowledge and experience gained over many years. Our engineers assess and
evaluate each of our customer’s fire protection & safety needs, advice them on the
correct systems required for their individual sites, supervise materials installation
and subsequently offer a planned program of continuous service & maintenance
specifically created for each individual customers according to the manufacturer’s
recommendation and the international standards.
REDA operates three service centers in Saudi Arabia: Al Khobar, Jubail and Yanbu.

SERVICES PERFORMED

Maintenance of Rescue Systems


Maintenance of self-contained breathing apparatus (SCBA).
Trained and Certified technician by SCOTT (Tyco Group)
Maintenance of Fire Extinguishers
Hydraulic testing and refilling of ANSUL fire extinguishers.

Page 6 of 14
Fire Fighting & Safety Equipment and Systems

AREAS OF SPECIALIZATION
• Industrial Safety Supplies

• Safety Engineering Services

• Fire Lose Prevention Engineering

• Fire Protection and Detection Systems


Construction

• Fire Fighting Equipment Supply

• Maintenance and Inspection Services for Fire


Protection Systems

• Occupational Health and Safety Services

• Fire Truck Inspection & Maintenance

A
ACCT
T II V
V II T
T II E
E SS

1- Consultancy and Engineering Services:

• Design verification and as-built drawings in accordance to the international


codes and standards.
• Review of plans, P&ID drawings.
• Risk analysis and Process Safety Management.
• Issuance and review of the specification and scope of works in accordance
to the international codes and standards (ASME, OSHA, NFPA, DIN, EN, BS).
• Projects supervision and management.
• Damage analysis and loss adjustment.

2- Safety Engineering Services:

• Consultancy
• Risk Analysis and Risk Control
• Loss Prevention Planning
• Site Inspection

3- Industrial Safety Supplies:


• Safety Equipment
• Safety Uniforms and Accessories
• Means of egress
Page 7 of 14
Fire Fighting & Safety Equipment and Systems

4-Fire Lose Prevention Engineering:


• Design,
• Hazard and Risk Analysis,
• Fire Control,
• Construction,
• Testing and Commissioning

5-New Electromechanical Projects Management:


• Supervision,
• Construction Design Review,
• Project Cost Control
• Inspection and Field Survey
• Quality Control
• Testing and Commissioning

6-Maintenance and Inspection Services For Fire Protection


Systems and Fire Fighting Equipment:
• Periodic Inspection
• Preventive Maintenance

7-Occupational Health and Safety Services:

• Health and Safety Workplace Inspections


• Process Design
• Engineering Controls
• Electrical Classification of Equipment/Machinery in Hazardous locations
• Ventilation
• Indoor Air Quality Assessment
• Noise Testing
• Industrial Hygiene Programs

8-Environmental Engineering and Consultancy:

- Pollution Control Equipment


- Process Design/Modifications
- Assessment of effluent from Industrial operations
- Treatment facilities; Design and Installation

9-Fire Truck Inspection & Maintenance:

• Periodic Inspection
• Preventive Maintenance

Page 8 of 14
Fire Fighting & Safety Equipment and Systems

C
CAA PP A
ABB II L
L II T
T II E
E SS

REDA, cooperate with international companies. These companies offer everything


from Design, Supply, Installation, Commissioning and Testing.
Our company is also able to provide services to specialized industries, such as
petrochemical, and can provide its customers with the means to get the project
completed.
The company team is committed to delivering its customer's projects on time, safely,
within budget and with the highest degree of quality.

PP R
ROOD
DUUC
CTT SS

In line with the comprehensive scope of our advisory services, materials supply,
repair & maintenance services, REDA carries a large inventory of specialized fire
protection and safety items.
We keep for ready-supply various types of Self Contained Breathing Apparatus (SCBA)
with all accessories.
All type and sizes of fire extinguishers, portable, mobile and fixed fire monitors,
wide range of effective fire nozzles, a range of fire & safety valves, various
diameters of industrial and municipal fire hoses.
All types of fire-fighting fire entry suits and fire retardant station uniforms including
fire helmets, fire gloves and fire boots.
A large selection of chemical suits against all type of chemicals at various
concentrations.
Safety equipment such stretchers, burn kits, flashlights, various types of safety
shower personal protection, gas masks and accessories.
Fire alarm and extinguishing systems and a range of specialized equipment to be
installed and used on fire trucks.

REDA has an established firefighting and safety equipment business which is also
involved in marketing and distribution of a wide range materials, services and
equipments for many industrial activities.

Page 9 of 14
Fire Fighting & Safety Equipment and Systems

Personal protective equipment


and energy-absorbing products:
Hearing Protection
Face Protection
Head Protection
Respiratory Protection
Prescription & Non-prescriptive Safety Eyewear
Isotherm Cool Vest
Protective Clothing
Footwear & Boots
Gloves

Fire Fighting

Flow Control group

Pipe & Pipe Fittings, Tubing, & Flow Meters


Woven Fabric, Rubber Covered Hose
Hose Hardware and Accessories
Nozzles & Accessories

Fire Extinguishers
Cartridge-Operated
Cartridge-Operated
Portable Fire Extinguishers
Stored Pressure Portable Fire Extinguishers
Firefighting Agents
Foam Fire Extinguishing
Carbon Dioxide Fire Extinguishing
Alternative Fire Extinguishing Systems
Dry Chemical/Powder Fire Extinguishing

Page 10 of 14
Fire Fighting & Safety Equipment and Systems

Fire Protection Specialties & Equipments


Control, Detection and Alarm Equipments
Ventilation Equipment
Thermal Imaging/Camera
Supplied Air Respirators and Air Quality Equipment
SCBA, self-contained breathing apparatus
Free Air Pumps & Compressors
Carbon Monoxide Monitors
Breathing Air Filtration Systems (Purifying)
Breathing Air Conditioners (Cooling)

Emergency Response and Accident


Managing Products and Equipments
Hazardous Spill Control Products
Emergency Escape Breathing Device (EEBD)
First Aid Products
Emergency/Fire Blanket
Tempered water blending system specially designed for
eyewash units
Drench Shower, Eye/face and body spray
Rescue Products
Stretchers & Stretcher Kits & Accessories
Evacuation Chair
Backboards
Inflatable Splints
Head and Neck Immobilizer (Extrication Collar)

Page 11 of 14
Fire Fighting & Safety Equipment and Systems

Partners
REDA ‘‘ss partners include the following:

ANSUL, a subsidiary of the American


Tyco group - world leader in security
and fire-protection systems - who
supply fire extinguishers and fire
fighting foam and engineered systems.

SCOTT health & safety, who produce


the highest quality of self contain
breathing apparatus, full range of
respiratory equipment portable and
fixed gas detection for whom we
operate the only approved service
centers in Saudi Arabia.

Williams Fire & Hazard Control, Inc®


is an industrial firefighting response
company with three generations of
flammable liquid firefighting
assessment and extinguishment
expertise.

AKRON Brass, the makers of a wide


range of fire fighting nozzles, portable
& fixed monitors, fire valves and fire
truck fittings.

FLEXLINE Corporation, offers a


complete line of woven fabric and
rubber covered fire hose products,
along with a full complement of hose
hardware and accessories.

Encon Safety, whose equipment


includes eyewear safety eyewash &
shower units storage cabinets for all
industrial activities.

Page 12 of 14
Fire Fighting & Safety Equipment and Systems

Globe, one of America's leading


manufacturers of fire fighting suits
providing high personal protection
complying with the latest NFPA
requirements.

Red Head Brass, makers of all type of


coupling adapters and pyrolite / brass
connections.

Haws, who produce drinking water


fountain and safety shower units.

SERVUS, Leading manufacturer of


Firefighter Footwear.

CairnsHELMETS, a manufacturer of fire


helmets. MSA, a manufacturer of
protective products for safety and
health purposes.

JUNKIN, manufacture of first aid and


rescue tools, equipments and
accessories.

Crews Inc., producers and suppliers of


quality industrial strength eye
protection, welding goggles, and face
shields.

Pyro-Chem; Maufacturer of Fire


Extinguishing systems including FM 200;
kitchen hood; dry/wet chemical etc

Page 13 of 14
Fire Fighting & Safety Equipment and Systems

O
O FF FF II C
CEE L
LOOC
CAAT
T II O
ONN SS
AL KHOBAR, SAUDI ARABIA YANBU, SAUDI ARABIA
TRADING & DEVELOPMENT P.O. Box 2077
Co. For MACHINERY & Jeddah 21451
EQUIPMENT (REDA) Ltd. Kingdom of Saudi Arabia
Khobar-Dammam Tel : (966 4) 391 3702
Expressway Fax : (966 4) 391 3702
P.O. Box 2923 Contacts:
Al Khobar 31952 sales@[Link]
Kingdom of Saudi Arabia
Tel : (966 3) 857 0079
Fax : (966 3) 857 0087
Contacts:
sales@[Link]

RIYADH, SAUDI ARABIA KUWAIT CITY, KUWAIT


Al Meezan Building, 6th REDA CHEMICALS COMPANY Ltd.
Floor, Olaya St. Al Awkaf Complex, Sharg Area
P.O. Box 58866 P.O. Box 22013, SAFAT 13081 - Kuwait
Riyadh 11515 City, KUWAIT
Kingdom of Saudi Arabia Tel : (965) 242 3604
Tel : (966 1) 279 2265 Fax: (965) 242 3621
Fax : (966 1) 463 0125 Contacts:
Contacts: sales@[Link]
sales@[Link]

JEDDAH, SAUDI ARABIA Headquarters : PARIS, FRANCE


Ring Road - Expressway, REDA INDUSTRIAL MATERIALS
Breman INTERNATIONAL S.A.R.L.
P.O. Box 2077 28, Avenue HOCHE
Jeddah 21451 Paris 75008
Kingdom of Saudi Arabia France
Tel : (966 2) 661 0605 Tel : (33 1) 456 12 670
Fax : (966 2) 660 5906 Fax : (33 1) 456 12 665
Contacts: Contacts :
sales@[Link] sales@[Link]

Page 14 of 14
TRADING & DEVELOPMENT CO. FOR MACHINERY & EQUIPMENT LTD.
FIRE & SAFETY DIVISION
Al Khobar : Tel (9663) 857-0079 - Fax (9663) 857-0087
Email: sales@[Link]
Al Khobar-Dammam Road, P.O. Box 2923, 31952 Al Khobar, Saudi Arabia

MAJOR REDA
PROJECTS
REFERENCE
LIST
TRADING & DEVELOPMENT CO. FOR MACHINERY & EQUIPMENT LTD.
FIRE & SAFETY DIVISION
Al Khobar : Tel (9663) 857-0079 - Fax (9663) 857-0087
Email: sales@[Link]
Al Khobar-Dammam Road, P.O. Box 2923, 31952 Al Khobar, Saudi Arabia

MAJOR PROJECTS EXECUTED BY REDA FIRE & SAFETY DIVISION FOR


INTERNATIONAL EPC CONTRACTORS, SAUDI ARAMCO & SABIC
SERIAL CUSTOMER PROJECT SYSTEM
NO.
1. SKEC Jubail Export Refinery Pkg 5B Supply of Fire Fighting Equipment & Valves
2. TECHNICAS Jubail Export Refinery Pkg 1 Supply of Fire Fighting Equipment

3. BECHTEL/TECHNIP Aramco - Khursaniyah Gas Plant Supply of Fire Fighting Equipment


4. SUMITOMO/ICC Aramco – Khursaniyah Communication Design, Supply, Supervision, Testing And
Center Commissioning of NOVEC1230 Fire Suppression
System.
5. SNAMPROGETTI Aramco - Khurais Water Injection Supply of Fire Fighting Equipment
Project
6. SNAMPROGETTI Aramco - Qurrayah S.T.P Supply of Fire Fighting Equipment
7. SNC-Lavalin Aracmo – Shaybah Central Processing Supply of Valves & Indicator Post
Facility
8. HYUNDAI Khurais Central Processing Facilities Supply of Fire Fighting Equipment Package
9. SNAMPROGETTI Khurais Crude Contract Supply of Fire Fighting Equipment Package
10. HITACHI PetroRabigh Design, Supply, Installation, Testing & Commissioning
of VESDA System

Page 1 of 4
TRADING & DEVELOPMENT CO. FOR MACHINERY & EQUIPMENT LTD.
FIRE & SAFETY DIVISION
Al Khobar : Tel (9663) 857-0079 - Fax (9663) 857-0087
Email: sales@[Link]
Al Khobar-Dammam Road, P.O. Box 2923, 31952 Al Khobar, Saudi Arabia

SERIAL CUSTOMER PROJECT SYSTEM


NO.
11. SNC-Lavalin – Saipem Aramco – Water Injection Pumping Supply of Fire Fighting Equipment
Station Facility
12. SNC Lavalin Aramco – Shaybah Central Processing Supply of Fire Fighting Equipment
Facility
13. Saudi Aramco Dammam Computer Center and Tower Design, Supply, Installation, Testing & Commissioning
Computer Center of Fire Alarm System
14. Saudi Aramco Building-840, Switchgear Room and Design, Supply, Installation, Testing & Commissioning
UPS Room of NOVEC1230 Fire Suppression and Alarm System
15. Saudi Aramco Building-345, Riyadh, Communication Supply, Installation, Testing & Commissioning of Fire
Room, Battery Room and UPS Room Alarm System
16. Saudi Aramco Building-345, Riyadh, Communication Design, Supply, Installation, Testing & Commissioning
Room, Battery Room and UPS Room of NOVEC1230 Fire Suppression and Alarm System
17. Petrofac Karan Gas Facilities, Saudi Aramco Supply of Fire Fighting Equipment
18. Hyundai Engineering Karan Gas Facilities, Saudi Aramco Supply of Fire Fighting Equipment
19. GS Engg & Const Manifa Central Facilities Supply of Fire Fighting Equipment
20. JGC Japan Manifa Central Facilities Supply of Fire Fighting Equipment
21. Technicas Reunidas Manifa Central Facilities Supply of Fire Fighting Equipment
22. Snamprogetti/Saipem Manifa Central Facilities Supply of Fire Fighting Equipment
23. SUMITOMO/H. Kabani Security Bldg and Exchange Building Design, Supply, Installation, Testing & Commissioning
of NOVEC1230 Fire Suppression System
Page 2 of 4
TRADING & DEVELOPMENT CO. FOR MACHINERY & EQUIPMENT LTD.
FIRE & SAFETY DIVISION
Al Khobar : Tel (9663) 857-0079 - Fax (9663) 857-0087
Email: sales@[Link]
Al Khobar-Dammam Road, P.O. Box 2923, 31952 Al Khobar, Saudi Arabia

SERIAL CUSTOMER PROJECT SYSTEM


NO.
24. SUMITOMO/H. Kabani Security Bldg and Exchange Building Design, Supply, Testing & Commissioning of Fire
Alarm System
25. LINDE Sabic United - JUPC Ethylene Plant Wet Sprinkler system, High Pressure CO2 System,
Breathing Air System, Fire Hoses and Fire
extinguishers
26. SABIC-HADEED Hadeed-II Expansion (DR Module I, Hot High Pressure CO2 System, FM 200 and Fire
Strip Mill, Slab Castor Area) Extinguishers
27. SNC-LAVALIN GULF FARABI PETROCHEMICAL CO. Water Spray Deluge Systems, Fire Fighting
Equipments, Fire Extinguishers
28. JGC CORPORATION Jubail Chevron Philips Fire Fighting Equipments, Foam Systems
29. SABIC R&T SABIC Warehouses Automatic Sprinkler system, water storage tank as per
At Riyadh, Dammam & Jeddah API 650
30. SABIC SHARED Emergency Response Equipment Mobile Fire Fighting System with 2Nos 6000 GPM
SERVICES each Diesel Pumps and Foam System
31. VOEIST-ALPINE HADEED II Expansion HP CO2 / LP CO2 Extinguishing System, Fire Fighting
Equipment & FM 200
32. POSCO E&C SABIC – HADEED CCL Automatic Sprinkler/ Spray System, Preaction System,
HP CO2, FM200 And Fire Fighting Equipment

33. Saline Water Conversion Pumping Station Generator room High Pressure CO2 Systems

Page 3 of 4
Aramco Overseas Company King Abdullah Sports City
MEP Specification

SECTION 21 22 00 - NOVEC 1230 CLEAN AGENT SYSTEM

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.

1.2 SUMMARY

A. Section Includes:

1. Pipes, fittings, and specialties.


2. Fire-protection valves.
3. Alarm devices.
4. Manual control stations.
5. Control panels.
6. Pressure gages.

B. Related Sections:

1. Section 283111 "Digital, Addressable Fire-Alarm System" for alarm devices not
specified in this Section.

1.3 APPLICABLE CODES AND STANDARDS

A. The specifications and standards listed below form a part of this section of the
specifications. The system shall fully comply with the latest issue, with all updates, of these
standards as applicable.

1. NFPA No. 2001 - Clean Agent Fire Extinguishing Systems


2. NFPA No. 70 - National Electrical Code
3. NFPA No. 72 - Standard For Protective Signaling
4. Factory Mutual Approval Guide
5. U.L. Listings

1.4 REQUIREMENTS

A. The NOVEC 1230 Suppression System installation shall be made in accordance with the
drawings, specifications and applicable standards.

1.5 EXCLUSIONS

A. The work listed below shall be provided by others, or under other sections of this
specification

1. 230 VAC or 208/230 VAC power supply to the control panel


2. Interlock wiring and conduit for shutdown of HVAC, dampers and/or electric power
supplies relays or shunt trip breakers.

WER5, KA101-OVE-05_ZZZ-XTC-Z0-00001 | Rev 2.0 | August 2011 Page 38


Aramco Overseas Company King Abdullah Sports City
MEP Specification

3. Connection to local/remote fire alarm systems, listed central alarm station(s) or


sprinkler preaction/deluge valve actuation.

1.6 QUALITY ASSURANCE

A. Manufacturer

1. The manufacturer of the Suppression System hardware and detection components


shall have a minimum of 10 years experience in the design and manufacture of
similar types of suppression systems and can refer to similar installations providing
satisfactory service.
2. The name of the manufacturer, part numbers and serial numbers shall appear on all
major components.
3. All devices, components and equipment shall be the products of the same
manufacturer.
4. All devices, components and equipment shall be new, standard products of the
manufacturer’s latest design and suitable to perform the functions intended.
5. All devices and equipment shall be U.L listed and/or FM approved.
6. Locks for all cabinets shall be keyed alike.

B. Installer
1. The installing contractor shall be trained by the supplier to design, install, test and
maintain Suppression Systems
2. When possible, the installing contractor shall employ a NICET certified special
hazard designer, level 2 or above, who will be responsible for this project.
3. The installing contractor shall be an experienced firm regularly engaged in the
installation of automatic Clean Agent, or similar, fire suppression systems in strict
accordance with all applicable standards.
4. The installing contractor must have a minimum of five (5) years experience in the
design, installation and testing of Clean Agent, or similar, fire suppression systems. A
list of systems of a similar nature and scope shall be provided on request.

1.7 SUBMITTALS

A. The installing contractor shall submit the following design information and drawings for
approval prior to starting work on this project.
1. Field installation layout drawings having a scale of not less than 1/8” = 1’-0” or
1:1000m detailing the location of all agent storage tanks, pipe runs including pipe
sizes and lengths, control panel(s), detectors, manual pull stations, abort stations,
audible and visual alarms, etc.
2. Auxiliary details and information such as maintenance panels, door holders, special
sealing requirements and equipment shutdowns
3. Separate layouts, or drawings, shall be provided for each level, ( i.e.; room,
underfloor, and above ceiling) and for mechanical and electrical work.
4. A separate layout or drawing shall show isometric details of agent storage containers,
mounting details and proposed pipe runs and sizes.
5. Electrical layout drawings shall show the location of all devices and include point-to-
point conduit runs and a description of the method(s) used for detector mounting
6. Provide an internal control panel wiring diagram which shall include power supply
requirements and field wiring termination points.
7. Complete hydraulic flow calculations, from a U.L. listed computer program, shall be
provided for all engineered Clean Agent systems. Calculation sheet(s) must include
the manufacturers name and U.L. listing number for verification. The individual

WER5, KA101-OVE-05_ZZZ-XTC-Z0-00001 | Rev 2.0 | August 2011 Page 39


Aramco Overseas Company King Abdullah Sports City
MEP Specification

sections of pipe and each fitting to be used, as shown on the isometrics, must be
identified and included in the calculation. Total agent discharge time must be shown
and detailed by zone.
8. Provide calculations for the battery stand-by power supply taking into consideration
the power requirements of all alarms, initiating devices and auxiliary components
under full load conditions.
9. A complete sequence of operation shall be submitted detailing all alarm devices,
shutdown functions, remote signaling, damper operation, time delay and agent
discharge for each zone or system

B. Submit drawings, calculations and system component data sheets for approval to the local
Fire Prevention Agency, Company Representatives Insurance Underwriter and all other
Authorities Having Jurisdiction before starting installation. Submit approved plans to the
Architect/Engineer for record.

1.8 SYSTEM DESCRIPTION AND OPERATION

A. The system shall be a NOVEC 1230 Suppression System.


B. The system shall provide a minimum design concentration of 5.3 %, by volume, in all areas
and/or protected spaces, at the minimum anticipated temperature within the protected area.
C. The system shall be complete in all ways. It shall include all mechanical and electrical
installation, all detection and control equipment, agent storage containers, HFC-227ea agent,
discharge nozzles, pipe and fittings, manual release and abort stations, audible and visual
alarm devices, auxiliary devices and controls, shutdowns, alarm interface, caution/ advisory
signs, functional checkout and testing, training and all other operations necessary for a
functional, U.L. Listed and/or F.M. approved NOVEC Clean Agent Suppression System.
D. The general contractor shall be responsible for sealing and securing the protected spaces
against agent loss and/or leakage during the 10 minute "hold" period.
E. The system(s) shall be actuated by a combination of ionization and/or photoelectric
detectors installed at a maximum spacing of 23.2 sq. m. per detector, in both the room,
underfloor and above ceiling protected spaces. If the air flow is one air change per minute,
photoelectric detectors only shall be installed at a spacing not to exceed 11.6 sq. m per
detector.
F. Detectors shall be standard Cross-Zoned detection, or single detector release, using either a
Class "A" or Class "B" wiring arrangement. No other detection / wiring arrangements will
be acceptable
G. Automatic operation of each protected area shall be as follows:
1. Actuation of one (1) detector, within the system, shall:
a. Illuminate the "ALARM" lamp on the control panel face
b. Energize an alarm bell and/or an optional visual indicator
c. Transfer sets of 5 Amp rated auxiliary contacts which can perform auxiliary
system functions such as:
1) Operate door holder/closures on access doors
2) Transmit a signal to a fire alarm system
3) Shutdown HVAC equipment
d. Light an individual lamp on an optional graphic annunciator
2. Actuation of a 2nd detector, within the system, shall:
a. Illuminate the "PRE-DISCHARGE" lamp on the control panel face
b. Energize a predischarge horn or horn/strobe device
c. Shut down the HVAC system and/or close dampers
d. Start time-delay sequence (not to exceed 60 seconds)
e. System abort sequence is enabled at this time
f. Light an individual lamp on an optional graphic annunciator

WER5, KA101-OVE-05_ZZZ-XTC-Z0-00001 | Rev 2.0 | August 2011 Page 40


Aramco Overseas Company King Abdullah Sports City
MEP Specification

3. After completion of the time-delay sequence, the NOVEC Clean Agent system shall
discharge and the following shall occur:
a. Illuminate a "SYSTEM FIRED" lamp on the control panel face
b. Shutdown of all power to high-voltage equipment
c. Energize a visual indicator(s) outside the hazard in which the discharge
occurred
d. Energize a "System Fired" audible device
4. The system shall be capable of being actuated by manual discharge devices located at
each hazard exit. Operation of a manual device shall duplicate the sequence
description above except that the time-delay and abort functions shall be bypassed.
The manual discharge station shall be of the electrical actuation type and shall be
supervised at the main control panel.

1.9 MATERIALS AND EQUIPMENT

A. The NOVEC 1230 Clean Agent System materials and equipment shall be standard products
of the supplier's latest design and suitable to perform the functions intended. When one or
more pieces of equipment must perform the same function(s), they shall be duplicates
produced by one manufacturer.
1. All devices and equipment shall be U.L. Listed and/or FM approved

B. Each system shall have its own supply of clean agent.


1. The system design can be modular, central storage, or a combination of both design
criteria.
2. Systems shall be designed in accordance with the manufacturer's guidelines.
3. Each supply shall be located within the hazard area, or as near as possible, to reduce
the amount of pipe and fittings required to install the system.
4. Containers shall be of high-strength alloy steel construction and conform to NFPA
2001.
5. Containers shall be actuated by parallel wired initiators.
6. Each container shall have a pressure gauge and low pressure switch to provide visual
and electrical supervision of the container pressure. The low pressure switch shall be
wired to the control panel to provide an audible and visual "Trouble" alarm in the
event the container pressure drops below 1986 kPa. The pressure gauge shall be color
coded to provide an easy, visual indication of container pressure.
7. Each container shall have a pressure relief provision that automatically operates when
the internal temperature exceeds 66°C.
8. Engineered discharge nozzles shall be provided, within the manufacturers guidelines,
to distribute the NOVEC 1230 agent throughout the protected spaces.
9. Distribution piping, and fittings, shall be installed in accordance with the
manufacturer's requirements, NFPA 2001 and approved piping standards and
guidelines. All distribution piping shall be installed by qualified individuals using
good, accepted practices and quality procedures. All piping shall be adequately
supported and anchored at all directional changes and nozzle locations.
a. All piping shall be reamed, blown clear and swabbed with suitable solvents to
remove burrs, mill varnish and cutting oils before assembly.
b. All pipe threads shall be sealed with Teflon tape pipe sealant applied to the
male thread only.

C. CONTROL PANEL
1. Three (3) Class “B” Style Y notification appliance circuits rated for 2.0 amps @ 24
VDC
2. Up to two (2) Style B initiating device circuits capable of sequential alarm, cross-
zone, or single detector release operation.

WER5, KA101-OVE-05_ZZZ-XTC-Z0-00001 | Rev 2.0 | August 2011 Page 41


TRADING & DEVELOPMENT CO. FOR MACHINERY & EQUIPMENT LTD.
FIRE & SAFETY DIVISION
Al Khobar : Tel (9663) 857-0079 - Fax (9663) 857-0087
Email: sales@[Link]
Al Khobar-Dammam Road, P.O. Box 2923, 31952 Al Khobar, Saudi Arabia

MAJOR PROJECTS EXECUTED BY REDA FIRE & SAFETY DIVISION FOR


INTERNATIONAL EPC CONTRACTORS
SERIAL CUSTOMER PROJECT DATE COMPLETION SYSTEM
NO. OF P.O DATE
1. BECHTEL/TECHNIP Aramco - Supply of Fire Fighting Equipment
Khursaniyah
Gas Plant 25.10.2006 21.10.2007
2. SUMITOMO/ICC Aramco – Design, Supply, Supervision, Testing And
Khursaniyah Commissioning of Fire Suppression System.
13.04.2006 30.06.2008
Communication
Center
3. SNAMPROGETTI Aramco - Supply of Fire Fighting Equipment
Khurais Water 10.06.2008 10.06.2010
Injection Project
4. SNAMPROGETTI Aramco - Supply of Fire Fighting Equipment
01.01.2007 01.05.2009
Qurrayah S.T.P
5. SNC-Lavalin Aracmo – Supply of Valves & Indicator Post
Shaybah Central
01.07.2007 02.12.2008
Processing
Facility
6. HYUNDAI Khurais Central 07.07.2008 01.11.2009 Supply of Fire Fighting Equipment Package

Page 1 of 9
TRADING & DEVELOPMENT CO. FOR MACHINERY & EQUIPMENT LTD.
FIRE & SAFETY DIVISION
Al Khobar : Tel (9663) 857-0079 - Fax (9663) 857-0087
Email: sales@[Link]
Al Khobar-Dammam Road, P.O. Box 2923, 31952 Al Khobar, Saudi Arabia

SERIAL CUSTOMER PROJECT DATE COMPLETION SYSTEM


NO. OF P.O DATE
Processing
Facilities
7. SNAMPROGETTI Khurais Crude Supply of Fire Fighting Equipment Package
06.08.2008 03.03.2009
Contract
8. SNC-Lavalin – Aramco – Water Supply of Fire Fighting Equipment
Saipem Injection
05.05.2009 12.11.2009
Pumping Station
Facility
9. LINDE Sabic United - Wet Sprinkler system, High Pressure CO2
JUPC Ethylene 06.12.2007 12.08.2008 System, Breathing Air System, Fire Hoses and
Plant Fire extinguishers
10. SABIC-HADEED Hadeed-II High Pressure CO2 System, FM 200 and Fire
Expansion (DR Extinguishers
Module I, Hot 28.08.2005 12.11.2008
Strip Mill, Slab
Castor Area)
11. SNC-LAVALIN GULF FARABI Water Spray Deluge Systems, Fire Fighting
PETROCHEMICA24.11.2005 24.08.2006 Equipments, Fire Extinguishers
CO.
12. JGC Jubail Chevron Fire Fighting Equipments, Foam Systems
12.02.2006 01.11.2008
CORPORATION Philips

Page 2 of 9
TRADING & DEVELOPMENT CO. FOR MACHINERY & EQUIPMENT LTD.
FIRE & SAFETY DIVISION
Al Khobar : Tel (9663) 857-0079 - Fax (9663) 857-0087
Email: sales@[Link]
Al Khobar-Dammam Road, P.O. Box 2923, 31952 Al Khobar, Saudi Arabia

SERIAL CUSTOMER PROJECT DATE COMPLETION SYSTEM


NO. OF P.O DATE
13. SABIC R&T SABIC Automatic Sprinkler system, water storage
Warehouses tank as per API 650
At Riyadh, 26.05.2007 01.12.2008
Dammam &
Jeddah
14. SABIC SHARED Emergency Mobile Fire Fighting System with 2Nos 6000
SERVICES Response 25.03.2005 01.05.2006 GPM each Diesel Pumps and Foam System
Equipment
15. VOEIST-ALPINE HADEED II HP CO2 / LP CO2 Extinguishing System, Fire
Expansion 28.08.2005 01.12.2008 Fighting Equipment & FM 200

16. POSCO E&C SABIC – Automatic Sprinkler/ Spray System, Preaction


HADEED CCL System, HP CO2, FM200 And Fire Fighting
26.09.2006 01.12.2009 Equipment

17. Saline Water Pumping Station High Pressure CO2 Systems


Conversion Generator room 02.03.2007 01.09.2007
Corporation (SWCC)
18. LINDE SABIC ASU FM 200 System and Fire Fighting Equipment
GAS V Project – 21.12.2005
Jubail 06.05.2005

Page 3 of 9
TRADING & DEVELOPMENT CO. FOR MACHINERY & EQUIPMENT LTD.
FIRE & SAFETY DIVISION
Al Khobar : Tel (9663) 857-0079 - Fax (9663) 857-0087
Email: sales@[Link]
Al Khobar-Dammam Road, P.O. Box 2923, 31952 Al Khobar, Saudi Arabia

SERIAL CUSTOMER PROJECT DATE COMPLETION SYSTEM


NO. OF P.O DATE

19. AIR PRODUCTS SABIC – GAS FM 200, Alarm System and Fire Fighting
Yanbu 22.06.2006 22.12.2007 Equipment

20. SABIC Al Bayroni FM 200, Alarm System and Fire Fighting


12.12.2006 05.11.2008
(Samad) Equipment
21. SAMSUNG Saudi Automatic Sprinkler System
ENGINEERING Polyolefins 12.05.2004 12.12.2004
company
22. SIEMENS Hadeed Vacuum CO2 Fire Extinguishing, Fire Hose and Fire
Degasser 19.03.2005 20.08.2006 Extinguishers

23. TECHNIP ITALY Olefins plant – Fire Fighting Equipment


25.10.2006 31.03.2007
Yanbu
24. SINOPEC/AKAR PP & LLDPE Design, Supply, Supervision, Testing And
KEVEARNER Yanbu 25.10.2006 31.03.2008 Commissioning Of Fire Sprinkler & Deluge
Systems
25. SINOPEC/AKAR PHU Yansab – Supply of fire fighting equipment
28.10.2006 31.03.2007
KEVEARNER Yanbu KSA
26. AKAR KEVEARNER PP & LLDPE 08.10.2006 31.03.2007 Engineering, Procurement, Supply, Supervision,

Page 4 of 9
TRADING & DEVELOPMENT CO. FOR MACHINERY & EQUIPMENT LTD.
FIRE & SAFETY DIVISION
Al Khobar : Tel (9663) 857-0079 - Fax (9663) 857-0087
Email: sales@[Link]
Al Khobar-Dammam Road, P.O. Box 2923, 31952 Al Khobar, Saudi Arabia

SERIAL CUSTOMER PROJECT DATE COMPLETION SYSTEM


NO. OF P.O DATE
Yansab – Yanbu Testing and commissioning of Fire Alarm System
KSA
27. AKAR KEVEARNER PP & LLDPE Engineering, Procurement, Supply, Supervision,
Yansab – Yanbu 08.10.2006 31.03.2008 Testing and commissioning of FM 200 system
KSA
28. SINOPEC Utility and Engineering, Procurement, Supply, Supervision,
INTERNATIONAL Offshore – 06.10.2009 31.03.2010 Installation Testing and commissioning of FM 200
Yansab system
29. Sabic Jubail direct SAFCO 2 & Replacement of Halon System to FM 200 System
23.05.2007 03.03.2009
order IBB
30. Sabic Jubail direct SHARQ Replacement of Halon system to Novec 1230 fire
30.07.2007 01.12.2009
order protection fluid
31. Sabic Jubail direct ARRAZI 3&4 Engineering, Procurement, Supply, Supervision,
order and Radio Installation Testing and commissioning of FM 200
07.09.2007 07.09.2009
communication system
room
32. Sabic Jubail direct ARRAZI entire Up gradation of Fire alarm system and NCS
28.01.2008 14.12.2008
order plant
33. Sabic Jubail direct IBN ZAHR Up gradation of Fire alarm system and
24.07.2007 01.12.2007
order Plant Replacement of New NCS

Page 5 of 9
TRADING & DEVELOPMENT CO. FOR MACHINERY & EQUIPMENT LTD.
FIRE & SAFETY DIVISION
Al Khobar : Tel (9663) 857-0079 - Fax (9663) 857-0087
Email: sales@[Link]
Al Khobar-Dammam Road, P.O. Box 2923, 31952 Al Khobar, Saudi Arabia

SERIAL CUSTOMER PROJECT DATE COMPLETION SYSTEM


NO. OF P.O DATE
34. Sabic Jubail direct Various plants Supply of Fire extinguishers, Safety equipment,
Open
order – Blanket order Thunderstorm Foam, Rescue equipment etc.
35. SNAMPROGETTI KCC 25.05.2005 11.12.2006 Supply of Complete fire fighting equipment
36. SNC-LAVALIN Khuraiyah 12.08.2006 15.02.2007 Supply of Complete fire fighting equipment
37. Fluor Saudi Kayan Design, Engineering, Supply Installation of
07.02.2008 30.11.2010
Project Deluge valve
38. Fluor Saudi Kayan Design, Engineering, Supply Installation of Fire
07.02.2008 30.11.2010
Project Alarm system
39. Tecnicas Reunidas Saudi Kayan Design, Engineering, Supply and Installation of
Project Foam system, Deluge system, Breathing Air
25.06.2008 13.12.2010
System, Co2 system, PIV, Fire hydrant and fire
monitors.
40. Daelim Saudi Kayan Design, Engineering, Supply and Installation of
Project Foam system, Deluge system, Breathing Air
04.06.2008 15.10.2010
System, Co2 system, PIV, Fire hydrant and fire
monitors.
41. CTCI Saudi Kayan Design, Engineering, Supply and Installation of
18.08.2008 20.10.2010
Project Breathing Air System.
42. HQCEC / Daelim Saudi Kayan Design, Engineering, Supply and Installation of
Project 04.12.2009 PIVs System.
04.06.2008

Page 6 of 9
TRADING & DEVELOPMENT CO. FOR MACHINERY & EQUIPMENT LTD.
FIRE & SAFETY DIVISION
Al Khobar : Tel (9663) 857-0079 - Fax (9663) 857-0087
Email: sales@[Link]
Al Khobar-Dammam Road, P.O. Box 2923, 31952 Al Khobar, Saudi Arabia

SERIAL CUSTOMER PROJECT DATE COMPLETION SYSTEM


NO. OF P.O DATE

43. Sabic Petrokemya Desing, supply, installation commissioning of


Halon 21.11.2007 01.07.2010 replacing Halong 1301 system to NOVEC 1230
replacement and Co2
44. Fluor Saudi Kayan Design, Engineering, Supply and Installation of
Project Foam system, Deluge system, Breathing Air
02.05.2008 30.11.2010
System, Co2 system, PIV, Fire hydrant and fire
monitors.
45. Daelim Saudi Kayan Deluge system,
HDPE Sprinkler System,
30.06.2009 12.12.2010
Fire fighting equipment
Co2 system & Breathing air system
46. Samsung engineering Saudi Kayan Design, Engineering, Supply and Installation of
co. PP & PH 21.08.2008 12.12.2010 Co2 system, Sprinkler system
And supply of complete fire fighting equipment
47. HYUNDAI AAC – Sahara Design, Engineering, Supply and Installation of
project 07.08.2008 09.09.2010 NOVEC SYSTEM
And supply of complete fire fighting equipment
48. Petrokemya HALON Design, Engineering, Supply and Installation of
21.11.2007 01.07.2010
replacement NOVEC fire suppression system and Co2 system.

Page 7 of 9
TRADING & DEVELOPMENT CO. FOR MACHINERY & EQUIPMENT LTD.
FIRE & SAFETY DIVISION
Al Khobar : Tel (9663) 857-0079 - Fax (9663) 857-0087
Email: sales@[Link]
Al Khobar-Dammam Road, P.O. Box 2923, 31952 Al Khobar, Saudi Arabia

SERIAL CUSTOMER PROJECT DATE COMPLETION SYSTEM


NO. OF P.O DATE
Dismantling and processing of existing Halon
system

49. Petrokemya Up gradation of Design, Engineering, Supply and Installation of


Fire Alarm 28.12.2007 30.07.2011 existing Fire alarm system to New Fire Alarm
System system utilizing NOTIFIER (Honeywell) brand.
50. United Sea water Design, engineering, fabrication and installation of
18.11.2009 15.11.2010
manifold sea water manifold
51. Ibn Sina Monitor & Design, engineering, fabrication and installation of
Manifold 26.05.2007 12.05.2008 big flow Monitor and manifold for the tank farm
protection
52. Yamama North Park- Design, Supply, Supervision, installation and
Aramco 15.03.2009 15.11.2011 Testing Commissioning of Fire fighting and fire
alarm system for a multistory building.
53. Safco Compressor Design, Supply, Supervision, installation and
shelter 23.05.2007 20.07.2009 Testing Commissioning of Fire alarm system for
protection ammonia compressor shelter
54. Petrokemya (Pegasus) Deluge system Design, Supply, Supervision, installation and
06.04.2009 29.08.2010
Testing Commissioning of Deluge system
55. Aramco Data center 12.07.2009 01.12.2011 Halon replacement system

Page 8 of 9
TRADING & DEVELOPMENT CO. FOR MACHINERY & EQUIPMENT LTD.
FIRE & SAFETY DIVISION
Al Khobar : Tel (9663) 857-0079 - Fax (9663) 857-0087
Email: sales@[Link]
Al Khobar-Dammam Road, P.O. Box 2923, 31952 Al Khobar, Saudi Arabia

SERIAL CUSTOMER PROJECT DATE COMPLETION SYSTEM


NO. OF P.O DATE
56. Sabic – Hadeed Halon Complete Halon replacement project
01.10.2007 On Going
replacement
57. Sabic – Hadeed Dist cooling Design supply supervision installation and testing
plant & commissioning of CO2/FM-200 fire
09.06.2009 On Going
suppression system & Fire alarm system in New
district cooling plant.
58. Aramco - Suwaidi Bulk Plant 23.01.2010 28.11.2011 Supply of foam skid
59. Sinopac Wasia bulk Supply of foam skid
plant 07.09.2010 12.12.2011

60. HADEED Upgrade Of Upgrade of fire Alarm System in HADEED base


NCS System 23.12.2008 28.03.2011

61. HADEED CSD Workshop Design supply supervision installation and testing
12.09.2009 27.10.2010 & commissioning of CO2 fire suppression system
for new switchgear room.
62. HADEED Elevator 11.12.2010 27.04.2011 Supply fire alarm system for Elevator Project
63. SUMITOMO KAUST 19.02.2009 Design, Engineering, supply and Installation of
12.11.2010
Novec 1230 system

Page 9 of 9
FM200 FIRE SUPPRESSION SYSTEM & FIRE DETECTION SYSTEM
RAWDHAT AL-KHURAIM

Vendor Document

Project Name : FM200 & FIRE ALARM SYSTEM


RAWDHAT AL KHURAIM

Client : EMPOWER

Document Description : APPROVED TRANSMITTALS

Document Number : REDA-12M-005

Vendor Document Review


Action Code Description
F Final
A Approved, vendor to submit for final
B Approved As Corrected
C Revise and Resubmit
D Incomplete Submittal
E Not Approved
I For Your Information and Use
By: Date:

00 12-08-2012 Issued for Approval SH ITZ AS


Approved
Rev. Date Description Prepared Checked Approved
(Client)
Item PART NO. Material Description Room 1 Room 2 UoM Qtty
Volume, m3 960.00 475.00
1 570633 16 Litre Container Assembly D.O.T. w/ label 0 0 ea 0
2 570634 32 Litre Container Assembly D.O.T. w/ label 0 0 ea 0
3 570638 52 Litre Container Assembly D.O.T. w/ label 0 0 ea 0
4 570639 106 Litre Container Assembly D.O.T. w/ label 0 0 ea 0
5 570640 147 Litre Container Assembly D.O.T. w/ label 0 0 ea 0
6 570641 180 Litre Container Assembly D.O.T. w/ label 0 0 ea 0
7 570586 343 Litre Container Assembly D.O.T. w/ label 6 2 ea 8
8 570277 106 litre container liquid level indicator 0 0 ea 0
9 570278 147 litre, 180 litre & 343ltr container liquid level indicator 6 2 ea 8
10 NOVEC 1230 (TM) Agent (Kg) 655 292 kg 947
11 570085 Tank Bracket Assembly (Fits 16L-32L Tank) 0 0 ea 0
12 570092 Tank Bracket Assembly (Fits 52L-180L Tank) 0 0 ea 0
13 570336 Tank Bracket Assembly (Fits 343 Tank) 12 4 ea 16
14 570539 Discharge hose 11/4'' & adaptor 0 0 ea 0
15 570538 Discharge Hose 2" 0 0 ea 0
16 69841 3" Discharge Hose /Check valve Assembly 6 2 ea 8
17 570566 Check valve assy-11/4'' 0 0 ea 0
18 570568 Check valve assy-2'' 6 2 ea 8
19 307.209.037 80 mm manifold NPT - 2PT 0 0 ea 0
20 307.209.037 100 mm manifold NPT - 2PT 1 1 ea 2
21 570537 Electric Actuator 24VDC, 0.2A 2 2 ea 4
22 570549 Local Manual Actuator 2 2 ea 4
23 570550 Pneumatic Actuator 2 0 ea 2
24 32336 Pilot Hose 710mm-1/4" 2 0 ea 2
25 570342 Valve to Pilot hose Adaptor 2 0 ea 2
26 31811 Pilot line Tee 0 0 ea 0
27 31810 Pilot line Elbow 2 0 ea 2
28 570585 Supervisory Low Pressure Switch 6 2 ea 8
29 46250 Discharge Pressure Switch 1 1 ea 2
30 570191 Warning Plate (for use Outside Room) 1 1 ea 2
31 570190 Manual Release Sign 1 1 ea 2
32 76496 Switch, Main/Reserve, Surface Mount 1 1 ea 2
33 76498 Maintenance Lockout Switch 1 1 ea 2
34 570603 Nozzle, Brass, 3/4" 0 0 ea 0
35 570604 Nozzle, Brass, 1" 0 1 ea 1
36 570605 Nozzle, Brass, 1 1/4" 4 0 ea 4
37 570606 Nozzle, Brass, 1½" 0 0 ea 0
38 570607 Nozzle, Brass, 2" 0 0 ea 0
39 NFS-320 FM-200 System Releasing Panel Single Loop Addressable 1 0 ea 1
Notifier USA
40 BAT-12180-BP Two BAT-12180 (12v, 18 AH) 1 0 ea 1
41 FSP-851 FSP-851, Intelligent Addressable Photoelectric detector 2 2 ea 4
42 B210LP Intelligent detector base, with flange. 2 2 ea 4
43 NBG-12LRA Dual action lexan Releasing station with Abort 1 1 ea 2
44 SBA-10 Surface back-box; for N-ARA-10 and NBG-12LRA. 1 1 ea 2
45 SSM24-6 24V, 6” Bell. 1 1 ea 2
46 WBB Weatherproof Backbox, Red. 1 1 ea 2
47 P2R Horn/Strobe, 12/24 Volt, Red, Multi-Candela 1 1 ea 2
48 BBS-2 Back box for the horn/strobe 1 1 ea 2
49 FMM-1 FMM-1, Addressable Monitor Module; with FlashScan 2 2 ea 4
50 FRM-1 FRM-1, Addressable Relay Module; with FlashScan 2 2 ea 4
51 FCM-1 FCM-1, Addressable Control Module with FlashScan 2 2 ea 4
52 FCM-1-REL FCM-1-REL, Addressable Releasing Module with 1 1 ea 2
FlashScan only.
dn-7112:c • A-14

NFS-320(E)
Intelligent Addressable
Fire Alarm System
Intelligent Fire Alarm Control Panels

General
The NFS-320 intelligent Fire Alarm Control Panel is part of the
ONYX® Series of Fire Alarm Controls from NOTIFIER.
In stand-alone or network configurations, ONYX Series products
meet virtually every application requirement.
Designed with modularity and ease of system planning, the
NFS-320 can be configured with just a few devices for small
building applications, or for a large campus or high-rise applica-
tion. Simply add additional peripheral equipment to suit the
application.
NOTE: Unless called out with a version-specific “R” or “E” at the
end of the part number, “NFS-320” refers to models NFS-320,

[Link]
NFS-320R, and NFS-320E; similarly, “CPU-320” refers to the main
circuit board for CPU-320, and CPU-320E.

Features
• Listed to UL Standard 864, 9th edition. NFS-320
• One isolated intelligent Signaling Line Circuit (SLC) Style 4, 6
or 7.
• Field-programmable on panel or on PC, with VeriFire Tools
• Up to 159 detectors (any mix of ion, photo, thermal, or multi- program check, compare, simulate.
sensor) and 159 modules (Addressable pull stations, nor-
• Full QWERTY keypad.
mally open contact devices, two-wire smoke, notification, or
relay). 318 devices maximum. • Battery charger supports 18 – 200 amp hour batteries
• Standard 80-character display. • Non-alarm points for lower priority functions.
• Network options: • Remote ACK/Signal Silence/System Reset/Drill via monitor
modules.
– High-speed network for up to 200 nodes (NFS2-3030,
NFS2-640, NFS-320(C), NCA-2, DVC, ONYXWorks, • Automatic time control functions, with holiday exceptions.
NCS, NFS-3030, NFS-640, and NCA). • Surface Mount Technology (SMT) electronics.
– Standard network for up to 103 nodes (NFS2-3030, • Extensive, built-in transient protection.
NFS2-640, NFS-320(C), NCA-2, DVC, ONYXWorks, • Powerful Boolean logic equations.
NCS, NFS-3030, NFS-640, NCA, AFP-200, AFP-300/
400, AFP-1010, and AM2020). Up to 54 nodes when DVC FLASHSCAN® INTELLIGENT FEATURES:
is used in network paging. • Poll up to 318 devices in less than two seconds.
• 6.0 amp power supply with four Class A/B built-in Notification • Activate up to 159 outputs in less than five seconds.
Appliance Circuits (NAC). Selectable System Sensor, Whee- • Multicolor LEDs blink device address during Walk Test.
lock, or Gentex strobe synchronization.
• Fully digital, high-precision protocol (U.S. Patent 5,539,389).
• Built-in Alarm, Trouble, Security, and Supervisory relays.
• Manual sensitivity adjustment — nine levels.
• VeriFire® Tools online or offline programming utility. Upload/
Download, save, store, check, compare, and simulate panel • Pre-alarm ONYX intelligent sensing — nine levels.
databases. Upgrade panel firmware. • Day/Night automatic sensitivity adjustment.
• Autoprogramming and Walk Test reports. • Sensitivity windows:
• Optional universal 318-point DACT. – Ion – 0.5 to 2.5%/foot obscuration.
• 80-character remote annunciators (up to 32). – Photo – 0.5 to 2.35%/foot obscuration.
• EIA-485 annunciators, including custom graphics. – Laser (VIEW®) – 0.02 to 2.0%/foot obscuration.
• Printer interface (80-column and 40-column printers). – Acclimate Plus™ – 0.5 to 4.0%/foot obscuration.
• History file with 800-event capacity in nonvolatile memory, – IntelliQuad – 1.0 to 4.0%/foot obscuration.
plus separate 200-event alarm-only file. • Drift compensation (U.S. Patent 5,764,142).
• Alarm Verification selection per point, with tally. • Degraded mode — in the unlikely event that the CPU-320
• Autoprogramming and Walk Test reports. microprocessor fails, FlashScan detectors revert to degraded
• Presignal/Positive Alarm Sequence (PAS). operation and can activate the CPU-320 NAC circuits and
alarm relay. Each of the four built-in panel circuits includes a
• Silence inhibit and Auto Silence timer options. Disable/Enable switch for this feature.
• NAC coding functions: • Multi-detector algorithm involves nearby detectors in alarm
– March time. decision (U.S. Patent 5,627,515).
– Temporal. • Automatic detector sensitivity testing (NFPA-72 compliant).
– California two-stage coding. • Maintenance alert (two levels).
– Canadian two-stage. • Self-optimizing pre-alarm.
– Strobe synchronization.

dn-7112:c • 05/12/2009 — Page 1 of 6


FSC-851 INTELLIQUAD • Abort (four options).
ADVANCED MULTI-CRITERIA DETECTOR • Low-pressure CO2 listed.
• Detects all four major elements of a fire (smoke, heat, CO, HIGH-EFFICIENCY OFFLINE SWITCHING
and flame).
3.0 AMP POWER SUPPLY (6.0 A IN ALARM):
• Automatic drift compensation of smoke sensor and CO cell.
• 120 VAC (NFS-320); 240 VAC (NFS-320E).
• High nuisance-alarm immunity.
• Displays battery current/voltage on panel (with display).
• Six sensitivity levels.
VOICE FEATURES:
FSL-751 VIEW (VERY INTELLIGENT EARLY WARNING)
• Integrates with FireVoice-25/50 Series (see DN-7004).
SMOKE DETECTION TECHNOLOGY:
• Integrates via serial connection with FireVoice-25/50ZS
• Revolutionary spot laser design. Series (see DN-7003).
• Advanced ONYX intelligent sensing algorithms differentiate
between smoke and non-smoke signals (U.S. Patent
5,831,524).
FlashScan, Exclusive
• Addressable operation pinpoints the fire location.
World-Leading Detector Protocol
• No moving parts to fail or filters to change. At the heart of the NFS-320 is a set of detection devices and
• Early warning performance comparable to the best aspiration device protocol — FlashScan (U.S. Patent 5,539,389). Flash-
systems at a fraction of the lifetime cost. Scan is an all-digital protocol that gives superior precision and
high noise immunity.
FAPT-851 ACCLIMATE PLUS In addition to providing quick identification of an active input
LOW-PROFILE INTELLIGENT MULTI-SENSOR: device, this new protocol can also activate many output devices
• Detector automatically adjusts sensitivity levels without oper- in a fraction of the time required by competitive protocols. This
ator intervention or programming. Sensitivity increases with high speed also allows the NFS-320 to have the largest device
heat. per loop capacity in the industry — 318 points — yet every input
and output device is sampled in less than two seconds. The
• Microprocessor-based technology; combination photo and microprocessor-based FlashScan detectors have bicolor LEDs
thermal technology. that can be coded to provide diagnostic information, such as
• FlashScan or classic mode compatible. device address during Walk Test.
• Low-temperature warning signal at 40°F ± 5°F (4.44°C ±
2.77°C). ONYX Intelligent Sensing
RELEASING FEATURES: Intelligent sensing is a set of software algorithms that provides
• Ten independent hazards. the NFS-320 with industry-leading smoke detection capability.
These complex algorithms require many calculations on each
• Sophisticated cross-zone (three options).
reading of each detector, and are made possible by the high-
• Delay timer and Discharge timers (adjustable). speed microcomputer used by the NFS-320.

NFS-320

Sample
System
Options
[Link]

Page 2 of 6 — dn-7112:c • 05/12/2009


Drift Compensation and Smoothing: Drift compensation Networking: If networking two or more control panels, each
allows the detector to retain its original ability to detect actual unit requires a Network Control Module or High-Speed Net-
smoke, and resist false alarms, even as dirt accumulates. It work Control Module (see “Network Options” on page 4).
reduces maintenance requirements by allowing the system to These modules can be installed in any option board position
automatically perform the periodic sensitivity measurements (see manual), and additional option boards can be mounted in
required by NFPA 72. Smoothing filters are also provided by front of them.
software to remove transient noise signals, such as those
caused by electrical interference.
KDM-R2 Controls and Indicators
Maintenance Warnings: When the drift compensation per-
formed for a detector reaches a certain level, the performance of Program Keypad: QWERTY type (keyboard layout).
the detector may be compromised, and special warnings are 12 LED Indicators: Power; Fire Alarm; Pre-Alarm; Security;
given. There are three warning levels: (1) Low Chamber value; Supervisory; System Trouble; Signals Silenced; Points Dis-
(2) Maintenance Alert, indicative of dust accumulation that is abled; Control Active; Abort; Pre-Discharge; Discharge.
near but below the allowed limit; (3) Maintenance Urgent, indica- Keypad Switch Controls: Acknowledge/Scroll Display; Signal
tive of dust accumulation above the allowed limit. Silence; Drill; System Reset; Lamp Test.
Sensitivity Adjust: Nine sensitivity levels are provided for LCD Display: 80 characters (2 x 40) with long-life LED back-
alarm detection. These levels can be set manually, or can light.
change automatically between day and night. Nine levels of pre-
alarm sensitivity can also be selected, based on predetermined
levels of alarm. Pre-alarm operation can be latching or self- Configuration Guidelines
restoring, and can be used to activate special control functions. The NFS-320 system ships assembled; description and some
Self-Optimizing Pre-Alarm: Each detector may be set for “Self- options follow.
Optimizing” pre-alarm. In this special mode, the detector Note: Stand-alone and network systems require a main display.
“learns” its normal environment, measuring the peak analog On stand-alone systems, the panel’s keypad provides the
readings over a long period of time, and setting the pre-alarm required display. On network systems (two or more networked
level just above these normal peaks. fire panel nodes), at least one NCA-2, NCS, or ONYXWorks
Cooperating Multi-Detector Sensing: A patented feature of annunciation device is required.
ONYX intelligent sensing is the ability of a smoke sensor to con- NFS-320: The standard, factory-assembled NFS-320 system
sider readings from nearby sensors in making alarm or pre- includes the following components: one CPU-320 control panel
alarm decisions. Without statistical sacrifice in the ability to mounted on chassis (120 V operation — ships with grounding
resist false alarms, it allows a sensor to increase its sensitivity to cable, battery interconnect cables, and document kit); includes
actual smoke by a factor of almost two to one. integral power supply mounted to the CPU-320; one primary
display KDM-R2 keypad/display; and one cabinet for surface or
Field Programming Options semi-flush mounting. Purchase batteries separately. One or two
option boards may be mounted inside the NFS-320 cabinet;
Autoprogram. This timesaving feature is a special software additional option boards can be utilized in remote cabinets.
routine. The FACP “learns” what devices are physically con-
nected and automatically loads them in the program with default NFS-320R: Same as NFS-320 above, but in red enclosure.
values for all parameters. Requiring less than one minute to run, NOTE: For information on the ULC-listed version, see DN-60085.
this routine allows the user to have almost immediate fire protec- NFS-320E: Same as NFS-320 above, but with 240 V operation.
tion in a new installation, even if only a portion of the detectors
are installed. TR-320: Trim ring for the NFS-320 cabinet.
Keypad Program Edit (with KDM-R2) The NFS-320, like all
NOTIFIER intelligent panels, has the exclusive feature of pro- Option Modules
gram creation and editing capability from the front panel keypad, FCPS-24S6/-24S8: Remote six-amp and eight-amp power sup-
while continuing to provide fire protection. The architecture plies with battery charger. See DN-6927.
of the NFS-320 software is such that each point entry carries its
own program, including control-by-event links to other points. COMPATIBLE DEVICES, EIA-232 PORTS
This allows the program to be entered with independent per- PRN-6: 80-column printer. See DN-6956.
point segments, while the NFS-320 simultaneously monitors
VS4095/5: Printer, 40-column, 24 V. Mounted in external back-
other (already installed) points for alarm conditions.
box. See DN-3260.
VeriFire Tools is an offline programming and test utility that can
greatly reduce installation programming time, and increase con- COMPATIBLE DEVICES, EIA-485 PORTS
fidence in the site-specific software. It is Windows®-based and ACM-24AT: ONYX Series ACS annunciator – up to 96 points of
provides technologically advanced capabilities to aid the annunciation with Alarm or Active LED, Trouble LED, and switch
installer. The installer may create the entire program for the per circuit. Active/Alarm LEDs can be programmed (by pow-
NFS-320 in the comfort of the office, test it, store a backup file, ered-up switch selection) by point to be red, green, or yellow; the
then bring it to the site and download from a laptop into the Trouble LED is always yellow. See DN-6862.
panel.
AEM-24AT: Same LED and switch capabilities as ACM-24AT,
expands the ACM-24AT to 48, 72, or 96 points. See DN-6862.
Placement of Equipment ACM-48A: ONYX Series ACS annunciator – up to 96 points of
in Chassis and Cabinet annunciation with Alarm or Active LED per circuit. Active/Alarm
The following guidelines outline the NFS-320’s flexible system LEDs can be programmed (by powered-up switch selection) in
design. groups of 24 to be red, green, or yellow. Expandable to 96 points
with one AEM-48A. See DN-6862.
Wiring: When designing the cabinet layout, consider separation
of power-limited and non-power-limited wiring as discussed in AEM-48A: Same LED capabilities as ACM-48A, expands the
the NFS-320 Installation Manual. ACM-48A to 96 points. See DN-6862.
It is critical that all mounting holes of the NFS-320 are secured
with a screw or standoff to ensure continuity of Earth Ground.

dn-7112:c • 05/12/2009 — Page 3 of 6


TM-4: Transmitter Module. Includes three reverse-polarity cir- FDM-1: FlashScan dual monitor module. See DN-6720.
cuits and one municipal box circuit; mount on NFS-320 chassis FZM-1: FlashScan two-wire detector monitor module. See DN-
or remotely. See DN-6860. 6720.
LCD-80/FDU-80: 80-character, backlit LCD display. Mounts up FMM-101: FlashScan miniature monitor module. See DN-6720.
to 6,000 ft. (1828.8 m) from panel. Up to 32 per FACP. See
LCD-80/-80TM (DN-3198) and FDU-80 (DN-6820). FCM-1-REL: FlashScan releasing control module. See DN-
60390.
LDM: Lamp Driver Modules LDM-32, LDM-E32, and LDM-R32;
remote custom driver modules. See LDM data sheet, DN-0551. FCM-1: FlashScan NAC control module. See DN-6724.
ACM-8R: Remote Relay Module with eight Form-C contacts. FRM-1: FlashScan relay module. See DN-6724.
Can be located up to 6,000 ft. (1828.8 m) from panel on four NBG-12LX: Manual pull station, addressable. See DN-6726.
wires. See ACM-8R data sheet, DN-3558. ISO-X: Isolator module. See DN-2243.
SCS: Smoke control stations SCS-8, SCE-8, with lamp drivers XP6-C: FlashScan six-circuit supervised control module. See
SCS-8L, SCE-8L; eight (expandable to 16) circuits. See SCS DN-6924.
data sheet DN-4818.
XP6-MA: FlashScan six-zone interface module; connects intelli-
UDACT: Universal Digital Alarm Communicator Transmitter, 636 gent alarm system to two-wire conventional detection zone. See
channel. See DN-4867. DN-6925.
UZC-256: Programmable Universal Zone Coder provides posi- XP6-R: FlashScan six-relay (Form-C) control module. See DN-
tive non-interfering successive zone coding. Microprocessor- 6926.
controlled, field-programmable from IBM®-compatible PCs
(requires optional programming kit). See DN-3404. XP10-M: FlashScan ten-input monitor module. See DN-6923.

COMPATIBLE INTELLIGENT DEVICES NETWORK OPTIONS


BEAMHK: Heating kit for transmitter/receiver unit of NCM-W, NCM-F: Standard Network Communications Mod-
FSB-200(S) below. See DN-6985. ules. Wire and multi-mode fiber versions available. See DN-
6861.
BEAMHRK: Heating kit for use with the reflector of FSB-200(S)
HS-NCM-W/MF/SF/WMF/WSF/MFSF: High-speed network
below. See DN-6985.
communications modules. Wire, single-mode fiber, multi-
BEAMLRK: Long-range accessory kit, FSB-200(S) below. See mode fiber, and media conversion models are available. See
DN-6985. DN-60454.
BEAMMRK: Multi-mount kit, FSB-200(S) below. See DN-6985. RPT-W, RPT-F, RPT-WF: Standard-network repeater board with
BEAMSMK: Surface-mount kit, FSB-200(S) below. See DN- wire connection (RPT-W), fiber connection (RPT-F), or allowing
6985. a change in media type between wire and fiber (RPT-WF). See
DN-6971.
FSB-200: Intelligent beam smoke detector. See DN-6985.
NCS5-W-ONYX: Network Control Station, Wire. UL-Listed
FSB-200S: Intelligent beam smoke detector with integral sensi- graphics PC with mouse, 19" color flat-screen LCD monitor.
tivity test. See DN-6985. Order as necessary for network systems. Each NCS con-
FSC-851: FlashScan IntelliQuad Advanced Multi-Criteria Detec- sumes one of 103 network addresses. See ONYX DN-6869.
tor. See DN-60412. NCS5-F-ONYX: Network Control Station, Fiber. UL-Listed
FSI-851: Low-profile FlashScan ionization detector. See DN- graphics PC with mouse, 19” color flat-screen LCD monitor.
6934. Order as necessary for network systems. Each NCS consumes
FSP-851: Low-profile FlashScan photoelectric detector. See one of 103 network addresses. See ONYX DN-6869.
DN-6935. ONYXWorks-NW: UL-listed graphics PC workstation for stan-
FSP-851T: Low-profile FlashScan photoelectric detector with dard NOTI•FIRE•NET with wire media. Includes NFN Gateway
135°F (57°C) thermal. See DN-6935. wire version (NFN-GW-PC-W) and 19" color flat-screen LCD
monitor. Each ONYXWorks workstation consumes one of 103
FST-851: FlashScan thermal detector 135°F (57°C). See network addresses. See DN-7048.
DN-6936.
ONYXWORKS-HNW: UL-listed graphics PC workstation for
FST-851R: FlashScan thermal detector 135°F (57°C) with rate- wire high-speed NOTI•FIRE•NET. Includes HS-NFN Gateway
of-rise. See DN-6936. (NFN-GW-PC-HNW) and 19" color flat-screen LCD monitor.
FST-851H: FlashScan 190°F (88°C) high-temperature thermal Each ONYXWorks consumes one of up to 200 network
detector. See DN-6936. addresses. See DN-7048.
DNR: InnovairFlex low-flow non-relay duct-detector housing ONYXWorks-NF: UL-listed graphics PC workstation for stan-
(order FSP-851 separately). Replaces FSD-751PL/FSD- dard NOTI•FIRE•NET with fiber media. Includes NFN Gateway
751RPL. See DN-60429. wire version (NFN-GW-PC-F) and 19" color flat-screen LCD
monitor. Each ONYXWorks workstation consumes one of 103
DNRW: Same as above with NEMA-4 rating, watertight. See
network addresses. See DN-7048.
DN-60429.
FAPT-851: FlashScan Acclimate Plus low-profile multi-sensor ONYXWORKS-HNSF: UL-listed graphics PC workstation for
detector. See DN-6937.
single-mode-fiber high-speed NOTI•FIRE•NET. Includes HS-
NFN Gateway (NFN-GW-PC-HNSF) and 19" color flat-screen
FSL-751: FlashScan VIEW laser photo detector. See DN-6886. LCD monitor. Each ONYXWorks consumes one of up to 200
B224RB: Low-profile relay base. See DN-60054. network addresses. See DN-7048.
B224BI: Isolator base for low-profile detectors. See DN-60054. ONYXWORKS-HNMF: UL-listed graphics PC workstation for
multi-mode-fiber high-speed NOTI•FIRE•NET. Includes HS-
B710LP: Low-profile base. Standard U.S. style. See DN-60054.
NFN Gateway (NFN-GW-PC-HNMF) and 19" color flat-screen
B501: European-style, 4" (10.16 cm) base. See DN-60054. LCD monitor. Each ONYXWorks consumes one of up to 200
B501BH-2: Standard sounder baseSee DN-60054. network addresses. See DN-7048.
B501BHT-2: Temporal tone sounder base. See DN-60054. NFN-GW-EM: NFN Gateway, embedded.
FMM-1: FlashScan monitor module. See DN-6720.

Page 4 of 6 — dn-7112:c • 05/12/2009


OTHER OPTIONS
DPI-232: Direct Panel Interface, specialized modem for extend-
ing serial data links to remotely located FACPs and/or peripher-
als; mount on NFS-320 chassis. See DN-6870.
VeriFire-TCD: VeriFire Tools CD-ROM. Contains programming
software for the ONYX Series. Includes local panel connection
cable. See DN-6871.
BAT Series: Batteries. NFS-320 utilizes two 12 volt, 18 to 200
AH batteries. This series of products replaces the previous PS
Series. See DN-6933.
NFS-LBB: Battery Box (required for batteries larger than 25
AH).
NFS-LBBR: Same as above, but red.
411: Slave Digital Alarm Communicator. See DN-6619.
411UDAC: Digital Alarm Communicator. See DN-6746.

dn-7112:c • 05/12/2009 — Page 5 of 6


SYSTEM SPECIFICATIONS

System Capacity (noncondensing) at 32°C ± 2°C (90°F ± 3°F). However, the


useful life of the system's standby batteries and the electronic
• Intelligent Signaling Line Circuits ......................................... 1 components may be adversely affected by extreme tempera-
• Intelligent detectors ......................................................... 159 ture ranges and humidity. Therefore, it is recommended that
• Addressable monitor/control modules .............................. 159 this system and its peripherals be installed in an environment
• Programmable internal hardware and output circuits .......... 4 with a normal room temperature of 15 – 27°C/60 – 80°F.
• Programmable software zones ........................................... 99
• Special programming zones ............................................... 14 Agency Listings and Approvals
• LCD annunciators per CPU-320/-320E .............................. 32 The listings and approvals below apply to the basic NFS-320
• ACS annunciators control panel. In some cases, certain modules may not be listed
per CPU-320/-320E ........................ 32 addresses x 64 points by certain approval agencies, or listing may be in process. Con-
sult factory for latest listing status.
Specifications • UL Listed: file S635
• CSFM: 7170-0028:244; 7165-0028:243
• Primary input power, CPU-320 board: 120 VAC, 50/60 Hz,
3.0 A. CPU-320E board: 220/240 VAC, 50/60 Hz, 1.5 A. • FM Approved
• Total output 24 V power: 6.0 A in alarm. • MEA: 128-07-E , FDNY Certificate #6007, #6025
NOTE: The power supply has a total of 6.0 A of available power. • FDNY COA # 6022 (HS-NCM)
This is shared by all internal circuits. • City of Chicago
• Standard notification circuits (4): 1.5 A each. NOTE: For ULC-listed model NFS-320C, see DN-60085.
• Four-wire detector power: 1.25 A.
• Non-resettable regulated power outputs: 1.25 A each.
Standards
• Non-resettable 5V power: 0.15 A. The NFS-320 complies with the following UL Standards and
• Battery charger range: 18 AH – 200 AH. Use separate cabi- NFPA 72 Fire Alarm Systems requirements:
net for batteries over 25 AH. • UL 864 (Fire).
• Optional high-capacity (25 – 120 AH) battery charger: CHG- • UL 1076 (Burglary).
120 (see CHG-120 data sheet, DN-6040). • LOCAL (Automatic, Manual, Waterflow and Sprinkler Super-
• Float rate: 27.6 V. visory).
• AUXILIARY (Automatic, Manual and Waterflow) (requires
Cabinet Specifications TM-4).
• REMOTE STATION (Automatic, Manual, Waterflow and
NFS-320 cabinet dimensions: BACKBOX, OUTSIDE: 18.240"
Sprinkler Supervisory) (requires TM-4).
(46.33 cm) height, 5.77" (14.656 cm) deep. WITH DOOR:
18.870" (47.93 cm) wide x 18.469" (46.911 cm) high x 5.817" • PROPRIETARY (Automatic, Manual, Waterflow and Sprinkler
(14.775 cm) deep. BACKBOX, INSIDE: 18.120" (46.025 cm) Supervisory). Not applicable for FM.
inner width, 5.175" (13.145 cm) inner depth. • CENTRAL STATION (Automatic, Manual, Waterflow and
Sprinkler Supervisory) (requires UDACT).
Temperature and Humidity Ranges • EMERGENCY VOICE/ALARM.
This system meets NFPA requirements for operation at 0 –
49°C/32 – 120°F and at a relative humidity 93% ± 2% RH

NOTI•FIRE•NET™, IntelliQuad™, and ONYXWorks™ are trademarks; and


Acclimate® Plus™, FlashScan®, NION®, NOTIFIER®, ONYX®, UniNet®,
VeriFire®, and VIEW® are registered trademarks of Honeywell International
Inc. Microsoft® and Windows® are registered trademarks of Microsoft
Corporation. Echelon® is a registered trademark of Echelon Corporation.
IBM® is a registered trademark of IBM Corporation.
©2009 by Honeywell International Inc. All rights reserved. Unauthorized use
of this document is strictly prohibited.

This document is not intended to be used for installation purposes.


We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
All specifications are subject to change without notice.
Made in the U.S. A.
For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118.
[Link]

Page 6 of 6 — dn-7112:c • 05/12/2009


dn-6935:c • H-202

FSP-851, FSP-851T, &


FSP-851R
Intelligent Plug-In Photoelectric
Intelligent/Addressable Devices

General

[Link]
Notifier 851 Series intelligent plug-in smoke detectors with
integral communication provide features that surpass conven-
tional detectors. Detector sensitivity can be programmed in
the control panel software. Sensitivity is continuously moni-
tored and reported to the panel. Point ID capability allows
each detector’s address to be set with decade address
switches, providing exact detector location for selective main-
tenance when chamber contamination reaches an unaccept-
able level. The FSP-851 photoelectric detector’s unique
optical sensing chamber is engineered to sense smoke pro- FSP-851 with B710LP base
duced by a wide range of combustion sources. Dual electronic
thermistors add 135°F (57°C) fixed-temperature thermal sens-
ing on the FSP-851T. The FSP-851R is a remote test capable

[Link]
detector for use with DNR(W) duct detector housings.
FSP-851 series detectors are compatible with all ONYX
series Notifier intelligent Fire Alarm Control Panels (FACP).
FlashScan® (U.S. Patent 5,539,389) is a communication pro-
tocol developed by Notifier that greatly increases the speed of
communication between analog intelligent devices. Intelligent
devices communicate in a grouped fashion. If one of the
devices in the group has new information, the panel’s CPU
stops the group poll and concentrates on single points. The
FSP-851T with B710LP base
net effect is response speed greater than five times that of ear-
lier designs.

Features Specifications
• Sleek, low-profile design.
Size: 2.1” (5.3cm) high x 4.1” (10.4cm) diameter installed in
• Addressable-analog communication. B501 base, 6.1” (15.5cm) diameter installed in B710LPbase.
• Stable communication technique with noise immunity. Shipping Weight: 5.2oz. (147g).
• Low standby current. Operating Temperature: FSP-851, 0°C to 49°C (32°F to
• Two-wire SLC connection. 120°F); FSP-851T, 0°C to 38°C (32°F to 100°F). Low temper-
• FlashScan (NFS-320, NFS-640, NFS2-640, NFS-3030, ature signal for FSP-851T at 45°F +/- 10°F (7.22°C +/-
NFS2-3030) and classic CLIP systems (AFP-100, AFP- 5.54°C). FSP-851R installed in a DNR(W), -20°C to 70°C (-4°F
200, AFP-300, AFP-400, NFS-640, AM2020/AFP1010, to 158°F).
NFS-3030) compatible. UL/ULC Listed Velocity Range: 0-4000 ft/min. (1219.2 m/
• Rotary, decimal addressing (1-99 on CLIP systems, 1-159 min.), suitable for installation in ducts.
on FlashScan systems). Relative Humidity: 10%-93% noncondensing.
• Optional remote, single-gang LED accessory.
Thermal Ratings: Fixed-temperature setpoint 135°F (57°C).
• Dual LED design provides 360° viewing angle.
• Visible bi-color LEDs blink green every time the detector is DETECTOR SPACING AND APPLICATIONS
addressed, and illuminate steady red on alarm (FlashScan Notifier recommends spacing detectors in compliance with
systems only). NFPA 72. In low airflow applications with smooth ceiling,
• Remote test feature from the panel. space detectors 30 feet (9.144m) for ceiling heights 10 feet
• Walk test with address display (an address on 121 will blink (3.148m) and higher. For specific information regarding
the detector LED: 12-[pause]-1(FlashScan systems only). detector spacing, placement, and special applications refer to
NFPA 72. System Smoke Detector Application Guide,
• Built-in functional test switch activated by external magnet. document A05-1003, is available at [Link]
• Built-in tamper-resistant feature.
ELECTRICAL SPECIFICATIONS
• Sealed against back pressure.
• Constructed of off-white Bayblend®, designed to commer- Voltage Range: 15-32 volts DC peak.
cial standards, and offers an attractive appearance. Standby Current (max. avg.): 300μA @ 24VDC (one com-
• 94-5V plastic flammability rating. munication every five seconds with LED enabled).
• SEMS screws for wiring of the separate base. LED Current (max.): 6.5mA @ 24VDC (‘ON’).
• Optional relay, isolator, and sounder bases. BASES AVAILABLE
NOTE: “A” suffix indicates ULC Listed model.

dn-6935:c • 3/12/10 — Page 1 of 2


B710LP(A): 6.1” (15.5cm) diameter. FSP-851T:Same as FSP-851 but includes a built-in 135°F
B501(A): 4.1” (10.4cm) diameter. (57°C) fixed-temperature thermal device.

B200SR(A): Intelligent sounder base, configurable for temp-3 FSP-851TA:Same as FSP-851T but with ULC listing.
or steady sound. FSP-851R: Low-profile intelligent photoelectric sensor,
B224RB(A) Relay Base: Screw Terminals, up to 14AWG remote test capable. For use with DNRW.
(2.0mm2); Relay Type, Form-C; Rating, 2.0A @ 30VDC resis- FSP-851RA: Same as FSP-851R but with ULC listing.
tive, 0.3A @ 110VDC inductive, 1.0A @ 30VDC inductive;
Dimensions, 6.2” (15.748cm) x 1.2” (3.048cm) x 1.2” BASES
(3.048cm). B710LP: Standard U.S. low-profile base.
B224BI(A) Isolator Base: Dimensions, 6.2” (15.748cm) x 1.2” B710LPBP:Standard U.S. low-profile base, pkg. of 10.
(3.048cm) x 1.2” (3.048cm); Maximum, 25 devices between B710LPA:Standard U.S. low-profile base, ULC listing.
isolator bases.
B501BP:Standard European flangeless base, pkg. of 10.
Installation B501A:Standard European flangeless base, ULC listing.
FSP-851 plug-in detectors use a separate base to simplify B200SR(A): Intelligent sounder base, configurable for temp-3
installation, service, and maintenance. A special tool allows or steady sound.
maintenance personnel to plug in and remove detectors with- B224RB(A):Intelligent relay base.
out using a ladder.
B224BI(A):Intelligent isolator base. Isolates SLC from loop
Mount base on an electrical backbox which is at least 1.5” shorts.
(3.81cm) deep. Suitable mounting base boxes include:
• 4.0” (10.16cm) square box. ACCESSORIES
• 3.5” (8.89cm) or 4.0” (10.16cm) octagonal box. F110:Retrofit replacement flange for older style bases. Con-
verts older high profile base for use with FlashScan detectors.
• Single-gang box (except relay or isolator base).
• With B200SR base, use an appropriate junction box. RA100Z(A):Remote LED annunciator. 3-32VDC. Fits U.S.
single-gang electrical box. Supported by B710LP(A) and
• With B224RB or B224BI base, use a 3.5” (8.89cm) octago- B501(A) bases only.
nal box, or a 4.0” (10.16cm) octagonal or square box.
SMK400E:Surface mounting kit provides for entry of surface
NOTE: 1) Because of inherent supervision provided by the SLC
loop, end-of-line resistors are not required. Wiring “T-taps” or
wiring conduit. For use with B501(A) base only.
branches are permitted for style 4 (Class “B”) wiring. 2) When RMK400:Recessed mounting kit. For use with B501(A) base
using relay or sounder bases, consult data sheet DN-2243 (ISO-X) only.
for device limitations between isolator modules and isolator bases.
SMB600:Surface mounting kit for use with B710LP(A).
Agency Listings and Approvals BCK-200B:Black detector covers, box of 10. For use with
FSP-851 only.
These listings and approvals apply to the modules specified in
this document. In some cases, certain modules or applications WCK-200B: White detector covers, box of 10. For use with
may not be listed by certain approval agencies, or listing may FSP-851 only.
be in process. Consult factory for latest listing status. M02-04-00:Test magnet.
• UL Listed: S1115 M02-09-00:Test magnet with telescope stick.
• ULC Listed: S1115 (FSP-851A, FSP-851TA) XR2B:Detector removal tool. Allows installation and/or
• MEA Listed: 225-02-E removal of FlashScan Series detector heads from base in high
• FM Approved ceiling installations.
• CSFM: 7272-0028:206 T55-127-010:Detector removal tool without pole.
• Maryland State Fire Marshal: Permit # 2122 XP-4:Extension pole for XR2B. Comes in three 5-ft. sections.
• BSMI: CI313066760036
• CCCF: Certif. # 2004081801000017 (FSP-851T)
Certif. # 2004081801000016 (FSP-851)
• Lloyd’s Register: 03/60011

Product Line Information


NOTE: “A or “CDN” suffix indicates ULC listed model.
Notifier® and FlashScan® are registered trademarks of Honeywell Interna-
FSP-851:Low-profile intelligent photoelectric sensor. Must be
tional Inc. Bayblend® is a registered trademark of Bayer Corporation.
mounted to one of the bases listed below.
©2010 by Honeywell International Inc. All rights reserved. Unauthorized use
FSP-851A:Same as FSP-851 but with ULC listing. of this document is strictly prohibited.

This document is not intended to be used for installation purposes.


We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
All specifications are subject to change without notice.
Made in the U.S. A.
For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118.
[Link]

Page 2 of 2 — dn-6935:c • 3/12/10


dn-60054:B
Intelligent Bases
B7102PJ(A), B2241BI(A), B224RB(A), B501J
B501BH-2, B501BHT-2
Mounting Kits, and Accessories

Addressable Devices

General

[Link]
Intelligent FlashScan® and CLIP mounting bases and kits pro-
vide a variety of ways to install NOTIFIER detectors in any appli-
cation. Intelligent detectors can be mounted in either flanged or

[Link]
flangeless bases depending on junction box selection (see
Junction Box Selection Guide). Across this product line, detec-
tors plug in easily to the base with SEMS screws; and models Relay Base
employ various 12 to 24 AWG wire ranges. Flangeless Mounting Base
Relay, isolator, and sounder bases can be used to meet local

[Link]
code requirements. Relay bases provide one Form-C contact
relay for control of auxiliary functions such as door closure and
elevator recall. Isolator bases allow loops to continue to operate
under fault conditions and automatically restore when the fault is

[Link]
removed. Sounder bases are available in temporal and non-tem-
poral pattern versions depending on whether the signal is to be
used for evacuation purposes. Recessed Mounting
Flanged Mounting Base
The RMK400 recessed mounting kit provides the most aes-
thetically pleasing installation. Surface mounting boxes are

[Link]
available when flush mounting isn’t possible.

Specifications

[Link]
Diameter: For B501: 4.1" (104 mm). For B224BI, B224RB,
B710LP: 6.1" (155 mm). For B501BH-2, B501BHT-2: 6.0" (152
mm). Standard Sounder Base Flangeless Surface Mounting
Wire gauge: for B224BI, B224RB: 14 to 24 AWG. For
B710LP,B501, B501BH-2, B501BHT-2: 12 to 24 AWG.
Temperature range: For B224BI, B224RB, B501BH-2, Startup capacitance: 200 μF.
B501BHT-2: 32°F to 120°F (0°C to 49°C). For B501 and
Sounder delay time: For B501BH-2 and B501BHT-2, 0.75 to
B710LP, -4°F to 150°F (0°C to 66°C).
5.7 seconds.
Humidity range: 10% to 93% RH, non-condensing.
Sound output: greater than 90 dBA measured in anechoic
System temperature and humidity ranges: This system room at 10 feet (3.048 m), 24 volts. 85 dBA minimum in UL
meets NFPA requirements for operation at 0°C to 49°C (32°F to reverberant room.
120°F); and at a relative humidity (noncondensing) of 85% at
30°C (86°F) per NFPA, and 93% ± 2% at 32°C ± 2°C (89.6°F ±
1.1°F) per ULC. However, the useful life of the system’s standby
Recessed Mounting Kit
batteries and the electronic components may be adversely The RMK400 can be used with drywall or suspended ceilings.
affected by extreme temperature ranges and humidity. There- The aesthetically pleasing design can be used with standard
fore, it is recommended that this system and all peripherals be junction boxes — suitable for use with 4.0” (10.16 cm) octago-
installed in an environment with a nominal room temperature of nal, 50 mm, and 60 mm junction boxes connected to flexible
15°C to 27°C (60°F to 80°F). conduit. Note that junction boxes are not included in the kit. As
an application example, with the B501 base, the RMK400 pro-
Electrical Ratings vides a simple installation solution in applications that demand a
lower-profile smoke detector.
FOR B224RB, B224BI:
Operating voltage: 15 to 32 VDC (powered by SLC). Product Line Information
Standby ratings: <500 μA maximum @ 24 VDC. INTELLIGENT BASES
Set time (B224RB only): short delay 55 to 90 msec; long delay B501: Flangeless mounting base.
6 to 9 seconds.
B501A: Flangeless mounting base, ULC Listed.
Reset time (B224RB only): 20 msec maximum.
B501BP: Flangeless mounting base, ULC Listed.
Relay characteristics (B224RB only): two-coil latching relay;
one Form-C contact; ratings (UL/CSA): 0.9 A @ 125 VAC, 0.9 A B710LP: Flanged mounting base.
@ 110 VDC, and 3.0 A @ 30 VDC. B710LPA: Flanged mounting base, ULC Listed.
FOR B501BH-2, B501BHT-2: B710LPBP: Flanged mounting base.
External supply voltage: 17 to 32 VDC. B501BH-2: Plug-in System Sensor standard sounder detec-tor
base, steady tone. Includes B501 base.
Standby current: 1.0 mA maximum.
B501BHT-2: Plug-in System Sensor temporal tone sounder
Alarm current: 15 mA maximum. base.
Maximum ripple voltage: 10% of supply voltage.

dn-60054:B • 06/08/09 — Page 1 of 2


B501BHA: Plug-in System Sensor standard sounder detec-tor M02-09-00: Test magnet with telescoping handle.
base, steady tone, with ULC Listing. Includes B501 base. XR2B: Detector removal tool (T55-127-000 included).
B501BHTA: Plug-in System Sensor temporal tone sounder XP-4: Extension pole for XR2B (5 to 15 ft/1.524 to 4.572 m).
base, with ULC listing.
T55-127-000: Detector removal head.
B224RB: Relay base.
BCK-200B: Black detector kit, package of 10
B224RBA: Relay base, ULC Listed.
B224BI: Isolator base. Agency Listings and Approvals
B224BIA: Isolator base, ULC Listed.
The listings and approvals below apply to intelligent bases as
MOUNTING KITS AND ACCESSORIES noted. In some cases, certain modules or applications may not
be listed by certain approval agencies, or listing may be in pro-
RMK400: Recessed mounting kit.
cess. Consult factory for latest listing status.
SMK400E: Surface mounting kit, flangeless.
• UL Listed: S911
SMB600: Surface mounting kit, flanged. • ULC Listed: S911
F110: Retrofit flange for B501B, B524. • FM Approved
RA400Z: Remote LED annunciator. • MEA: 22-95-E, 205-94-E Vol. 2; 257-06-E
RA400ZA: Remote LED annunciator, ULC Listed. • CSFM: 7170-0554:150, 7300-0554:108, 7300-0554:109,
M02-04-00: Detector test magnet. 7300-1653:109; 7300-1653:126, 7300-1653:191

Junction Box Selection Guide


4.0" Sq.
Single- with 3.0"
Base Models Gang 3.5" Oct. 4.0" Oct. 4.0" Sq. mud ring 50 mm 60 mm 70 mm 75 mm
B501 No Yes No No Yes Yes Yes Yes No
B710LP Yes Yes Yes Yes Yes No No No No
B224RB No Yes Yes Yes No No Yes Yes Yes
B224BI No Yes Yes Yes No No No Yes Yes
B501BH-2 No No No Yes No No No No No
B501BHT-2 No No No Yes No No No No No
NOTE: Box depth contingent on base and wire size.
Refer to National Electric Code or applicable local codes for appropriate recommendations.

FlashScan®, NOTIFIER® and System Sensor® are registered trademarks


of Honeywell International Inc.
©2009 by Honeywell International Inc. All rights reserved. Unauthorized use
of this document is strictly prohibited.

This document is not intended to be used for installation purposes.


We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
All specifications are subject to change without notice.
Made in the U.S. A.
For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118.
[Link]

Page 2 of 2 — dn-60054:B • 06/08/09


September 17, 2001 DN-6840 • F-710

NBG-12LR and NBG-12LRA


Dual-Action Agent Release Stations
Section: Releasing Panels

California
GENERAL State Fire
Marshal
The NBG-12LR and NBG-12LRA are Agent Release Sta-
tions designed for use with NOTIFIER Fire Alarm Control 7150-0028:199
Panels with releasing capabilities and RP Series Releas-
ing Systems.
S692
FEATURES Approved
• Non-coded, dual action operation.
• Made with durable polycarbonate.
• Optional surface backbox.
• NBG-12LRA includes:
" Abort switch.
" Power-on indication.
" Released indication.
" Manual release (dual-action).
• NBG-12LR includes:
" Dual-action release only.

APPLICATIONS
The NBG-12LRA and NBG-12LR are ideal for areas such
as clean rooms and computer rooms where a chemical
agent is used to extinguish a fire.

PRODUCT LINE INFORMATION


NBG-12LRA Agent release station with abort switch,
Release LED, Normal LED.
NBG-12LR Dual-action agent release station.
SBA-10 Surface backbox for NBG-12LRA.
SB-10 Surface backbox for NBG-12LR.

[Link]

NOTIFIER

Dual-Action NBG-12LRA
(shown activated)

This document is not intended to be used for installation purposes. We try to keep our
product information up-to-date and accurate. We cannot cover all specific applications or
anticipate all requirements. All specifications are subject to change without notice.
For more information, contact NOTIFIER. Phone: (203) 484-7161 FAX: (203) 484-7118

12 Clintonville Road, Northford, Connecticut 06472

DN-6840 • 09/17/01 — Page 1 of 2


WIRING

[Link]
Dual-Action NBG-12LR
NOTIFIER

[Link]

*NOTE: Mount End-of-Line Resistor on the last unit.


*Mount 4.7K ELR on the last unit when abort switch and manual release switch are
connected to control panel circuits. Mount 47K resistor on last unit when abort switch and
manual release switch are connected to monitor module or control module. Refer to
control panel manual for the listed ELR. Refer to the following documents when connect-
ing to the control panel: S-500/TC-2 (P/N 15019/15023); S-5000/TCM-2 (P/N 15583/
15805); RP-1002 (P/N 15151); AFP-200 (P/N 15511), AFP-400 (P/N 50253).

DIMENSIONS, BACKBOXES

12345678901234
12345678901234
12345678901234
12345678901234
Normally Open
12345678901234
12345678901234
12345678901234
Abort Switch
12345678901234
12345678901234

[Link]
[Link]

NBG-12LRA (rear view)


Agent Release Pull Station

Page 2 of 2 — DN-6840 • 09/17/01


dn-6724:b2

FCM-1(A) & FRM-1(A)


Series
Control and Relay Modules
Intelligent / Addressable Devices

General
FCM-1(A) Control Module: The FCM-1(A) Addressable Con-
trol Module provides Notifier intelligent fire alarm control pan-
els a circuit for Notification Appliances (horns, strobes,
speakers, etc.) Addressability allows the FCM-1(A) to be acti-
vated, either manually or through panel programming, on a
select (zone or area of coverage) basis.
FRM-1(A) Relay Module: The FRM-1(A) Addressable Relay
Module provides the system with a dry-contact output for acti-
vating a variety of auxiliary devices, such as fans, dampers,
control equipment, etc. Addressability allows the dry contact to
be activated, either manually or through panel programming,
on a select basis.
FlashScan® (U.S. Patent 5,539,389) is a communication pro-
tocol developed by NOTIFIER Engineering that greatly
enhances the speed of communication between analog intelli-

[Link]
gent devices. Intelligent devices communicate in a grouped
fashion. If one of the devices within the group has new infor-
mation, the panel CPU stops the group poll and concentrates
on single points. The net effect is response speed greater than
five times that of other designs.
FCM-1(A)
Features
• Built-in type identification automatically identifies these • The FCM-1(A) is configured for a single Class B (Style Y) or
devices to the control panel. Class A (Style Z) Notification Appliance Circuit.
• Internal circuitry and relay powered directly by two-wire • The FRM-1(A) provides two Form-C dry contacts that
SLC loop. The FCM-1(A) module requires power (for horns, switch together.
strobes, etc.), or audio (for speakers).
• Integral LED “blinks” green each time a communication is Operation
received from the control panel and turns on in steady red Each FCM-1(A) or FRM-1(A) uses one of 159 possible module
when activated. addresses on a SLC loop (99 on CLIP loops). It responds to
• LED blink may be deselected globally (affects all devices). regular polls from the control panel and reports its type and
• High noise immunity (EMF/RFI). status, including the open/normal/short status of its Notifica-
tion Appliance Circuit (NAC). The LED blinks with each poll
• The FCM-1(A) may be used to switch 24-volt NAC power, received. On command, it activates its internal relay. The
audio (up to 70.7 Vrms). FCM-1(A) supervises Class B (Style Y) or Class A (Style Z)
• Wide viewing angle of LED. notification or control circuits.
• SEMS screws with clamping plates for wiring ease. Upon code command from the panel, the FCM-1(A) will dis-
• Direct-dial entry of address 01– 159 for FlashScan loops, connect the supervision and connect the external power sup-
01 – 99 for CLIP mode loops. ply in the proper polarity across the load device. The
• Speaker, and audible/visual applications may be wired for disconnection of the supervision provides a positive indication
Class B or A (Style Y or Z). to the panel that the control relay actually turned ON. The
external power supply is always relay isolated from the com-
munication loop so that a trouble condition on the external
Applications power supply will never interfere with the rest of the system.
The FCM-1(A) is used to switch 24 VDC audible/visual power, Rotary switches set a unique address for each module. The
high-level audio (speakers), or control telephone devices. The address may be set before or after mounting. The built-in
FRM-1(A) may be programmed to operate dry contacts for
TYPE CODE (not settable) will identify the module to the con-
applications such as door holders or Air Handling Unit shut- trol panel, so as to differentiate between a module and a sen-
down, and to reset four-wire smoke detector power. sor address.
NOTE: Refer to the SLC Manual (PN 51253) for details regarding
releasing applications with the FCM-1(A). Refer to the FCM-1-REL
datasheet (DN-60390) for new FlashScan® releasing applications.
Specifications for FCM-1(A)
Normal operating voltage: 15 to 32 VDC.
Construction Maximum current draw: 6.5 mA (LED on).
• The face plate is made of off-white heat-resistant plastic. Average operating current: 350 μA direct poll, 375 μA group
• Controls include two rotary switches for direct-dial entry of poll with LED flashing, 485 μA Max. (LED flashing, NAC
address (01-159). shorted.)

dn-6724:b2 • 6/17/10 — Page 1 of 2


Maximum NAC Line Loss: 4 VDC. Contact Ratings for FRM-1(A)
External supply voltage (between Terminals T10 and
T11): Maximum (NAC): Regulated 24 VDC; Maximum Current Maximum Load Application
(Speakers): 70.7 V RMS, 50W. Rating Voltage Description
Drain on external supply: 1.7 mA maximum using 24 VDC 3A 30 VDC Resistive Non-Coded
supply; 2.2 mA Maximum using 80 VRMS supply. 2A 30 VDC Resistive Coded
Max NAC Current Ratings: For class B wiring system, the .9 A 110 VDC Resistive Non-Coded
current rating is 3A; For class A wiring system, the current rat-
ing is 2A. .9 A 125 VDC Resistive Non-Coded
Temperature range: 32°F to 120°F (0°C to 49°C). .5 A 30 VDC
Inductive
Coded
(L/R=5ms)
Humidity range: 10% to 93% non-condensing.
Inductive
Dimensions: 4.5" (114.3 mm) high x 4" (101.6 mm) wide x 1A 30 VDC
(L/R=2ms)
Coded
1.25" (31.75 mm) deep. Mounts to a 4" (101.6 mm) square x
2.125" (53.975 mm) deep box. Inductive
.3 A 125 VAC Non-Coded
(PF=0.35)
Accessories: SMB500 Electrical Box; CB500 Barrier
Inductive
1.5 A 25 VAC (PF=0.35) Non-Coded
Specifications for FRM-1(A)
Normal operating voltage: 15 to 32 VDC. Inductive
Maximum current draw: 6.5 mA (LED on). .7 A 70.7 VAC (PF=0.35) Non-Coded

Average operating current: 230 μA direct poll; 255 μA group


poll. Inductive
2A 25 VAC (PF=0.35) Non-Coded
EOL resistance: not used.
Temperature range: 32°F to 120°F (0°C to 49°C). NOTE: Maximum (Speakers): 70.7 V RMS, 50 W
Humidity range: 10% to 93% non-condensing.
Dimensions: 4.5" (114.3 mm) high x 4" (101.6 mm) wide x Product Line Information
1.25" (31.75 mm) deep. Mounts to a 4" (101.6 mm) square x NOTE: “A” suffix indicates ULC Listed model.
2.125" (53.975 mm) deep box.
FCM-1(A): Intelligent Addressable Control Module.
Accessories: SMB500 Electrical Box; CB500 Barrier
FRM-1(A): Intelligent Addressable Relay Module.
Agency Listings and Approvals A2143-20: Capacitor, required for Class A (Style Z) operation
of speakers.
In some cases, certain modules may not be listed by certain
approval agencies, or listing may be in process. Consult fac- SMB500: Optional Surface-Mount Backbox.
tory for latest listing status. CB500: Control Module Barrier — required by UL for separat-
• UL: S635 ing power-limited and non-power limited wiring in the same
junction box as FCM-1(A).
• ULC: S3705 (A version only)
NOTE: For installation instructions, see the following documents:
• FM Approved
• CSFM: 7300-0028:202, 7300-0028:219 • FCM-1(A) Installation document I56-1169.
• MEA: 14-00-E • FRM-1(A) Installation document I56-3502.
• FDNY: COA #6038, #6026 • Notifier SLC Wiring Manual, document 51253.

Notifier® and FlashScan® are registered trademarks of Honeywell


International Inc.
©2010 by Honeywell International Inc. All rights reserved. Unauthorized use
of this document is strictly prohibited.

This document is not intended to be used for installation purposes.


We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
All specifications are subject to change without notice.
Made in the U.S. A.
For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118.
[Link]

Page 2 of 2 — dn-6724:b2 • 6/17/10


dn-6720:B • H-220

FMM-1, FMM-101,
FZM-1 & FDM-1
Monitor Modules with FlashScan®
Intelligent/Addressable Devices

General
Four different monitor modules are available for Notifier’s intel-
ligent control panels for a variety of applications. Monitor mod-
ules supervise a circuit of dry-contact input devices, such as
conventional heat detectors and pull stations, or monitor and
power a circuit of two-wire smoke detectors (FZM-1).
FMM-1 is a standard-sized module (typically mounts to a 4"
[10.16 cm] square box) that supervises either a Class A (Style
D) or Class B (Style B) circuit of dry-contact input devices.
FMM-101 is a miniature monitor module (a mere 1.3" (3.302
cm) H x 2.75" (6.985 cm) W x 0.5" (1.270 cm) D) that super-
vises a Class B (Style B) circuit of dry-contact input devices.
Its compact design allows the FMM-101 to often be mounted
in a single-gang box behind the device it monitors.
FZM-1 is a standard-sized module that monitors and super-

[Link]
vises compatible two-wire, 24 volt, smoke detectors on a
Class A (Style D) or Class B (Style B) circuit.
FDM-1 is a standard-sized dual monitor module that monitors
and supervises two independent two-wire Style B (Class B)
dry-contact initiating device circuits (IDCs) at two separate, FMM-1 (Type H)
consecutive addresses in intelligent, two-wire systems.
A) Initiating Device Circuit. A 47K ohm End-of-Line Resistor
FlashScan® (U.S. Patent 5,539,389) is a communication pro- (provided) terminates the Style B circuit. No resistor is
tocol developed by NOTIFIER that greatly increases the speed required for supervision of the Style D circuit.
of communication between analog intelligent devices. Intelli-
gent devices communicate in a grouped fashion. If one of the FMM-1 OPERATION
devices within the group has new information, the panel CPU Each FMM-1 uses one of the available module addresses on
stops the group poll and concentrates on single points. The an SLC loop. It responds to regular polls from the control panel
net effect is response speed greater than five times that of and reports its type and the status (open/normal/short) of its
other designs. protocols. Initiating Device Circuit (IDC). A flashing LED indicates that
the module is in communication with the control panel. The
FMM-1 Monitor Module LED latches steady on alarm (subject to current limitations on
the loop).
• Built-in type identification automatically identifies this device
as a monitor module to the control panel. FMM-1 SPECIFICATIONS
• Powered directly by two-wire SLC loop. No additional power Nominal operating voltage: 15 to 32 VDC.
required.
Maximum current draw: 5.0 mA (LED on).
• High noise (EMF/RFI) immunity.
Maximum operating current: 375 µA (LED flashing).
• SEMS screws with clamping plates for ease of wiring.
Maximum IDC wiring resistance: 1,500 ohms.
• Direct-dial entry of address: 01 – 159 on FlashScan sys-
tems; 01 – 99 on CLIP systems. , 01 – 99 on . EOL resistance: 47K ohms.
• LED flashes green during normal operation (this is a pro- Temperature range: 32°F to 120°F (0°C to 49°C).
grammable option) and latches on steady red to indicate
Humidity range: 10% to 93% noncondensing.
alarm.
The FMM-1 Monitor Module is intended for use in intelligent, Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x
two-wire systems, where the individual address of each mod- 1.25" (3.175 cm) deep. Mounts to a 4" (10.16 cm) square x
ule is selected using the built-in rotary switches. It provides 2.125" (5.398 cm) deep box.
either a two-wire or four-wire fault-tolerant Initiating Device Cir-
cuit (IDC) for normally-open-contact fire alarm and supervisory FMM-101 Mini Monitor Module
devices. The module has a panel-controlled LED indicator.
• Built-in type identification automatically identifies this device
The FMM-1 can be used to replace MMX-1 modules in
as a monitor module to the panel.
existing systems.
• Powered directly by two-wire SLC loop. No additional power
FMM-1 APPLICATIONS required.
Use to monitor a zone of four-wire smoke detectors, manual • High noise (EMF/RFI) immunity.
fire alarm pull stations, waterflow devices, or other normally- • Tinned, stripped leads for ease of wiring.
open dry-contact alarm activation devices. May also be used
• Direct-dial entry of address: 01 – 159 on FlashScan sys-
to monitor normally-open supervisory devices with special
tems; 01 – 99 on CLIP systems. , 01 – 99 on .
supervisory indication at the control panel. Monitored circuit
may be wired as an NFPA Style B (Class B) or Style D (Class

dn-6720:B • 01/21/09 — Page 1 of 4


• LED flashes during normal operation; this is a programma-

[Link]
ble option.
• LED latches steady to indicate alarm on command from
control panel.
The FZM-1 Interface Module is intended for use in intelligent,
addressable systems, where the individual address of each
module is selected using built-in rotary switches. This module
allows intelligent panels to interface and monitor two-wire con-
ventional smoke detectors. It transmits the status (normal,
open, or alarm) of one full zone of conventional detectors back
to the control panel. All two-wire detectors being monitored
must be UL compatible with the module. The FZM-1 can be
used to replace MMX-2 modules in existing systems.
FZM-1 APPLICATIONS
Use the FZM-1 to monitor a zone of two-wire smoke detectors.
The monitored circuit may be wired as an NFPA Style B (Class
B) or Style D (Class A) Initiating Device Circuit. A 3.9 K ohm
End-of-Line Resistor (provided) terminates the end of the Style
The FMM-101 Mini Monitor Module can be installed in a sin- B or D (class B or A) circuit (maximum IDC loop resistance is
gle-gang junction directly behind the monitored unit. Its small 25 ohms). Install ELR across terminals 8 and 9 for Style D
size and light weight allow it to be installed without rigid mount- application.
ing. The FMM-101 is intended for use in intelligent, two-wire FZM-1 OPERATION
systems where the individual address of each module is
selected using rotary switches. It provides a two-wire initiating Each FZM-1 uses one of the available module addresses on
device circuit for normally-open-contact fire alarm and security an SLC loop. It responds to regular polls from the control panel
devices. The FMM-101 can be used to replace MMX-101 and reports its type and the status (open/normal/short) of its
modules in existing systems. Initiating Device Circuit (IDC). A flashing LED indicates that
the module is in communication with the control panel. The
FMM-101 APPLICATIONS LED latches steady on alarm (subject to current limitations on
Use to monitor a single device or a zone of four-wire smoke the loop).
detectors, manual fire alarm pull stations, waterflow devices, or FZM-1 SPECIFICATIONS
other normally-open dry-contact devices. May also be used to
monitor normally-open supervisory devices with special super- Nominal operating voltage: 15 to 32 VDC.
visory indication at the control panel. Monitored circuit/device Maximum current draw: 5.1 mA (LED on).
is wired as an NFPA Style B (Class B) Initiating Device Circuit.
Maximum IDC wiring resistance: 25 ohms.
A 47K ohm End-of-Line Resistor (provided) terminates the cir-
cuit. Maximum operating current: 270 µA (LED flashing).
EOL resistance: 3.9K ohms.
FMM-101 OPERATION
Each FMM-101 uses one of the available module addresses External supply voltage (between Terminals T3 and T4):
on an SLC loop. It responds to regular polls from the control DC voltage: 24 volts power limited. Ripple voltage: 0.1 Vrms
panel and reports its type and the status (open/normal/short) maximum. Current: 90 mA per module maximum.
of its Initiating Device Circuit (IDC). Temperature range: 32°F to 120°F (0°C to 49°C).
FMM-101 SPECIFICATIONS Humidity range: 10% to 93% noncondensing.
Nominal operating voltage: 15 to 32 VDC. Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x
1.25" (3.175 cm) deep. Mounts to a 4" (10.16 cm) square x
Maximum operating current: 375 µA.
2.125" (5.398 cm) deep box.
Maximum IDC wiring resistance: 1,500 ohms.
EOL resistance: 47K ohms. FDM-1 Dual Monitor Module
Temperature range: 32°F to 120°F (0°C to 49°C). The FDM-1 Dual Monitor Module is intended for use in intelli-
Humidity range: 10% to 93% noncondensing. gent, two-wire systems. It provides two independent two-wire
initiating device circuits (IDCs) at two separate, consecutive
Dimensions: 1.3" (3.302 cm) high x 2.75" (6.985 cm) wide x addresses. It is capable of monitoring normally open contact
0.65" (1.651 cm) deep. fire alarm and supervisory devices; or either normally open or
Wire length: 6" (15.24 cm) minimum. normally closed security devices. The module has a single
panel-controlled LED.
FZM-1 Interface Module NOTE: The FDM-1 provides two Class B (Style B) IDC circuits
ONLY. Class A (Style D) IDC circuits are NOT supported in any
• Supports compatible two-wire smoke detectors. application.
• Supervises IDC wiring and connection of external power
source. FDM-1 SPECIFICATIONS
• High noise (EMF/RFI) immunity. Normal operating voltage range: 15 to 32 VDC.
• SEMS screws with clamping plates for ease of wiring. Maximum current draw: 6.4 mA (LED on).
• Direct-dial entry of address: 01 – 159 on FlashScan sys- Maximum operating current: 750 µA (LED flashing).
tems, 01 – 99 on CLIP systems. Maximum IDC wiring resistance: 1,500 ohms.

Page 2 of 4 — dn-6720:B • 01/21/09


EOL resistance: 47K ohms.
Temperature range: 32° to 120°F (0° to 49°C).
Humidity range: 10% to 93% (non-condensing).
Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x
2.125" (5.398 cm) deep.
FDM-1 AUTOMATIC ADDRESSING
The FDM-1 automatically assigns itself to two addressable
points, starting with the original address. For example, if the
FDM-1 is set to address “26”, then it will automatically assign
itself to addresses “26” and “27”.
NOTE: “Ones” addresses on the FDM-1 are 0, 2, 4, 6, or 8 only.
Terminals 6 and 7 use the first address, and terminals 8 and 9 use
the second address.

CAUTION:
! Avoid duplicating addresses on the system.

Installation
FMM-1, FZM-1, and FDM-1 modules mount directly to a stan-
dard 4" (10.16 cm) square, 2.125" (5.398 cm) deep, electrical
box. They may also be mounted to the SMB500 surface-mount
box. Mounting hardware and installation instructions are pro-
vided with each module. All wiring must conform to applicable
local codes, ordinances, and regulations. These modules are
intended for power-limited wiring only.
The FMM-101 module is intended to be wired and mounted
without rigid connections inside a standard electrical box. All
wiring must conform to applicable local codes, ordinances, and
regulations.

Agency Listings and Approvals


In some cases, certain modules may not be listed by certain
approval agencies, or listing may be in process. Consult fac-
tory for latest listing status.
• UL: S635
• ULC: S3705
• FM Approved
• CSFM: 7300-0028:202
• MEA: 457-99-E, 457-99-E Vol. 3, 143-01-E
• U.S. Coast Guard:
– 161.002/23/3 (AFP-200: FMM-1/-101, FZM-1)
– 161.002/42/1 (NFS-640: FMM-1/-101)
• Lloyd’s Register:
– 03/60011/E1 (FMM-1/-101, FZM-1)
– 94/60004/E2 (AFP-200: except FDM-1)
– 02/60007 (NFS-640: FDM-1)

Product Line Information


NOTE: “A” suffix indicates ULC-listed model.
FMM-1(A): Monitor module.
FMM-101(A): Monitor module, miniature.
FZM-1(A): Monitor module, two-wire detectors.
FDM-1(A): Monitor module, dual, two independent Class B
circuits.
SMB500: Optional surface-mount backbox.
NOTE: See installation instructions and refer to the SLC Wiring
Manual, PN 51253.

dn-6720:B • 01/21/09 — Page 3 of 4


DN-60390:B • H-235

FCM-1-REL(A)
Releasing Control Module

Intelligent/Addressable Devices

General
The FCM-1-REL Releasing Control Module is specifically
designed for fire suppression releasing applications in Flash-
Scan® systems. Power to the release agent solenoid(s) runs
through the module for full-time monitoring and supervision.
The FCM-1-REL Releasing Control Module uses a redun-
dant protocol; the module must be armed with a pair of sig-
nals in order to activate. It will then enter a 3-second window
awaiting a pair of confirmation signals. If no confirmation is
received, the module will automatically reset. It also super-
vises the wiring to the connected load and reports the status
to the panel as NORMAL, OPEN, or SHORT CIRCUIT. The
module has two pairs of output termination points available
for fault-tolerant wiring and a panel-controlled LED indicator.
The module may be connected to either one 24VDC solenoid
or up to two 12VDC solenoids (in series). To ensure proper
operation, this module shall be connected to a compatible
Notifier system control panel only (list available from Notifier).

[Link]
In addition, please refer to Notifier Device Compatibility Doc-
ument PN 15378 for the list of compatible solenoids.
NOTE: FCM-1-REL is required for all new FlashScan-mode
releasing applications with NFS2-3030 (version 14.0 or higher),
NFS2-640 (version 12.0 or higher) and NFS-320(E)(C) (version
FCM-1-REL
12.0 or higher) panels. Use FCM-1 for releasing applications on
NFS-640, NFS-3030, and all CLIP mode panels.
EXTERNAL SUPPLY
Features • Normal Operating Voltage: 24 VDC Nominal
• Redundant protocol for added protection • Maximum Line Loss: 2.3 VDC (total allowable loss from
• Configurable for Class A or Class B operation power supply to module and from module to solenoid)
• External supply voltage monitoring • Minimum Operating Voltage to Activate Solenoid:
• Can power one 24V or two 12V solenoids 18 VDC (at solenoid)
• SEMS screws for easing wiring • Standby Current: 6.4 mA
• Panel controlled status LED • Activation Current: 10 mA
• Analog communications SOLENOID
• Rotary address switches • Supervisory Loop Voltage: 3.3 V
• Low standby current • Supervisory Loop Current (Normal): 30 mA
• Mounts in standard 4" (10.16 cm) junction box • Maximum Activation Current: 2 A
• FlashScan operation
Product Line Information
Specifications NOTE: “A” suffix indicates ULC Listed model.
FCM-1-REL(A): Releasing Control Module.
GENERAL SPECIFICATIONS
• Operating Voltage: 15 to 32 VDC SMB500: Optional Surface-Mount Backbox.
• Communication Line Loop Impedance: 40 Ohm max. CB500: Control Module Barrier — required by UL for sepa-
• Temperature Range: 14°F to 140°F (-10° to 60°C) rating power-limited and non-power limited wiring in the
same junction box as FCM-1-REL.
• Relative Humidity: 10% to 95% noncondensing
• Shipping Weight: 5.5 oz (156 g)
• Dimensions: 4.275" W × 4.675" H × 1.400" D
(10.86 cm W × 11.87 cm H × 3.56 cm D)
SLC
• Average Operating Current: 700 µA max @ 24 VDC
(one communication every 5 sec. with LED enabled)
• Maximum Activation Current: 9.0 mA (LED on)

DN-60390:B • 05/20/2009 — Page 1 of 2


Agency Listings and Approvals
These listings and approvals apply to the modules specified
in this document. In some cases, certain modules or applica-
tions may not be listed by certain approval agencies, or list-
ings may be in process. Consult factory for latest listing
status.
• UL Listed: S635
• ULC Listed: (FCM-1-RELA)
• FM Approved
• CSFM: 7300-0028:249

Notifier® and FlashScan® are registered trademarks of Honeywell


International Inc.
©2009 by Honeywell International Inc. All rights reserved. Unauthorized use
of this document is strictly prohibited.

This document is not intended to be used for installation purposes.


We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
All specifications are subject to change without notice.
Made in the U.S. A.
For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118.
[Link]

Page 2 of 2 — DN-60390:B • 05/20/2009


Notifier® and FlashScan® are registered trademarks of Honeywell
International Inc.
©2009 by Honeywell International Inc. All rights reserved. Unauthorized use
of this document is strictly prohibited.

This document is not intended to be used for installation purposes.


We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
All specifications are subject to change without notice.
Made in the U.S. A.
For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118.
[Link]

Page 4 of 4 — dn-6720:B • 01/21/09


DN-7087:A • J-70

SpectrAlert® Advance
Selectable Output
Notification Appliances
Audio/Visual Devices

General [Link] [Link]

System Sensor® SpectrAlert® Advance selectable-output


horns, strobes and horn/strobes are rich with features guaran-
teed to cut installation times and maximize profits. The SpectrA-
lert Advance series of notification appliances is designed to
simplify your installations, with features such as: plug-in
designs, instant feedback messages to ensure correct installa-
tion of individual devices, and eleven field-selectable candela
settings for wall and ceiling strobes and horn/strobes.
Indoor Ceiling Horn/Strobe Outdoor Ceiling Strobe
More specifically, when installing Advance products, first attach
[Link] [Link]
a universal mounting plate to a four-inch square, four-inch octa-
gon, or double-gang junction box. The two-wire mounting plate
attaches to a single-gang junction box.
Then, connect the notification appliance circuit wiring to the
SEMS terminals on the mounting plate.
Finally, attach the horn, strobe, or horn/strobe to the mounting
plate by inserting the product’s tabs in the mounting plate’s
grooves. The device will rotate into position, locking the prod-
uct’s pins into the mounting plate’s terminals. The device will
Indoor Wall Horn/Strobe Indoor Ceiling Strobe
temporarily hold in place with a catch until it is secured with a
[Link] [Link]
captured mounting screw.
SpectrAlert Advance products allow you to choose:
• 12 or 24 volts.
• At 24 volts, 15, 15/75, 30, 75, 95, 110, 115, 135, 150, 177, or
185 candela by way of a rear-mounted slide switch and front
viewing window.
• Horn tones and volume by way of a rotary switch.
• The SpectrAlert Advance series includes outdoor notification
appliances. Outdoor strobes and horn/strobes (two-wire and Indoor Wall Horn Outdoor Wall Strobe
four-wire) are available for wall or ceiling. Outdoor horns are
available for wall only. All System Sensor outdoor products • Minimal intrusion into the backbox.
are rated between –40°F and 151°F (–40°C and 66°C) in wet • Horn rated at 88+ dbA at 16 volts.
or dry applications.
• Rotary switch for tone selection.
Models available:
• Three horn volume settings.
• Indoor wall-mount: horn, strobe, 2-wire horn/strobe, 4-wire • Electrically compatible with existing SpectrAlert products.
horn/strobe.
• Indoor ceiling-mount: strobe, 2-wire horn/strobe, 4-wire horn/
strobe.
Engineering Specifications
• Outdoor wall-mount: horn, strobe, 2-wire horn/strobe, 4-wire SpectrAlert Advance horns, strobes, and horn/strobes shall
horn/strobe. mount to a standard 4.0" x 4.0" x 1.5" (10.16 x 10.16 x 3.81 cm)
• Outdoor ceiling-mount: strobe, 2-wire horn/strobe, 4-wire backbox, 4.0" (10.16 cm) octagonal backbox, or a double-gang
horn/strobe. backbox. Two-wire products shall also mount to a single-gang
2.0" x 4.0" x 1.875" (5.08 x 10.16 x 4.763 cm) backbox. A uni-
versal mounting plate shall be used for mounting ceiling and
Features wall products. The notification appliance circuit wiring shall ter-
• Plug-in design. minate at the universal mounting plate. Also, SpectrAlert
• Same mounting plate for wall- and ceiling-mount units. Advance products, when used with the Sync•Circuit™ Module
accessory, shall be powered from a non-coded notification appli-
• Shorting spring on mounting plate for continuity check before ance circuit output and shall operate on a nominal 12 or 24
installation. volts. When used with the Sync•Circuit Module, 12-volt rated
• Captive mounting screw. notification appliance circuit outputs shall operate between 9
• Tamper-resistance capability. and 17.5 volts; 24-volt rated notification appliance circuit outputs
• Field-selectable candela settings on wall and ceiling units: shall operate between 17 and 33 volts. Indoor SpectrAlert
15, 15/75, 30, 75, 95, 110, 115, 135, 150, 177, 185. Advance products shall operate between 32°F and 120°F (0°C
and 49°C) from a regulated DC, or full-wave-rectified, unfiltered
• Automatic selection of 12 or 24 volt operation at 15 and 15/75
power supply. Strobes and horn/strobes shall have field-select-
candela.
able candela settings including 15, 15/75, 30, 75, 95, 110, 115,
• Outdoor wall and ceiling products. 135, 150, 177, 185.
• Outdoor products rated from –40°F and 151°F (–40°C and
66°C).

DN-7087:A • 10/18/06 — Page 1 of 4


STROBE Operating Specifications
The strobe shall be a System Sensor SpectrAlert Advance • Standard operating temperature: 32°F to 120°F (0°C to 49°C).
Model _______ listed to UL 1971 and shall be approved for fire
• K Series operating temperature: –40°F to 151°F (–40°C to
protective service. The strobe shall be wired as a primary-sig-
66°C).
naling notification appliance and comply with the Americans with
Disabilities Act requirements for visible signaling appliances, • Humidity range: 10% to 93% non-condensing (indoor products).
flashing at 1 Hz over the strobe’s entire operating voltage range. • Strobe flash rate: 1 flash per second.
The strobe light shall consist of a xenon flash tube and associ- • Nominal voltage: regulated 12 VDC/FWR or regulated 24
ated lens/reflector system. VDC/FWR. NOTE: Full Wave Rectified (FWR) voltage is a
non-regulated, time-varying power source that is used on
HORN/STROBE COMBINATION some power supply and panel outputs.
The horn/strobe shall be a System Sensor SpectrAlert Advance • Operating voltage range: 8 V to 17.5 V (12 V nominal); or
Model _______ listed to UL 1971 and UL 464 and shall be 16 V to 33 V (24 V nominal). NOTE: P, S, PC, and SC prod-
approved for fire protective service. The horn/strobe shall be ucts will operate at 12 V nominal only for 15 cd and 15/75 cd.
wired as a primary-signaling notification appliance and comply
• Input terminal wire gauge: 12 to 18 AWG (3.31 to 0.821 mm²).
with the Americans with Disabilities Act requirements for visible
signaling appliances, flashing at 1 Hz over the strobe’s entire • Ceiling-mount dimensions (including lens): 6.8" diameter
operating voltage range. The strobe light shall consist of a x 2.5" deep (17.3 cm diameter x 6.4 cm deep).
xenon flash tube and associated lens/reflector system. The horn • Wall-mount dimensions (including lens): 5.6" H x 4.7" W x
shall have three audibility options and an option to switch 2.5" D (14.2 cm H x 11.9 cm W x 6.4 cm D).
between a Temporal 3 pattern and a Non-Temporal (continuous) • Horn dimensions: 5.6" H x 4.7" W x 1.3" D (14.2 cm H x
pattern. These options are set by a multiple position switch. On 11.9 cm W x 3.3 cm D).
four-wire products, the strobe shall be powered independently of
the sounder. The horn on horn/strobe models shall operate on a
coded or non-coded power supply.
Agency Listings and Approvals
The listings and approvals below apply to SpectrAlert Advance
OUTDOOR PRODUCTS Selectable Output Notification Devices. In some cases, certain
SpectrAlert Advance outdoor horns, strobes and horn/strobes modules may not be listed by certain approval agencies, or list-
shall be listed for outdoor use by UL and shall operate between ing may be in process. Consult factory for latest listing status.
–40°F and 151°F (–40°C and 66°C). The products shall be listed • UL Listed: file S4011 (HR__, HW__, P2__, P4__, PC2__,
for use with a System Sensor outdoor/weatherproof backbox PC4__ models); file S5512 (models SCR, SCRH, SCW,
with half-inch and three-fourths-inch conduit entries. SCWH, SR, SRH, SW, SWH); file S3593 (SCRHK, SCRK,
SRHK, SRK).
SYNCHRONIZATION MODULE
• ULC Listed: file CS1099 (HRA, HRKA); file CS1089 (typi-
The module shall be a System Sensor Sync•Circuit _______ cally “A” models, with exception of outdoor strobes). See
listed to UL 464 and shall be approved for fire protective service. Canadian data sheet for listings and specifications.
The module shall synchronize SpectrAlert strobes at 1 Hz and
• FM approved.
horns at Temporal 3. Also, while operating the strobes, the mod-
ule shall silence the horns on horn/strobe models over a single • MEA approved: file 452-05-E.
pair of wires. The module shall mount to a 4.688" x 4.688" x • CSFM approved: file 7125-1653:186 (SCR, SCRH, SCW,
2.125" (11.906 x 11.906 x 5.398 cm) backbox. The module shall SCWH, SR, SRH, SW, SWH); file 7125-1653:188 P2__,
also control two Style Y (class B) circuits or one Style Z (Class P4__, PC2__, PC4__ models); file 7135-1653:189 (HR, HRK,
A) circuit. The module shall synchronize multiple zones. Daisy- HW); file 7300-1653:187 (SCRHK, SCRK, SRHK, SRK).
chaining two or more synchronization modules together will syn-
chronize all the zones they control. The module shall not oper-
ate on a coded power supply.

Strobe Current Draw, Horn Current Draw,


UL Maximum (mA RMS) UL Maximum (mA RMS)
8 – 17.5 V 16 – 33 V 8 – 17.5 V 16 – 33 V
Sound
Candela DC FWR DC FWR Pattern dB DC FWR DC FWR
15 123 128 66 71 Temporal High 57 55 69 75
15/75 142 148 77 81 Temporal Medium 44 49 58 69

Standard 30 NA N/A 94 96 Temporal Low 38 44 44 48


Candela 75 NA NA 158 153 Non-temporal High 57 56 69 75
Range 95 NA NA 181 176 Non-temporal Medium 42 50 60 69
110 NA NA 202 195 Non-temporal Low 41 44 50 50
115 NA NA 210 205 Coded High 57 55 69 75
135 NA NA 228 207 Coded Medium 44 51 56 69
High 150 NA NA 246 220 Coded Low 40 46 52 50
Candela
Range 177 NA NA 281 251
185 NA NA 286 258

Page 2 of 4 — DN-7087:A • 10/18/06


Horn and Horn/Strobe Horn and Horn/Strobe Output (dBA)
Rotary Switch Setting 8 – 17.5 V 16 – 33 V
Switch Sound
Setting Repetition Rate dB Level Position Pattern dB DC FWR DC FWR
1 Temporal horn High 1 Temporal High 78 78 84 84
2 Temporal horn Medium 2 Temporal Medium 74 74 80 80
3 Temporal horn Low 3 Temporal Low 71 73 76 76
4 Normal horn High 4 Non-temporal High 82 82 88 88
5 Normal horn Medium 5 Non-temporal Medium 78 78 85 85
6 Normal horn Low 6 Non-temporal Low 75 75 81 81
7* Externally coded High 7* Coded High 82 82 88 88
8* Externally coded Medium 8* Coded Medium 78 78 85 85
9* Externally coded Low 9* Coded Low 75 75 81 81
*NOTE: Settings 7, 8, and 9 are not available *NOTE: Settings 7, 8, and 9 are not available on 2-wire horn/strobe.
on 2-wire horn/strobe.

Two-Wire Horn/Strobe, STANDARD Candela Range (15 – 115 cd),


UL Maximum Current Draw (mA RMS)
8 – 17.5 V 16 – 33 V

Input, Sound Pattern, dB Level 15 15/75 15 15/75 30 75 95 110 115


DC Input, Temporal, High 137 147 79 90 107 176 194 212 218
DC Input, Temporal, Medium 132 144 69 80 97 157 182 201 210
DC Input, Temporal, Low 132 143 66 77 93 154 179 198 207
DC Input, Non-temporal, High 141 152 91 100 116 176 201 221 229
DC Input, Non-temporal, Medium 133 145 75 85 102 163 187 207 216
DC Input, Non-temporal, Low 131 144 68 79 96 156 182 201 210
FWR Input, Temporal, High 136 155 88 97 112 168 190 210 218
FWR Input, Temporal, Medium 129 152 78 88 103 160 184 202 206
FWR Input, Temporal, Low 129 151 76 86 101 160 184 194 201
FWR Input, Non-temporal, High 142 161 103 112 126 181 203 221 229
FWR Input, Non-temporal, Medium 134 155 85 95 110 166 189 208 216
FWR Input, Non-temporal, Low 132 154 80 90 105 161 184 202 211

Two-Wire Horn/Strobe, HIGH Candela Range (135 – 185 cd),


UL Maximum Current Draw (mA RMS)
16 – 33 V 16 – 33 V

DC Input 135 150 177 185 FWR Input 135 150 177 185
DC, Temporal, High 245 259 290 297 FWR, Temporal, High 215 231 258 265
DC, Temporal, Medium 235 253 288 297 FWR, Temporal, Medium 209 224 250 258
DC, Temporal, Low 232 251 282 292 FWR, Temporal, Low 207 221 248 256
DC, Non-temporal, High 255 270 303 309 FWR, Non-temporal, High 233 248 275 281
DC, Non-temporal, Medium 242 259 293 299 FWR, Non-temporal, Medium 219 232 262 267
DC, Non-temporal, Low 238 254 291 295 FWR, Non-temporal, Low 214 229 256 262

[Link]

DN-7087:A • 10/18/06 — Page 3 of 4


Ordering Information
Model Description* Model Description
WALL HORN/STROBES CEILING HORN/STROBES
P2R 2-wire horn/strobe, standard cd, red. PC2R 2-wire horn/strobe, standard cd, red.
P2RH 2-wire horn/strobe, high cd, red. PC2RH 2-wire horn/strobe, high cd, red.
P2RK 2-wire horn/strobe, standard cd, red, outdoor.** PC2RK 2-wire horn/strobe, standard cd, red, outdoor.
P2RHK 2-wire horn/strobe, high cd, red, outdoor. PC2RHK 2-wire horn/strobe, high cd, red, outdoor.
P2W 2-wire horn/strobe, standard cd, white. PC2W 2-wire horn/strobe, standard cd, white.
P2WH 2-wire horn/strobe, high cd, white. PC2WH 2-wire horn/strobe, high cd, white.
P4R 4-wire horn/strobe, standard cd, red. PC4R 4-wire horn/strobe, standard cd, red.
P4RH 4-wire horn/strobe, high cd, red. PC4RH 4-wire horn/strobe, high cd, red.
P4RK 4-wire horn/strobe, standard cd, red, outdoor. PC4RK 4-wire horn/strobe, standard cd, red, outdoor.
P4RHK 4-wire horn/strobe, high cd, red, outdoor. PC4RHK 4-wire horn/strobe, high cd, red, outdoor.
P4W 4-wire horn/strobe, standard cd, white. PC4W 4-wire horn/strobe, standard cd, white.
P4WH 4-wire horn/strobe, high cd, white. PC4WH 4-wire horn/strobe, high cd, white.
WALL STROBES CEILING STROBES
SR Strobe, standard cd, red. SCR Strobe, standard cd, red.
SRH Strobe, high cd, red. SCRH Strobe, high cd, red.
SRK Strobe, standard cd, red, outdoor. SCRK Strobe, standard cd, red, outdoor.
SRHK Strobe, high cd, red, outdoor. SCRHK Strobe, high cd, red, outdoor.
SW Strobe, standard cd, white. SCW Strobe, standard cd, white.
SWH Strobe, high cd, white. SCWH Strobe, high cd, white.
ACCESSORIES HORNS
BBS-2 Backbox skirt, wall, red. HR Horn, red.
BBSW-2 Backbox skirt, wall, white. HRK Horn, red, outdoor.
BBSC-2 Backbox skirt, ceiling, red. HW Horn, white.
BBSCW-2 Backbox skirt, ceiling, white. ACCESSORIES, continued
SA-WBB Weatherproof backbox, wall. MP-2W-20BP 2-wire indoor mounting plates, pkg of 20.
SA-WBBC Weatherproof backbox, ceiling. cont’d at right MPK-2W-20BP 2-wire outdoor mounting plates, pkg of 20.
NOTE: *“High cd” refers to strobes that include 135, 150, 177, and 185 candela settings. “Standard cd” refers to strobes that
include 15, 15/75, 30, 75, 95, 110, and 115 candela settings. **All outdoor models (“K” suffix) include weatherproof backbox.

Sync•Circuit™ is a trademark, and NOTIFIER®, SpectrAlert®, and System


Sensor® are registered trademarks of Honeywell International Inc.
©2006 by Honeywell International Inc. All rights reserved. Unauthorized use
of this document is strictly prohibited.

This document is not intended to be used for installation purposes.


We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
All specifications are subject to change without notice.

For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118.
[Link]

Page 4 of 4 — DN-7087:A • 10/18/06


DN-6910:A • J-200

SSM Series
Alarm Bells

Audio/Visual Appliances

General
System Sensor’s SSM Series alarm bells are low-current,
high-decibel notification appliances for use in fire and burglary
systems or other signaling applications. They come pre-wired
to reduce installation time, and also incorporate a polarized
electrical design for use with supervision circuitry.
With reliable performance, SSM Series alarm bells provide
loud, resonant tones. They operate on 24 VDC and are motor-
driven.
SSM Series alarm bells offer simplified installation. For indoor
use, SSM Series alarm bells mount to a standard 4" (10.16
cm) square electrical box. For outdoor applications, a WBB
weatherproof backbox is used.
[Link]

Features
• Approved for indoor or outdoor (with WBB backbox) use.
• Low current draw.
• High dB output.
• Three sizes available: 6" (15.24 cm), 8" (20.32 cm), and Agency Listings and Approvals
10" (25.40 cm) diameter. These listings and approvals apply to the modules specified in
• 24 VDC models; polarized for use with supervision circuitry. this document. In some cases, certain modules or applications
• Bells mount directly to standard 4" (10.16 cm) square elec- may not be listed by certain approval agencies, or listing may
trical box. be in process. Consult factory for latest listing status.
• UL Listed: S4011
Specifications • ULC Listed: S7539 (SSM24-6A, SSM24-8A, SSM24-10A)
Nominal voltage: 24 VDC. • MEA Listed: 331-01-E
Operating voltage range: 19.2 to 26.4 VDC. • FM Approved
Average current draw: 0.03 A. • CSFM: 7135-1653:125

Sound output: 85 dB.


Ordering Information
Operating temperature range: –31°F (–35°C) to +140°F
(+60°C). SSM24-6: 6" (15.24 cm) bell, 24 VDC, polarized, 85 dBA.

Termination: provided with two sets of leads for in/out wiring. SSM24-6A: Canadian model of 6" bell above.

Service use: Fire Alarm, General Signaling, Burglar Alarm. SSM24-8: 8" (20.32 cm) bell, 24 VDC, polarized, 85 dBA.
SSM24-8A: Canadian model of 8" bell above.
Engineering and Architectural SSM24-10: 10" (25.40 cm) bell, 24 VDC, polarized, 85 dBA.
Specifications SSM24-10A: Canadian model of 10" above.
Model shall be a SSM Series alarm bell. Bells shall have WBB: Weatherproof backbox.
underdome strikers and operating mechanisms. Gongs on
said bell shall be no smaller than nominal 6" (15.24 cm), 8"
(20.32 cm), or 10" (25.40 cm) (specify size) with an operating
voltage of 24 VDC. Bells shall be suitable for surface or semi-
flush mounting. Outdoor surface-mounted installations shall
be weatherproof (using optional WBB weatherproof backbox);
otherwise, bells shall mount to a standard 4" (10.16 cm)
square electrical box having a minimum projection of 2.5"
(6.35 cm). Bells shall be located as shown on the installation
drawings or as determined by the Authority Having Jurisdic-
tion. Bells shall be Listed for indoor/outdoor use by Underwrit-
ers Laboratories, ULC (Canada), and the California State Fire
Marshal, and approved by Factory Mutual and MEA.

DN-6910:A • 3/6/07 — Page 1 of 2


©2008 by Honeywell International Inc. All rights reserved. Unauthorized use
of this document is strictly prohibited.

This document is not intended to be used for installation purposes.


We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
All specifications are subject to change without notice.
Made in the U.S. A.
For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118.
[Link]

Page 2 of 2 — DN-6910:A • 3/6/07


DN-2243:A • H-300

ISO-X
Fault Isolator Module

Intelligent/Addressable Devices

General
The Notifier ISO-X Fault Isolator Module is used with the NFS-
3030, NFS2-3030, NFS-640, NFS2-640, NFS-320, and AFP-
200 to protect the system against wire-to-wire short circuits on
the SLC loops.

Features
• Powered by SLC loop directly, no external power required.
• Mount in standard 4.0" (10.16 cm) square (2.125" [5.398
cm] deep) junction boxes.
• Integral LED blinks to indicate normal condition. Illuminates
steady when short circuit condition is detected.
• High noise (EMF/RFI) immunity.

[Link]
• Wide viewing angle of LED.
• SEMS screws with clamping plates for ease of wiring.
• Opens SLC loop automatically on detection of short, pre-
venting the short from causing failure of the entire loop.
• Automatically resets on correction of short.
• Supports Style 4, 6, or 7 wiring.

Applications ISO-X
The Fault Isolator Modules should be spaced between groups
of sensors in a loop to protect the rest of the loop. Use to iso-
late short circuit problems within a section of a loop so that
other sections can continue to operate normally. The ISO-X
Construction
supports a maximum of 25 devices in-between isolators, The face plate is made of off-white plastic. Includes yellow
except when using relay bases or IPX multisensors. LED indicator that pulses when normal and illuminates steady
NOTE: ON LOADS PER RELAY BASE AND MULTI-SENSOR when a short is detected.
DETECTORS/ISOLATORS/ISOLATOR BASES: the maximum
number of addressable devices between isolators (or B224BI iso- Operation
lator bases) is 25 devices.
Automatically opens circuit when the line voltage drops below
four volts. Fault Isolator Modules should be spaced between
groups of addressable devices (maximum 25, see notes on
page 1) in a loop to protect the rest of the loop. If a short
occurs between any two isolators, then both isolators immedi-
[Link]
ately switch to an open circuit state and isolate the groups of
sensors between them. The remaining units on the loop con-
B224RB relay bases and IPX-751 multisensor detectors draw tinue to fully operate.
more current than all other intelligent devices. When calculat-
ing the 25-device maximum: In Style 4 loops, the ISO-X is generally used at each T-tap
branch, to limit the effect of short circuits on a branch to the
• B224RB represents 2.5 devices. devices on that branch. The LED indicator is on continuously
• IPX-751 in a standard base represents 12 devices. during a short circuit condition.
• IPX-751 in a relay base represents 14.5 devices. The ISO-X Fault Isolator Module automatically restores the
• All other addressable devices represent 1 device. shorted portion of the communications loop to normal condi-
See examples on page 2. tion when the short circuit condition is removed.

NOTE: ON MAXIMUM NUMBER OF DEVICES: See the SLC


Manual (p/n 51253) for information on loss of addresses due to
Installation
current limitations. Each module or base added reduces the • Mount on a standard 4" (10.16 cm) mounting junction box
capacity of address positions in an SLC. All SLC field devices must which is at least 2.125" (5.398 cm) deep.
have been purchased after February 1995 to meet the aforemen-
tioned requirements. If the SLC field devices were purchased prior • Terminal screws are provided for “in and out” wiring.
to February 1995, each ISO-X used reduces the capacity of an • Installation instructions are provided with each module.
SLC by two address positions. Requirements differ as applied to • Surface-mount box is available as an option.
relay bases (see note above).

DN-2243:A • 4/8/08 — Page 1 of 2


Specifications • US Coast Guard: 161.002/23/2(AFP-200); 161.002/27/3
(AFP-1010, AM-2020); 161.002/42/1(NFS-640)
Operating voltage: 15 – 32 VDC (peak).
Current range: 5 mA for LED latched in alarm. .Architectual/Engineering
Standby current: 400 μA maximum, plus supervision cur- Specifications
rent.
Fault Isolator Modules shall be provided to automatically iso-
Pulsing current: 30 mA for 15 mS (CMX-1, CMX-2, FCM-1). late wire-to-wire short circuits on an SLC loop. The Fault Isola-
Temperature range: 32°F to 120°F (0°C to 49°C). tor Module shall limit the number of modules or detectors that
may be rendered inoperative by a short circuit fault on the SLC
Relative humidity: 10% to 93%. Loop. If a wire-to-wire short occurs, the Fault Isolator Module
Weight: 150 grams (5 oz.). shall automatically open-circuit (disconnect) the SLC loop.
When the short circuit condition is corrected, the Fault Isolator
Agency Listings and Approvals Module shall automatically reconnect the isolated section of
the SLC loop. The Fault Isolator Module shall not require any
In some cases, certain modules may not be listed by certain address-setting, and its operations shall be totally automatic. It
approval agencies, or listing may be in process. Consult fac- shall not be necessary to replace or reset an Fault Isolator
tory for latest listing status. Module after its normal operation. The Fault Isolator Module
• UL: S635 (UOXX); BP6480 (AMCX, APOU) shall mount in a standard 4.0" (10.16 cm) deep electrical box,
in a surface-mounted backbox, or in the Fire Alarm Control
• ULC: S635 (OUOXXC, ISO-XA)
Panel. It shall provide a single LED which shall flash to indi-
• FM Approved cate that the Isolator is operational and shall illuminate steadily
• CSFM: 7165-0028:141; 7165-0028:164; 7165-0028:181; to indicate that a short circuit condition has been detected and
7165-0028:214; 7165-0028:224; 7170-0028:153; isolated.
7170-0028:182; 7165-0028:195; 7170-0028:216;
7170-0028:223; 7165-0028:243; 7170-0028:244 Product Line Information
• MEA: 17-96-E; 104-93-E Vol. VI; 290-91-E Vol. V; 317-01-
ISO-X: Isolator Module.
E; 447-99-E
• Lloyd’s Register: 94/60004 (E2); 93/60140 (E2) ISO-XA: Isolator Module. Canadian (ULC) version.
• BSA: 578-81-SA SMB500: Surface Mount Backbox

Examples of Device Counts


(see notes under Applications)
[Link]

Example 1

[Link]
Example 2
[Link]

Example 3

NOTIFIER® is a registered trademark of Honeywell International Inc.


©2008 by Honeywell International Inc. All rights reserved. Unauthorized use
of this document is strictly prohibited.

This document is not intended to be used for installation purposes.


We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
All specifications are subject to change without notice.
Made in the U.S. A.
For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118.
[Link]

Page 2 of 2 — DN-2243:A • 4/8/08


System Components
UL EX-4510 9-1-10 Page 1-2
REV. 3

Agent Tank Shipping Assembly

The agent tank assemblies are manufactured in accor-


dance with DOT 4BW450 and consist of a tank fitted with a
valve and internal siphon tube. Eight partial filled tank sizes
are available. A nameplate is adhered to the tank displaying
the agent weight and gross weight. Tanks are superpressur-
ized with dry nitrogen to 360 psi (25 bar) at 70 °F (21 °C).
All tanks are available in multiple fill increments.
Note: Quantity of agent will have to be specified on cus-
tomer P.O. when ordering factory filled tank shipping
assemblies.
Also, when low pressure switch and liquid level indicator
installed options are required, they must be specified when A

ordering.

Component Material Approvals


Tank Steel DOT4BW450
Valve Brass
Valve/Tank Assembly UL Listed 006901
ULC Listed
FM Approved

Shipping Nominal Agent Approximate Dimension Equivalent


Assembly Tank Size Quantity Empty Weight “A” Diameter Valve Length
Part No./TC lb (kg) lb (kg) lb (kg) in. (cm) in. (cm) Size ft (m)
570635 20 9 to 21 33 12 10 1 in. 20
(9.1) (4.1 to 9.5) (15) (30.4) (25.4) (6.096)
570633 50 18 to 42 41 19.8 10 1 in. 20
(22.7) (8.2 to 19.1) (18.6) (50.2) (25.4) (6.096)
570634 90 36 to 84 57.5 32.8 10 1 in. 20
(40.8) (16.3 to 38.1) (26) (83.3) (25.4) (6.096)
570638 140 58 to 137 108 23.5 16 2 in. 35
(63.5) (26 to 62.1) (49) (59.6) (40.6) (10.668)
570639/570651 280 117 to 280 158 40.2 16 2 in. 35
(127) (53.1 to 127) (71.7) (102) (40.6) (10.668)
570640/570652 390 163 to 388 198 53.3 16 2 in. 35
(177) (73.9 to 176) (90) (135) (40.6) (10.668)
570641/570653 450 199 to 459 233 64.3 16 2 in. 35
(204) (90.3 to 204) (106) (163) (40.6) (10.668)
570586/570654 850 379 to 851 456 57.7 24 3 in. 85
(386) (172 to 386) (207) (146.6) (61) (25.91)

TYCO FIRE SUPPRESSION & BUILDING PRODUCTS Copyright ©2010 Tyco Fire Suppression & Building Products
ONE STANTON STREET All rights reserved.
MARINETTE, WI 54143-2542 715-735-7411 Form No. F-2003184-3
ANSUL ®
System Components
UL EX-4510 12-1-03 Page 1-1

3M™ Novec™ 1230 Fire Protection Fluid

Novec 1230 fluid has been developed as a halon replace-


ment alternative to HFCs, HCFCs, and PFCs in special
hazard, high value applications. It has unique qualities that
provide the right balance of fire extinguishing performance,
end use safety, and environmental sustainability. Novec
1230 fluid is low in toxicity and environment impact. It is a
liquid at room temperature, with a low vapor pressure,
which allows for ease in handling, storage, and shipping.
Novec 1230 fluid is available in two sizes of containers:
Part No. 570533 – 30 gallon (113.6 L) Drum Shipping
Assembly
Part No. 570534 – 220 gallon (832.8 L) Tote Shipping
Assembly

ANSUL and SAPPHIRE are trademarks of Ansul Incorporated or its affiliates.

ANSUL INCORPORATED, ONE STANTON STREET, MARINETTE, WI 54143-2542 715-735-7411 Form No. F-2003183 © 2003 Ansul Incorporated Litho in U.S.A.
ANSUL ®
System Components
UL EX-4510 12-1-03 Page 1-7

Mounting Bracket Assembly

The mounting bracket assembly consists of a nut, bolt, and


two bracket straps (back channel must be supplied by oth-
ers). Approved type of Unistrut Channel is series P1000T,
1.6 in. x 1.6 in. (41 mm x 41 mm).
Each strap is notched for insertion into the channel, allow- A

ing the tank to be properly aligned. The bracket assembly is


designed to be mounted to a rigid vertical surface with the
tank assembly resting fully on the floor or vertical surface.
A single bracket assembly is required for 20, 50, 90, 140,
280, 390, and 450 lb. tank sizes. Two bracket assemblies
are required for the 850 lb. size tank.

Component Material Approvals 006759

Mounting Bracket Steel UL Listed


ULC Listed
FM Approved

Shipping “A”
Assembly Dimension
Part No. Description in. (cm)
570085 Bracket Assembly for 15.7 (40)
20, 50, and 90 lb. tanks
(10 in. diameter)
570092 Bracket Assembly for 23.6 (60)
140, 280, 390, and
450 lb. tanks
(16 in. diameter)
570336 Bracket Assembly for 27.3 (69)
850 lb. tank
(24 in. diameter)

ANSUL and SAPPHIRE are trademarks of Ansul Incorporated or its affiliates.

ANSUL INCORPORATED, ONE STANTON STREET, MARINETTE, WI 54143-2542 715-735-7411 Form No. F-2003189 © 2003 Ansul Incorporated Litho in U.S.A.
ANSUL ®
System Components
UL EX-4510 12-1-03 Page 1-19

Liquid Level Indicator

The liquid level indicator is used to measure the level of liq-


uid Novec™ 1230 agent in the tanks. The amount (weight)
of agent is determined by converting the level measure-
ment into a weight measurement using the weight conver-
sion tables located in this manual.
The liquid level is found by lifting the measuring tape from
inside the tube to the end (or approximately 3 in. above the
anticipated liquid level) and slowly lowering the tape until a
magnetic interlock with the float is felt. The tape will then
remain in the up position, allowing a reading at the top of
the housing. This measurement is accomplished without
removing the tank from the fire suppression system.
The indicator can be installed in empty tanks with the prop-
er port or tanks can be ordered with the indicator already
installed.

Component Material Approvals


Liquid Level Body: Brass UL Listed
Indicator ULC Listed
Tape: Steel FM Approved

006255

Shipping Assembly
Part No. Description
570277 Liquid Level Indicator for
280 lb. Tank
570278 Liquid Level Indicator for
390 and 850 lb. Tanks
570589 Liquid Level Indicator for
450 lb. Tank

ANSUL and SAPPHIRE are trademarks of Ansul Incorporated or its affiliates.

ANSUL INCORPORATED, ONE STANTON STREET, MARINETTE, WI 54143-2542 715-735-7411 Form No. F-2003203 © 2003 Ansul Incorporated Litho in U.S.A.
ANSUL ®
System Components
UL EX-4510 12-1-03 Page 1-10

3 In. Discharge Hose/


Check Valve Assembly

The 3 in. discharge hose/check valve assembly combines 3 IN. NPT


the elbow, hose, check valve, and swivel coupling for con-
nection to the valve discharge outlet and the discharge CHECK VALVE
manifold. The check valve provides a 1 1/2 in. (3.8 cm)
height adjustment.

Component Material Approvals APPROX.


27 1/2 IN.
3 in. Discharge Hose: Double Braided UL Listed (69.9 cm)
Hose/Check Stainless Steel ULC Listed
Valve Elbow: Stainless Steel FM Approved
Valve Swivel Nut:
Stainless Steel
Check Valve Body:
Cadmium Plated 3 IN. FLARED
SWIVEL
Mild Steel
Check Valve Seal
and Seat: Brass 006247

Spring: 8 1/2 IN.


Stainless Steel (21.6 cm)

Shipping Assembly
Part No. Description
69841 3 in. Discharge Hose/
Check Valve Assembly

ANSUL and SAPPHIRE are trademarks of Ansul Incorporated or its affiliates.

ANSUL INCORPORATED, ONE STANTON STREET, MARINETTE, WI 54143-2542 715-735-7411 Form No. F-2003191 © 2003 Ansul Incorporated Litho in U.S.A.
ANSUL ®
System Components
UL EX-4510 12-1-03 Page 1-9

Manifold Check Valves

The manifold check valve is designed to prevent a loss of


agent during a discharge in the event that a tank has been
removed from the system. The check valve is a “mushroom”
type, which lifts into the manifold as discharge occurs.
Two sizes of manifold check valves are available: 1 in. and
2 in.
Manifold are constructed of standard Schedule 40 pipe and
300 lb. fittings. The check valves assemble directly into the
fittings.

Thread
Component Material Type Approvals
Check Body: 1 in. NPT UL Listed 006889
Valve Brass and ULC Listed
Stem and 2 in. NPT FM Approved
Seal:
Stainless
Steel

Shipping Assembly
Part No. Description
570566 1 in. Manifold Check Valve
570568 2 in. Manifold Check Valve

ANSUL and SAPPHIRE are trademarks of Ansul Incorporated or its affiliates.

ANSUL INCORPORATED, ONE STANTON STREET, MARINETTE, WI 54143-2542 715-735-7411 Form No. F-2003192 © 2003 Ansul Incorporated Litho in U.S.A.
ANSUL ®
System Components
UL EX-4510 12-1-03 Page 1-4

Electric Actuator – 24 VDC

The 24 VDC electric actuator is required to electrically actu- 1 IN. BSP


ate the tank valve. An electric signal is required from the
AUTOPULSE Control panel which operates the solenoid in
the actuator. This causes the actuator to open the tank
valve and discharge the agent. On multiple tank systems,
only one actuator is required, on the master valve. The
remaining tanks will be actuated pneumatically through
1/4 in. stainless steel hose and a pneumatic actuator
installed on the top of each tank valve.
The actuator draw is 0.2A.
Note: Composite cap attached to actuator is used as the
3.3 IN.
reset tool. To reset actuator, put cap in place and turn (85 mm)

knurled swivel coupling until cap threads are completely


engaged. A small “click” will be heard while resetting. 006763

Thread
Component Material Type Approvals
Electric Body: Steel 1 in. UL Listed
Actuator Swivel Nut: BSPP ULC Listed
Brass FM Approved
Actuation Pin:
1.8 IN.
Stainless (45 mm)
Steel

Shipping Assembly
Part No. Description
570537 Electric Actuator

ANSUL and SAPPHIRE are trademarks of Ansul Incorporated or its affiliates.

ANSUL INCORPORATED, ONE STANTON STREET, MARINETTE, WI 54143-2542 715-735-7411 Form No. F-2003186 © 2003 Ansul Incorporated Litho in U.S.A.
System Components
UL EX-4510 12-1-03 Page 1-13

Local Manual Actuator

The local manual actuator is used to mechanically operate


the tank. To prevent accidental actuation, the actuator con- STRIKE
BUTTON
tains a steel safety pin. The pin must be removed to operate
the actuator. The actuator is operated by depressing the
strike button.
SAFETY
The actuator can be mounted either on the top port of the PIN

tank valve or on top of the electric solenoid valve.

Component Material Approvals


Local Manual Body: Brass UL Listed
Actuator ULC Listed
Safety Pin: Steel FM Approved
Actuation Pin:
Stainless Steel
006890

Shipping Assembly
Part No. Description
570549 Local Manual Actuator

ANSUL and SAPPHIRE are trademarks of Ansul Incorporated or its affiliates.

ANSUL INCORPORATED, MARINETTE, WI 54143-2542 715-735-7411 Form No. F-2003195 Copyright © 2008 Ansul Incorporated
ANSUL ®
System Components
UL EX-4510 12-1-03 Page 1-12

Pneumatic Actuator

The pneumatic actuator is required to pneumatically actu- 1/4 IN. NPT


ate the agent tanks. The actuator operates from pressure
received from the nitrogen cartridge located in the ANSUL
AUTOMAN II-C release. When the pneumatic actuator is
pressurized, the internal actuator piston pushes down on
the valve stem, opening the tank valve, allowing the agent
to discharge.

Component Material Approvals


Pneumatic Brass UL Listed
Actuator ULC Listed
FM Approved

006764
Shipping Assembly
Part No. Description
570550 Pneumatic Actuator

ANSUL and SAPPHIRE are trademarks of Ansul Incorporated or its affiliates.

ANSUL INCORPORATED, ONE STANTON STREET, MARINETTE, WI 54143-2542 715-735-7411 Form No. F-2003194 © 2003 Ansul Incorporated Litho in U.S.A.
System Components
UL EX-4510 4-1-05 Page 1-20
REV. 1

Actuation Line Components

1/4 in. Actuation Hose Male Actuation Tee – Part No. 31811
The 1/4 in. stainless steel actuation hose is used to connect The male actuation tee is used to connect multiple actua-
the 1/4 in. actuation line to the pneumatic actuator located tion hoses together. The actuation tee has a 7/16-20 thread
on the tank valve. The hose is used when the actuation line for connecting to the female actuation hose and a NPT
is rigid 1/4 in. pipe and fittings. The hose has a 1/4 in. NPT thread for connecting to the pneumatic actuator on the tank
male thread on one end and a 7/16-20 female thread on the valve.
other end. A male straight adaptor, Part No. 32338, is 7/16 – 20
required with this hose. Three lengths of hoses are
available.
SEE CHART

1/4 IN. NPT

000435
000432
Part No.
______ Description
_________
73597 16 in. (40.6 cm) Hose Male Actuation Elbow – Part No. 31810
415142 32 in. (81.3 cm) Hose The male actuation elbow is used to connect the actuation
430815 42 in. (106.7 cm) Hose hose to a single or last tank in a multiple tank system. The
elbow connects between the hose and the pneumatic actu-
1/4 in. Female Actuation Hose – Part No. 32336 ator on the valve. The elbow has a 7/16-20 thread for con-
The 1/4 in. stainless steel, female actuation hose is used to necting to the hose and a 1/4 in. NPT thread for connecting
connect the actuation line compression tees between each to the pneumatic actuator on the tank valve.
agent tank. The hose has the same thread, 7/16-20, as the
7/16 – 20
compression tees.
24 IN.
(61 cm)

1/4 IN. NPT

000433
000436

Male Actuation Connector – Part No. 32338 Male Adaptor – Part No. 570342
The male connector is used to connect the 1/4 in. female The male adaptor is required to attach the 1/4 in. actuation
actuation hose to rigid 1/4 in. actuation fittings and also the hose to the master tank pilot port. When using the male
pneumatic actuator. The connector has a 7/16-20 thread for adaptor on the master tank pilot port, a 1/4 in. pipe coupling
connecting to the actuation hose and a 1/4 in. NPT thread must be used between the adaptor and the male hose
for connecting to the actuation piping and pneumatic thread.
actuator.
1/4 – 18 NPT
1/4 IN. MALE 1/4 IN.
BSP MALE NPT

004820

000434
7/16 – 20

ANSUL and SAPPHIRE are trademarks of Ansul Incorporated or its affiliates.

ANSUL INCORPORATED, MARINETTE, WI 54143-2542 715-735-7411 Form No. F-2003200-1 Copyright © 2008 Ansul Incorporated
ANSUL ®
System Components
UL EX-4510 12-1-03 Page 1-15

Low Pressure Switch

The low pressure switch is used to indicate a pressure drop


within the SAPPHIRE tank. The switch is factory mounted
(must be specified when ordering tank) in the 1/8 in. switch
port of the tank valve. The switch continuously monitors the
tank pressure and in the event of the pressure dropping 000716

below 290 psi (20 bar), the switch operates, enabling the
condition to be signaled at the control panel.
The low pressure switch is optional and must be ordered
separately when ordering the SAPPHIRE tank.

Shipping Assembly
Part No. Description
570585 Low Pressure Switch

Switch Electrical
Component Material Point/Type Rating Approvals
Low Pressure Hermetically Sealed Opens on fall at Maximum Current: UL Listed
Switch Stainless Steel Body 290 psi +/- 10 psi 2.9A ULC Listed
(20 bar +/- .7 bar) Voltage Range: FM Approved
5-28 VDC
6 ft. (1.8 m) Wire Leads Closes on rise at
350 psi +/- 10 psi
(24 bar +/- .7 bar)

ANSUL and SAPPHIRE are trademarks of Ansul Incorporated or its affiliates.

ANSUL INCORPORATED, ONE STANTON STREET, MARINETTE, WI 54143-2542 715-735-7411 Form No. F-2003197 © 2003 Ansul Incorporated Litho in U.S.A.
System Components
UL EX-4986 4-1-10 Page 2-16

FM-200® SYSTEMS Pressure Switch – DPST

The pressure switch is operated by the FM-200 ® agent 3 5/8 IN.


2 7/8 IN.
(9.2 cm)
pressure when the system is discharged. The pressure (7.3 cm)

switch can be used to open or close electrical circuits to


either shut down equipment or turn on lights or alarms. The
double pole, single throw (DPST) pressure switch is con-
structed with a gasketed, water-tight housing. The housing
is constructed of malleable iron. A 1/4 in. NPT pressure inlet
4 9/16 IN.
is used to connect the pressure switch from the FM-200 (12 cm)
system.
The pressure switch can be installed either in the distribu-
tion piping or between the master tank and slave tanks on
004593
the actuation line.
Minimum operating pressure is 50 psi (3.5 bar).
000716

Shipping Assembly
Part No. Description
46250 Pressure Switch – DPST

Thread Electrical
Component Material Size/Type Rating Approvals
Pressure Switch Switch: BAKELITE Conduit Inlet: 2 HP – 240 UL Listed
DPST 3/4 in. NPT Female VAC/480 VAC ULC Listed
Housing: Malleable Iron Pressure Inlet: 2 HP – 250 VDC FM Approved
Piston: Brass 1/4 in. NPT Female 30A – 250V AC/DC
Cover: Brass 5A – 480V AC/DC

PYRO-CHEM is a trademark of Tyco Fire Suppression & Building Products or its affiliates. PC2009037
System Components
UL EX-4510 12-1-03 Page 1-17

Warning Signs

Two warning signs are available for warning personnel that


the space is protected by a SAPPHIRE system and no one
should enter after a discharge without being properly pro-
tected. Each sign is made of aluminum and contains four
WARNING
mounting holes for ease of installation. THIS SPACE IS PROTECTED BY A SAPPHIRE™
FIRE SUPPRESSION SYSTEM

Component Material Approvals WHEN SYSTEM IS DISCHARGED AS A RESULT


OF FIRE, CAUTION MUST BE TAKEN TO AVOID
Warning Sign Aluminum UL Listed EXPOSURE TO PRODUCTS OF COMBUSTION.
ULC Listed
FM Approved DO NOT ENTER WITHOUT APPROVED SELF-
CONTAINED BREATHING APPARATUS OR
UNTIL AREA IS PROPERLY VENTILATED.

Shipping Assembly
Part No. Description
570580 Warning Sign
570581 Agent Discharge Warning Sign LABEL NO. 570580

006894

WHEN ALARM SOUNDS


VACATE AT ONCE
™ ™

3M NOVEC 1230 FIRE


PROTECTION FLUID
BEING RELEASED

LABEL NO. 570581

006895

ANSUL and SAPPHIRE are trademarks of Ansul Incorporated or its affiliates.

ANSUL INCORPORATED, MARINETTE, WI 54143-2542 715-735-7411 Form No. F-2003199 Copyright © 2008 Ansul Incorporated
ANSUL 
Detection and Control Components

AutoPulse Key Maintenance Switch

Features TYPICAL WIRING DIAGRAM


• Stackable, screw-terminal, contact blocks KEY-OPERATED CONTROL UNIT
LOCK-OUT SWITCH RELEASE CIRCUIT
• Compatible with AUTOPULSE® control units 24 VDC
ACTUATOR
TERMINALS*

• Surface-mount assemblies listed by Underwriters N.C.


(–)
Laboratories, Inc.
N.O.
• Components mounted on stainless steel switch plate (+)

Applications POLARITY IS
SHOWN
The Key Maintenance Switch is used to interrupt the release IN ALARM
24 VDC POWER CONDITION
circuit signal to the fire suppression system. It is key-operat- SOURCE
ed to allow authorized personnel to deactivate the release
circuit during service or maintenance. An indicator lamp, 24 VDC
INDICATOR LAMP
located on the switch plate, will light when the switch is in the
* SEE CONTROL UNIT MANUAL FOR SPECIFIC WIRING REQUIREMENTS.
“lock-out” mode to serve as a reminder that the release cir-
cuit has been disconnected.

Description Ordering Information


The Key Maintenance Switch assembly consists of a key- Shipping
operated switch, 24 VDC indicator lamp, normally-open con- Weight
tact block, normally-closed contact block, and stainless steel Part No. Description lb. (kg)
switch plate with silk-screened label. Surface-mount assem-
blies include a double-gang weather-proof box and gasket. 76498 Maintenance Switch, Surface-Mount 2.0 (0.9)
The stackable, screw-terminal contact blocks are rated for 28 76499 Maintenance Switch, Flush-Mount 2.0 (0.9)
VDC @ 1.1 amp make/break or 6 amp continuous carry. 76485 Extra Contact Block, N.C. 0.25 (0.11)
Listings and Approvals 76486 Extra Contact Block, N.O. 0.25 (0.11)
The switch is UL listed when installed in the surface-mount 78179 Spare Key 0.25 (0.11)
box (with gasket) that is provided with the surface-mount 470273 Extender-Back Box 0.25 (0.11)
assembly.

MOUNTING DIMENSIONS
SURFACE-MOUNT FLUSH-MOUNT
4 11/16 IN. 3 1/8 IN. 2 3/4 IN.
(119 mm) (79 mm) (70 mm)

NORMAL
LOCK-OUT

4 5/8 IN.
(117 mm)

ANSUL
FIRE SUPPRESSION SYSTEM ABORT

ANSUL and AUTOPULSE are trademarks of Ansul Incorporated or its affiliates.

3-33

ANSUL INCORPORATED, ONE STANTON STREET, MARINETTE, WI 54143-2542 715-735-7411 Form No. F-95110-1 2003 Ansul Incorporated Litho in U.S.A.
ANSUL ®
System Components
UL EX-4510 12-1-03 Page 1-11

Discharge Nozzles

The discharge nozzles are available in a 180° and 360° pat-


tern and are designed to uniformly distribute the Novec™
1230 agent throughout the hazard area.
The 180° nozzle has seven ports and the 360° nozzle has
sixteen ports. Six sizes of nozzles are available, 1/2 through
2 in.
The hydraulic flow program will determine the nozzle size
and orifice size required.
004824
Note: When ordering nozzles, orifice size must be speci-
fied when ordered.

Component Material Threads Approvals


1/2 in. Nozzle Brass 1/2 in. NPT UL Listed
3/4 in. Nozzle 3/4 in. NPT ULC Listed
1 in. Nozzle 1 in. NPT FM Approved
1 1/4 in. Nozzle 1 1/4 in. NPT
1 1/2 in. Nozzle 1 1/2 in. NPT
2 in. Nozzle 2 in. NPT
004823

Shipping Assembly
Part No. Description
570515 1/2 in Nozzle – 180°
570516 3/4 in. Nozzle – 180°
570517 1 in. Nozzle – 180°
004840
570518 1 1/4 in. Nozzle – 180° 180° NOZZLE 360° NOZZLE
PATTERN PATTERN
570519 1 1/2 in. Nozzle – 180°
570520 2 in. Nozzle – 180°
570602 1/2 in. Nozzle – 360°
570603 3/4 in. Nozzle – 360°
570604 1 in. Nozzle – 360°
570605 1 1/4 in. Nozzle – 360°
570606 1 1/2 in. Nozzle – 360°
570607 2 in. Nozzle – 360°

ANSUL and SAPPHIRE are trademarks of Ansul Incorporated or its affiliates.

ANSUL INCORPORATED, ONE STANTON STREET, MARINETTE, WI 54143-2542 715-735-7411 Form No. F-2003193 © 2003 Ansul Incorporated Litho in U.S.A.
() () () ()
.
()
()

-4: "
>"Ic-
>> ." -4:-'" -....-
.~

~I I I§-4:
-
J> J>

< -< ~
;:~
.... ....
. -< ....
- -
~

- J>
J>
~

~ "
"
()

> >> > > >>> >>>

~
-' > " -' ~::1-,~
-' J>
<" <-'-' -'-'
J> () J> J>
< .... <
-4:
-'
.... . -" -....
-"
-<

-4:-'
, <
~

.
.~

-'
~

.
-<

- < -4: -'


~
• l',.,
-'
J>
-
J>
< < J> -" < <
-<
-4: ....< "" () C

>>>>>>>>>>>
-A.,z~~,.6:>,..A>J;I-«,..[Link]\"

~::::~~~~~:;5::£
• .~ _ < ­ J ~ _ ~ ~ ~ ~
r > > > > > > > > > > > > > >.> > > >
o .-If .,..b J>

:;~~~~:<;:~o~~~-;;:::rl-;;£
o > ~ 1 ~ > -A .-If 0
~ "J ...". -A

< _ ~ . - ,~ .. -
"s -A 0 .,J ,... J> .,..0. ...... ~ -­
r
r'41 t..
-4:-[Link].-t. .. o ..... < .. ~\ < > .. 0 ~ _ -'4. .....c: .-b < ~ _ 0 ..... ..~, -
.-..,z. c, -<>L -"--" .... ". '-'J>"J><-_ -,,<--<L Ii=:
~
t' .f
t
[.
,<;;
L
1::
.i,C

>
F -< L
f
~ ~

-I ~
-=< (;:

..?£
-<

~ ~<~ --< -"


:;-->'0 -' -
...
~
- -< -'~ --<
t.... . L .....no
~ -" t'
-,.
'-.
l' .-. ---~
no
---·lo·t.
£:
b-
,~
_

~:t ~~. ~Yo :~ <e.~ ~• ~f ~f r It- 1.~ . : ~~ t."= t."= it ~.~ 1.?~- ~t ;F~,{~ "'~,,-: F
-< ---

l
il:

fu·~ - ~;
~. \.- f ~ Efu "= ~ t· ~. .~. t·I'!:.'
i

'\; 1- ,~ '~~ "


V·I: ~- ~ ~ . '.c,~ 1- - ,. f '~, f:; ;., fu
E~' t-:
-c r
t ' ~.
,
~
~ -.. -. .t" t' ,t"-;-".-e...
~_ . ~ ~ _~
c- !;.'.:..-ot:' • • -,
\,;.-~~~~~~~~~~~~~f~~-
-'.:..~'~.~ '~-e... 'f
~
r " f - ,t' ,t' ~' r r '~
~ ~t ., . , ~. r ~ l t ~ li 1: r:t: cr· r:f> ,tl":~ l":~ r[: l-~, [~ r . £ ~,.
,. - ~. f,. '&- ~ ,;-". . • ~ f:.' •
~ ~
L. \I:

.t - -t' ~,. 1:' ,t'


h
.[
~ ~.~ ,r ~ ~ -11­ \1:', - - • 'If.
~ t ~. £tit ~ .~ t Ii=: '&- 'S; ~ t t t ~ t .~~, t t t i 'E ~ ~ ~.
t - .f - t ·~t ~;
r
0'
- '\;
c-

r
0'

t'
t
[. t'
'f.
t'
r f
r:,
tt:
~
- ,~, t'
--.
IS'"
'~ ~- t' ~
L

-­ t
§~fr
0' t
r ;j L c,t' r:~ ...,t: _ 'l-!-t' r ~,
[,

~_ r. [ rf f
---- r;,..
/:' ,t'
, ~,~, -',.r;; ,t' - t, [,- i
L '-'
,t' ,t ,f. f .t' .r;;
~ ... ,(;, c !:= t' t ... y. ... - ~ c ~
,--'
~
r- >., [- [
' - c 1I
0'
'f> _
[Link]'t~ ~C> 'tIi" ~~'1'['~ ~ r t ~, ~'t ,~..~ i ~ ~ r- ~
[,c 'v> ' .. L

~ 1:=: 'r. ,I;. .1:." -[ L. n '1:: !:=
-'<;; c
;-.' '&- ~ - - /: ~ -e. I" \r. - ~,c. ~ ~,c
,I;.

- '1 ,. - 'e: t - 'I). !E:. .. t"<;; t.. ~ l ~ "'-: ~ [, . r;,.. ~ g 't: &' .)., ("' -:- '~I

&. '~ .& ~ f' ~. ~. 'f= ~ [: ~ t ~ ~ ~,- ~ ~ ~- ~ t 1, -= ~. ~ ~. ~ ti


[ r t

~: f' 't-:: 1\Z 1:'- .~ k,f n 1.r (...f ~:t.'1~.


'f,.
f; [ ~'~, t .~ '& .~' t' r.[ t l;' ~: . ~- ~ f' f:' ~. l

~'t f' -'!f. t;' t;' t .~: '[ \,; r, ( .- 1:,'\ 't' f t' ~. ,t'
.1-' R
t~. 'J;'~ t: ,r.L.
f f' t;' f' 't" G; f'~' (
't.
f' 1,. \.. Q. !f:,- f'. ,:,~ 't.f 't ~t;' I,.t; t'f
f> -- 1. ,I (..
f. 't' f
''t' 'f,. 't' f _ 't ~' ~ 't.
\,. r·' ~ f 't ~ I,. 't'
't
.
t~:~ 1
~ 'f' ~t'
[ 't' 't 't'
t;' ~'
't' f I,·
f.
~'
1,.f
'ct.. t' !; ~
t' I,., I
[, tEo, _
~ - -t-'f:­L
'~~. ['
- I=..~

:1:1-"1>1<1-'1 ()1_1 .... 1-4:1_1~


'f.' ;; t L
\'.,~
­ -
;I;I~I;I~I~I~I:I~I-"I>I<I~I"I-I""I~I-I~
Certificate of Compliance
This certificate is issued for the following:

ALTERNATE FACILITY FOR MANUFACTURING OF


FM-200® AND SAPPHIRE® CLEAN AGENT SYSTEMS

Prepared for: Manufactured at:

Tyco Safety Products Ltd. Reda Fire & Hazard Control Division
Burlington House, Hewett Road 2nd Industrial Area
Gapton Hall Industrial Estate Dammam 31482
Great Yarmouth, Norfolk NR31 0NN Saudi Arabia
United Kingdom

FM Approvals Class: 5612

Approval Identification: 0003037960 Approval Granted: March 8, 2011

Said Approval is subject to satisfactory field performance, continuing follow-up Facilities and Procedures Audits, and strict
conformity to the constructions as shown in the Approval Guide, an online resource of FM Approvals.

For more than 160 years FM Approvals has partnered with business and industry
to reduce property losses.

March 8, 2011

Richard B. Dunne Date


Group Manager -Hydraulics
FM Approvals
1151 Boston-Providence Turnpike
Norwood, MA 02062
Certificate Number 20110804-EX4510 Page 1 of 2
Report Reference 2011 August 4
Issue Date 2011 August 4

Issued to: Ansul Inc.

1 Stanton St
Marinette, WI 54143

This is to certify that Clean Agent Extinguishing System Units


representative samples of SEE ADDENDUM PAGE 2

®
Have been investigated by Underwriters Laboratories Inc. (UL) or any authorized
licensee of UL in accordance with the Standard(s) indicated on this Certificate.

Standard(s) for Safety: UL 2166, "Halocarbon Clean Agent Extinguishing System Units,"
NFPA 2001, "National Fire Protection Association Standard on Clean Agent Fire
Extinguishing Systems"

Additional Information: See UL On-Line Certification Directory at [Link] for additional information.

Only those products bearing the UL Listing Mark should be considered as being covered by UL's Listing and Follow-
Up Service.

The UL Listing Mark generally includes the following elements: the symbol UL in a circle: with the word “LISTED”; a
control number (may be alphanumeric) assigned by UL; and the product category name (product identifier) as indicated in the
appropriate UL Directory.

Look for the UL Listing Mark on the product

William R. Carney
Director, North American Certification Programs
Underwriters Laboratories Inc.
Any information and documentation involving UL Mark services are provided on behalf of Underwriters Laboratories Inc. (UL) or any authorized licensee of UL
For questions, please contact a local UL Customer Service Representative at [Link]
Certificate Number 20110804-EX4510 Page 2 of 2
Report Reference 2011 August 4
Issue Date 2011 August 4

This is to verify that representative samples of the product as specified on this certificate were tested
according to the current UL requirements.

CLEAN AGENT EXTINGUISHING SYSTEM UNITS, ENGINEERED TYPE


in the following Models, when initial agent filling is completed at Reda Fire and Hazard Control, 2nd
Industrial Area, Damman 31482 Saudia Arabia:

Hygood Models 16926, 9180, 9190, 9200, 14692, 9210, 14693, 14694, 9220, 9230, 9240 and 14798,
containing FM-200 (HFC-227ea) clean agent.

Fireater Models 16946, 9180, 9190, 9200, 14692, 9210, 14693, 14694, 9220, 9230, 9240 and 14798,
containing FM-200 (HFC-227ea) clean agent.

Ansul Sapphire Models 570635, 570633, 570634, 570638, 570639, 570640, 570641, and 570586,
containing NovecTM 1230 Fire Protection Fluid (FK-5-1-12) clean agent.

William R. Carney
Director, North American Certification Programs
Underwriters Laboratories Inc.
Any information and documentation involving UL Mark services are provided on behalf of Underwriters Laboratories Inc. (UL) or any authorized licensee of UL
For questions, please contact a local UL Customer Service Representative at [Link]

You might also like