The document is an installation and user manual for the Kappa System, which is designed for elevator management. It includes detailed descriptions of the system components, installation procedures, safety precautions, and programming instructions. The manual emphasizes the importance of following guidelines to ensure proper operation and safety during installation and use.

Uploaded by

Mahmoud Rob
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
2K views36 pages

DIGI Installation Manual 21E2

The document is an installation and user manual for the Kappa System, which is designed for elevator management. It includes detailed descriptions of the system components, installation procedures, safety precautions, and programming instructions. The manual emphasizes the importance of following guidelines to ensure proper operation and safety during installation and use.

Uploaded by

Mahmoud Rob
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

Gruppo Millepiani S.p.A.

Legal headquarter http://www.gruppomillepiani.it


Corso Europa, 76 - 20020 Solaro MI P.IVA: 02731550121 e-mail:[email protected]
Tel. 02 92274700 – Fax 02 92274701 Cap. Soc. €. 1.000.000,00 Int. Versato
Operational headquarter Iscrizione Reg. Imprese di Milano N° 02731550121
Via De Amicis 20 – 20020 SOLARO MI
02 97388850 Fax 02 97388870-Italy

Kappa SYSTEM
System for elevator management

INSTALLATION/USER MANUAL
Pag 1 of 36
Installation_manual_21D.doc v2.1
Gruppo Millepiani S.p.A.
Legal headquarter http://www.gruppomillepiani.it
Corso Europa, 76 - 20020 Solaro MI P.IVA: 02731550121 e-mail:[email protected]
Tel. 02 92274700 – Fax 02 92274701 Cap. Soc. €. 1.000.000,00 Int. Versato
Operational headquarter Iscrizione Reg. Imprese di Milano N° 02731550121
Via De Amicis 20 – 20020 SOLARO MI
02 97388850 Fax 02 97388870-Italy

Summary

SYSTEM DESCRIPTION…………………………….……………………………………………………………………………………………….3
INTRODUCTION……………………………………………………………………………………………………………………………………….4
PRELIMINARY TESTS ……………………………………………………………………………………………………………………………….5
PUT INTO SERVICE ………………………………………………………………………………………………………………………………….8
ALARM RESET ……………………………………………………………………………………………………………………………………….15
PROGRAMMING MANUAL …………………… ……………………………………………………………………………………………..16

Pag 2 of 36
Installation_manual_21D.doc v2.1
Gruppo Millepiani S.p.A.
Legal headquarter http://www.gruppomillepiani.it
Corso Europa, 76 - 20020 Solaro MI P.IVA: 02731550121 e-mail:[email protected]
Tel. 02 92274700 – Fax 02 92274701 Cap. Soc. €. 1.000.000,00 Int. Versato
Operational headquarter Iscrizione Reg. Imprese di Milano N° 02731550121
Via De Amicis 20 – 20020 SOLARO MI
02 97388850 Fax 02 97388870-Italy

SYSTEM DESCRIPTION

The KAPPA System is composed of the combination between K-CTR controller mother board and
secondary electric boards on car , car operating panel and at each floor , communicating via CAN BUS
protocol.

Electronic boards are :

1. K-CTR Controller mother board. It’s the main board ,located into controller.
2. K-CAR Auxiliary car roof board, acquirse signals of car travelling,door operators etc , located in a
box on car top.
3. K-COP Car operating panel interface board, located beside car operating panel.
4. K-EPB Floor board,collects floor calls,floor signals etc , located into shaft , at each floor .
5. K-LDG Floor board, full collective type collects floor calls,signals etc , located into shaft , at each
floor .
6. K-DSP Proprietary display board , located beside display.
7. K-IO Auxiliary I/O expansion board, general purpose. Location depends on function required.
8. K-ALE Alarm board, emergency battery charger, located into controller.
9. K-SPD Speed control safety system board, located into controller.
10. K-SYS Voice syntethizer board, located beside car operating panel
11. K-ENC Special signals dedicated board , A3 MRL optional board , located into controller or into
shaft.

Note that depending on the options required you may have only some of these boards.

Pag 3 of 36
Installation_manual_21D.doc v2.1
Gruppo Millepiani S.p.A.
Legal headquarter http://www.gruppomillepiani.it
Corso Europa, 76 - 20020 Solaro MI P.IVA: 02731550121 e-mail:[email protected]
Tel. 02 92274700 – Fax 02 92274701 Cap. Soc. €. 1.000.000,00 Int. Versato
Operational headquarter Iscrizione Reg. Imprese di Milano N° 02731550121
Via De Amicis 20 – 20020 SOLARO MI
02 97388850 Fax 02 97388870-Italy

INTRODUCTION

Reading this manual, you’ll be able to put the lift into service performing
some simple operations as described below.
Read carefully all parts of the manual before initiating to commissioning
the lift. This manual is also intended for normally operating the lift. Into
programming section you’ll learn about options and features of the
controller.

After performing electrical connections, check for correct operations


before to switch on electrical power supply , to avoid damages in case of
commissioning errors .

DANGER ! In temporary installation connect safety inspection device as follows ( Fig 1 ) . Be


sure to connect logical low voltage circuits to connector M3 and safety chain circuits to connector
VS1 .

HAZARDOUS VOLTAGE! The lift is equipped with capacitors , so hazardous voltage may
remain 3minutes after the switch off of main power supply. Wait at least for this time before to
service controller .

Pag 4 of 36
Installation_manual_21D.doc v2.1
Gruppo Millepiani S.p.A.
Legal headquarter http://www.gruppomillepiani.it
Corso Europa, 76 - 20020 Solaro MI P.IVA: 02731550121 e-mail:[email protected]
Tel. 02 92274700 – Fax 02 92274701 Cap. Soc. €. 1.000.000,00 Int. Versato
Operational headquarter Iscrizione Reg. Imprese di Milano N° 02731550121
Via De Amicis 20 – 20020 SOLARO MI
02 97388850 Fax 02 97388870-Italy

Preliminary TEST
Provisional operation without car connection :

Referring to installation schematics, connect circuits as follows :

o Terminals “R”, “S”, “T” (Pag. 1) to power supply net. Be sure that power supply is appropriate for the
lift controller ( Nominal voltage, phase number , rated power ) and that power supply cables section
is correct for rated current.
o Motor Supply “U”, “V”, “W” (Pag. 1). Be sure to connect motor phases exactly as into schematics .
Wrong connections may cause uncontrolled movements or big hurts of torque. Serious injury may
occur not respecting this !
o If hydraulic lift connect valvles supply (Pag. 4), motor and thermal protection (Pag. 1)
o If traction lift (Pag. 20) connect brake supply (Pag. 1) and motor thermal protection (Pag. 1)
o Bridge out connection releated to not existing devices (Pag.3)
o Remove wire on connector M3 (wires P 1 e P4- M3) on K-CTR board into controller and connect
inspection box (Fig. 1)

Following verification has now to be performed, before to give any command to the lift:

o Check all supply voltage, Power Supply (Pag. 1), Power supply of K-CTR board (Pag. 2)
o Check that safety circuit led’s on K-CTR board into controller are off. When you give an inspection
command, all leds will be on (SIC 1, 2, 3, 4, 5, 6 – Pag.3)

Pag 5 of 36
Installation_manual_21D.doc v2.1
Gruppo Millepiani S.p.A.
Legal headquarter http://www.gruppomillepiani.it
Corso Europa, 76 - 20020 Solaro MI P.IVA: 02731550121 e-mail:[email protected]
Tel. 02 92274700 – Fax 02 92274701 Cap. Soc. €. 1.000.000,00 Int. Versato
Operational headquarter Iscrizione Reg. Imprese di Milano N° 02731550121
Via De Amicis 20 – 20020 SOLARO MI
02 97388850 Fax 02 97388870-Italy

Fig.1

Magnets positioning on shaft

For magnets positioning on shaft you should refer to schematics on pg. 70/80

HYDRAULIC LIFT – STOPPING LEVEL

Into the picture you can see magnets positioning


on guiderails, be careful that the overlaps between
IU and ID must be at least 4cm.
To reach overlaps use parameters :
“2.03-Rit.stop salita”
“2.04-Rit.stop discesa”
At top and bottom floors , for correct positioning,
Force the lift to leveling , top floor leveling down and
Bottom floor leveling up.
In this way you can check the correct lift stopping.

ROPE LIFT – STOPPING LEVEL

Into the picture you can see magnets positioning


on guiderails, be careful that the overlaps between
IU and ID must be at least 5cm.
To reach overlaps use parameters :
“2.03-Rit.stop salita”
“2.04-Rit.stop discesa”
If the lift is VVVF equipped , the approaching speed
( velocità accostamento ) is significant.

Pag 6 of 36
Installation_manual_21D.doc v2.1
Gruppo Millepiani S.p.A.
Legal headquarter http://www.gruppomillepiani.it
Corso Europa, 76 - 20020 Solaro MI P.IVA: 02731550121 e-mail:[email protected]
Tel. 02 92274700 – Fax 02 92274701 Cap. Soc. €. 1.000.000,00 Int. Versato
Operational headquarter Iscrizione Reg. Imprese di Milano N° 02731550121
Via De Amicis 20 – 20020 SOLARO MI
02 97388850 Fax 02 97388870-Italy

SLOWING MAGNETS POSITIONING ( for hydraulic and ropes lift )


Slowing magnets are located between each floor.

In the picture you can see slowing magnets


positioning , with different cases :
1° - upgoing slowing magnet IU is over the
slowing downgoing magnet ID and
between them the distance is > 5cm
PERMITTED POSITIONING (OK)
2° - upgoing slowing magnet IU is beside the
slowing downgoing magnet ID and
between them the distance is > 5cm
PERMITTED POSITIONING (OK)
3° - The distance between magnets is
< 5cm
NOT PERMITTED POSITIONING (NO!!)
For the height of “slowing distance” refer to schematics on pg 70/80
With digital shaft system, slowing magnets are not required. The slowing distance is calculated with
motor encoder signals ( see digital shaft chapter )

TOP/BOTTOM SYNCRONIZATORS

Into the picture you can see the positioning of round


magnets on guiderails. The round magnets
SD and SU ( top and bottom syncronizators )
are to be fixed on the appropriate clamp.
Round SD and SU magnets are to be
Fixed just about 3 cm after the slowing
Magnet of top and bottom floors.
SD or SU must be reached after the lift has
Reached the slowing megnet ( ID or IU ). This
Is for safety, as if the lift reaches SD or SU
Stillin high speed , immediately a slowing
Command will be given .

SD and SU polarity check


With car positioned between floors ( middle shaft ) , on car top board ( K-CAR ) check that leds SU and SD
are both on.
Going DOWN with car inspection, you should see SD led getting off when you reach SD magnet, and
remain off under SD magnet.
Going UP with car inspection, you should see SU led getting off when you reach SU magnet, and remain off
over SU magnet. If you get in some position into the shaft both SU and SD leds OFF, this will cause an error.

Pag 7 of 36
Installation_manual_21D.doc v2.1
Gruppo Millepiani S.p.A.
Legal headquarter http://www.gruppomillepiani.it
Corso Europa, 76 - 20020 Solaro MI P.IVA: 02731550121 e-mail:[email protected]
Tel. 02 92274700 – Fax 02 92274701 Cap. Soc. €. 1.000.000,00 Int. Versato
Operational headquarter Iscrizione Reg. Imprese di Milano N° 02731550121
Via De Amicis 20 – 20020 SOLARO MI
02 97388850 Fax 02 97388870-Italy

Put into normal service

CAN BUS resistance check to be performed at the end of commisioning , without power supply,
alarm battery disconnected , and all connectors correctly inserted.

With a digital tester positioned on ohm “Ω” ( 200 ohm full scale ) measure between terminals 1 and 2 of
connector SL1 on K-CTR :

• 60Ω = correct value


• 120Ω = one SLC termination missing (SLC bridge)
• 40Ω = too much SLC terminations

Repeat the same measure between terminals 1 and 2 of connector SL2 on K-CTR :

Consider that if the value is not correct, you should check that the first and the last boards connected to
sl1 are with slc closed. If the value is >60 ohm you have one missing enclosure ( at begin or end of sl1 ) ,
if it’s <60 ohm you have too much enclosures. The same as to sl2 line. Some tolerance in values is
permitted , depending also of the instrument used , about 10%.

Operating the lift with incorrect can bus ohmic values may produce errors on can bus line itself or lift
random problems or stops. Ask for technical assistance in case of dubt.

All the electronic boards supplied with lift are programmed and set into factory. All the electronic boards
supplied as spare parts must be checked for setting depending on lift installation.

Pag 8 of 36
Installation_manual_21D.doc v2.1
Gruppo Millepiani S.p.A.
Legal headquarter http://www.gruppomillepiani.it
Corso Europa, 76 - 20020 Solaro MI P.IVA: 02731550121 e-mail:[email protected]
Tel. 02 92274700 – Fax 02 92274701 Cap. Soc. €. 1.000.000,00 Int. Versato
Operational headquarter Iscrizione Reg. Imprese di Milano N° 02731550121
Via De Amicis 20 – 20020 SOLARO MI
02 97388850 Fax 02 97388870-Italy

50. ALARM LIST- Visualizzation


Schema
Alarm Alarm cause Notes-explanations
ref.
Nessun allarme No alarm in memory
At start the input SP on K-CTR
Check the series of NC auxiliary contacts on main contactors
START PERMIT avvio board has not switched OFF. Pag.4:A5
(ORANGE wires), or contactors command circuit.
Terminals Q4/11 - 12 (K-CTR)
At stop the input SP on K-CTR
Check the series of NC auxiliary contacts on main contactors
START PERMIT fermata board has not switched ON. Pag.4:A5
(ORANGE wires), or contactors command circuit.
TerminalsQ4/11 - 12 (K-CTR)
Check:
No communication between K-CTR - Flexible cable to SL1
SL1 interrotto K-CAR and K-CAR boards, Time-Out 5s. - Motor’s cable shield (if Pag.6:D3
Terminals SL1/1 - 2 (K-CTR / K-CAR) VVVF)
- Earth poor connections
Check:
Only for platforms.
- Flexible cable to SL1
No communication between K-CTR
SL1 interrotto K-COP - Motor’s cable shield (if Pag.6:D3
and K-COP boards, Time-Out 5s VVVF)
Terminals SL1/1 - 2 (K-CTR / K-COP)
- Earth poor connections
Inverter fault Use the inverter diagnostic specific keypad to identify the
V3F in blocco Pag.4:H5
Terminal Q6/2 (K-CTR input RDY) inverter error. Check inveter
With “vano digitale” option, encoder data are incorrect:
Check :
Encoder inputs wrong.
- Encoder reply cable and
Dati encoder errati Terminals connections Q3 (K-CTR) Pag. 4
connections Q3 K-CTR
- Parameters 09 VANO
DIGITALE
With VANO DIGITALE shaft system,
The lift will go to reset to adjust the offset. Consider the
Offset max. encoder offset maximum reached for
ropes elongation.
encoder value .
Only for VANO DIGITALE , wrong Only if vano digitale, check parameters “9.09-Taratura livelli”
Errore direz. avvio Pag.70/80
direction at start. : error occurred in automatic floor reading.
Safety leveling module fault Check the safety levelling module ( DZSM ) and the correct
Difetto DZSM Pag. 5:C5
Terminal Q5/9 (K-CTR). behavior magnets IU – ID – IZ
Check:
- Terminals connections of
Magnets count (IU, ID) went
IU/ID
wrong. Pag. 5:D4
Conteggio vano magn. - Magnets positioning on shaft
Terminals MST/1 - 2 (K-CTR) Pag.70/80
or sensors on car top
- Magnets missing
- Magnets in wrong additions
Check for slowing magnets position, with VANO DIGITALE
At stop the lift goes over the stop
Mancanza IU al piano check parameter. “9.10-Taratura rallent.” Pag.70/80
magnets going down.
Check for slowing magnets position, with VANO DIGITALE
At stop the lift goes over the stop
Mancanza ID al piano check parameter. “9.10-Taratura rallent.” Pag.70/80
magnets going up.
Check for slowing magnets position, with VANO DIGITALE
At stop, the floor has been passed
Errore livello piano check parameter. “9.10-Taratura rallent.” Pag.70/80
over.

Pag 9 of 36
Installation_manual_21D.doc v2.1
Gruppo Millepiani S.p.A.
Legal headquarter http://www.gruppomillepiani.it
Corso Europa, 76 - 20020 Solaro MI P.IVA: 02731550121 e-mail:[email protected]
Tel. 02 92274700 – Fax 02 92274701 Cap. Soc. €. 1.000.000,00 Int. Versato
Operational headquarter Iscrizione Reg. Imprese di Milano N° 02731550121
Via De Amicis 20 – 20020 SOLARO MI
02 97388850 Fax 02 97388870-Italy

If hydraulic lift, IZ magnet at floor Check :


missing. - IZ magnets on shaft, Pag. 5:D4
Difetto zona porte
Terminals MST/3 (K-CTR) monostable sensor on car top. Pag.70/80
- IZ sensor faulty
Check:
- Check for value 1.08
sufficient for the application
Tempo corsa High speed travel timeout Pag.4
- Mechanical issues
- Safety chain/valves voltage if
hydraulic
Check:
- Check for value 1.08
sufficient for the application
Tempo bassa velocita Low speed travel timeout Pag.4
- Mechanical issues
- Safety chain/valves voltage if
hydraulic
Check:
- Check for value 1.08
The lift has not leave the floor at sufficient for the application
T. rilascio piano Pag.4/20
start - Mechanical issues
- Safety chain/valves voltage if
hydraulic
Check:
Travel time expired , the lift has not - Mechanical issues
Difetto livellazione Pag.4
completed releveling into 15 s - Safety chain/valves voltage if
hydraulic
When starting opening the controller checks for opening
switch on door operator. If it’s opened from the beginning,
Opening switch on door operator
the alarm is triggered.
faulty
Limite apertura Check for switches on door operator or cable connections. Pag.13/14
Terminals DOPA/1 - 4 (K-CAR)
An opening command is sent for the time written in
Terminals DOPB/1 - 4 (K-CAR)
parameters “3.12-T.Minimo Apertura , to try to open the
door.
Closing switch on door operator When starting closing, the controller checks for closing
faulty. switch on door operator.If it’s opened from the beginning,
Limite chiusura Pag.13/14
Terminals DOPA/2 - 4 (K-CAR) the alarm is triggered.
Terminals DOPB/2 - 4 (K-CAR) Check for switches on door operator or cable connections.
Timeout for opening reached Check:
before to reach opening switch ( - Values into 3.06 side A and
T. max. apertura opened ). 4.06 side B, is enough to completely open the door Pag.13/14
Terminals DOPA/1 - 4 (K-CAR) - Door switch faulty
Terminals DOPB/1 - 4 (K-CAR) - Mechanical issues on door
Check:
Timeout for closing reached before
- Values into 3.06 side A and
to reach closing switch ( opened ). 4.06 side B, is enough to completely close the door
T. max. chiusura Pag.13/14
Terminals DOPA/2 - 4 (K-CAR)
- Door switch faulty
Terminals DOPB/2 - 4 (K-CAR)
- Mechanical issues on door
Check the connections between :
Missing connection between K-CTR
Scheda K-COM assente K-COM and K-CAR if a traditional lift , K-COM and K-COP if Pag.13
and K-COM boards.
platform.
K-COM board connection missing Fermator door operator OFF or faulty. Check power supplì
Fermator spento Pag.13
with Fermator door operator. and connections of door operator.
Check for machine room temperature:value exceeded
Temp. locale macch. Terminals Q7/1 - 3 (K-CTR) Pag.6:A4
(thermostat T5-40)

Pag 10 of 36
Installation_manual_21D.doc v2.1
Gruppo Millepiani S.p.A.
Legal headquarter http://www.gruppomillepiani.it
Corso Europa, 76 - 20020 Solaro MI P.IVA: 02731550121 e-mail:[email protected]
Tel. 02 92274700 – Fax 02 92274701 Cap. Soc. €. 1.000.000,00 Int. Versato
Operational headquarter Iscrizione Reg. Imprese di Milano N° 02731550121
Via De Amicis 20 – 20020 SOLARO MI
02 97388850 Fax 02 97388870-Italy

Temperatura olio Terminals M1/1 - 2 (K-CTR) Check for oil temperature : contact switched ( open ) Pag.1:F5

Pressione olio Terminals M1/3 - 4 (K-CTR) Check for oil pressure : contact switched ( open ) Pag.1:F5
Check for motor temperature ( thermistor )
Termico motore Terminals M1/5 - 6 (K-CTR) Pag.1:G5
Check parameter “2.02-Soglia termistore”
After 60s of continued closed switch, the pushbutton is
Pag.10:D2
Puls. UPB bloccato Landing up call button locked deleted, flashing the red light. If it opens, the function is re-
Pag.11:D2
activated.
After 60s of continued closed switch, the pushbutton is
Pag.10:D2
Puls. DNB bloccato Landing up call button locked deleted, flashing the red light. If it opens, the function is re-
Pag.11:D2
activated.
Check:
- Power supply to safety chain
QS1/1 e QS1/3
No supply on safety chain - board K-48(48Vdc)/K- Pag.2:C5
Sic. 1 - SUPPLY
Terminals : QS1/1 - 3 (K-CTR) 230(230Vac) Pag.3:A4
- automatic switch “AM”
- Phase relay “RF”
- Pit stop “PST”
Check:
No supply on safety chain - Overtravel “FLS/D”, “FLS-U”
Sic. 2 - SHAFT Pag.3:C4
Terminals VS1/5 - 7 (K-CTR) - Shock absorber “X”
- Overspeed governor “OSG”
Check:
- Parachute“SGS”
No supply on safety chain
Sic. 3 – CAR - Stop inspection car top Pag.3:D4
Terminals CS1/1 - 3 (K-CTR)
- 2° Stop (if present)
- Pin lock “LKP” MRL lifts
No supply on safety chain Check:
Sic. 4 - SWING Pag.3:F4
Terminals VS2/1 - 3 (K-CTR) - Swing safety contacts
No supply on safety chain Check:
Sic. 5 - CAR D Pag.3:G4
Terminals CS1/5 - 7 (K-CTR) - Car door contacts
Check:
No supply on safety chain - Landing doors contacts
Sic. 6 - LOCKS Pag.3:G4
Terminals VS2/5 - 7 (K-CTR) Retiring cam correctly
activated “PT”
Both contacts SU/SD opened
Check and syncronize bistable sensors and magnets SU – SD
Rif. Inf & Sup attivi Terminals BST/1 - 2 (K-CAR) Pag.5:H2
(shaft syncronizators )
Terminals BST/3 - 4 (K-CAR)
Check :
Error of level identification - Magnets number and
Rif. inf.: Err. Piano Terminals BST/3 - 4 (K-CAR) position Pag.5:H2
- Correct overlap of floor stop
IU and ID magnets
Check :
Error of level identification - Magnets number and
Rif. sup.: Err. Piano Terminals BST/1 - 2 (K-CAR) position Pag.5:H2
- Correct overlap of floor stop
IU and ID magnets

Pag 11 of 36
Installation_manual_21D.doc v2.1
Gruppo Millepiani S.p.A.
Legal headquarter http://www.gruppomillepiani.it
Corso Europa, 76 - 20020 Solaro MI P.IVA: 02731550121 e-mail:[email protected]
Tel. 02 92274700 – Fax 02 92274701 Cap. Soc. €. 1.000.000,00 Int. Versato
Operational headquarter Iscrizione Reg. Imprese di Milano N° 02731550121
Via De Amicis 20 – 20020 SOLARO MI
02 97388850 Fax 02 97388870-Italy

Check :
At bottom floor bistable switch
- Magnets number and
missed.
Piano inf: No rifas. position Pag.5:H2
Terminals BST/3 - 4 (K-CAR)
- Correct overlap of floor stop
IU and ID magnets
Check :
At top floor bistable (SU)switch - Magnets number and
Piano sup: No rifas. missed Terminals BST/1 - 2 (K-CAR) position Pag.5:H2
- Correct overlap of floor stop
IU and ID magnets
With VANO DIGITALE at high speed
(V4) bottom bistable switch has Pag.5:H2
Quota rifas. infer. Check for position ( decrease ) of bottom bistable switch SD
been reached. Terminals BST/3 - 4 Pag.80
(K-CAR)
With VANO DIGITALE at high speed
(V4) top bistable switch has been Pag.5:H2
Quota rifas. super. Check for position ( increase ) of top bistable switch SU
reached. Terminals BST/1 - 2 (K- Pag.80
CAR)
EN 81-21 ispez. EU Terminals Q8/2 - 8 (K-CTR) Switch “EU” in off position (EN 81-21) Pag.60:A5
Check :
Terminals Q8/1 - 8 (K-CTR)
- Overtravel switch “FCU” Pag.60:A5
EN 81-21 blocco FCU Reduced PIT/Headroom overtravel
- Mechanical position of FCU Pag.70/80
switch
- parameter “5.06 (EN 81-21)”
Emergenza Net power supply failure Net supply switched off Pag. 25

HD clock error Hardware main board K-CTR failure Replace K-CTR


Keypad – K-CTR communication failure. Check for software
Errore connessione
versions
Azzeramento allarmi Delete alarm list ( confirm with ENTER )
VF6 A/B VF6 A/B Fermator door operator off, missing, faulty or not
Ferm. VF6-A/B assente
Fermator door operator off connected
Check for A3 safety contact.RDF or inspection required to
Blocco Emendam. A3 A3 safety contact switched
delete error
Check for A3 safety contact.RDF or inspection required to
Emend.A3 KENC guasta A3 otion board missing or faulty
delete error

Pag 12 of 36
Installation_manual_21D.doc v2.1
Gruppo Millepiani S.p.A.
Legal headquarter http://www.gruppomillepiani.it
Corso Europa, 76 - 20020 Solaro MI P.IVA: 02731550121 e-mail:[email protected]
Tel. 02 92274700 – Fax 02 92274701 Cap. Soc. €. 1.000.000,00 Int. Versato
Operational headquarter Iscrizione Reg. Imprese di Milano N° 02731550121
Via De Amicis 20 – 20020 SOLARO MI
02 97388850 Fax 02 97388870-Italy

Pag 13 of 36
Installation_manual_21D.doc v2.1
Gruppo Millepiani S.p.A.
Legal headquarter http://www.gruppomillepiani.it
Corso Europa, 76 - 20020 Solaro MI P.IVA: 02731550121 e-mail:[email protected]
Tel. 02 92274700 – Fax 02 92274701 Cap. Soc. €. 1.000.000,00 Int. Versato
Operational headquarter Iscrizione Reg. Imprese di Milano N° 02731550121
Via De Amicis 20 – 20020 SOLARO MI
02 97388850 Fax 02 97388870-Italy

IMPORTANT NOTICE ! Only safety errors ( sic.2-sic3 and travel timers ) lock
the lift. To reset these errors is necessary trained people engage.

Alarm reset :

BE CAREFUL!

To reset an alarm of the lift operate one of these:


- Activate inspection switch from car top, then switch in normal position again.
or
- Activate RDF switch ( controller operation ) , then switch in normal position again.
or
- Disconnect and reconnect M3 connector on K-CTR main board into controller
or
- Delete alarms into menu “50. LISTA GUASTI”, “02-Cancellazione”

One of these , if the alarm is solved ( not still active ) , will reset the lift.

Pag 14 of 36
Installation_manual_21D.doc v2.1
Gruppo Millepiani S.p.A.
Legal headquarter http://www.gruppomillepiani.it
Corso Europa, 76 - 20020 Solaro MI P.IVA: 02731550121 e-mail:[email protected]
Tel. 02 92274700 – Fax 02 92274701 Cap. Soc. €. 1.000.000,00 Int. Versato
Operational headquarter Iscrizione Reg. Imprese di Milano N° 02731550121
Via De Amicis 20 – 20020 SOLARO MI
02 97388850 Fax 02 97388870-Italy

Programming MANUAL

1.PARAMETRI BASE ( base parameters )

Factory User
Parameters Default Value Possibilities Note
Value Value

00)Italiano
01)English
01-Lingua 00)Italiano 00 00 Keypad language.
02)French
03)Deutch
02-Numero fermate 2 2, . . , 64 Number of lift stops
00)SAPB
01)Down Collective
03-Modo chiamate 00)SAPB 02)Full Collective Set the call logic system
03)SAPB/Car
DownColl
01.0 = with
automatic
04.0 = 4 sec.
04-Tempo occupato 03.0 door Timeout for lift busy state
10.0 = 10 sec.
04.0 = with
swing door
Sets the numer of floors under 0
05-Num.sotterranei 01 01, . ., 09
floor ( negative floors )
06-Piano di parcheggio 01 01, 02, . . , 64 Parking floor
0m = Parking disabled
Parking time ( after this the lift
07-Tempo parcheggio 15m 10m = 10 min.
goes to parking floor )
15m = 15 min.
10.0 = 10 sec. Set run timeout supervision
08-Tempo corsa 20.0s
20.0 = 20 sec. between adjacent floors
09-Numero porte 01 01, 02 Number of door operators
00) Don't Open
01) Side A Set side opening
10-Lato porte 01)Side A 02) Side B ATTENTION: 0 sets no opening,
03) Both A+B call to this floor is disabled !!
04) Selective A/B
NO = function Door preopening option ( only if
11-Preapertura disabled controller is equipped with
SI = function enabled option )
Initial delay to start , waiting the
12-Tempo pattino ON 060
CAM to switch on.
Delay at stop for CAM switch off
13-Tempo pattino OFF 000
( wait this time to open doors )
Lift floor positioning after reset
14-Park dopo reset 00
first travel

Pag 15 of 36
Installation_manual_21D.doc v2.1
Gruppo Millepiani S.p.A.
Legal headquarter http://www.gruppomillepiani.it
Corso Europa, 76 - 20020 Solaro MI P.IVA: 02731550121 e-mail:[email protected]
Tel. 02 92274700 – Fax 02 92274701 Cap. Soc. €. 1.000.000,00 Int. Versato
Operational headquarter Iscrizione Reg. Imprese di Milano N° 02731550121
Via De Amicis 20 – 20020 SOLARO MI
02 97388850 Fax 02 97388870-Italy

2.MENU MOTORE ( Motor menu )

Factory User
Parameters Default Value Possibilities Note
Value Value

12)V3F Closed loop Motor type. Factory set, do not


01-Motore tipo 00)Non impostato 12) 12)
change this parameter

02-Soglia termistore 100 0 .. 250 Motor thermistor alarm level.

03-Ritardo stop salita 0.20s 0.00s ..2.50s Time delay to stop upgoing
04-Ritardo stop
0.20s 0.00s ..2.50s Time delay to stop downgoing
discesa
00)No Micro-levelling option for
05-Microlivellazione NO
01)Yes hydraulic lift
06-Rit.stop microliv 0.00s 0.00s ..2.50s Time delay to stop microleveling
Time for star-delta starting
07-Oleo t.stella 0.00s 0.00s ..2.50s
hydraulic lift
Time delay for high speed valve
08-Oleo t.start high 0.50s 0.00s ..2.50s
hydraulic lift
Timedelay for soft stop valve
09-Oleo t.soft stop 0.00s 0.00s ..2.50s
hydraulic lift
Timedelay for BUCHER valve
10-Oleo t.stop BUCHER 1.00s 0.00s ..2.50s
hydraulic lift
11-V3F T.start
0.00s 0.00s ..2.50s V3F time delay at start
UP/DOWN
V3F time delay at start to give
12- V3F T.start SPEED 0.00s 0.00s ..2.50s
speed
13- V3F T.stop
0.70s 0.00s ..2.50s V3F time delay at stop
UP/DOWN
Main contactor delay at stop .
14- V3F T.stop MAIN 1.00s 0.00s ..2.50s Minimum value : 1s ! Do not
modify
00)Slow Inspection speed ( high or low
15-Velocità ispezione Veloce(Fast)
01)Fast speed )
00)No
16-Abilita gest ready si Ready signal enabled in K-CTR
01)Yes
Delay for reset command after
17-Ritardo reser RDY 30s 0s-120s
RDY switch in K-CTR
00)No Lift stop after RDY switch off in
18-Blocco dopo RDY No
01)Yes K-CTR

Pag 16 of 36
Installation_manual_21D.doc v2.1
Gruppo Millepiani S.p.A.
Legal headquarter http://www.gruppomillepiani.it
Corso Europa, 76 - 20020 Solaro MI P.IVA: 02731550121 e-mail:[email protected]
Tel. 02 92274700 – Fax 02 92274701 Cap. Soc. €. 1.000.000,00 Int. Versato
Operational headquarter Iscrizione Reg. Imprese di Milano N° 02731550121
Via De Amicis 20 – 20020 SOLARO MI
02 97388850 Fax 02 97388870-Italy

3.OPERATORE LATO A/4. OPERATORE LATO B


( door operator)

Factory User
Parameters Default Value Possibilities Note
Value Value

00)Manual
01)SemiAutomatic
02)Automatic
01-Tipo operatore 02)Automatic 02 02 Type of first ( A ) door operator
03)FERMATOR serial
04)FERMATOR VVVF6

00)Not equipped Type ( normally opened/closed )


02)Contatto chiuso
02-Finecorsa Apert. 02) 02) 01)Normally opened of door operator’s opening
( normally closed )
02)Normally closed microswitches, if equipped
00)Not equipped Type ( normally opened/closed )
02)Contatto chiuso
02-Finecorsa Chius. 02) 02) 01)Normally opened of door operator’s closing
( normally closed )
02)Normally closed microswitches, if equipped
For EN81 rules, doors have o
00)Opened
04-Stazionamento 01)Chiuso (closed) 01)Chiuso 01)Chiuso remain closed at standstill at
01)CLosed
floor
Time duration for door keep
05-T. Stazionamento 5s 1s .. 25s
opened at floor after a call.
Timeout for door opening/closing
06-T. Movim. Porta 10s 1s .. 40s
commands
00)With
Door close command operation
07-Chiusura Porta 00)Cade su finecorsa microswitches
system
01)Always on
00)With
Door open command operation
08-Apertura Porta 00)Cade su finecorsa microswitches
system
01)Always on
00)No
09-Chiusura in moto 00)Nessun comando 01)Impulse Door closing during travel
02)Always on
02)Contatto 00)Not equipped
Door’s safety shoe contact type
10-Costola mobile chiuso(normally 01)Normally opened
Input on K-CAR, conn. DOPA/3
closed) 02)Normally closed
02)Contatto 00)Not equipped
Door’s photocell contact type
11-Fotocellula chiuso(normally 01)Normally opened
Input on K-CAR, conn. PHA/1
closed) 02)Normally closed
Minimum time for door opening
12-T.Minimo Apertura 0.50s 0.00s ..2.00s
command

Pag 17 of 36
Installation_manual_21D.doc v2.1
Gruppo Millepiani S.p.A.
Legal headquarter http://www.gruppomillepiani.it
Corso Europa, 76 - 20020 Solaro MI P.IVA: 02731550121 e-mail:[email protected]
Tel. 02 92274700 – Fax 02 92274701 Cap. Soc. €. 1.000.000,00 Int. Versato
Operational headquarter Iscrizione Reg. Imprese di Milano N° 02731550121
Via De Amicis 20 – 20020 SOLARO MI
02 97388850 Fax 02 97388870-Italy

IMPORTANT! With a door operator NOT EQUIPPED with opening or closing


microswitches , set parameters as follows ( 3. for door A , 4. for door B ) :
3. 02-Finecorsa Apert. = 00)Not equipped
3. 03-Finecorsa Chius. = 00)Not equipped
3.06-T. Movim. Porta = 6s
3. 07-Chiusura Porta = 00)With microswitches
3.08 – Apertura Porta = 00) With microswitches
If equipped with Fermator VVVF4 door operator set :
se Fermator VVVF4
3.09-Chiusura in moto = 02)Always on

If into parameter 3.01 ( door A ) or 4.01 ( door B ) it’s set 03 value ( 4.01=3
Type of operator serial ) , you’ll be able to see the paramaters of door’s
inverter operator ). Note that when you modify a parameter, after a few
seconds you’ll see the new value.

Pag 18 of 36
Installation_manual_21D.doc v2.1
Gruppo Millepiani S.p.A.
Legal headquarter http://www.gruppomillepiani.it
Corso Europa, 76 - 20020 Solaro MI P.IVA: 02731550121 e-mail:[email protected]
Tel. 02 92274700 – Fax 02 92274701 Cap. Soc. €. 1.000.000,00 Int. Versato
Operational headquarter Iscrizione Reg. Imprese di Milano N° 02731550121
Via De Amicis 20 – 20020 SOLARO MI
02 97388850 Fax 02 97388870-Italy

Electronic door operator parameters (Fermator VVVF4)

Factory User
Parameters Default Value Possibilities Note
Value Value

13-Param.FERMATOR Press ENTER to see parameters


It’s automatically set after door
A01-Larghezza Porta xxx Door’s width
training operation
Final opening travel at slow
A02-Spazio Rall. Ap. 002
speed (cm)
Final closing travel at slow speed
A03-Spazio Rall. Ch. 004
(cm)
Opening acceleration
A04-Accel. Apertura 010
(mm/s2)
Closing acceleration
A05-Accel. Chiusura 010
(mm/s2)
Opening deceleration
A06-Decel. Apertura 008
(mm/s2)
Closing deceleration
A07-Decel. Chiusura 004
(mm/s2)
Speed at final opening or closing
A08-Veloc. in Chius. 070
travel
A09-Coppia Apertura 045 Opening torque

A10-Coppia Chiusura 045 Closing torque

A11-Veloc. Accoppiam 100 Max 200 mm/s Closing-coupling final speed


Travel for opening coupling
A12-Spazio Accoppiam 007
system
> in training
,overwrites
params
Nessuna protezione > motor data
A13-Protezione Protezione parziale protected
Protezione completa against
changes
> save all
modifies

Pag 19 of 36
Installation_manual_21D.doc v2.1
Gruppo Millepiani S.p.A.
Legal headquarter http://www.gruppomillepiani.it
Corso Europa, 76 - 20020 Solaro MI P.IVA: 02731550121 e-mail:[email protected]
Tel. 02 92274700 – Fax 02 92274701 Cap. Soc. €. 1.000.000,00 Int. Versato
Operational headquarter Iscrizione Reg. Imprese di Milano N° 02731550121
Via De Amicis 20 – 20020 SOLARO MI
02 97388850 Fax 02 97388870-Italy

Do not save
A14-Salvataggio Save parameters
Save
AT1-Test Apertura Opening command for test

AT2-Test Chiusura Closing command for test


Photocell signal disable .Set
00)No
14-Fotocellula FR 01)Si “00=NO for devices connected
01)Yes
on K-CAR conn. PHA
00)No
15-Costola mobile FR 01)Si Safety shoe signal disable
01)Yes

Regulation parameters behaviour:

Pag 20 of 36
Installation_manual_21D.doc v2.1
Gruppo Millepiani S.p.A.
Legal headquarter http://www.gruppomillepiani.it
Corso Europa, 76 - 20020 Solaro MI P.IVA: 02731550121 e-mail:[email protected]
Tel. 02 92274700 – Fax 02 92274701 Cap. Soc. €. 1.000.000,00 Int. Versato
Operational headquarter Iscrizione Reg. Imprese di Milano N° 02731550121
Via De Amicis 20 – 20020 SOLARO MI
02 97388850 Fax 02 97388870-Italy

5.OPZIONI ( options )

Factory User
Parameters Default Value Possibilities Note
Value Value

01-Tempo luce
5m 1m .. 60m Car light / fan timeout
cabina
00)7 segments
01)Binary from 0
02)Binary from 1
03)1 Pole/floor Car display type selection
02-Display K-COP 02)Binario da 1
04) GRAY code from Connector CPI on K-COP board
0
05) GRAY code from
1
00)7 segments
01)Binary from 0
02)Binary from 1
03)1 Pole/floor
03-Display K-LDG 02)Binario da 1 Floor display tipe selection
04) GRAY code from
0
05) GRAY code from
1
00)7 segments
01)Binary from 0
02)Binary from 1
03)1 Pole/floor Parallel display interface with K-IR board
04-Display K-I/O 03)1 Filo x Piano
04) GRAY code from Connettore LPI (1)
0
05) GRAY code from
1
00)Disabled
01)Beep on
05-EN 81-70 (bip) 00)Disabilitato pushbutton Acoustic EN 81.70 signal
02)Beep on
pushbutton at floor
00)Disabled
06-EN 81-21 00)Disabilitato 01)FCU + EU Safety devices control for reduced head/pit
02)EU
00)No
07-Controllo DZSM 00)No Check funtion for “DZSM” enabled at floor
01)Yes

Pag 21 of 36
Installation_manual_21D.doc v2.1
Gruppo Millepiani S.p.A.
Legal headquarter http://www.gruppomillepiani.it
Corso Europa, 76 - 20020 Solaro MI P.IVA: 02731550121 e-mail:[email protected]
Tel. 02 92274700 – Fax 02 92274701 Cap. Soc. €. 1.000.000,00 Int. Versato
Operational headquarter Iscrizione Reg. Imprese di Milano N° 02731550121
Via De Amicis 20 – 20020 SOLARO MI
02 97388850 Fax 02 97388870-Italy

Factory User
Parameters Default Value Possibilities Note
Value Value

00)Disabled
01)Hydro lowest
floor Activates the net supply off-emergency
02)Hydro first stop function .
03)Rope lowest The type of emergency to choose changes
08-Emergenza 00)Disabilitato floor by the type of lift and the behavior
04)Rope first stop desired.
05)Rope brake
IU+ID
06)Rope brake IU/ID
07)Rope brake IZ
Delay time from net supply-off to
09-Ritardo
4.0s 2.0s .. 25.0s emergency activation. To be used to
Emergenza
suppress V3F errors in case of net off.
Photocell automatic switch off delay
10-Escl. fotocellula 0s 0s .. 60s
0s = Photocell always on.
00)At stop
01)At end opening Lift at floor output. If 02 it signalizes the
11-Presente seriale 00)Alla fermata
02)Out of service out of service state
function
After an error on magnets count ( IU , ID )
00)No
12-Reset su err.vano 00)No 01)Lift goes to reset
01)Yes
00)Count corrected by software
Inspection movement over SU,SD The lift
13-Ispezione 00)No stops on SU or SD, after a command starts
00)No
estremo 01)Yes in slow speed toward the first magnet IU
or ID.
00)No Soft stop of car in inspection, living only
14-Ispez. Rall->Stop 00)No
01)Yes RUN button.
Minimum load function ( with SAPB it
00)No
15-Abil. minimo car. 00)No holds door opened with minimum load
01)Yes
activated )
“ALT” Pushbutton
Inputs on K-COP/K-CAR
00)Disabled Values “01 or 02” – lift stop suddenly and
01)Slowdown + stop wait for another command.
16-Stop/fuori serviz 00)Disabilitato
02)Fast stop Value “03” - lift olds at floor with door
03)Out of service opened.
On display you’ll see “ALT” if function is
enabled.

Pag 22 of 36
Installation_manual_21D.doc v2.1
Gruppo Millepiani S.p.A.
Legal headquarter http://www.gruppomillepiani.it
Corso Europa, 76 - 20020 Solaro MI P.IVA: 02731550121 e-mail:[email protected]
Tel. 02 92274700 – Fax 02 92274701 Cap. Soc. €. 1.000.000,00 Int. Versato
Operational headquarter Iscrizione Reg. Imprese di Milano N° 02731550121
Via De Amicis 20 – 20020 SOLARO MI
02 97388850 Fax 02 97388870-Italy

00)No Delay car calls after two stops without


17-Abil. false chiam 00)No
01)Yes passing the photocell
00)No
18-Abil. apert. reset 00)No Enable door opening after reset
01)Yes
00)No
01)Std. U.S.T.I.F.
19-Monitoraggio 00)Nessuno 02)MONITECH Lift remote monitoring ( with Monitech )
03)MONITECH +
USTIF
00)No
01)Yes + msg. K-SYS
20-Anti-violenza 00)No Special option
02)Yes+ no msg. K-
SYS
Number of re-opening for floor call.
21-Apertura al piano 00 00 .. 03 00=disabled

22-T.doppia
0.0s 0.0s ..3.5s Locks the double call at floor for set time
chiamata
Making a call from “A”side:door opening
00)No
23-Divis. lati A/B 00)No on “A” side , making a call from “B” side ,
01)Yes
door opening on “B” side.

Pag 23 of 36
Installation_manual_21D.doc v2.1
Gruppo Millepiani S.p.A.
Legal headquarter http://www.gruppomillepiani.it
Corso Europa, 76 - 20020 Solaro MI P.IVA: 02731550121 e-mail:[email protected]
Tel. 02 92274700 – Fax 02 92274701 Cap. Soc. €. 1.000.000,00 Int. Versato
Operational headquarter Iscrizione Reg. Imprese di Milano N° 02731550121
Via De Amicis 20 – 20020 SOLARO MI
02 97388850 Fax 02 97388870-Italy

7.MANOVRE SPECIALI ( special


features)

00)No
01-Abilita Priorita 00)No Enable priority function
01)Yes
02-Piano Priorita 01 Priority floor
00) A side
03-Lato Priorita 00)Lato A 01) B side Select door side A or B for priority
02)Sides A+B
00)No
04-Abilita Rinvio 00)No Enalble floor recall function
01)Yes
05-Piano Rinvio 01 Select floor recall function
00) A side
06-Lato Rinvio 00)Lato A 01) B side Select door side A or B for recall function
02) A+B sides
Time for recall option. The lift waits at
07-T. Attesa Rinvio 10s floor, with door opened , waiting for a car
call (flashing pushbutton)

Pag 24 of 36
Installation_manual_21D.doc v2.1
Gruppo Millepiani S.p.A.
Legal headquarter http://www.gruppomillepiani.it
Corso Europa, 76 - 20020 Solaro MI P.IVA: 02731550121 e-mail:[email protected]
Tel. 02 92274700 – Fax 02 92274701 Cap. Soc. €. 1.000.000,00 Int. Versato
Operational headquarter Iscrizione Reg. Imprese di Milano N° 02731550121
Via De Amicis 20 – 20020 SOLARO MI
02 97388850 Fax 02 97388870-Italy

00)No
08-Abilita risparmio 00)No Energy saving option
01)Yes
Timeout after Energy saving :
0: disable Energy saving
09-Ritardo risparmio 4m • V3f, K-CAR/K-COP,Car light
disabled

10-Abilita OSS K- 00)No Out of service key at floor enabled , “OSC”


00)No
LDG 01)Yes input on K-LDG

Pag 25 of 36
Installation_manual_21D.doc v2.1
Gruppo Millepiani S.p.A.
Legal headquarter http://www.gruppomillepiani.it
Corso Europa, 76 - 20020 Solaro MI P.IVA: 02731550121 e-mail:[email protected]
Tel. 02 92274700 – Fax 02 92274701 Cap. Soc. €. 1.000.000,00 Int. Versato
Operational headquarter Iscrizione Reg. Imprese di Milano N° 02731550121
Via De Amicis 20 – 20020 SOLARO MI
02 97388850 Fax 02 97388870-Italy

9. VANO DIGITALE(digital shaft)

Enable to acquire RFD ( controller


01-Misura soglia 00)Verify enabled
00)Verif. abilitata inspection ) safety speed for rescue
SPD 01)Speed measure
operation for MRL lifts
00)Magnes (K-CTR)
Selects the shaft type , and where to
01)Digital (K-CTR)
02-Gestione vano 00)Magneti (K-CTR) connect sensors ( K-CTR or K-CAR )
02)Magnets(K-CAR)
Do not change these parameters
03)Digital (K-CAR)
00)No
03-Inverti encoder 00)No To be set by rotation sense of pulley
01)Yes
04-Corsa impianto
cm. : ..... Lift travel value ( cm )
cm
If active converts frome pulse to cm.To be
05-Conversione in 00)No
00)No activated only after all positions and
cm 01)Yes
speeds acquire.
06-Divisore encoder Valore: . . . 50 Scaling factor for pulse encoder signal
00)No
07--Misura livelli 00)No Floor magnets position acquire
01)Yes
08-Misura 00)No
00)No Slowdown magnets position acquire
rallentam. 01)Si
P: 0 L:….. H:…..
09-Taratura livelli Levels positions list
P: 1 L:….. H:…..
R:01 Q: . . . . .
R:02 Q: . . . . .
10-Taratura rallent. Slowdown positions list
R:03 Q: . . . . .
R:04 Q: . . . . .
Acquired speed safety level . See “soglia
11-Tarat. Soglia SPD cm/sec: .....
SPD” parameter 9.01
00)Standard
12-Controllo
00)Standard 01)Ropes Ropes compensation option
encoder
compensation
If syncronizators SU/SD reached at V3 or
13-Rallenta su V2, slowdon act after time set.
0.01s 0.00s .. 2.50s
SU/SD If SU/SD reached at V4 : slowdown act
immediately
14-Stop If top or bottom floors <= 10cm, floor level
00)No
quota+magnet is calculated as level value+magnets

Pag 26 of 36
Installation_manual_21D.doc v2.1
Gruppo Millepiani S.p.A.
Legal headquarter http://www.gruppomillepiani.it
Corso Europa, 76 - 20020 Solaro MI P.IVA: 02731550121 e-mail:[email protected]
Tel. 02 92274700 – Fax 02 92274701 Cap. Soc. €. 1.000.000,00 Int. Versato
Operational headquarter Iscrizione Reg. Imprese di Milano N° 02731550121
Via De Amicis 20 – 20020 SOLARO MI
02 97388850 Fax 02 97388870-Italy

DIGITAL SHAFT SETUP PROCEDURE

BE CAREFUL ! For digital shaft setup it’s ,mandatory that an encoder or a digital encoder
repetition is connected to terminal Q3 of K-CTR board.

Setup procedure
1) Put magnets on guiderails into shaft as descrive into wiring diagram 30.8002.00 pg. 80

2) Check fot the following parameters:


• 1. 02-Numero Fermate( stop numbers ) – Set the number of stops of the lift
• 2. 01-Motore Tipo ( motor type ) – it must be n.12 ( V3F generico C/L )
• 9. 02-Vano digitale ( digital shaft ) – it must be 01 (Digitale (K-CTR) )
• 9. 06-Divisore encoder -- It must be 50
3) Check for the speed levels set into the inverer , as you can use four speed with digital shaft:
1. V4 – Alta velocità ( high speed ) , [FRENIC LIFT – C11] – 1m/s
2. V3 – Velocità intermedia ( intermediate-high speed ) [FRENIC LIFT – C09] – 0,80m/s
3. V2 – Velocità intermedia ( intermediate-low speed ) [FRENIC LIFT – C05] – 0,30m/s
4. V1 – Velocità accostamento ( approaching speed ) [FRENIC LIFT – C07] – 0,05m/s

BE CAREFUL ! During digital shaft setup, the lift moves automatically up and down at inspection
speed. Be sure all the safety systems are properly working, and be sure the car is ready to travel
into shaft with all safety requirements. Serious injury may occur not respecting this !

4) Perform levels acquiring and saving :


• menu 9 VANO DIGITALE ( digital shaft ), param.-9.07 : “Misura livelli” ( levels measure )
press “Enter”: the lift will go to reset, at the lowest floor , then automatically goes up in inspection
speed, reading the lowest position of first IU magnet ( IU-L ). After this, reading the bottom
syncronizator ( SU ) the car pass into slow speed and stops at floor.
The lift now starts again ,going down in inspection speed toward the highest position of first IU
magnet ( IU – H ).This two values IU-L and IU-H will be saved into 9.09 “Tara livelli”( levels setup ).

Pag 27 of 36
Installation_manual_21D.doc v2.1
Gruppo Millepiani S.p.A.
Legal headquarter http://www.gruppomillepiani.it
Corso Europa, 76 - 20020 Solaro MI P.IVA: 02731550121 e-mail:[email protected]
Tel. 02 92274700 – Fax 02 92274701 Cap. Soc. €. 1.000.000,00 Int. Versato
Operational headquarter Iscrizione Reg. Imprese di Milano N° 02731550121
Via De Amicis 20 – 20020 SOLARO MI
02 97388850 Fax 02 97388870-Italy

5) Perform slowdown distance acquiring :


• menu 9 VANO DIGITALE ( digital shaft ), param.-9.08 : “Misura rallentam.” ( slowdown measure )
press “Enter”: the lift will go to reset, at the lowest floor , then automatically goes up at V4 speed ,
performing a slowdown and measuring the slowdown space.
• After this the lift automatically performs a reset, and a travel at various speeds ( V3,V2,V1).
• The slowing down distances, at various speeds are saved into 9.10 “Taratura rallent.” ( slowdown
measures ) R4, R3, R2, R1.

6) Press “ESC” many times to memorize and finish the procedure.

7) Test sto be performed before normal travelling :

Into menu “9.09-Tara livelli” ( levels setup ) check that for all the floors position value “L” is lower than
position value “H”

Example for 3 stops lift : P0 L . . . . 0 H . . . 81 ( level 0 position value )


P1 L . 1373 H . 1398 ( level 1 position value )
P2 L . 2025 H . 2048 ( level 2 position value )

As described, you can see that “L” value is always lower than “H” value

Into menu “9.10-Tara rallentamenti” (slowdown measures) check that for all the speeds the values are
proportional to the speeds ( speed higher = slowdown distance bigger )

Ex. R1 . . . . 8 (V1-Accostamento) - approach speed


R2 . . . 70 (V2-Velocità intermedia bassa) – intermediate slow speed
R3 . . 150 (V3-Velocità intermedia alta) – intermediate high speed
R4 . . 300 (V4-Velocità alta) – high speed
If you found R3=R4 it means that V3=V4 , so you ‘ll have to change the V3 speed level into the inverter.
After this you’ll perform again pt 5 of the procedure.
If the values are correct, now you can move the lift in normal operation.

Pag 28 of 36
Installation_manual_21D.doc v2.1
Gruppo Millepiani S.p.A.
Legal headquarter http://www.gruppomillepiani.it
Corso Europa, 76 - 20020 Solaro MI P.IVA: 02731550121 e-mail:[email protected]
Tel. 02 92274700 – Fax 02 92274701 Cap. Soc. €. 1.000.000,00 Int. Versato
Operational headquarter Iscrizione Reg. Imprese di Milano N° 02731550121
Via De Amicis 20 – 20020 SOLARO MI
02 97388850 Fax 02 97388870-Italy

BE CAREFULL ! Do not perform the first call to highest or lowest floor !

Operate the first call to the nearest floor ( but not the highest or lowest ) , and check the correct lift
positioning at floor.
Consider that the car must run at least 5-10cm in approaching speed to perform a correct floor positioning.
Now try making a call travelling for two floors.
If the lift arrives a little bit over the floor, try to increase into menu “9.10-Tara rallentamenti” (slowdown
measures) the values of R3 o R4 .

IMPORTANT! Note that the slowdown distance is given by R1 and R2 or R3 or R4 . So


increasing R1 value you’ll also increase slowdond distance.

So you can also try to increase R1 if the auto-set slowdown distance is not sufficient.

After trying the stop sto all floors, move the magnets at each floor, if necessary,to fine set the floor
positioning.Perform again the procedure at pt 4 ( levels acquire ).

Errors and common problems solutions :


ERROR “Quota rifasatore Sup” / “Quota rifasatore Inf” ( level top/bottom syncronizator )
CONDITION SU or SD syncronizator has been met at high speed ( V4 )
SOLUTION Move SU higher or SD lower so that the lift can slowdown before it

ERRORE “Piano Inf No Rifas” / “Piano Sup No Rifas” ( bottom/top level , No syncronizator )
CONDITION The lift is at top or bottom floor, but the SU or SD signal doesn’t appear
SOLUTION check for SU or SD magnet position, or sensor,or wiring. Use leds on K-CAR ( car top ) or
keypad to easier check.

ERROR “Rif Inf Err Piano” / “Rif Sup Err Piano” ( error bottom/top level )
CONDITION The lift is at floor with SU or SD switched, but the floor is not top or bottom.
SOLUTION Check for IU,ID floor magnets correct positions ( minimum overlap 4cm !! )

ERRORE “Mancanza IU al piano” / “Mancanza ID al piano” ( missing IU / ID at floor )


CONDITION In stopping phase, the lift overtravelled the floor magnets (IU+ID),
If it stops upgoing and only IU is energized , error : “Mancanza IU al piano”
If it stops downgoing and only ID is energized , error : “Mancanza ID al piano”

SOLUTION Verificare la sovrapposizione dei magneti di fermata IU/ID, devono essere di almeno 4cm
Verificare le quote di rallentamento, param. “09.10-Taratura rallent. ”

Pag 29 of 36
Installation_manual_21D.doc v2.1
Gruppo Millepiani S.p.A.
Legal headquarter http://www.gruppomillepiani.it
Corso Europa, 76 - 20020 Solaro MI P.IVA: 02731550121 e-mail:[email protected]
Tel. 02 92274700 – Fax 02 92274701 Cap. Soc. €. 1.000.000,00 Int. Versato
Operational headquarter Iscrizione Reg. Imprese di Milano N° 02731550121
Via De Amicis 20 – 20020 SOLARO MI
02 97388850 Fax 02 97388870-Italy

These errors do not stop the lift, but signalize a not correct behavior , so the lift will go to reset after one of
this signalization, to acquire again a zero position mark. Check for IU/IU , SU/SD magnets position if one of
these errors appear.

Pag 30 of 36
Installation_manual_21D.doc v2.1
Gruppo Millepiani S.p.A.
Legal headquarter http://www.gruppomillepiani.it
Corso Europa, 76 - 20020 Solaro MI P.IVA: 02731550121 e-mail:[email protected]
Tel. 02 92274700 – Fax 02 92274701 Cap. Soc. €. 1.000.000,00 Int. Versato
Operational headquarter Iscrizione Reg. Imprese di Milano N° 02731550121
Via De Amicis 20 – 20020 SOLARO MI
02 97388850 Fax 02 97388870-Italy

18.DESTINAZIONE USCITE ( outputs destination )

00)Not active
01)Upgoing signal
02)Downgoing
signal
03)Busy signal
04) DZSM module
enable
05)Preopening
enable
Selectable outputs from connector Q5 /Q8
01-Q8.4 (OT1) 03)Occupato 06)Energy-save
Of K-CTR main board.
07)Inspection
08) V4-High spd
09)V3-Insp high spd
10)V2-Insp slow spd
11)V1-Slow spd
12) V3F Ready
signal
13)V3F emergency
off
02)Direzione
02-Q8.5 (OT2)
discesa
03-Q8.6 (OT3) 01)Direzione salita
04)Abil. Modulo
04-Q5.7-8 (RTR)
DZSM

Pag 31 of 36
Installation_manual_21D.doc v2.1
Gruppo Millepiani S.p.A.
Legal headquarter http://www.gruppomillepiani.it
Corso Europa, 76 - 20020 Solaro MI P.IVA: 02731550121 e-mail:[email protected]
Tel. 02 92274700 – Fax 02 92274701 Cap. Soc. €. 1.000.000,00 Int. Versato
Operational headquarter Iscrizione Reg. Imprese di Milano N° 02731550121
Via De Amicis 20 – 20020 SOLARO MI
02 97388850 Fax 02 97388870-Italy

11.POLARITA INGRESSI ( input polarity )

00)Not available Disable or reverse input’s polarity


01-Sovraccarico 02)Contatto chiuso 01)Normally opened K-CTR - M2/1 OLD
02)Normally closed K-CAR - LWD/3 OLD
00)Not available Disable or reverse input’s polarity
02-Pieno carico 01)Contatto Aperto 01)Normally opened K-CTR - M2/2 FLD
02)Normally closed K-CAR - LWD/2 FLD
00)Not available
Disable or reverse input’s polarity
03-Minimo carico 01)Contatto Aperto 01)Normally opened
K-CAR - LWD/1 MLD
02)Normally closed
00)Not available
Disable or reverse input’s polarity
04-Input FID (K-CTR) 01)Contatto Aperto 01)Normally opened
K-CTR – V1/1 FID
02)Normally closed
00)Not available
05-Input FRD (K- Disable or reverse input’s polarity
01)Contatto Aperto 01)Normally opened
CTR) K-CTR – V1/2 FRD
02)Normally closed
00)Not available
Disable or reverse input’s polarity
06-Input RST (K-CTR) 00)Non presente 01)Normally opened
K-CTR – V1/3 RST
02)Normally closed
00)Not available
07-Imput OSS (K- Disable or reverse input’s polarity
00)Non presente 01)Normally opened
CTR) K-CTR – V1/4 OSS
02)Normally closed
00)Not available
08-Imput IN3 (K- Disable or reverse input’s polarity
00)Non presente 01)Normally opened
CTR) K-CTR – Q8/3 IN3
02)Normally closed
Disable or reverse input’s polarity
00)Not available
09-Pulsante
01)Contatto Aperto 01)Normally opened
apertura K-CAR - AUX/1 IN1
02)Normally closed
K-COP – DOB/1
00)Not available
10-Pulsante Disable or reverse input’s polarity
01)Contatto Aperto 01)Normally opened
chiusura K-COP – DCB/1
02)Normally closed
00)Not available
11-Input PRC (K- Disable or reverse input’s polarity
01)Contatto Aperto 01)Normally opened
COP) K-COP – PRC/1
02)Normally closed
00)Not available
12-Input OSS (K- Disable or reverse input’s polarity
01)Contatto Aperto 01)Normally opened
COP) K-COP – OSS/1
02)Normally closed
Disable or reverse input’s polarity
00)Not available
13-Input STOP (K-
01)Contatto Aperto 01)Normally opened
COP) K-CAR - AUX/2 IN2
02)Normally closed
K-COP – STOP/1
00)Not available
Disable or reverse input’s polarity
14-Input IN3 (K-CAR) 00)Non presente 01)Normally opened
K-CAR - AUX/3 IN3
02)Normally closed

Pag 32 of 36
Installation_manual_21D.doc v2.1
Gruppo Millepiani S.p.A.
Legal headquarter http://www.gruppomillepiani.it
Corso Europa, 76 - 20020 Solaro MI P.IVA: 02731550121 e-mail:[email protected]
Tel. 02 92274700 – Fax 02 92274701 Cap. Soc. €. 1.000.000,00 Int. Versato
Operational headquarter Iscrizione Reg. Imprese di Milano N° 02731550121
Via De Amicis 20 – 20020 SOLARO MI
02 97388850 Fax 02 97388870-Italy

12.PIANI BASSI

00)No
01-Abilita p. bassi 00)No Enable the funcion
01)Yes
I:01 Normale Normal
02- I:02 Normale Short with magnets
Set the correct type
Norm/Magneti/Non I:03 Normale Short without
I:04 Normale magnets
00)Not available
Disable or reverse input’s polarity
03-Minimo carico 01)Contatto Aperto 01)Normally opened
K-CAR - LWD/1 MLD
02)Normally closed

ATTENTION!
Short floor at top/bottom:
Shaft with magnets – Put magnet of syncronizator SU/SD just in line with slowdown
magnet (IU/ID) of the nearest floor , see diagram on pg. 70/80

Digital shaft- Set parameter on “Basso c/magneti”


Put magnet of syncronizator SU/SD over nearest floor , see diagram on pg. 70/80

Pag 33 of 36
Installation_manual_21D.doc v2.1
Gruppo Millepiani S.p.A.
Legal headquarter http://www.gruppomillepiani.it
Corso Europa, 76 - 20020 Solaro MI P.IVA: 02731550121 e-mail:[email protected]
Tel. 02 92274700 – Fax 02 92274701 Cap. Soc. €. 1.000.000,00 Int. Versato
Operational headquarter Iscrizione Reg. Imprese di Milano N° 02731550121
Via De Amicis 20 – 20020 SOLARO MI
02 97388850 Fax 02 97388870-Italy

13.CONTATORI ( counters )

01-Avviamenti totali Total number of travel.Not clearable

02-Avviam. parziali Partial number of travel. Clearable.

03-Livellaz. Salita Number of relevelling upgoing

04-Aperture lato A Number of door opening side A

05-Aperture lato B Number of door opening side B

Pag 34 of 36
Installation_manual_21D.doc v2.1
Gruppo Millepiani S.p.A.
Legal headquarter http://www.gruppomillepiani.it
Corso Europa, 76 - 20020 Solaro MI P.IVA: 02731550121 e-mail:[email protected]
Tel. 02 92274700 – Fax 02 92274701 Cap. Soc. €. 1.000.000,00 Int. Versato
Operational headquarter Iscrizione Reg. Imprese di Milano N° 02731550121
Via De Amicis 20 – 20020 SOLARO MI
02 97388850 Fax 02 97388870-Italy

40. RISERVATO DIGI ( Digilift reserved )

Clear all parameter values !!! Do not


01-Default Totale perform this without asking for tecnichal
assistance
Clear only some parameters . Do not
02-Default Parziale perform this without asking for tecnichal
assistance
Clear values of menu 13 ( not creared :
03-Azzera contatori
Total number of travels )

WARNING! Using option “01-Default Totale” i twill be necessary to set again all parameters of
your installation.

WARNING! Using option “02-Default Parziale” parameters that are not changed are :
1.02-Numero Fermate
1.03-Modo Chiamate
2.01-Motore Tipo
3.01-Tipo Operatore
4.01-Tipo Operatore
5.06-EN 81-21
5.08-Emergenza
5.17-Monitoraggio
9.02-Gestione vano
9.03-Inverti encoder
14.01-Abilita gruppo
14 02-Numero impianto
18.DESTINAZ. USCITE (All sub parameters)

Pag 35 of 36
Installation_manual_21D.doc v2.1
Gruppo Millepiani S.p.A.
Legal headquarter http://www.gruppomillepiani.it
Corso Europa, 76 - 20020 Solaro MI P.IVA: 02731550121 e-mail:[email protected]
Tel. 02 92274700 – Fax 02 92274701 Cap. Soc. €. 1.000.000,00 Int. Versato
Operational headquarter Iscrizione Reg. Imprese di Milano N° 02731550121
Via De Amicis 20 – 20020 SOLARO MI
02 97388850 Fax 02 97388870-Italy

Gruppo Millepiani S.p.A.


Via De Amicis, 20
20020 Solaro -MI
Tel. +39 0297388850
Fax +39 0297388870
www.digilift.it [email protected]

Pag 36 of 36
Installation_manual_21D.doc v2.1