Manual de Operación Daikin
Manual de Operación Daikin
INSTALLATION
OPERATION
MAINTENANCE
MODELS DM AHU
DA AHU
DS AHU
AHUR VRV AHU
VER: O-AHU01-AUG19-12
The design and construction are subject to change without any notice for future improvement.
Table of Contents
1. General ....................................................................................................................1
2. Shipment ..................................................................................................................1
3. Handling / Rigging .....................................................................................................2
4. Storage ....................................................................................................................2
5. Assembly and Installation ........................................................................................... 2
6. Commissioning and Operation ................................................................................... 12
7. Maintenance ........................................................................................................... 14
8. Trouble Shooting ..................................................................................................... 16
9. Appendix ................................................................................................................ 17
-1-
3. Handling / Rigging 4. Storage
Air handling units can be delivered as For external storage prior to installation,
separate section or completely assembled. the units must be protected from dust,
To prevent damage to unit cabinetry, a rain, constant sun exposure and rodents.
specific lifting method for offloading the Although covered in shrink-wrapped
units is recommended as shown in plastic sheeting, this is not intended for
Figure 1. The spreader bars must be in long-term storage and should be remove
position to prevent straps or cables from as soon as it is offloaded. Unit therefore
rubbing the frame panel. Ensure stability should be more protected by tarpaulins or
and balance when lifting the units and similar. Avoid exposed the units for coil
avoid twisting or uneven lifting. Care connection damages by transient load.
should be taken to prevent coil The fan impeller or motor drive must be
connections, drain pan connection, rotated once every month. Should the
damper operators and accessory section units be stored for a period of exceeding 6
from damage. months, then it is recommended that the
Do not push hard on the unit it self of on drive belts be removed and store
the metal base. Use large wooden beam separately.
to evenly distribute the force. Dropping
the units will result in permanently IMPORTANT
damage of ball bearing, fan shaft or INSTALLATION AND MAINTENANCE
loosen coil from the mounting. ARE TO BE PERFORMED ONLY BY
QUALIFIED AND EXPERIENCED
PERSONNEL WHO ARE FAMILIAR
WITH NATIONAL AND LOCAL CODES
AND REGULATION.
5.1 General
The system design and installation should
follow accepted industrial practice, such as
described in the ASHRAE Handbook.
These units are not designed to be
weatherproof (unless equipped with
canopy) and therefore should not be
Figure 1 - Lifting method when offloading units installed outdoors. Flexible connections
should be used on the outlet and inlet
Transportation on the building site should duct connections for all units. A minimal
be done using forklift truck or a crane amount of air leakage is normal on the
(See Figure 2). The forks must only be cabinet and it will not affect unit
applied under the unit base frame and not performance. The air handling units are
against the panel. In case when fork of not design to be suspended from the top
the forklift is too short then suitable of the unit. Therefore, when the unit is
extensions should be used. ceiling hung, make sure unit is supported
with a base rail of channel.
5.2 Foundation
Adequate space should be left around the
unit for coils & drainage piping, filter
replacement, and maintenance. (See
Figure 3). If site access space for coil is
not follow recommendation, AHU need to
dismantle for coil replacement. The unit is
installed at a height that allows the
Figure 2 - Transportation by forklift truck
installation of condensate drain trap.
-2-
The section joints are pre-installed on
cabinets and base frames as shown in
Figure 7 (For AHU combination of 2
sections and above). The joint for side will
located outside of AHU, joint for top
bottom will be located inside of AHU.
-3-
Figure 9 – Tighten the base frame section joint
-4-
Standard Air Series VRV AHU
5.4.2 Restrained Vibration Isolator Figure 16 - Standard Air Series VRV AHU Unit
-5-
5.6 Coil Installation/ Pipe Connection Figure 19 shows the correct mounting
method and the position of TXV sensing
5.6.1 General bulb according to the piping size.
The coil will perform as per rating only if
IMPORTANT
the airflow is uniformly pass-through the
coil surface. AFTER PIPE-WORK DONE, SITE
INSTALLER MUST WRAP THE PIPE
CONNECTION WITH INSULATION
IMPORTANT
AND SEAL THE HOLES BETWEEN
HIGH VELOCITY SPOTS ON THE COIL
PIPE CONNECTIONS AND PANEL.
MAY CAUSE MOISTURE CARRY OVER.
THEREFORE, UNIFORM AIRFLOW 5.6.2 Water Coil
ACROSS COIL SURFACE IS CRUCIAL.
Water supply, water return, drains and
External pipe-work must be adequately vents connections are extending through
supported to ensure load-free towards coil the end panel of the coil section. All
connections. Swing joints or flexible connections are labeled on the end panel.
fittings are to be provided in all piping For control equipment, follow
connections, particularly those adjacent to recommendations from the manufacturer
heating source, to absorb expansion and regarding the types, sizing and installation
contraction strains. Failure to comply will of equipment. Hot water coils are not
result in damage to the coils & headers. recommended to be used with entering air
below 40oF (4.4oC).
IMPORTANT
5.6.3 Winterizing Water Coils
TO AVOID DAMAGING THE COIL
CONNECTIONS AT COIL HEADER, IT Coil freeze-up may occur due to air
IS ESSENTIAL TO HOLD THE stratification, failure of outdoor air
CONNECTOR / PIPE WITH TOOLS dampers and/or preheat controls. Routine
WHILST APPLYING COUNTER FORCE draining of water coils for winter shutdown
TO TIGHTEN THE JOINT. (See Figure cannot guarantee zero freeze-up incidents,
18) which may result in coil damage. It is
recommended to completely drain the coil
and treated with anti-freeze solution.
Fill each coil independently with an anti-
freeze solution by using a small circulating
pump follow by complete draining. Check
the freezing point of anti-freeze before
proceed in each coil. Diluted effect
normally occurred due to a small amount
of water always remaining in each coil.
Therefore, ensure sufficient amount of
Figure 18 – Coil header connection method anti-freeze solution be remained in coil to
prevent freeze-up.
-6-
suction line, never place the bulb on the
common line.
Thermostatic expansion valve is to be
equipped with external equalizer tubes
that are field connected to the suction line.
The valve should be in accordance to the
manufacturer recommendations, allowing
approximately 35-psi pressure drop
through the coil and distributor at full load.
Do not oversize the valve, proper
expansion valve operation is necessary in
order to realize the rated coil capacity.
IMPORTANT
CAREFULLY READ THROUGH
Figure 20 – Drain Trap Arrangement
MANUFACTURING INSTRUCTION
FOR APPLING ANTI-FREEZE
5.7 Electrical Installation
SOLUTION. SOME PRODUCTS WILL
HAVE DIFFERENT FREEZING POINT Electric connecting should be compliant
IN ITS NATURAL STATE WHEN with relevant local laws and regulations.
MIXED WITH WATER. COIL FREEZE- All installation and management activities
UP IS NOT THE RESPONSIBILITY OF must be carried out by qualified personnel.
MANUFACTURER Refer to the specific wiring diagram and
It is not recommended to operate DX coil electrical component manual are attached
for air-conditioning purpose at below with the product before electrical
freezing suction temperature, 0oC which installation.
will result frost build-up at fins surface. If
the full load operating point for the coil is IMPORTANT
selected at a “safe” temperature, a system MAKE SURE ALL THE ELECTRIC
analysis is required to check for the lowest POWER DISCONNECT AND SECURE
probable suction temperature at light load FROM SWITCH ON BEFORE DOING
condition. WIRING CONNECTION
-7-
adjust belt tension using the adjusting
screw and nuts on the motor base.
Use recognized belt tension gauge to
check the belt tension by apply a force
large enough at the center of the belt to
deflect the belt by 16mm per meter (See
Figure 25). The deflection force for any
belt should be within the minimum and
maximum force shown in table 1. Readjust
the tension to maximum value when it
drops to min. value. The deflection force
of factory setting is based on “Initial
Fitting”, re-tensioning as “Retension” after
the unit has run for 24 hours.
WARNING
OVER TENSION TOWARD DRIVE
BELT WILL CAUSE PREMATURE
FAILURE OF BELT AND BEARING
DAMAGE.
-8-
Table 1 - Belt Tensioning Force
Deflection Force (N)
Pulley
Belt Section Initial Fitting Retension
Diameter
Min Max Min Max
SPZ <70 12 17 12 16
71-90 15 22 15 19
91-125 19 27 19 24
SPA <100 20 29 20 25
101-140 27 39 27 34
141-200 32 47 32 40
SPB <160 36 54 36 46
161-224 46 67 46 58
225-355 53 79 53 69
Refer to factory specifications for tension values that are not included
Refer to the diameter of smaller pulley
5.9 Accessory Items they are integral with central plant control
or associated ductwork under negative
5.9.1 Filter pressure condition.
Air handling units can be supplied with flat
5.9.3 Variable Pitch Pulley
filters and/or bag filters. There are 2 types
of filter frame, sliding frame or universal Modifications of the pulley diameter must
clip. Insert the filter into the frame by be done when stationery by moving the
following airflow arrow indicated. adjustable flange. Each complete rotation
of one of the two disks results in a
5.9.2 Mixing Box variation of the pulley diameter. (See
Fresh air and return air dampers can be Table 2 & Figure 26) When the required
linked together and drives by the same diameter is obtained, adjustable flange is
actuator if both are same size. Care must locked by tighten the four clamp screws.
be taken to ensure dampers are in open To get the same diameter in the two
position while the fan is running whether grooves of pulleys, screw the two mobile
flanges on the central flange. Then
-9-
unscrew the two mobile flanges by the load-free toward cabinet collar when initial
same number of turnings to get the positioned.
required diameter. Compliance with the Codes of Practice in
Note that the belt centre line shifts when duct assembly and acoustic layout are
diameter changes. Driven pulley may need necessary to ensure the best possible
realignment. performance of the unit whilst avoiding
excessive pressure loss in the duct system
and minimize undue air stream noise. Duct
connections to and from units should allow
straight, smooth airflow. Sharp turns in
the fan discharge should be avoided,
particularly turns opposed to wheel
rotation. Turning vanes should be used.
Discharge plenums or any abrupt change
in duct should be avoided.
5.10. Ductwork
Connections to unit cabinet are made by
site drilling into the frame on the unit inlet
or fan discharge collar. This should be
- 10 -
5.11 Assembly of Complete Knock
Down Unit (CKD)
Due to container size constrain, some air
handling units are packed in unassembled
condition - CKD method. All parts required
are packed in section by section. It is
recommended to open one section at a
time to avoid confusion when assembly.
For CKD, additional drawing will be
provided for assembly at site.
- 11 -
WARNING Fan array is available for EC plug fan.
DO NOT HEAT ANY PART ON DX Ensure all fans are control to run
COIL IF REFRIGERANT STILL IN THE simultaneously and with same speed.
SYSTEM. HEATING UP WILL CAUSE Fans running at unequal speeds can result
DANGER OF HIGH PRESSURE INSIDE uneven airflow that cause performance,
THE COILS. sound, vibration problems that lead to
failure.
6. Commissioning and Operation
In case one of the fan is down, blank off
6.1 Pre-run Check plate shall be temporarily installed on the
nonfunctional fan to prevent air re-
6.1.1 Preparation circulation while waiting fan replacement
(See Figure 32). If present of differential
The complete air handling unit and all pressure controller, ensure the pressure
accessory components should be tube of nonfunctional fan is capped and
thoroughly cleaned and all dust & debris amend the setting of controller accordingly.
completely removed.
Make sure that all transport brackets and
packing have been removed.
Ensure all screws, bolts and nuts on AHU
are secured tightly (not loose during AHU
transportation or handling).
Ensure all panel and belt drive settings are
secured due to change during shipment or
installation.
In case additional equipment is installed at
site, ensure air leaking spots are being
seal with additional baffle plates or seal
with silicone to prevent air bypassing.
- 12 -
Check all dampers are operating correctly
as per design.
Make sure all filter media are installed in
correct airflow direction.
IMPORTANT
FAILURE TO PROVIDE MOTOR
OVERLOAD PROTECTION COULD
RESULT IN MOTOR DAMAGE.
CONNECT THE MOTOR TO AN
OVERLOAD PROTECTIVE DEVICE
THAT IS RATED IN COMPLIANCE
WITH THE APPLICABLE CODE.
a. Check the rotation of the fan impeller.
Figure 33 - Wiring Diagram without Neutral
If the fan rotates in opposite direction
from desire, reverse any two phase
FOR 380-415V/3PH, STAR
connection at motor terminal.
CONNECTION WITH NEUTRAL
b. Check that there is no unusual noise
(Figure 34), NEUTRAL POINT MUST
or vibration. Stop and investigate if
BE CONNECTED IN ACCORDANCE
found. (refer to section 8)
WITH WIRING DIARGRAM IN ORDER
c. Measure the voltage and drawn
TO CARRY CURRENT DUE TO current of the motor. The drawn
UNBALANCED PHASE VOLTAGE. current must not exceed the full load
current mentioned at motor
IMPORTANT
nameplate.
SAFETY THERMOSTAT IS FOR
OVERHEATING PROTECTION ONLY, 6.3 After first 48 hours of operation
NOT FOR CONTROL PURPOSE.
DEFAULT SETPOINT IS 60˚C. a. Make sure complete isolate the
IT MUST BE CONNECTED TO Electrical source.
CONTACTOR (WHETHER SUPPLIED b. Re-check and Re-tension the drive
BY FACTORY OR SITE) TO CUT-OFF belts due to stretch.
HEATER IN CASE OF OVERHEATING c. Check and adjust the pulley alignment
HEATER. to ensure the motor fixing is properly
secure.
d. Check all bearing, wheel bolts & nuts
and sheave set screws (or cap screw)
are in secure position.
- 13 -
CAUTION Check that vibration isolator mounts are
HIGH AIR TEMPERATURE IN FAN functioning well.
SECTION CAN CAUSE MOTOR Inspect for any obstructions or blockages
at air intakes and discharges.
OVERHEAT AND DAMAGE. ON
Check fan bearings are secured and no
DRAW-THROUGH AIR HANDLERS,
undue noise by observe/listen using metal
ADJUST THE DISCHARGE AIR
bar as a conductor.
TEMPERATURE OF THE HEATING
If unit equipped with belt guard, check
SECTION NOT TO EXCEED 1040F
that it is fitted correctly and secure.
(400C). If there is any undue noise or knocking
6.4 Fan Operating Limits from bearing, replace both bearings. Fan
bearing are grease for life, but larger units
The fan operating limits for forward curve with standard bearing require semi-annual
and airfoil fan are shown on the Table 3. or annual lubrication at bearing greasing
Total static pressure should be limited to nipple. Recommended lubricants are
1000 Pa for forward curve and 1500 Pa for Standard Din 51823, K3N or ISO XM2.
backward curve/airfoil fan.
Table 3 - Fan Operating limits 7.2 Drive Belt
Backward
Forward Curved Belts that are split or have frayed edges or
Blower Curve/Airfoil
Size Max. Max. Max. Max. any other sign of damage (rubber shred
RPM kW RPM kW on floor) must be replaced in full set.
200 3800 3 5700 2
225 3400 4 5400 3
250 2600 4 4400 3 IMPORTANT
280 2400 6 3900 4 DURING MAINTENANCE AND
315 2100 6 3500 5 SERVICING, UNIT MUST BE
355 1900 8 3100 6
400 1700 8 2700 8
COMPLETELY ISOLATED AND
450 1400 10 2500 11 PRECAUTIONS TAKEN TO PREVENT
500 1200 11 2200 11 ACCIDENT FROM HAPPENING.
560 1100 15 1900 15
630 900 15 1700 15 Check the belt tension and alignment, re-
710 850 25 1500 30 tension and re-align if necessary. Refer to
800 750 25 1350 30
900 650 30 1150 35
Section 5.7 for belt tensioning procedure.
1000 600 30 1050 35 New belt drive must be re-tensioned after
the first 48 hours of operation.
6.5 Installation of VRV AHU Control For replacement of belts, remove the belt
Box (EKEQ) guard before starting work. To change the
belts, first loosen the adjusting screw and
For installation VRV AHU Control Box,
move the motor towards the fan to enable
please refer to the Installation And
old belts to be taken off and put on of
Operation Manual in VRV ED or refer to
new belts. (Matched belts must be used)
manufacturer for advices.
Tension the belts by following instruction
6.6 MicroTech III Commissioning at Section 5.7.
MicroTech III is an option. For
7.3 Coil Section
commissioning of MicroTech III, please
refer to the MicroTech III Commissioning Periodic cleaning of coils is required. Dirty
Manual in VRV ED or refer to coils have tendency to increase airside
manufacturer for advices. pressure drops and reduce cooling/heating
efficiency. Dry cleaning is done by using a
7. Maintenance powerful vacuum cleaner on the dust-
accumulated side. If coil is very dirty, coils
7.1 Fan / Motor need to be removed for wet cleaning by
Check for soiling, corrosion, damage and trained personnel. Ensure coil fins are not
tendency of excessive vibration. damage when performing dry/wet
Check that all bolts and nuts and flexible cleaning. In the event that fin edges have
connections are securely fixed. been bent, treat with aid of a coil comb.
- 14 -
Check that frost protection is working 7.4 Filter Section
before starting of each winter season.
During system start up, filters are likely to
Ensure the frost sensor is correctly
become rapidly blocked.
installed and working within desired
temperature range. Disposable filters and bag filters must be
For direct expansion coils, do not use hot replaced each time when pressure drop
water or steam to clean these coils. During reaches the indicated dirty condition by
normal operation, the fin block must not D.M. Manometer. Washable filters must be
be ice up. If this occurs, check the cleaned periodically.
refrigeration system.
7.5 Dampers
Check that drain pan and drain trap are
free from blockage and water Check for dirt accumulation, damage and
accumulation at pan. sign of corrosion. Clean with cloth or high
pressure air. Check damper blade turning
manually or central control for smooth
operation.
Table 4 - Recommended Maintenance intervals
Maintenance interval
Component Description Action
Weekly Monthly 3 Monthly 6 Monthly Yearly
- 15 -
7.6 Electric Heater 7.8 Moisture Eliminator
Check for dirt accumulation and clean if Check the dirt accumulation at the blades,
necessary with a soft brush. Check the remove and clean the blades if necessary.
safety control, cables and connections Ensure the blades are correctly positioned
operation. and not distorted.
8. Trouble Shooting
Use Table 5 to assist in trouble-shoot the
malfunction in Air Handling Unit operation.
- 16 -
c) Over-lubricant. c) Purge and clean surface.
d) Misaligned bearing. d) Check & re-align shaft.
Water present in cooling a) Drain trap clog. a) Clean & clear clog.
coil drain pan or overflow b) Incorrect hydraulic trapping. b) Resize trap and check air break
arrangement.
Premature drive belts a) Improper tension or alignment. a) Check tension and alignment.
failure b) Incorrect belt being fitted. b) Replace with full set.
c) Dirt or grease on belts. c) Clean belt & pulley, check for grease
d) Belt rubbing. leak.
e) Worn sheaves. d) Remove obstruction.
e) Replace sheaves.
Belt swelling or softening a) Excessive contamination by oil, certain a) Replace with full set. Isolate the source
cutting fluids or rubber solvent. of contaminate.
Belt whipping during a) Incorrect tensioning. a) Re-tension belts.
running
Filter collapsing a) Filter block with dirt. a) Replace at advised dirty condition.
b) Air velocity too high. b) Check unit running conditions.
Note: The table is intended as a diagnostic aid.
9. Appendix
9.1 Assembly of heat wheel
1. Heat wheel unit bottom section has already assembled with heat wheel support assembly
and heat wheel baffle bottom when delivered.
2. Placed the baffle centre to the penta-post / centre-post or panel.
3. Placed the heat wheel on the heat wheel support assembly in the bottom section from
opening on top/side, depends on the design.
4. Screw the heat wheel to the heat wheel support assy. by using self-drilling screws.
5. screwed the heat wheel baffle left/right and centre
6. Assemble the top cabinet section to the bottom section. If required, remove some panel to
facilitate assembly work of heat wheel. Screw the baffle left/right and centre to top section
cabinet.
7. Assemble the heat wheel baffle top.
8. Assembled back the remaining panels.
- 17 -