MODBUS Connection C5 en
MODBUS Connection C5 en
C5
EN
Modbus RTU protocol works via RS485 interface, connection is provided to terminals 1,2,3 of the C5 controller (Pic.
1). Default interface settings and ID are as follows:
Baudrate 19200
Word length 8
Parity EVEN
Stop bits 1
Modbus ID 1
These settings can be changed using laptop connected to webserver (Pic. 2). To connect devices use twisted pair
cable. Maximum cable length is 150m. Connect GND cables together, if distance between the RS485 interfaces is more
than 10m.
Modbus TCP protocol uses Ethernet interface, connection is provided to RJ-45 socket (Pic.1) on the C5 controller
(CAT5 cable is recommended). The maximum cable length between device and C5 controller board must not exceed
100m. Default IP address is 192.168.0.50, port 502. The IP address can be changed using laptop connected to webserver
(Pic. 2) or control panel (Pic. 3).
1 - RS 485 B
2 - RS 485 A
3 - GND
Ethernet
RJ45, 10Mbit
service Logout
Overview CONFIGURATION
FIRMWARE
LANGUAGES
Modes
SETTINGS RESET
DATE/TIME
Functions
CONNECTIVITY
Save
UAB KOMFOVENT we reserve the right to make changes without prior notice
2 Modbus_connection_C5_22-10
OPERATION
On/Off 1, 2000
Operation mode selection 100 Extract temperature
Operation mode settings 101-126 Setpoint 2032
Flow control mode 127 Actual 2007
Flow units 459
Temperature control mode 128
Active functions 2217 Extract air filter
Function settings 501-545 Impurity level 2208
Active alarm count/reset 1000 Filter status 2853
Clean calibration 18002
Exhaust temperature
Actual 2009 Air-quality sensor
Sensor type 545, 2013
Extract airflow Setpoint 501, 503
Setpoint Actual 2014
2038-2039
Actual 2004-2005
Fan level 2022 Supply temperature
Setpoint 2033
Actual 2006
OUTDOOR ROOM
Supply airflow
Setpoint 2036-2037
Actual 2002-2003
Fan level 2021
UAB KOMFOVENT we reserve the right to make changes without prior notice
Modbus_connection_C5_22-10 3
EN
MODES
Modbus Data
Description Data values
register Type Access Range Default
Comfort1: Setpoint
105 int R/W 50-400 210 200 => 20,0C
temperature
Comfort2: Setpoint
110 int R/W 50-400 210 200 => 20,0C
temperature
Economy1: Setpoint
115 int R/W 50-400 200 200 => 20,0C
temperature
Economy2: Setpoint
120 int R/W 50-400 190 200 => 20,0C
temperature
Special: Setpoint
125 int R/W 50-400 210 200 => 20,0C
temperature
127 int R/W 0-1 0 Flow control mode 0-CAV, 1-VAV, 2 - DCV
128 int R/W 0-2 0 Temp. control mode 0-Supply, 1-Extract, 2-Room
130 int R/W 100-5000 500 VAV sensors range 500 => 500Pa
UAB KOMFOVENT we reserve the right to make changes without prior notice
4 Modbus_connection_C5_22-10
OPERATION PROGRAM
Modbus Data
Description Data values
register Type Access Range Default
201 int8x2 R/W 0:00-23:59 0:00 Event01: Start time 0x0805 => 8:05
202 int8x2 R/W 0:00-24:00 0:00 Event01: Stop time 0x0805 => 8:05
205 int8x2 R/W 0:00-23:59 0:00 Event02: Start time 0x0805 => 8:05
206 int8x2 R/W 0:00-24:00 0:00 Event02: Stop time 0x0805 => 8:05
209 int8x2 R/W 0:00-23:59 0:00 Event03: Start time 0x0805 => 8:05
210 int8x2 R/W 0:00-24:00 0:00 Event03: Stop time 0x0805 => 8:05
213 int8x2 R/W 0:00-23:59 0:00 Event04: Start time 0x0805 => 8:05
214 int8x2 R/W 0:00-24:00 0:00 Event04: Stop time 0x0805 => 8:05
217 int8x2 R/W 0:00-23:59 0:00 Event05: Start time 0x0805 => 8:05
218 int8x2 R/W 0:00-24:00 0:00 Event05: Stop time 0x0805 => 8:05
221 int8x2 R/W 0:00-23:59 0:00 Event06: Start time 0x0805 => 8:05
222 int8x2 R/W 0:00-24:00 0:00 Event06: Stop time 0x0805 => 8:05
225 int8x2 R/W 0:00-23:59 0:00 Event07: Start time 0x0805 => 8:05
226 int8x2 R/W 0:00-24:00 0:00 Event07: Stop time 0x0805 => 8:05
UAB KOMFOVENT we reserve the right to make changes without prior notice
Modbus_connection_C5_22-10 5
EN
OPERATION PROGRAM
Modbus Data
Description Data values
register Type Access Range Default
229 int8x2 R/W 0:00-23:59 0:00 Event08: Start time 0x0805 => 8:05
230 int8x2 R/W 0:00-24:00 0:00 Event08: Stop time 0x0805 => 8:05
233 int8x2 R/W 0:00-23:59 0:00 Event09: Start time 0x0805 => 8:05
234 int8x2 R/W 0:00-24:00 0:00 Event09: Stop time 0x0805 => 8:05
237 int8x2 R/W 0:00-23:59 0:00 Event10: Start time 0x0805 => 8:05
238 int8x2 R/W 0:00-24:00 0:00 Event10: Stop time 0x0805 => 8:05
241 int8x2 R/W 0:00-23:59 0:00 Event11: Start time 0x0805 => 8:05
242 int8x2 R/W 0:00-24:00 0:00 Event11: Stop time 0x0805 => 8:05
245 int8x2 R/W 0:00-23:59 0:00 Event12: Start time 0x0805 => 8:05
246 int8x2 R/W 0:00-24:00 0:00 Event12: Stop time 0x0805 => 8:05
249 int8x2 R/W 0:00-23:59 0:00 Event13: Start time 0x0805 => 8:05
250 int8x2 R/W 0:00-24:00 0:00 Event13: Stop time 0x0805 => 8:05
253 int8x2 R/W 0:00-23:59 0:00 Event14: Start time 0x0805 => 8:05
UAB KOMFOVENT we reserve the right to make changes without prior notice
6 Modbus_connection_C5_22-10
OPERATION PROGRAM
Modbus Data
Description Data values
register Type Access Range Default
254 int8x2 R/W 0:00-24:00 0:00 Event14: Stop time 0x0805 => 8:05
257 int8x2 R/W 0:00-23:59 0:00 Event15: Start time 0x0805 => 8:05
258 int8x2 R/W 0:00-24:00 0:00 Event15: Stop time 0x0805 => 8:05
261 int8x2 R/W 0:00-23:59 0:00 Event16: Start time 0x0805 => 8:05
262 int8x2 R/W 0:00-24:00 0:00 Event16: Stop time 0x0805 => 8:05
265 int8x2 R/W 0:00-23:59 0:00 Event17: Start time 0x0805 => 8:05
266 int8x2 R/W 0:00-24:00 0:00 Event17: Stop time 0x0805 => 8:05
269 int8x2 R/W 0:00-23:59 0:00 Event18: Start time 0x0805 => 8:05
270 int8x2 R/W 0:00-24:00 0:00 Event18: Stop time 0x0805 => 8:05
273 int8x2 R/W 0:00-23:59 0:00 Event19: Start time 0x0805 => 8:05
274 int8x2 R/W 0:00-24:00 0:00 Event19: Stop time 0x0805 => 8:05
277 int8x2 R/W 0:00-23:59 0:00 Event20: Start time 0x0805 => 8:05
278 int8x2 R/W 0:00-24:00 0:00 Event20: Stop time 0x0805 => 8:05
UAB KOMFOVENT we reserve the right to make changes without prior notice
Modbus_connection_C5_22-10 7
EN
HOLLYDAY SCHEDULE
Modbus Data
Description Data values
register Type Access Range Default
301 int8x2 R/W 01.01-12.31 Event01: Start date 0x020C => Feb12
303 int8x2 R/W 01.01-12.31 Event01: Stop date 0x020C => Feb12
306 int8x2 R/W 01.01-12.31 Event02: Start date 0x020C => Feb12
308 int8x2 R/W 01.01-12.31 Event02: Stop date 0x020C => Feb12
311 int8x2 R/W 01.01-12.31 Event03: Start date 0x020C => Feb12
313 int8x2 R/W 01.01-12.31 Event03: Stop date 0x020C => Feb12
316 int8x2 R/W 01.01-12.31 Event04: Start date 0x020C => Feb12
318 int8x2 R/W 01.01-12.31 Event04: Stop date 0x020C => Feb12
321 int8x2 R/W 01.01-12.31 Event05: Start date 0x020C => Feb12
323 int8x2 R/W 01.01-12.31 Event05: Stop date 0x020C => Feb12
326 int8x2 R/W 01.01-12.31 Event06: Start date 0x020C => Feb12
UAB KOMFOVENT we reserve the right to make changes without prior notice
8 Modbus_connection_C5_22-10
HOLLYDAY SCHEDULE
Modbus Data
Description Data values
register Type Access Range Default
328 int8x2 R/W 01.01-12.31 Event06: Stop date 0x020C => Feb12
331 int8x2 R/W 01.01-12.31 Event07: Start date 0x020C => Feb12
333 int8x2 R/W 01.01-12.31 Event07: Stop date 0x020C => Feb12
336 int8x2 R/W 01.01-12.31 Event08: Start date 0x020C => Feb12
338 int8x2 R/W 01.01-12.31 Event08: Stop date 0x020C => Feb12
341 int8x2 R/W 01.01-12.31 Event09: Start date 0x020C => Feb12
343 int8x2 R/W 01.01-12.31 Event09: Stop date 0x020C => Feb12
346 int8x2 R/W 01.01-12.31 Event10: Start date 0x020C => Feb12
348 int8x2 R/W 01.01-12.31 Event10: Stop date 0x020C => Feb12
RECIRCULATION SCHEDULLE
Modbus Data
Description Data values
register Type Access Range Default
401 int8x2 R/W 0:00-23:59 0:00 Event01: Start time 0x0805 => 8:05
UAB KOMFOVENT we reserve the right to make changes without prior notice
Modbus_connection_C5_22-10 9
EN
RECIRCULATION SCHEDULLE
Modbus Data
Description Data values
register Type Access Range Default
402 int8x2 R/W 0:00-24:00 0:00 Event01: Stop time 0x0805 => 8:05
405 int8x2 R/W 0:00-23:59 0:00 Event02: Start time 0x0805 => 8:05
406 int8x2 R/W 0:00-24:00 0:00 Event02: Stop time 0x0805 => 8:05
409 int8x2 R/W 0:00-23:59 0:00 Event03: Start time 0x0805 => 8:05
410 int8x2 R/W 0:00-24:00 0:00 Event03: Stop time 0x0805 => 8:05
413 int8x2 R/W 0:00-23:59 0:00 Event04: Start time 0x0805 => 8:05
414 int8x2 R/W 0:00-24:00 0:00 Event04: Stop time 0x0805 => 8:05
417 int8x2 R/W 0:00-23:59 0:00 Event05: Start time 0x0805 => 8:05
418 int8x2 R/W 0:00-24:00 0:00 Event05: Stop time 0x0805 => 8:05
SETTINGS
Modbus Data
Description Data values
register Type Access Range Default
452 int R 1-7 7 Day of week 1-Mon, 2-Tue, 3-Wed, 4-Thu, 5-Fri, 6-Sat, 7-Sun
UAB KOMFOVENT we reserve the right to make changes without prior notice
10 Modbus_connection_C5_22-10
SETTINGS
Modbus Data
Description Data values
register Type Access Range Default
459 int R/W 0-3 0 Flow units 0-m3/h, 1-l/s, 2-m3/s, 3-Pa
FUNCTIONS
Modbus Data
Description Data values
register Type Access Range Default
Outdoor comp.
505 int R/W 0..1 0 ventilation: Enable/ 0-Disable, 1-Enable
Disable
Outdoor comp.
506 int R/W -400..500 -400 ventilation: Winter -150 => -15.0C
comp. stop
Outdoor comp.
507 int R/W -400..500 0 ventilation: Winter -150 => -15.0C
comp. start
Outdoor comp.
508 int R/W -400..500 200 ventilation: Summer 250 => 25.0C
comp. start
Outdoor comp.
509 int R/W -400..500 500 ventilation: Summer 250 => 25.0C
comp. stop
Min. temperature
510 int R/W 0..1 0 0-Disable, 1-Enable
control: Enable/Disable
Min. temperature
511 int R/W -400..500 150 -150 => -15.0C
control: Setpoint
Override function:
512 int R/W 0..1 1 0-Disable, 1-Enable
Enable/Disable
Override function:
513 int R/W 0..2 0 0-All time, 1-If on, 2-If off
Override type
UAB KOMFOVENT we reserve the right to make changes without prior notice
Modbus_connection_C5_22-10 11
EN
FUNCTIONS
Modbus Data
Description Data values
register Type Access Range Default
Operation on demand:
517 int R/W 0..1 0 0-Disable, 1-Enable
Enable/Disable
Operation on demand:
518 int R/W 200..1800 150 200..1800ppm, 10..90%, 10..90%RH, 5..45C
Setpoint
Recirculation control:
519 int R/W 0..1 0 0-Disable, 1-Enable
Enable/Disable
Recirculation control:
520 int R/W 200..1800 600 200..1800ppm, 10..90%, 10..90%RH, 5..45C
Setpoint
Recirculation control:
521 int R/W 0..80 30
Min. fresh air
Recirculation control:
522 int R/W -400..500 -400 Winter recirculation -150 => -15.0C
end
Recirculation control:
523 int R/W -400..500 0 Winter recirculation -150 => -15.0C
start
Recirculation control:
524 int R/W -400..500 200 Summer recirculation 250 => 25.0C
start
Recirculation control:
525 int R/W -400..500 500 Summer recirculation 250 => 25.0C
end
Recirculation control:
526 int R/W 0..100 0
Default recirculation
Recirculation control:
527 int R/W 0..100 60
Activated recirculation
Humidity control:
528 int R/W 0..1 0 0-Disable, 1-Enable
Enable/Disable
Humidity control:
529 int R/W 10..90 1000 10..90%RH
Setpoint 1
Humidity control:
531 int R/W 10..90 1000 10..90%RH
Setpoint 2
Recirculation control:
534 int R/W 200..1800 900 200..1800ppm, 10..90%, 10..90%RH, 5..45C
Setpoint 2
Recirculation control:
536 int R/W 0..100 20
Min. fresh air 2
Inspection lighting:
538 bin R/W 0..1 0
Enable/Disable
Additional zone 1:
539 bin R/W 0..1 0
Enable/Disable
Additional zone 1:
540 int R/W -400..400 210 200 => 20,0C
Setpoint
Additional zone 2:
541 bin R/W 0..1 0
Enable/Disable
UAB KOMFOVENT we reserve the right to make changes without prior notice
12 Modbus_connection_C5_22-10
FUNCTIONS
Modbus Data
Description Data values
register Type Access Range Default
Additional zone 2:
542 int R/W -400..400 210 200 => 20,0C
Setpoint
External room 200 => 20.0C. Overrides extract flow temperature sensor for
543 int R/W -500..1200 -32768
temperature sensor temperature control only when written value is in range
545 int R/W 0..4 0 Air quality sensor type 0 – CO2, 1 – VOCq, 2 – VOCp, 3 – RH, 4 – temperature
548 int R/W 0..1 0 Humidity control: Type 0 - Relative humidity, 1 - Absolute humidity
ALARMS
Modbus Data
Description Data values
register Type Access Range Default
Alarm1(newest)
1102 int8x2 R 01.01-12.31 - 0x020C => Feb12
month-day
Alarm1(newest)
1104 int R 0..59 -
seconds
UAB KOMFOVENT we reserve the right to make changes without prior notice
Modbus_connection_C5_22-10 13
EN
ALARMS
Modbus Data
Description Data values
register Type Access Range Default
MONITORING DATA
Modbus Data
Description Data values
register Type Access Range Default
C5 Start/Stop current
2000 int R 0-2 - 0-Stop, 1-Enabled but fans are stopped, 2-Running
status
2002-2003 int R - - Current supply flow 3500 => 3500 m3/h, 3.500 m3/s, 3500 l/s
2004-2005 int R - - Current exhaust flow 3500 => 3500 m3/h, 3.500 m3/s, 3500 l/s
Current outdoor
2008 int R -500..1200 - 250 => 25.0C
temp., C
Current exhaust
2009 int R -500..1200 - 250 => 25.0C
temp., C
2013 int R 0..4 - Air quality sensor type 0-CO2, 1-VOCq, 2-VOCp, 3-RH, 4-TMP
UAB KOMFOVENT we reserve the right to make changes without prior notice
14 Modbus_connection_C5_22-10
MONITORING DATA
Modbus Data
Description Data values
register Type Access Range Default
Current temp.
2032 int R 50..400 - 250 => 25.0C
setpoint, C
Additional zone 1:
2041 int R -500..1200 - 250 => 25.0C
current supply temp., C
Additional zone 1:
2042 int R -500..1200 - current return water 250 => 25.0C
temp., C
Additional zone 2:
2043 int R -500..1200 - 250 => 25.0C
current supply temp., C
Additional zone 2:
2044 int R -500..1200 - current return water 250 => 25.0C
temp., C
UAB KOMFOVENT we reserve the right to make changes without prior notice
Modbus_connection_C5_22-10 15
EN
MONITORING DATA
Modbus Data
Description Data values
register Type Access Range Default
Heat exchanger
2201 int R 0..100, 255 - 255 - Unavailable
thermal efficiency, %
Heat exchanger
2203-2204 int R - 2500 => 2.5kW (0xFFFFFFFF - Unavailable)
recovery, W
Heat exchanger
2220-2221 int R 0..4’000’000 -
operation, kWh
Modbus Data
Description Data values
register Type Access Range Default
Electric heater: heater 0..1200 when NTC sensor is selected, 0-1000 when TK70
2304 int R 0..1200 -
temperature sensor is selected
2307 bin R - - Electric heater: alarms b2 – TK60 alarm, b1 – TK70 alarm, b0 – TK100 alarm
UAB KOMFOVENT we reserve the right to make changes without prior notice
16 Modbus_connection_C5_22-10
MONITORING DATA ZONE 1
Modbus Data
Description Data values
register Type Access Range Default
2320 int R -1000..1000 - DX level unit: level > 0 – heating, < 0 – cooling, -32768 – forced stop
DX modulated unit:
2331 int R 0..1000 -
cooler level
DX modulated unit:
2335 bin R - - b2 – heating, b1 – cooling, b0 – operation
control outputs
DX modulated unit:
2336 bin R - - b0 – external error
inputs
DX modulated unit:
2337 bin R - - b0 – external error alarm
alarms
Modbus Data
Description Data values
register Type Access Range Default
UAB KOMFOVENT we reserve the right to make changes without prior notice
Modbus_connection_C5_22-10 17
EN
Modbus Data
Description Data values
register Type Access Range Default
Electric heater: heater 0..1200 when NTC sensor is selected, 0-1000 when TK70
2404 int R 0..1200 -
temperature sensor is selected
2407 bin R - - Electric heater: alarms b2 – TK60 alarm, b1 – TK70 alarm, b0 – TK100 alarm
2420 int R -1000..1000 - DX level unit: level > 0 – heating, < 0 – cooling, -32768 – forced stop
DX modulated unit:
2431 int R 0..1000 -
cooler level
DX modulated unit:
2435 bin R - - b2 – heating, b1 – cooling, b0 – operation
control outputs
DX modulated unit:
2436 bin R - - b0 – external error
inputs
DX modulated unit:
2437 bin R - - b0 – external error alarm
alarms
UAB KOMFOVENT we reserve the right to make changes without prior notice
18 Modbus_connection_C5_22-10
SERVICE
Modbus Data
Description Data values
register Type Access Range Default
Settings reset to
902 bin R/W 0 b3-485_Config, b2-IP+Mask, b1-Flow_mode, b0-Temp_mode
default
Digital input:
2852 bin R 0..1 - For AHU without filter pressure sensors. 0-Clean, 1-Dirty
Outdoor filter
Digital input:
2853 bin R 0..1 - For AHU without filter pressure sensors. 0-Clean, 1-Dirty
Extract filter
Controller firmware
18004 int R 0..9999 -
version
18005 int R/W 0..1000 0 Service time counter 0..100.0%, Write 0x99C5 to reset
UAB KOMFOVENT we reserve the right to make changes without prior notice
Modbus_connection_C5_22-10 19
UAB KOMFOVENT PARTNERS