The document discusses the Modbus connection for a C5 controller. It supports Modbus RTU via an RS485 interface connected to terminals 1,2,3 with default settings of 19200 baud, 8 data bits, even parity, 1 stop bit, and ID 1. Modbus TCP uses the Ethernet interface via an RJ45 port. Default IP is 192.168.0.50 port 502. Tables list available Modbus registers for modes, functions, alarms/status, inputs/outputs, and settings.

Uploaded by

Lander
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
279 views20 pages

MODBUS Connection C5 en

The document discusses the Modbus connection for a C5 controller. It supports Modbus RTU via an RS485 interface connected to terminals 1,2,3 with default settings of 19200 baud, 8 data bits, even parity, 1 stop bit, and ID 1. Modbus TCP uses the Ethernet interface via an RJ45 port. Default IP is 192.168.0.50 port 502. Tables list available Modbus registers for modes, functions, alarms/status, inputs/outputs, and settings.

Uploaded by

Lander
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

Modbus connection

C5
EN

C5 controller supports Modbus RTU and Modbus TCP/IP protocols

Modbus RTU protocol works via RS485 interface, connection is provided to terminals 1,2,3 of the C5 controller (Pic.
1). Default interface settings and ID are as follows:
Baudrate 19200
Word length 8
Parity EVEN
Stop bits 1
Modbus ID 1

These settings can be changed using laptop connected to webserver (Pic. 2). To connect devices use twisted pair
cable. Maximum cable length is 150m. Connect GND cables together, if distance between the RS485 interfaces is more
than 10m.
Modbus TCP protocol uses Ethernet interface, connection is provided to RJ-45 socket (Pic.1) on the C5 controller
(CAT5 cable is recommended). The maximum cable length between device and C5 controller board must not exceed
100m. Default IP address is 192.168.0.50, port 502. The IP address can be changed using laptop connected to webserver
(Pic. 2) or control panel (Pic. 3).
1 - RS 485 B
2 - RS 485 A
3 - GND

Ethernet
RJ45, 10Mbit

Picture 1. C5 controller board

service Logout

Overview CONFIGURATION
FIRMWARE
LANGUAGES
Modes
SETTINGS RESET
DATE/TIME
Functions
CONNECTIVITY

Alarms/Status IP 192 . 168 . 0 . 50


IP mask 255 . 255 . 0 .0
Inputs/Outputs
Modbus ID 1

Settings RS-485 19200 baud 8E1


BACnet port 47808
BACnet ID 1100
TEMPERATURE SENSORS

Save

Picture 2. Connectivity settings

UAB KOMFOVENT we reserve the right to make changes without prior notice
2 Modbus_connection_C5_22-10
OPERATION
On/Off 1, 2000
Operation mode selection 100 Extract temperature
Operation mode settings 101-126 Setpoint 2032
Flow control mode 127 Actual 2007
Flow units 459
Temperature control mode 128
Active functions 2217 Extract air filter
Function settings 501-545 Impurity level 2208
Active alarm count/reset 1000 Filter status 2853
Clean calibration 18002
Exhaust temperature
Actual 2009 Air-quality sensor
Sensor type 545, 2013
Extract airflow Setpoint 501, 503
Setpoint Actual 2014
2038-2039
Actual 2004-2005
Fan level 2022 Supply temperature
Setpoint 2033
Actual 2006

OUTDOOR ROOM

Outdoor air filter


Impurity level 2207 Air heaters/coolers
Filter status 2852 Electrical heater level 2025
Clean calibration 18002
Water heater level 2016
DX level 2027
Outdoor temperature Heat-pump level 2026
Actual 2008 Water cooler level 2017
Additional zone 1 2041-2042,
Heat exchanger 2300-2323
Level 2019
Efficiency Additional zone 2 2043-2044,
2201
2325-2337
Internal supply temperature
Actual 2040 Return water temperature
Actual 2010

Supply airflow
Setpoint 2036-2037
Actual 2002-2003
Fan level 2021

UAB KOMFOVENT we reserve the right to make changes without prior notice
Modbus_connection_C5_22-10 3
EN

Following tables lists available Modbus registers

MODES

Modbus Data
Description Data values
register Type Access Range Default

1 int R/W 0-1 0 AHU On/Off control 0-Off, 1-On

Operation mode 1-Comfort1, 2-Comfort2, 3-Economy1, 4-Economy2,


100 int R/W 1-6 1
selection 5-Special, 6-Program

Auto-correction to be within allowed range (20-100% of


101-102 int32 R/W - - Comfort1: Supply flow
maximum supply flow or 0)

Auto-correction to be within allowed range (20-100% of


103-104 int32 R/W - - Comfort1: Extract flow
maximum extract flow or 0)

Comfort1: Setpoint
105 int R/W 50-400 210 200 => 20,0C
temperature

Auto-correction to be within allowed range (20-100% of


106-107 int32 R/W - - Comfort2: Supply flow
maximum supply flow or 0)

Auto-correction to be within allowed range (20-100% of


108-109 int32 R/W - - Comfort2: Extract flow
maximum extract flow or 0)

Comfort2: Setpoint
110 int R/W 50-400 210 200 => 20,0C
temperature

Auto-correction to be within allowed range (20-100% of


111-112 int32 R/W - - Economy1: Supply flow
maximum supply flow or 0)

Auto-correction to be within allowed range (20-100% of


113-114 int32 R/W - - Economy1: Extract flow
maximum extract flow or 0)

Economy1: Setpoint
115 int R/W 50-400 200 200 => 20,0C
temperature

Auto-correction to be within allowed range (20-100% of


116-117 int32 R/W - - Economy2: Supply flow
maximum supply flow or 0)

Auto-correction to be within allowed range (20-100% of


118-119 int32 R/W - - Economy2: Extract flow
maximum extract flow or 0)

Economy2: Setpoint
120 int R/W 50-400 190 200 => 20,0C
temperature

Auto-correction to be within allowed range (20-100% of


121-122 int32 R/W - - Special: Supply flow
maximum supply flow or 0)

Auto-correction to be within allowed range (20-100% of


123-124 int32 R/W - - Special: Extract flow
maximum extract flow or 0)

Special: Setpoint
125 int R/W 50-400 210 200 => 20,0C
temperature

b4-Dehumidifying, b3-Humidifying, b2-Recirculation, b1-


126 bin R/W - 31 Special: Configuration
Cooling, b0-Heating (1-Enable, 0-Disable)

127 int R/W 0-1 0 Flow control mode 0-CAV, 1-VAV, 2 - DCV

128 int R/W 0-2 0 Temp. control mode 0-Supply, 1-Extract, 2-Room

0-Not calibrated, 1-Calibrating, 2-Supply, 3-Extract,


129 int R/W 0-4 0 VAV status/calibration
4-Double. Write 0x99C5 to start VAV calibration

130 int R/W 100-5000 500 VAV sensors range 500 => 500Pa

Nominal supply Auto-correction to be within allowed range (0-90% of VAV


131 int R/W 0-4500 0
pressure sensors range)

Nominal exhaust Auto-correction to be within allowed range (0-90% of VAV


132 int R/W 0-4500 0
pressure sensors range)

UAB KOMFOVENT we reserve the right to make changes without prior notice
4 Modbus_connection_C5_22-10
OPERATION PROGRAM

Modbus Data
Description Data values
register Type Access Range Default

b6-Sun, b5-Sat, b4-Fri, b3-Thu, b2-Wed, b1-Tue, b0-Mon


200 bin R/W - 0 Event01: Days
(1-Select, 0-Deselect)

201 int8x2 R/W 0:00-23:59 0:00 Event01: Start time 0x0805 => 8:05

202 int8x2 R/W 0:00-24:00 0:00 Event01: Stop time 0x0805 => 8:05

0-Standby,1-Comfort1, 2-Comfort2, 3-Economy1,


203 int R/W 0-5 0 Event01: Mode
4-Economy2, 5-Special

b6-Sun, b5-Sat, b4-Fri, b3-Thu, b2-Wed, b1-Tue, b0-Mon


204 bin R/W - 0 Event02: Days
(1-Select, 0-Deselect)

205 int8x2 R/W 0:00-23:59 0:00 Event02: Start time 0x0805 => 8:05

206 int8x2 R/W 0:00-24:00 0:00 Event02: Stop time 0x0805 => 8:05

0-Standby,1-Comfort1, 2-Comfort2, 3-Economy1,


207 int R/W 0-5 0 Event02: Mode
4-Economy2, 5-Special

b6-Sun, b5-Sat, b4-Fri, b3-Thu, b2-Wed, b1-Tue, b0-Mon


208 bin R/W - 0 Event03: Days
(1-Select, 0-Deselect)

209 int8x2 R/W 0:00-23:59 0:00 Event03: Start time 0x0805 => 8:05

210 int8x2 R/W 0:00-24:00 0:00 Event03: Stop time 0x0805 => 8:05

0-Standby,1-Comfort1, 2-Comfort2, 3-Economy1,


211 int R/W 0-5 0 Event03: Mode
4-Economy2, 5-Special

b6-Sun, b5-Sat, b4-Fri, b3-Thu, b2-Wed, b1-Tue, b0-Mon


212 bin R/W - 0 Event04: Days
(1-Select, 0-Deselect)

213 int8x2 R/W 0:00-23:59 0:00 Event04: Start time 0x0805 => 8:05

214 int8x2 R/W 0:00-24:00 0:00 Event04: Stop time 0x0805 => 8:05

0-Standby,1-Comfort1, 2-Comfort2, 3-Economy1,


215 int R/W 0-5 0 Event04: Mode
4-Economy2, 5-Special

b6-Sun, b5-Sat, b4-Fri, b3-Thu, b2-Wed, b1-Tue, b0-Mon


216 bin R/W - 0 Event05: Days
(1-Select, 0-Deselect)

217 int8x2 R/W 0:00-23:59 0:00 Event05: Start time 0x0805 => 8:05

218 int8x2 R/W 0:00-24:00 0:00 Event05: Stop time 0x0805 => 8:05

0-Standby,1-Comfort1, 2-Comfort2, 3-Economy1,


219 int R/W 0-5 0 Event05: Mode
4-Economy2, 5-Special

b6-Sun, b5-Sat, b4-Fri, b3-Thu, b2-Wed, b1-Tue, b0-Mon


220 bin R/W - 0 Event06: Days
(1-Select, 0-Deselect)

221 int8x2 R/W 0:00-23:59 0:00 Event06: Start time 0x0805 => 8:05

222 int8x2 R/W 0:00-24:00 0:00 Event06: Stop time 0x0805 => 8:05

0-Standby,1-Comfort1, 2-Comfort2, 3-Economy1,


223 int R/W 0-5 0 Event06: Mode
4-Economy2, 5-Special

b6-Sun, b5-Sat, b4-Fri, b3-Thu, b2-Wed, b1-Tue, b0-Mon


224 bin R/W - 0 Event07: Days
(1-Select, 0-Deselect)

225 int8x2 R/W 0:00-23:59 0:00 Event07: Start time 0x0805 => 8:05

226 int8x2 R/W 0:00-24:00 0:00 Event07: Stop time 0x0805 => 8:05

UAB KOMFOVENT we reserve the right to make changes without prior notice
Modbus_connection_C5_22-10 5
EN

OPERATION PROGRAM

Modbus Data
Description Data values
register Type Access Range Default

0-Standby,1-Comfort1, 2-Comfort2, 3-Economy1,


227 int R/W 0-5 0 Event07: Mode
4-Economy2, 5-Special

b6-Sun, b5-Sat, b4-Fri, b3-Thu, b2-Wed, b1-Tue, b0-Mon


228 bin R/W - 0 Event08: Days
(1-Select, 0-Deselect)

229 int8x2 R/W 0:00-23:59 0:00 Event08: Start time 0x0805 => 8:05

230 int8x2 R/W 0:00-24:00 0:00 Event08: Stop time 0x0805 => 8:05

0-Standby,1-Comfort1, 2-Comfort2, 3-Economy1,


231 int R/W 0-5 0 Event08: Mode
4-Economy2, 5-Special

b6-Sun, b5-Sat, b4-Fri, b3-Thu, b2-Wed, b1-Tue, b0-Mon


232 bin R/W - 0 Event09: Days
(1-Select, 0-Deselect)

233 int8x2 R/W 0:00-23:59 0:00 Event09: Start time 0x0805 => 8:05

234 int8x2 R/W 0:00-24:00 0:00 Event09: Stop time 0x0805 => 8:05

0-Standby,1-Comfort1, 2-Comfort2, 3-Economy1,


235 int R/W 0-5 0 Event09: Mode
4-Economy2, 5-Special

b6-Sun, b5-Sat, b4-Fri, b3-Thu, b2-Wed, b1-Tue, b0-Mon


236 bin R/W - 0 Event10: Days
(1-Select, 0-Deselect)

237 int8x2 R/W 0:00-23:59 0:00 Event10: Start time 0x0805 => 8:05

238 int8x2 R/W 0:00-24:00 0:00 Event10: Stop time 0x0805 => 8:05

0-Standby,1-Comfort1, 2-Comfort2, 3-Economy1,


239 int R/W 0-5 0 Event10: Mode
4-Economy2, 5-Special

b6-Sun, b5-Sat, b4-Fri, b3-Thu, b2-Wed, b1-Tue, b0-Mon


240 bin R/W - 0 Event11: Days
(1-Select, 0-Deselect)

241 int8x2 R/W 0:00-23:59 0:00 Event11: Start time 0x0805 => 8:05

242 int8x2 R/W 0:00-24:00 0:00 Event11: Stop time 0x0805 => 8:05

0-Standby,1-Comfort1, 2-Comfort2, 3-Economy1,


243 int R/W 0-5 0 Event11: Mode
4-Economy2, 5-Special

b6-Sun, b5-Sat, b4-Fri, b3-Thu, b2-Wed, b1-Tue, b0-Mon


244 bin R/W - 0 Event12: Days
(1-Select, 0-Deselect)

245 int8x2 R/W 0:00-23:59 0:00 Event12: Start time 0x0805 => 8:05

246 int8x2 R/W 0:00-24:00 0:00 Event12: Stop time 0x0805 => 8:05

0-Standby,1-Comfort1, 2-Comfort2, 3-Economy1,


247 int R/W 0-5 0 Event12: Mode
4-Economy2, 5-Special

b6-Sun, b5-Sat, b4-Fri, b3-Thu, b2-Wed, b1-Tue, b0-Mon


248 bin R/W - 0 Event13: Days
(1-Select, 0-Deselect)

249 int8x2 R/W 0:00-23:59 0:00 Event13: Start time 0x0805 => 8:05

250 int8x2 R/W 0:00-24:00 0:00 Event13: Stop time 0x0805 => 8:05

0-Standby,1-Comfort1, 2-Comfort2, 3-Economy1,


251 int R/W 0-5 0 Event13: Mode
4-Economy2, 5-Special

b6-Sun, b5-Sat, b4-Fri, b3-Thu, b2-Wed, b1-Tue, b0-Mon


252 bin R/W - 0 Event14: Days
(1-Select, 0-Deselect)

253 int8x2 R/W 0:00-23:59 0:00 Event14: Start time 0x0805 => 8:05

UAB KOMFOVENT we reserve the right to make changes without prior notice
6 Modbus_connection_C5_22-10
OPERATION PROGRAM

Modbus Data
Description Data values
register Type Access Range Default

254 int8x2 R/W 0:00-24:00 0:00 Event14: Stop time 0x0805 => 8:05

0-Standby,1-Comfort1, 2-Comfort2, 3-Economy1,


255 int R/W 0-5 0 Event14: Mode
4-Economy2, 5-Special

b6-Sun, b5-Sat, b4-Fri, b3-Thu, b2-Wed, b1-Tue, b0-Mon


256 bin R/W - 0 Event15: Days
(1-Select, 0-Deselect)

257 int8x2 R/W 0:00-23:59 0:00 Event15: Start time 0x0805 => 8:05

258 int8x2 R/W 0:00-24:00 0:00 Event15: Stop time 0x0805 => 8:05

0-Standby,1-Comfort1, 2-Comfort2, 3-Economy1,


259 int R/W 0-5 0 Event15: Mode
4-Economy2, 5-Special

b6-Sun, b5-Sat, b4-Fri, b3-Thu, b2-Wed, b1-Tue, b0-Mon


260 bin R/W - 0 Event16: Days
(1-Select, 0-Deselect)

261 int8x2 R/W 0:00-23:59 0:00 Event16: Start time 0x0805 => 8:05

262 int8x2 R/W 0:00-24:00 0:00 Event16: Stop time 0x0805 => 8:05

0-Standby,1-Comfort1, 2-Comfort2, 3-Economy1,


263 int R/W 0-5 0 Event16: Mode
4-Economy2, 5-Special

b6-Sun, b5-Sat, b4-Fri, b3-Thu, b2-Wed, b1-Tue, b0-Mon


264 bin R/W - 0 Event17: Days
(1-Select, 0-Deselect)

265 int8x2 R/W 0:00-23:59 0:00 Event17: Start time 0x0805 => 8:05

266 int8x2 R/W 0:00-24:00 0:00 Event17: Stop time 0x0805 => 8:05

0-Standby,1-Comfort1, 2-Comfort2, 3-Economy1,


267 int R/W 0-5 0 Event17: Mode
4-Economy2, 5-Special

b6-Sun, b5-Sat, b4-Fri, b3-Thu, b2-Wed, b1-Tue, b0-Mon


268 bin R/W - 0 Event18: Days
(1-Select, 0-Deselect)

269 int8x2 R/W 0:00-23:59 0:00 Event18: Start time 0x0805 => 8:05

270 int8x2 R/W 0:00-24:00 0:00 Event18: Stop time 0x0805 => 8:05

0-Standby,1-Comfort1, 2-Comfort2, 3-Economy1,


271 int R/W 0-5 0 Event18: Mode
4-Economy2, 5-Special

b6-Sun, b5-Sat, b4-Fri, b3-Thu, b2-Wed, b1-Tue, b0-Mon


272 bin R/W - 0 Event19: Days
(1-Select, 0-Deselect)

273 int8x2 R/W 0:00-23:59 0:00 Event19: Start time 0x0805 => 8:05

274 int8x2 R/W 0:00-24:00 0:00 Event19: Stop time 0x0805 => 8:05

0-Standby,1-Comfort1, 2-Comfort2, 3-Economy1,


275 int R/W 0-5 0 Event19: Mode
4-Economy2, 5-Special

b6-Sun, b5-Sat, b4-Fri, b3-Thu, b2-Wed, b1-Tue, b0-Mon


276 bin R/W - 0 Event20: Days
(1-Select, 0-Deselect)

277 int8x2 R/W 0:00-23:59 0:00 Event20: Start time 0x0805 => 8:05

278 int8x2 R/W 0:00-24:00 0:00 Event20: Stop time 0x0805 => 8:05

0-Standby,1-Comfort1, 2-Comfort2, 3-Economy1,


279 int R/W 0-5 0 Event20: Mode
4-Economy2, 5-Special

UAB KOMFOVENT we reserve the right to make changes without prior notice
Modbus_connection_C5_22-10 7
EN

HOLLYDAY SCHEDULE

Modbus Data
Description Data values
register Type Access Range Default

300 int R/W 2010-2250   Event01: Start year  

301 int8x2 R/W 01.01-12.31   Event01: Start date 0x020C => Feb12

302 int R/W 2010-2250   Event01: Stop year  

303 int8x2 R/W 01.01-12.31   Event01: Stop date 0x020C => Feb12

0-Standby, 1-Comfort1, 2-Comfort2, 3-Economy1,


304 int R/W 0-6   Event01: Mode
4-Economy2, 5-Special, 6-Program

305 int R/W 2010-2250   Event02: Start year  

306 int8x2 R/W 01.01-12.31   Event02: Start date 0x020C => Feb12

307 int R/W 2010-2250   Event02: Stop year  

308 int8x2 R/W 01.01-12.31   Event02: Stop date 0x020C => Feb12

0-Standby, 1-Comfort1, 2-Comfort2, 3-Economy1,


309 int R/W 0-6   Event02: Mode
4-Economy2, 5-Special, 6-Program

310 int R/W 2010-2250   Event03: Start year  

311 int8x2 R/W 01.01-12.31   Event03: Start date 0x020C => Feb12

312 int R/W 2010-2250   Event03: Stop year  

313 int8x2 R/W 01.01-12.31   Event03: Stop date 0x020C => Feb12

0-Standby, 1-Comfort1, 2-Comfort2, 3-Economy1,


314 int R/W 0-6   Event03: Mode
4-Economy2, 5-Special, 6-Program

315 int R/W 2010-2250   Event04: Start year  

316 int8x2 R/W 01.01-12.31   Event04: Start date 0x020C => Feb12

317 int R/W 2010-2250   Event04: Stop year  

318 int8x2 R/W 01.01-12.31   Event04: Stop date 0x020C => Feb12

0-Standby, 1-Comfort1, 2-Comfort2, 3-Economy1,


319 int R/W 0-6   Event04: Mode
4-Economy2, 5-Special, 6-Program

320 int R/W 2010-2250   Event05: Start year  

321 int8x2 R/W 01.01-12.31   Event05: Start date 0x020C => Feb12

322 int R/W 2010-2250   Event05: Stop year  

323 int8x2 R/W 01.01-12.31   Event05: Stop date 0x020C => Feb12

0-Standby, 1-Comfort1, 2-Comfort2, 3-Economy1,


324 int R/W 0-6   Event05: Mode
4-Economy2, 5-Special, 6-Program

325 int R/W 2010-2250   Event06: Start year  

326 int8x2 R/W 01.01-12.31   Event06: Start date 0x020C => Feb12

UAB KOMFOVENT we reserve the right to make changes without prior notice
8 Modbus_connection_C5_22-10
HOLLYDAY SCHEDULE

Modbus Data
Description Data values
register Type Access Range Default

327 int R/W 2010-2250   Event06: Stop year  

328 int8x2 R/W 01.01-12.31   Event06: Stop date 0x020C => Feb12

0-Standby, 1-Comfort1, 2-Comfort2, 3-Economy1,


329 int R/W 0-6   Event06: Mode
4-Economy2, 5-Special, 6-Program

330 int R/W 2010-2250   Event07: Start year  

331 int8x2 R/W 01.01-12.31   Event07: Start date 0x020C => Feb12

332 int R/W 2010-2250   Event07: Stop year  

333 int8x2 R/W 01.01-12.31   Event07: Stop date 0x020C => Feb12

0-Standby, 1-Comfort1, 2-Comfort2, 3-Economy1,


334 int R/W 0-6   Event07: Mode
4-Economy2, 5-Special, 6-Program

335 int R/W 2010-2250   Event08: Start year  

336 int8x2 R/W 01.01-12.31   Event08: Start date 0x020C => Feb12

337 int R/W 2010-2250   Event08: Stop year  

338 int8x2 R/W 01.01-12.31   Event08: Stop date 0x020C => Feb12

0-Standby, 1-Comfort1, 2-Comfort2, 3-Economy1,


339 int R/W 0-6   Event08: Mode
4-Economy2, 5-Special, 6-Program

340 int R/W 2010-2250   Event09: Start year  

341 int8x2 R/W 01.01-12.31   Event09: Start date 0x020C => Feb12

342 int R/W 2010-2250   Event09: Stop year  

343 int8x2 R/W 01.01-12.31   Event09: Stop date 0x020C => Feb12

0-Standby, 1-Comfort1, 2-Comfort2, 3-Economy1,


344 int R/W 0-6   Event09: Mode
4-Economy2, 5-Special, 6-Program

345 int R/W 2010-2250   Event10: Start year  

346 int8x2 R/W 01.01-12.31   Event10: Start date 0x020C => Feb12

347 int R/W 2010-2250   Event10: Stop year  

348 int8x2 R/W 01.01-12.31   Event10: Stop date 0x020C => Feb12

0-Standby, 1-Comfort1, 2-Comfort2, 3-Economy1,


349 int R/W 0-6   Event10: Mode
4-Economy2, 5-Special, 6-Program

RECIRCULATION SCHEDULLE

Modbus Data
Description Data values
register Type Access Range Default

b6-Sun, b5-Sat, b4-Fri, b3-Thu, b2-Wed, b1-Tue, b0-Mon


400 bin R/W - 0 Event01: Days
(1-Select, 0-Deselect)

401 int8x2 R/W 0:00-23:59 0:00 Event01: Start time 0x0805 => 8:05

UAB KOMFOVENT we reserve the right to make changes without prior notice
Modbus_connection_C5_22-10 9
EN

RECIRCULATION SCHEDULLE

Modbus Data
Description Data values
register Type Access Range Default

402 int8x2 R/W 0:00-24:00 0:00 Event01: Stop time 0x0805 => 8:05

403 int R/W 0..100 0 Event01: Level  

b6-Sun, b5-Sat, b4-Fri, b3-Thu, b2-Wed, b1-Tue, b0-Mon


404 bin R/W - 0 Event02: Days
(1-Select, 0-Deselect)

405 int8x2 R/W 0:00-23:59 0:00 Event02: Start time 0x0805 => 8:05

406 int8x2 R/W 0:00-24:00 0:00 Event02: Stop time 0x0805 => 8:05

407 int R/W 0..100 0 Event02: Level  

b6-Sun, b5-Sat, b4-Fri, b3-Thu, b2-Wed, b1-Tue, b0-Mon


408 bin R/W - 0 Event03: Days
(1-Select, 0-Deselect)

409 int8x2 R/W 0:00-23:59 0:00 Event03: Start time 0x0805 => 8:05

410 int8x2 R/W 0:00-24:00 0:00 Event03: Stop time 0x0805 => 8:05

411 int R/W 0..100 0 Event03: Level  

b6-Sun, b5-Sat, b4-Fri, b3-Thu, b2-Wed, b1-Tue, b0-Mon


412 bin R/W - 0 Event04: Days
(1-Select, 0-Deselect)

413 int8x2 R/W 0:00-23:59 0:00 Event04: Start time 0x0805 => 8:05

414 int8x2 R/W 0:00-24:00 0:00 Event04: Stop time 0x0805 => 8:05

415 int R/W 0..100 0 Event04: Level  

b6-Sun, b5-Sat, b4-Fri, b3-Thu, b2-Wed, b1-Tue, b0-Mon


416 bin R/W - 0 Event05: Days
(1-Select, 0-Deselect)

417 int8x2 R/W 0:00-23:59 0:00 Event05: Start time 0x0805 => 8:05

418 int8x2 R/W 0:00-24:00 0:00 Event05: Stop time 0x0805 => 8:05

419 int R/W 0..100 0 Event05: Level  

SETTINGS

Modbus Data
Description Data values
register Type Access Range Default

450 int8x2 R/W 0:00-23:59 0:00 Time 0x0805 => 8:05

451 int R/W 0-59 0 Seconds  

452 int R 1-7 7 Day of week 1-Mon, 2-Tue, 3-Wed, 4-Thu, 5-Fri, 6-Sat, 7-Sun

453 int8x2 R/W 01.01-12.31 01.01 Date 0x020C => Feb12

454 int R/W 2010-2250 2012 Year  

455 int R/W 0-3 0 Language 0-English,1-Lithuanian,2-Russian, 3-Polish

456 int R/W 1-247 1 Modbus address  

UAB KOMFOVENT we reserve the right to make changes without prior notice
10 Modbus_connection_C5_22-10
SETTINGS

Modbus Data
Description Data values
register Type Access Range Default

457-458 int32 R/W 192.168.0.50 IP address  

459 int R/W 0-3 0 Flow units 0-m3/h, 1-l/s, 2-m3/s, 3-Pa

460-467 int8x2 R -   AHU S/N  

468-479 int8x2 R     AHU name  

480-481 int8x2 R/W   IP mask With auto correction

Speed (b4..b3): 0 – 9600, 1 – 19200, 2 – 38400, 3 – 57600;


482 int R/W - 19200 8E1 RS-485
parity (b1): 0 – none, 1 – even; stop bits (b0): 0 – 1, 1 – 2

483 char R/W 0..1 0 Daylight saving time 0-Disable, 1-Enable

485 short R/W 0..65535 47809 BACnet port

486-487 int32 R/W 0..4194303 20087 BACnet ID

FUNCTIONS

Modbus Data
Description Data values
register Type Access Range Default

Air quality control:


501 int R/W 200..1800 1000 200..1800ppm, 10..90%, 10..90%RH, 5..45C
Setpoint 1

Air quality control: 1-Comfort1, 2-Comfort2, 3-Economy1, 4-Economy2,


502 int R/W 1..5 1
Mode 1 5-Special

Air quality control:


503 int R/W 200..1800 1000 200..1800ppm, 10..90%, 10..90%RH, 5..45C
Setpoint 2

Air quality control: 1-Comfort1, 2-Comfort2, 3-Economy1, 4-Economy2,


504 int R/W 1..5 1
Mode 1 5-Special

Outdoor comp.
505 int R/W 0..1 0 ventilation: Enable/ 0-Disable, 1-Enable
Disable
Outdoor comp.
506 int R/W -400..500 -400 ventilation: Winter -150 => -15.0C
comp. stop
Outdoor comp.
507 int R/W -400..500 0 ventilation: Winter -150 => -15.0C
comp. start
Outdoor comp.
508 int R/W -400..500 200 ventilation: Summer 250 => 25.0C
comp. start
Outdoor comp.
509 int R/W -400..500 500 ventilation: Summer 250 => 25.0C
comp. stop

Min. temperature
510 int R/W 0..1 0 0-Disable, 1-Enable
control: Enable/Disable

Min. temperature
511 int R/W -400..500 150 -150 => -15.0C
control: Setpoint

Override function:
512 int R/W 0..1 1 0-Disable, 1-Enable
Enable/Disable

Override function:
513 int R/W 0..2 0 0-All time, 1-If on, 2-If off
Override type

Override function: 0-Standby, 1-Comfort1, 2-Comfort2, 3-Economy1,


514 int R/W 0..6 2
Mode 4-Economy2, 5-Special, 6-Program

Summer night cooling:


515 int R/W 0..1 0 0-Disable, 1-Enable
Enable/Disable

UAB KOMFOVENT we reserve the right to make changes without prior notice
Modbus_connection_C5_22-10 11
EN

FUNCTIONS

Modbus Data
Description Data values
register Type Access Range Default

Summer night cooling:


516 int R/W 100..500 250 250 => 25.0C
Start temperature

Operation on demand:
517 int R/W 0..1 0 0-Disable, 1-Enable
Enable/Disable

Operation on demand:
518 int R/W 200..1800 150 200..1800ppm, 10..90%, 10..90%RH, 5..45C
Setpoint

Recirculation control:
519 int R/W 0..1 0 0-Disable, 1-Enable
Enable/Disable

Recirculation control:
520 int R/W 200..1800 600 200..1800ppm, 10..90%, 10..90%RH, 5..45C
Setpoint

Recirculation control:
521 int R/W 0..80 30  
Min. fresh air

Recirculation control:
522 int R/W -400..500 -400 Winter recirculation -150 => -15.0C
end
Recirculation control:
523 int R/W -400..500 0 Winter recirculation -150 => -15.0C
start
Recirculation control:
524 int R/W -400..500 200 Summer recirculation 250 => 25.0C
start
Recirculation control:
525 int R/W -400..500 500 Summer recirculation 250 => 25.0C
end

Recirculation control:
526 int R/W 0..100 0  
Default recirculation

Recirculation control:
527 int R/W 0..100 60  
Activated recirculation

Humidity control:
528 int R/W 0..1 0 0-Disable, 1-Enable
Enable/Disable

Humidity control:
529 int R/W 10..90 1000 10..90%RH
Setpoint 1

Humidity control: 1-Comfort1, 2-Comfort2, 3-Economy1, 4-Economy2,


530 int R/W 1..5 1
Mode 1 5-Special

Humidity control:
531 int R/W 10..90 1000 10..90%RH
Setpoint 2

Humidity control: 1-Comfort1, 2-Comfort2, 3-Economy1, 4-Economy2,


532 int R/W 1..5 2
Mode 2 5-Special

Recirculation control: 1-Comfort1, 2-Comfort2, 3-Economy1, 4-Economy2,


533 int R/W 1..5 1
Mode 1 5-Special

Recirculation control:
534 int R/W 200..1800 900 200..1800ppm, 10..90%, 10..90%RH, 5..45C
Setpoint 2

Recirculation control: 1-Comfort1, 2-Comfort2, 3-Economy1, 4-Economy2,


535 int R/W 1..5 2
Mode 2 5-Special

Recirculation control:
536 int R/W 0..100 20  
Min. fresh air 2

Summer night cooling:


537 int R/W 150..500 200 200 => 20.0C
Stop temperature

Inspection lighting:
538 bin R/W 0..1 0  
Enable/Disable

Additional zone 1:
539 bin R/W 0..1 0  
Enable/Disable

Additional zone 1:
540 int R/W -400..400 210 200 => 20,0C
Setpoint

Additional zone 2:
541 bin R/W 0..1 0  
Enable/Disable

UAB KOMFOVENT we reserve the right to make changes without prior notice
12 Modbus_connection_C5_22-10
FUNCTIONS

Modbus Data
Description Data values
register Type Access Range Default

Additional zone 2:
542 int R/W -400..400 210 200 => 20,0C
Setpoint

External room 200 => 20.0C. Overrides extract flow temperature sensor for
543 int R/W -500..1200 -32768
temperature sensor temperature control only when written value is in range

Overrides digital input IN4 for combined heating & cooling


Digital input IN4
544 int R/W -1..2 0 coil control. (-1 – function not available or disabled, 0 –
override
heating (winter mode), 1 – cooling (summer mode), 2 – error)

545 int R/W 0..4 0 Air quality sensor type 0 – CO2, 1 – VOCq, 2 – VOCp, 3 – RH, 4 – temperature

CF heat exchanger 0-No calibration, 1- Calibrated, 2-Calibrating. Write 1 to start


546 int R/W 0..2 -
calibration calibration

547 int R/W 0..2 - HUM mode 0-Supply, 1-Indoor+Supply, 2-Indoor

548 int R/W 0..1 0 Humidity control: Type 0 - Relative humidity, 1 - Absolute humidity

Relative humidity: 0 - %RH.


549 int R/W 0..1 0 Humidity control: Units
Absolute humidity: 0 - g/m3, 1 - g/kg.

550 int R/W 20..100 0 OCV Minimum airflow %

ALARMS

Modbus Data
Description Data values
register Type Access Range Default

Writing 0x99C5 - Active alarms reset and restore previous


1000 int R/W 0..10 - Active alarms count
mode

Active alarm 1 code


1001 hex R -  
(newest)

1002 hex R - Active alarm 2 code  

1003 hex R - Active alarm 3 code  

1004 hex R - Active alarm 4 code  

1005 hex R - Active alarm 5 code  

1006 hex R - Active alarm 6 code  

1007 hex R - Active alarm 7 code  

1008 hex R - Active alarm 8 code  

1009 hex R - Active alarm 9 code  

1010 hex R   - Active alarm 10 code  

1100 int R 0..50 - Alarm history count  

1101 int R 2010..2250 - Alarm1(newest) year  

Alarm1(newest)
1102 int8x2 R 01.01-12.31 - 0x020C => Feb12
month-day

1103 int8x2 R 0:00-23:59 - Alarm1(newest) time 0x0805 => 8:05

Alarm1(newest)
1104 int R 0..59 -  
seconds

UAB KOMFOVENT we reserve the right to make changes without prior notice
Modbus_connection_C5_22-10 13
EN

ALARMS

Modbus Data
Description Data values
register Type Access Range Default

1105 hex R - Alarm1(newest) code 4B => 0x0104

….. ….. ….. ….. ….. ……… …..

1346 int R 2010..2250 - Alarm50 year  

1347 int8x2 R 01.01-12.31 - Alarm50 month-day 0x020C => Feb12

1348 int8x2 R 0:00-23:59 - Alarm50 time 0x0805 => 8:05

1349 int R 0..59 - Alarm50 seconds  

1350 hex R   - Alarm50 code 4B => 0x0104

MONITORING DATA

Modbus Data
Description Data values
register Type Access Range Default

C5 Start/Stop current
2000 int R 0-2 - 0-Stop, 1-Enabled but fans are stopped, 2-Running
status

0-Standby, 1-Comfort1, 2-Comfort2, 3-Economy1,


2001 int R 0-5 - Current mode
4-Economy2, 5-Special

2002-2003 int R - - Current supply flow 3500 => 3500 m3/h, 3.500 m3/s, 3500 l/s

2004-2005 int R - - Current exhaust flow 3500 => 3500 m3/h, 3.500 m3/s, 3500 l/s

2006 int R -500..1200 - Current supply temp., C 250 => 25.0C

2007 int R -500..1200 - Current extract temp., C 250 => 25.0C

Current outdoor
2008 int R -500..1200 - 250 => 25.0C
temp., C

Current exhaust
2009 int R -500..1200 - 250 => 25.0C
temp., C

Current return water


2010 int R -500..1200 - 250 => 25.0C
temp., C

2011 int R 0..1000 - Supply air pressure  250 => 250 Pa

2012 int R 0..1000 - Extract air pressure  250 => 250 Pa

2013 int R 0..4 - Air quality sensor type 0-CO2, 1-VOCq, 2-VOCp, 3-RH, 4-TMP

CO2: 0..2000ppm, VOC: 0..1000(0..100%), RH: 0..1000(0..100%),


2014 int R 0..2000 - Current air quality level
TMP: 0..500(0..50C)

Current supply air


2015 int R 0..1000 - 157 => 15.7%
humidity

2016 int R 0..1000 - Water heater level  

2017 int R 0..1000 - Water cooler level  

2018 int R 0..1000 - Humidity control level  

2019 int R 0..1000 - Heat exchanger level  

UAB KOMFOVENT we reserve the right to make changes without prior notice
14 Modbus_connection_C5_22-10
MONITORING DATA

Modbus Data
Description Data values
register Type Access Range Default

2020 int R 0..1000 - Recirculation level  

2021 int R 0..1000 - Supply fan level  

2022 int R 0..1000 - Exhaust fan level  

Outdoor air damper


2023 int R 0..1000 -  
actuator level

Exhaust air damper


2024 int R 0..1000 -  
actuator level

2025 int R 0..1000 - Electric heater level  

2026 int R -1000..1000 - Heat pump level  

2027 int R -1000..1000 - DX level  

2028 bin R 0..1 - OVR input  

2029 bin R 0..1 - Fire system input  

2030 bin R 0..1 - External stop input  

2031 bin R 0..1 - Control input  

Current temp.
2032 int R 50..400 - 250 => 25.0C
setpoint, C

Current supply air


2033 int R 50..400 - 250 => 25.0C
temp. setpoint, C

2034 bin R 0..1 - Water heater pump  

2035 bin R 0..1 - Water cooler pump  

Current supply flow


2036-2037 int R - - 3500 => 3500 m3/h, 3.500 m3/s, 3500 l/s
setpoint

Current extract flow


2038-2039 int R - - 3500 => 3500 m3/h, 3.500 m3/s, 3500 l/s
setpoint

Current internal supply


2040 int R -500..1200 - 250 => 25.0C
temp., C

Additional zone 1:
2041 int R -500..1200 - 250 => 25.0C
current supply temp., C

Additional zone 1:
2042 int R -500..1200 - current return water 250 => 25.0C
temp., C

Additional zone 2:
2043 int R -500..1200 - 250 => 25.0C
current supply temp., C

Additional zone 2:
2044 int R -500..1200 - current return water 250 => 25.0C
temp., C

2045 int R 0..1 - Alarm DOUT 0-No alarms, 1-Active alarms

Current supply air


2046 int R 0..400 - 250 => 25.0 g/m3 or g/kg
absolute humidity

b8-Exhaust fan units(0-h, 1-kWh), b7-Supply fan units(0-h,


Counters/efficiencies 1-kWh), b6-Exhaust fan counter, b5-Heater counter,
2200 bin R   -
configuration b4-Extract filter, b3-Outdoor filter, b2-Exhaust SFP, b1-
Supply SFP, b0-HX efficiency (0-Unavailable, 1-Available)

UAB KOMFOVENT we reserve the right to make changes without prior notice
Modbus_connection_C5_22-10 15
EN

MONITORING DATA

Modbus Data
Description Data values
register Type Access Range Default

Heat exchanger
2201 int R 0..100, 255 - 255 - Unavailable
thermal efficiency, %

2202 int R 0..100, 255 - Energy saving, % 255 - Unavailable

Heat exchanger
2203-2204 int R - 2500 => 2.5kW (0xFFFFFFFF - Unavailable)
recovery, W

2205 int R - Supply SFP 125 => 1.25

2206 int R - Exhaust SFP 125 => 1.25

Outdoor air filter


2207 int R 0..100 -  For AHU with filter pressure sensors
impurity level, %

Exhaust air filter


2208 int R 0..100 -  For AHU with filter pressure sensors
impurity level, %

Air heater operation,


2209-2210 int R 0..1’000’000 -  
hours

Supply fan operation,


2211-2212 int R 0..50’000’000 -  
hours or kWh

Exhaust fan operation,


2213-2214 int R 0..50’000’000 -  
hours or kWh

Current supply fan


2215 int R 0..65535 -  
power, W

Current exhaust fan


2216 int R 0..65535 -  
power, W

2217 bin R - Active functions b5-OOD,b4-AQC,b3-SNC,b2-MTC,b1-OVR,b0-OCV

Air cooler operation,


2218-2219 int R 0..1’000’000 -  
hours

Heat exchanger
2220-2221 int R 0..4’000’000 -  
operation, kWh

Air heater operation,


2222-2223 int R 0..4’000’000 -  
kWh

MONITORING DATA ZONE 1

Modbus Data
Description Data values
register Type Access Range Default

2300 int R 0..1000 - Electric heater: level

Electric heater: cooler


2301 int R 0..1000 -
level

Electric heater: air


2302 int R -500..1200 -
temperature

Electric heater: air


2303 int R 0..1000 -
quality

Electric heater: heater 0..1200 when NTC sensor is selected, 0-1000 when TK70
2304 int R 0..1200 -
temperature sensor is selected

Electric heater: stages


2305 bin R - - b3 – stage4, b2 – stage3, b1 – stage2, b0 – stage1
active

2306 bin R - - Electric heater: inputs b2 – TK70, b1 – TK60, b0 – TK100

2307 bin R - - Electric heater: alarms b2 – TK60 alarm, b1 – TK70 alarm, b0 – TK100 alarm

2310 int R 0..1000 - Water: heater level

UAB KOMFOVENT we reserve the right to make changes without prior notice
16 Modbus_connection_C5_22-10
MONITORING DATA ZONE 1

Modbus Data
Description Data values
register Type Access Range Default

2311 int R 0..1000 - Water: cooler level

2312 int R -500..1200 - Water: air temperature

2313 int R 0..1000 - Water: air quality

Water: return water


2314 int R -300..1200 -
temperature

2315 bin R - - Water: outputs b1 – cooling pump, b0 – heating pump

b1 – combined coil is: 1-cooling, 0-heating, b0 – low water


2316 bin R - - Water: inputs
temperature,

2317 bin R - - Water: alarms b0 – Low water temperature

2320 int R -1000..1000 - DX level unit: level > 0 – heating, < 0 – cooling, -32768 – forced stop

DX level unit: cooler


2321 int R 0..1000 -
level

DX level unit: air


2322 int R -500..1200 -
temperature

2323 int R 0..1000 - DX level unit: air quality

DX level unit: operating b4 – reverse: 1-heating, 0-cooling, b3 – stage4, b2 – stage3,


2325 bin R - -
& stages active b1 – stage2, b0 – stage1

2326 bin R - - DX level unit: inputs b0 – external error

2327 bin R - - DX level unit: alarms b0 – external error alarm

DX modulated unit: Level or temperature setpoint (t → 0..10V) or temperature


2330 int R -1000..1000 -
level/setpoint/error error signal (0..5..10V), depending on configuration

DX modulated unit:
2331 int R 0..1000 -
cooler level

DX modulated unit: air


2332 int R -500..1200 -
temperature

DX modulated unit: air


2333 int R 0..1000 -
quality

DX modulated unit:
2335 bin R - - b2 – heating, b1 – cooling, b0 – operation
control outputs

DX modulated unit:
2336 bin R - - b0 – external error
inputs

DX modulated unit:
2337 bin R - - b0 – external error alarm
alarms

MONITORING DATA ZONE 2

Modbus Data
Description Data values
register Type Access Range Default

2400 int R 0..1000 - Electric heater: level

Electric heater: cooler


2401 int R 0..1000 -
level

Electric heater: air


2402 int R -500..1200 -
temperature

Electric heater: air


2403 int R 0..1000 -
quality

UAB KOMFOVENT we reserve the right to make changes without prior notice
Modbus_connection_C5_22-10 17
EN

MONITORING DATA ZONE 2

Modbus Data
Description Data values
register Type Access Range Default

Electric heater: heater 0..1200 when NTC sensor is selected, 0-1000 when TK70
2404 int R 0..1200 -
temperature sensor is selected

Electric heater: stages


2405 bin R - - b3 – stage4, b2 – stage3, b1 – stage2, b0 – stage1
active

2406 bin R - - Electric heater: inputs b2 – TK70, b1 – TK60, b0 – TK100

2407 bin R - - Electric heater: alarms b2 – TK60 alarm, b1 – TK70 alarm, b0 – TK100 alarm

2410 int R 0..1000 - Water: heater level

2411 int R 0..1000 - Water: cooler level

2412 int R -500..1200 - Water: air temperature

2413 int R 0..1000 - Water: air quality

Water: return water


2414 int R -300..1200 -
temperature

2415 bin R - - Water: outputs b1 – cooling pump, b0 – heating pump

b1 – combined coil is: 1-cooling, 0-heating, b0 – low water


2416 bin R - - Water: inputs
temperature,

2417 bin R - - Water: alarms b0 – Low water temperature

2420 int R -1000..1000 - DX level unit: level > 0 – heating, < 0 – cooling, -32768 – forced stop

DX level unit: cooler


2421 int R 0..1000 -
level

DX level unit: air


2422 int R -500..1200 -
temperature

2423 int R 0..1000 - DX level unit: air quality

DX level unit: operating b4 – reverse: 1-heating, 0-cooling, b3 – stage4, b2 – stage3,


2425 bin R - -
& stages active b1 – stage2, b0 – stage1

2426 bin R - - DX level unit: inputs b0 – external error

2427 bin R - - DX level unit: alarms b0 – external error alarm

DX modulated unit: Level or temperature setpoint (t → 0..10V) or temperature


2430 int R -1000..1000 -
level/setpoint/error error signal (0..5..10V), depending on configuration

DX modulated unit:
2431 int R 0..1000 -
cooler level

DX modulated unit: air


2432 int R -500..1200 -
temperature

DX modulated unit: air


2433 int R 0..1000 -
quality

DX modulated unit:
2435 bin R - - b2 – heating, b1 – cooling, b0 – operation
control outputs

DX modulated unit:
2436 bin R - - b0 – external error
inputs

DX modulated unit:
2437 bin R - - b0 – external error alarm
alarms

UAB KOMFOVENT we reserve the right to make changes without prior notice
18 Modbus_connection_C5_22-10
SERVICE

Modbus Data
Description Data values
register Type Access Range Default

b4-Special, b3-Economy2, b2-Economy1, b1-Comfort2,


900 bin R/W   0 Modes reset to default
b0-Comfort1

Functions reset to b9-ZN2, b8-ZN1, b7-HUM, b6-REC, b5-OOD, b4-SNC, b3-OVR,


901 bin R/W 0
default b2-MTC, b1-OCV, b0-AQC

Settings reset to
902 bin R/W 0 b3-485_Config, b2-IP+Mask, b1-Flow_mode, b0-Temp_mode
default

Digital input:
2852 bin R 0..1 - For AHU without filter pressure sensors. 0-Clean, 1-Dirty
Outdoor filter

Digital input:
2853 bin R 0..1 - For AHU without filter pressure sensors. 0-Clean, 1-Dirty
Extract filter

18000 int R/W 0 - User password reset Write 0x99C5 to reset

18001 int R/W 0 - User settings reset Write 0x99C5 to reset

Clean air filters


18002 int R/W 0 - Write 0x99C5 to start calibration
calibration

Write 0x??C5 to reset, ?? => b2-Exhaust fan, b1-Supply fan,


18003 int R/W 0 - Counters reset b0-Air heater (1 – Reset). 0X01C5 => Reset air heater counter
only, 0x07C5 => Reset both fans and air heater counters

Controller firmware
18004 int R 0..9999 -  
version

18005 int R/W 0..1000 0 Service time counter 0..100.0%, Write 0x99C5 to reset

UAB KOMFOVENT we reserve the right to make changes without prior notice
Modbus_connection_C5_22-10 19
UAB KOMFOVENT PARTNERS

SERVICE AND SUPPORT


Phone: +370 5 200 8000 AT J. PICHLER Gesellschaft m. b. H. www.pichlerluft.at
[email protected] Ventilair group www.ventilairgroup.com
BE
ACB Airconditioning www.acbairco.be
Komfovent AB CZ REKUVENT s.r.o. www.rekuvent.cz
Ögärdesvägen 12B
433 30 Partille, Sverige WESCO AG www.wesco.ch
Phone: +46 31 487 752 CH
SUDCLIMATAIR SA www.sudclimatair.ch
[email protected]
www.komfovent.se CLIMAIR GmbH www.climair.ch
CH / LI
Trivent AG www.trivent.com
Komfovent Oy DK Øland A/S www.oeland.dk
Muuntotie 1 C1
FI-01 510 VANTAA EE BVT Partners www.bvtpartners.ee
Phone: +358 20 730 6190
FR ATIB www.atib.fr
[email protected]
www.komfovent.com HR Microclima www.microclima.hr
AIRVENT Légtechnikai Zrt. www.airvent.hu
Komfovent GmbH HU Gevent Magyarország Kft. www.gevent.hu
Konrad-Zuse-Str. 2a, 42551 Velbert,
Deutschland Merkapt www.merkapt.hu
Phone: +49 0 2051 6051180 IR Fantech Ventilation Ltd www.fantech.ie
[email protected]
www.komfovent.de Blikk & Tækniþjónustan ehf www.bogt.is
IS
Hitataekni ehf www.hitataekni.is
SIA Komfovent IT Icaria srl www.icariavmc.it
Bukaišu iela 1, LV-1004 Riga
Phone: +371 24 664433 Ventilair group www.ventilairgroup.com
[email protected] NL DECIPOL-Vortvent www.vortvent.nl
www.komfovent.lv
CLIMA DIRECT BV www.climadirect.com
Ventilution AS www.ventilution.no
Vidzemes filiāle
Alejas iela 12A, LV-4219 Valmiermuiža, NO Ventistål AS www.ventistal.no
Valmieras pagasts, Burtnieku novads
Thermo Control AS www.thermocontrol.no
Phone: +371 29 358 145
[email protected] PL Ventia Sp. z o.o. www.ventia.pl
www.komfovent.lv
SE Nordisk Ventilator AB www.nordiskventilator.se
SI Agregat d.o.o www.agregat.si

www.komfovent.com SK TZB produkt, s.r.o. www.tzbprodukt.sk

Modbus_connection_C5_22-10

You might also like