PUMP & MOTOR POWER CALCULATION
I. General Input
Temperature 0C: 20
Density (Kg/m3): 999.9
Gravity (m/s2) 9.8
Note: Efficiency, the η-curve
The efficiency is the relation between the supplied power and the utilised amount of power. In the world of pumps, the efficiency η P is the relation between the
power, which the pump delivers to the water (P H) and the power input to the shaft (P2)
E. MOTOR DATA INPUT FOR FIRE PROTECTION SERVICE 100 % RATED FLOW
Flow, Q
497 PUMP SET SELECTION REMARKS
(m3/h)
Head, H Pump Power, Motor Power,
95.0 128.60 181.13
(mH2O) (kW) (kW)
Base on QCVN 02:2020/BCA - Item [Link]: The minimum
Pump eff. power of electric motors must be greater than or equal to the
71.00% Recommended Driver Motor Rating (kW) 200
(%) capacity of the pump when operating at the point of 150%
capacity.
E. MOTOR DATA INPUT FOR FIRE PROTECTION SERVICE 150 % RATED FLOW
Flow, Q
745.5 PUMP SET SELECTION REMARKS
(m3/h)
Head, H Pump Power, Motor Power,
73.80 149.86 180.55 Head ratio: 77.68%
(mH2O) (kW) (kW)
Base on QCVN 02:2020/BCA - Item [Link]: The minimum
Pump eff. power of electric motors must be greater than or equal to the
83.00% Recommended Driver Motor Rating (kW) 200
(%) capacity of the pump when operating at the point of 150%
capacity.