PLC Motor Logic

The document discusses how a PLC controls a motor. The PLC receives inputs from sensors monitoring the motor's vibration, temperature, and overload status. It also receives signals from start/stop buttons and the motor's local/remote status. If all interlocks are healthy, the PLC sends a start command to the motor feeder to power the motor. It monitors for trip conditions or a stop button press to send a stop command. The motor feeder provides run feedback to the PLC. This allows the PLC to remotely control and safely start/stop the motor based on sensor readings and operator inputs.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
779 views5 pages

PLC Motor Logic

The document discusses how a PLC controls a motor. The PLC receives inputs from sensors monitoring the motor's vibration, temperature, and overload status. It also receives signals from start/stop buttons and the motor's local/remote status. If all interlocks are healthy, the PLC sends a start command to the motor feeder to power the motor. It monitors for trip conditions or a stop button press to send a stop command. The motor feeder provides run feedback to the PLC. This allows the PLC to remotely control and safely start/stop the motor based on sensor readings and operator inputs.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 5

Instrumentation Tools

Learn Instrumentation and Control Engineering. Inst Tools covers topics of Industrial
Instrumentation, PLC, DCS, SCADA, Field Instruments, Analyzers and so on.
https://instrumentationtools.com

Author: Instrumentation Tools

Categories: PLC Tutorials

How PLC Controls a Motor ?

om
s .c
ol
To
i on
at
nt
me
ru
st

Now we are discussing about How a PLC controls a motor ?. Before going into the article, let us
assume some conditions here. A PLC has to start a Motor when the Start button is pressed. It
In

has three interlocks which are Motor Vibration High, Overload & Motor Temperature High. if any
of the interlock activated then PLC has to stop the motor immediately. PLC has to stop the
motor if the stop button is pressed. PLC trip logic or interlock has to be enable only when motor
is in Remote mode.

InstrumentationTools.com
Instrumentation Tools
Learn Instrumentation and Control Engineering. Inst Tools covers topics of Industrial
Instrumentation, PLC, DCS, SCADA, Field Instruments, Analyzers and so on.
https://instrumentationtools.com

In above figure : Red LED indicator lights on the input and output cards of the PLC indicate if
those respective I/O channels are energized.

Note :

1. In above figure, Local Control Panel signals are not shown. Local control panel is
connected to motor feeder directly.
2. 24v DC power directly connected ( in general fuses or barriers will be used, power will

om
be distributed through bus bar)

.c
PLC Inputs

s
ol
Start push button
Stop push button To
Vibration High
on
Temperature High
Overload Trip
i

Run feedback
at

Local/Remote status
nt

PLC Outputs
me

Start Command (Remote Start)


ru

Stop Command (Remote Stop)


Start Permissive ( Optional)
st
In

The motor is a three phase, 415V AC powered device. So by default high voltage equipment will
be powered from substations or motor control centers (MCC) which are maintained by electrical.
So we consider this motor is connected to a simple motor feeder in the substation. Generally the
motor feeder have inputs from field (local control panel) & PLC also. Which are shown in below
figure.

InstrumentationTools.com
Instrumentation Tools
Learn Instrumentation and Control Engineering. Inst Tools covers topics of Industrial
Instrumentation, PLC, DCS, SCADA, Field Instruments, Analyzers and so on.
https://instrumentationtools.com

om
s .c
ol
To
i on
at
nt

Note : the motor feeder may have start, stop, some other trips indications like overload etc… in
me

the motor feeder panel which are not shown in the fig. These are mounted on the motor feeder
ru

panel (in addition to LCP).


st

If motor feeder receives start & stop command inputs from PLC then we call them as Remote
Start & Remote Stop signals. Similarly if motor feeder receives start & stop command inputs
In

from local control panel (LCP) which is installed in field (near to motor) then we call them as
Local Start & Local Stop signals. In common practice, this LCP has emergency stop &
Local/Remote selection switch also. The motor feeder also sends a Local/Remote status to
PLC. If Local/Remote selection switch is in Local mode then motor feeder will only consider
signals from LCP and ignore the commands from PLC. Similarly if Local/Remote Selection
switch in Remote Mode then motor feeder will consider signals from Remote i.e. PLC and
ignore the signals from LCP.

For example : if Local/Remote selection Switch in Remote Mode. If field operator pressed the
start push button from the field LCP then motor will not be started as the selection is in remote
mode. Depends on the Local/Remote selection switch status the motor feeder will decides
which signals to be consider i.e. either PLC or LCP signals.

Note : Local/Remote Selection will not be applied for Emergency Stop or Stop Commands either
from PLC or LCP. Whatever mode it is, the Stop commands will be accepted by motor feeder
and stops the motor immediately. This is a safety concern.

Also Read : How a 4-20mA Transmitter Works ?

InstrumentationTools.com
Instrumentation Tools
Learn Instrumentation and Control Engineering. Inst Tools covers topics of Industrial
Instrumentation, PLC, DCS, SCADA, Field Instruments, Analyzers and so on.
https://instrumentationtools.com

Lets see how a PLC controls a motor.

Now Local/Remote selection switch is in Remote mode.

Here we are sending an Permissive signal ( Start Permissive) to the motor feeder. For starting
the motor, the permissive must be healthy otherwise motor feeder will be de-energized or will
not start the motor. In PLC, Start permissive will be used as a extra safety & for checking the
interlock status. if all the interlocks are healthy then only permissive signal will be sent to motor
feeder. Generally we call this as “Start Permissive”, as name implies it is only required for

om
starting the motor, after motor started the status of this permissive signal will not be considered

.c
by motor feeder (Only required for starting the motor). This is an optional signal. For High
capacity motors, start permissive signals will be used. For normal or low capacity motors these

s
are very rarely used, again depends on our applications, industry, requirements etc.

ol
Lets say all interlocks are healthy, so PLC sends the permissive signal to motor feeder.
To
on
Now start push button is pressed.
i

First PLC checks the Local/Remote status, if it is in Remote then proceeds further. Again it
at

checks for any active trips/interlocks. If there is no interlock or all working normal, then PLC
sends a start command to substation where motor feeder is installed.
nt
me

In this example we have three interlocks: Motor Vibration High, Motor Temperature High &
Overload trip. In generally High capacity motors are equipped with Vibration sensors &
ru

temperature sensors. In our example we consider vibration signals as fail safe, so default status
is normally closed, if high vibration appears then the contact become Normally Open & PLC
st

trips/stops the motor. We have another interlock which is Overload trip, this input is taken from
In

the motor feeder. The temperature sensors signal is normally open and when temperature high
then it becomes normally close and PLC trips/Stops the motor.

Note: Fail safe or default contact status either NC or NO are depends on our application or logic
requirements. Here we are only discussing an example for understanding the concept.

After receiving the start command from the PLC, motor feeder will be energized and power up
the motor. After motor started, the motor feeder will send the Run feedback to the PLC. The run
feedback will be displayed on the graphics.

In some PLC’s or in safety PLC’s if the Run feedback is not received in specified time frame (
say within 5 seconds) then PLC automatically sends an Stop signals to the motor feeder. This is
a optional feature in normal PLC applications( must in safety PLC’s).

Say now Vibration High came, then PLC sends a stop command to motor feeder and it
immediately stops the motor. The run feedback status also updates accordingly.

Example Video :

Motor will be started when Level Transmitter will be High & again it will stopped at Level
Transmitter Low

InstrumentationTools.com
Instrumentation Tools
Learn Instrumentation and Control Engineering. Inst Tools covers topics of Industrial
Instrumentation, PLC, DCS, SCADA, Field Instruments, Analyzers and so on.
https://instrumentationtools.com

Start Permissive signal not used in the below video.

MCC : Motor Control Center or Substation where motor will be powered.

PLC/DCS : Control System, where Motor can be controlled as per logic (Auto) or as per
operator action (Manual).

LCP : Local Control Panel which is installed in the field, near motor in which start, stop push

om
buttons are available

s .c
ol
To
i on
at
nt
me
ru
st
In

InstrumentationTools.com
Powered by TCPDF (www.tcpdf.org)