0% found this document useful (0 votes)
45 views3 pages

Air System Sizing for Q_first System

This document summarizes the air system sizing for the Q_first system in Casablanca, Morocco. It includes 1 zone covering 136 square meters. The central cooling coil is designed to handle a peak cooling load of 53 kW in August. The central heating coil is sized for a maximum heating load of 19.9 kW. The supply fan is designed to deliver a maximum airflow of 2791 liters per second.

Uploaded by

zakaria qeddi
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
45 views3 pages

Air System Sizing for Q_first System

This document summarizes the air system sizing for the Q_first system in Casablanca, Morocco. It includes 1 zone covering 136 square meters. The central cooling coil is designed to handle a peak cooling load of 53 kW in August. The central heating coil is sized for a maximum heating load of 19.9 kW. The supply fan is designed to deliver a maximum airflow of 2791 liters per second.

Uploaded by

zakaria qeddi
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

Air System Sizing Summary for Q_first system

Project Name: Untitled 01/21/2024


Prepared by: hmm 11:53

Air System Information


Air System Name: Q_first system Number of zones: 1
Air System Type: Single Zone CAV Floor Area: 136,0 sqm
Location: Casablanca, Morocco

Sizing Calculation Information


Calculation Months: Jan to Dec Calculation method: Transfer Function Method

Central Cooling Coil Sizing Data


Total coil load: 53,0 kW Load occurs at: Aug 1400
Total coil load: 53,0 kW OA DB / WB: 34,9/25,0
Sensible coil load: 37,9 kW Entering DB / WB: 26,3/19,8
Coil airflow: 2791 L/s Leaving DB / WB: 15,0/14,4
Sensible heat ratio: 0,715 Coil ADP: 13,7 C
Area per unit load: 2,6 sqm/kW Bypass Factor: 0,100
Load per unit area: 389,7 W/sqm Resulting RH: 56 %
Design supply temp: 15,0 C

Central Heating Coil Sizing Data


Max coil load: 19,9 kW Load occurs at: Des Htg
Coil airflow: 2791 L/s Ent DB / Lvg DB: 16,3/22,2
Load per unit area: 146,1 W/sqm

Supply Fan Sizing Data


Actual max airflow: 2791 L/s Fan motor BHP: 1,25 BHP
Standard airflow: 2770 L/s Fan motor kW: 0,93 kW
Actual max airflow per unit area: 20,52 L/(s-sqm) Fan static: 180,00 Pa

Outdoor Ventilation Air Data


Design airflow: 330 L/s Airflow per person: 4,72 L/s/person
Airflow per unit floor area: 2,43 L/(s-sqm)

Space Sizing Data

Space Name Maximum Design Time of Peak Maximum Space Space


Cooling Airflow Load Heating Floor L/(s-sqm)
Sensible kW L/s Load kW Area
sqm
Q_Restaurant 33,4 2791 Aug 1300 16,1 136,0 20,52

Block Load 4.15 Page 1 of 3


System Design Load Summary for Q_first system
Project Name: Untitled 01/21/2024
Prepared by: hmm 11:53

DESIGN COOLING DESIGN HEATING


Aug 1400 Design Heating Day
OA DB / WB 34,9 C / 25 C OA DB / WB 5 C / 1,4 C
Zone Loads based on TFM Details Sensible W Latent W Details Sensible W Latent W
Window and Skylight Solar Loads 48 sqm 1693 - 48 sqm - -
Wall Transmission 39 sqm 8186 - 39 sqm 777 -
Roof Transmission 136 sqm 3510 - 136 sqm 4894 -
Window Transmission 48 sqm 1433 - 48 sqm 2083 -
Skylight Transmission 0 sqm 0 - 0 sqm 0 -
Door Loads 0 sqm 0 - 0 sqm 0 -
Floor Transmission 0 sqm 0 - 0 sqm 0 -
Partitions/Ceilings 94 sqm 732 - 94 sqm 1447 -
Overhead Lighting 3750 W 3750 - 0W 0 -
Electric Equipment 1230 W 1230 - 0W 0 -
People 70 4956 6846 0 0 0
Infiltration - 1723 1965 - 5468 2
Miscellaneous - 3078 1320 - 0 0
Safety Factor 10% / 5% 10336 1728 10% 5005 1
>>Total Zone Loads - 33321 10638 - 16136 2
Thermostat and Pulldown Adjustment - -165 0 - -388 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Ventilation Load 330 L/s 3823 4454 330 L/s 5058 0
Supply Fan Load 2791 L/s 930 - 2791 L/s -930 -
>> Total System Loads - 37909 15092 - 19876 2
Central Cooling Coil - 37909 15096 - 0 0
Central Heating Coil - 0 - - 19876 -
>> Total Coil Loads - 37909 15096 - 19876 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Block Load 4.15 Page 2 of 3


System PsychrometricsforQ_first system
Project Name: Untitled 01/21/2024
Prepared by: hmm 11:53

Location: Casablanca, Morocco


Altitude: 61,9 m
Data for: Aug DESIGN COOLING DAY, 1400
0,020
1. Outdoor Air
2. Mixed Air
3. Central Cooling Coil Outlet
4. Supply Fan Outlet 0,018
5. Room Air

0,016
1

0,014

Specific Humidity ( kg/kg )


0,012
2
5

34 0,010

0,008

0,006

0,004

0,002

0,000
0 10 20 30
Temperature (C)