Air System Sizing Summary for Q_first system
Project Name: Untitled 01/21/2024
Prepared by: hmm 11:53
Air System Information
Air System Name: Q_first system Number of zones: 1
Air System Type: Single Zone CAV Floor Area: 136,0 sqm
Location: Casablanca, Morocco
Sizing Calculation Information
Calculation Months: Jan to Dec Calculation method: Transfer Function Method
Central Cooling Coil Sizing Data
Total coil load: 53,0 kW Load occurs at: Aug 1400
Total coil load: 53,0 kW OA DB / WB: 34,9/25,0
Sensible coil load: 37,9 kW Entering DB / WB: 26,3/19,8
Coil airflow: 2791 L/s Leaving DB / WB: 15,0/14,4
Sensible heat ratio: 0,715 Coil ADP: 13,7 C
Area per unit load: 2,6 sqm/kW Bypass Factor: 0,100
Load per unit area: 389,7 W/sqm Resulting RH: 56 %
Design supply temp: 15,0 C
Central Heating Coil Sizing Data
Max coil load: 19,9 kW Load occurs at: Des Htg
Coil airflow: 2791 L/s Ent DB / Lvg DB: 16,3/22,2
Load per unit area: 146,1 W/sqm
Supply Fan Sizing Data
Actual max airflow: 2791 L/s Fan motor BHP: 1,25 BHP
Standard airflow: 2770 L/s Fan motor kW: 0,93 kW
Actual max airflow per unit area: 20,52 L/(s-sqm) Fan static: 180,00 Pa
Outdoor Ventilation Air Data
Design airflow: 330 L/s Airflow per person: 4,72 L/s/person
Airflow per unit floor area: 2,43 L/(s-sqm)
Space Sizing Data
Space Name Maximum Design Time of Peak Maximum Space Space
Cooling Airflow Load Heating Floor L/(s-sqm)
Sensible kW L/s Load kW Area
sqm
Q_Restaurant 33,4 2791 Aug 1300 16,1 136,0 20,52
Block Load 4.15 Page 1 of 3
System Design Load Summary for Q_first system
Project Name: Untitled 01/21/2024
Prepared by: hmm 11:53
DESIGN COOLING DESIGN HEATING
Aug 1400 Design Heating Day
OA DB / WB 34,9 C / 25 C OA DB / WB 5 C / 1,4 C
Zone Loads based on TFM Details Sensible W Latent W Details Sensible W Latent W
Window and Skylight Solar Loads 48 sqm 1693 - 48 sqm - -
Wall Transmission 39 sqm 8186 - 39 sqm 777 -
Roof Transmission 136 sqm 3510 - 136 sqm 4894 -
Window Transmission 48 sqm 1433 - 48 sqm 2083 -
Skylight Transmission 0 sqm 0 - 0 sqm 0 -
Door Loads 0 sqm 0 - 0 sqm 0 -
Floor Transmission 0 sqm 0 - 0 sqm 0 -
Partitions/Ceilings 94 sqm 732 - 94 sqm 1447 -
Overhead Lighting 3750 W 3750 - 0W 0 -
Electric Equipment 1230 W 1230 - 0W 0 -
People 70 4956 6846 0 0 0
Infiltration - 1723 1965 - 5468 2
Miscellaneous - 3078 1320 - 0 0
Safety Factor 10% / 5% 10336 1728 10% 5005 1
>>Total Zone Loads - 33321 10638 - 16136 2
Thermostat and Pulldown Adjustment - -165 0 - -388 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Ventilation Load 330 L/s 3823 4454 330 L/s 5058 0
Supply Fan Load 2791 L/s 930 - 2791 L/s -930 -
>> Total System Loads - 37909 15092 - 19876 2
Central Cooling Coil - 37909 15096 - 0 0
Central Heating Coil - 0 - - 19876 -
>> Total Coil Loads - 37909 15096 - 19876 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads
Block Load 4.15 Page 2 of 3
System PsychrometricsforQ_first system
Project Name: Untitled 01/21/2024
Prepared by: hmm 11:53
Location: Casablanca, Morocco
Altitude: 61,9 m
Data for: Aug DESIGN COOLING DAY, 1400
0,020
1. Outdoor Air
2. Mixed Air
3. Central Cooling Coil Outlet
4. Supply Fan Outlet 0,018
5. Room Air
0,016
1
0,014
Specific Humidity ( kg/kg )
0,012
2
5
34 0,010
0,008
0,006
0,004
0,002
0,000
0 10 20 30
Temperature (C)
Block Load 4.15 Page 3 of 3