Drawings Volume 1
Drawings Volume 1
1
RHIT MOENCH RENOVATION
SET NO.
Terre Haute, Indiana
04/01/21
DATE
Construction Documents
PACKAGE
RATIO PROJECT NO.
19010.000
SEAL | DATE 04/01/21
PACKAGE
Construction Documents
OWNER ARCHITECT VOLUME
Rose-Hulman Institute of RATIO 1
Technology 101 South Pennsylvania Street
Indianapolis, Indiana 46204
5500 Wabash Avenue (317) 633-4040
Terre Haute, Indiana 47803 RATIO PROJECT NO.
PROJECT NAME
Indianapolis, Indiana 46204
(317)-634-4672 04/01/21
PROJECT ADDRESS
GENERAL FD-204.2 SECOND LEVEL - AREA 2 - FIRE PROTECTION DEMOLITION M-702 CONTROLS - MISCELLANEOUS T-202.3 CRAPO LEVEL 2 - AREA 3 (LL1) - TELECOM.
A. THE FOLLOWING GENERAL NOTES APPLY TO THESE
CONTRACT DOCUMENTS AND ARE NOT SPECIFIC TO ANY
RHIT MOENCH
RENOVATION
ONE DISCIPLINE.
G-002 SHEET INDEX AND PROJECT LOCATION FP-101 OVERALL LOWER LEVEL 2 - FIRE PROTECTION M-703 CONTROL SEQUENCES - AIR HANDLING UNITS (AHU) T-203.1 FIRST LEVEL - AREA 1 - TELECOM. B. IT IS THE CONTRACTORS RESPONSIBILITY TO REVIEW AND
G-003 LIFE SAFETY PLANS AND CODE SUMMARY FP-102 OVERALL LOWER LEVEL1 - FIRE PROTECTION T-203.2 FIRST LEVEL - AREA 2 - TELECOM. COORDINATE THE WORK OF ALL SUB-CONTRACTORS,
TRADES AND SUPPLIERS WITH THE REQUIREMENTS OF THE
STRUCTURAL
FP-103
FP-104
OVERALL FIRST LEVEL - FIRE PROTECTION
OVERALL SECOND LEVEL - FIRE PROTECTION
ELECTRICAL
E-001 SYMBOLS, ABBREVIATIONS, & GENERAL NOTES - ELECTRICAL
T-203.3
T-204.1
CRAPO LEVEL 3 - AREA 3 (L1) - TELECOM.
SECOND LEVEL - AREA 1 - TELECOM.
CONTRACT BEFORE COMMENCING CONSTRUCTION, AND TO
ASSURE THAT ALL PARTIES ARE AWARE OF ALL
5500 Wabash Avenue
S-001 GENERAL NOTES FP-201.1 LOWER LEVEL 2 - AREA 1 - FIRE PROTECTION ED-201.1 LOWER LEVEL 2 - AREA 1 - ELECTRICAL DEMOLITION T-204.2 SECOND LEVEL - AREA 2 - TELECOM.
REQUIREMENTS, REGARDLESS OF WHERE THE
REQUIREMENTS OCCUR IN THE CONTRACT DOCUMENTS,
WHICH MIGHT AFFECT THE WORK OF THAT PARTY.
Terre Haute, Indiana
S-002 GENERAL NOTES FP-201.2 LOWER LEVEL 2 - AREA 2 - FIRE PROTECTION ED-201.2 LOWER LEVEL 2 - AREA 2 - ELECTRICAL DEMOLITION T-301 ENLARGED PLANS - TECHNOLOGY
S-003 DESIGN INFORMATION FP-202.1 LOWER LEVEL 1 - AREA 1 - FIRE PROTECTION ED-201.3 CRAPO LEVEL 1 - AREA 3 (LL2) - ELECTRICAL DEMOLITION T-302 BUILDING SECTION - TELECOM.
C. PARTIAL SETS OF DRAWINGS ARE INCOMPLETE AND
SHOULD NOT BE DISTRIBUTED OR UTILIZED BY THE 47803
CONTRACTOR.
SD-112 LOWER LEVEL 1 DEMOLITION PLAN FP-202.2 LOWER LEVEL 1 - AREA 2 - FIRE PROTECTION ED-202.1 LOWER LEVEL 1- AREA 1 - ELECTRICAL DEMOLITION T-401 DETAILS - TELECOM. BONDING AND GROUNDING D. THE CONSTRUCTION DOCUMENTS ESTABLISH DETAILED Owner
SD-113 FIRST LEVEL DEMOLITION PLAN FP-202.3 CRAPO LEVEL 2 - AREA 3 (LL1) - FIRE PROTECTION ED-202.2 LOWER LEVEL 1 - AREA 2 - ELECTRICAL DEMOLITION T-402 DETAILS - PHYSICAL SECURITY MINIMUM REQUIREMENTS FOR THE CONSTRUCTION OF THE
Rose-Hulman Institute of Technology
PROJECT.
SD-114 SECOND LEVEL DEMOLITION PLAN FP-203.1 FIRST LEVEL - AREA 1 - FIRE PROTECTION ED-202.3 CRAPO LEVEL 2 - AREA 3 (LL1) - ELECTRICAL DEMOLITION T-403 DETAILS - TELECOM. BACKBONE AND ROUGH-INS E. THE GENERAL NOTES, SYMBOLS AND DEFINITIONS 5500 Wabash Avenue
SD-115 ROOF DEMOLITION PLAN FP-203.2 FIRST LEVEL - AREA 2 - FIRE PROTECTION ED-203.1 FIRST LEVEL - AREA 1 - ELECTRICAL DEMOLITION T-404 IDENTIFICATION DETAILS - TELECOM. APPLICABLE ONLY TO EACH DISCIPLINE CAN BE FOUND AT Terre Haute, Indiana 47803
THE FRONT OF EACH DISCIPLINES PORTION OF THE SET OF 812-877-1511
SD-200 ENLARGED DEMOLITION PLANS FP-203.3 CRAPO LEVEL 3 - AREA 3 (L1) - FIRE PROTECTION ED-203.2 FIRST LEVEL - AREA 2 - ELECTRICAL DEMOLITION DRAWINGS AND IS LISTED AS PART OF THE OVERALL
PROJECT INDEX OF DRAWINGS. ▐►VERIFY◄▌
SD-500 STRUCTURAL DEMOLITION ELEV, SECTIONS AND DETAILS FP-204.1 SECOND LEVEL - AREA 1 - FIRE PROTECTION ED-203.3 CRAPO LEVEL 3 - AREA 3 (L1) - ELECTRICAL DEMOLITION F. BASIC FIRE PROTECTION AND THE EXITING SCHEME ARE
S-102 LOWER LEVEL 1 FLOOR PLAN FP-204.2 SECOND LEVEL - AREA 2 - FIRE PROTECTION ED-204.1 SECOND LEVEL - AREA 1 - ELECTRICAL DEMOLITION ILLUSTRATED BY THE EGRESS PLAN(S) AND APPLICABLE
FIRE AND BUILDING CODE SUMMARY ON SHEET ▐►G-002◄▌
S-102.3 LOWER LEVEL 1 FLOOR PLAN - AREA 3 FP-204.3 SKYLIGHT LEVEL - AREAS 1 & 2 - FIRE PROTECTION ED-204.2 SECOND LEVEL - AREA 2 - ELECTRICAL DEMOLITION G. THE ARCHITECTURAL DRAWINGS ESTABLISH, COORDINATE
S-103 FIRST LEVEL FLOOR PLAN ALTERNATE ED-220.1 ROOF - AREA 1 - ELECTRICAL DEMOLITION AS WELL AS TAKE PRECEDENCE FOR THE FINISH
APPEARANCE OF ALL EXPOSED ELEMENTS OF THE WORK OF
S-103.1 FIRST LEVEL FLOOR PLAN - AREA 1 FP-205 ATTIC LEVEL - AREA 1 - FIRE PROTECTION ED-220.2 ROOF - AREA 2 - ELECTRICAL DEMOLITION ALL TRADES INCLUDING THAT WORK WHICH IS ILLUSTRATED
S-103.2 FIRST LEVEL FLOOR PLAN - AREA 2 FP-501 FIRE RISER DIAGRAM ED-231.1 LOWER LEVEL 2 - AREA 1 - FIRE ALARM DEMOLITION PRIMARILY ON DRAWINGS OF OTHER DISCIPLINES.
H. THE DRAWINGS MAY MAKE REFERENCE TO AND/OR
S-104 SECOND LEVEL FLOOR PLAN ED-231.2 LOWER LEVEL 2 - AREA 2 - FIRE ALARM DEMOLITION ILLUSTRATE ITEMS WHICH ARE NOT PART OF THE WORK OF Architect
PLUMBING THE CONTRACT. THESE NOT IN CONTRACT ITEMS ARE
S-104.1 SECOND LEVEL FLOOR PLAN - AREA 1 ED-231.3 CRAPO LEVEL 1 - AREA 3 (LL2) - FIRE ALARM DEMOLITION REFERENCED AND/OR ILLUSTRATED FOR THE RATIO
S-104.2 SECOND LEVEL FLOOR PLAN - AREA 2 PD-201.1 LOWER LEVEL 2 - AREA 1 - PLUMBING DEMOLITION ED-232.1 LOWER LEVEL 1 - AREA 1 - FIRE ALARM DEMOLITION CONTRACTORS REFERENCE, INFORMATION AND 101 South Pennsylvania Street
COORDINATION ONLY. Indianapolis, Indiana 46204
S-105 ROOF FRAMING PLAN PD-201.2 LOWER LEVEL 2 - AREA 2 - PLUMBING DEMOLITION ED-232.2 LOWER LEVEL 1 - AREA 2 - FIRE ALARM DEMOLITION I. THE CONTRACTOR IS RESPONSIBLE TO COMPLY WITH
317-633-4040
S-200 ENLARGED PLANS PD-201.3 CRAPO LEVEL 1 - AREA 3 (LL2) - PLUMBING DEMOLITION ED-232.3 CRAPO LEVEL 2 - AREA 3 (LL1) - FIRE ALARM DEMOLITION APPLICABLE LAWS, CODES, REGULATIONS AND ORDINANCES
OF THE PLACE (CITY, COUNTY, DISTRICT AND STATE) WHERE
S-500 TYPICAL STRUCTURAL STEEL DETAILS PD-202.1 LOWER LEVEL 1 - AREA 1 - PLUMBING DEMOLITION ED-233.1 FIRST LEVEL - AREA 1 - FIRE ALARM DEMOLITION THE PROJECT IS LOCATED - ALTHOUGH SUCH
REQUIREMENTS MAY NOT BE REFLECTED BY THESE Structural Engineer
S-501 STRUCTURAL STEEL SECTIONS AND DETAILS PD-202.2 LOWER LEVEL 1 - AREA 2 - PLUMBING DEMOLITION ED-233.2 FIRST LEVEL - AREA 2 - FIRE ALARM DEMOLITION CONTRACT DOCUMENTS. Fink Roberts & Petrie, Inc.
S-502 STRUCTURAL STEEL SECTIONS AND DETAILS PD-202.3 CRAPO LEVEL 2 - AREA 3 (LL1) - PLUMBING DEMOLITION ED-233.3 CRAPO LEVEL 3 - AREA 3 (L1) - FIRE ALARM DEMOLITION J. EXISTING CONDITIONS SHOWN ARE FROM AVAILABLE
RECORD DRAWINGS AND OR VISUAL FIELD SURVEYS. THE 9449 Priority Way W Dr #200
S-503 STRUCTURAL STEEL SECTIONS AND DETAILS PD-203.1 FIRST LEVEL - AREA 1 - PLUMBING DEMOLITION ED-234.1 SECOND LEVEL - AREA 1 - FIRE ALARM DEMOLITION CONTRACTOR SHALL VERIFY ACTUAL EXISTING CONDITIONS Indianapolis, Indiana 46240
PD-203.2 FIRST LEVEL - AREA 2 - PLUMBING DEMOLITION ED-234.2 SECOND LEVEL - AREA 2 - FIRE ALARM DEMOLITION AT THE SITE PRIOR TO SUBMITTING A BID. THE CONTRACTOR 317-872-8400
SHALL NOTIFY THE ARCHITECT OF ANY DISCREPANCIES.
ARCHITECTURAL PD-204.1 SECOND LEVEL - AREA 1 - PLUMBING DEMOLITION ED-501 RISER DIAGRAM - MAIN DISTRIBUTION & 480V ELECTRICAL K. THE CONTRACTOR SHALL OBTAIN ALL REQUIRED PERMITS
A-001 GENERAL NOTES, SYMBOLS, AND STANDARD MOUNTING PD-204.2 SECOND LEVEL - AREA 2 - PLUMBING DEMOLITION DEMOLITION AND SIMILAR RELEASES REQUIRED FOR THE
Mechanical / Electrical Engineer
CONSTRUCTION AND OCCUPANCY OF THE PROJECT. THE
HEIGHTS PD-205.1 ATTIC LEVEL - AREA 1 - PLUMBING DEMOLITION ED-502 ELEVATIONS - WIREWAY DEMOLITION CONTRACTOR SHALL FURNISH COPIES OF ALL SUCH ITEMS R.E. Dimond & Associates, Inc.
TO THE OWNER AND ARCHITECT WITHIN 10 DAYS OF
A-002 INTERIOR PARTITION TYPES AND STANDARD PARTITION PD-220.1 ROOF - AREA 1 - PLUMBING DEMOLITION E-201.1 LOWER LEVEL 2 - AREA 1 - LIGHTING RECEIPT OF SUCH ITEMS. IF PERMITS ARE ISSUED SUBJECT 732 N Capitol Avenue
DETAILS PD-220.2 ROOF - AREA 2 - PLUMBING DEMOLITION E-201.2 LOWER LEVEL 2 - AREA 2 - LIGHTING TO CERTAIN CONDITIONS OR REVISIONS TO THE WORK OR IF Indianapolis, Indiana 46204
AE-101 LOWER LEVEL 2 EXISTING PLAN PERMITS ARE DELAYED FOR ANY REASON, THE 317-634-4672
P-100.2 UNDERSLAB - AREA 2 - PLUMBING E-201.3 CRAPO LEVEL 1 - AREA 3 (LL2) - LIGHTING CONTRACTOR SHALL NOTIFY THE OWNER AND ARCHITECT.
AE-102 LOWER LEVEL 1 EXISTING PLAN P-201.1 LOWER LEVEL 2 - AREA 1 - PLUMBING E-202.1 LOWER LEVEL 1 - AREA 1 - LIGHTING L. THE CONTRACTOR SHALL TAKE PRECAUTIONS TO MAINTAIN
AND PROTECT NEW WORK AS WELL AS EXISTING SYSTEMS
AE-103 FIRST LEVEL EXISTING PLAN P-201.2 LOWER LEVEL 2 - AREA 2 - PLUMBING E-202.2 LOWER LEVEL 1 - AREA 2 - LIGHTING AND ELEMENTS WHICH ARE TO REMAIN. ANY DAMAGE TO
AE-104 SECOND LEVEL EXISTING PLAN P-202.1 LOWER LEVEL 1 - AREA 1 - PLUMBING E-202.3 CRAPO LEVEL 2 - AREA 3 (LL1) - LIGHTING SUCH SYSTEMS AND ELEMENTS SHALL BE IMMEDIATELY
REPAIRED IN A MANNER ACCEPTABLE TO THE ARCHITECT.
AD-111 LOWER LEVEL 2 DEMOLITION PLAN P-202.2 LOWER LEVEL 1 - AREA 2 - PLUMBING E-203.1 FIRST LEVEL - AREA 1 - LIGHTING IF SATISFACTORY REPAIRS CANNOT BE MADE, THE
AD-112 LOWER LEVEL 1 DEMOLITION PLAN CONTRACTOR SHALL REPLACE SYSTEMS AND ELEMENTS
P-203.1 FIRST LEVEL - AREA 1 - PLUMBING E-203.2 FIRST LEVEL - AREA 2 - LIGHTING WITH LIKE NEW QUALITY ACCEPTABLE TO THE ARCHITECT.
AD-113 FIRST LEVEL DEMOLITION PLAN P-203.2 FIRST LEVEL - AREA 2 - PLUMBING E-203.3 CRAPO LEVEL 3 - AREA 3 (L1) - LIGHTING ALL REPAIRS AND REPLACEMENT COST SHALL BE THE
FINANCIAL RESPONSIBILITY OF THE CONTRACTOR.
AD-114 SECOND LEVEL DEMOLITION PLAN P-204.1 SECOND LEVEL - AREA 1 - PLUMBING E-204.1 SECOND LEVEL - AREA 1 - LIGHTING
AD-115 ROOF DEMOLITION PLAN P-204.2 SECOND LEVEL - AREA 2 - PLUMBING E-204.2 SECOND LEVEL - AREA 2 - LIGHTING REV. 03/31/09
AD-201 EXTERIOR DEMO ELEVATIONS P-205.1 ATTIC LEVEL - AREA 1 - PLUMBING E-211.1 LOWER LEVEL 2 - AREA 1 - POWER
A-101 LOWER LEVEL 2 OVERALL FLOOR PLAN P-220.1 ROOF - AREA 1 - PLUMBING E-211.2 LOWER LEVEL 2 - AREA 2 - POWER
A-101.1 LOWER LEVEL 2 FLOOR PLAN - AREA 1 P-220.2 ROOF - AREA 2 - PLUMBING E-211.3 CRAPO LEVEL 1 - AREA 3 (LL2) - POWER
A-101.2 LOWER LEVEL 2 FLOOR PLAN - AREA 2 P-301 ENLARGED PLANS - PLUMBING E-212.1 LOWER LEVEL 1 - AREA 1 - POWER
A-102 LOWER LEVEL 1 OVERALL FLOOR PLAN P-401 DETAILS - PLUMBING E-212.2 LOWER LEVEL 1 - AREA 2 - POWER
A-102.1 LOWER LEVEL 1 FLOOR PLAN - AREA 1 P-601 SCHEDULES - PLUMBING E-212.3 CRAPO LEVEL 2 - AREA 3 (LL1) - POWER
A-102.2 LOWER LEVEL 1 FLOOR PLAN - AREA 2 E-213.1 FIRST LEVEL - AREA 1 - POWER
A-102.3 CRAPO LEVEL 2 FLOOR PLAN - AREA 3 (LL1) MECHANICAL E-213.2 FIRST LEVEL - AREA 2 - POWER
A-103 FIRST LEVEL OVERALL FLOOR PLAN PM-001 SYMBOLS, ABBREVIATIONS, & GENERAL NOTES - MECHANICAL E-213.3 CRAPO LEVEL 3 - AREA 3 (L1) - POWER
A-103.1 FIRST LEVEL FLOOR PLAN - AREA 1 MD-201.1 LOWER LEVEL 2 - AREA 1 - MECHANICAL DEMOLITION E-214.1 SECOND LEVEL - AREA 1 - POWER
A-103.2 FIRST LEVEL FLOOR PLAN - AREA 2 MD-201.2 LOWER LEVEL 2 - AREA 2 - MECHANICAL DEMOLITION E-214.2 SECOND LEVEL - AREA 2 - POWER
A-103.3 CRAPO LEVEL 3 FLOOR PLAN - AREA 3 (L1) MD-202.1 LOWER LEVEL 1 - AREA 1 - MECHANICAL DEMOLITION E-220.1 ROOF - AREA 1 - ELECTRICAL
A-104 SECOND LEVEL OVERALL FLOOR PLAN MD-202.2 LOWER LEVEL 1 - AREA 2 - MECHANICAL DEMOLITION E-220.2 ROOF - AREA 2 - ELECTRICAL
A-104.1 SECOND LEVEL FLOOR PLAN - AREA 1 MD-202.3 CRAPO LEVEL 2 - AREA 3 (LL1) - MECHANICAL DEMOLITION E-231.1 LOWER LEVEL 2 - AREA 1 - FIRE ALARM
A-104.2 SECOND LEVEL FLOOR PLAN - AREA 2 MD-203.1 FIRST LEVEL - AREA 1 - MECHANICAL DEMOLITION E-231.2 LOWER LEVEL 2 - AREA 2 - FIRE ALARM REGION MAP
A-105 ROOF PLAN - OVERALL MD-203.2 FIRST LEVEL - AREA 2 - MECHANICAL DEMOLITION E-231.3 CRAPO LEVEL 1 - AREA 3 (LL2) - FIRE ALARM
A-105.1 SKYLIGHT PLAN MD-203.3 CRAPO LEVEL 1 - AREA 3 (L1) - MECHANICAL DEMOLITION E-232.1 LOWER LEVEL 1 - AREA 1 - FIRE ALARM
A-131.1 LOWER LEVEL 2 REFLECTED CEILING PLAN - AREA 1 MD-204.1 SECOND LEVEL - AREA 1 - MECHANICAL DEMOLITION E-232.2 LOWER LEVEL 1 - AREA 2 - FIRE ALARM
A-131.2 LOWER LEVEL 2 REFLECTED CEILING PLAN - AREA 2 MD-204.2 SECOND LEVEL - AREA 2 - MECHANICAL DEMOLITION E-232.3 CRAPO LEVEL 2 - AREA 3 (LL1) - FIRE ALARM
A-132.1 LOWER LEVEL 1 REFLECTED CEILING PLAN - AREA 1 MD-205.1 ATTIC LEVEL - AREA 1 MECHANICAL DEMOLITION E-233.1 FIRST LEVEL - AREA 1 - FIRE ALARM
A-132.2 LOWER LEVEL 1 REFLECTED CEILING PLAN - AREA 2 MD-220.1 ROOF - AREA 1 - MECHANICAL DEMOLITION E-233.2 FIRST LEVEL - AREA 2 - FIRE ALARM
A-132.3 LOWER LEVEL 1 REFLECTED CEILING PLAN - AREA 3 MD-220.2 ROOF - AREA 2 - MECHANICAL DEMOLITION E-233.3 CRAPO LEVEL 3 - AREA 3 (L1) - FIRE ALARM
A-133.1 FIRST LEVEL REFLECTED CEILING PLAN - AREA 1 M-201.1 LOWER LEVEL 2 - AREA 1 - AIR DISTRIBUTION E-234.1 SECOND LEVEL - AREA 1 - FIRE ALARM
A-133.2 FIRST LEVEL REFLECTED CEILING PLAN - AREA 2 M-201.2 LOWER LEVEL 2 - AREA 2 - AIR DISTRIBUTION E-234.2 SECOND LEVEL - AREA 2 - FIRE ALARM
A-133.3 FIRST LEVEL REFLECTED CEILING PLAN - AREA 3 M-202.1 LOWER LEVEL 1 - AREA 1 - AIR DISTRIBUTION E-235.1 ATTIC LEVEL - AREA 1 - FIRE ALARM
A-134.1 SECOND LEVEL REFLECTED CEILING PLAN - AREA 1 M-202.2 LOWER LEVEL 1 - AREA 2 - AIR DISTRIBUTION E-310 LOWER LEVEL 2 BOILER ROOM UNIT F - ELECTRICAL SEAL | DATE 04/01/21
A-134.2 SECOND LEVEL REFLECTED CEILING PLAN - AREA 2 M-202.3 CRAPO LEVEL 2 - AREA 3 (LL1) - AIR DISTRIBUTION E-401 DETAILS - GROUNDING PROJECT
LOCATION
A-152.2 LOWER LEVEL 1 FINISH PLAN - AREA 2 M-203.1 FIRST LEVEL - AREA 1 - AIR DISTRIBUTION E-402 DETAILS - LIGHTING
A-152.3 LOWER LEVEL 1 FINISH PLAN - AREA 3 M-203.2 FIRST LEVEL - AREA 2 - AIR DISTRIBUTION E-403 DETAILS - ELECTRICAL
A-153.2 FIRST LEVEL FINISH PLAN - AREA 2 M-203.3 CRAPO LEVEL 3 - AREA 3 (L1) - AIR DISTRIBUTION E-404 DETAILS - ELECTRICAL
A-153.3 FIRST LEVEL FINISH PLAN - AREA 3 M-204.1 SECOND LEVEL - AREA 1 - AIR DISTRIBUTION E-501 RISER DIAGRAM - MAIN DISTRIBUTION & 480V ELECTRICAL
A-154.1 SECOND LEVEL FINISH PLAN - AREA 1 M-204.2 SECOND LEVEL - AREA 2 - AIR DISTRIBUTION E-502 RISER DIAGRAM - 208V ELECTRICAL
A-154.2 SECOND LEVEL FINISH PLAN - AREA 2 M-205.1 ATTIC LEVEL - AREA 1 - AIR DISTRIBUTION E-503 RISER DIAGRAM - EMERGENCY ELECTRICAL
A-172 LOWER LEVEL 1 FURNITURE PLAN M-211.1 LOWER LEVEL 2 - AREA 1 - HYDRONICS E-504 RISER DIAGRAM - CRAPO HALL
A-173 FIRST LEVEL FURNITURE PLAN M-211.2 LOWER LEVEL 2 - AREA 2 - HYDRONICS E-505 TRANSFORMER SCHEDULE
A-174 SECOND LEVEL FURNITURE PLAN M-212.1 LOWER LEVEL 1 - AREA 1 - HYDRONICS E-506 ELEC. PANELBOARD INTERIOR RETROFIT SCHEDULE SHEET ISSUE
A-201 EXTERIOR ELEVATIONS M-212.2 LOWER LEVEL 1 - AREA 2 - HYDRONICS E-601 SCHEDULES - LIGHTING 1 Construction Documents 04/01/21
A-202 EXTERIOR ELEVATIONS M-212.3 CRAPO LEVEL 2 - AREA 3 (LL1) - HYDRONICS E-611 SCHEDULES - PANELBOARDS - MAIN DISTRIBUTION
A-301 BUILDING SECTIONS M-213.1 FIRST LEVEL - AREA 1 - HYDRONICS E-612 SCHEDULES - PANELBOARDS - EMERGENCY
A-321 ROOF MONITOR SECTIONS M-213.2 FIRST LEVEL - AREA 2 - HYDRONICS E-613 SCHEDULES - PANELBOARDS - EMERGENCY
A-322 ROOF MONITOR SECTIONS M-213.3 CRAPO LEVEL 3 - AREA 3 (L1) - HYDRONICS E-614 SCHEDULES - PANELBOARDS - AREA A
A-350 EXTERIOR DETAILS M-214.1 SECOND LEVEL - AREA 1 - HYDRONICS E-615 SCHEDULES - PANELBOARDS - AREA B
A-351 EXTERIOR DETAILS M-214.2 SECOND LEVEL - AREA 2 - HYDRONICS E-616 SCHEDULES - PANELBOARDS - AREA B
A-401 ENLARGED PLANS M-220.1 ROOF - AREA 1 - AIR DISTRIBUTION E-617 SCHEDULES - PANELBOARDS - AREA C
A-402 CAFE M-220.2 ROOF - AREA 2 - AIR DISTRIBUTION E-618 SCHEDULES - PANELBOARDS - AREA C PROJECT LOCATION
A-403 CAFE M-301 ATTIC MECHANICAL ROOM UNIT A (AHU-1) E-619 SCHEDULES - PANELBOARDS - AREA D
A-404 LIVING WALL M-302 MECHANICAL ROOM B207 (AHU-3) E-620 SCHEDULES - PANELBOARDS - AREA D
A-421 STAIR AND RAMP PLANS AND SECTIONS M-303 MECHANICAL ROOM C201 (AHU-5) E-621 SCHEDULES - PANELBOARDS - AREA E
A-422 STAIR AND RAMP PLANS, SECTIONS, AND DETAILS M-304 MECHANICAL ROOM C218 (AHU-6) E-622 SCHEDULES - PANELBOARDS - AREA E
A-423 STAIR AND RAMP DETAILS M-305 MECHANICAL ROOM C214 (AHU-7) E-623 SCHEDULES - PANELBOARDS - AREA F
A-501 INTERIOR ELEVATIONS M-306 MECHANICAL ROOM C215 (AHU-8) E-624 SCHEDULES - PANELBOARDS - TELECOM B107A
A-502 INTERIOR ELEVATIONS M-307 MECHANICAL ROOM E201 (AHU-9) E-625 SCHEDULES - PANELBOARDS - CRAPO
A-530 MILLWORK DETAILS M-308 MECHANICAL ROOM G116 (AHU-10)
A-531 MILLWORK DETAILS M-309 MECHANICAL ROOM FL201 (AHU-11 E.) TELECOMMUNICATIONS PROJECT
A-532 PLAN DETAILS M-310 SECOND LEVEL - CENTRAL MONITOR - AIR DISTRIBUTION T-001 SYMBOLS, ABBREVIATIONS, & GENERAL NOTES - TELECOM. LOCATION
A-540 CEILING DETAILS M-311 SECOND LEVEL - CENTRAL MONITOR - HYDRONICS TD-201.1 LOWER LEVEL 2 - AREA 1 - TELECOM. DEMOLITION
A-601 DOOR SCHEDULE M-321 SECTIONS - MECHANICAL TD-201.2 LOWER LEVEL 2 - AREA 2 - TELECOM. DEMOLITION
A-602 DOOR DETAILS M-322 SECTIONS - MECHANICAL TD-201.3 CRAPO LEVEL 1 - AREA 3 (LL2) - TELECOM. DEMOLITION
A-621 WINDOW ELEVATIONS AND DETAILS M-323 SECTIONS - MECHANICAL TD-202.1 LOWER LEVEL 1 - AREA 1 - TELECOM. DEMOLITION COPYRIGHT NOTICE: THIS ARCHITECTURAL AND ENGINEERING DRAWING IS GIVEN IN CONFIDENCE
A-622 EXTERIOR WINDOW ELEVATIONS AND DETAILS M-324 SECTIONS - MECHANICAL TD-202.2 LOWER LEVEL 1 - AREA 2 - TELECOM. DEMOLITION AND SHALL BE USED ONLY PURSUANT TO THE AGREEMENT WITH RATIO. NO OTHER USE,
DISSEMINATION OR DUPLICATION MAY BE MADE WITHOUT PRIOR WRITTEN CONSENT OF RATIO. ALL
A-650 FINISH SCHEDULE AND FINISH DETAILS M-401 DETAILS - AIR DISTRIBUTION TD-202.3 CRAPO LEVEL 2 - AREA 3 (LL1) - TELECOM. DEMOLITION
COMMON LAW RIGHTS OF COPYRIGHT AND OTHERWISE ARE HEREBY SPECIFICALLY RESERVED.
A-901 3D ROOF AXONS M-402 DETAILS - AIR DISTRIBUTION TD-203.1 FIRST LEVEL - AREA 1 - TELECOM. DEMOLITION PROJECT NO. 19010.000
M-411 DETAILS - HYDRONICS TD-203.2 FIRST LEVEL - AREA 2 - TELECOM. DEMOLITION SHEET TITLE
FIRE PROTECTION
FD-201.1 LOWER LEVEL 2 - AREA 1 - FIRE PROTECTION DEMOLITION
M-412
M-415
DETAILS - HYDRONICS
AHU - PROFILES
TD-203.3
TD-204.1
CRAPO LEVEL 3 - AREA 3 (L1) - TELECOM. DEMOLITION
SECOND LEVEL - AREA 1 - TELECOM. DEMOLITION
SHEET INDEX AND
FD-201.2 LOWER LEVEL 2 - AREA 2 - FIRE PROTECTION DEMOLITION M-416 AHU - PROFILES TD-204.2 SECOND LEVEL - AREA 2 - TELECOM. DEMOLITION PROJECT LOCATION
FD-202.1 LOWER LEVEL 1 - AREA 1 - FIRE PROTECTION DEMOLITION M-417 AHU - PROFILES T-201.1 LOWER LEVEL 2 - AREA 1 - TELECOM.
FD-202.2 LOWER LEVEL 1 - AREA 2 - FIRE PROTECTION DEMOLITION M-601 SCHEDULES - AIR DISTRIBUTION T-201.2 LOWER LEVEL 2 - AREA 2 - TELECOM.
4/1/2021 12:32:11 PM
FD-203.1 FIRST LEVEL - AREA 1 - FIRE PROTECTION DEMOLITION M-602 SCHEDULES - AIR DISTRIBUTION T-201.3 CRAPO LEVEL 1 - AREA 3 (LL2) - TELECOM.
FD-203.2 FIRST LEVEL - AREA 2 - FIRE PROTECTION DEMOLITION M-611 SCHEDULES - HYDRONICS T-202.1 LOWER LEVEL 1 - AREA 1 - TELECOM.
FD-204.1 SECOND LEVEL - AREA 1 - FIRE PROTECTION DEMOLITION SHEET NUMBER
M-701 CONTROLS - GENERAL T-202.2 LOWER LEVEL 1 - AREA 2 - TELECOM.
G-002
CODE SUMMARY GENERAL LIFE SAFETY PLAN NOTES
A. REFER TO SHEET G-003 FOR CODE SUMMARY.
B. REFER TO DOOR SCHEDULE FOR REQUIRED DOOR RATING.
RHIT MOENCH
2222222222222222
2222222222222222
C. REFER TO INTERIOR PARTITION TYPES AND FLOOR PLAN
FOR ADDITIONAL PARTITION REQUIREMENTS INCLUDING
WALL HEIGHT, UL DESIGN, AND FIRE RATING.
D. REFER TO [site plan] FOR BUILDING ADJACENCIES AND
RENOVATION
PROPERTY LINES.
E. REFER TO [demolition plans, site plan, phasing drawings] FOR
5500 Wabash Avenue
TEMPORARY CONSTRUCTION REQUIREMENTS.
F. REFER TO FLOOR PLANS FOR FIRE EXTINGUISHER Terre Haute, Indiana
2222
2222
LOCATIONS.
DW
222 FEC 222 Owner
LIFE SAFETY PLAN LEGEND
22
22
22
22
222 222 Rose-Hulman Institute of Technology
5500 Wabash Avenue
RM NAME ROOM NAME, AREA & Terre Haute, Indiana 47803
2222 150 SF OCCUPANT CAPACITY 812-877-1511
22222
20
EXIT DIRECTION ARROW
3333333333333333333333333 3333333333333333333333333333333333333333333333 45 EXIT POPULATION
120 EXIT CAPACITY [POPULATION]
PATH OF TRAVEL
22
Indianapolis, Indiana 46240
2222222 FIRE RATED CEILING. RATING AS
1-HR NOTED...1-HR, 2-HR, ETC. 317-872-8400
DN
Mechanical / Electrical Engineer
R.E. Dimond & Associates, Inc.
OCCUPANT LOAD SCHEDULE 732 N Capitol Avenue
Indianapolis, Indiana 46204
FLOOR LEVEL OCCUPANT LOAD 317-634-4672
LOWER LEVEL 2 200
LOWER LEVEL 350
550
22
22
22
TRAVEL DIST. A 112' - 0"
333333333333333
TRAVEL DIST. B 80' - 0"
G-003
1/32" = 1'-0"
APPROVED VARIANCES
VARIANCE
NUMBER DESCRIPTION
13-xx-xx(a)
13-xx-xx(b)
13-xx-xx(c)
13-xx-xx(d)
13-xx-xx(e)
D4 LOWER LEVEL 1 LIFE SAFETY PLAN
G-003
1/32" = 1'-0"
11
11
2222
2222
333333333333333333333333333333333333333333333333 333333333333333333333333333333333333333333333333
SEAL | DATE 04/01/21
222 222
22
22
22
22
222 222
3333333333333333333333333333333333333333333333 3333333333333333333333333333333333333333333333
SHEET ISSUE
1 Construction Documents 04/01/21
TO48
TO48
TO48
22 22
22
22
22
22
SHEET NUMBER
A2 FIRST LEVEL LIFE SAFETY PLAN A4 SECOND LEVEL LIFE SAFETY PLAN
G-003
1/32" = 1'-0"
G-003
1/32" = 1'-0" G-003
1.0 GENERAL PROJECT INFORMATION 13. PRINCIPAL OPENING SIZES AND LOCATIONS ARE INDICATED ON THE STRUCTURAL 1.3 SUBMITTALS 1.5 DEMOLITION AND STRUCTURAL REINFORCEMENT:
DRAWINGS. ADDITIONAL SMALLER OPENINGS, BLOCK OUTS AND SLEEVES MAY BE
1. STRUCTURAL DRAWINGS ARE PART OF A SINGLE DOCUMENT ISSUE INCLUDING REQUIRED BY OTHER TRADES AND SHALL BE CONSTRUCTED USING THE CRITERIA 1. THE CONTRACTOR SHALL SUBMIT FOR STRUCTURAL ENGINEER'S REVIEW A 1. REFER TO "SD" DRAWINGS FOR STRUCTURAL DEMOLITION WORK.
MULTIPLE DISCIPLINES. STRUCTURAL DRAWINGS AND SPECIFICATIONS ARE FULLY INDICATED IN THE STRUCTURAL DOCUMENTS. IF NO DETAILS ARE APPLICABLE, SCHEDULE WHICH DETAILS THE ESTIMATED QUANTITY OF SHOP DRAWINGS FOR
COMPLIMENTARY AND SUPPLEMENTAL TO EACH OTHER AND SHALL BE TAKEN AS A SUBMIT PROPOSED METHOD TO THE STRUCTURAL ENGINEER FOR APPROVAL. EACH SUBMITTAL AND THE DATE SHOP DRAWINGS WILL BE RECEIVED BY THE 2. CONTRACTOR SHALL DOCUMENT EXISTING CRACKS AND STRUCTURAL DAMAGE
WHOLE. WHERE CONFLICTS OCCUR, STRICTER REQUIREMENTS APPLY.
STRUCTURAL WORK PERFORMED UNDER THESE DRAWINGS AND SPECIFICATIONS
SHALL BE COORDINATED WITH EACH INDIVIDUAL CONTRACTOR. SEE DIVISION 1 OF
14. THERE SHALL BE NO VERTICAL OR HORIZONTAL SLEEVES SET, OR HOLES CUT OR
DRILLED IN ANY BEAM OR COLUMN UNLESS IT IS SHOWN ON THE STRUCTURAL
STRUCTURAL ENGINEER. THE STRUCTURAL ENGINEER SHALL HAVE THE
OPPORTUNITY TO REVIEW THE PROPOSED SCHEDULE AND SUBMIT COMMENTS TO
THE CONTRACTOR. THE FINAL SHOP DRAWING SCHEDULE SHALL BE MUTUALLY 3.
PRIOR TO BEGINNING DEMOLITION WORK.
GENERAL NOTES
3/31/2021 5:22:19 PM
SHEET NUMBER
S-001
3.2 REINFORCING STEEL 5.0 STRUCTURAL STEEL 5.40 NON LOAD BEARING COLD FORMED METAL STUDS FOR EXTERIOR WALLS
AND SOFFITS
1. PROVIDE MINIMUM CONCRETE COVER FOR REINFORCING STEEL IN 1. STRUCTURAL STEEL CONSTRUCTION SHALL CONFORM TO AISC 360, THE
ACCORDANCE WITH THE ACI “BUILDING CODE REQUIREMENTS FOR AMERICAN INSTITUTE OF STEEL CONSTRUCTION “SPECIFICATION FOR 1. EXTERIOR WALL METAL STUD CLADDING BACKUP SYSTEMS AND THEIR
STRUCTURAL CONCRETE” (ACI 318), UNLESS OTHERWISE INDICATED. STRUCTURAL STEEL BUILDINGS. CONNECTIONS TO THE STRUCTURE ARE TO BE DESIGNED, FURNISHED AND
INSTALLED BY THE CONTRACTOR. SEE CLADDING BACKUP DESIGN CRITERIA
FOR PERFORMANCE REQUIREMENTS
RHIT MOENCH
2. SPREAD REINFORCING STEEL AROUND SMALL OPENINGS AND SLEEVES IN 2. SHOP CONNECTIONS, UNLESS OTHERWISE SHOWN, MAY BE EITHER BOLTED OR
SLABS AND WALLS, WHERE POSSIBLE, AND WHERE BAR SPACING WILL NOT
EXCEED 1.5 TIMES THE NORMAL SPACING. DISCONTINUE BARS AT LARGE
OPENINGS, WHERE NECESSARY, AND PROVIDE AN AREA OF REINFORCEMENT,
WELDED. FIELD CONNECTIONS SHALL BE BOLTED UNLESS OTHERWISE
DETAILED ON THE DRAWINGS. 2. SEE DIVISION 5 SPECIFICATION SECTIONS OF THE PROJECT MANUAL FOR
ADDITIONAL CRITERIA.
RENOVATION
EQUAL TO THE INTERRUPTED REINFORCEMENT, IN FULL LENGTH BARS,
DISTRIBUTING ONE-HALF EACH SIDE OF THE OPENING. WHERE SHRINKAGE AND
3. BOLTED CONNECTIONS SHALL BE BEARING-TYPE CONNECTIONS USING 3/4 INCH
DIAMETER ASTM A325-N BOLTS WITH STANDARD 13/16 INCH DIAMETER HOLES, 3. SEE ARCHITECTURAL DRAWINGS FOR ADDITIONAL INFORMATION AND FOR
REQUIRED DEPTHS OF MEMBERS TO BE INTEGRATED INTO THE WALL SECTIONS.
5500 Wabash Avenue
TEMPERATURE REINFORCEMENT IS INTERRUPTED, ADD (2)-#5 x OPENING UNLESS OTHERWISE NOTED OR DETAILED ON THE DRAWINGS, OR APPROVED
DIMENSION +4’-0’ ON EACH SIDE OF THE OPENING. PROVIDE #5 x 4’-0” DIAGONAL
BARS IN BOTH FACES, AT EACH CORNER OF OPENINGS LARGER THAN 12 INCHES
BY THE STRUCTURAL ENGINEER. Terre Haute, Indiana
IN ANY DIRECTION. 4. PREPARATION OF FAYING SURFACES AND TENSIONING OF SLIP CRITICAL BOLTS
SHALL BE IN ACCORDANCE WITH THE “RCSC SPECIFICATION FOR STRUCTURAL 47803
3. MECHANICAL SPLICES, EMBEDDED DOWELS WITH MECHANICAL SPLICES, AND JOINTS USING HIGH STRENGTH BOLTS.” 5.41 COLD-FORMED METAL FRAMING
DOWEL BAR SUBSTITUTES, WHICH ARE USED IN LIEU OF LAP SPLICES, SHALL Owner
DEVELOP 125% OF THE SPECIFIED YIELD STRENGTH OF THE REINFORCING BAR 5. TENSION BOLTS IN ACCORDANCE WITH SECTION 8 OF THE “SPECIFICATION FOR
PER ACI REQUIREMENTS, AND SHALL BE USED ONLY WHERE INDICATED OR STRUCTURAL JOINTS USING HIGH STRENGTH BOLTS”, UNLESS NOTED 1. SEE SECTION 054100 OF THE PROJECT MANUAL FOR ADDITIONAL Rose-Hulman Institute of Technology
WHERE APPROVED BY THE ENGINEER OF RECORD. OTHERWISE. INFORMATION AND CRITERIA. 5500 Wabash Avenue
2. COLD-FORMED METAL FRAMING (CFMF) MEMBERS THROUGHOUT THE Terre Haute, Indiana 47803
4. POSITION DOWELS FOR VERTICAL WALL REINFORCEMENT IN COLUMN 6. CONNECTIONS WHICH ARE NOT FULLY DETAILED ON THE STRUCTURAL 812-877-1511
FOOTINGS AND WALL FOOTING STEPS WITH 6 INCHES MAXIMUM BOTTOM DRAWINGS SHALL BE DESIGNED BY THE STEEL FABRICATOR IN ACCORDANCE DRAWINGS ARE DESIGNATED IN ACCORDANCE WITH THE STEEL STUD
COVER. WITH THE AISC “MANUAL OF STEEL CONSTRUCTION”, AND SHALL BE DESIGNED MANUFACTURERS ASSOCIATION (SSMA) IDENTIFICATION SYSTEM. ALL
AND DETAILED BY A PROFESSIONAL ENGINEER LICENSED IN THE STATE WHERE SUBMITTALS AND SHOP DRAWINGS PERTAINING TO CFMF SHALL ADHERE TO THE
5. FIELD BENDING OF REINFORCING STEEL IS PROHIBITED. THE PROJECT IS LOCATED. SAME IDENTIFICATION SYSTEM. ALL SECTIONS FURNISHED SHALL MEET OR
EXCEED THE SSMA LISTED SECTION PROPERTIES.
6. SEE DIVISION 1 AND DIVISION 3 SPECIFICATIONS OF THE PROJECT MANUAL FOR A. ALL STEEL CONNECTION FORCES INDICATED WITHIN THE DRAWINGS 3. REFER TO PLANS FOR WALL AND HEADER TYPES. REFER TO WALL AND
SPECIFIED INSPECTION REQUIREMENTS. COORDINATE POUR SCHEDULES WITH ARE SERVICE LEVEL LOADS (ASD) UNLESS NOTED OTHERWISE. HEADER SCHEDULES FOR MEMBER TYPE, SIZE, AND THICKNESS REQUIRED.
THE A/E AND THE INSPECTION AGENCY TO ALLOW ADEQUATE TIME AND
PREPARATION FOR OBSERVATION AND INSPECTION. B. BEAM END CONNECTIONS SHALL BE DESIGNED FOR THE VERTICAL 4. MINIMUM YIELD STRENGTH (FY) FOR ALL CFMF MEMBERS OF 33 AND 43 MIL (1/1000
SHEAR REACTIONS INDICATED ON THE FRAMING PLANS. WHERE SUCH INCHES) THICKNESS SHALL BE 33KSI. MINIMUM YIELD STRENGTH OF ALL CFMF
REACTIONS HAVE NOT BEEN INDICATED, NON-COMPOSITE BEAM MEMBERS OF 54, 68, AND 97 MIL THICKNESS SHALL BE 50KSI.
CONNECTIONS (BEAMS WITHOUT SHEAR STUDS) SHALL BE DESIGNED
FOR ONE-HALF THE BEAM LOAD CAPACITY AS GIVEN IN THE AISC
Architect
5. UNLESS SPECIFICALLY NOTED OTHERWISE, ALL STRUCTURAL TRACK
“ALLOWABLE LOADS ON BEAMS” TABLE. SECTIONS USED IN LOAD-BEARING AND EXTERIOR WALLS SHALL BE T125 RATIO
3.3 CAST IN PLACE CONCRETE
WITH DEPTH TO MATCH SPECIFIED WALL. 101 South Pennsylvania Street
C. BEAM WEB SHEAR CONNECTIONS SHALL TYPICALLY BE DOUBLE
1. THE MIXING, HANDLING, PLACING, AND CURING OF CONCRETE SHALL BE IN ANGLES, 5/16 INCH MINIMUM THICKNESS, UNLESS DETAILED OTHERWISE, 6. ALL STUDS, TRACKS, BRIDGING AND ACCESSORIES SHALL BE FORMED FROM Indianapolis, Indiana 46204
ACCORDANCE WITH THE ACI “BUILDING CODE REQUIREMENTS FOR STRUCTURAL OR WHERE OTHERWISE PERMITTED BY TYPICAL BEAM CONNECTION STEEL HAVING A GALVANIZED COATING MEETING THE REQUIREMENTS OF 317-633-4040
CONCRETE” (ACI 318). DETAILS. ASTM A653. PROVIDE G60 COATING MINIMUM, UNLESS NOTED OTHERWISE.
PROVIDE G90 COATING AT FRAMING AT FRAMING OUTSIDE OF BUILDING
2. SEE ARCHITECTURAL DRAWINGS FOR CHAMFER REQUIREMENTS FOR CORNERS D. PRIOR TO THE REVIEW OF THE STRUCTURAL STEEL SHOP DRAWINGS, INSULATION ENEVELOPE, SUCH AS OVERHANGS, SOFFITS, ETC.. Structural Engineer
OF CONCRETE. WHERE NOT INDICATED, PROVIDE ¾” CHAMFERS ON EXPOSED SUBMIT CONNECTIONS NOT SPECIFICALLY DETAILED ON THE DRAWINGS
CORNERS OF CONCRETE EXCEPT THOSE ABUTTING MASONRY. TO THE STRUCTURAL ENGINEER FOR REVIEW. 7. A MINIMUM UN-PUNCHED LENGTH OF 10” IS REQUIRED AT EACH END OF ALL
Fink Roberts & Petrie, Inc.
LOAD-BEARING AND EXTERIOR WALL STUDS. NO PUNCHING OF HOLES OF 9449 Priority Way W Dr #200
3. SEE DIVISION 3 SPECIFICATION, CAST-IN-PLACE CONCRETE SECTION, OF THE E. FOR CONNECTION DESIGN AND DETAILING, SET CONNECTION WORK ANY TYPE SHALL BE PERMITTED IN THESE AREAS. CFMF MEMBERS USED IN Indianapolis, Indiana 46240
PROJECT MANUAL FOR CONCRETE MIX PROPORTIONING REQUIREMENTS. POINT AT INTERSECTION OF MEMBER CENTERLINES, UNLESS HEADER CONSTRUCTION SHALL BE UN-PUNCHED FOR THEIR ENTIRE LENGTH. 317-872-8400
OTHERWISE NOTED OR UNLESS ECCENTRICITY IS ACCOUNTED FOR IN
4. SEE DIVISION 3 SPECIFICATION CONCRETE FORMWORK SECTION OF THE PROJECT CONNECTION DESIGN AND DOES NOT ADVERSELY IMPACT MEMBER 8. FIELD WELDING OF COLD FORMED FRAMING ELEMENTS SHALL NOT BE
MANUAL, FOR FORM REMOVAL AND RESHORING REQUIREMENTS. CAPACITY. PERMITTED FOR ANY ELEMENT OF THICKNESS LESS THAN 68 MILS, UNLESS
NOTED OTHERWISE. Mechanical / Electrical Engineer
5. SEE DIVISION 3 SPECIFICATION, CAST-IN-PLACE CONCRETE SECTION OF THE F. ALL BEAM REACTIONS, AXIAL FORCES AND MOMENTS ACT
PROJECT MANUAL, FOR HOT WEATHER CONCRETING REQUIREMENTS. R.E. Dimond & Associates, Inc.
CONCURRENTLY UON. 9. BOTH FLANGES OF LOAD-BEARING WALL STUDS SHALL BE ATTACHED TO
732 N Capitol Avenue
6. SEE DIVISION 3 SPECIFICATION, CAST-IN-PLACE CONCRETE SECTION OF THE THE TOP AND BOTTOM TRACKS WITH ONE #12 SCREW EACH FLANGE OR 1
G. BEAM REACTIONS ACT IN GRAVITY DIRECTION WHEREAS AXIAL FORCES INCH LONG FILLET WELDS EACH FLANGE. WELD OPTION NOT PERMITTED Indianapolis, Indiana 46204
PROJECT MANUAL, FOR COLD WEATHER CONCRETING REQUIREMENTS. AND MOMENTS ARE REVERSIBLE UON. 317-634-4672
FOR FIELD WELDING OF STUDS LESS THAN 68 MILS.
7. FINISHING OF SLABS: AFTER SCREEDING, BULL FLOATING AND FLOATING 7. FOR BEAMS FRAMING OVER THE TOP OF A COLUMN, PROVIDE 3/8 INCH 10. ALL WELDS SHALL BE PERFORMED BY OPERATORS QUALIFIED IN
OPERATIONS HAVE BEEN COMPLETED, APPLY FINAL FINISH AS INDICATED BELOW, STIFFENER PLATES EACH SIDE OF THE BEAM WEB UNLESS DETAILED ACCORDANCE WITH THE AMERICAN WELDING SOCIETY’S “STRUCTURAL
AND AS DESCRIBED IN DIVISION 3 SPECIFICATION, CAST-IN-PLACE CONCRETE OTHERWISE. WELDING CODE - SHEET METAL” (AWS D1.3)
SECTION OF THE PROJECT MANUAL.
8. LOCATE CENTERLINES OF DIAGONAL VERTICAL BRACING MEMBERS ON COLUMN 11. ALL WELDS SHALL BE TOUCHED UP WITH GALVANIZING PAINT.
• FLOOR SLABS, INTERIOR RAMPS AND STEPS TROWEL FINISH CENTERLINES UNLESS OTHERWISE INDICATED.
• EXTERIOR RAMPS AND STEPS BROOM FINISH
12. ALL STUDS SHALL HAVE FULL BEARING AGAINST THE INSIDE TRACK WEB TOP AND
9. SUB-BASE (LEVELING) PLATES WILL NOT BE ALLOWED UNDER COLUMN BASE BOTTOM. ALL STUDS SHALL BE CUT SQUARE.
• FINISHING OF FORMED SURFACES: REFER TO FORMED CONCRETE PLATES, UNLESS APPROVED BY STRUCTURAL ENGINEER.
SURFACE CATEGORY TABLE PROVIDED ON DESIGN INFORMATION
DRAWINGS FOR FINISHING REQUIREMENTS. 10. SPLICES SHALL BE ALLOWED ONLY AT LOCATIONS EXPLICITLY INDICATED ON 13. TRACK SPLICES WITHIN A WALL PANEL SHALL BE SECURELY ANCHORED TO A
THE STRUCTURAL DRAWINGS UNLESS APPROVED OTHERWISE IN WRITING BY COMMON ELEMENT (I.E. STUD OR HEADER) OR BUTT-WELDED TOGETHER.
THE STRUCTURAL ENGINEER.
8. TOLERANCES: REFER TO DIVISION 3 SPECIFICATION CONCRETE FORM WORK FOR 14. LATERAL BRIDGING CONSISTING OF 2 1/2” OR 1 1/2" COLD-ROLLED CHANNELS AND
SPECIAL TOLERANCE REQUIREMENTS AT OPENINGS FOR ELEVATORS, SHAFT 11. ALL STEEL MEMBERS AND EMBEDMENTS EXPOSED TO AN EXTERIOR OR 54 MIL CLIP ANGLES SHALL BE INSTALLED IN ALL LOAD-BEARING AND EXTERIOR
OPENINGS, ROUGH OPENINGS FOR DOORS, WINDOWS AND SLAB EDGES. UNCONDITIONED ENVIRONMENT SHALL BE PROTECTED WITH A HOT-DIPPED WALLS TO RESIST TORSIONAL FORCES. BRIDGING SHALL BE SPACED VERTICALLY
GALVANIZED FINISH OR APPROVED ZINC RICH EXTERIOR COATING SYSTEM, AT ONE-THIRD POINTS OF THE STUD CLEAR HEIGHT OR AT 4’-0” MAXIMUM
9. CURING OF SLABS: CURE SLABS WITH CURING COMPOUND OR MOISTURE UNLESS NOTED OTHERWISE. (WHICHEVER IS THE LESSER SPACING).
RETENTION COVERS AS DESCRIBED IN DIVISION 3 SPECIFICATION, CAST-IN-PLACE
CONCRETE SECTION OF THE PROJECT MANUAL. 15. MINIMUM TRACK FASTENING TO CONCRETE SLABS SHALL BE 0.177” DIAMETER
12. PROVIDE HOLES IN ALL STEEL AS REQUIRED TO PREVENT ANY ACCUMULATION POWDER ACTUATED FASTENERS WITH 1” MINIMUM PENETRATION INTO CONCRETE
OF WATER. PENETRATIONS ADDED TO MEMBERS FOR THIS PURPOSE SHALL BE AT EACH STUD.
10. SEE DIVISIONS 1 AND 3 OF THE PROJECT MANUAL FOR TESTING AND INSPECTION LIMITED IN SIZE SUCH AS NOT TO REDUCE MEMBER AND/OR CONNECTION
PROGRAM REQUIREMENTS. COORDINATE AS REQUIRED WITH THE TESTING AND CAPACITY, AND SHALL BE GROUND SMOOTH. 16. VOIDS BENEATH THE TRACKS SHALL NOT BE PERMITTED. REFER TO THE
INSPECTION AGENCY. CONCRETE SECTION OF THE GENERAL NOTES FOR FLOOR FLATNESS
13. ALL COPES, HOLES, OPENINGS AND MODIFICATIONS REQUIRED IN STRUCTURAL REQUIREMENTS. WHERE UNEVENNESS OF THE SUPPORTING FLOOR SLAB
STEEL MEMBERS FOR ERECTION OR THE WORK OF OTHER TRADES SHALL BE PREVENTS CONTINUOUS SOLID BEARING, THE BOTTOM TRACK SHALL BE
SHOWN ON THE SHOP DRAWINGS FOR APPROVAL BY THE ARCHITECT AND LEVELED IN A MANNER PROPOSED BY THE CONTRACTOR AND APPROVED BY THE
STRUCTURAL ENGINEER. ENGINEER OF RECORD.
3.5 POST INSTALLED ADHESIVE ANCHOR REINFORCING DOWELS
14. STEEL USING COMPLETE JOINT PENETRATION GROOVE WELDS THAT FUSE 17. CUTTING OF LOAD-BEARING OR EXTERIOR WALL STUDS, HEADERS, OR TRACKS IS NOT
1. ANCHOR DRILLED-IN DOWELS TO EXISTING CONCRETE WITH AN ADHESIVE THROUGH THE THICKNESS OF THE FLANGE OR WEB SHALL HAVE A MINIMUM PERMITTED WITHOUT THE EXPRESSED APPROVAL OF THE ENGINEER OF RECORD.
ANCHOR SYSTEM; SEE DIVISION 3 SPECIFICATION SECTION CAST-IN-PLACE CHARPY V-NOTCH IMPACT TESTING VALUE AS SPECIFIED IN AISC 360.
CONCRETE OF THE PROJECT MANUAL, FOR PRODUCT STANDARDS.
18. MULTIPLE STUDS ARRANGED AS A “STUD-COLUMN” SHALL BE WELDED TOGETHER
15. SEE DIVISION 1 OF THE PROJECT MANUAL AND STRUCTURAL STEEL IN GROUPS OF AT LEAST TWO STUDS WITH 2” WELDS AT TOP AND BOTTOM AND 1”
2. DRILLED HOLE SIZE AND INSTALLATION PROCEDURE SHALL BE IN ACCORDANCE SPECIFICATION SECTION, FOR STRUCTURAL STEEL TESTING AND INSPECTION WELDS AT 16” ON CENTER IN BETWEEN. WELDS SHALL BE PLACED ON BOTH SIDES
REQUIREMENTS. COORDINATE AS REQUIRED WITH THE TESTING AND OF STUD-COLUMN ASSEMBLY.
WITH THE MANUFACTURER’S PUBLISHED INSTALLATION INSTRUCTIONS (MPII).
INSPECTION AGENCY.
18. REFER TO THE AESS TABLE ON THE DESIGN INFORMATION DRAWING FOR SEAL | DATE 04/01/21
ARCHITECTURALLY EXPOSED STRUCTURAL STEEL REQUIREMENTS.
6. FOR ALL ROOF DECKS, PROVIDE DECK DEPTH, MINIMUM GAGE AS INDICATED ON
THE DRAWINGS..
GENERAL NOTES
3/31/2021 5:22:21 PM
SHEET NUMBER
S-002
RHIT MOENCH
DESIGN INFORMATION
CONCRETE SCHEDULE AESS CATEGORIES TABLE RENOVATION
CLASS f'c AIR CONTENT USED FOR REMARKS CATEGORY 1 2 3 4
5.5 POST INSTALLED ANCHOR MATERIAL: ASTM F1554, GRADE 55 UNLESS NOTED
OTHERWISE
7.0 DESIGN WIND AND SEISMIC LOAD CRITERIA FOR CLADDING AND CLADDING BACKUP: 2. TO OBTAIN WORKING LOADS FOR ASD DESIGN, MULTIPLY PRESSURES BY 0.6
IN ACCORDANCE WITH 2012 IBC LOAD COMBINATIONS.
1. CLADDING WIND LOADS: (ASCE 7-10) 3. PLUS AND MINUS SIGNS SIGNIFY PRESSURES ACTING TOWARD AND AWAY FROM
A. BUILDING IS TO BE CONSIDERED FULLY ENCLOSED SURFACE RESPECTIVELY.
a. INTERNAL PRESSURE COEFFICIENT, GCpi = + 0.18 4. ZONE LOCATIONS SHALL BE AS DEFINED BY THE DESIGN CRITERIA ELEVATIONS
b. EXTERNAL PRESSURE COEFFICIENTS ARE TO BE BASED ON AND SHALL NOT BE LESS THAN THOSE SHOWN IN ASCE 7-10 FIGURE 30.4-1 FOR
COMPONENT EFFECTIVE WIND AREA AND ASCE 7-10, FIGURE 30.4 MEAN ROOF UP TO 60' AND ASCE 7-10 FIGURE 30.6-1 FOR MEAN ROOF HEIGHT
OR 30.6 GREATER THAN 60'
B. TOPOGRAPHIC FACTOR, Kzt = 1.0
C. WIND DIRECTIONALITY FACTOR, Kd = 0.85
D. NOTE: ALLOWABLE STRESS INCREASE FOR WIND LOADING SHALL NOT
BE USED. (SEE ASCE 7-10, TABLE 26.6-1) MINIMUM ROOF CLADDING DESIGN PRESSURES
DESIGN
INFORMATION
3/31/2021 5:22:25 PM
SHEET NUMBER
S-003
RHIT MOENCH
N10 N9 N8 N7 N6 N5 N4 N3 N2 N1 RENOVATION
5500 Wabash Avenue
A
Terre Haute, Indiana
47803
Owner
B
Rose-Hulman Institute of Technology
5500 Wabash Avenue
Terre Haute, Indiana 47803
2 812-877-1511
SD-200
9.8 8.9 7.9 6.9 5.9 5.1 4.1 3.1 2.1 1.2
D Architect
RATIO
101 South Pennsylvania Street
Indianapolis, Indiana 46204
317-633-4040
E
Structural Engineer
Fink Roberts & Petrie, Inc.
9449 Priority Way W Dr #200
Indianapolis, Indiana 46240
317-872-8400
F
F
3 G
M E
2
D
C
N
B 1
A
O KEY PLAN
SHEET ISSUE
1 Construction Documents 04/01/21
S10 S9 S8 S7 S6 S5 S4 S3 S2 S1
V
PLAN NOTES:
1. SEE S000 SERIES DRAWINGS FOR GENERAL NOTES, CONCRETE COPYRIGHT NOTICE: THIS ARCHITECTURAL AND ENGINEERING DRAWING IS GIVEN IN CONFIDENCE
AND SHALL BE USED ONLY PURSUANT TO THE AGREEMENT WITH RATIO. NO OTHER USE,
SCHEDULES, DESIGN INFORMATION, AND LOADING CRITERIA. DISSEMINATION OR DUPLICATION MAY BE MADE WITHOUT PRIOR WRITTEN CONSENT OF RATIO. ALL
COMMON LAW RIGHTS OF COPYRIGHT AND OTHERWISE ARE HEREBY SPECIFICALLY RESERVED.
LOWER LEVEL 1
DEMOLITION PLAN
3/31/2021 5:14:45 PM
SD-112
RHIT MOENCH
N10 N9 N8 N7 N6 N5 N4 N3 N2 N1 RENOVATION
5500 Wabash Avenue
A
Terre Haute, Indiana
47803
Owner
B
Rose-Hulman Institute of Technology
5500 Wabash Avenue
4 Terre Haute, Indiana 47803
SD-200 812-877-1511
2 / SD-500
DEMO
9.8 8.9 7.9 6.9 5.9 5.1 4.1 3.1 2.1 1.2
D Architect
RATIO
101 South Pennsylvania Street
Indianapolis, Indiana 46204
317-633-4040
E
Structural Engineer
Fink Roberts & Petrie, Inc.
9449 Priority Way W Dr #200
Indianapolis, Indiana 46240
317-872-8400
F
F
3 G
M E
2
D
C
N
B 1
A
O KEY PLAN
SHEET ISSUE
1 Construction Documents 04/01/21
S10 S9 S8 S7 S6 S5 S4 S3 S2 S1
6
SD-200
FIRST LEVEL
DEMOLITION PLAN
3/31/2021 5:14:55 PM
SD-113
RHIT MOENCH
N10 N9 N8 N7 N6 N5 N4 N3 N2 N1 RENOVATION
5500 Wabash Avenue
A
Terre Haute, Indiana
47803
Owner
B
Rose-Hulman Institute of Technology
5500 Wabash Avenue
Terre Haute, Indiana 47803
812-877-1511
9.8 8.9 7.9 6.9 5.9 5.1 4.1 3.1 2.1 1.2
D Architect
RATIO
101 South Pennsylvania Street
Indianapolis, Indiana 46204
317-633-4040
E
Structural Engineer
Fink Roberts & Petrie, Inc.
9449 Priority Way W Dr #200
Indianapolis, Indiana 46240
317-872-8400
F
F
3 G
M
3
E
2
SD-200
D
C
N
B 1
A
O KEY PLAN
SHEET ISSUE
1 Construction Documents 04/01/21
S10 S9 S8 S7 S6 S5 S4 S3 S2 S1
T
1
SD-200
9.8 8.9 7.9 6.9 5.9 5.1 4.1 3.1 2.1 1.2
U
7
SD-200
W 1. SEE S000 SERIES DRAWINGS FOR GENERAL NOTES, CONCRETE PROJECT NO. 19040.000
SCHEDULES, DESIGN INFORMATION, AND LOADING CRITERIA.
SHEET TITLE
SECOND LEVEL
DEMOLITION PLAN
3/31/2021 5:15:06 PM
SD-114
RHIT MOENCH
N10 N9 N8 N7 N6 N5 N4 N3 N2 N1 RENOVATION
5500 Wabash Avenue
A
Terre Haute, Indiana
47803
Owner
B
Rose-Hulman Institute of Technology
5500 Wabash Avenue
Terre Haute, Indiana 47803
812-877-1511
9.8 8.9 7.9 6.9 5.9 5.1 4.1 3.1 2.1 1.2
D Architect
RATIO
4
101 South Pennsylvania Street
● Indianapolis, Indiana 46204
SD-500
317-633-4040
E
4 Structural Engineer
SD-500 Fink Roberts & Petrie, Inc.
SEE ARCHITECTURAL DRAWINGS 9449 Priority Way W Dr #200
FOR NON-STRUCTURAL EXISTING Indianapolis, Indiana 46240
MONITOR DEMOLITION, TYPICAL 317-872-8400
F
F
3 G
M E
2
D
C
N
B 1
A
O KEY PLAN
REMOVE MISCELLANEOUS
STEEL FRAMING ABOVE ROOF;
VERIFY EXTENT WITH OWNER
PRIOR TO DEMOLITION
Q 3
SD-500
TYP
SHEET ISSUE
1 Construction Documents 04/01/21
S10 S9 S8 S7 S6 S5 S4 S3 S2 S1
5
SD-200
U
ROOF DEMOLITION
PLAN
3/31/2021 5:15:14 PM
SD-115
5.1 4.1
16'-10" FIELD VERIFY
N10
RHIT MOENCH
S8
17'-3 1/4" FIELD VERIFY
S7
17'-3 1/4" FIELD VERIFY
S6
7'-6 1/4"
RENOVATION
3 9/16" 4'-9 7/16" 1 11/16"
FIELD VERIFY M
5500 Wabash Avenue
Terre Haute, Indiana
FIELD VERIFY
REMOVE EXISTING WOOD DECKING REMOVE BRIDGE
REMOVE EXISTING RAMP FRAMING AND SLAB
6'-0"
TO LEVEL SURFACE 47803
T C
Owner
FIELD VERIFY
(E) C12x20.7
4'-11 11/16"
Rose-Hulman Institute of Technology
5500 Wabash Avenue
5'-9 1/4"
FIELD VERIFY
812-877-1511
(E) 10x12
(E) 10x12
(E) 10x12
(E) 10x12
(E) 10x12
(E) 10x12
(E) W5x16
(E) W5x16
7'-7 3/8"
5
6'-0"
1 / SD-500
SD-500
DEMO
18'-8 7/8" FIELD VERIFY
17'-7 7/8" FIELD VERIFY
FIELD VERIFY
TIMBER BEAM AFTER NEW
7'-8 1/2"
SUPPORT FRAMING IS INSTALLED (E) C12x20.7
(E) 10x12
FIELD VERIFY
9.8
6'-0"
Architect
(E) 10x12
(E) 10x12
(E) 10x12
(E) 10x12
(E) 10x12
(E) 10x12
RATIO
101 South Pennsylvania Street
10'-0 1/2"
N
Indianapolis, Indiana 46204
317-633-4040
3" T&G
CUT AND REMOVE WOOD DECKING
EXISTING 10x16 TIMBER Structural Engineer
2'-0"5 9/16" GIRDER AFTER NEW SUPPORT Fink Roberts & Petrie, Inc.
FRAMING IS INSTALLED
9449 Priority Way W Dr #200
(E) 10x16 (E) 10x16
U Indianapolis, Indiana 46240
2'-6 7/8"
317-872-8400
7'-1 3/16"
(E) 10x12
SCALE: 1/4" = 1'-0" SCALE: 1/4" = 1'-0" 732 N Capitol Avenue
Indianapolis, Indiana 46204
317-634-4672
17'-8 1/4" FIELD VERIFY
N5 N4
9'-5"
(E) 10x12
(E) 10x12
(E) 10x12
(E) 10x12
(E) 10x12
(E) 10x12
S4 S3
REMOVE EXISTING
(E) W8x10 WOOD DECKING TO 2 3/4" 8'-4 1/4"
BEAM CENTERLINE
1'-4"
T
REMOVE EXISTING WOOD C
(E) W8x10
DECKING AFTER NEW REMOVE ROOF DECKING AS
2'-9"
FRAMING BELOW IS INSTALLED REMOVE EXISTING 10" SLAB REQUIRED TO INSTALL MECH
(E) 10x12
AFTER NEW FRAMING IS HOOD; COORDINATE SIZE AND
INSTALLED BELOW LOCATION WITH MEP
CONTRACTOR, SEE 6/S-500 FOR
(E) 10x16 (E) 10x16 TYPICAL ROOF DECK OPENING
V FRAMING
U
D
ENLARGED DEMO PLAN - SECOND LEVEL SOUTH ENLARGED DEMO PLAN - FIRST LEVEL ENLARGED DEMO PLAN - ROOF
1 SCALE: 1/4" = 1'-0"
4 SCALE: 1/8" = 1'-0"
5 SCALE: 1/8" = 1'-0"
S2
S8 S7 S6
17'-3 1/4" 17'-3 1/4" 6'-11 3/8" 1'-10 1/4"
FIELD VERIFY FIELD VERIFY
(E) 10x12
(E) 10x12
(E) 10x12
(E) 10x12
(E) 10x12
(E) 10x12
FOOTING (3 LOCATIONS)
2'-0"
SHEET ISSUE
(E) 10x12
(E) 10x12
(E) 10x12
(E) 10x12
(E) 10x12
(E) 10x12
(E) 10x12
ENLARGED DEMO PLAN - FIRST LEVEL ENLARGED DEMO PLAN - SECOND LEVEL
6 SCALE: 1/8" = 1'-0"
7 SCALE: 1/4" = 1'-0"
PLAN NOTES:
ENLARGED
1. SEE S000 SERIES DRAWINGS FOR GENERAL NOTES, CONCRETE
DEMOLITION PLANS
SCHEDULES, DESIGN INFORMATION, AND LOADING CRITERIA.
3/31/2021 5:15:22 PM
SHEET NUMBER
SD-200
5.9 5.1
C
7 1/2"
3'-6 1/2" 5'-11"
1'-1 7/8"
RHIT MOENCH
D
RENOVATION
6'-4" 2'-11" 5500 Wabash Avenue
07 ROOF LEVEL
148'-10 1/2"
Terre Haute, Indiana
EXISTING MONITOR;
SEE ARCHITECTURAL
47803
Owner
REMOVE EXISTING 1 1/2" DIAMETER ROD
REMOVE EXISTING VARYING
Rose-Hulman Institute of Technology
REMOVE EXISTING 18 1/2" THICK 5500 Wabash Avenue
MASONRY WALL AFTER NEW THICKNESS MASONRY WALL AFTER
LINTEL IS INSTALLED. NEW LINTEL IS INSTALLED. REMOVE EXISTING W10x49, EA SIDE Terre Haute, Indiana 47803
FIELD VERIFY WALL THICKNESS. FIELD VERIFY WALL THICKNESS. 812-877-1511
7'-2"
SEE ARCHITECTURAL
Architect
RATIO
101 South Pennsylvania Street
Indianapolis, Indiana 46204
317-633-4040
02 LOWER LEVEL 1
110'-7 1/16" 03 FIRST LEVEL
120'-11 13/16" Structural Engineer
Fink Roberts & Petrie, Inc.
EXISTING DOOR 9449 Priority Way W Dr #200
OPENING Indianapolis, Indiana 46240
EXISTING W6x20 COLUMN TO REMAIN 317-872-8400
5.9
5.1
EXISTING MONITOR,
SEE ARCHITECTURAL
SHEET ISSUE
1 Construction Documents 04/01/21
STRUCTURAL
DEMOLITION ELEV,
SECTIONS AND
3/31/2021 5:15:25 PM
DETAILS
SHEET NUMBER
SD-500
RHIT MOENCH
N10 N9 N8 N7 N6 N5 N4 N3 N2 N1 RENOVATION
5500 Wabash Avenue
A
Terre Haute, Indiana
47803
Owner
B
Rose-Hulman Institute of Technology
5500 Wabash Avenue
Terre Haute, Indiana 47803
812-877-1511
9.8 8.9 7.9 6.9 5.9 5.1 4.1 3.1 2.1 1.2
D Architect
RATIO
101 South Pennsylvania Street
Indianapolis, Indiana 46204
317-633-4040
E
Structural Engineer
Fink Roberts & Petrie, Inc.
9449 Priority Way W Dr #200
Indianapolis, Indiana 46240
317-872-8400
F
F
3 G
M E
2
D
C
N
B 1
A
O KEY PLAN
SHEET ISSUE
1 Construction Documents 04/01/21
S10 S9 S8 S7 S6 S5 S4 S3 S2 S1
LOWER LEVEL 1
FLOOR PLAN
3/31/2021 5:22:34 PM
S-102
RHIT MOENCH
RENOVATION
5500 Wabash Avenue
Terre Haute, Indiana
47803
Owner
Rose-Hulman Institute of Technology
5500 Wabash Avenue
Terre Haute, Indiana 47803
812-877-1511
N10
Architect
A RATIO
101 South Pennsylvania Street
Indianapolis, Indiana 46204
317-633-4040
Structural Engineer
Fink Roberts & Petrie, Inc.
9449 Priority Way W Dr #200
Indianapolis, Indiana 46240
317-872-8400
4
S-501
9.8
F
3 G
E
2
E D
B 1
A
KEY PLAN
G
SHEET ISSUE
1 Construction Documents 04/01/21
LOWER LEVEL 1
FLOOR PLAN - AREA
3
3/31/2021 5:22:37 PM
SHEET NUMBER
S-102.3
RHIT MOENCH
N10 N9 N8 N7 N6 N5 N4 N3 N2 N1 RENOVATION
5500 Wabash Avenue
A
Terre Haute, Indiana
47803
Owner
B
Rose-Hulman Institute of Technology
5500 Wabash Avenue
Terre Haute, Indiana 47803
812-877-1511
9.8 8.9 7.9 6.9 5.9 5.1 4.1 3.1 2.1 1.2
D Architect
RATIO
101 South Pennsylvania Street
Indianapolis, Indiana 46204
317-633-4040
E
Structural Engineer
Fink Roberts & Petrie, Inc.
9449 Priority Way W Dr #200
Indianapolis, Indiana 46240
317-872-8400
F
F
3 G
M E
2
D
C
N
B 1
A
O KEY PLAN
SHEET ISSUE
1 Construction Documents 04/01/21
S10 S9 S8 S7 S6 S5 S4 S3 S2 S1
S-103
9.8 8.9 7.9 6.9 5.9 5.1 4.1 3.1 2.1 1.2 PLAN NOTES:
Structural Engineer
Fink Roberts & Petrie, Inc.
9449 Priority Way W Dr #200
Indianapolis, Indiana 46240
SEE FOUNDATION PLAN, SLAB ON GRADE 317-872-8400
O
PLAN OR STEEL COLUMN SCHEDULE FOR
COLUMN BASE PLATE AND ANCHOR ROD
INFORMATION. SEE ANCHOR PLACEMENT Mechanical / Electrical Engineer
DETAILS FOR LAYOUT EMBEDMENT
LENGTH AND PROTECTION LENGTH. R.E. Dimond & Associates, Inc.
732 N Capitol Avenue
Indianapolis, Indiana 46204
SEE FOUNDATION PLAN 317-634-4672
2" NON-SHRINK GROUT
FOR TOP OF FOOTING
2" CLR
3" CLR
P
3" CLR,
TYP
SEE COLUMN FOOTING SCHEDULE
FOR FOOTING INFORMATION
BEARING CAPACITY
COLUMN SQUARE FOOTING SCHEDULE 2 KSF
BOTTOM
MARK SIZE REMARKS
REINFORCEMENT
F
R
3 G
E
2
D
B 1
A
S
KEY PLAN
S10 S9 S8 S7 S6 S5 S4 S3 S2 S1
S-502
10'-2 1/2"
(TYP)
HSS6x6x5/16
U 2F4
TF 114'-9" (FV)
2'-1 7/8"
SHEET NUMBER
FIRST LEVEL FLOOR PLAN - AREA 1
1 SCALE: 1/8" = 1'-0"
S-103.1
N10 N9 N8 N7 N6 N5 N4 N3 N2 N1 RHIT MOENCH
RENOVATION
5500 Wabash Avenue
A
Terre Haute, Indiana
47803
Owner
Rose-Hulman Institute of Technology
5500 Wabash Avenue
Terre Haute, Indiana 47803
812-877-1511
Architect
RATIO
101 South Pennsylvania Street
Indianapolis, Indiana 46204
317-633-4040
C
Structural Engineer
Fink Roberts & Petrie, Inc.
9449 Priority Way W Dr #200
Indianapolis, Indiana 46240
317-872-8400
1
9.8 8.9 7.9 6.9 5.9 5.1 4.1 3.1 2.1 1.2
S-200
Mechanical / Electrical Engineer
5
R.E. Dimond & Associates, Inc.
S-501
732 N Capitol Avenue
Indianapolis, Indiana 46204
D 317-634-4672
PLAN NOTES: F
1. SEE S000 SERIES DRAWINGS FOR GENERAL NOTES, CONCRETE
3 G
C
G
B 1
A
LEGEND
S-103.2
RHIT MOENCH
N10 N9 N8 N7 N6 N5 N4 N3 N2 N1 RENOVATION
5500 Wabash Avenue
A
Terre Haute, Indiana
47803
Owner
B
Rose-Hulman Institute of Technology
5500 Wabash Avenue
Terre Haute, Indiana 47803
812-877-1511
9.8 8.9 7.9 6.9 5.9 5.1 4.1 3.1 2.1 1.2
D Architect
RATIO
101 South Pennsylvania Street
Indianapolis, Indiana 46204
317-633-4040
E
Structural Engineer
Fink Roberts & Petrie, Inc.
9449 Priority Way W Dr #200
Indianapolis, Indiana 46240
317-872-8400
F
F
3 G
M E
2
D
C
N
B 1
A
O KEY PLAN
SHEET ISSUE
1 Construction Documents 04/01/21
S10 S9 S8 S7 S6 S5 S4 S3 S2 S1
9.8 8.9 7.9 6.9 5.9 5.1 4.1 3.1 2.1 1.2
SECOND LEVEL
FLOOR PLAN
3/31/2021 5:23:13 PM
S-104
9.8 8.9 7.9 6.9 5.9 5.1 4.1 3.1 2.1 1.2 RHIT MOENCH
RENOVATION
5500 Wabash Avenue
Terre Haute, Indiana
47803
Owner
Rose-Hulman Institute of Technology
M 5500 Wabash Avenue
Terre Haute, Indiana 47803
812-877-1511
C12x20.7
S-503
Architect
N
RATIO
101 South Pennsylvania Street
Indianapolis, Indiana 46204
317-633-4040
Structural Engineer
Fink Roberts & Petrie, Inc.
9449 Priority Way W Dr #200
Indianapolis, Indiana 46240
317-872-8400
O
Mechanical / Electrical Engineer
R.E. Dimond & Associates, Inc.
732 N Capitol Avenue
Indianapolis, Indiana 46204
317-634-4672
PLAN NOTES:
LEGEND
R
INDICATES OPENING IN SLAB. COORDINATE SIZE AND
E
2
LOCATION WITH MECHANICAL CONTRACTOR.
D
A INDICATES SPAN DIRECTION OF 1 1/2", 20 GAGE WIDE RIB
METAL ROOF DECK WITH (2) LAYERS OF 3/4" PLYWOOD C
INDICATES SPAN DIRECTION OF 1 1/2", 20 GAGE WIDE RIB
B METAL ROOF DECK B 1
INDICATES SPAN DIRECTION OF 3", LAMINATES SOUTHERN
C PINE T&G ROOF DECKING A
(S) INDICATES SLOPING MEMBER
KEY PLAN
S
S10 S9 S8 S7 S6 S5 S4 S3 S2 S1
2 SHEET ISSUE
S-200 1 Construction Documents 04/01/21
9.8 8.9 7.9 6.9 5.9 5.1 4.1 3.1 2.1 1.2
3
S-200
SECOND LEVEL
FLOOR PLAN - AREA
1
3/31/2021 5:23:20 PM
SHEET NUMBER
SECOND LEVEL FLOOR PLAN - AREA 1
1 SCALE: 1/8" = 1'-0" S-104.1
N10 N9 N8 N7 N6 N5 N4 N3 N2 N1
RHIT MOENCH
A
RENOVATION
5500 Wabash Avenue
Terre Haute, Indiana
47803
Owner
Rose-Hulman Institute of Technology
5500 Wabash Avenue
Terre Haute, Indiana 47803
812-877-1511
B
Architect
RATIO
101 South Pennsylvania Street
C Indianapolis, Indiana 46204
317-633-4040
Structural Engineer
Fink Roberts & Petrie, Inc.
9.8 8.9 7.9 6.9 5.9 5.1 4.1 3.1 2.1 1.2 9449 Priority Way W Dr #200
Indianapolis, Indiana 46240
317-872-8400
PLAN NOTES:
S-502
LEGEND
SHEET ISSUE
J
1 Construction Documents 04/01/21
SECOND LEVEL
FLOOR PLAN - AREA
2
3/31/2021 5:23:28 PM
9.8 8.9 7.9 6.9 5.9 5.1 4.1 3.1 2.1 1.2
SHEET NUMBER
SECOND LEVEL FLOOR PLAN - AREA 2
1 SCALE: 1/8" = 1'-0" S-104.2
RHIT MOENCH
N10 N9 N8 N7 N6 N5 N4 N3 N2 N1 RENOVATION
5500 Wabash Avenue
A
Terre Haute, Indiana
47803
Owner
B
Rose-Hulman Institute of Technology
5500 Wabash Avenue
Terre Haute, Indiana 47803
812-877-1511
9.8 8.9 7.9 6.9 5.9 5.1 4.1 3.1 2.1 1.2
D 6
● Architect
S-200
RATIO
(SIM)
101 South Pennsylvania Street
7 Indianapolis, Indiana 46204
●
S-502 317-633-4040
E
Structural Engineer
Fink Roberts & Petrie, Inc.
7 9449 Priority Way W Dr #200
S-502 Indianapolis, Indiana 46240
317-872-8400
F
J
4
S-200
F
3 G
M E
2
D
C
N
B 1
A
O KEY PLAN
SHEET ISSUE
1 Construction Documents 04/01/21
S
5
S-200
S10 S9 S8 S7 S6 S5 S4 S3 S2 S1
T
6 PLAN NOTES:
S-200
1. SEE S000 SERIES DRAWINGS FOR GENERAL NOTES, CONCRETE
SCHEDULES, DESIGN INFORMATION, AND LOADING CRITERIA.
LEGEND
COPYRIGHT NOTICE: THIS ARCHITECTURAL AND ENGINEERING DRAWING IS GIVEN IN CONFIDENCE
BFX INDICATES FOOTING MARK. "B" INDICATES REQUIRED AND SHALL BE USED ONLY PURSUANT TO THE AGREEMENT WITH RATIO. NO OTHER USE,
BEARING CAPACITY IN KSF AND FX INDICATES BEARING MARK. DISSEMINATION OR DUPLICATION MAY BE MADE WITHOUT PRIOR WRITTEN CONSENT OF RATIO. ALL
COMMON LAW RIGHTS OF COPYRIGHT AND OTHERWISE ARE HEREBY SPECIFICALLY RESERVED.
S-105
S8 S7 S6
17'-3 1/4" FIELD VERIFY 17'-3 1/4" FIELD VERIFY
4'-8 3/16" 2" 5'-2 11/16" 5'-2 11/16" 3'-9"
1'-5 11/16"
5'-2 11/16" 5'-2 11/16" 3'-0 7/8"
RHIT MOENCH
DBE 132'-8 1/2" DBE 130'-6 7/16"
RENOVATION
N5 N4 T
5500 Wabash Avenue
2 3/4" 8'-4 1/4" 6" Terre Haute, Indiana
RAMP SLOPE DOWN
47803
TB 132'-5 1/2"
6'-10 1/4"
6
TB 132'-5 1/2"
TB 131'-11 5/8"
W6x12
S-503
TB 130'-7 7/8"
TB 131'-6 3/8"
TB 131'-1 1/8"
TB 130'-3 3/8"
W6x12
A Owner
W6x12
W6x12
W6x12
W6x12
W6x12
Rose-Hulman Institute of Technology
(E) W24x84 PLAN NOTES: 5500 Wabash Avenue
C W6x12
1'-4" Terre Haute, Indiana 47803
1'-8 1/8"
● HSS8x4x5/16 812-877-1511
SCHEDULES, DESIGN INFORMATION, AND LOADING CRITERIA. SIM S-502 TB 134'-3 7/8"
4'-9 15/16"
2'-9"
2. SEE DRAWING S500 FOR STRUCTURAL STEEL COLUMN BASE DBE 132'-8 1/2"
HSS12x6x5/16
PLATE AND ANCHOR ROD DETAILS.
TB 133'-0 3/8" 14 15
6"
6
S-502 S-502
W16x31 6 W6x12
S-501
TB 120'-1 3/8" TB 132'-9 7/8"
(E) 10x12
HSS12x6x5/16
(E) 10x12
(E) 10x12
(E) 10x12
(E) 10x12
(E) 10x12
S-502
TB 132'-8 3/8"
RAMP SLOPE DOWN
TYP
4'-9 15/16"
(E) 10x12
(E) 10x12
TB 120'-0 7/8"
TB 120'-0 7/8"
EXISTING 10" Architect
W18x35
W18x35
CONCRETE SLAB
LEGEND W6x12 EXISTING 3" RATIO
WOOD DECKING
13'-0 3/8"
2'-7 13/16"
BFX INDICATES FOOTING MARK. "B" INDICATES REQUIRED ● TB 133'-2 3/8"
BEARING CAPACITY IN KSF AND FX INDICATES BEARING MARK. SIM S-502 Indianapolis, Indiana 46204
317-633-4040
A
TF INDICATES TOP OF FOOTING ELEVATION. (E) 10x16 (E) 10x16
T/SLAB 120'-11 13/16" U
2'-2 1/8"
2'-4"
TB INDICATES TOP OF BEAM ELEVATION. Structural Engineer
INDICATES OPENING IN SLAB. COORDINATE SIZE AND W8x10 W6x12 T/DECKING 134'-3 13/16" Fink Roberts & Petrie, Inc.
LOCATION WITH MECHANICAL CONTRACTOR. TB 133'-7 3/8" 9449 Priority Way W Dr #200
4 Indianapolis, Indiana 46240
4'-9 15/16"
1'-1"
13
FV
(E) 10x12
METAL ROOF DECK WITH (2) LAYERS OF 3/4" PLYWOOD S-502
(E) 10x12
(E) 10x12
(E) 10x12
(E) 10x12
METAL ROOF DECK W6x12 Mechanical / Electrical Engineer
9'-11"
W8x10
INDICATES SPAN DIRECTION OF 3", LAMINATED SOUTHERN
4
TB 134'-0 3/8" R.E. Dimond & Associates, Inc.
●
3" WOOD DECKING INFILL
C S-503 732 N Capitol Avenue
(E) 10x12
12 PINE T&G ROOF DECKING TO MATCH EXISTING
Indianapolis, Indiana 46204
(E) 10x12
(E) 10x12
S-502 INDICATES SLOPING MEMBER DBE 134'-3 13/16"
(S) 317-634-4672
(E) W8x10
W8x10
W8x10
(E) W8x10
6'-5"
2'-10" 5'-1"
FIELD VERIFY
5.9 5.1
S3 S2
17'-3 1/4" FIELD VERIFY 14'-1" FIELD VERIFY
5'-9 1/16" 5'-9 1/16" 5'-9 1/16" EQ EQ 4.1 3.1 2.1 2'-10 5/16"
16'-10" FIELD VERIFY 17'-0" FIELD VERIFY FIELD VERIFY
FIELD VERIFY FIELD VERIFY FIELD VERIFY
W16x20 COLUMN
7 3/8" 8'-9 11/16" 6'-4 5/16" 10'-5 11/16" 4'-8 5/16" 12'-3 11/16" 2'-10 5/16"
EXTENSION, TYPICAL
S-501 S-501
3'-3 1/2" 4'-1 7/8"
5'-11 5/8"
HSS8x6x1/2 TB 149'-9"
HSS8x6x1/2 TB 149'-9"
HSS6x4x1/4
TB 153'-6"
W6x16 TB 149'-7" W6x16 TB 149'-7" W6x16 TB 149'-7"
EQ
W8x10 W8x10
EQ
17'-8 1/4" FIELD VERIFY
W8x10
2'-6"
W6x16 (S)
W6x16 (S)
W6x16 (S)
W6x16 (S)
W8x10 W8x10 2 W6x16 W6x16 W6x16
S-501
(E) 10x12
(E) 10x12
(E) 10x12
B
HSS6x4x1/4
EQ
TB 153'-6"
EQ
EXISTING 3"
WOOD DECKING (E) W12x19 W/ (E) C8x11.5 TB 146'-7 11/16" FV (E) W12x19 W/ (E) C8x11.5 TB 146'-7 11/16" FV (E) W12x19 W/ (E) C8x11.5 TB 146'-7 11/16" FV SEAL | DATE 04/01/21
S4 S3 S2
SHEET ISSUE
1 Construction Documents 04/01/21
ENLARGED PLAN CENTRAL MONITOR TYPICAL BAY SOUTH MONITOR PLAN
3 4 5 SCALE: 1/4" = 1'-0"
SCALE: 1/4" = 1'-0" SCALE: 1/4" = 1'-0"
HSS6x4x1/4
HSS8x6x1/2
HSS6x4x1/4
HSS8x6x1/2
16
7'-0" 7'-0" 7'-0" 7'-0" 2'-6 1/2"
EXISTING S-502
HSS8x4x5/16 (S) HSS8x4x5/16 (S) MASONRY WALL 3/4" DIA. HANGER
ROD, TYP
9"
HSS6x4x1/4
HSS8x6x1/2
(E) C9x13.4
(E) C9x13.4
(E) C9x13.4
(E) C9x13.4
12 12
5'-3"
● ●
S-503
S-502 S-502
SIM SIM
G
SHEET NUMBER
S-200
CENTERLINE OF
GIRDER
1 1/2" (MIN)
(2) HEAVY HEX NUTS
RHIT MOENCH
PROJECTION
AND 3/8" x 3" x 3" A572 GR 50
PLATE WASHERS
1'-2"
TOP OF FOUNDATION
ANCHOR RODS WITH DOUBLE 2" 5" 5" 2" 5500 Wabash Avenue
SEE PLAN FOR
COLUMN AND
NUTS AND PLATE WASHERS FOR
LEVELING. SEE BASE PLATE DETAILS FOR
ANCHOR ROD LAYOUT. CLEAN OIL FROM
1/4 (2) ANGLES Terre Haute, Indiana
BASE PLATE
47803
2"
ASTM F1554 GR36 ANCHOR RODS PRIOR TO INSTALLATION
1" DIAMETER INFORMATION
NOTE: CLIP PLATE WASHERS
5"
ANCHOR ROD
1'-0"
FINISHED COLUMN END IF NECESSARY TO CLEAR
1'-2"
SEE PLAN FOR COLUMN
Owner
TOP OF CONCRETE Rose-Hulman Institute of Technology
5"
HEAVY HEX NUT ELEVATION
2" NON-SHRINK GROUT 5500 Wabash Avenue
2"
FOR 1" ANCHOR RODS Terre Haute, Indiana 47803
NOTES: 812-877-1511
3" NON-SHRINK GROUT 1" THICK A572 GR50
FOR 1 1/2" ANCHOR RODS BASE PLATE
TACK WELD (BRACED BAYS) SEE FOUNDATION 1. DESIGN CONNECTION AS STANDARD AISC SIMPLE DOUBLE ANGLE UNLESS SPECIFICALLY
PLAN FOR ANCHOR HSS6x6 DETAILED OTHERWISE.
ROD INFORMATION PER PLAN
2. CONTRACTOR HAS OPTION TO BOLT OR WELD ANGLES UNLESS SPECIFICALLY DETAILED
OTHERWISE.
NOTE:
NOTE: PROVIDE HOT DIP GALVANIZED ASSEMBLIES WHERE PROJECTED 3. CONNECTION DEPTH SHALL BE AT LEAST 2/3 x BEAM T-DIMENSION.
PORTION IS EXPOSED TO EXTERIOR OR UNCONDITIONED ATMOSPHERE.
1. PROVIDE 1 13/16" DIA HOLES FOR 1" DIA ANCHOR RODS
4. SAME APPLIES FOR TYPICAL BEAM TO COLUMN CONNECTION
Architect
RATIO
TYPICAL ANCHOR ROD DETAIL TYPICAL COLUMN BASE DETAIL TYP BASE PLATE DETAIL TYPICAL BEAM TO GIRDER CONNECTION 101 South Pennsylvania Street
1 NOT-TO-SCALE
2 NOT-TO-SCALE
3 NOT-TO-SCALE
4 NOT-TO-SCALE
Indianapolis, Indiana 46204
317-633-4040
Structural Engineer
Fink Roberts & Petrie, Inc.
9449 Priority Way W Dr #200
Indianapolis, Indiana 46240
317-872-8400
2"
3"
SEE FRAMING PLAN
FOR BEAM SIZE AND PROVIDE ANGLE FRAME AS
REACTION VALUES INDICATED UNLESS MEMBER
SIZES ARE GIVEN ON PLAN. TH
FOR SQUARE AND RECTANGULAR HSS ID M
BEAM PER PLAN 36/4 PATTERN AT ALL W MU
PROVIDE WT OR END SHEAR PLATE T I
. NOTES: INTERMEDIATE SUPPORTS
H EE A X
DESIGN WELD TO HSS COLUMN FOR (2) L4x4x5/16 x 7" LONG JOIST OR BEAM SPACING PER PLAN S 6" M
VERTICAL REACTION WITH ECCENTRICITY STRIP BOTTOM END LAPS SHALL OCCUR ONLY AT SUPPORT POINTS. 3
1.
OF HALF THE HSS DIMENSION FLANGE AS REQUIRED
2. SUPPORTS MAY BE WIDE FLANGE BEAMS, STEEL JOIST OR COLD FORMED
PROVIDE CONNECTION DEPTH TO PREVENT (2) 1/2" DIAMETER x 6" LONG NOTES: LIGHT GAGE METAL FRAMING (WIDE FLANGE CONDITION SHOWN).
PLASTIFICATION OF HSS WALL BASED ON VERTICAL LAG SCREWS, EACH SIDE
REACTION TIMES HALF OF HSS DIMENSION 1. PROVIDE ANGLE FRAME FOR OPENINGS 12" SQUARE OR LARGER. 3. FASTEN THRU MULTIPLE SHEETS AT ALL ENDS AND SIDE LAPS.
EXISTING TIMBER BEAM
OR GIRDER PER PLAN 2. COORDINATE SIZE AND LOCATION OF OPENINGS WITH MECHANICAL CONTRACTOR 4. DECK UNITS SHALL BE CONTINUOUS OVER AS MANY SPANS
PRIOR TO FABRICATION. AS THE STRUCTURAL STEEL LAYOUT WILL PERMIT.
3. FOR FRAME ANGLE BEARING LOCATIONS ON STEEL JOISTS THAT DO NOT OCCUR 5. USE HILTI X-HSN 24 FASTENERS AT JOIST AND X-ENP-L15 AT WIDE FLANGE BEAMS, PLATES
AT PANEL POINTS, SEE "TYPICAL JOIST AND DECK REINFORCING DETAIL" FOR AND ANGLES 1/4" THICK OR GREATER AND #10 SCREWS AT COLD FORMED METAL FRAMING SUPPORTS.
REINFORCING REQUIREMENTS.
2" MIN
METAL ROOF
DECK
3"
SHEET ISSUE
1 Construction Documents 04/01/21
NOTES:
TYPICAL
STRUCTURAL STEEL
DETAILS
3/31/2021 5:23:40 PM
SHEET NUMBER
S-500
5.9 5.1 5.9 5.1
EQ
14'-1" FIELD VERIFY
EQ EQ
14'-1" FIELD VERIFY
EQ
RHIT MOENCH
RENOVATION
2 2
5500 Wabash Avenue
●
S
S-502
TB 153'-8 1/16"
TB 153'-6"
S-502 TB 153'-8 1/16"
TB 153'-6"
Terre Haute, Indiana
3" WOOD T&G ROOF DECKING 3" WOOD T&G ROOF DECKING
47803
2x SOUTHERN PINE NAILER 2x SOUTHERN PINE NAILER
Owner
Rose-Hulman Institute of Technology
12'-8" FIELD VERIFY 5500 Wabash Avenue
3/4" DIA. BAR WITH CLEVIS 3/4" DIA. BAR WITH CLEVIS
AT EA END, TYP AT EA END, TYP Terre Haute, Indiana 47803
812-877-1511
4
S-502
3 TB 149'-9" 3 TB 149'-9"
●
S-502 S-502
CENTRAL MONITOR SECTION AT COLUMN CENTRAL MONITOR INTERMEDIATE SECTION MONITOR SOUTH SECTION
1 SCALE: 1/2" = 1'-0"
2 SCALE: 1/2" = 1'-0"
3 SCALE: 1/2" = 1'-0"
N1
FIELD
T FIELD
VERIFY VERIFY
N10 9
04 SECOND LEVEL S-502 06 SOUTH SECOND LEVEL
SEE ARCHITECTURAL 130'-6 13/32" 134'-3 13/16"
03 FIRST LEVEL
120'-11 13/16"
L6x6x1/2x7'-0 1/2" EA SIDE;
4" MINIMUM BEARING EA. END
5
EXISTING MASONRY WALL
S-502
L8x8x1/2x10'-8" EA SIDE;
4" MINIMUM BEARING EA. END
7'-1 1/2" AFF
1/2" 1/2" 8
S-501
3/16 SEAL | DATE 04/01/21
5 3/8" x 6'-4" PLATE
●
SECTION SECTION
NEW CONCRETE RAMP, #4 x 1'-0" LONG
5 SCALE: 1" = 1'-0"
6 SCALE: 3/4" = 1'-0"
1" MINIMUM THICKNESS; DOWEL AT 12" OC,
SEE ARCHITECTURAL EMBED 4" SHEET ISSUE
1 Construction Documents 04/01/21
02 LOWER LEVEL 1
4"
110'-7 1/16"
T
1'-1" (FV)
5.9
9" TOP OF RAMP
VARIES SEE PLAN
SHEET NUMBER
S-501
5.9 1/4
WOOD DECKING
S RHIT MOENCH
RENOVATION
WOOD DECKING 1'-0"
3 SIDES, TYP PER PLAN
PER PLAN
1/4
2x NAILER
2x NAILER 3/16 2-12
WP
3 SIDES,
TYP 1/4 3/4" DIAMETER ROD
5500 Wabash Avenue
3/4" DIAMETER ROD CJP WELD,
1/4 2-12 w/ # 2 1/2" CLEVIS GRIND SMOOTH
w/ # 2 1/2" CLEVIS, TYP
1 1/2" METAL Terre Haute, Indiana
3"
L6x4x3/8 (LLH) ROOF DECK
1 1/2"
CONTINUOUS
1/2" GUSSET PLATE
47803
1/4" BENT PLATE
CONTINUOUS Owner
BOTT/ANGLE L3x3x5/16 x 0'-4" LONG,
EL = 149'-2" 3 SIDES, EACH SIDE Rose-Hulman Institute of Technology
1/4 TYP 1/4 5500 Wabash Avenue
1/2" GUSSET PLATE 1/2" GUSSET PLATE COLUMN BEAM PER
EACH SIDE 1/2" GUSSET PLATE
Terre Haute, Indiana 47803
PER PLAN PLAN, TYP 812-877-1511
1/4" CLOSURE PLATE
NEW W6 COLUMN 3/4" DIAMETER ROD
EXTENSION 1/2" CAP PLATE 1/4 w/ # 2 1/2" CLEVIS
NOTE: ALL VISIBLE STEEL AND CONNECTIONS TO BE AESS CATEGORY 3. NOTE: ALL VISIBLE STEEL AND CONNECTIONS TO BE AESS CATEGORY 3. NOTE: ALL VISIBLE STEEL AND CONNECTIONS TO BE AESS CATEGORY 3.
MONITOR CONNECTION DETAIL MONITOR CONNECTION DETAIL MONITOR CONNECTION DETAIL MONITOR CONNECTION DETAIL
1 SCALE: 1" = 1'-0"
2 SCALE: 1" = 1'-0"
3 SCALE: 1 1/2" = 1'-0"
4 SCALE: 1" = 1'-0"
Architect
RATIO
101 South Pennsylvania Street
Indianapolis, Indiana 46204
317-633-4040
S8
2"
EXISTING TIMBER
(2) - 1/2" Ø LAG BEAM PER PLAN Mechanical / Electrical Engineer
2x NAILER 3 SIDES, TYP
SCREWS EACH SIDE
3"
1/4 R.E. Dimond & Associates, Inc.
HSS12x6 PER PLAN 732 N Capitol Avenue
DECKING
PER PLAN
1/4 2-12 Indianapolis, Indiana 46204
WP 3/4" DIAMETER ROD
3/8" TAB PLATE 317-634-4672
w/ # 2 1/2" CLEVIS 3/16
1/4 T/BEAM VARIES, L6x4x3/8 (LLH)
(2) - L3x3x5/16 HSS4x4x5/16 AT 4'-0" OC MAX
BEAM SEE PLAN CONTINUOUS
PER PLAN TB VARIES, SEE PLAN 1/2" GUSSET PLATE
3/16
BOTT/ANGLE
EL = 149'-2" 1/4 04 SECOND LEVEL
EACH SIDE 130'-6 13/32"
1/4 1/2" GUSSET PLATE
EACH SIDE
2L3x3x5/16 HANGER 1/2"x5"x0'-10" PLATE
BEAM PER PLAN 1/4" CLOSURE PLATE
(2) - 1/2" DIA. HILTI KH-EZ
SCREW ANCHORS,
2" EMBED, 7" GA
NOTE: ALL VISIBLE STEEL AND CONNECTIONS TO BE AESS CATEGORY 3.
D
1'-1" (FV)
S6
EXISTING
MASONRY WALL
EACH SIDE
3/16
EXISTING 3" WOOD DECKING EXISTING
L3x3x5/16 x 0'-6" WITH 1/4" 10" SLAB
STIFFENER CENTERED
4"
BEAM PER PLAN 1/4
(2) - 1/2"x4" LAG SCREWS 5/16" x 0'-6" BENT PLATE 4"
SEAL | DATE 04/01/21
L4x4x3/8x0'-8", EA SIDE
SHEET ISSUE
DETAIL DETAIL SECTION SECTION 1 Construction Documents 04/01/21
9 SCALE: 1 1/2" = 1'-0"
10 SCALE: 1 1/2" = 1'-0"
11 SCALE: 1" = 1'-0"
12 SCALE: 1" = 1'-0"
EXISTING
WOOD DECKING
(2) 3/4" DIAMETER EXISTING
THRU BOLTS WOOD DECKING
(2) 3/4" DIAMETER
1"
THRU BOLTS
3" 2" 3"
1 1/2"
3"
WOOD DECKING
1 1/2"
2x NAILER AND SHALL BE USED ONLY PURSUANT TO THE AGREEMENT WITH RATIO. NO OTHER USE,
DISSEMINATION OR DUPLICATION MAY BE MADE WITHOUT PRIOR WRITTEN CONSENT OF RATIO. ALL
HSS6x6 COL
3 SIDES COMMON LAW RIGHTS OF COPYRIGHT AND OTHERWISE ARE HEREBY SPECIFICALLY RESERVED.
3/16
PER PLAN
2x NAILER PROJECT NO. 19040.000
1/4
L5x3x5/16 (LLV)
BEAM SHEET TITLE
PER PLAN
COLUMN
1/4 HSS3x3x1/4 x 0'-10 1/4" LONG
AT 3'-0" OC
STRUCTURAL STEEL
PER PLAN
SECTIONS AND
1/4
DETAILS
3/31/2021 5:43:57 PM
S-502
G
5'-0"
5
RHIT MOENCH
●
S-503 RENOVATION
S8 5500 Wabash Avenue
(FV) (FV) Terre Haute, Indiana
8.9
(4) 1/2" DIAMETER x 6" LONG
47803
LAG SCREWS, 6" GAGE
5.1 Owner
EXISTING C9 DECKING
PURLIN PER PLAN 06 SOUTH SECOND LEVEL
Rose-Hulman Institute of Technology
PER PLAN 3 SIDES, TYP 134'-3 13/16" 5500 Wabash Avenue
EXISTING
3/16
MATCH
Terre Haute, Indiana 47803
20'-3"
C4 PER PLAN 812-877-1511
2"
EXISTING C9
PURLIN
2"
04 SECOND LEVEL
3"
PER PLAN
6 1/2"
130'-6 13/32" 1/4
EXISTING TIMBER
BEAM PER PLAN
03 FIRST LEVEL
120'-11 13/16"
EXISTING 10"
CONCRETE SLAB
3/4" DIAMETER ROD
2" MIN
3/16
20'-3" AFF
BEAM PER PLAN
MC6, CAP EACH
END WITH 1/4" PLATE (2) CLIP ANGLE CONNECTION,
REMOVE CONCRETE
ENCASEMENT AS REQUIRED TO
FACILITATE CONNECTION.
DETAIL SECTION
5 SCALE: 1 1/2" = 1'-0"
6 SCALE: 1" = 1'-0"
SHEET ISSUE
1 Construction Documents 04/01/21
STRUCTURAL STEEL
SECTIONS AND
DETAILS
3/31/2021 5:48:38 PM
SHEET NUMBER
S-503
ABBREVIATIONS ARCHITECTURAL MATERIAL LEGEND
A F M T
A/C AIR CONDITIONING F-R FIRE RESISTIVE MAX. MAXIMUM T. THICKNESS
GENERAL ARCHITECTURAL NOTES
FINISHED WOOD
ACOUS.
A.C.T.
ACP
ACOUSTICAL
ACOUSTICAL CEILING TILE
ACOUSTICAL CEILING PANEL
FAB.
F.C.U.
F.D.
FABRICATE/FABRICATOR
FAN COIL UNIT
FLOOR DRAIN
MB.
M.C.
M.D.F.
MARKER BOARD
MECHANICAL CONTRACTOR
MEDIUM DENSITY FIBERBOARD
T.B.
TBD
T.C.
TACK BOARD
TO BE DETERMINED
TOP OF CURB
EARTH SHOWN CUT AND ELEVATION ACOUSTICAL CEILING TILE
A. THESE GENERAL NOTES APPLY TO ARCHITECTURAL
DRAWINGS.
RHIT MOENCH
ADA
ADAAG
AMERICANS W/DISABILITIES ACT
AMERICANS W/DISABILITIES
ACCESSIBILITY GUIDELINES
F.E.
F.E.C.
F.F.E.
FIRE EXTINGUISHER
FIRE EXTINGUISHER CABINET
FINISH FLOOR ELEVATION
MECH.
M.E.P.
MFR.
MECHANICAL
MECH./ELECT./PLUMBING
MANUFACTURER(ING)
T.D.
TECH.
TEL.
TOP OF DECK
TECHNICAL
TELEPHONE
GRANULAR FILL ENGINEERED WOOD: GLUE
LAMINATED
RESINOUS FLOORING:
TERRAZO, TROWEL-ON, UNO
B. WORK SHOWN ON THE DRAWINGS SHALL BE BASE BID
UNLESS SPECIFICALLY NOTED TO BE BY ALTERNATE BID.
C. FIELD VERIFY EXISTING FINISH FLOOR ELEVATIONS PRIOR TO
RENOVATION
SAND, GROUT WOOD FLOOR, WOOD TILE: CERAMIC, QUARRY, UNO STARTING CONSTRUCTION. MATCH NEW FLOOR ELEVATIONS
ADJ.
A/E
ADJUSTABLE
ARCHITECT/ENGINEER
F.F.&E. FURNISHINGS, FIXTURES AND
EQUIPMENT
M.H.
MIN.
MANHOLE
MINIMUM
TEMP.
T&G
TEMPORARY
TONGUE AND GROOVE
AS NOTED SHINGLES, OR SIDING WITH EXISTING UNLESS NOTED OTHERWISE.
D. DIMENSIONS TO EXISTING CONSTRUCTION ARE TO FINISH
5500 Wabash Avenue
CAST-IN-PLACE CONCRETE PARTICLEBOARD CARPET, CARPET TILE (DETAIL)
A.F.F.
ALT.
ABOVE FINISHED FLOOR
ALTERNATE
F.H.C.
FIN.
FIRE HOSE CABINET
FINISH(ED)
MISC.
M.O.
MISCELLANEOUS
MASONRY OPENING
T.M.
TMPRD.
TOP OF MASONRY
TEMPERED
SURFACE. DIMENSIONS TO NEW CONSTRUCTION ARE TO
STRUCTURAL CENTERLINE, FACE OF CONCRETE OR Terre Haute, Indiana
MASONRY CONSTRUCTION, OR TO FACE OF FINISH UNLESS
ALUM.
A.P.
ALUMINUM
ACCESS PANEL
FLR.
FLUOR.
FLOOR
FLUORESCENT
MTL. METAL T/O
T.P.
TOP OF
TOP OF PAVEMENT
PRECAST CONCRETE, CAST
STONE
PLYWOOD GRATING
SHOWN IN PLAN NOTED OTHERWISE. FIELD VERIFY ALL CONDITIONS AND
DIMENSIONS PRIOR TO STARTING WORK AND NOTIFY
47803
ARCH. ARCHITECT/ARCHITECTURAL F/O FACE OF N T.S. TOP OF STEEL CONCRETE MASONRY UNIT GLASS FIBER REINFORCED GRATING ARCHITECT IMMEDIATELY IF DISCREPANCIES ARE FOUND
A.V. AUDIO/VISUAL F.O. FINISH OPENING N.A.F. NO APPLIED FININSH T.W. TOP OF WALL CONCRETE SIDING OR TRIM BETWEEN CONTRACT DOCUMENTS AND ACTUAL FIELD Owner
F.O.B. FACE OF BLOCK N.I.C. NOT IN CONTRACT TYP. TYPICAL CONDITIONS. Rose-Hulman Institute of Technology
BRICK MASONRY EIFS INSULATED GLASS: E. DO NOT SCALE DRAWINGS. REFER DIMENSION QUESTIONS
B F.O.BR. FACE OF BRICK NO. NUMBER 5500 Wabash Avenue
(SMALL SCALE) TO ARCHITECT FOR INTERPRETATION.
BD. BOARD F.O.C. FACE OF CONCRETE N.T.S. NOT TO SCALE U STONE: LIMESTONE, Terre Haute, Indiana 47803
F. DOOR AND FRAME NUMBERS CORRESPOND TO RESPECTIVE
BITUM. BITUMINOUS F.O.F. FACE OF FINISH U.N.O. UNLESS NOTED OTHERWISE GRANITE, MARBLE OR AS SPRAYED FIREPROOFING INSULATED GLASS: ROOM NUMBERS. IN ROOMS WITH MULTIPLE OPENINGS, A 812-877-1511
BLDG. BUILDING F.O.G. FACE OF GYPSUM BD. NOTED SHOWN ON ROLLED SHAPE (DETAIL) SUFFIX HAS BEEN ADDED TO DOOR NUMBERS, I.E., A101-B.
O UTIL. UTILITY
B/O BOTTOM OF F.O.S. FACE OF STUD O.A. OVER ALL U.V. UNIT VENTILATOR TERRA COTTA, STRUCTURAL BATT INSULATION: THERMAL MEMBRANE: WATERPROOF, G. LOCATE INSIDE FACE OF DOOR FRAME JAMBS 6 INCHES
B.O.W. BOTTOM OF WALL FPRF. FIREPROOF CLAY TILE OR ACOUSTICAL, UNO ROOF, DAMPPROOFING FROM FINISH FACE OF ADJACENT WALLS UNLESS NOTED
O.C. ON CENTER
OTHERWISE.
BSMT. BASEMENT FT. FOOT/FEET O.D. OUTSIDE DIAMETER V
METAL: TYPE AS NOTED RIGID INSULATION: THERMAL, AIR BARRIER SYSTEM H. COORDINATE EQUIPMENT WORK WITH MANUFACTURERS AND
F.V. FIELD VERIFY O.F.C.I. OWNER FURNISHED-CONTRACTOR V.C.T. VINYL COMPOSITION TILE SUPPLIERS TO INSURE PROPER ROUGH-IN CLEARANCES FOR
ACOUSTICAL, OR SAFING
C INSTALLED VERT. VERTICAL INSTALLATION, USE AND MAINTENANCE.
CAB. CABINET G O.F.O.I. OWNER FURNISHED-OWNER VEST. VESTIBULE METAL: ROLLED SHAPES GYPSUM WALL BOARD I. PROTECT EXISTING SURFACES TO REMAIN THAT ARE NOT
C.F.C.I. CONTRACTOR GA. GAUGE INSTALLED INCLUDED IN SCOPE OF WORK BUT THAT ARE WITHIN AREAS
VIF VERIFY IN FIELD
FURNISHED-CONTRACTOR INSTALLED O.H. OPPOSITE HAND OF CONSTRUCTION ACTIVITY.
G.C. GENERAL CONTRACTOR WOOD FRAMING / BLOCKING: PLASTER ON METAL LATH J. PATCH, REPAIR AND RESTORE EXISTING FINISHES AND
C.G. CORNER GUARD GEN. GENERAL OPG. OPENING W CONTINOUS SURFACES TO AS NEW CONDITION AS REQUIRED TO MATCH Architect
C.I.P. CAST-IN-PLACE GL. GLASS OPP. OPPOSITE W WIDE/WIDTH SURROUNDING MATERIALS OR TO PROVIDE APPROPRIATE
C.J. CONTROL JOINT G.W.B./ GYPSUM WALL BOARD
WOOD SHIM SHEATHING: GYPSUM, OR AS
SUBSTRATE PRIOR TO INSTALLING NEW FINISHES. AREAS
RATIO
W/ WITH NOTED
CL. CENTERLINE GWB P NOTED TO BE PATCHED OR REPAIRED ON THE DRAWINGS 101 South Pennsylvania Street
W.C. WATER CLOSET
CLG. CEILING P.L. PROPERTY LINE ARE GIVEN FOR REFERENCE AND SHALL NOT BE Indianapolis, Indiana 46204
WD. WOOD
CLR CLEAR(ANCE) H P. LAM PLASTIC LAMINATE NOTE: PATTERNS SHOWN REPRESENT CUT MATERIALS IN
INTERPRETED TO LIMIT THE SCOPE OF WORK. 317-633-4040
W.H. WATER HEATER K. VERTICAL COURSING FOR NEW MASONRY WALL
C.M CONSTRUCTION MANAGER H. HEIGHT PLAS. PLASTER W/O WITHOUT PLAN OR SECTION, UNLESS NOTED OTHERWISE ABOVE. CONSTRUCTION SHALL EQUAL EIGHT INCHES (8") FOR ONE
CMP COMPOSITE METAL PANEL HB HOSE BIBB PR. PAIR WT. WEIGHT CONCRETE MASONRY UNIT PLUS ONE MORTAR JOINT AND Structural Engineer
C.M.U. CONCRETE MASONRY UNIT HDWR. HARDWARE PREFAB. PREFABRICATED W.W.F. WELDED WIRE FABRIC THREE BRICK COURSES PLUS THREE MORTAR JOINTS,
COL. COLUMN H.M. HOLLOW METAL PT. BD. PARTICLE BOARD UNLESS NOTED OTHERWISE. Fink Roberts & Petrie, Inc.
CONC. CONCRETE HORIZ. HORIZONTAL PTD. PAINTED ARCHITECTURAL SYMBOLS LEGEND L. TOOTH NEW MASONRY INTO EVERY OTHER COURSE OF
EXISTING MASONRY UNLESS OTHERWISE INDICATED.
9449 Priority Way W Dr #200
CONST. CONSTRUCTION HT. HEIGHT PWD. PLYWOOD Indianapolis, Indiana 46240
MISCELLANEOUS PROVIDE HORIZONTAL ANCHORS BETWEEN NEW AND
CONT. CONTINUOUS HVAC. HEATING, VENTILATION & A.C. EXISTING MASONRY AT CONDITIONS THAT PROHIBIT 317-872-8400
ANGLE
CONTR. CONTRACTOR H.W. HOT WATER Q TOOTHED-TYPE CONSTRUCTION. HORIZONTAL JOINTS OF
CONTRACTOR CENTER LINE NEW MASONRY SHALL MATCH EXISTING UNLESS OTHERWISE
Q.T. QUARRY TILE
COOR. COORDINATE # NUMBER INDICATED. NEW MASONRY BOND SHALL MATCH EXISTING
I COLUMN GRIDS Mechanical / Electrical Engineer
CPT. CARPET PARTITION TYPE SYMBOL* UNLESS OTHERWISE INDICATED.
I.D. INSIDE DIAMETER R R.E. Dimond & Associates, Inc.
101
A EXISTING DOOR / DOOR NUMBER M. PROVIDE CONTROL JOINTS (C.J.) IN MASONRY
C.T. CERAMIC TILE INCAN. INCANDESCENT R RADIUS CONSTRUCTION AS INDICATED. WHERE NOT SHOWN, 732 N Capitol Avenue
C.W. COLD WATER INFO. INFORMATION R.C.P. REFLECTED CEILING PLAN 1 NEW M8A.D.2.A *REFER TO INTERIOR PARTITION LEGEND PROVIDE MAXIMUM SPACING BETWEEN VERTICAL JOINTS OF Indianapolis, Indiana 46204
INSUL. INSULATION R.D. ROOF DRAIN S2A.P 30'-0” AND MAXIMUM DISTANCE BETWEEN OUTSIDE CORNERS
CT-1 AND JOINTS OF 8'-0”. PROVIDE JOINTS BETWEEN INTERIOR
317-634-4672
D INT. INTERIOR REF. REFERENCE KEY NOTE (SHAPE VARIES)
D.E.F.S. DIERCT EXTERIOR FINISH SYSTEM ELEVATION DATUM LOAD BEARING AND NON-LOAD BEARING PARTITIONS, AT ALL
REFL. REFLECTED
REFERENCE ABRUPT CHANGES IN WALL HEIGHT, AT CHANGES IN
DEPT. DEPARTMENT J REINF. REINFORCED PARTITION THICKNESS AND AT PILASTER LOCATIONS. VERIFY
DET. DETAIL JAN. JANITOR RESIL. RESILIENT FINAL CONTROL JOINT LOCATIONS WITH ARCHITECT PRIOR
W10 WINDOW NUMBER
D.F. DRINKING FOUNTAIN J.C. JANITOR CLOSET R.H. RIGHT HAND TO STARTING WORK.
DIA. DIAMETER JST. BRG. JOIST BEARING RM ROOM 1 N. PROVIDE CONTROL JOINTS (C.J.) IN GYPSUM BOARD WALL
DIM. DIMENSION JT. JOINT R.O. ROUGH OPENING A101 ENLARGED DRAWING REFERENCE CONSTRUCTION AS INDICATED. WHERE NOT SHOWN,
DISP. DISPENSER
-
18"
42" 12" 12" MIN. 24" MIN.
X. REPAIR AND PATCH SPRAYED FIRE-RESISTIVE AND FIRESTOP SEAL | DATE 04/01/21
TOILET PAPER MIN. ACCESSIBLE MATERIALS WHERE DAMAGED DUE TO INSTALLATION OF NEW
MOUNTING AREA KNEE CLEARANCE MATERIALS TO RESTORE SPECIFIED FIRE RATING.
FOLD DOWN SOAP SHELF, WHERE
70"
38" MAX.
TOE CLEARANCE
48".
PACKAGES OR WILL BE INCLUDED IN FUTURE BID PACKAGES
46"
6" 6" 8"
36" MAX.
SPACE
34" MAX.
33"- 36"
IS SHOWN ON THESE CONSTRUCTION DOCUMENTS FOR
40"
40"
1 1/2" DIAMETER GRAB
34"
24" STD.
17" H.C.
18"
17"
OF MECHANICAL AND ELECTRICAL COORDINATION DRAWINGS
18" MIN.
9"
9"
9"
OF COORDINATION ISSUES.
7" - 9" AA. REFER TO LIFE SAFETY PLAN DRAWINGS AND CODE
TOE CLEARANCE * 1 1/2" MIN. CLEAR REQUIRED
SUMMARY FOR FIRE-RATED FLOOR, WALL, CEILING AND ROOF
SPACE AROUND ALL GRAB BARS
LOCATIONS. INSTALL FIRESTOPPING AT PENETRATIONS IN SHEET ISSUE
RATED CONSTRUCTION AND AT TOPS OF RATED WALLS.
WATER CLOSET WATER CLOSET URINAL LAVATORY OR VANITY SINK ELECTRIC WATER TRANSFER ADA 1 Construction Documents 04/01/21
BB. REFER TO STRUCTURAL DRAWINGS FOR FOOTING AND
SIDE WALL BACK WALL COOLER SHOWER FOUNDATION DRAINS, UNDERSLAB DRAINAGE AND BACKFILL
ACCESSIBLE FIXTURES INDICATED WITH ACCESSIBLE FIXTURES INDICATED WITH REQUIREMENTS.
HATCH ON FLOOR PLAN HATCH ON FLOOR PLAN CC. REFER TO LANDSCAPE AND CIVIL DRAWINGS FOR SITE
ELEMENTS AND IMPROVEMENTS ADJACENT TO BUILDING
EXTERIOR.
DD. REFER TO A-002 FOR PARTITION CONSTRUCTION TYPE.
EE. WALLS SHOWN WITHIN THE CONFINES OF CONSTRUCTION
THROUGH OMISSION OF GRAY SHADING AT PORTIONS OF
STANDARD TOILET ROOM ACCESSORY MOUNTING HEIGHTS PLAN REQUIRE ARCHITECTURAL WORK. SOME IS REPAIR OF
SELECTIVE WALL DEMO DUE TO REQUIRED SHAFT WORK.
ONCE WORK IS COMPLETED AND STUDS. INSULATION AND
DRYWALL ARE REPAIRED, PROVIDE NEW FINISHES TO MATCH
PER MANUFACTURER'S
EXISTING ADJACENT BASE AND PAINT COLOR. VERIFY
REFLECTIVE SURFACE
DIMENSION FROM
CL OF PUSH BUTTON
RECOMMENDATION
TOP OF CHANGING
COORDINATE WITH
BOTTOM EDGE OF
TOP OF COUNTER
TOP OF CONTROL
FINISH FLOOR
BOTTOM OF UNIT
BOTTOM OF UNIT
TOP OF HANDLE
TOP OF SHELF
TOP OF SHELF
TOP OF HOOK
WHEN IN USE
B.O. MIRROR
TOP OF UNIT
TOP OF UNIT
TOP OF UNIT
CL OF HOOK
CL OF SLOT
CL OF UNIT
CL OF BAR
SURFACE
SURFACE
TO:
OR
MOUNTING
70"
MAX. 48"
MAX. 48"
MAX. 48"
60" TYP.
48" ADA
MAX. 40"
54"
AND SHALL BE USED ONLY PURSUANT TO THE AGREEMENT WITH RATIO. NO OTHER USE,
33 1/2"
42"
42"
15" MIN.
15" MIN.
40"
40"
MAX
DISSEMINATION OR DUPLICATION MAY BE MADE WITHOUT PRIOR WRITTEN CONSENT OF RATIO. ALL
34"
34"
34"
34"
30"
25"
COMMON LAW RIGHTS OF COPYRIGHT AND OTHERWISE ARE HEREBY SPECIFICALLY RESERVED.
24"
MOUNTING HEIGHTS
SHEET NUMBER
A-001
INTERIOR PARTITION TYPES INTERIOR PARTITION NOTES
1 1/2"
SHOWN IN ARCHITECTURAL PLANS WILL REQUIRE WALL TO
BE REPAINTED CORNER TO CORNER TO MATCH EXISTING
PAINT. Terre Haute, Indiana
D. REFER TO WALL SECTIONS FOR EXTERIOR WALL
S1FA 1 1/2" METAL 'Z' FURRING WITH (1) LAYER
5/8" GYPSUM WALL BOARD ONE SIDE
CONSTRUCTION. 47803
2 1/8"
E. PROVIDE WATER RESISTANT GWB IN ALL ROOMS
CONTAINING OPERABLE PLUMBING FIXTURES AND WITHIN
4 FEET OF DRINKING FOUNTAINS / WATER COOLERS, U.N.O. Owner
F. PROVIDE LATERAL BRACING FOR PARTITIONS WHICH Rose-Hulman Institute of Technology
EXTEND ABOVE CEILING.
3 5/8" METAL STUDS WITH (1) LAYER 5/8" 5500 Wabash Avenue
S3A GYPSUM WALL BOARD EACH SIDE
G. PROVIDE FIRE RESISTIVE RATED GYPSUM WALL BOARD AT
Terre Haute, Indiana 47803
4 7/8"
ALL RATED ASSEMBLIES TO MEET ASSEMBLY
* 1 HR RATED UL419 REQUIREMENTS. 812-877-1511
* ACOUSTIC ATTEN. COMPONENTS STC- H. PROVIDE FIRE RESISTIVE JOINT SYSTEMS EQUAL TO WALL
RATING AT ALL PENETRATIONS AND AT HEAD / FLOOR
INTERSECTIONS WITH RATED ASSEMBLIES.
3 5/8" METAL STUDS WITH (2) LAYERS 5/8"
S3B TYPE X GYPSUM WALL BOARD EACH SIDE
I. PROVIDE ACOUSTICAL SEALANT AT WALL SILL, HEAD,
PENETRATIONS AND ADDITIONAL SPECIFIED SOUND
6 1/8"
* 2 HR RATED U419 ATTENUATION COMPONENTS AT SOUND RATED WALLS.
* ACOUSTIC ATTEN. COMPONENTS J. PROVIDE SPECIFIED TILE BACKER BOARD AT ALL WALLS
STC-50 SCHEDULED TO HAVE CERAMIC TILE.
K. ISOLATE NON-LOAD-BEARING STUD FRAMING FROM
3 5/8" METAL STUDS WITH (1) LAYER 5/8"
S3C GYPSUM WALL BOARD ONE SIDE
BUILDING STRUCTURE TO PREVENT TRANSFER OF
4 1/4"
VERTICAL LOADS WHILE PROVIDING LATERAL SUPPORT AS
* ACOUSTIC ATTEN. COMPONENTS SPECIFIED. Architect
STC-32 L. STUD SPACING 16" O.C. UNLESS NOTED OTHERWISE
RATIO
REV. 04/03/09 101 South Pennsylvania Street
Indianapolis, Indiana 46204
4" METAL SHAFT WALL STUDS WITH (2)
S4Y LAYERS 5/8" GYPSUM WALL BOARD ONE
317-633-4040
5 1/4"
SIDE AND 1" GYPSUM SHAFT LINER
* 2 HR RATED U417 INTERIOR PARTITION LEGEND
* ACOUSTIC ATTEN. COMPONENTS Structural Engineer
STC-39 PARTITION TYPE SYMBOL
Fink Roberts & Petrie, Inc.
PARTITION DESIGNATION
6" METAL STUDS WITH (1) LAYER 5/8" 9449 Priority Way W Dr #200
S6A GYPSUM WALL BOARD EACH SIDE
PARTITION TYPE Indianapolis, Indiana 46240
317-872-8400
7 1/4"
* ACOUSTIC ATTEN. COMPONENTS FIRE RATING (I.E. 1= 1 HOUR)
STC-44 ACOUSTICAL ATTENUATION
REQ'D
M8A.D.2.A
Mechanical / Electrical Engineer
8" METAL STUDS WITH (1) LAYER 5/8" PARTITION HEIGHT CODE
S8A GYPSUM WALL BOARD EACH SIDE S2A.P R.E. Dimond & Associates, Inc.
732 N Capitol Avenue
9 1/4"
ADDITIONAL PARTITION
DESIGNATION, WHERE
Indianapolis, Indiana 46204
OCCURS 317-634-4672
NEW PARTITIONS
1'-0"
PARTITIONS TO BE DEMOLISHED
5 5/8"
* 2 HR RATED UL906
* ACOUSTIC ATTEN. COMPONENTS
STC-46 (D) TERMINATE AT FLOOR / ROOF DECK
7 5/8"
(C) TERMINATE AT CEILING
6"
HEIGHT AS
7 5/8" CONCRETE MASONRY UNIT WITH INDICATED IN
M8E (1) LAYER 5/8" GYPSUM WALL BOARD INCHES OR (V)
INDICATES
9 3/4"
OVER 1 1/2" METAL FURRING ONE SIDE
HEIGHT THAT
VARIES
8"
* ACOUSTIC ATTEN. COMPONENTS STC
>54 (rating based on concrete density-verify
concrete density)
7 1/4"
SEAL | DATE 04/01/21
SHEET ISSUE
1 Construction Documents 04/01/21
COMBINATION OF THE
OCCURS) OCCURS)
FIRE EXTINGUISHER
FIRE EXTINGUISHER
CABINET, FIREHOSE
NOTES:
RECEPTACLE TRIM
WORK SURFACES
CABINET, OR ANY
ELECTRICAL OR
BY DIMENSION, OR TO LOCATE
ABOVE
6'-8"
SHEET TITLE
INTERSECTING WALLS AS DETAILED DOOR CONTROLLERS, FIRE ALARM
SO AS NOT TO INTERFERE WITH THE PULL SWITCHES AND SIMILAR ITEMS
INTERIOR PARTITION
6"
4'-0"
SEGMENT IS LESS THAN 24" WIDE, ALLOWING THE OPERABLE PARTS WINDOW, DOOR
CENTER THE DEVICES AS DETAILED. TO BE LESS THAN 4'-0" AFF) OR "FEATURE"
THAT SEPARATES
WALL INTO STANDARD
4/1/2021 12:10:17 PM
A-002
RHIT MOENCH
RENOVATION
N10 N9 N8 N7 N6 N5 N4 N3 N2 N1 5500 Wabash Avenue
Terre Haute, Indiana
A A 47803
Owner
Rose-Hulman Institute of Technology
SERVER 5500 Wabash Avenue
OFFICE RECEIVING ROOM
G138 G134
Terre Haute, Indiana 47803
G110 MECHANICAL B B 812-877-1511
TECH SHOP ROOM CHEMICAL
G130 G106 STORAGE STORAGE
FL206 FL205 ELECTRICAL
SWITCH GEAR MECHANICAL
OFFICE OFFICE FL203 FL201
STORAGE OFFICE
G136 G132 WORK AREA
G100B G100A G108
C C
CIRCULATION CIRCULATION RESTROOM MECHANICAL
G100 G111 G101
OFFICE FL202
OFFICE OFFICE
G153 G151 G133 OFFICE Architect
G131 OFFICE OFFICE BREAK AREA RATIO
G123 G113 G103A MAIL DIST.
OFFICE OFFICE OFFICE D CENTER D 101 South Pennsylvania Street
G149 G147 G137 ANNEX Indianapolis, Indiana 46204
OFFICE OFFICE OFFICE EL204 317-633-4040
G135 G121 G115 CONFERENCE N10 N9 N8 N7 N6 N5 N4 N3 N2 N1
OFFICE ROOM DELIVERY DELIVERY
OFFICE G103 STORAGE ELEV 1
OFFICE G143 CAGE CAGE Structural Engineer
G141 OFFICE OFFICE OFFICE G105 -
G145 - -
G139 G119 G117 E E Fink Roberts & Petrie, Inc.
OFFICE ELEVATOR 9449 Priority Way W Dr #200
EL202A MECHANICAL FAB. LAB Indianapolis, Indiana 46240
EL203 STOCK 317-872-8400
STORAGE
CL208
MACHINE FABRICATION Mechanical / Electrical Engineer
F F
TOOL LAB II LAB
EL202 EL207
R.E. Dimond & Associates, Inc.
STAIR CIRCULATION TOOL ROOM 732 N Capitol Avenue
- EL211 EL205 Indianapolis, Indiana 46204
317-634-4672
G G
INSTRUCTIONAL
TECHNOLOGY
DL204
MACHINE
H TOOL SHOP H
I.T. DL202
MENS R.R. EQUIP./OFFICE
DL203 DL204A
J MANAGER J
OFFICE OFFICE
DL204B DL205
ROBOTICS
CLASSROOM
L DL207 L
MATERIALS
ROBOTICS
M LAB M
WORKROOM/STORAGE
CL207
DL207A
STAIR
CL211
STORAGE
N CL202B N
CUSTODIAL
CUSTODIAL STORAGE
SERVICES CL212
CL202
P P
SHEET ISSUE
1 Construction Documents 04/01/21
LOWER LEVEL 2
EXISTING PLAN
4/1/2021 11:29:49 AM
SHEET NUMBER
AE-101
RHIT MOENCH
RENOVATION
N10 N9 N8 N7 N6 N5 N4 N3 N2 N1 5500 Wabash Avenue
Terre Haute, Indiana
A A 47803
Owner
CLOSET ANALYTICAL CHEMISTRY Rose-Hulman Institute of Technology
G220A OFFICE OFFICE
LAB LAB
G218 G212 MENS R.R. 5500 Wabash Avenue
FL106 FL104 Terre Haute, Indiana 47803
G206
B B 812-877-1511
OFFICE
CLASSROOM G216 OFFICE STUDY AREA
G222 CLASSROOM G210B G204
G220 BIOCHEMISTRY LAB SUPPORT
WOMENS R.R. OFFICE LAB OFFICE
OFFICE OFFICE CLOSET FL101A
G202 FL107 FL110 FL103
G214 G210A -
C C
OFFICE OFFICE OFFICE OFFICE
FL108 FL109 FL102 FL101
STORAGE Architect
9.8 8.9 7.9 FL102A
6.9 5.9 5.5 5.1 4.1 3.1 2.1 1.2
OFFICE OFFICE OFFICE OFFICE RATIO
G215B G215A G211 G205 D D 101 South Pennsylvania Street
Indianapolis, Indiana 46204
317-633-4040
CLASSROOM CLASSROOM N10 N9 N8 N7 N6 N5 N4 N3 N2 N1
G221 G219
OFFICE ELEV 1
OFFICE OFFICE OFFICE OFFICE - Structural Engineer
G205A MAIL
G217 G213 G209 G207 E LOUNGE DISTRIBUTION E Fink Roberts & Petrie, Inc.
EL112 CENTER HOUSEKEEPING 9449 Priority Way W Dr #200
EL106 EQUIPMENT
VENDING
Indianapolis, Indiana 46240
ROOM
MACHINE EL102
317-872-8400
COOK
GREENHOUSE ROOM
G219A EL103
F F Mechanical / Electrical Engineer
R.E. Dimond & Associates, Inc.
732 N Capitol Avenue
WOMENS R.R. MENS R.R.
Indianapolis, Indiana 46204
EL105 EL104
317-634-4672
G G
SEMICONDUCTOR
OFFICE OFFICE OPTICS LAB
OFFICE OFFICE
OFFICE DL110D DL110F DL110G DL108
DL110E OFFICE
DL110C DL107
H H
OFFICE
DL110B OFFICE NUCLEAR OFFICE
DL110A PHYSICS LAB
ADMIN OFFICE DL106
DL105
OPTICAL DL110
J ENGINEERING J
LAB 3
OFFICE OPTICAL
DL115 OFFICE METROLOGY
DL116
DL120 LAB OFFICE
DL104 DL103
ELECTRICAL
EQUIPMENT
K ROOM K
OPTICAL DL118
ENGINEERING
LAB 1 SENIOR OFFICE
DL117 DARK ROOM DESIGN LAB DL102
DL117A DL101
CLASSROOM
L L
DL119 ACOUSTICS
OPTICAL HOLOGRAPHIC PROJECTS
ENGINEERING INTERFEROMETRY LAB OFFICE
LAB 2 LAB CL110 CL109
CL118 CL112
CIRCULATION
CL111
M M
M.T.F.
MEASUREMENT NON-LINEAR CONFERENCE
LAB OPTICS LAB ROOM H BAR
CL114 CL115 CL116 EL108
N N
R R
MACHINE
ELECTRICAL SHOP OFFICE OFFICE
ROOM BL107 BL106 BL100
PHYSICS LAB BL115
2 CUSTODIAL
S STORAGE S
BL114
BL116 ELEV 2
BL118
S10 S9 S8 S7 S6 S5 S4 S3 S2 S1
OFFICE OFFICE OFFICE
AL104 AL103 AL102
T T
ELEVATOR
MECHANICAL STORAGE
BL117 AL101A
9.8 8.9 7.9 6.9 5.9 5.5 5.1 4.1 3.1 2.1 1.2
ART CURATOR WATER ROOM
AL101 AL106
U U
V V
COPYRIGHT NOTICE: THIS ARCHITECTURAL AND ENGINEERING DRAWING IS GIVEN IN CONFIDENCE
AND SHALL BE USED ONLY PURSUANT TO THE AGREEMENT WITH RATIO. NO OTHER USE,
DISSEMINATION OR DUPLICATION MAY BE MADE WITHOUT PRIOR WRITTEN CONSENT OF RATIO. ALL
COMMON LAW RIGHTS OF COPYRIGHT AND OTHERWISE ARE HEREBY SPECIFICALLY RESERVED.
AE-102
RHIT MOENCH
RENOVATION
N10 N9 N8 N7 N6 N5 N4 N3 N2 N1 5500 Wabash Avenue
Terre Haute, Indiana
A A 47803
Owner
NMR LAB RESEARCH
LAB CHEMICAL Rose-Hulman Institute of Technology
F106 STORAGE
F105 5500 Wabash Avenue
F102A
Terre Haute, Indiana 47803
B B 812-877-1511
LAB LAB ORGANIC LAB GENERAL
CLASSROOM CLASSROOM STOCKROOM
G306 G304 F108 COMPUTER CHEMISTRY
G310 G308 F102
AND Room LAB
STOCKROOM
REFERENCE F101A F101
OFFICE MANAGER
CLOSET ROOM
F104 F103
G304A F107
C C
CUSTODIAL
STORAGE
F113
PREPARATION
OFFICE OFFICE ADMIN OFFICE COPYROOM LAB
Architect
9.8 8.9 F109 7.9 F110 6.9 F111 F112
5.9 5.5 5.1 F114 4.1 3.1 2.1 1.2
RATIO
OFFICE
D D 101 South Pennsylvania Street
G309
EQUIPMENT SERVER/EQUIP. Indianapolis, Indiana 46204
CLASSROOM CLASSROOM CLASSROOM REPAIR ROOM STORAGE 317-633-4040
OFFICE
N10 N9 N8 N7
E107A
N6 E107C
N5 N4 N3 CLASSROOMN2 N1
G317 G315 G313
G305 ELEV 1 E104
OFFICE - Structural Engineer
G311 OFFICE WOMENS R.R.
E E109 E Fink Roberts & Petrie, Inc.
G307 TECHNICIAN
OFFICE 9449 Priority Way W Dr #200
WORKSHOP E107B MENS R.R. Indianapolis, Indiana 46240
E107 E108 317-872-8400
OFFICE
D105
J J
ELECTRONIC OFFICE
CALIBRATION D104
LABORATORY
D116
CIRCUITS
ECE LAB TECH
LEARNING
LABORATORY D117
CENTER DESIGN LAB OFFICE
K D115 D101-A D101 D103 K
OFFICE
D118
STORAGE OFFICE
D116 D102
L L
INSTRUMENT
ROOM OFFICE
EQUIPMENT C114 C110
WORKSHOP/STORAGE
STORAGE
C112
C115A
DIGITAL
ELECTRONIC
MECHATRONICS OFFICE
M C111 C109 M
MICROCOMPUTER
LABORATORY
C115
OFFICE
C108
N N
P P
ELECTRICAL
STAIR
ROOM
-
B107A STORAGE
ELECTRICAL B105A
ROOM
CLASSROOM
B107
B106 ADVANCED
Q CIRCUIT Q
STUDY AREA SHEET ISSUE
- OFFICE LABORATORY
B108B B105 1 Construction Documents 04/01/21
OFFICE
B108C
OFFICE E.I.T.
B108A B103C
R R
TEST OFFICE
BUSINESS SOLDERING OFFICE
AND FINANCE ENGINEERING B103A
LAB LAB B101 OFFICE
CONFERENCE
B104 B102 B100
ROOM
OFFICE
B109
B103B
S CUSTODIAL
S
ELEV 2 CIRCULATION
STORAGE
GM ROOM - B103
B110
S10 S9 B111 S8 S7 S6 S5 S4 S3 S2 S1
T T
CIRCULATION WORKROOM / OFFICE
SERVER
OFFICE A100 BREAKROOM A105
ROOM OFFICE
9.8 A140 8.9 7.9 6.9 5.9 A100A
5.5 5.1 4.1 A102B
3.1 OFFICE 2.1 1.2
A102A
OFFICE OFFICE A103
OFFICE OFFICE OFFICE
A136 A138 ADMIN OFFICE
A124 A126 A106
A102
U WORKROOM / STORAGE U
BREAKROOM OFFICE A104B OFFICE
APPLICATIONS A122 A101 A107
ELECTRICAL
READING A118A
STORAGE
ROOM OFFICE STORAGE OFFICE ELEC. AND SAFE OFFICE OFFICE
A130 A128 A120B A118 STORAGE A104A A104
A120A A108
A101A
V CIRCULATION V
ADMIN OFFICE COPYRIGHT NOTICE: THIS ARCHITECTURAL AND ENGINEERING DRAWING IS GIVEN IN CONFIDENCE
A120 AND SHALL BE USED ONLY PURSUANT TO THE AGREEMENT WITH RATIO. NO OTHER USE,
A113 DISSEMINATION OR DUPLICATION MAY BE MADE WITHOUT PRIOR WRITTEN CONSENT OF RATIO. ALL
OFFICE COMMON LAW RIGHTS OF COPYRIGHT AND OTHERWISE ARE HEREBY SPECIFICALLY RESERVED.
OFFICE A109
OFFICE OFFICE OFFICE OFFICE OFFICE OFFICE OFFICE OFFICE OFFICE OFFICE OFFICE
A121 PROJECT NO. 19010.000
A123 A125 A127 A129 A117 A116 A115 A114 A112 A111 A110
SHEET TITLE
W W
FIRST LEVEL
EXISTING PLAN
S10 S9 S8 S7 S6 S5 S4 S3 S2 S1
4/1/2021 11:30:02 AM
AE-103
RHIT MOENCH
RENOVATION
N10 N9 N8 N7 N6 N5 N4 N3 N2 N1 5500 Wabash Avenue
Terre Haute, Indiana
A
CONFERENCE
A 47803
ROOM OFFICE OFFICE OFFICE OFFICE OFFICE OFFICE OFFICE OFFICE OFFICE OFFICE Owner
F230 F228 F226 F224 F222 F220 F218 F216 F214 F212 F210
Rose-Hulman Institute of Technology
5500 Wabash Avenue
STORAGE Terre Haute, Indiana 47803
B ADMIN OFFICE F208 B 812-877-1511
F231 BREAK AREA
USABILITY F207
LAB OFFICE
WORKROOM / F225A F206
BREAKROOM OFFICE
F233 CSSE LAB F205
CSSE LAB
C USABILITY F225 C
LAB CONTROL F217 OFFICE
ROOM F204
STAIRWELL F225B
F235 CUSTODIAL OFFICE
F237 F203 Architect
9.8 8.9 7.9 6.9 5.9 5.5 5.1 4.1 3.1 2.1 1.2
RATIO
D D 101 South Pennsylvania Street
Indianapolis, Indiana 46204
MECHANICAL 317-633-4040
N10 N9 N8 N7
ROOM N6 N5 N4 N3 CLASSROOMN2 N1
E203 E104
ELEV 1 WOMENS R.R.
E203 E202 Structural Engineer
E E Fink Roberts & Petrie, Inc.
9449 Priority Way W Dr #200
OFFICE OFFICE MECHANICAL Indianapolis, Indiana 46240
OFFICE E206 E205 ROOM 317-872-8400
E207 E201
G G
STORAGE OFFICE
OFFICE
D223A D208
D222
OFFICE OFFICE OFFICE OFFICE
OFFICE D220 D221 D209 OFFICE
D224
D223 D207
H H
STORAGE OFFICE
OFFICE D226A OFFICE
D219A
D225 STUDENT D206
OFFICE
STUDY AREA
OFFICE D219
D210
OFFICE D227 OFFICE OFFICE
D226 D219B D205
J STORAGE
J
STORAGE /
D217A OFFICE OFFICE
WORKROOM
D218 D204
OFFICE D226C OFFICE
D228 ADMIN OFFICE OFFICE D211
D229 D216 OFFICE OFFICE
D217 D203
K STORAGE
K
OFFICE OFFICE
D226D
D230 D202
CONFERENCE
OFFICE
OFFICE OFFICE D215B ROOM
OFFICE D212 OFFICE
OFFICE D232 D214 D215A
D201
D231
L L
MECHANICAL OFFICE
ROOM MECHANICAL C211
ROOM OFFICE
C215
C214 C212
OFFICE
C210
M IT CLOSET M
C200B OFFICE
STAFF C209
STUDY AREA RESOURCES
- C200
OFFICE
STORAGE C208
C200A
N N
CIRCULATION
B210
OFFICE
C216 OFFICE
C217
P P
STORAGE
MECHANICAL
W9NAA ROSE C205B
ROOM
TECH RADIO
MECHANICAL B202
CLUB
ROOM B204
B203
Q PROJECTION
Q
STUDENT
SHEET ISSUE
ROOM
CONFERENCE BBE HIVE OFFICE 1 Construction Documents 04/01/21
B111A
ROOM B201
B205
B205A
R R
SYNTHETIC
DIGITAL
BIOLOGY
SIGNAL
LABORATORY
PROCESSING
B206
LAB
B200
S S
ELEV 2
GM ROOM B208
S10 S9 B111 S8 MECHANICAL
S7 S6 S5 S4 S3 S2 S1
ROOM
B207
T T
CUSTODIAL
STORAGE MECHANICAL
OFFICE A223A ROOM
9.8 ADMIN OFFICE8.9 7.9 6.9 5.9 5.5 5.1 4.1 3.1 2.1 1.2
A218A CLASSROOM MENS R.R. A301
A218 CLASSROOM
A219 WOMENS R.R. A223 CLASSROOM
A220 A222 A202
STORAGE /
U STORAGE / STORAGE / PROJECTOR U
PROJECTOR PROJECTOR ELECTRICAL A202A
OFFICE OFFICE A219A A220A SITTING AREA ROOM OFFICE
A218C A218B - BREAKROOM A200A A201
A200 WORK AREA / OFFICE
STORAGE A203A
STORAGE CIRCULATION A203
A219B A220F
V V
OFFICE COPYRIGHT NOTICE: THIS ARCHITECTURAL AND ENGINEERING DRAWING IS GIVEN IN CONFIDENCE
AND SHALL BE USED ONLY PURSUANT TO THE AGREEMENT WITH RATIO. NO OTHER USE,
A203B DISSEMINATION OR DUPLICATION MAY BE MADE WITHOUT PRIOR WRITTEN CONSENT OF RATIO. ALL
WORKROOM COMMON LAW RIGHTS OF COPYRIGHT AND OTHERWISE ARE HEREBY SPECIFICALLY RESERVED.
OFFICE OFFICE
OFFICE OFFICE OFFICE OFFICE OFFICE OFFICE OFFICE OFFICE A207 OFFICE OFFICE
A209 OFFICE A203D
A217 A216 A215 A214 A213 A212 A211 A210 ADMIN OFFICE A206 A205 A204 OFFICE PROJECT NO. 19010.000
A208 A203C
SHEET TITLE
W W
SECOND LEVEL
EXISTING PLAN
S10 S9 S8 S7 S6 S5 S4 S3 S2 S1
4/1/2021 11:30:10 AM
AE-104
GENERAL DEMOLITION NOTES
A. THESE GENERAL DEMOLITION NOTES APPLY TO DEMOLITION DRAWINGS.
B. FIELD VERIFY CONDITIONS AND COORDINATE DEMOLITION OR REMOVAL WORK
RHIT MOENCH
WITH CORRESPONDING NEW CONSTRUCTION AND WITH APPROPRIATE TRADES
PRIOR TO STARTING DEMOLITION WORK. IF DISCREPANCIES ARE FOUND
BETWEEN CONTRACT DOCUMENTS AND ACTUAL FIELD CONDITIONS, NOTIFY
RENOVATION
ARCHITECT IMMEDIATELY.
C. OWNER WILL REMOVE LOOSE SALVAGEABLE ITEMS, I.E., EQUIPMENT, FURNITURE,
CABINETRY, FILE CABINETS, WALL-MOUNTED PROJECTION SCREENS, ARTWORK,
5500 Wabash Avenue
PLAQUES, ETC., PRIOR TO CONTRACTOR STARTING DEMOLITION WORK IN EACH
AREA. OWNER WILL STORE AND REINSTALL SUCH ITEMS. [OR] OWNER WILL STORE
MAJORITY OF LOOSE SALVAGEABLE ITEMS IN THE CENTER OF EACH ROOM
Terre Haute, Indiana
CONTAINING SAID ITEMS, I.E., EQUIPMENT, FURNITURE, CABINETRY, FILE
CABINETS, WALL-MOUNTED PROJECTION SCREENS, ARTWORK, ETC., PRIOR TO
47803
CONTRACTOR STARTING WORK. CONTRACTOR SHALL PROTECT SUCH ITEMS
DURING CONSTRUCTION. Owner
D. DEMOLISHED MATERIALS ARE THE PROPERTY OF THE CONTRACTOR UNLESS
NOTED OTHERWISE AND SHALL BE PROMPTLY DISPOSED OF OFF-SITE.
Rose-Hulman Institute of Technology
E. ITEMS NOTED TO BE REMOVED AND TURNED OVER TO OWNER SHALL BE 5500 Wabash Avenue
DELIVERED AS DIRECTED BY OWNER. Terre Haute, Indiana 47803
F. REMOVE ITEMS IN THEIR ENTIRETY UNLESS OTHERWISE INDICATED. 812-877-1511
DESCRIPTION OF PRIMARY ITEMS TO BE REMOVED IS GENERAL IN NATURE, AND
REMOVAL OF SECONDARY COMPONENTS SUCH AS BLOCKING, SUPPORTS,
ANCHORS, TRIM, ADHESIVE, PIPING, WIRING, ETC., RELATED TO PRIMARY ITEMS
SHALL BE INCLUDED.
G. PROTECT EXISTING SURFACES TO REMAIN IN AREAS ADJACENT TO DEMOLITION
WORK.
H. REPAIR FINISHES AND SURFACES LEFT EXPOSED BY DEMOLITION OR REMOVAL OF
EQUIPMENT, USING NEW MATERIALS TO MATCH SURROUNDING SURFACES.
REPAIR EXISTING FLOOR, BASE, WAINSCOT, WALL AND CEILING FINISHES TO
CORRECT DEFECTS EITHER CAUSED OR EXPOSED BY DEMOLITION WORK OR
EQUIPMENT REMOVAL. REPAIRED SURFACES SHALL BE SMOOTH AND
UNDETECTABLE UNDER FINAL FINISHES. AREAS NOTED ON THE DRAWINGS TO BE Architect
REPAIRED OR PATCHED ARE GIVEN FOR REFERENCE AND SHALL NOT BE
AD-201 INTERPRETED TO LIMIT THE SCOPE OF WORK. RATIO
I. PATCH EXISTING FLOOR, WALL, CEILING AND ROOF CONSTRUCTION AT 101 South Pennsylvania Street
ABANDONED PENETRATION LOCATIONS WITH NEW MATERIALS AS REQUIRED TO Indianapolis, Indiana 46204
A3 RECEIVE NEW FINISHES AND TO MAINTAIN ORIGINAL FIRE RATING OF ASSEMBLY 317-633-4040
WHERE APPLICABLE.
J. PORTIONS OF EXISTING MASONRY WALLS NOTED TO BE REMOVED AND OPENINGS
TO BE CUT INTO EXISTING MASONRY WALLS SHALL BE REMOVED BACK TO THE
NEAREST VERTICAL MORTAR JOINT. PROVIDE A MINIMUM BEARING OF 8 AT EACH Structural Engineer
END FOR NEW MASONRY LINTELS AND FIELD VERIFY FINAL LENGTH. ALLOW A Fink Roberts & Petrie, Inc.
07 MINIMUM OF 4 NEW MASONRY AT JAMB CONDITIONS OR END WALL CONDITIONS
OF MASONRY WALLS. REFER TO DEMOLITION PLANS FOR LOCATIONS OF WALL, 9449 Priority Way W Dr #200
FLOOR, CEILING OR ROOF OPENINGS. Indianapolis, Indiana 46240
07 K. PROVIDE SMOOTH TRANSITIONS BETWEEN FLOOR, WALL AND CEILING SURFACES 317-872-8400
07 C3 AD-201 PRIOR TO INSTALLING NEW FINISHES WHERE WALLS OR OTHER ITEMS ARE
AD-201 C6 REMOVED. FILL FLOOR VOIDS WITH CONCRETE OR MATERIAL MATCHING
07 ADJACENT MATERIALS AND LEVEL FLOOR SURFACES TO PROVIDE A SMOOTH
07 TRANSITION FROM ONE SIDE OF WALL TO THE OTHER WHERE PORTIONS OF Mechanical / Electrical Engineer
WALLS ARE REMOVED. R.E. Dimond & Associates, Inc.
07 L. ADDITIONAL FLOOR TILE MAY BE PRESENT BENEATH FINISHES IN ROOMS WITH
EXISTING FLOOR TILE OR CARPET. REMOVE ALL LAYERS OF EXISTING FLOOR 732 N Capitol Avenue
COVERINGS TO PROVIDE APPROPRIATE SUBSTRATE FOR NEW FLOOR FINISHES. Indianapolis, Indiana 46204
07 07 M. SELECTIVE DEMOLITION FOR INSTALLATION OF NEW MECHANICAL OR ELECTRICAL 317-634-4672
N.I.C. 07 WORK SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR OR TRADE
REQUIRING THE DEMOLITION. THIS INCLUDES, BUT IS NOT LIMITED TO, FLOOR
SLAB AND PAVEMENT CUTTING FOR UNDERGROUND PIPING, CORING FOR WALL
AND FLOOR PENETRATIONS, ROOF PENETRATIONS, ETC. REFER TO MECHANICAL
07 07 07
AND ELECTRICAL DRAWINGS FOR ADDITIONAL DEMOLITION INFORMATION.
N. DISCONNECT AND CAP-OFF OR REMOVE OBSOLETE EXISTING UTILITY AND
11 SERVICE LINES PRIOR TO STARTING DEMOLITION WORK.
07 08 O. REMOVE ABANDONED UNDERGROUND UTILITIES AND INSTALL ENGINEERED FILL.
P. IF EXISTING ITEMS TO BE REMOVED OR DISTURBED ARE SUSPECTED OR
07 DISCOVERED TO CONTAIN ASBESTOS OR OTHER HAZARDOUS MATERIALS, STOP
07 08 DEMOLITION AND NOTIFY OWNER AND ARCHITECT IMMEDIATELY.
07 08 07 08 Q. REPAIR AND PATCH SPRAYED FIRE-RESISTIVE AND FIRESTOP MATERIALS WHERE
DAMAGED DUE TO SELECTIVE DEMOLITION ACTIVITIES TO RESTORE ORIGINAL
FIRE RATING UNLESS OTHERWISE INDICATED.
07 R. THE FOLLOWING DEMOLITION WORK SHALL BE PERFORMED AS PART OF THE
07 08 08 07 WORK UNDER THE APPROPRIATE PROJECT MANUAL SECTIONS: A.) REMOVAL OF
EXISTING ROOFING. B.) REMOVAL OF EXISTING WINDOWS, TEMPORARY WINDOW
OPENING CLOSURES AND OPENING PREPARATION TO RECEIVE NEW WINDOW
UNITS.
07 S. REFER TO WALL SECTIONS NOTED ON DEMOLITION PLANS FOR ADDITIONAL
DEMOLITION INFORMATION.
T. REFER TO PROJECT MANUAL DIVISION 4 FOR SPECIAL REQUIREMENTS
07 08 REGARDING DISPOSAL OF DEMOLISHED MASONRY RUBBLE.
07 U. ALL WALL AND FLOOR FINISHES ARE TO REMAIN UNLESS NOTED OTHERWISE.
07
38 08
REV. 11/08/05
KEYNOTES - DEMOLITION
07 08
07
08
01 REMOVE EXISTING WALL CONSTRUCTION, DOORS AND FRAMES COMPLETELY. F
02 REMOVE EXISTING BRICK WIINDOW FILL IN IT'S ENTIRETY.
03 DUCTED FUME HOODS TO BE REMOVED BY THE HAZARDOUS MATERIAL ABATEMENT
3 G
12 07
CONTRACTOR.
04 REMOVE EXISTING BUILT-IN EQUIPMENT/CABINETRY IN IT'S ENTIRETY.
E
2
07 08 07 08
05 REMOVE EXISTING LOOSE EQUIPMENT, MACHINES, FURNITURE AND INSTALLED D
MARKERBOARDS STORE AS REQUESTED BY OWNER.
06 EXISTING WOOD FLOORING AND STRUCTURE ABOVE TO REMAIN
07 REMOVE ALL EXISTING MECHANICAL, TIE UP AND SALVAGE LIGHT FIXTURES ONLY
C
WHERE CEILING GRID REPLACEMENT OCCUR, WHERE CEILING IS TO REMAIN EXPOSED
07 08 07 08 TO DECK, ASSUME NEW MECHANICAL AND OTHER COMPONENTRY IS TO BE DRYFALL
PAINTED TO MATCH EXISTING EXPOSED STRUCTURE. WHERE CEILING IS EXPOSED
B 1
WOOD TIMBER, COLOR OF DUCTS IS TO BE DETERMINED.
07 08 REMOVE EXISTING ACOUSTICAL TILE CEILING AND SUPPORTS IN IT'S ENTIRETY. TIE UP A
07 08 07 08 AND SALVAGE LIGHT FIXTURES AS DESCRIBED IN NOTE 07. ASSUME NEW CEILING
GRID AND TILES ARE TO BE INSTALLED AND WILL CONCEAL NEW MECHANICAL
EQUIPMENT..
KEY PLAN
08 09 REMOVE EXISTING LIGHTING IN THIS SHADED AREA. REFERENCE RCP FOR CEILING IN
07 THIS AREA.
10 REMOVE EXISTING FLOORING, BASE AND WALL FINISHES IN THEIR ENTIRETY AND SEAL | DATE 04/01/21
08 PREPARE FOR NEW.
07 11 DESIGN INTENT IS TO MAINTAIN VERTICAL FACE AND UNDERSIDE OF BULKHEADS/
DRYWALL CEILINGS WHERE POSSIBLE AND PATCH TO AS-NEW CONDITION IF ANY
WORK ABOVE THE CEILING IS REQUIRED, IN LIEU OF REBUILDING IF ANY LIGHT
FIXTURES EXIST, SALVAGE AND REUSED IN PATCHED CEILING IF POSSIBLE..
12 REMOVE EXISTING DRYWALL CEILING AND SUPPORTS. REFERENCE RCP FOR FINAL
DESIGN INTENT. IF IN EXISTENCE, WALL SCONCES ARE TO REMAIN.. IF CEILING
07 LIGHTS EXIST, SALVAGE FOR REUSE IN NEW CEILING UNLESS SHOWN OTHERWISE IN
NEW CEILING PLAN..
13 EXISTING TO REMAIN.
08 07
14 REMOVE HORIZONTAL PORTION OF HARDLID CEILINGS FOR HVAC WORK. REMOVE
WOOD PANELING IN CEILINGS. EXISTING STEPPED COFFER, DRYWALL WRAPPED
08 TRUSSES AND VERTICAL PORTIONS OF HARDLID CEILINGS TO REMAIN FOR REUSE.
38 07 07 15 REMOVE EXISTING CERAMIC TILE ON WALLS AND FLOOR IN ITS ENTIRETY.
SHEET ISSUE
16 REMOVE EXISTING LEVEL 2 BRIDGE CONSTRUCTION AND RAILING IN ITS ENTIRETY TO
CREATE OPENING TO BELOW 1 Construction Documents 04/01/21
07 07 17 CAREFULLY SALVAGE ACOUSTICAL PANELS MOUNTED TO WALLS FOR POSSIBLE
08
REUSE BY OWNER. VERIFY RELOCATION DIRECTION WITH OWNER.
07 18 WALLS N THIS AREA REPRESENT TEMPORARY OFFICES CREATED IN INTIAL PHASE OF
CONSTRUCTION. THESE ARE TO BE REMOVED, ALONG WITH CEILINGS AND FINISHES
29 AT CORRECT PHASE TO CONVERT THESE ROOMS TO CLASSROOMS. EXISTING
CEILINGS CAN REMAIN AND LIGHTING RECONFIGURED DURING TEMPORARY OFFICE
N.I.C.
PHASE AND ALL IS TO BE REMOVED FOR FINAL CLASSROOM PHASE.
19 REMOVE EXISTING GLAZING AND FRAMING AS REQUIRED TO ACCEPT NEW
MECHANICAL LOUVER.
07 07
08 20 REMOVE EXISTING WINDOWS AND FRAMES IN THEIR ENTIRETY.
08 21 REMOVE SECTION OF EXISTING WOOD FLOOR AND STRUCTURE-COORDINATE WITH
07
STRUCTURAL.
07 08 22 REMOVE EXISTING SKYLIGHT FRAME, GLAZING, AND ACCESSORIES DOWN TO EXISTING
CURB IN ENTIRETY.
23 REMOVE EXISTING ROOF DUCT CHASE, FRAMING, AND ROOFING IN ENTIRETY.
24 REMOVE EXISTING ROOFING, INSULATION, AND CRICKET MATERIAL IN ENTIRETY TO
RECEIVE NEW ROOF AND FLASHINGS.
25 REMOVE EXISTING METAL LADDER, PLATFORM, AND SUPPORTS COMPLETE.
26 REMOVE EXISTING DOOR PANEL AND HARDWARE AT TOP OF PLATFORM, FRAME TO
REMAIN.
27 REMOVE EXISTING CONCRETE HOUSEKEEPING PAD FLUSH TO SURROUNDING FLOOR
ELEVATION TO RECEIVE NEW HOUSEKEEPING PAD.
29 EXISTING CEILING AND LIGHTING ARE NEWLY CONSTRUCTED AT TIME OF ACADEMIC
BUILDING CONSTRUCTION. EXISTING TO REMAIN WITHOUT DISRUPTION IF POSSIBLE.
IF NOT POSSIBLE, ASSUME NARRATIVE FROM 07 AND 08 TO BE APPLIED TO THIS AREA.
30 ALTERNATE BID # A-2: REPLACE EXISTING LINEAR PENDANT WITH NEW SPECIALTY
LIGHTING FOR LIVING WALL PER ELECTRICAL LIGHTING PLANS
31 EXISTING CEILING AND LIGHTING ARE NEWLY CONSTRUCTED AT TIME OF 2020
SUMMER CONSTRUCTION. AS MUCH OF EXISTING CENTER PORTION TO REMAIN
WITHOUT DISRUPTION IF POSSIBLE.
33 REMOVE EXISTING SKYLIGHT AND LIGHTING. REFERENCE ARCHITECTURAL AND
B5 LOWER LEVEL 2 DEMOLITION PLAN DETAILED SECTIONS FOR ARCHITECTURAL DESIGN INTENT TO DETERMINE EXTENT OF
DEMOLITION.
COPYRIGHT NOTICE: THIS ARCHITECTURAL AND ENGINEERING DRAWING IS GIVEN IN CONFIDENCE
AD-111 AND SHALL BE USED ONLY PURSUANT TO THE AGREEMENT WITH RATIO. NO OTHER USE,
1/16" = 1'-0" 34 FLOORING TO REMAIN AT STAIRS. REMOVE EXISTING DISPLAY PILASTERS UNDER
DISSEMINATION OR DUPLICATION MAY BE MADE WITHOUT PRIOR WRITTEN CONSENT OF RATIO. ALL
COMMON LAW RIGHTS OF COPYRIGHT AND OTHERWISE ARE HEREBY SPECIFICALLY RESERVED.
STAIRS.
35 REMOVE ALL EXISTING CEILING, LIGHTING, REMAINING WALL FINISHES AND FLOOR PROJECT NO. 19010.000
FINISHES. PREP AREA FOR NEW CEILING, FINISHES, HVAC AND FLOOR PLAN LAYOUT
AS NEEDED. SHEET TITLE
36 REMOVE SECTION OF EXISTING WOOD FLOOR AND STRUCTURE-COORDINATE WITH
STRUCTURAL. REMOVE EXSTING LIGHTING IN THIS AREA. LOWER LEVEL 2
37 INVESTIGATE CONSTRUCTION OF THIS HORIZONTAL BEAM TO DETERMINE FEASIBILITY
OF REMOVING BOTTOM FURRING STRIPS AND RECONSTRUCTION TO MATCH HEIGHT
OF HORIZONTAL BEAM TO
DEMOLITION PLAN
38 PROVIDE ALT. BID NO A-5 TO REMOVE EXISITNG QUARRY TILE ON STAIRS AND
4/1/2021 11:29:00 AM
PREPARE FOR NEW TREADS, RISERS, LANDING AND STRINGERS AS REQUIRED PER
THE FINISH PLANS. THIS INCLUDES REMOVAL OF PEDESTALS ON LEVEL 1.
39 REMOVE ROOFING, INSULATION, AND STRUCTURE AS REQUIRED FOR NEW ROOF
HATCH.
40 SELECTIVELY DEMO AS REQUIRED FOR HVAC WORK. IF FLOORING ABOVE IS SHEET NUMBER
AFFECTED, CAREFULLY SALVAGE FLOORING FOR REINSTALLATION AFTER HVAC WORK
AD-111
IS COMPLETE.
41 SELECTIVELY DEMO BEHIND COLUMNS TO ALLOW FOR FULL PENETRATION WELDING
OF COLUMN STUBS.
GENERAL DEMOLITION NOTES
A. THESE GENERAL DEMOLITION NOTES APPLY TO DEMOLITION DRAWINGS.
B. FIELD VERIFY CONDITIONS AND COORDINATE DEMOLITION OR REMOVAL WORK
RHIT MOENCH
WITH CORRESPONDING NEW CONSTRUCTION AND WITH APPROPRIATE TRADES
PRIOR TO STARTING DEMOLITION WORK. IF DISCREPANCIES ARE FOUND
BETWEEN CONTRACT DOCUMENTS AND ACTUAL FIELD CONDITIONS, NOTIFY
RENOVATION
ARCHITECT IMMEDIATELY.
AD-201
C. OWNER WILL REMOVE LOOSE SALVAGEABLE ITEMS, I.E., EQUIPMENT, FURNITURE,
CABINETRY, FILE CABINETS, WALL-MOUNTED PROJECTION SCREENS, ARTWORK,
5500 Wabash Avenue
02 02 02
A3
PLAQUES, ETC., PRIOR TO CONTRACTOR STARTING DEMOLITION WORK IN EACH
AREA. OWNER WILL STORE AND REINSTALL SUCH ITEMS. [OR] OWNER WILL STORE
MAJORITY OF LOOSE SALVAGEABLE ITEMS IN THE CENTER OF EACH ROOM
Terre Haute, Indiana
CONTAINING SAID ITEMS, I.E., EQUIPMENT, FURNITURE, CABINETRY, FILE
CABINETS, WALL-MOUNTED PROJECTION SCREENS, ARTWORK, ETC., PRIOR TO
47803
CONTRACTOR STARTING WORK. CONTRACTOR SHALL PROTECT SUCH ITEMS
01 DURING CONSTRUCTION. Owner
03
D. DEMOLISHED MATERIALS ARE THE PROPERTY OF THE CONTRACTOR UNLESS
01 35
04 05 03 NOTED OTHERWISE AND SHALL BE PROMPTLY DISPOSED OF OFF-SITE.
Rose-Hulman Institute of Technology
35 05 05 05 35 01 35 04 01 E. ITEMS NOTED TO BE REMOVED AND TURNED OVER TO OWNER SHALL BE 5500 Wabash Avenue
DELIVERED AS DIRECTED BY OWNER. Terre Haute, Indiana 47803
02 01 01 F. REMOVE ITEMS IN THEIR ENTIRETY UNLESS OTHERWISE INDICATED. 812-877-1511
01
05 05 03 N.I.C. C3 AD-201 DESCRIPTION OF PRIMARY ITEMS TO BE REMOVED IS GENERAL IN NATURE, AND
05 REMOVAL OF SECONDARY COMPONENTS SUCH AS BLOCKING, SUPPORTS,
35 35 AD-201 C6
35 01 ANCHORS, TRIM, ADHESIVE, PIPING, WIRING, ETC., RELATED TO PRIMARY ITEMS
05 SHALL BE INCLUDED.
35 05 04 05 05
35 G. PROTECT EXISTING SURFACES TO REMAIN IN AREAS ADJACENT TO DEMOLITION
01 01 01 35 01 01 35 WORK.
35 05 35 05 H. REPAIR FINISHES AND SURFACES LEFT EXPOSED BY DEMOLITION OR REMOVAL OF
35 05 EQUIPMENT, USING NEW MATERIALS TO MATCH SURROUNDING SURFACES.
01 35 05
35 35 05 35 REPAIR EXISTING FLOOR, BASE, WAINSCOT, WALL AND CEILING FINISHES TO
05 05 01 35 35 CORRECT DEFECTS EITHER CAUSED OR EXPOSED BY DEMOLITION WORK OR
N.I.C. 10
07 EQUIPMENT REMOVAL. REPAIRED SURFACES SHALL BE SMOOTH AND
07 10 UNDETECTABLE UNDER FINAL FINISHES. AREAS NOTED ON THE DRAWINGS TO BE
01 Architect
05 01 35 01 REPAIRED OR PATCHED ARE GIVEN FOR REFERENCE AND SHALL NOT BE
05 INTERPRETED TO LIMIT THE SCOPE OF WORK. RATIO
05 I. PATCH EXISTING FLOOR, WALL, CEILING AND ROOF CONSTRUCTION AT
35 05 01 101 South Pennsylvania Street
35 35 ABANDONED PENETRATION LOCATIONS WITH NEW MATERIALS AS REQUIRED TO
35 17 10 07 Indianapolis, Indiana 46204
05
07 10 11 10 07 07 07 RECEIVE NEW FINISHES AND TO MAINTAIN ORIGINAL FIRE RATING OF ASSEMBLY 317-633-4040
01 35 WHERE APPLICABLE.
09 J. PORTIONS OF EXISTING MASONRY WALLS NOTED TO BE REMOVED AND OPENINGS
05 05 01 TO BE CUT INTO EXISTING MASONRY WALLS SHALL BE REMOVED BACK TO THE
05 01 07 NEAREST VERTICAL MORTAR JOINT. PROVIDE A MINIMUM BEARING OF 8 AT EACH Structural Engineer
05 05 35 35
35 END FOR NEW MASONRY LINTELS AND FIELD VERIFY FINAL LENGTH. ALLOW A Fink Roberts & Petrie, Inc.
35 01 01 01
35 MINIMUM OF 4 NEW MASONRY AT JAMB CONDITIONS OR END WALL CONDITIONS
04 05 09 OF MASONRY WALLS. REFER TO DEMOLITION PLANS FOR LOCATIONS OF WALL, 9449 Priority Way W Dr #200
05 10 07 10 01 07 05 FLOOR, CEILING OR ROOF OPENINGS. Indianapolis, Indiana 46240
17 08 10 K. PROVIDE SMOOTH TRANSITIONS BETWEEN FLOOR, WALL AND CEILING SURFACES 317-872-8400
04 01 PRIOR TO INSTALLING NEW FINISHES WHERE WALLS OR OTHER ITEMS ARE
01 REMOVED. FILL FLOOR VOIDS WITH CONCRETE OR MATERIAL MATCHING
11 ADJACENT MATERIALS AND LEVEL FLOOR SURFACES TO PROVIDE A SMOOTH
01 37 TRANSITION FROM ONE SIDE OF WALL TO THE OTHER WHERE PORTIONS OF Mechanical / Electrical Engineer
07
09 10
10 09 10 12 12 WALLS ARE REMOVED. R.E. Dimond & Associates, Inc.
07 L. ADDITIONAL FLOOR TILE MAY BE PRESENT BENEATH FINISHES IN ROOMS WITH
EXISTING FLOOR TILE OR CARPET. REMOVE ALL LAYERS OF EXISTING FLOOR 732 N Capitol Avenue
34 38 38 34 Indianapolis, Indiana 46204
12 12 COVERINGS TO PROVIDE APPROPRIATE SUBSTRATE FOR NEW FLOOR FINISHES.
M. SELECTIVE DEMOLITION FOR INSTALLATION OF NEW MECHANICAL OR ELECTRICAL 317-634-4672
17 10 WORK SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR OR TRADE
REQUIRING THE DEMOLITION. THIS INCLUDES, BUT IS NOT LIMITED TO, FLOOR
SLAB AND PAVEMENT CUTTING FOR UNDERGROUND PIPING, CORING FOR WALL
AND FLOOR PENETRATIONS, ROOF PENETRATIONS, ETC. REFER TO MECHANICAL
07 07 07 07 07 07 07 AND ELECTRICAL DRAWINGS FOR ADDITIONAL DEMOLITION INFORMATION.
08 08 08 08 08 08 08 N. DISCONNECT AND CAP-OFF OR REMOVE OBSOLETE EXISTING UTILITY AND
07 SERVICE LINES PRIOR TO STARTING DEMOLITION WORK.
06 O. REMOVE ABANDONED UNDERGROUND UTILITIES AND INSTALL ENGINEERED FILL.
07 P. IF EXISTING ITEMS TO BE REMOVED OR DISTURBED ARE SUSPECTED OR
DISCOVERED TO CONTAIN ASBESTOS OR OTHER HAZARDOUS MATERIALS, STOP
11 08
DEMOLITION AND NOTIFY OWNER AND ARCHITECT IMMEDIATELY.
07 Q. REPAIR AND PATCH SPRAYED FIRE-RESISTIVE AND FIRESTOP MATERIALS WHERE
08 07 07 07 07 07 DAMAGED DUE TO SELECTIVE DEMOLITION ACTIVITIES TO RESTORE ORIGINAL
07 08 08 FIRE RATING UNLESS OTHERWISE INDICATED.
08 08
08 R. THE FOLLOWING DEMOLITION WORK SHALL BE PERFORMED AS PART OF THE
WORK UNDER THE APPROPRIATE PROJECT MANUAL SECTIONS: A.) REMOVAL OF
EXISTING ROOFING. B.) REMOVAL OF EXISTING WINDOWS, TEMPORARY WINDOW
07 OPENING CLOSURES AND OPENING PREPARATION TO RECEIVE NEW WINDOW
UNITS.
08 07 07 07 S. REFER TO WALL SECTIONS NOTED ON DEMOLITION PLANS FOR ADDITIONAL
08 08 06 08 DEMOLITION INFORMATION.
07 07 T. REFER TO PROJECT MANUAL DIVISION 4 FOR SPECIAL REQUIREMENTS
07 REGARDING DISPOSAL OF DEMOLISHED MASONRY RUBBLE.
08
07 07 U. ALL WALL AND FLOOR FINISHES ARE TO REMAIN UNLESS NOTED OTHERWISE.
08 11 11 08
REV. 11/08/05
07
07
08 07
08 KEYNOTES - DEMOLITION
07 08
08
07
08
06 01 07 08 01 REMOVE EXISTING WALL CONSTRUCTION, DOORS AND FRAMES COMPLETELY. F
07
07 08
07 02 REMOVE EXISTING BRICK WIINDOW FILL IN IT'S ENTIRETY.
03 DUCTED FUME HOODS TO BE REMOVED BY THE HAZARDOUS MATERIAL ABATEMENT
3 G
08
07
08
12 12 11
11 12
CONTRACTOR.
04 REMOVE EXISTING BUILT-IN EQUIPMENT/CABINETRY IN IT'S ENTIRETY.
E
2
11 05 REMOVE EXISTING LOOSE EQUIPMENT, MACHINES, FURNITURE AND INSTALLED D
11 MARKERBOARDS STORE AS REQUESTED BY OWNER.
06 EXISTING WOOD FLOORING AND STRUCTURE ABOVE TO REMAIN
06 C
07 07 07 38 07 REMOVE ALL EXISTING MECHANICAL, TIE UP AND SALVAGE LIGHT FIXTURES ONLY
07 07
08 08 08 WHERE CEILING GRID REPLACEMENT OCCUR, WHERE CEILING IS TO REMAIN EXPOSED
11 11
TO DECK, ASSUME NEW MECHANICAL AND OTHER COMPONENTRY IS TO BE DRYFALL
PAINTED TO MATCH EXISTING EXPOSED STRUCTURE. WHERE CEILING IS EXPOSED
B 1
11
1/8"
WOOD TIMBER, COLOR OF DUCTS IS TO BE DETERMINED.
12 12 11 12 08 REMOVE EXISTING ACOUSTICAL TILE CEILING AND SUPPORTS IN IT'S ENTIRETY. TIE UP A
11 07 AND SALVAGE LIGHT FIXTURES AS DESCRIBED IN NOTE 07. ASSUME NEW CEILING
07 GRID AND TILES ARE TO BE INSTALLED AND WILL CONCEAL NEW MECHANICAL
08 07
08 EQUIPMENT..
07 08
07 08 08 N.I.C. KEY PLAN
06 09 REMOVE EXISTING LIGHTING IN THIS SHADED AREA. REFERENCE RCP FOR CEILING IN
THIS AREA.
07
11 11 11 11 10 REMOVE EXISTING FLOORING, BASE AND WALL FINISHES IN THEIR ENTIRETY AND SEAL | DATE 04/01/21
PREPARE FOR NEW.
11 07 08 07 08
07 08 11 DESIGN INTENT IS TO MAINTAIN VERTICAL FACE AND UNDERSIDE OF BULKHEADS/
07 DRYWALL CEILINGS WHERE POSSIBLE AND PATCH TO AS-NEW CONDITION IF ANY
01 08 WORK ABOVE THE CEILING IS REQUIRED, IN LIEU OF REBUILDING IF ANY LIGHT
07 07 07 07 FIXTURES EXIST, SALVAGE AND REUSED IN PATCHED CEILING IF POSSIBLE..
12 REMOVE EXISTING DRYWALL CEILING AND SUPPORTS. REFERENCE RCP FOR FINAL
11 DESIGN INTENT. IF IN EXISTENCE, WALL SCONCES ARE TO REMAIN.. IF CEILING
LIGHTS EXIST, SALVAGE FOR REUSE IN NEW CEILING UNLESS SHOWN OTHERWISE IN
07 07 NEW CEILING PLAN..
06 07 13 EXISTING TO REMAIN.
07 08 08
07 08 08 07 14 REMOVE HORIZONTAL PORTION OF HARDLID CEILINGS FOR HVAC WORK. REMOVE
08 WOOD PANELING IN CEILINGS. EXISTING STEPPED COFFER, DRYWALL WRAPPED
TRUSSES AND VERTICAL PORTIONS OF HARDLID CEILINGS TO REMAIN FOR REUSE.
07 11 15 REMOVE EXISTING CERAMIC TILE ON WALLS AND FLOOR IN ITS ENTIRETY.
08 SHEET ISSUE
16 REMOVE EXISTING LEVEL 2 BRIDGE CONSTRUCTION AND RAILING IN ITS ENTIRETY TO
CREATE OPENING TO BELOW 1 Construction Documents 04/01/21
07 08 07 08 07 17 CAREFULLY SALVAGE ACOUSTICAL PANELS MOUNTED TO WALLS FOR POSSIBLE
07 08 07 REUSE BY OWNER. VERIFY RELOCATION DIRECTION WITH OWNER.
08
08 18 WALLS N THIS AREA REPRESENT TEMPORARY OFFICES CREATED IN INTIAL PHASE OF
11 CONSTRUCTION. THESE ARE TO BE REMOVED, ALONG WITH CEILINGS AND FINISHES
07 08 11
AT CORRECT PHASE TO CONVERT THESE ROOMS TO CLASSROOMS. EXISTING
07 CEILINGS CAN REMAIN AND LIGHTING RECONFIGURED DURING TEMPORARY OFFICE
07 PHASE AND ALL IS TO BE REMOVED FOR FINAL CLASSROOM PHASE.
08 07
06 07 08 07 19 REMOVE EXISTING GLAZING AND FRAMING AS REQUIRED TO ACCEPT NEW
07 08 08
08 MECHANICAL LOUVER.
07
20 REMOVE EXISTING WINDOWS AND FRAMES IN THEIR ENTIRETY.
11 21 REMOVE SECTION OF EXISTING WOOD FLOOR AND STRUCTURE-COORDINATE WITH
STRUCTURAL.
12 12 11 07 07
22 REMOVE EXISTING SKYLIGHT FRAME, GLAZING, AND ACCESSORIES DOWN TO EXISTING
CURB IN ENTIRETY.
07 38 23 REMOVE EXISTING ROOF DUCT CHASE, FRAMING, AND ROOFING IN ENTIRETY.
11
07 08 07 08 07 08 24 REMOVE EXISTING ROOFING, INSULATION, AND CRICKET MATERIAL IN ENTIRETY TO
07 12 RECEIVE NEW ROOF AND FLASHINGS.
07
25 REMOVE EXISTING METAL LADDER, PLATFORM, AND SUPPORTS COMPLETE.
26 REMOVE EXISTING DOOR PANEL AND HARDWARE AT TOP OF PLATFORM, FRAME TO
07 REMAIN.
07 27 REMOVE EXISTING CONCRETE HOUSEKEEPING PAD FLUSH TO SURROUNDING FLOOR
ELEVATION TO RECEIVE NEW HOUSEKEEPING PAD.
07 29 EXISTING CEILING AND LIGHTING ARE NEWLY CONSTRUCTED AT TIME OF ACADEMIC
BUILDING CONSTRUCTION. EXISTING TO REMAIN WITHOUT DISRUPTION IF POSSIBLE.
IF NOT POSSIBLE, ASSUME NARRATIVE FROM 07 AND 08 TO BE APPLIED TO THIS AREA.
30 ALTERNATE BID # A-2: REPLACE EXISTING LINEAR PENDANT WITH NEW SPECIALTY
LIGHTING FOR LIVING WALL PER ELECTRICAL LIGHTING PLANS
31 EXISTING CEILING AND LIGHTING ARE NEWLY CONSTRUCTED AT TIME OF 2020
SUMMER CONSTRUCTION. AS MUCH OF EXISTING CENTER PORTION TO REMAIN
WITHOUT DISRUPTION IF POSSIBLE.
33 REMOVE EXISTING SKYLIGHT AND LIGHTING. REFERENCE ARCHITECTURAL AND
DETAILED SECTIONS FOR ARCHITECTURAL DESIGN INTENT TO DETERMINE EXTENT OF
COPYRIGHT NOTICE: THIS ARCHITECTURAL AND ENGINEERING DRAWING IS GIVEN IN CONFIDENCE
DEMOLITION. AND SHALL BE USED ONLY PURSUANT TO THE AGREEMENT WITH RATIO. NO OTHER USE,
DISSEMINATION OR DUPLICATION MAY BE MADE WITHOUT PRIOR WRITTEN CONSENT OF RATIO. ALL
34 FLOORING TO REMAIN AT STAIRS. REMOVE EXISTING DISPLAY PILASTERS UNDER COMMON LAW RIGHTS OF COPYRIGHT AND OTHERWISE ARE HEREBY SPECIFICALLY RESERVED.
STAIRS.
35 REMOVE ALL EXISTING CEILING, LIGHTING, REMAINING WALL FINISHES AND FLOOR PROJECT NO. 19010.000
FINISHES. PREP AREA FOR NEW CEILING, FINISHES, HVAC AND FLOOR PLAN LAYOUT
AS NEEDED. SHEET TITLE
36 REMOVE SECTION OF EXISTING WOOD FLOOR AND STRUCTURE-COORDINATE WITH
STRUCTURAL. REMOVE EXSTING LIGHTING IN THIS AREA.
37 INVESTIGATE CONSTRUCTION OF THIS HORIZONTAL BEAM TO DETERMINE FEASIBILITY
LOWER LEVEL 1
OF REMOVING BOTTOM FURRING STRIPS AND RECONSTRUCTION TO MATCH HEIGHT
OF HORIZONTAL BEAM TO
DEMOLITION PLAN
A5 LOWER LEVEL 1 DEMOLITION PLAN 38 PROVIDE ALT. BID NO A-5 TO REMOVE EXISITNG QUARRY TILE ON STAIRS AND
PREPARE FOR NEW TREADS, RISERS, LANDING AND STRINGERS AS REQUIRED PER
4/1/2021 11:29:09 AM
AD-112
1/16" = 1'-0" THE FINISH PLANS. THIS INCLUDES REMOVAL OF PEDESTALS ON LEVEL 1.
39 REMOVE ROOFING, INSULATION, AND STRUCTURE AS REQUIRED FOR NEW ROOF
HATCH.
40 SELECTIVELY DEMO AS REQUIRED FOR HVAC WORK. IF FLOORING ABOVE IS SHEET NUMBER
AFFECTED, CAREFULLY SALVAGE FLOORING FOR REINSTALLATION AFTER HVAC WORK
AD-112
IS COMPLETE.
41 SELECTIVELY DEMO BEHIND COLUMNS TO ALLOW FOR FULL PENETRATION WELDING
OF COLUMN STUBS.
GENERAL DEMOLITION NOTES
A. THESE GENERAL DEMOLITION NOTES APPLY TO DEMOLITION DRAWINGS.
B. FIELD VERIFY CONDITIONS AND COORDINATE DEMOLITION OR REMOVAL WORK
RHIT MOENCH
WITH CORRESPONDING NEW CONSTRUCTION AND WITH APPROPRIATE TRADES
PRIOR TO STARTING DEMOLITION WORK. IF DISCREPANCIES ARE FOUND
BETWEEN CONTRACT DOCUMENTS AND ACTUAL FIELD CONDITIONS, NOTIFY
RENOVATION
ARCHITECT IMMEDIATELY.
AD-201
C. OWNER WILL REMOVE LOOSE SALVAGEABLE ITEMS, I.E., EQUIPMENT, FURNITURE,
CABINETRY, FILE CABINETS, WALL-MOUNTED PROJECTION SCREENS, ARTWORK,
5500 Wabash Avenue
02 02 02
A3
02 02 PLAQUES, ETC., PRIOR TO CONTRACTOR STARTING DEMOLITION WORK IN EACH
AREA. OWNER WILL STORE AND REINSTALL SUCH ITEMS. [OR] OWNER WILL STORE
MAJORITY OF LOOSE SALVAGEABLE ITEMS IN THE CENTER OF EACH ROOM
Terre Haute, Indiana
CONTAINING SAID ITEMS, I.E., EQUIPMENT, FURNITURE, CABINETRY, FILE
CABINETS, WALL-MOUNTED PROJECTION SCREENS, ARTWORK, ETC., PRIOR TO
47803
03 03 03 CONTRACTOR STARTING WORK. CONTRACTOR SHALL PROTECT SUCH ITEMS
03 DURING CONSTRUCTION. Owner
04 01 01
D. DEMOLISHED MATERIALS ARE THE PROPERTY OF THE CONTRACTOR UNLESS
04 07 04 NOTED OTHERWISE AND SHALL BE PROMPTLY DISPOSED OF OFF-SITE.
Rose-Hulman Institute of Technology
05 5500 Wabash Avenue
05 35 05 04 01 E. ITEMS NOTED TO BE REMOVED AND TURNED OVER TO OWNER SHALL BE
18 18 18 18 35
35 35 05 02 DELIVERED AS DIRECTED BY OWNER. Terre Haute, Indiana 47803
02 F. REMOVE ITEMS IN THEIR ENTIRETY UNLESS OTHERWISE INDICATED. 812-877-1511
35 04
18 18 18 18 C3 AD-201 DESCRIPTION OF PRIMARY ITEMS TO BE REMOVED IS GENERAL IN NATURE, AND
07 05 REMOVAL OF SECONDARY COMPONENTS SUCH AS BLOCKING, SUPPORTS,
AD-201 C6
35 04 01 35 35 ANCHORS, TRIM, ADHESIVE, PIPING, WIRING, ETC., RELATED TO PRIMARY ITEMS
18 04
SHALL BE INCLUDED.
18 18 18 05 05
18 18 01 G. PROTECT EXISTING SURFACES TO REMAIN IN AREAS ADJACENT TO DEMOLITION
18 18 35 35 35 03 WORK.
H. REPAIR FINISHES AND SURFACES LEFT EXPOSED BY DEMOLITION OR REMOVAL OF
01 35 05 N.I.C. EQUIPMENT, USING NEW MATERIALS TO MATCH SURROUNDING SURFACES.
01 01 35 REPAIR EXISTING FLOOR, BASE, WAINSCOT, WALL AND CEILING FINISHES TO
N.I.C.
01 CORRECT DEFECTS EITHER CAUSED OR EXPOSED BY DEMOLITION WORK OR
01 35 35 EQUIPMENT REMOVAL. REPAIRED SURFACES SHALL BE SMOOTH AND
8'-1 3/4"
35 35 01 35 01 01 UNDETECTABLE UNDER FINAL FINISHES. AREAS NOTED ON THE DRAWINGS TO BE Architect
35 04 05 35 REPAIRED OR PATCHED ARE GIVEN FOR REFERENCE AND SHALL NOT BE
05 05 35 05 05 INTERPRETED TO LIMIT THE SCOPE OF WORK. RATIO
04 01
I. PATCH EXISTING FLOOR, WALL, CEILING AND ROOF CONSTRUCTION AT 101 South Pennsylvania Street
05 ABANDONED PENETRATION LOCATIONS WITH NEW MATERIALS AS REQUIRED TO Indianapolis, Indiana 46204
07
35 12 12 RECEIVE NEW FINISHES AND TO MAINTAIN ORIGINAL FIRE RATING OF ASSEMBLY 317-633-4040
17 WHERE APPLICABLE.
01
07 31 11 J. PORTIONS OF EXISTING MASONRY WALLS NOTED TO BE REMOVED AND OPENINGS
04 08 08 TO BE CUT INTO EXISTING MASONRY WALLS SHALL BE REMOVED BACK TO THE
17 01 07 Structural Engineer
05 NEAREST VERTICAL MORTAR JOINT. PROVIDE A MINIMUM BEARING OF 8 AT EACH
35 07 01 08 END FOR NEW MASONRY LINTELS AND FIELD VERIFY FINAL LENGTH. ALLOW A Fink Roberts & Petrie, Inc.
01 MINIMUM OF 4 NEW MASONRY AT JAMB CONDITIONS OR END WALL CONDITIONS
08 07 12 OPEN TO 9449 Priority Way W Dr #200
OF MASONRY WALLS. REFER TO DEMOLITION PLANS FOR LOCATIONS OF WALL,
08 01 LEVEL 2 FLOOR, CEILING OR ROOF OPENINGS. Indianapolis, Indiana 46240
04 07 CEILING 317-872-8400
K. PROVIDE SMOOTH TRANSITIONS BETWEEN FLOOR, WALL AND CEILING SURFACES
OPEN FROM LL1 08
05 PRIOR TO INSTALLING NEW FINISHES WHERE WALLS OR OTHER ITEMS ARE
THROUGH LEVEL 2 REMOVED. FILL FLOOR VOIDS WITH CONCRETE OR MATERIAL MATCHING
35
07 ADJACENT MATERIALS AND LEVEL FLOOR SURFACES TO PROVIDE A SMOOTH
TRANSITION FROM ONE SIDE OF WALL TO THE OTHER WHERE PORTIONS OF Mechanical / Electrical Engineer
07 08
WALLS ARE REMOVED. R.E. Dimond & Associates, Inc.
L. ADDITIONAL FLOOR TILE MAY BE PRESENT BENEATH FINISHES IN ROOMS WITH
EXISTING FLOOR TILE OR CARPET. REMOVE ALL LAYERS OF EXISTING FLOOR 732 N Capitol Avenue
38 38 11 31 11 COVERINGS TO PROVIDE APPROPRIATE SUBSTRATE FOR NEW FLOOR FINISHES. Indianapolis, Indiana 46204
07 08 M. SELECTIVE DEMOLITION FOR INSTALLATION OF NEW MECHANICAL OR ELECTRICAL 317-634-4672
17 WORK SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR OR TRADE
REQUIRING THE DEMOLITION. THIS INCLUDES, BUT IS NOT LIMITED TO, FLOOR
SLAB AND PAVEMENT CUTTING FOR UNDERGROUND PIPING, CORING FOR WALL
11 AND FLOOR PENETRATIONS, ROOF PENETRATIONS, ETC. REFER TO MECHANICAL
07 08 07 07
AND ELECTRICAL DRAWINGS FOR ADDITIONAL DEMOLITION INFORMATION.
07 08 08
N. DISCONNECT AND CAP-OFF OR REMOVE OBSOLETE EXISTING UTILITY AND
08 SERVICE LINES PRIOR TO STARTING DEMOLITION WORK.
07 O. REMOVE ABANDONED UNDERGROUND UTILITIES AND INSTALL ENGINEERED FILL.
07 08 06 07
08 07 08 07 08 P. IF EXISTING ITEMS TO BE REMOVED OR DISTURBED ARE SUSPECTED OR
OPEN TO 07 07 01 08 DISCOVERED TO CONTAIN ASBESTOS OR OTHER HAZARDOUS MATERIALS, STOP
LEVEL 2 08 DEMOLITION AND NOTIFY OWNER AND ARCHITECT IMMEDIATELY.
CEILING 08 07 Q. REPAIR AND PATCH SPRAYED FIRE-RESISTIVE AND FIRESTOP MATERIALS WHERE
07 11 08 DAMAGED DUE TO SELECTIVE DEMOLITION ACTIVITIES TO RESTORE ORIGINAL
07 FIRE RATING UNLESS OTHERWISE INDICATED.
07 08 11 11 08 R. THE FOLLOWING DEMOLITION WORK SHALL BE PERFORMED AS PART OF THE
WORK UNDER THE APPROPRIATE PROJECT MANUAL SECTIONS: A.) REMOVAL OF
EXISTING ROOFING. B.) REMOVAL OF EXISTING WINDOWS, TEMPORARY WINDOW
11
OPENING CLOSURES AND OPENING PREPARATION TO RECEIVE NEW WINDOW
06 UNITS.
07
S. REFER TO WALL SECTIONS NOTED ON DEMOLITION PLANS FOR ADDITIONAL
07 08 DEMOLITION INFORMATION.
DESIGN LAB
T. REFER TO PROJECT MANUAL DIVISION 4 FOR SPECIAL REQUIREMENTS
07 08 D101 REGARDING DISPOSAL OF DEMOLISHED MASONRY RUBBLE.
07 08
08 U. ALL WALL AND FLOOR FINISHES ARE TO REMAIN UNLESS NOTED OTHERWISE.
08 01 07
OPEN TO 07
LEVEL 2 07 01 08
07 08 REV. 11/08/05
CEILING 07 08
01 08
08 07 KEYNOTES - DEMOLITION
07
07 08
11
01
07 01 REMOVE EXISTING WALL CONSTRUCTION, DOORS AND FRAMES COMPLETELY.
07 08 01 F
08
06
07
07
01 08
MECHATRONICS
C111
08 02 REMOVE EXISTING BRICK WIINDOW FILL IN IT'S ENTIRETY.
03 DUCTED FUME HOODS TO BE REMOVED BY THE HAZARDOUS MATERIAL ABATEMENT
3 G
07 08
07
01 07 08
CONTRACTOR.
04 REMOVE EXISTING BUILT-IN EQUIPMENT/CABINETRY IN IT'S ENTIRETY.
E
2
07
OPEN TO 05 REMOVE EXISTING LOOSE EQUIPMENT, MACHINES, FURNITURE AND INSTALLED D
LEVEL 2 08 MARKERBOARDS STORE AS REQUESTED BY OWNER.
12 11 11
CEILING 08 01 06 EXISTING WOOD FLOORING AND STRUCTURE ABOVE TO REMAIN
OPEN TO
16 LEVEL 2 07 07 REMOVE ALL EXISTING MECHANICAL, TIE UP AND SALVAGE LIGHT FIXTURES ONLY C
07 11 38 38 07
CEILING 08 WHERE CEILING GRID REPLACEMENT OCCUR, WHERE CEILING IS TO REMAIN EXPOSED
11 11
08 TO DECK, ASSUME NEW MECHANICAL AND OTHER COMPONENTRY IS TO BE DRYFALL
PAINTED TO MATCH EXISTING EXPOSED STRUCTURE. WHERE CEILING IS EXPOSED B 1
11 WOOD TIMBER, COLOR OF DUCTS IS TO BE DETERMINED.
08 REMOVE EXISTING ACOUSTICAL TILE CEILING AND SUPPORTS IN IT'S ENTIRETY. TIE UP A
12 11 AND SALVAGE LIGHT FIXTURES AS DESCRIBED IN NOTE 07. ASSUME NEW CEILING
11 12 GRID AND TILES ARE TO BE INSTALLED AND WILL CONCEAL NEW MECHANICAL
08 07 08 07 EQUIPMENT..
N.I.C. 09 REMOVE EXISTING LIGHTING IN THIS SHADED AREA. REFERENCE RCP FOR CEILING IN KEY PLAN
07 08 07 08 07 08 THIS AREA.
OPEN TO 10 REMOVE EXISTING FLOORING, BASE AND WALL FINISHES IN THEIR ENTIRETY AND
LEVEL 2 08 SEAL | DATE 04/01/21
01 01 PREPARE FOR NEW.
CEILING 07 07 08
11 DESIGN INTENT IS TO MAINTAIN VERTICAL FACE AND UNDERSIDE OF BULKHEADS/
07 08 07 08 DRYWALL CEILINGS WHERE POSSIBLE AND PATCH TO AS-NEW CONDITION IF ANY
07 WORK ABOVE THE CEILING IS REQUIRED, IN LIEU OF REBUILDING IF ANY LIGHT
07 08 07 08
01 07 FIXTURES EXIST, SALVAGE AND REUSED IN PATCHED CEILING IF POSSIBLE..
01 12 REMOVE EXISTING DRYWALL CEILING AND SUPPORTS. REFERENCE RCP FOR FINAL
DESIGN INTENT. IF IN EXISTENCE, WALL SCONCES ARE TO REMAIN.. IF CEILING
LIGHTS EXIST, SALVAGE FOR REUSE IN NEW CEILING UNLESS SHOWN OTHERWISE IN
38 07 NEW CEILING PLAN..
06 13 EXISTING TO REMAIN.
01
14 REMOVE HORIZONTAL PORTION OF HARDLID CEILINGS FOR HVAC WORK. REMOVE
07 08 07 08 WOOD PANELING IN CEILINGS. EXISTING STEPPED COFFER, DRYWALL WRAPPED
11 12 11
TRUSSES AND VERTICAL PORTIONS OF HARDLID CEILINGS TO REMAIN FOR REUSE.
11 15 REMOVE EXISTING CERAMIC TILE ON WALLS AND FLOOR IN ITS ENTIRETY.
12 07 16 REMOVE EXISTING LEVEL 2 BRIDGE CONSTRUCTION AND RAILING IN ITS ENTIRETY TO SHEET ISSUE
08 CREATE OPENING TO BELOW 1 Construction Documents 04/01/21
07
01 07 08 17 CAREFULLY SALVAGE ACOUSTICAL PANELS MOUNTED TO WALLS FOR POSSIBLE
08 REUSE BY OWNER. VERIFY RELOCATION DIRECTION WITH OWNER.
07 11
11 01 18 WALLS N THIS AREA REPRESENT TEMPORARY OFFICES CREATED IN INTIAL PHASE OF
08 12 12 CONSTRUCTION. THESE ARE TO BE REMOVED, ALONG WITH CEILINGS AND FINISHES
OPEN TO AT CORRECT PHASE TO CONVERT THESE ROOMS TO CLASSROOMS. EXISTING
LEVEL 2 08 CEILINGS CAN REMAIN AND LIGHTING RECONFIGURED DURING TEMPORARY OFFICE
CEILING 08 08 PHASE AND ALL IS TO BE REMOVED FOR FINAL CLASSROOM PHASE.
07
08 08 07 07 07 19 REMOVE EXISTING GLAZING AND FRAMING AS REQUIRED TO ACCEPT NEW
01 07 08 08 MECHANICAL LOUVER.
07 08
07 20 REMOVE EXISTING WINDOWS AND FRAMES IN THEIR ENTIRETY.
07
14 21 REMOVE SECTION OF EXISTING WOOD FLOOR AND STRUCTURE-COORDINATE WITH
06 STRUCTURAL.
01 11 11 22 REMOVE EXISTING SKYLIGHT FRAME, GLAZING, AND ACCESSORIES DOWN TO EXISTING
CURB IN ENTIRETY.
OPEN TO
38 BELOW 23 REMOVE EXISTING ROOF DUCT CHASE, FRAMING, AND ROOFING IN ENTIRETY.
11 11 12 12
24 REMOVE EXISTING ROOFING, INSULATION, AND CRICKET MATERIAL IN ENTIRETY TO
RECEIVE NEW ROOF AND FLASHINGS.
25 REMOVE EXISTING METAL LADDER, PLATFORM, AND SUPPORTS COMPLETE.
3'-0"
3'-0" 26 REMOVE EXISTING DOOR PANEL AND HARDWARE AT TOP OF PLATFORM, FRAME TO
07 36 3'-0" 21 13 08 07 REMAIN.
21 06 07
3'-0"
06 30 ALTERNATE BID # A-2: REPLACE EXISTING LINEAR PENDANT WITH NEW SPECIALTY
21 08 07 40 06 07 LIGHTING FOR LIVING WALL PER ELECTRICAL LIGHTING PLANS
3'-0"
08 31 EXISTING CEILING AND LIGHTING ARE NEWLY CONSTRUCTED AT TIME OF 2020
08 08 07 08 07
07 06 SUMMER CONSTRUCTION. AS MUCH OF EXISTING CENTER PORTION TO REMAIN
06 WITHOUT DISRUPTION IF POSSIBLE.
07 08 07 08 07 08 07 13 07 06 06 07
08 33 REMOVE EXISTING SKYLIGHT AND LIGHTING. REFERENCE ARCHITECTURAL AND
DETAILED SECTIONS FOR ARCHITECTURAL DESIGN INTENT TO DETERMINE EXTENT OF
07 08 07 DEMOLITION. COPYRIGHT NOTICE: THIS ARCHITECTURAL AND ENGINEERING DRAWING IS GIVEN IN CONFIDENCE
06 06 40 06 AND SHALL BE USED ONLY PURSUANT TO THE AGREEMENT WITH RATIO. NO OTHER USE,
34 FLOORING TO REMAIN AT STAIRS. REMOVE EXISTING DISPLAY PILASTERS UNDER DISSEMINATION OR DUPLICATION MAY BE MADE WITHOUT PRIOR WRITTEN CONSENT OF RATIO. ALL
COMMON LAW RIGHTS OF COPYRIGHT AND OTHERWISE ARE HEREBY SPECIFICALLY RESERVED.
STAIRS.
06 06 06 06 06 06 08 07 06 06 06 06 06 06 35 REMOVE ALL EXISTING CEILING, LIGHTING, REMAINING WALL FINISHES AND FLOOR
07 07 07 07 07 07 07 07 07 07 07 07 FINISHES. PREP AREA FOR NEW CEILING, FINISHES, HVAC AND FLOOR PLAN LAYOUT PROJECT NO. 19010.000
AS NEEDED. SHEET TITLE
36 REMOVE SECTION OF EXISTING WOOD FLOOR AND STRUCTURE-COORDINATE WITH
STRUCTURAL. REMOVE EXSTING LIGHTING IN THIS AREA.
37 INVESTIGATE CONSTRUCTION OF THIS HORIZONTAL BEAM TO DETERMINE FEASIBILITY
FIRST LEVEL
OF REMOVING BOTTOM FURRING STRIPS AND RECONSTRUCTION TO MATCH HEIGHT
OF HORIZONTAL BEAM TO DEMOLITION PLAN
38 PROVIDE ALT. BID NO A-5 TO REMOVE EXISITNG QUARRY TILE ON STAIRS AND
PREPARE FOR NEW TREADS, RISERS, LANDING AND STRINGERS AS REQUIRED PER
FIRST LEVEL DEMOLITION PLAN
4/1/2021 11:29:18 AM
AD-201
C. OWNER WILL REMOVE LOOSE SALVAGEABLE ITEMS, I.E., EQUIPMENT, FURNITURE,
CABINETRY, FILE CABINETS, WALL-MOUNTED PROJECTION SCREENS, ARTWORK,
5500 Wabash Avenue
A3
PLAQUES, ETC., PRIOR TO CONTRACTOR STARTING DEMOLITION WORK IN EACH
AREA. OWNER WILL STORE AND REINSTALL SUCH ITEMS. [OR] OWNER WILL STORE
MAJORITY OF LOOSE SALVAGEABLE ITEMS IN THE CENTER OF EACH ROOM
Terre Haute, Indiana
CONTAINING SAID ITEMS, I.E., EQUIPMENT, FURNITURE, CABINETRY, FILE
CABINETS, WALL-MOUNTED PROJECTION SCREENS, ARTWORK, ETC., PRIOR TO
47803
CONTRACTOR STARTING WORK. CONTRACTOR SHALL PROTECT SUCH ITEMS
DURING CONSTRUCTION. Owner
D. DEMOLISHED MATERIALS ARE THE PROPERTY OF THE CONTRACTOR UNLESS
NOTED OTHERWISE AND SHALL BE PROMPTLY DISPOSED OF OFF-SITE.
Rose-Hulman Institute of Technology
E. ITEMS NOTED TO BE REMOVED AND TURNED OVER TO OWNER SHALL BE 5500 Wabash Avenue
DELIVERED AS DIRECTED BY OWNER. Terre Haute, Indiana 47803
F. REMOVE ITEMS IN THEIR ENTIRETY UNLESS OTHERWISE INDICATED. 812-877-1511
C3 AD-201 DESCRIPTION OF PRIMARY ITEMS TO BE REMOVED IS GENERAL IN NATURE, AND
AD-201 C6 REMOVAL OF SECONDARY COMPONENTS SUCH AS BLOCKING, SUPPORTS,
ANCHORS, TRIM, ADHESIVE, PIPING, WIRING, ETC., RELATED TO PRIMARY ITEMS
SHALL BE INCLUDED.
G. PROTECT EXISTING SURFACES TO REMAIN IN AREAS ADJACENT TO DEMOLITION
WORK.
N.I.C. H. REPAIR FINISHES AND SURFACES LEFT EXPOSED BY DEMOLITION OR REMOVAL OF
39 EQUIPMENT, USING NEW MATERIALS TO MATCH SURROUNDING SURFACES.
REPAIR EXISTING FLOOR, BASE, WAINSCOT, WALL AND CEILING FINISHES TO
CORRECT DEFECTS EITHER CAUSED OR EXPOSED BY DEMOLITION WORK OR
EQUIPMENT REMOVAL. REPAIRED SURFACES SHALL BE SMOOTH AND
UNDETECTABLE UNDER FINAL FINISHES. AREAS NOTED ON THE DRAWINGS TO BE Architect
REPAIRED OR PATCHED ARE GIVEN FOR REFERENCE AND SHALL NOT BE
INTERPRETED TO LIMIT THE SCOPE OF WORK. RATIO
I. PATCH EXISTING FLOOR, WALL, CEILING AND ROOF CONSTRUCTION AT 101 South Pennsylvania Street
ABANDONED PENETRATION LOCATIONS WITH NEW MATERIALS AS REQUIRED TO Indianapolis, Indiana 46204
11 12 RECEIVE NEW FINISHES AND TO MAINTAIN ORIGINAL FIRE RATING OF ASSEMBLY 317-633-4040
01 WHERE APPLICABLE.
12
07 01 J. PORTIONS OF EXISTING MASONRY WALLS NOTED TO BE REMOVED AND OPENINGS
08 TO BE CUT INTO EXISTING MASONRY WALLS SHALL BE REMOVED BACK TO THE
01 Structural Engineer
07 NEAREST VERTICAL MORTAR JOINT. PROVIDE A MINIMUM BEARING OF 8 AT EACH
13 END FOR NEW MASONRY LINTELS AND FIELD VERIFY FINAL LENGTH. ALLOW A Fink Roberts & Petrie, Inc.
REMOVE MINIMUM OF 4 NEW MASONRY AT JAMB CONDITIONS OR END WALL CONDITIONS
01 OF MASONRY WALLS. REFER TO DEMOLITION PLANS FOR LOCATIONS OF WALL, 9449 Priority Way W Dr #200
STAIRS &
RAILING FLOOR, CEILING OR ROOF OPENINGS. Indianapolis, Indiana 46240
05 05 K. PROVIDE SMOOTH TRANSITIONS BETWEEN FLOOR, WALL AND CEILING SURFACES 317-872-8400
12 20 05 07
below 05 09 08 01 31 PRIOR TO INSTALLING NEW FINISHES WHERE WALLS OR OTHER ITEMS ARE
08
REMOVED. FILL FLOOR VOIDS WITH CONCRETE OR MATERIAL MATCHING
11
ADJACENT MATERIALS AND LEVEL FLOOR SURFACES TO PROVIDE A SMOOTH
13 TRANSITION FROM ONE SIDE OF WALL TO THE OTHER WHERE PORTIONS OF Mechanical / Electrical Engineer
W01 W02
10 04 15 04 04 WALLS ARE REMOVED. R.E. Dimond & Associates, Inc.
11 L. ADDITIONAL FLOOR TILE MAY BE PRESENT BENEATH FINISHES IN ROOMS WITH
12 12 05 12 EXISTING FLOOR TILE OR CARPET. REMOVE ALL LAYERS OF EXISTING FLOOR 732 N Capitol Avenue
OPEN TO BELOW OPEN TO BELOW Indianapolis, Indiana 46204
38 11 07 10 05 COVERINGS TO PROVIDE APPROPRIATE SUBSTRATE FOR NEW FLOOR FINISHES.
11 11 M. SELECTIVE DEMOLITION FOR INSTALLATION OF NEW MECHANICAL OR ELECTRICAL 317-634-4672
30 30 15 04 WORK SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR OR TRADE
04 04
REQUIRING THE DEMOLITION. THIS INCLUDES, BUT IS NOT LIMITED TO, FLOOR
SLAB AND PAVEMENT CUTTING FOR UNDERGROUND PIPING, CORING FOR WALL
08 07 01 07 AND FLOOR PENETRATIONS, ROOF PENETRATIONS, ETC. REFER TO MECHANICAL
01 07 07 11 11
08 08 08 AND ELECTRICAL DRAWINGS FOR ADDITIONAL DEMOLITION INFORMATION.
01 N. DISCONNECT AND CAP-OFF OR REMOVE OBSOLETE EXISTING UTILITY AND
07 07 07 07 07 01 07 SERVICE LINES PRIOR TO STARTING DEMOLITION WORK.
08 08 08 08 O. REMOVE ABANDONED UNDERGROUND UTILITIES AND INSTALL ENGINEERED FILL.
08 08
41 41 P. IF EXISTING ITEMS TO BE REMOVED OR DISTURBED ARE SUSPECTED OR
OPEN TO BELOW DISCOVERED TO CONTAIN ASBESTOS OR OTHER HAZARDOUS MATERIALS, STOP
07 07 07 07 DEMOLITION AND NOTIFY OWNER AND ARCHITECT IMMEDIATELY.
08 07 Q. REPAIR AND PATCH SPRAYED FIRE-RESISTIVE AND FIRESTOP MATERIALS WHERE
08 08 08
07 DAMAGED DUE TO SELECTIVE DEMOLITION ACTIVITIES TO RESTORE ORIGINAL
08
07 07 FIRE RATING UNLESS OTHERWISE INDICATED.
07 07 08 01 07 R. THE FOLLOWING DEMOLITION WORK SHALL BE PERFORMED AS PART OF THE
08 08
08 08 01 08 WORK UNDER THE APPROPRIATE PROJECT MANUAL SECTIONS: A.) REMOVAL OF
41 41
33 EXISTING ROOFING. B.) REMOVAL OF EXISTING WINDOWS, TEMPORARY WINDOW
OPENING CLOSURES AND OPENING PREPARATION TO RECEIVE NEW WINDOW
07 07 01 01 07
07 UNITS.
08 08 08 S. REFER TO WALL SECTIONS NOTED ON DEMOLITION PLANS FOR ADDITIONAL
01 08 07 07 DEMOLITION INFORMATION.
07
08 08 07 07 T. REFER TO PROJECT MANUAL DIVISION 4 FOR SPECIAL REQUIREMENTS
08
08 REGARDING DISPOSAL OF DEMOLISHED MASONRY RUBBLE.
01 08
OPEN TO BELOW 41 41 U. ALL WALL AND FLOOR FINISHES ARE TO REMAIN UNLESS NOTED OTHERWISE.
07 07 08 07 07 REV. 11/08/05
08 07
08 08
07
07 07
08 KEYNOTES - DEMOLITION
08 07 01 07
07 08 08
01 08 41 08 01 08
41
01 07
01 REMOVE EXISTING WALL CONSTRUCTION, DOORS AND FRAMES COMPLETELY.
F
07 07
01
07
08 02 REMOVE EXISTING BRICK WIINDOW FILL IN IT'S ENTIRETY.
03 DUCTED FUME HOODS TO BE REMOVED BY THE HAZARDOUS MATERIAL ABATEMENT
3 G
07 01
41 41
01
08 08 07
08
CONTRACTOR.
04 REMOVE EXISTING BUILT-IN EQUIPMENT/CABINETRY IN IT'S ENTIRETY.
E
2
OPEN TO BELOW
05 REMOVE EXISTING LOOSE EQUIPMENT, MACHINES, FURNITURE AND INSTALLED D
11 01 01 07 MARKERBOARDS STORE AS REQUESTED BY OWNER.
16 12 09
08 06 EXISTING WOOD FLOORING AND STRUCTURE ABOVE TO REMAIN
12 09 38 07 07 REMOVE ALL EXISTING MECHANICAL, TIE UP AND SALVAGE LIGHT FIXTURES ONLY C
11
29 08 WHERE CEILING GRID REPLACEMENT OCCUR, WHERE CEILING IS TO REMAIN EXPOSED
41
33
41 01
07
01 08
TO DECK, ASSUME NEW MECHANICAL AND OTHER COMPONENTRY IS TO BE DRYFALL
PAINTED TO MATCH EXISTING EXPOSED STRUCTURE. WHERE CEILING IS EXPOSED
B 1
WOOD TIMBER, COLOR OF DUCTS IS TO BE DETERMINED.
07 08 08 REMOVE EXISTING ACOUSTICAL TILE CEILING AND SUPPORTS IN IT'S ENTIRETY. TIE UP A
AND SALVAGE LIGHT FIXTURES AS DESCRIBED IN NOTE 07. ASSUME NEW CEILING
31 GRID AND TILES ARE TO BE INSTALLED AND WILL CONCEAL NEW MECHANICAL
07 07 EQUIPMENT..
07 08 08 N.I.C. KEY PLAN
09 REMOVE EXISTING LIGHTING IN THIS SHADED AREA. REFERENCE RCP FOR CEILING IN
41 41 THIS AREA.
OPEN TO BELOW
10 REMOVE EXISTING FLOORING, BASE AND WALL FINISHES IN THEIR ENTIRETY AND SEAL | DATE 04/01/21
PREPARE FOR NEW.
11 DESIGN INTENT IS TO MAINTAIN VERTICAL FACE AND UNDERSIDE OF BULKHEADS/
07 01 07
33 DRYWALL CEILINGS WHERE POSSIBLE AND PATCH TO AS-NEW CONDITION IF ANY
07 07 08 08 WORK ABOVE THE CEILING IS REQUIRED, IN LIEU OF REBUILDING IF ANY LIGHT
01 01 FIXTURES EXIST, SALVAGE AND REUSED IN PATCHED CEILING IF POSSIBLE..
41 41 12 REMOVE EXISTING DRYWALL CEILING AND SUPPORTS. REFERENCE RCP FOR FINAL
DESIGN INTENT. IF IN EXISTENCE, WALL SCONCES ARE TO REMAIN.. IF CEILING
LIGHTS EXIST, SALVAGE FOR REUSE IN NEW CEILING UNLESS SHOWN OTHERWISE IN
38 13 NEW CEILING PLAN..
13 EXISTING TO REMAIN.
13 07
14 REMOVE HORIZONTAL PORTION OF HARDLID CEILINGS FOR HVAC WORK. REMOVE
OPEN TO BELOW WOOD PANELING IN CEILINGS. EXISTING STEPPED COFFER, DRYWALL WRAPPED
07 08 07 08 01
41 TRUSSES AND VERTICAL PORTIONS OF HARDLID CEILINGS TO REMAIN FOR REUSE.
41
14 15 REMOVE EXISTING CERAMIC TILE ON WALLS AND FLOOR IN ITS ENTIRETY.
OPEN TO BELOW SHEET ISSUE
16 REMOVE EXISTING LEVEL 2 BRIDGE CONSTRUCTION AND RAILING IN ITS ENTIRETY TO
07 01 CREATE OPENING TO BELOW 1 Construction Documents 04/01/21
07 08 07 07
08 17 CAREFULLY SALVAGE ACOUSTICAL PANELS MOUNTED TO WALLS FOR POSSIBLE
08 08 07
REUSE BY OWNER. VERIFY RELOCATION DIRECTION WITH OWNER.
11 01 18 WALLS N THIS AREA REPRESENT TEMPORARY OFFICES CREATED IN INTIAL PHASE OF
14 41 41 CONSTRUCTION. THESE ARE TO BE REMOVED, ALONG WITH CEILINGS AND FINISHES
AT CORRECT PHASE TO CONVERT THESE ROOMS TO CLASSROOMS. EXISTING
CEILINGS CAN REMAIN AND LIGHTING RECONFIGURED DURING TEMPORARY OFFICE
PHASE AND ALL IS TO BE REMOVED FOR FINAL CLASSROOM PHASE.
14 07 07 19 REMOVE EXISTING GLAZING AND FRAMING AS REQUIRED TO ACCEPT NEW
08 08 MECHANICAL LOUVER.
20 REMOVE EXISTING WINDOWS AND FRAMES IN THEIR ENTIRETY.
41 41 21 REMOVE SECTION OF EXISTING WOOD FLOOR AND STRUCTURE-COORDINATE WITH
STRUCTURAL.
33 22 REMOVE EXISTING SKYLIGHT FRAME, GLAZING, AND ACCESSORIES DOWN TO EXISTING
CURB IN ENTIRETY.
14 11 11 OPEN TO BELOW
07 01 38 23 REMOVE EXISTING ROOF DUCT CHASE, FRAMING, AND ROOFING IN ENTIRETY.
01 41 24 REMOVE EXISTING ROOFING, INSULATION, AND CRICKET MATERIAL IN ENTIRETY TO
41 RECEIVE NEW ROOF AND FLASHINGS.
38
25 REMOVE EXISTING METAL LADDER, PLATFORM, AND SUPPORTS COMPLETE.
26 REMOVE EXISTING DOOR PANEL AND HARDWARE AT TOP OF PLATFORM, FRAME TO
31 REMAIN.
11 B2
AD-114 27 REMOVE EXISTING CONCRETE HOUSEKEEPING PAD FLUSH TO SURROUNDING FLOOR
08 08 21
ELEVATION TO RECEIVE NEW HOUSEKEEPING PAD.
07 07 07 ABOVE 08
07 08 08 07 29 EXISTING CEILING AND LIGHTING ARE NEWLY CONSTRUCTED AT TIME OF ACADEMIC
10 10 07 BUILDING CONSTRUCTION. EXISTING TO REMAIN WITHOUT DISRUPTION IF POSSIBLE.
08
05 09 05 09 IF NOT POSSIBLE, ASSUME NARRATIVE FROM 07 AND 08 TO BE APPLIED TO THIS AREA.
08 30 ALTERNATE BID # A-2: REPLACE EXISTING LINEAR PENDANT WITH NEW SPECIALTY
08 21 10 09 09 10 07 07 07 07 LIGHTING FOR LIVING WALL PER ELECTRICAL LIGHTING PLANS
07 08
31 08 08 08 31 EXISTING CEILING AND LIGHTING ARE NEWLY CONSTRUCTED AT TIME OF 2020
07 08 SUMMER CONSTRUCTION. AS MUCH OF EXISTING CENTER PORTION TO REMAIN
10 09 09 10
MECHANICAL 21 WITHOUT DISRUPTION IF POSSIBLE.
07
ROOM 31 01 31 33 REMOVE EXISTING SKYLIGHT AND LIGHTING. REFERENCE ARCHITECTURAL AND
08
A301 DETAILED SECTIONS FOR ARCHITECTURAL DESIGN INTENT TO DETERMINE EXTENT OF
07 DEMOLITION. COPYRIGHT NOTICE: THIS ARCHITECTURAL AND ENGINEERING DRAWING IS GIVEN IN CONFIDENCE
27 11 11 11 11 11 11 11 11 08 AND SHALL BE USED ONLY PURSUANT TO THE AGREEMENT WITH RATIO. NO OTHER USE,
34 FLOORING TO REMAIN AT STAIRS. REMOVE EXISTING DISPLAY PILASTERS UNDER DISSEMINATION OR DUPLICATION MAY BE MADE WITHOUT PRIOR WRITTEN CONSENT OF RATIO. ALL
07 COMMON LAW RIGHTS OF COPYRIGHT AND OTHERWISE ARE HEREBY SPECIFICALLY RESERVED.
STAIRS.
25 08 08 08 08 08 08 08 08 08 08 08 08 08 08 08
01 08 35 REMOVE ALL EXISTING CEILING, LIGHTING, REMAINING WALL FINISHES AND FLOOR
07 07 07 07 07 07 07 07 07 07 07 07 PROJECT NO. 19010.000
26 07 07 07 07 FINISHES. PREP AREA FOR NEW CEILING, FINISHES, HVAC AND FLOOR PLAN LAYOUT
AS NEEDED. SHEET TITLE
36 REMOVE SECTION OF EXISTING WOOD FLOOR AND STRUCTURE-COORDINATE WITH
STRUCTURAL. REMOVE EXSTING LIGHTING IN THIS AREA.
37 INVESTIGATE CONSTRUCTION OF THIS HORIZONTAL BEAM TO DETERMINE FEASIBILITY
SECOND LEVEL
OF REMOVING BOTTOM FURRING STRIPS AND RECONSTRUCTION TO MATCH HEIGHT
OF HORIZONTAL BEAM TO DEMOLITION PLAN
38 PROVIDE ALT. BID NO A-5 TO REMOVE EXISITNG QUARRY TILE ON STAIRS AND
B2 ATTIC MEZZANINE DEMOLITION PLAN A5 SECOND LEVEL DEMOLITION PLAN PREPARE FOR NEW TREADS, RISERS, LANDING AND STRINGERS AS REQUIRED PER
4/1/2021 11:29:30 AM
AD-114 AD-114
THE FINISH PLANS. THIS INCLUDES REMOVAL OF PEDESTALS ON LEVEL 1.
3/32" = 1'-0" 1/16" = 1'-0" 39 REMOVE ROOFING, INSULATION, AND STRUCTURE AS REQUIRED FOR NEW ROOF
HATCH.
40 SELECTIVELY DEMO AS REQUIRED FOR HVAC WORK. IF FLOORING ABOVE IS SHEET NUMBER
AFFECTED, CAREFULLY SALVAGE FLOORING FOR REINSTALLATION AFTER HVAC WORK
IS COMPLETE.
41 SELECTIVELY DEMO BEHIND COLUMNS TO ALLOW FOR FULL PENETRATION WELDING
OF COLUMN STUBS. AD-114
GENERAL DEMOLITION NOTES
A. THESE GENERAL DEMOLITION NOTES APPLY TO DEMOLITION DRAWINGS.
B. FIELD VERIFY CONDITIONS AND COORDINATE DEMOLITION OR REMOVAL WORK
RHIT MOENCH
WITH CORRESPONDING NEW CONSTRUCTION AND WITH APPROPRIATE TRADES
PRIOR TO STARTING DEMOLITION WORK. IF DISCREPANCIES ARE FOUND
BETWEEN CONTRACT DOCUMENTS AND ACTUAL FIELD CONDITIONS, NOTIFY
RENOVATION
ARCHITECT IMMEDIATELY.
AD-201
C. OWNER WILL REMOVE LOOSE SALVAGEABLE ITEMS, I.E., EQUIPMENT, FURNITURE,
CABINETRY, FILE CABINETS, WALL-MOUNTED PROJECTION SCREENS, ARTWORK,
5500 Wabash Avenue
A3
PLAQUES, ETC., PRIOR TO CONTRACTOR STARTING DEMOLITION WORK IN EACH
AREA. OWNER WILL STORE AND REINSTALL SUCH ITEMS. [OR] OWNER WILL STORE
MAJORITY OF LOOSE SALVAGEABLE ITEMS IN THE CENTER OF EACH ROOM
Terre Haute, Indiana
CONTAINING SAID ITEMS, I.E., EQUIPMENT, FURNITURE, CABINETRY, FILE
CABINETS, WALL-MOUNTED PROJECTION SCREENS, ARTWORK, ETC., PRIOR TO
47803
CONTRACTOR STARTING WORK. CONTRACTOR SHALL PROTECT SUCH ITEMS
DURING CONSTRUCTION. Owner
D. DEMOLISHED MATERIALS ARE THE PROPERTY OF THE CONTRACTOR UNLESS
NOTED OTHERWISE AND SHALL BE PROMPTLY DISPOSED OF OFF-SITE.
Rose-Hulman Institute of Technology
E. ITEMS NOTED TO BE REMOVED AND TURNED OVER TO OWNER SHALL BE 5500 Wabash Avenue
DELIVERED AS DIRECTED BY OWNER. Terre Haute, Indiana 47803
F. REMOVE ITEMS IN THEIR ENTIRETY UNLESS OTHERWISE INDICATED. 812-877-1511
C3 AD-201 DESCRIPTION OF PRIMARY ITEMS TO BE REMOVED IS GENERAL IN NATURE, AND
AD-201 C6 REMOVAL OF SECONDARY COMPONENTS SUCH AS BLOCKING, SUPPORTS,
ANCHORS, TRIM, ADHESIVE, PIPING, WIRING, ETC., RELATED TO PRIMARY ITEMS
SHALL BE INCLUDED.
G. PROTECT EXISTING SURFACES TO REMAIN IN AREAS ADJACENT TO DEMOLITION
WORK.
H. REPAIR FINISHES AND SURFACES LEFT EXPOSED BY DEMOLITION OR REMOVAL OF
EQUIPMENT, USING NEW MATERIALS TO MATCH SURROUNDING SURFACES.
REPAIR EXISTING FLOOR, BASE, WAINSCOT, WALL AND CEILING FINISHES TO
CORRECT DEFECTS EITHER CAUSED OR EXPOSED BY DEMOLITION WORK OR
EQUIPMENT REMOVAL. REPAIRED SURFACES SHALL BE SMOOTH AND
UNDETECTABLE UNDER FINAL FINISHES. AREAS NOTED ON THE DRAWINGS TO BE Architect
REPAIRED OR PATCHED ARE GIVEN FOR REFERENCE AND SHALL NOT BE
INTERPRETED TO LIMIT THE SCOPE OF WORK. RATIO
I. PATCH EXISTING FLOOR, WALL, CEILING AND ROOF CONSTRUCTION AT 101 South Pennsylvania Street
ABANDONED PENETRATION LOCATIONS WITH NEW MATERIALS AS REQUIRED TO Indianapolis, Indiana 46204
24 RECEIVE NEW FINISHES AND TO MAINTAIN ORIGINAL FIRE RATING OF ASSEMBLY 317-633-4040
WHERE APPLICABLE.
J. PORTIONS OF EXISTING MASONRY WALLS NOTED TO BE REMOVED AND OPENINGS
22 24 TO BE CUT INTO EXISTING MASONRY WALLS SHALL BE REMOVED BACK TO THE
NEAREST VERTICAL MORTAR JOINT. PROVIDE A MINIMUM BEARING OF 8 AT EACH Structural Engineer
END FOR NEW MASONRY LINTELS AND FIELD VERIFY FINAL LENGTH. ALLOW A Fink Roberts & Petrie, Inc.
24 MINIMUM OF 4 NEW MASONRY AT JAMB CONDITIONS OR END WALL CONDITIONS
OF MASONRY WALLS. REFER TO DEMOLITION PLANS FOR LOCATIONS OF WALL, 9449 Priority Way W Dr #200
FLOOR, CEILING OR ROOF OPENINGS. Indianapolis, Indiana 46240
23 24 K. PROVIDE SMOOTH TRANSITIONS BETWEEN FLOOR, WALL AND CEILING SURFACES 317-872-8400
8 PRIOR TO INSTALLING NEW FINISHES WHERE WALLS OR OTHER ITEMS ARE
REMOVED. FILL FLOOR VOIDS WITH CONCRETE OR MATERIAL MATCHING
ADJACENT MATERIALS AND LEVEL FLOOR SURFACES TO PROVIDE A SMOOTH
TRANSITION FROM ONE SIDE OF WALL TO THE OTHER WHERE PORTIONS OF Mechanical / Electrical Engineer
W01 W02 3
WALLS ARE REMOVED. R.E. Dimond & Associates, Inc.
L. ADDITIONAL FLOOR TILE MAY BE PRESENT BENEATH FINISHES IN ROOMS WITH
EXISTING FLOOR TILE OR CARPET. REMOVE ALL LAYERS OF EXISTING FLOOR 732 N Capitol Avenue
COVERINGS TO PROVIDE APPROPRIATE SUBSTRATE FOR NEW FLOOR FINISHES. Indianapolis, Indiana 46204
M. SELECTIVE DEMOLITION FOR INSTALLATION OF NEW MECHANICAL OR ELECTRICAL 317-634-4672
22 22 WORK SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR OR TRADE
REQUIRING THE DEMOLITION. THIS INCLUDES, BUT IS NOT LIMITED TO, FLOOR
SLAB AND PAVEMENT CUTTING FOR UNDERGROUND PIPING, CORING FOR WALL
AND FLOOR PENETRATIONS, ROOF PENETRATIONS, ETC. REFER TO MECHANICAL
AND ELECTRICAL DRAWINGS FOR ADDITIONAL DEMOLITION INFORMATION.
22 N. DISCONNECT AND CAP-OFF OR REMOVE OBSOLETE EXISTING UTILITY AND
SERVICE LINES PRIOR TO STARTING DEMOLITION WORK.
23 O. REMOVE ABANDONED UNDERGROUND UTILITIES AND INSTALL ENGINEERED FILL.
P. IF EXISTING ITEMS TO BE REMOVED OR DISTURBED ARE SUSPECTED OR
DISCOVERED TO CONTAIN ASBESTOS OR OTHER HAZARDOUS MATERIALS, STOP
DEMOLITION AND NOTIFY OWNER AND ARCHITECT IMMEDIATELY.
Q. REPAIR AND PATCH SPRAYED FIRE-RESISTIVE AND FIRESTOP MATERIALS WHERE
DAMAGED DUE TO SELECTIVE DEMOLITION ACTIVITIES TO RESTORE ORIGINAL
FIRE RATING UNLESS OTHERWISE INDICATED.
R. THE FOLLOWING DEMOLITION WORK SHALL BE PERFORMED AS PART OF THE
WORK UNDER THE APPROPRIATE PROJECT MANUAL SECTIONS: A.) REMOVAL OF
EXISTING ROOFING. B.) REMOVAL OF EXISTING WINDOWS, TEMPORARY WINDOW
OPENING CLOSURES AND OPENING PREPARATION TO RECEIVE NEW WINDOW
UNITS.
S. REFER TO WALL SECTIONS NOTED ON DEMOLITION PLANS FOR ADDITIONAL
REMOVE ALL EXISTING DEMOLITION INFORMATION.
ROOF DRAINS TO BE T. REFER TO PROJECT MANUAL DIVISION 4 FOR SPECIAL REQUIREMENTS
REPLACED WITH REGARDING DISPOSAL OF DEMOLISHED MASONRY RUBBLE.
COMBINATION ROOF U. ALL WALL AND FLOOR FINISHES ARE TO REMAIN UNLESS NOTED OTHERWISE.
DRAIN AND OVERFLOW
UNITS TYPICAL REV. 11/08/05
KEYNOTES - DEMOLITION
22 22
PAINTED TO MATCH EXISTING EXPOSED STRUCTURE. WHERE CEILING IS EXPOSED
WOOD TIMBER, COLOR OF DUCTS IS TO BE DETERMINED.
B 1
08 REMOVE EXISTING ACOUSTICAL TILE CEILING AND SUPPORTS IN IT'S ENTIRETY. TIE UP
AND SALVAGE LIGHT FIXTURES AS DESCRIBED IN NOTE 07. ASSUME NEW CEILING A
7
6 GRID AND TILES ARE TO BE INSTALLED AND WILL CONCEAL NEW MECHANICAL
EQUIPMENT..
23
09 REMOVE EXISTING LIGHTING IN THIS SHADED AREA. REFERENCE RCP FOR CEILING IN KEY PLAN
THIS AREA.
10 REMOVE EXISTING FLOORING, BASE AND WALL FINISHES IN THEIR ENTIRETY AND
PREPARE FOR NEW. SEAL | DATE 04/01/21
11 DESIGN INTENT IS TO MAINTAIN VERTICAL FACE AND UNDERSIDE OF BULKHEADS/
DRYWALL CEILINGS WHERE POSSIBLE AND PATCH TO AS-NEW CONDITION IF ANY
WORK ABOVE THE CEILING IS REQUIRED, IN LIEU OF REBUILDING IF ANY LIGHT
FIXTURES EXIST, SALVAGE AND REUSED IN PATCHED CEILING IF POSSIBLE..
12 REMOVE EXISTING DRYWALL CEILING AND SUPPORTS. REFERENCE RCP FOR FINAL
DESIGN INTENT. IF IN EXISTENCE, WALL SCONCES ARE TO REMAIN.. IF CEILING
LIGHTS EXIST, SALVAGE FOR REUSE IN NEW CEILING UNLESS SHOWN OTHERWISE IN
NEW CEILING PLAN..
13 EXISTING TO REMAIN.
14 REMOVE HORIZONTAL PORTION OF HARDLID CEILINGS FOR HVAC WORK. REMOVE
WOOD PANELING IN CEILINGS. EXISTING STEPPED COFFER, DRYWALL WRAPPED
TRUSSES AND VERTICAL PORTIONS OF HARDLID CEILINGS TO REMAIN FOR REUSE.
15 REMOVE EXISTING CERAMIC TILE ON WALLS AND FLOOR IN ITS ENTIRETY.
23 CONFIRM WITH
OWNER WHICH 16 REMOVE EXISTING LEVEL 2 BRIDGE CONSTRUCTION AND RAILING IN ITS ENTIRETY TO SHEET ISSUE
CREATE OPENING TO BELOW
ROOF-MOUNTED 1 Construction Documents 04/01/21
EQUIPMENT AND 17 CAREFULLY SALVAGE ACOUSTICAL PANELS MOUNTED TO WALLS FOR POSSIBLE
24 REUSE BY OWNER. VERIFY RELOCATION DIRECTION WITH OWNER.
MISC. STEEL NEEDS
TO BE REMOVED. 18 WALLS N THIS AREA REPRESENT TEMPORARY OFFICES CREATED IN INTIAL PHASE OF
CONSTRUCTION. THESE ARE TO BE REMOVED, ALONG WITH CEILINGS AND FINISHES
AT CORRECT PHASE TO CONVERT THESE ROOMS TO CLASSROOMS. EXISTING
CEILINGS CAN REMAIN AND LIGHTING RECONFIGURED DURING TEMPORARY OFFICE
PHASE AND ALL IS TO BE REMOVED FOR FINAL CLASSROOM PHASE.
22 19 REMOVE EXISTING GLAZING AND FRAMING AS REQUIRED TO ACCEPT NEW
MECHANICAL LOUVER.
20 REMOVE EXISTING WINDOWS AND FRAMES IN THEIR ENTIRETY.
4 22
21 REMOVE SECTION OF EXISTING WOOD FLOOR AND STRUCTURE-COORDINATE WITH
STRUCTURAL.
22 REMOVE EXISTING SKYLIGHT FRAME, GLAZING, AND ACCESSORIES DOWN TO EXISTING
CURB IN ENTIRETY.
24 5
23 REMOVE EXISTING ROOF DUCT CHASE, FRAMING, AND ROOFING IN ENTIRETY.
24 REMOVE EXISTING ROOFING, INSULATION, AND CRICKET MATERIAL IN ENTIRETY TO
RECEIVE NEW ROOF AND FLASHINGS.
25 REMOVE EXISTING METAL LADDER, PLATFORM, AND SUPPORTS COMPLETE.
26 REMOVE EXISTING DOOR PANEL AND HARDWARE AT TOP OF PLATFORM, FRAME TO
REMAIN.
27 REMOVE EXISTING CONCRETE HOUSEKEEPING PAD FLUSH TO SURROUNDING FLOOR
ELEVATION TO RECEIVE NEW HOUSEKEEPING PAD.
29 EXISTING CEILING AND LIGHTING ARE NEWLY CONSTRUCTED AT TIME OF ACADEMIC
BUILDING CONSTRUCTION. EXISTING TO REMAIN WITHOUT DISRUPTION IF POSSIBLE.
IF NOT POSSIBLE, ASSUME NARRATIVE FROM 07 AND 08 TO BE APPLIED TO THIS AREA.
30 ALTERNATE BID # A-2: REPLACE EXISTING LINEAR PENDANT WITH NEW SPECIALTY
LIGHTING FOR LIVING WALL PER ELECTRICAL LIGHTING PLANS
31 EXISTING CEILING AND LIGHTING ARE NEWLY CONSTRUCTED AT TIME OF 2020
SUMMER CONSTRUCTION. AS MUCH OF EXISTING CENTER PORTION TO REMAIN
WITHOUT DISRUPTION IF POSSIBLE.
33 REMOVE EXISTING SKYLIGHT AND LIGHTING. REFERENCE ARCHITECTURAL AND
DETAILED SECTIONS FOR ARCHITECTURAL DESIGN INTENT TO DETERMINE EXTENT OF
DEMOLITION. COPYRIGHT NOTICE: THIS ARCHITECTURAL AND ENGINEERING DRAWING IS GIVEN IN CONFIDENCE
34 FLOORING TO REMAIN AT STAIRS. REMOVE EXISTING DISPLAY PILASTERS UNDER AND SHALL BE USED ONLY PURSUANT TO THE AGREEMENT WITH RATIO. NO OTHER USE,
DISSEMINATION OR DUPLICATION MAY BE MADE WITHOUT PRIOR WRITTEN CONSENT OF RATIO. ALL
STAIRS. COMMON LAW RIGHTS OF COPYRIGHT AND OTHERWISE ARE HEREBY SPECIFICALLY RESERVED.
35 REMOVE ALL EXISTING CEILING, LIGHTING, REMAINING WALL FINISHES AND FLOOR
FINISHES. PREP AREA FOR NEW CEILING, FINISHES, HVAC AND FLOOR PLAN LAYOUT PROJECT NO. 19010.000
AS NEEDED.
36 REMOVE SECTION OF EXISTING WOOD FLOOR AND STRUCTURE-COORDINATE WITH SHEET TITLE
STRUCTURAL. REMOVE EXSTING LIGHTING IN THIS AREA.
37 INVESTIGATE CONSTRUCTION OF THIS HORIZONTAL BEAM TO DETERMINE FEASIBILITY ROOF DEMOLITION
OF REMOVING BOTTOM FURRING STRIPS AND RECONSTRUCTION TO MATCH HEIGHT
OF HORIZONTAL BEAM TO
38 PROVIDE ALT. BID NO A-5 TO REMOVE EXISITNG QUARRY TILE ON STAIRS AND
PLAN
PREPARE FOR NEW TREADS, RISERS, LANDING AND STRINGERS AS REQUIRED PER
4/1/2021 11:29:38 AM
SHEET ISSUE
1 Construction Documents 04/01/21
T/O PARAPET
142'-8"
N SECOND LEVEL
133'-6 13/16"
20 20 20 20
02 02 02 02 02 02 02 02 02
FIRST LEVEL
120'-11 13/16"
19 20 02 20 02 20 02
20 02 20 02
LOWER LEVEL
110'-7 1/16"
EXTERIOR DEMO
ELEVATIONS
A3 NORTH DEMO ELEVATION
4/1/2021 11:29:44 AM
AD-201
1/8" = 1'-0"
SHEET NUMBER
AD-201
KEYNOTE LEGEND
RHIT MOENCH
RENOVATION
N10 N9 N8 N7 N6 N5 A-201 N4 N3 N2 N1 5500 Wabash Avenue
AREA 3 AREA 2 A3
Terre Haute, Indiana
A 47803
Owner
Rose-Hulman Institute of Technology
SERVER 5500 Wabash Avenue
OFFICE RECEIVING ROOM
G138 G134
Terre Haute, Indiana 47803
G110 MECHANICAL B 812-877-1511
268 SF 372 SF
TECH SHOP 509 SF
ROOM C3 A-201
G130 G106 STORAGE
A-201 C6 ELECTRICAL
730 SF 666 SF FL206
2872 SF SWITCH GEAR MECHANICAL
STORAGE OFFICE OFFICE FL203 FL201
G100B OFFICE
G136 G132 WORK AREA 282 SF 2933 SF
27 SF 142 SF 146 SF G100A G108
79 SF
189 SF C
CIRCULATION CIRCULATION RESTROOM MECHANICAL
G100 G111 G101
OFFICE 1227 SF FL202
OFFICE OFFICE 153 SF 61 SF 316 SF
G153 G151 G133 OFFICE Architect
119 SF 92 SF 93 SF G131 OFFICE OFFICEBREAK AREA RATIO
173 SF
G123 G113 G103A MAIL DIST.
OFFICE OFFICE OFFICE 106 SF 105 SF 58 SF
D CENTER 101 South Pennsylvania Street
G149 G147 G137 ANNEX Indianapolis, Indiana 46204
116 SF 93 SF 93 SF OFFICE OFFICE OFFICE 317-633-4040
EL204
G135 G121 G115 CONFERENCE DELIVERY 82 SF
144 SF 107 SF 105 SF CAGE
OFFICE ROOM DELIVERY
OFFICE G103 STORAGE - ELEV 1 CAGE
OFFICE G143 255 SF G105 129 SF - Structural Engineer
101 SF G141 OFFICE OFFICE OFFICE -
G145 145 SF
204 SF 84 SF 129 SF Fink Roberts & Petrie, Inc.
180 SF G139 G119 G117 E
184 SF 162 SF 159 SF ELEVATOR
OFFICE 9449 Priority Way W Dr #200
MECHANICAL FAB. LAB
EL202A
EL203
Indianapolis, Indiana 46240
120 SF STOCK
88 SF STORAGE 317-872-8400
AREA 3 AREA 2
CL208
215 SF
G
INSTRUCTIONAL
TECHNOLOGY
DL204 MACHINE
248 SF TOOL SHOP
DL202
1058 SF
H
I.T.
MENS R.R. EQUIP./OFFICE
DL203 DL204A
151 SF
415 SF
C2
J A-301
OFFICE
MANAGER
DL205
OFFICE 134 SF
DL204B
60 SF WORK SHOP OFFICE
DL206A DL206 MANUFACTURING
129 SF 97 SF
K LAB
DL201
1101 SF
ROBOTICS MATERIALS
E
2
M WORKROOM/STORAGE LAB D
DL207A CL207
197 SF 1076 SF
A2 STAIR C
A-301 CL211
STORAGE
133 SF
B 1
N CL202B
120 SF CUSTODIAL A
CUSTODIAL
STORAGE
SERVICES
CL212
CL202
436 SF
41 SF DN KEY PLAN
LOWER LEVEL 2
OVERALL FLOOR
PLAN
4/1/2021 11:41:34 AM
SHEET NUMBER
A-101
KEYNOTE LEGEND RHIT MOENCH
RENOVATION
5500 Wabash Avenue
Terre Haute, Indiana
47803
Owner
DL201A Rose-Hulman Institute of Technology
AREA 2 5500 Wabash Avenue
AREA 2 Terre Haute, Indiana 47803
ROBOTICS 812-877-1511
CLASSROOM
L DL207 CL207C
AREA 1
AREA 1 825 SF
CL207B
Architect
RATIO
MATERIALS 101 South Pennsylvania Street
ROBOTICS LAB Indianapolis, Indiana 46204
M CL207
WORKROOM/STORAGE 317-633-4040
1076 SF
DL207A
197 SF
Structural Engineer
Fink Roberts & Petrie, Inc.
A2 STAIR CL207A 9449 Priority Way W Dr #200
A-301 CL211 Indianapolis, Indiana 46240
133 SF
CUSTODIAL 317-872-8400
STORAGE
CL212
CL202B 41 SF
Mechanical / Electrical Engineer
STORAGE R.E. Dimond & Associates, Inc.
CL212
N CL202B
120 SF 732 N Capitol Avenue
Indianapolis, Indiana 46204
CL202 317-634-4672
CUSTODIAL
SERVICES
CL202
436 SF CIRCULATION
-
DN
CL205
B 1
A
KEY PLAN
SHEET ISSUE
1 Construction Documents 04/01/21
LOWER LEVEL 2
FLOOR PLAN - AREA
1
4/1/2021 11:41:37 AM
SHEET NUMBER
A-101.1
KEYNOTE LEGEND
N10 N9 N8 N7 N6 N5 A-201
N4 N3 N2 N1
RHIT MOENCH
A3 RENOVATION
AREA 2 5500 Wabash Avenue
A
FL206E
Terre Haute, Indiana
47803
Owner
Rose-Hulman Institute of Technology
5500 Wabash Avenue
Terre Haute, Indiana 47803
812-877-1511
STORAGE
STORAGE FL205
FL206
2872 SF
ELECTRICAL Architect
SWITCH GEAR
FL203
MECHANICAL RATIO
282 SF FL201 101 South Pennsylvania Street
2933 SF
Indianapolis, Indiana 46204
317-633-4040
FL202
C Structural Engineer
FL203 Fink Roberts & Petrie, Inc.
9449 Priority Way W Dr #200
Indianapolis, Indiana 46240
MECHANICAL 317-872-8400
FL202
316 SF
FL205
Mechanical / Electrical Engineer
R.E. Dimond & Associates, Inc.
FL201
732 N Capitol Avenue
Indianapolis, Indiana 46204
317-634-4672
D
EL203 EL204
FAB. LAB
OFFICE STOCK
EL202A STORAGE
120 SF CL208
215 SF
AREA 2
EL211B
F
MACHINE
TOOL LAB II
EL202 FABRICATION
F
826 SF LAB
EL207
957 SF
3 G
CIRCULATION
STAIR
-
EL211
211 SF
TOOL ROOM
EL205
175 SF
E
2
A5 119 SF
A-301 D
G
EL211A
B 1
DL202B
A
INSTRUCTIONAL
TECHNOLOGY DL202A
DL204 KEY PLAN
248 SF
MACHINE
TOOL SHOP
SEAL | DATE 04/01/21
DL202
1058 SF
SHEET ISSUE
1 Construction Documents 04/01/21
C2
A-301
J DL201B
MANAGER
OFFICE OFFICE
DL204B DL205
60 SF 134 SF
MANUFACTURING
K LAB
DL201
1101 SF
DL201A
AREA 2
AREA 2
ROBOTICS
CLASSROOM
L DL207 CL207C
AREA 1
AREA 1 825 SF
COPYRIGHT NOTICE: THIS ARCHITECTURAL AND ENGINEERING DRAWING IS GIVEN IN CONFIDENCE
CL207B AND SHALL BE USED ONLY PURSUANT TO THE AGREEMENT WITH RATIO. NO OTHER USE,
DISSEMINATION OR DUPLICATION MAY BE MADE WITHOUT PRIOR WRITTEN CONSENT OF RATIO. ALL
COMMON LAW RIGHTS OF COPYRIGHT AND OTHERWISE ARE HEREBY SPECIFICALLY RESERVED.
LOWER LEVEL 2
A3 LOWER LEVEL 2 PLAN
FLOOR PLAN - AREA
A-101.2
1/8" = 1'-0" 2
4/1/2021 11:41:41 AM
SHEET NUMBER
A-101.2
KEYNOTE LEGEND
RHIT MOENCH
AREA 3 AREA 2 RENOVATION
N10 N9 N8 N7 N6 N5 A-201 N4 N3 N2 N1
5500 Wabash Avenue
A3 Terre Haute, Indiana
A
DEPT.
47803
HEAD FACULTYFACULTYFACULTYFACULTYFACULTYFACULTYFACULTYFACULTY
FL116B OFFICE OFFICE OFFICE OFFICE OFFICE OFFICE OFFICE OFFICE Owner
CLOSET FL115 FL113 FL111 FL109 FL107 FL105 FL103 FL101
G220A Rose-Hulman Institute of Technology
32 SF MENS R.R.
G206
5500 Wabash Avenue
165 SF STUDY AREA B ADMIN Terre Haute, Indiana 47803
C3 A-201 812-877-1511
CLASSROOM CLASSROOM G204 OFFICE
CLASSROOM 299 SF A-201 FL116
G222 G203 C6
938 SF G220 FACULTY
733 SF
FACULTYFACULTYFACULTY
WOMENS R.R. FACULTY OFFICE FACULTY
OFFICE OFFICE OFFICE
G202 OFFICE COLLISION
110 SF
C FL114
FL112
FL108
FL106 FL104 FL102
14
Architect
STG. RATIO
G210A D
KITCHEN
101 South Pennsylvania Street
CAFE Indianapolis, Indiana 46204
EL127 EL125
CLASSROOM CLASSROOM CLASSROOM 278 SF 317-633-4040
DW
HOUSEKEEPING
G221 G219 G208
858 SF 852 SF STUDENT ELEV 1 EQUIPMENT
AREA - ROOM
G210 84 SF EL102 Structural Engineer
E 184 SF
Fink Roberts & Petrie, Inc.
STORAGE MAIL SORT 9449 Priority Way W Dr #200
EL126 CORRIDOR EL103
-- Indianapolis, Indiana 46240
93 SF 466 SF
COOK 317-872-8400
LOUNGE
GREENHOUSE
EL112
G219A 2409 SF
1266 SF
F Mechanical / Electrical Engineer
R.E. Dimond & Associates, Inc.
WOMENS R.R. MENS R.R. 732 N Capitol Avenue
A5
A-301
EL105 EL104 Indianapolis, Indiana 46204
225 SF 256 SF
317-634-4672
G
SEMICONDUCTOR
OFFICE OFFICE OFFICE OFFICE OPTICS LAB
AREA 3 AREA 2 OFFICE DL110D DL110E DL110F DL110G DL108
DL110C 228 SF
OFFICE
DL107
217 SF
H
OFFICE
DL110B OFFICEADMIN OFFICE NUCLEAR
DL110A DL110 PHYSICS LAB OFFICE
DL105 DL106
230 SF
OPTICAL 253 SF
J ENGINEERING
LAB 3 OPTICAL
DL115 OFFICE METROLOGY
OFFICE
1095 SF DL116 LAB
DL120 OFFICE
DL104 DL103
255 SF
230 SF
ELECTRICAL
EQUIPMENT
K ROOM
DL118
OPTICAL
ENGINEERING SENIOR OFFICE
LAB 1 DARK ROOM DESIGN LAB
AREA 2 G112 DL102 AREA 2
DL117 195 SF
DL101 230 SF
544 SF 253 SF
CLASSROOM
L
DL119 ACOUSTICS
AREA 1 AREA 1
OPTICAL 384 SF PROJECTS
ENGINEERING LAB OFFICE F
LAB 2
CL118
CL110
223 SF
CL109
230 SF
3 G
M
748 SF E
2
M.T.F. D
MEASUREMENT NON-LINEAR CONFERENCE
A2 LAB OPTICS LAB ROOM H BAR
A-301 CL114 CL115 CL116 EL108 C
182 SF 346 SF 289 SF 183 SF
N
B 1
A
OFFICE ADMIN OFFICE OFFICE
OFFICE CL108 CL106 CL105
CL107 207 SF 266 SF 288 SF
213 SF
KEY PLAN
PHYSICS LAB
O 3 E.I.T.
CL117 CL102A SEAL | DATE 04/01/21
1712 SF CLASSROOM 48 SF
CL119 OPTICAL
ELECTRICAL OFFICE
454 SF COMMUNICATIONS
ROOM CL104
STORAGE LAB
CL101 184 SF
81 SF CL102B CL103
107 SF 218 SF
P
ENGINEERING
PHYSICS LAB OFFICE
1 BL103 OFFICE
MATERIALS BL110 158 SF BL102
604 SF 191 SF
PROCESSING
PHYSICS LAB LAB
BL112 OFFICE
Q 1
BL113 509 SF BL104
163 SF
1672 SF
PHYSICS
SHEET ISSUE
STOCK ROOM OFFICE OFFICE 1 Construction Documents 04/01/21
BL108 BL109 OFFICE BL101
385 SF 231 SF 171 SF
BL105
163 SF
R
MACHINE
ELECTRICAL SHOP OFFICE OFFICE
ROOM BL107 BL106 BL100
706 SF 182 SF 193 SF
PHYSICS LAB BL115
195 SF
S 2
BL114 ELEV 2
1652 SF
CUSTODIAL -
STORAGE 45 SF
BL116
159 SF OFFICE OFFICE OFFICE
9.8 8.9 6.9 5.9 5.5
AL104 5.1 AL103 4.1AL102 3.1 2.1 1.2
112 SF
111 SF 109 SF
T
ELEVATOR
STORAGE
MECHANICAL
ART CURATOR AL101A
BL117 215 SF
32 SF AL101
341 SF
7.9
U
WATER ROOM
AL106
50 SF
V
COPYRIGHT NOTICE: THIS ARCHITECTURAL AND ENGINEERING DRAWING IS GIVEN IN CONFIDENCE
AND SHALL BE USED ONLY PURSUANT TO THE AGREEMENT WITH RATIO. NO OTHER USE,
DISSEMINATION OR DUPLICATION MAY BE MADE WITHOUT PRIOR WRITTEN CONSENT OF RATIO. ALL
COMMON LAW RIGHTS OF COPYRIGHT AND OTHERWISE ARE HEREBY SPECIFICALLY RESERVED.
W SHEET TITLE
C2
A-301
LOWER LEVEL 1
OVERALL FLOOR
S10 S9 S8 S7 S6 S5 S4 S3 S2 S1
PLAN
4/1/2021 11:41:52 AM
A-102
OPTICAL
ENGINEERING SENIOR OFFICE
DARK ROOM
LAB 1 DESIGN LAB DL102
G112 230 SF
DL117 195 SF DL101
AREA 2 544 SF 253 SF AREA 2
KEYNOTE LEGEND RHIT MOENCH
L
DL117B
CLASSROOM
DL119
384 SF
RENOVATION
HOLOGRAPHIC ACOUSTICS
5500 Wabash Avenue
OPTICAL PROJECTS OFFICE
ENGINEERING
LAB 2
INTERFEROMETRY
LAB
S3C
LAB
CL110
CL109
230 SF
Terre Haute, Indiana
CL112
CL118
748 SF
223 SF
47803
CL110 Owner
CL112A
CL112 Rose-Hulman Institute of Technology
CL109
5500 Wabash Avenue
M CL114 Terre Haute, Indiana 47803
812-877-1511
M.T.F.
MEASUREMENT NON-LINEAR CONFERENCE
A2 LAB OPTICS LAB ROOM CIRCULATION STAIR H BAR
A-301 CL114 CL115 CL116 - - EL108
4200 SF 107 SF 183 SF
182 SF 346 SF 289 SF
Architect
N RATIO
101 South Pennsylvania Street
CL105B Indianapolis, Indiana 46204
CL117 317-633-4040
ENGINEERING OFFICE
PHYSICS LAB BL103
1 158 SF OFFICE
BL110 BL102
604 SF BL103 191 SF
BL110
MATERIALS
PROCESSING BL104
LAB
BL102
PHYSICS LAB BL112 OFFICE
Q 1 509 SF
BL104
BL113 163 SF
1672 SF BL101
PHYSICS
BL112 BL105
STOCK ROOM OFFICE OFFICE
BL108 BL109 BL101
385 SF 231 SF 171 SF
OFFICE
BL105 F
BL113
BL108
163 SF
3 G
R X
BL100A
E
2
BL100
D
BL106
BL114
C
BL107 MACHINE
SHOP OFFICE OFFICE
B 1
ELECTRICAL BL107 BL106 BL100
706 SF 182 SF 193 SF A
ROOM
BL115
195 SF
BL115 KEY PLAN
PHYSICS LAB
S 2
BL114 SEAL | DATE 04/01/21
1652 SF
CIRCULATION
ELEV 2
-
- 1018 SF
45 SF
CUSTODIAL
STORAGE
BL116
159 SF
OFFICE
9.8 8.9 6.9 5.9 5.5OFFICE 5.1 AL103 4.1 OFFICE 3.1 2.1 1.2
AL104 112 SF AL102
BL117 111 SF 109 SF
AL101
T
ELEVATOR
MECHANICAL SHEET ISSUE
BL117 STORAGE 1 Construction Documents 04/01/21
32 SF AL101A
XAL101A 215 SF
ART CURATOR
AL101
341 SF
AL106
WATER ROOM
7.9 AL106
50 SF
A-102.1
RHIT MOENCH
KEYNOTE LEGEND
RENOVATION
00-A1
00-A2
CENTER WALL ON COLUMN GRID LINE
CENTER WALL ON MULLION CENTER LINE
5500 Wabash Avenue
A-201
N10 N9 N8 N7 N6 N5 N4 N3 N2 N1 097553.A01
105500.16
VEGETATIVE WALL SYSTEM
PRIVATE DELIVERY POSTAL SPECIALTIES
Terre Haute, Indiana
A3
47803
AREA 2 TYP.
A3 TYP. A5 C5 A3 A3 A3 Owner
EW01 EW01 A-622 A-622A-622 EW01 A-622 EW01 A-622 EW01 A-622
Rose-Hulman Institute of Technology
A 5500 Wabash Avenue
Terre Haute, Indiana 47803
00-A2 00-A2 00-A2 00-A2 812-877-1511
COMMUNICATIONS
A-502 B1
CABLE
FACULTY FACULTY FACULTY FACULTY FACULTY FACULTY FACULTY FACULTY
DEPT. HEAD OFFICE OFFICE OFFICE OFFICE OFFICE OFFICE OFFICE OFFICE
EW01
FL116B FL115 FL113 FL111 FL109 FL107 FL105 FL103 FL101
136 SF 136 SF 136 SF 137 SF 137 SF 136 SF 136 SF 128 SF
4'-6 1/2"
ADMIN OFFICE A-532 A5 A-201
C3
ALIGN
A-532
A-532 A5 101 South Pennsylvania Street
FL116 A-532
A3 A-502 O.H. Indianapolis, Indiana 46204
ALIGN
A-622 FL112 FL108 FL106 FL104 FL102 317-633-4040
FL116
00-A2 B1
EW01
B1 FACULTY FACULTY FACULTY FACULTY FACULTY Structural Engineer
FACULTY FL114 OFFICE COLLISION OFFICE OFFICE OFFICE Fink Roberts & Petrie, Inc.
OFFICE FL112 FL108 FL106 FL104 FL102
FL114 A-502 131 SF 270 SF 131 SF 132 SF 131 SF 9449 Priority Way W Dr #200
140 SF Indianapolis, Indiana 46240
C A-501 A7 A7 A7 A7 A-501 317-872-8400
A-501 A-501
A5
A-532 O.H. S3A O.H.
1'-5 7/8"
00-A1 A5
00-A1 Mechanical / Electrical Engineer
A-532
S3A.C
D6 R.E. Dimond & Associates, Inc.
A-422 732 N Capitol Avenue
B2 S3C.C Indianapolis, Indiana 46204
105500.16
2'-0" CLEAR E1 317-634-4672
9'-10 5/8"
CORRIDOR
A-401 A-501
FL120
1'-5 3/8"
1686 SF
3'-2 7/8"
105500.16 A1
S3A.C S3C.C
3/4"
FL120A
4'-0 3/8" FL120B
D
EL127
KITCHEN EL125 CORRIDOR
EL125 -
278 SF 261 SF
EL102
DW
CAFE HOUSEKEEPING
EL127 EQUIPMENT
ELEV 1 S3C ROOM
EL126
MOENCH - EL102
CAFE EL128 STORAGE 84 SF 184 SF
ELXXX EL126
93 SF
E
S3A.C 2'-0" S3C.D S3C.C
S3C.C
C1 B3 A-501 D4 MAIL SORT
F2 EL103 EL103
A-402 466 SF 1'-0"
A-402 D5
A-403 C1 LOUNGE
EL112 S3C.C S3C.C
S3A.C
2409 SF F
S1FA.D.A A3 A-402
EL104
3 G
F
A7
A-532
S7FA A7
A-532
E
2
2'-6" D
S3C.C
A5
AREA 2 WOMENS R.R.
EL105
MENS R.R.
EL104
B 1
A-301 225 SF 256 SF
E1
A-404
A
097553.A01
SEMICONDUCTOR
OFFICE OPTICS LAB
OFFICE OFFICE DL108
DL110D OFFICE DL110F DL110G 228 SF
OFFICE DL110E
OFFICE
DL110C DL107
217 SF
DL108
DL107
J
OPTICAL
ENGINEERING
LAB 3 OFFICE ELECTRICAL OPTICAL
DL115 DL116 EQUIPMENT OFFICE METROLOGY
1095 SF ROOM DL120 LAB
DL118 DL104 OFFICE
255 SF DL103
230 SF
DL104
DL120
DL115 DL103
DL117A DL102
DL119 DL101
OPTICAL
ENGINEERING SENIOR OFFICE
DARK ROOM
LAB 1 DESIGN LAB DL102
G112 230 SF
DL101 COPYRIGHT NOTICE: THIS ARCHITECTURAL AND ENGINEERING DRAWING IS GIVEN IN CONFIDENCE
DL117 195 SF
AND SHALL BE USED ONLY PURSUANT TO THE AGREEMENT WITH RATIO. NO OTHER USE,
AREA 2 544 SF 253 SF AREA 2 DISSEMINATION OR DUPLICATION MAY BE MADE WITHOUT PRIOR WRITTEN CONSENT OF RATIO. ALL
COMMON LAW RIGHTS OF COPYRIGHT AND OTHERWISE ARE HEREBY SPECIFICALLY RESERVED.
HOLOGRAPHIC ACOUSTICS
LOWER LEVEL 1
OPTICAL
ENGINEERING
LAB 2
INTERFEROMETRY
LAB
S3C
PROJECTS
LAB
CL110
OFFICE
CL109
230 SF
FLOOR PLAN - AREA
CL112 C2
CL118 A-301 223 SF
2
4/1/2021 11:42:05 AM
748 SF
9.8 8.9 6.9 5.9 5.5 5.1 4.1 3.1 2.1 1.2
A-102.2
1/8" = 1'-0"
KEYNOTE LEGEND
RHIT MOENCH
RENOVATION
5500 Wabash Avenue
Terre Haute, Indiana
47803
Owner
Rose-Hulman Institute of Technology
5500 Wabash Avenue
Terre Haute, Indiana 47803
812-877-1511
Architect
RATIO
N10 101 South Pennsylvania Street
Indianapolis, Indiana 46204
317-633-4040
B
G3 STUDY AREA
G204
299 SF
CLASSROOM A-501
G222 A-201 C6
CLASSROOM
938 SF
G220 A3
733 SF EW01 A-622
WOMENS R.R.
G202
110 SF
M8A C
X G203
STAIR CIRCULATION D6
X
- - A-422
179 SF 1404 SF
X G208 G210
G210A
STG.
F
A-501 G210A
STAIR
-
D
3 G
G1 B7
A-401
128 SF
E
2
N10 D
CLASSROOM CLASSROOM CLASSROOM
G221 G219 STUDENT C
G208
858 SF 852 SF
809 SF AREA
G210
G5 A-501 588 SF B 1
E5 A
E
KEY PLAN
COOK
GREENHOUSE
G219A
1266 SF
SHEET ISSUE
AREA 3 AREA 2 1 Construction Documents 04/01/21
CRAPO LEVEL 2
FLOOR PLAN - AREA
3 (LL1)
4/1/2021 12:07:04 PM
SHEET NUMBER
A-102.3
KEYNOTE LEGEND RHIT MOENCH
RENOVATION
N10 N9 N8 N7 N6 N5 A-201 N4 N3 N2 N1
5500 Wabash Avenue
A3
Terre Haute, Indiana
A 47803
AREA 3 AREA 2 FACULTYFACULTYFACULTY
FACULTYFACULTY
FACULTY FACULTYFACULTYFACULTYFACULTY FACULTYFACULTYFACULTYFACULTYFACULTYFACULTY DEPT. HEAD Owner
OFFICE OFFICE OFFICE OFFICE OFFICE OFFICE OFFICE OFFICE OFFICE OFFICE OFFICE OFFICE OFFICE OFFICE OFFICE OFFICE F105A
F137 F135 F133 F129 F127 F125 F123 F121 F119 F117 F115 F113 F111 F109 F107 238 SF
Rose-Hulman Institute of Technology
F131
133 SF 134 SF 133 SF 133 SF 134 SF 5500 Wabash Avenue
Terre Haute, Indiana 47803
CLASSROOM
STUDENT B ADMIN OFFICE 812-877-1511
G310 WORK AREA
940 SF F105 C3 A-201
CLASSROOM G304
CLASSROOM G306 A-201 193 SF
649 SF C6
G308
FACULTY FACULTY
OFFICE OFFICE FACULTYFACULTYFACULTYFACULTYFACULTY FACULTY FACULTY FACULTYFACULTYFACULTY FACULTY
CLOSET DATA
F132 F130 OFFICE OFFICE OFFICE OFFICE OFFICE COLLISION OFFICE OFFICE OFFICE OFFICE OFFICE
F114
G304A C F128 F126 F124 F122 F120 F116 F112 F110 F108 F106 F103
8 SF
FACULTY
ROOF
OFFICE
ACCESS
F101
G304B CORRIDOR
F132 Architect
RATIO
D 101 South Pennsylvania Street
Indianapolis, Indiana 46204
EQUIPMENT SERVER/EQUIP. WOMENS R.R.
REPAIR ROOM
317-633-4040
CLASSROOM CLASSROOM CLASSROOM 13 SEAT STORAGE E109
G317 G315 G313 E107A E107C 123 SF
CLASSROOM
CONF. 209 SF E104
860 SF 854 SF 824 SF 98 SF
G305 ELEV 1 1958 SF Structural Engineer
-
TECHNICIAN 84 SF
Fink Roberts & Petrie, Inc.
E OFFICE 9449 Priority Way W Dr #200
E107B Indianapolis, Indiana 46240
WORKSHOP 96 SF MENS R.R.
STORAGE AREA 3 AREA 2 317-872-8400
E107 E108
G305A 481 SF 242 SF
OFFICE
D105
143 SF
J
OFFICE
ELECTRONIC D104
CALIBRATION 144 SF
LABORATORY
CIRCUITS D116 ECE LAB TECH
LEARNING
LABORATORY 115 SF D117
130 SF
CENTER DESIGN LAB OFFICE
K D115 D101-A D101 D103
1409 SF 612 SF 943 SF 165 SF
OFFICE
D118
98 SF
STORAGE OFFICE
AREA 2 AREA 2
D115A D102
97 SF 145 SF
L
INSTRUMENT
AREA 1 AREA 1
ROOM OFFICE F
EQUIPMENT
STORAGE
C114
517 SF
WORKSHOP/STORAGE C110
142 SF
3 G
C112
C115A
200 SF
236 SF
E
2
DIGITAL
ELECTRONIC
MECHATRONICS OFFICE D
M C111 C109
MICROCOMPUTER 945 SF 165 SF
LABORATORY
C115 C
A2
1300 SF
A-301 OFFICE
C108
142 SF
B 1
N
A
P ELECTRICAL
ROOM
B107A ELECTRICAL
227 SF STORAGE
ROOM B105A
B107 216 SF
33 SF CLASSROOM
B106 ADVANCED
Q 581 SF CIRCUIT SHEET ISSUE
STUDY AREA
144 OFFICE LABORATORY
B108B B105 1 Construction Documents 04/01/21
226 SF
154 SF 1278 SF
OFFICE
B108C E.I.T.
187 SF OFFICE
B108A B103C
154 SF 17 SF
R
BUSINESS TEST OFFICE
AND FINANCE ENGINEERING B103A SOLDERING OFFICE
CONFERENCE LAB 128 SF LAB B101 OFFICE
ROOM B104 B102 162 SF B100
B109 241 SF OFFICE 193 SF
196 SF
472 SF B103B
123 SF
S CUSTODIAL
ELEV 2
STORAGE
GM ROOM -
B110 47 SF
B111 123 SF
1794 SF
9.8 8.9 6.9 5.9 5.5 5.1 4.1 3.1 2.1 1.2
T
NEW MTL STUD CIRCULATION WORKROOM / OFFICE
OFFICE WRAP AT STEEL - OFFICE BREAKROOM A105
A140 COLUMNS 964 SF A102A A102B OFFICE 134 SF
229 SF
SERVER 149 SF 131 SF
OFFICE OFFICE ROOM ADMIN OFFICE A103
OFFICE OFFICE 181 SF
OFFICE
A136 A138 A100A A102 A106
A124 7.9A126 114 SF 113 SF 97 SF 252 SF 139 SF
U 137 SF 117 SF
WORKROOM / STORAGE
OFFICE A104B OFFICE
BREAKROOM
APPLICATIONS ELEC. A101 11 SF
A107
A122 348 SF
READING 288 SF A118A 138 SF
ROOM 14 SF ELEC. AND
STORAGE OFFICE STORAGE OFFICE STORAGE SAFE OFFICE OFFICE
A130 A120B A104
A120A 265 SF
A128 A118 A101A A104A A108
12 SF 137 SF
19 SF 108 SF 117 SF 14 SF 54 SF 141 SF
V CIRCULATION ADMIN OFFICE COPYRIGHT NOTICE: THIS ARCHITECTURAL AND ENGINEERING DRAWING IS GIVEN IN CONFIDENCE
AND SHALL BE USED ONLY PURSUANT TO THE AGREEMENT WITH RATIO. NO OTHER USE,
A120 A113 DISSEMINATION OR DUPLICATION MAY BE MADE WITHOUT PRIOR WRITTEN CONSENT OF RATIO. ALL
257 SF 179 SF COMMON LAW RIGHTS OF COPYRIGHT AND OTHERWISE ARE HEREBY SPECIFICALLY RESERVED.
OFFICE
OFFICE A109
OFFICE OFFICE OFFICE OFFICE OFFICE OFFICE OFFICE OFFICE OFFICE OFFICE OFFICE PROJECT NO. 19010.000
A121 205 SF
185 SF A123 A125 A127 A129 A117 A116 A115 A114 A112 A111 A110
125 SF 128 SF 127 SF 139 SF 124 SF 152 SF
125 SF 137 SF 125 SF 126 SF 138 SF SHEET TITLE
W FIRST LEVEL
C2 OVERALL FLOOR
A-301
PLAN
4/1/2021 11:42:21 AM
S10 S9 S8 S7 S6 S5 S4 S3 S2 S1
A-103
AREA 2 STORAGE AREA 2
D115A
97 SF
CIRCULATION
-
1132 SF
OFFICE
D102
145 SF
KEYNOTE LEGEND RHIT MOENCH
D115A D102
L S3C C112A
RENOVATION
AREA 1
INSTRUMENT
S3C
C110
AREA 1 5500 Wabash Avenue
ROOM
C114
OFFICE
C110
Terre Haute, Indiana
517 SF
47803
142 SF
EQUIPMENT WORKSHOP/STORAGE
STORAGE C112
C115A S3C 236 SF
200 SF Owner
C112B Rose-Hulman Institute of Technology
S3C 5500 Wabash Avenue
Terre Haute, Indiana 47803
MECHATRONICS OFFICE
M C114 812-877-1511
C111 C109
DIGITAL 945 SF 165 SF
ELECTRONIC S3C
MICROCOMPUTER C109
LABORATORY
C115
1300 SF
A2
A-301 C108
OFFICE
CIRCULATION
C108
- 142 SF
5589 SF Architect
RATIO
N C111
101 South Pennsylvania Street
Indianapolis, Indiana 46204
317-633-4040
Structural Engineer
Fink Roberts & Petrie, Inc.
MAIL ROOM 9449 Priority Way W Dr #200
C104 Indianapolis, Indiana 46240
OFFICE
OFFICE 51 SF 317-872-8400
DYNAMIC C118
C117
SYSTEMS AND 109 SF
116 SF
CONTROLS
O LABORATORY Mechanical / Electrical Engineer
C116 C101A
S3C R.E. Dimond & Associates, Inc.
1492 SF S3C C104
732 N Capitol Avenue
OFFICE ADMIN Indianapolis, Indiana 46204
C103 317-634-4672
SERVER 168 SF
ROOM
WORKROOM /
B107B BREAKROOM
4'-0" 298 SF S3C
OFFICE C103A OFFICE
CLEAN AGENT 279 SF
C101A C105
CLOSET S3C 222 SF 227 SF
S3A C116A C105
C116A
2'-0"
S3A
P
ELECTRICAL
ROOM
B107A
227 SF B107
ELECTRICAL STORAGE
ROOM B105A
216 SF
B107
33 SF
S3C
CLASSROOM
B106
581 SF
Q
ADVANCED
STUDY AREA CIRCUIT
144 OFFICE LABORATORY
226 SF
B108B B105
154 SF 1278 SF
S3C
(8) QTY VENDING MACHINES B106
TO BE RELOCATED HERE OFFICE
FROM THEIR EXISTING B108C
LOCATION IN ROOM EL103. F
3
187 SF
E.I.T. G
OFFICE
B103C
B108A
154 SF B108A
17 SF S3C E
2
R D
OFFICE C
B103A
128 SF
BUSINESS
AND FINANCE
TEST
ENGINEERING
SOLDERING
LAB
OFFICE
B101
162 SF
B 1
CONFERENCE LAB B102 OFFICE
ROOM B104 193 SF B100 A
241 SF 196 SF
S3C B109 B104
472 SF OFFICE
B103B
123 SF KEY PLAN
S3C
9.8 8.9 7.9 6.9 5.9 5.5 5.1 4.1 3.1 2.1 1.2
T A100
SHEET ISSUE
A105
1 Construction Documents 04/01/21
C1 CIRCULATION A1 OFFICE
A-422 A-422 WORKROOM /
- A105
964 SF
OFFICE BREAKROOM
OFFICE A102A A102B
134 SF
A140 149 SF 131 SF
X 229 SF OFFICE
X
A103
SERVER A102A 181 SF
OFFICE OFFICE OFFICE ROOM ADMIN OFFICE OFFICE
OFFICE A126 A136 A138 A100A A102
114 SF
A106
A124 117 SF 113 SF 97 SF 252 SF 139 SF
A106
137 SF
D1 03
A-422
U A103
STORAGE
A104B A107
WORKROOM / OFFICE 11 SF
BREAKROOM A101 OFFICE
A122 348 SF A104 A107
ELEC. 138 SF
288 SF
A118A
APPLICATIONS 14 SF 03
READING
ROOM STORAGE ELEC. AND
STORAGE A130 OFFICE OFFICE SAFE OFFICE
A120B STORAGE A104 OFFICE
A120A 265 SF A128 12 SF A118 A101A A104A
19 SF 108 SF 117 SF 54 SF
137 SF A108
14 SF
141 SF
A118A A101A A108
V A118
CIRCULATION ADMIN OFFICE
A113 A113 A109
A120 03
257 SF 179 SF
A117 A115 A114 A112 A111 A110
OFFICE
A109
OFFICE 205 SF COPYRIGHT NOTICE: THIS ARCHITECTURAL AND ENGINEERING DRAWING IS GIVEN IN CONFIDENCE
A121 OFFICE OFFICE OFFICE OFFICE OFFICE OFFICE OFFICE OFFICE OFFICE OFFICE AND SHALL BE USED ONLY PURSUANT TO THE AGREEMENT WITH RATIO. NO OTHER USE,
185 SF OFFICE A115 A114 A112 A111 A110 DISSEMINATION OR DUPLICATION MAY BE MADE WITHOUT PRIOR WRITTEN CONSENT OF RATIO. ALL
A123 A125 A127 A129 A117 COMMON LAW RIGHTS OF COPYRIGHT AND OTHERWISE ARE HEREBY SPECIFICALLY RESERVED.
125 SF 128 SF 127 SF 139 SF 124 SF A116 125 SF 137 SF 125 SF 126 SF 138 SF
152 SF
PROJECT NO. 19010.000
SHEET TITLE
W FIRST LEVEL FLOOR
PLAN - AREA 1
4/1/2021 11:42:29 AM
S10 S9 S8 S7 S6 S5 S4 S3 S2 S1
C2
A2 FIRST LEVEL PLAN A-301
SHEET NUMBER
A-103.1
A-103.1
1/8" = 1'-0"
KEYNOTE LEGEND
RHIT MOENCH
00-A1
00-A2
CENTER WALL ON COLUMN GRID LINE
CENTER WALL ON MULLION CENTER LINE
RENOVATION
N10 N9 N8 N7 N6 N5 A-201
N4 N3 N2 N1 00-B2 ALIGN FINISH FACE OF WALL TYPE WITH FACE OF
WINDOW OPENING JAMB 5500 Wabash Avenue
A3 Terre Haute, Indiana
A3 A3 A7 A3 A3 A3 A3 A3
47803
A-622 A-622 A-622 A-622
A3
EW01 EW01 A-622 EW01 EW01 A-622 EW01 EW01 A-622 EW01 A-622 EW01
6" CLEAR EW01
TYP. A-622 Owner
A
Rose-Hulman Institute of Technology
00-A2 00-A2 00-A2 00-A2 00-A2 00-A2 00-A2 00-A2 5500 Wabash Avenue
9'-0" CLEAR
AREA 3 AREA 2 Terre Haute, Indiana 47803
S3C S3C.A 812-877-1511
FACULTY FACULTY FACULTY FACULTY
FACULTY FACULTY FACULTY FACULTY FACULTY DEPT. HEAD
OFFICE OFFICE OFFICE OFFICE FACULTY FACULTY FACULTY FACULTY FACULTY FACULTY FACULTY
OFFICE OFFICE OFFICE OFFICE OFFICE F105A
F135 F133 F131 F129 OFFICE OFFICE OFFICE OFFICE OFFICE OFFICE OFFICE
F137 133 SF F127 F125 F123 F107 E8 A-502 238 SF
EW01
130 SF
134 SF 133 SF 133 SF
134 SF 134 SF 133 SF F121 F119 F117 F115 F113 F111 F109 131 SF
EW01
133 SF 133 SF 133 SF 132 SF 132 SF 135 SF 135 SF
B1 A-502 B1 B1 B1 S3A.1.A
A-502 B1 A-502 A-502 A-502 A-502 B1 B1 A-502 B1 A-502 B1 B1 B1 A-502 A-502 B1 B1 A-502
A-502 B1 A-502 A-502 A-502 B1 00-B2
O.H. O.H. O.H. O.H. O.H. 6" CLEAR O.H. O.H. O.H. F105A
F137 F135 F133 F131 F129 F127 F125 F123 F121 F119 F117 F115 F113 F111 F109 F107
4'-5 1/8"
B 00-A1 00-A1 00-A1 00-A1 00-A1 00-A1
3'-0" MIN
00-A1
3'-8"
S3C.A
6" CLEAR
6'-1 3/4"
A-201 Architect
B3 A2 A2 A2 A2 A2 A2 C3
F132 F130
A-532 A-532 A-532 A-532 A-532 A-532 A-532 ADMIN OFFICE RATIO
ALIGN
O.H. F105 101 South Pennsylvania Street
F128 F126 F124 F122 F120 F116 F114 F112 F110 F108
ALIGN
A-201 F106
C6 F105
193 SF Indianapolis, Indiana 46204
A-502 B1 O.H. O.H. O.H. O.H. O.H. 00-A2 317-633-4040
1'-1"
EW01 EW01
FACULTY FACULTY A-502 B3 B3 A-502 A-502 B3 B3 A-502 B3 E4 A-502 B3 B3 A-502 A-502 B3 B3 A-502
A-502
OFFICE OFFICE FACULTY A-401 Structural Engineer
F132 FACULTY COLLISION FACULTY FACULTY FACULTY FACULTY A-502 FACULTY A3
F130 FACULTY FACULTY FACULTY FACULTY DATA Fink Roberts & Petrie, Inc.
134 SF 5'-0 1/4" (+/-) OFFICE F116 OFFICE OFFICE OFFICE OFFICE OFFICE A-622
131 SF OFFICE OFFICE OFFICE OFFICE
F122 271 SF F114 F112 F110 F108 F106 F103 9449 Priority Way W Dr #200
EQ EQ F128 F124 F120 F103
F126 133 SF 108 SF 132 SF 132 SF 134 SF 134 SF B1 143 SF
Indianapolis, Indiana 46240
C 132 SF 132 SF
133 SF 132 SF
JAN
F100 317-872-8400
A5 A5 B1
A-532 A5 A5 FACULTY
CIRCULATION 00-A1 00-A1 A-532 00-A1 A-532 00-A1 A-532
F101
OFFICE 7
- X
A-401 Mechanical / Electrical Engineer
128 SF O.H. A-502 F101
141 SF
X R.E. Dimond & Associates, Inc.
732 N Capitol Avenue
F100
13'-1 3/4"
Indianapolis, Indiana 46204
6'-0" 6"
F100A 317-634-4672
STAIR
-
119 SF
EQUIPMENT
REPAIR ROOM SERVER/EQUIP.
E107A STORAGE
209 SF E107C CLASSROOM
98 SF E104
1958 SF
S3C
ELEV 1 S3C
E107A -
84 SF
S3C WOMENS R.R.
E E109
123 SF
TECHNICIAN
OFFICE
E107B E107B
AREA 3 AREA 2 96 SF
S3C
WORKSHOP MENS R.R.
E107 E108
481 SF 242 SF
E107
CIRCULATION
-
F
3
1514 SF
G
F
INCLUDE IN ALT. BID NO. A-5 REMOVAL OF
EXISTING DISPLAY PEDESTALS UNDER STAIRS OFFICE
E
2
E102 E102A
AND REPLACING WITH PLATFORM TO MATCH ONE
SHOWN UNDER STAIRS IN LL1 CAFE AREA 158 SF D
C
A5
A-301
OFFICE
B 1
E101
160 SF A
G E100
KEY PLAN
OFFICE
D114 D105
143 SF
J D114A
OFFICE
D104
144 SF
D104
D116B D117
OFFICE
D118 S3C
98 SF
D116A D118
AREA 2 STORAGE AREA 2
CIRCULATION OFFICE
D115A - D102
97 SF
1132 SF 145 SF COPYRIGHT NOTICE: THIS ARCHITECTURAL AND ENGINEERING DRAWING IS GIVEN IN CONFIDENCE
D115A D102 AND SHALL BE USED ONLY PURSUANT TO THE AGREEMENT WITH RATIO. NO OTHER USE,
DISSEMINATION OR DUPLICATION MAY BE MADE WITHOUT PRIOR WRITTEN CONSENT OF RATIO. ALL
COMMON LAW RIGHTS OF COPYRIGHT AND OTHERWISE ARE HEREBY SPECIFICALLY RESERVED.
L S3C C112A
PROJECT NO. 19010.000
S3C AREA 1
AREA 1
INSTRUMENT C110 SHEET TITLE
ROOM
C114
517 SF
OFFICE
C110
142 SF
FIRST LEVEL FLOOR
EQUIPMENT
STORAGE
C115A
WORKSHOP/STORAGE
S3C
C112
236 SF
PLAN - AREA 2
200 SF
4/1/2021 11:42:37 AM
9.8 8.9 7.9 6.9 5.9 5.5 5.1 4.1 3.1 2.1 1.2
C2
A-301
A2 FIRST LEVEL PLAN SHEET NUMBER
A-103.2
1/8" = 1'-0"
A-103.2
RHIT MOENCH
KEYNOTE LEGEND
RENOVATION
5500 Wabash Avenue
Terre Haute, Indiana
47803
Owner
Rose-Hulman Institute of Technology
5500 Wabash Avenue
Terre Haute, Indiana 47803
812-877-1511
Architect
RATIO
101 South Pennsylvania Street
Indianapolis, Indiana 46204
317-633-4040
N10
Structural Engineer
Fink Roberts & Petrie, Inc.
9449 Priority Way W Dr #200
Indianapolis, Indiana 46240
317-872-8400
A
Mechanical / Electrical Engineer
R.E. Dimond & Associates, Inc.
AREA 3 AREA 2
732 N Capitol Avenue
Indianapolis, Indiana 46204
FACULTY
OFFICE
317-634-4672
EW01
F137
130 SF
PATCH FLOOR WHERE
DRAIN REMOVED IN
THIS AREA
D3 D1 F137
B
A-502 E4 A-502 E5
A-502
F132
CLASSROOM CLASSROOM STUDENT
G310 G306 WORK AREA A-201
940 SF CLASSROOM C6
853 SF G304
G308 649 SF
ROOF EW01
ACCESS FACULTY
A7 CLOSET
A-351 G304B OFFICE
G304A
4'-4"
8 SF F132
134 SF
G304B C
G308B G308A G306B G306A G304
CIRCULATION 5'-2"
-
1390 SF X
G305
F
3 G
E
2
D
13 SEAT D
CONF.
G305
C
N10
CLASSROOM
G317
CLASSROOM
G315
CLASSROOM
G313
G3
G305A
B 1
860 SF 854 SF 824 SF
S3A.C
G4 A-502 G1 A
KEY PLAN
STORAGE
G305A
E SEAL | DATE 04/01/21
AREA 3 AREA 2
E7
A-401
F
SHEET ISSUE
1 Construction Documents 04/01/21
CRAPO LEVEL 3
FLOOR PLAN - AREA
3 (L1)
4/1/2021 11:42:41 AM
SHEET NUMBER
A-103.3
RHIT MOENCH
KEYNOTE LEGEND
RENOVATION
N10 N9 N8 N7 N6 N5 A-201 N4 N3 N2 N1 5500 Wabash Avenue
A3
Terre Haute, Indiana
A
CONFERENCE
47803
AREA 3 AREA 2 ROOM OFFICE OFFICE OFFICE OFFICE OFFICE OFFICE OFFICE OFFICE OFFICE OFFICE Owner
F230 F228 F226 F224 F222 F220 F218 F216 F214 F212 F210
285 SF 202 SF 164 SF 163 SF 162 SF 162 SF 163 SF 163 SF 162 SF 162 SF 164 SF Rose-Hulman Institute of Technology
5500 Wabash Avenue
CIRCULATION STORAGE Terre Haute, Indiana 47803
B ADMIN OFFICE - F208 812-877-1511
F231 1224 SF 25 SF C3 A-201
BREAK AREA
182 SF
A-201 C6 F207
WORKROOM / USABILITY 58 SF
OFFICE
BREAKROOM LAB F206
153 SF
F233 F225A OFFICE
C 170 SF 69 SF
CSSE LAB CSSE LAB F205
148 SF
USABILITY F225 F217 OFFICE
LAB CONTROL 1428 SF 1337 SF
F204
ROOM 158 SF
STAIRWELL F225B
- CUSTODIAL 70 SF
OFFICE
275 SF - F203 Architect
149 SF
35 SF
RATIO
D 101 South Pennsylvania Street
Indianapolis, Indiana 46204
MECHANICAL 317-633-4040
ROOM CLASSROOM
G116 E104
556 SF ELEV 1 WOMENS R.R. 1958 SF
- E202 Structural Engineer
84 SF 140 SF
E Fink Roberts & Petrie, Inc.
9449 Priority Way W Dr #200
MECHANICAL Indianapolis, Indiana 46240
ROOM 317-872-8400
AREA 3 AREA 2
E201
451 SF
G
OFFICE OFFICE
D222 D208
119 SF
STORAGE 106 SF
D223A OFFICE OFFICE OFFICE OFFICE
OFFICE 10 SF D220 D221 D209 OFFICE
D224
D223 131 SF
146 SF 149 SF 157 SF D207
119 SF 123 SF
H
OFFICE CONFERENCE STUDENT OFFICE
D225 STORAGE D219A STUDY AREA D206
125 SF 134 SF 124 SF
D226A D210
10 SF
OFFICE 263 SF
OFFICE D227 OFFICE
D226 144 SF D205
120 SF
127 SF
J STORAGE /
WORKROOM OFFICE OFFICE
D226C D218 D204
OFFICE 78 SF 137 SF OFFICE 120 SF
D228 ADMIN OFFICE D211
257 SF D229 134 SF OFFICE
209 SF D203
120 SF
K
OFFICE FACULTY OFFICE
CONFERENCE
D230 STORAGE OFFICE D202
ROOM
124 SF D215B 124 SF
D226D 145 SF
D212
10 SF OFFICE 287 SF OFFICE
AREA 2 OFFICE D232 AREA 2
D201
D231 144 SF 120 SF
126 SF
L
AREA 1 OFFICE AREA 1
F
MECHANICAL
ROOM
C215
MECHANICAL
ROOM
C214
OFFICE
C212
C211
120 SF 3 G
P
STORAGE
MECHANICAL C205B
ROOM 18 SF
W9NAA ROSE
MECHANICAL TECH RADIO B202
ROOM CLUB
335 SF
B203 B204
128 SF
Q PROJECTION 96 SF
ROOM STUDENT
SHEET ISSUE
B111A CONFERENCE BBE HIVE OFFICE 1 Construction Documents 04/01/21
234 SF
ROOM B205 B201
229 SF
B205A 284 SF
136 SF
R
DIGITAL
SYNTHETIC
SIGNAL
BIOLOGY
PROCESSING
LABORATORY
LAB
B206
460 SF
B200
1109 SF
S
ELEV 2
-
GM ROOM MECHANICAL 42 SF
B111 ROOM
1794 SF
B207
469 SF
9.8 8.9 6.9 5.9 5.5 5.1 4.1 3.1 2.1 1.2
T
CUSTODIAL
CIRCULATION STORAGE MECHANICAL
- A223A ROOM
ADMIN OFFICE OFFICE 151 SF 27 SF MENS R.R.
A301
A218 A218A A223 590 SF CLASSROOM
409 SF 187 SF WOMENS R.R. 317 SF A202
A222 672 SF
7.9 SITTING AREA 125 SF STORAGE /
U A220 PROJECTOR
BREAKROOM A202A
OFFICE OFFICE OFFICE
A200 17 SF
A218C A218B 166 SF A201
122 SF 153 SF 134 SF
WORK AREA / OFFICE
ELECTRICAL STORAGE A203A
CIRCULATION ROOM A203 116 SF
V - A200A 97 SF
55 SF OFFICE COPYRIGHT NOTICE: THIS ARCHITECTURAL AND ENGINEERING DRAWING IS GIVEN IN CONFIDENCE
AND SHALL BE USED ONLY PURSUANT TO THE AGREEMENT WITH RATIO. NO OTHER USE,
A203B DISSEMINATION OR DUPLICATION MAY BE MADE WITHOUT PRIOR WRITTEN CONSENT OF RATIO. ALL
WORKROOM 115 SF COMMON LAW RIGHTS OF COPYRIGHT AND OTHERWISE ARE HEREBY SPECIFICALLY RESERVED.
OFFICE A207 OFFICE
OFFICE OFFICE OFFICE OFFICE OFFICE OFFICE OFFICE OFFICE A209 ADMIN OFFICE113 SF OFFICE OFFICE OFFICE A203D
A217 A216 A215 A214 A213 A212 A211 A210 226 SF A206 A205 A204 137 SF OFFICE PROJECT NO. 19010.000
108 SF 112 SF 115 SF 112 SF 115 SF 113 SF 113 SF 120 SF A208 114 SF 112 SF A203C
114 SF
119 SF
135 SF SHEET TITLE
W
SECOND LEVEL
C2
OVERALL FLOOR
S10 S9 S8 S7 S6
A-301
S5 S4 S3 S2 S1 PLAN
4/1/2021 11:42:54 AM
A-104
FACULTY
OFFICE CONFERENCE
STORAGE D215B ROOM
D226D 145 SF D212
10 SF OFFICE OFFICE 287 SF
D214 D215A
OFFICE
D231
D232
S3C D201 OFFICE
KEYNOTE LEGEND
S8A
OFFICE
D231
126 SF D226D
144 SF
OPEN TO OFFICE
BELOW C208
S3C STORAGE S3C 119 SF
S8A
C200A Architect
36 SF
N RATIO
101 South Pennsylvania Street
C216 Indianapolis, Indiana 46204
317-633-4040
O
Mechanical / Electrical Engineer
INFILL WITH LIKE WALL S3C R.E. Dimond & Associates, Inc.
CONSTRUCTION, 732 N Capitol Avenue
VERIFY WALL TYPE IN ADMIN Indianapolis, Indiana 46204
MECHANICAL FIELD, ALIGN TO MECHANICAL
ROOM ROOM C205 OFFICE 317-634-4672
EXISTING FINISH 219 SF
C218 FACES C201 C206
562 SF 569 SF 270 SF
C218 C201
STORAGE
C205B
18 SF
MECHANICAL
ROOM
B203
B202
335 SF
MECHANICAL W9NAA ROSE
ROOM TECH RADIO B202
B203 CLUB
128 SF B204 S3A
96 SF
Q
PROJECTION B111A
B201
ROOM
B111A
234 SF OFFICE
STUDENT BBE HIVE B201
CONFERENCE B205 229 SF S3C
ROOM 284 SF
B205A
136 SF
F
S300-1
STAIR
300-1
S3C
3 G
R
E
2
D
C
SYNTHETIC DIGITAL
BIOLOGY
LABORATORY
B206
SIGNAL
PROCESSING
LAB
B 1
460 SF B200
1109 SF
A
KEY PLAN
S
SEAL | DATE 04/01/21
ELEV 2
-
42 SF
GM ROOM
B111 MECHANICAL
S5 S4 S3 1794 SF
ROOM
B207 B207
469 SF
S3A
T 9.8 8.9 7.9 6.9 5.9 5.5 5.1 4.1 3.1 2.1 1.2
T A220
A202B
SHEET ISSUE
A223
MECHANICAL CIRCULATION 1 Construction Documents 04/01/21
ROOM - MECHANICAL
151 SF
A301 ROOM
A222
S3A OFFICE A301
ADMIN OFFICE A5 MENS R.R. 590 SF
A218 A218A A223
A2 187 SF CLASSROOM
409 SF 317 SF
A-351 A3 A7 A202
A301
A-422 CUSTODIAL
WOMENS R.R. STORAGE
672 SF
A222 A223A
U 125 SF A301
A218A 27 SF
SITTING AREA
LADDER
2'-0" CLEAR
11'-10 3/4" +/-
U
11'-5 1/4" +/-
C2
A-301
A-502 B1
CIRCULATION STORAGE
B - F208
ADMIN OFFICE 1224 SF 25 SF
F231 C3 A-201
182 SF
BREAK AREA Architect
A-201 USABILITY F207 RATIO
C6 58 SF
LAB 101 South Pennsylvania Street
OFFICE
F225A Indianapolis, Indiana 46204
69 SF F206
WORKROOM / 153 SF 317-633-4040
BREAKROOM
F233
170 SF
OFFICE Structural Engineer
F205
USABILITY 148 SF
Fink Roberts & Petrie, Inc.
C LAB CONTROL CSSE LAB CSSE LAB
F225 9449 Priority Way W Dr #200
ROOM F217 Indianapolis, Indiana 46240
1428 SF
F225B 1337 SF
70 SF OFFICE 317-872-8400
F204 B4
158 SF
S3C
C5 MECHANICAL
ROOM CLASSROOM
G116 WOMENS R.R. E104
A-403 556 SF E202 1958 SF
A1 A-502 A5 140 SF
ELEV 1
- S3C
84 SF
G116
E
S2C
C6 MECHANICAL
ROOM
E201
C5 A-422 451 SF
A-403 C1
2'-0" CLEAR
C3
E201
F F
W01 D3
W02 A-423
S3C.A 3 G
E5
A-421
CIRCULATION
- S3C.A
E
2
1838 SF
D
A-404
SEATING A-502 B7 B5 A-502
A5 E200 C
A-301 E4
B 1
A
G E200
S8A S8A
KEY PLAN
OFFICE D222 OFFICE
D222 D208
D208
119 SF D221 106 SF SEAL | DATE 04/01/21
STORAGE
S8A S3C
D223A
10 SF OFFICE OFFICE OFFICE
OFFICE D220
D223 D224 D221 D209 S3C OFFICE
OFFICE 146 SF
149 SF 157 SF
131 SF D207
D223
D224 D220 D209 123 SF
119 SF D223A
D225
OFFICE CONFERENCE OFFICE
D225 D219A D206
125 SF 134 SF D206 124 SF
STORAGE OFFICE STUDENT S3C
D226A
SHEET ISSUE
D219U STUDY AREA
10 SF D210 1 Construction Documents 04/01/21
OFFICE 263 SF
D226 D227 S3C D205
OFFICE OFFICE
OFFICE 144 SF
D219V D205
D226 120 SF
127 SF D226A D227 S8A
J
STORAGE / S3C
WORKROOM 1'-8" CLEAR
S8A
D226C OFFICE OFFICE
78 SF S3C
D218 D204
D204
137 SF 120 SF
OFFICE
OFFICE D211
S8A 134 SF
D228
257 SF ADMIN OFFICE OFFICE S3C
D217 D203
D229 D216 OFFICE
209 SF OFFICE D203
D229 D216 D217 D211 S8A 120 SF
D217A
K
STORAGE
D230
D217A D212
OFFICE OFFICE
D230 FACULTY D202
124 SF OFFICE CONFERENCE 124 SF
STORAGE D215B ROOM S3C
D226D 145 SF D212
10 SF OFFICE OFFICE 287 SF
D214 D215A
OFFICE D201 OFFICE
D231 S3C
OFFICE D232 D201
144 SF
D231 120 SF
126 SF D226D D232 D214 S8A
S8A COPYRIGHT NOTICE: THIS ARCHITECTURAL AND ENGINEERING DRAWING IS GIVEN IN CONFIDENCE
AND SHALL BE USED ONLY PURSUANT TO THE AGREEMENT WITH RATIO. NO OTHER USE,
L DISSEMINATION OR DUPLICATION MAY BE MADE WITHOUT PRIOR WRITTEN CONSENT OF RATIO. ALL
COMMON LAW RIGHTS OF COPYRIGHT AND OTHERWISE ARE HEREBY SPECIFICALLY RESERVED.
S8A
PROJECT NO. 19010.000
INFILL WITH LIKE WALL OFFICE
CONSTRUCTION, C211
C211 SHEET TITLE
VERIFY WALL TYPE IN S3C 120 SF
MECHANICAL
ROOM
FIELD, ALIGN TO
EXISTING FINISH
MECHANICAL
ROOM OFFICE SECOND LEVEL
C212
C215
557 SF
FACES C214
561 SF 158 SF
FLOOR PLAN - AREA
9.8 8.9 7.9 6.9 5.9 5.5 5.1 4.1 3.1 2.1 1.2
2
4/1/2021 11:43:11 AM
C2
A-301
A-104.2
1/8" = 1'-0"
GENERAL ROOFING NOTES
A. THESE GENERAL NOTES APPLY TO ROOF DRAWINGS.
B. VERIFY SIZE, LOCATION AND NUMBER OF ROOF
RHIT MOENCH
RENOVATION
PENETRATIONS INCLUDING VENTS, PIPES, CURBS, ROOF
DRAINS, CONDUITS, ETC. PROVIDE NEW FLASHING AND
SEAL PENETRATIONS WHETHER OR NOT INDICATED ON THE
DRAWINGS.
A-201
C. COMPLETE WORK ABOVE ROOF, SUCH AS MASONRY,
WELDING, MASONRY RESTORATION, ETC., PRIOR TO
5500 Wabash Avenue
A3
STARTING ROOFING WORK.
D. VERIFY AND MAINTAIN ROOF SLOPES AND DRAINAGE
PATTERNS. TEST FOR AND CORRECT ANY PONDING
Terre Haute, Indiana
CONDITIONS.
E. REPAIR AND REPLACE ROOFING SYSTEM OR STRUCTURE 47803
DAMAGED BY IMPROPER STORAGE, CONSTRUCTION
ACTIVITIES, OR LACK OF ADEQUATE TEMPORARY Owner
PROTECTION. THIS ALSO INCLUDES INTERIOR DAMAGE TO
FINISHES, EQUIPMENT, FURNISHINGS, ETC., RESULTING
Rose-Hulman Institute of Technology
FROM LEAKS. 5500 Wabash Avenue
F. NEW BLOCKING SHALL BE PRESERVATIVE-TREATED WOOD. Terre Haute, Indiana 47803
G. PAINT EXTERIOR LADDERS, BRACKETS, ETC., UNLESS 812-877-1511
C3 A-201 NOTED OTHERWISE.
A-201 H. CAP FASTENERS THAT PENETRATE ROOF DECK IN AREAS
C6 NOT CONCEALED BY CEILINGS WITH WIRE NUTS OR OTHER
MEANS ACCEPTABLE TO ARCHITECT UNLESS OTHERWISE
INDICATED. AREAS SUCH AS JANITOR CLOSETS, STORAGE
ALTERNATE: SHINGLE ROOF REPLACEMENT ROOMS, MECHANICAL AND ELECTRICAL EQUIPMENT
ROOMS, ETC., ARE EXEMPT FROM THIS REQUIREMENT
09 UNLESS OTHERWISE INDICATED.
I. REFER TO WALL SECTIONS NOTED ON ROOF PLANS FOR
INFORMATION.
J. REFER TO MECHANICAL DRAWINGS TO COORDINATE ROOF
CONDUCTOR LOCATIONS. Architect
T REV. 03/31/09 RATIO
101 South Pennsylvania Street
D.S. GENERAL RE-ROOFING NOTES Indianapolis, Indiana 46204
317-633-4040
1/2" : 1'-0" 01
DW
(VIF) A. THESE GENERAL NOTES APPLY TO ROOF DRAWINGS.
1/4" : 1'-0"
01 B. WORK SHOWN ON THE DRAWINGS SHALL BE BASE BID Structural Engineer
UNLESS SPECIFICALLY NOTED TO BE BY ALTERNATE BID.
Fink Roberts & Petrie, Inc.
1/4" : 1'-0"
1/4" : 1'-0"
C. FIELD VERIFY CONDITIONS AND COORDINATE WITH
1/2" : 1'-0" 1/2" : 1'-0"
D.S. APPROPRIATE TRADES PRIOR TO STARTING 9449 Priority Way W Dr #200
(VIF) (VIF) CONSTRUCTION. IF DISCREPANCIES ARE FOUND BETWEEN Indianapolis, Indiana 46240
01 1/2" : 1'-0" 01 CONTRACT DOCUMENTS AND ACTUAL FIELD CONDITIONS,
317-872-8400
1/4" : 1'-0"
1/4" : 1'-0"
1/4" : 1'-0"
E. PROTECT EXISTING SURFACES TO REMAIN IN AREAS Mechanical / Electrical Engineer
02 W01 D.S. D1 A-322 02
W02 3 ADJACENT TO DEMOLITION WORK. PROVIDE PLYWOOD
PROTECTION OVER EXISTING ROOF MEMBRANE AS R.E. Dimond & Associates, Inc.
REQUIRED. 732 N Capitol Avenue
7" / 12"
7" / 12"
A6 F. REPAIR FINISHES AND SURFACES LEFT EXPOSED BY
A5 A-322 Indianapolis, Indiana 46204
A-301 DEMOLITION OR REMOVAL OF EQUIPMENT USING NEW 317-634-4672
D.S. MATERIALS TO MATCH SURROUNDING SURFACES
10 10 INCLUDING ROOF DECK, SUBSTRATE, BLOCKING, ETC.
REPAIR EXISTING FINISHES TO CORRECT DEFECTS EITHER
1/2" : 1'-0" 1/2" : 1'-0" 1/2" : 1'-0" CAUSED OR EXPOSED BY DEMOLITION WORK OR
D.S.
(VIF) (VIF) (VIF) 1/2" : 1'-0" EQUIPMENT REMOVAL INCLUDING MASONRY, SHEET
(VIF) METAL, ETC. AREAS NOTED ON THE DRAWINGS TO BE
07 07 REPAIRED OR PATCHED ARE GIVEN FOR REFERENCE AND
1/4" : 1'-0"
1/4" : 1'-0"
1/4" : 1'-0"
1/4" : 1'-0"
TYP. TYP. SHALL NOT BE INTERPRETED TO LIMIT THE SCOPE OF
WORK.
G. PATCH EXISTING CEILING AND ROOF CONSTRUCTION AT
ROOF PLAN NOTES ABANDONED PENETRATION LOCATIONS WITH NEW
MATERIALS AS REQUIRED TO RECEIVE NEW FINISHES AND
A3 TO MAINTAIN ORIGINAL FIRE RATING OF ASSEMBLY WHERE
01 NEW SINGLE PLY MEMBRANE ROOFING OVER A-321 APPLICABLE.
H. REFER TO WALL SECTIONS NOTED ON ROOF PLANS FOR
SLOPED INSULATION UTILIZING EXISTING ADDITIONAL DEMOLITION INFORMATION.
WOOD OR METAL DECK. FLASH AROUND ALL I. SELECTIVE DEMOLITION, SUCH AS ROOF PENETRATIONS
1/4" : 1'-0"
1/4" : 1'-0"
EXISTING PENETRATIONS AND CURBS D.S. FOR INSTALLATION OF NEW MECHANICAL OR ELECTRICAL
05 08 06 06 08 05 WORK, SHALL BE THE RESPONSIBILITY OF THE
02 NEW STANDING SEAM METAL ROOFING OVER
1/4" : 1'-0"
1/4" : 1'-0"
TYP. TYP. TYP. TYP. CONTRACTOR OR TRADE REQUIRING THE DEMOLITION.
NEW ROOF SUBSTRATE REFER TO MECHANICAL AND ELECTRICAL DRAWINGS FOR
1/2" : 1'-0" ADDITIONAL DEMOLITION INFORMATION.
05 REPAIR EXISTING MASONRY SURROUNDING (VIF) J. REMOVE EXISTING GRAVEL BALLAST, ROOF MEMBRANE,
LIMESTONE OVERFLOWS AND DOWN FACE OF 1/2" : 1'-0" 1/2" : 1'-0" 1/2" : 1'-0"
INSULATION, THERMAL AND VAPOR BARRIERS, CANTS,
BUILDING AS REQUIRED FLASHING, COUNTERFLASHING AND COPING DOWN TO
(VIF) (VIF) (VIF)
A6 EXISTING STRUCTURAL ROOF DECK UNLESS NOTED
06 NEW SINGLE PLY MEMBRANE ROOFING OVER A-350 OTHERWISE. PLACE NEW ROOFING SYSTEM DIRECTLY
01 OVER EXISTING ROOF DECK.
NEW DUCT CHASE ENCLOSURE AS REQUIRED
K. REMOVE EXISTING SHINGLES, UNDERLAYMENT, FLASHING,
BY MEP NOTES AND DRAWINGS, REFERENCE
1/4" : 1'-0"
1/4" : 1'-0"
1/4" : 1'-0"
GUTTERS, AND INSULATION DOWN TO EXISTING
MEP NARRATIVE STRUCTURAL ROOF DECK UNLESS NOTED OTHERWISE.
A-202 A-202 PLACE NEW ROOFING SYSTEM DIRECTLY OVER EXISTING
07 NEW DUAL ROOF DRAIN WITH OVERFLOW IN B1 D.S. A1
ROOF DECK.
EXISTING ROOF DRAIN LOCATION L. REMOVE EXISTING ASPHALT AND MASTIC MATERIAL FROM
PARAPET WALLS AND SURROUNDING MATERIALS AS
08 PROVIDE HANDS-FREE FALL PROTECTION REQUIRED BY ROOF MEMBRANE SYSTEM
SYSTEM WITH DAVITS 7" / 12" 7" / 12" MANUFACTURER'S WARRANTY.
M. AT CONTRACTOR'S OPTION, REINSTALL EXISTING GRAVEL
09 NEW ROOF HATCH A-202 BALLAST IF TYPE AND SIZE IS APPROPRIATE, AND IF REUSE
D3
10 EXTEND ROOF MEMBRANE OVER EXISTING 01 A-322 IS ALLOWED UNDER REQUIRED WARRANTY. DO NOT STORE
09
PARAPET D2 BALLAST IN A MANNER THAT COULD CAUSE DAMAGE TO
2
EXISTING STRUCTURE. PROPERLY DISPOSE OF UNUSED
1/4" : 1'-0"
1/4" : 1'-0"
7" / 12"
7" / 12"
A2 D6 BALLAST OFF-SITE.
A-301 A-322 N. IF EXISTING ITEMS TO BE REMOVED OR DISTURBED ARE
02
SUSPECTED OR DISCOVERED TO CONTAIN ASBESTOS OR
OTHER HAZARDOUS MATERIALS, STOP DEMOLITION AND
1/2" : 1'-0" 1/2" : 1'-0" 1/2" : 1'-0" NOTIFY OWNER AND ARCHITECT IMMEDIATELY.
(VIF) 02(VIF) D.S. 02 (VIF) O. VERIFY SIZE, LOCATION AND NUMBER OF EXISTING ROOF
1/2" : 1'-0" PENETRATIONS INCLUDING VENTS, PIPES, CURBS, ROOF
7
6 (VIF) DRAINS, CONDUITS, ETC. PROVIDE NEW FLASHING AND
SEAL EXISTING PENETRATIONS WHETHER OR NOT
INDICATED ON THE DRAWINGS.
1/4" : 1'-0"
1/4" : 1'-0"
1/4" : 1'-0"
A6 P. COMPLETE WORK ABOVE ROOF, SUCH AS MASONRY WALL
A-350
REPAIR, WELDING, REPOINTING, ETC., PRIOR TO STARTING
1/4" : 1'-0"
RE-ROOFING WORK. SEAL | DATE 04/01/21
Q. RAISE EXISTING ROOF CURBS AND PROVIDE ADDITIONAL
BLOCKING FOR FANS, VENTS, INTAKES AND MECHANICAL
EQUIPMENT AS REQUIRED BY NEW ROOF SYSTEM AND
INSULATION THICKNESS.
R. RAISE EXISTING ROOF DRAINS, OVERFLOW DRAINS AND
SCUPPER OPENINGS AS REQUIRED BY NEW ROOF SYSTEM
1/4" : 1'-0"
1/4" : 1'-0"
AND INSULATION THICKNESS. EXTEND DRAIN PIPING AND
D.S.
REINSULATE AS REQUIRED.
S. PROVIDE NEW GRAVEL STOP AT EXTERIOR FASCIA
1/4" : 1'-0"
1/4" : 1'-0"
CONDITIONS AS REQUIRED BY NEW ROOF SYSTEM AND
INSULATION THICKNESS.
T. REMOVE EXISTING CAULKING AND PROVIDE NEW SEALANT
AT EXISTING FLASHING TO REMAIN.
1/2" : 1'-0" U. THE EXISTING ROOF SYSTEM MEMBRANE IS REPORTED TO
1/2" : 1'-0" 06 06 1/2" : 1'-0" 1/2" : 1'-0"
(VIF) BE ▐►FIRESTONE◄▌▐►CARLISLE] ▐►GOODYEAR◄▌
(VIF) (VIF) (VIF)
▐►OTHER◄▌AND IS STILL UNDER WARRANTY. WORK ON SHEET ISSUE
EXISTING ROOF AND CONNECTIONS TO EXISTING 1 Construction Documents 04/01/21
07 MEMBRANE SHALL BE PERFORMED AS REQUIRED TO
07 01
TYP. MAINTAIN CURRENT WARRANTY.
1/4" : 1'-0"
E5
3" / 12"
5
A-321 FINISHES, EQUIPMENT, FURNISHINGS, ETC., RESULTING
01 FROM LEAKS.
A-202
D3 Y. EXISTING WOOD BLOCKING SHALL REMAIN UNLESS
D.S. D.S. CONDITIONS REQUIRE REPLACEMENT OR UNLESS NOTED
OTHERWISE. NEW BLOCKING SHALL BE PRESERVATIVE-
TREATED WOOD.
Z. CAP FASTENERS THAT PENETRATE ROOF DECK IN AREAS
FRAMED OVERBUILD NOT CONCEALED BY CEILINGS WITH WIRE NUTS OR OTHER
ROOF CRICKET. MEANS ACCEPTABLE TO ARCHITECT UNLESS OTHERWISE
VERTICAL END OF INDICATED. AREAS SUCH AS JANITOR CLOSETS, STORAGE
CENTRAL MONITOR ROOMS, MECHANICAL AND ELECTRICAL EQUIPMENT
CLAD IN METAL PANEL. ROOMS, ETC., ARE EXEMPT FROM THIS REQUIREMENT
NORTH AND SOUTH UNLESS OTHERWISE INDICATED.
ENDS SIM. AA. REFER TO MECHANICAL DRAWINGS TO COORDINATE ROOF
CONDUCTOR LOCATIONS.
T
T
ALTERNATE: SHINGLE ROOF REPLACEMENT
ROOF PLAN -
C2
A-301
OVERALL
4/1/2021 11:43:18 AM
A-105
A-105
1/16" = 1'-0"
RHIT MOENCH
RENOVATION
5500 Wabash Avenue
Terre Haute, Indiana
47803
Owner
Rose-Hulman Institute of Technology
5500 Wabash Avenue
Terre Haute, Indiana 47803
812-877-1511
Architect
RATIO
101 South Pennsylvania Street
Indianapolis, Indiana 46204
317-633-4040
Structural Engineer
Fink Roberts & Petrie, Inc.
6.9 5.9 5.5 5.1 4.1 3.1 2.1
9449 Priority Way W Dr #200
Indianapolis, Indiana 46240
1/4" : 1'-0"
1/4" : 1'-0"
1/4" : 1'-0"
317-872-8400
N7 N6 N5 N4 1'-7 1/2"
A-202 B1 A1 A-202
L L Mechanical / Electrical Engineer
R.E. Dimond & Associates, Inc.
732 N Capitol Avenue
6.9 5.9 5.5 5.1 4.1 1'-7 1/2"
Indianapolis, Indiana 46204
317-634-4672
D D4 D
A-350
3"
D1
A-350
A-202
N7 N6 N5 N4
1/4" : 1'-0"
D2
M D3 M
A-322
A1 A-502 A5
2
7" / 12"
7" / 12"
1/4" : 1'-0"
1/4" : 1'-0"
8'-1 1/2"
8'-1 1/2"
A2 D6
E E A-301 A-322
1/4" : 1'-0"
7
6
D1
20'-0"
F F
20'-0"
3
F
3 G
1/4" : 1'-0"
1/4" : 1'-0"
1/4" : 1'-0"
1/4" : 1'-0"
E
2
7" / 12"
10'-1 1/4"
A6
A-322 O O D
A5
A-301
C
E6
A-351 1'-7 1/2"
A3 B 1
G A-322 G
A
1/2" : 1'-0" 7'-10" 1/2" : 1'-0"
(VIF) (VIF)
E4
A-351
KEY PLAN
1/4" : 1'-0"
1/4" : 1'-0"
1/4" : 1'-0"
1/4" : 1'-0"
H H
A3
A-321 Q 1/2" : 1'-0" 1/2" : 1'-0" 1/2" : 1'-0" Q
(VIF) (VIF) (VIF) SHEET ISSUE
1 Construction Documents 04/01/21
J J
1/4" : 1'-0"
1/4" : 1'-0"
1/4" : 1'-0"
1/4" : 1'-0"
1/4" : 1'-0"
R R
A-202
D4
K 1/2" : 1'-0" 1/2" : 1'-0" K
(VIF) (VIF)
E1
A-321
4
S S
46'-7 1/4"
1/4" : 1'-0"
1/4" : 1'-0"
14'-2 3/16"
1'-7 1/2" E5
A-202 A-202 A-321
B1 A1
L L S7 S6 S5 S4 S3 S2 COPYRIGHT NOTICE: THIS ARCHITECTURAL AND ENGINEERING DRAWING IS GIVEN IN CONFIDENCE
A-202 AND SHALL BE USED ONLY PURSUANT TO THE AGREEMENT WITH RATIO. NO OTHER USE,
D3 DISSEMINATION OR DUPLICATION MAY BE MADE WITHOUT PRIOR WRITTEN CONSENT OF RATIO. ALL
COMMON LAW RIGHTS OF COPYRIGHT AND OTHERWISE ARE HEREBY SPECIFICALLY RESERVED.
A-301
S7 S6 C2 S5 S4 S3 S2
A-301 SHEET NUMBER
RHIT MOENCH
B. INSTALL NEW ACT CEILINGS AT 1" LOWER THAN EXISTING HEIGHT UNLESS NOTED OTHERWISE.
G.C. TO COORDINATE PROVISION OF INFORMATION REGARDING EXISTING CEILING HEIGHTS.
CONFIRM ALL CEILING HEIGHTS INDICATED ON PLAN AND IMMEDIATELY REQUEST
CONFIRMATION FROM ARCHITECT IF THERE IS A CONFLICT BETWEEN HEIGHT SHOWN ON PLAN
AND ACHIEVING HEIGHT 1" LOWER THAN CURRENTLY IN FIELD.
C. UNLESS NOTED OR SHOWN OTHERWISE, EXISTING BULKHEADS ARE TO REMAIN, UNLESS
REMOVAL IS REQUIRED FOR HVAC INSTALLATION. IF REPAINTING IS REQUIRED, MATCH EXISTING
RENOVATION
FINISHES.
D. UNLESS NOTED OTHERWISE, ALL ROOMS SHOWN AS OPEN DECK TO REMAIN ARE TO ALSO 5500 Wabash Avenue
5.9 5.5 5.1 4.1 3.1 2.1 1.2 ASSUME THAT EXISTING LIGHTING IS TO REMAIN AND EXISTING CEILING FINISHES ARE TO
REMAIN..
E. UNLESS NOTED OR SHOWN OTHERWISE, ALL ROOMS SHOWN WITH NEW GRID TO RECIEVE NEW
Terre Haute, Indiana
2'X2' ACOUSTICAL CEILING GRID (BASIS OF DESIGN IS ARMSTRONG 1732 WITH TEGULAR REVEAL
EDGE AND CORRESPONDING CHICAGO METALLIC 15/16" EXPOSED TEE GRID). GRID IS INTENDED 47803
TO BE SHOWN IN THE PLANS AND INSTALLED
PAINT NEW F. AT EXISTING LOCATION SUCH THAT EXISTING LIGHTING TO BE RAISED ABOVE GRID DURING Owner
ACT-01 ACT-01 DUCTWORK TO CEILING WORK AND THEN CLEANED, SERVICED AS REQUIRED AND RELOCATED INTO NEW GRID
MATCH EXISTING ONCE CEILING WORK IS COMPLETED. THIS MEANS THAT THE CEILING GRID IS NOT NECESSARILY Rose-Hulman Institute of Technology
7'-1" A.F.F. 7'-8" A.F.F.
STRUCTURE. CENTERED IN THE ROOM TO ALLOW FOR REUSE OF LIGHTING CONDUIT. IN NEW AREAS WITH 5500 Wabash Avenue
GRID THAT DID NOT PREVIOUSLY HAVE GRID CEILING, CENTER WITHIN SPACE AS SHOWN. Terre Haute, Indiana 47803
G. CENTER PENETRATIONS IN ACOUSTICAL CEILING SYSTEMS WITHIN INDIVIDUAL CEILING PANELS, 812-877-1511
GWB EX
SUCH AS SPRINKLER HEADS, DIFFUSERS, LIGHT FIXTURES, ETC., UNLESS OTHERWISE
7'-1" A.F.F.
INDICATED.
H. PAINT NEW GYPSUM BOARD CEILING SURFACES AS SHOWN ON RCP'S.
GWB EX ROBOTICS I. PROVIDE CONTROL JOINTS (C.J.) IN GYPSUM BOARD CEILING CONSTRUCTION AS INDICATED.
7'-1 1/2" A.F.F. WORKROOM/STORAGE WHERE NOT SHOWN, PROVIDE MAXIMUM SPACING BETWEEN JOINTS OF 30'-0”. VERIFY FINAL
M M
DL207A CONTROL JOINT LOCATIONS WITH ARCHITECT PRIOR TO STARTING WORK WHETHER OR NOT
ACT-01 ACT-01 INDICATED ON THE DRAWINGS.
7'-1 1/2" A.F.F. 7'-8" A.F.F. J. CEILING ACCESS PANELS INDICATED ARE NOT INTENDED TO LIMIT NUMBER OF PANELS
MATERIALS
LAB REQUIRED. PANEL QUANTITY SHALL BE SUFFICIENT TO PROVIDE REQUIRED ACCESS WHETHER
OR NOT INDICATED ON THE DRAWINGS. VERIFY FINAL LOCATIONS WITH ARCHITECT PRIOR TO
CL207
STARTING WORK.
STAIR ACT-01 K. NEW EXPOSED DUCTS/ HVAC UNITS AT EXPOSED STAINED WOOD DECK CEILINGS TO BE BRUSH
A2 8'-10" A.F.F. Architect
A-301 CL211 PAINTED IN APPROPRIATE COATING TO MATCH PT-01, VERIFY COLOR OF PAINT AT ALL OTHER
LOCATIONS OF EXPOSED DUCTWORK AND HVAC UNITS. RATIO
101 South Pennsylvania Street
Indianapolis, Indiana 46204
21 CEILING LEGEND 317-633-4040
CUSTODIAL
STORAGE
STORAGE
N CL202B ACT-01 N CEILING TAG
CL212 Structural Engineer
7'-8" A.F.F.
CEILING TYPE Fink Roberts & Petrie, Inc.
XXX-01
10'-10" A.F.F. 9449 Priority Way W Dr #200
CEILING HEIGHT
CUSTODIAL (ABOVE FINISH FLOOR) Indianapolis, Indiana 46240
SERVICES 317-872-8400
CL202
25 25 25
WORK
OFFICE INSTRUMENT SHOP
CUSTODIAL CL203 STORAGE CL206
EXPOSED STRUCTURE TO REMAIN AS-
STORAGE CL205 IS UNLESS NOTED OTHERWISE. NEW BUILDING STANDARD 2'X2' GRID AND
CL202A DUCTWORK AND HVAC EQUIPMENT TO CEILING TILES
ACT-01 ACT-01 ACT-01 BE PREPPED AND DRYFALL PAINTED
8'-0" A.F.F. 8'-0" A.F.F. 8'-0" A.F.F. TO MATCH EXISTING EXPOSED
STRUCTURE WHERE APPLICABLE.
U.N.O. EXISTING LIGHTING TO BE
REUSED, BUT MAY NEED TO BE
RELOCATED DURING INSTALLATION OF
P P NEW HVAC AND DRYFALL PAINTING.
AREA N.I.C.
Q Q
COFFERED CIELING AT NORTH END ARE TO REMAIN. REPLACE EXISTING WOOD SLAT CEILING WITH
NEW 2X2 ACT CEILING.
33 REPAIR PORTION OF DEMOLISHED CEILING AND FLOOR ABOVE IF APPLICABLE TO MATCH EXISITNG
CONSTRUCTION ASSEMBLY AND MATERIALS SUCH THAT REPAIR IS VISIBLY SEAMLESS, INCLUDING SHEET NUMBER
FLOORING FINISHES ON LEVEL ABOVE.
A-131.1
N10 N9 N8 N7 N6 N5 N4 N3 N2 N1 GENERAL CEILING PLAN NOTES
A. THESE GENERAL NOTES APPLY TO SERIES A-130 REFLECTED CEILING DRAWINGS.
B. INSTALL NEW ACT CEILINGS AT 1" LOWER THAN EXISTING HEIGHT UNLESS NOTED OTHERWISE.
A5
G.C. TO COORDINATE PROVISION OF INFORMATION REGARDING EXISTING CEILING HEIGHTS.
CONFIRM ALL CEILING HEIGHTS INDICATED ON PLAN AND IMMEDIATELY REQUEST
RHIT MOENCH
CONFIRMATION FROM ARCHITECT IF THERE IS A CONFLICT BETWEEN HEIGHT SHOWN ON PLAN
A
A-622
A
AND ACHIEVING HEIGHT 1" LOWER THAN CURRENTLY IN FIELD.
C. UNLESS NOTED OR SHOWN OTHERWISE, EXISTING BULKHEADS ARE TO REMAIN, UNLESS
REMOVAL IS REQUIRED FOR HVAC INSTALLATION. IF REPAINTING IS REQUIRED, MATCH EXISTING
RENOVATION
FINISHES.
D. UNLESS NOTED OTHERWISE, ALL ROOMS SHOWN AS OPEN DECK TO REMAIN ARE TO ALSO 5500 Wabash Avenue
ASSUME THAT EXISTING LIGHTING IS TO REMAIN AND EXISTING CEILING FINISHES ARE TO
REMAIN..
E. UNLESS NOTED OR SHOWN OTHERWISE, ALL ROOMS SHOWN WITH NEW GRID TO RECIEVE NEW
Terre Haute, Indiana
2'X2' ACOUSTICAL CEILING GRID (BASIS OF DESIGN IS ARMSTRONG 1732 WITH TEGULAR REVEAL
EDGE AND CORRESPONDING CHICAGO METALLIC 15/16" EXPOSED TEE GRID). GRID IS INTENDED 47803
TO BE SHOWN IN THE PLANS AND INSTALLED
F. AT EXISTING LOCATION SUCH THAT EXISTING LIGHTING TO BE RAISED ABOVE GRID DURING Owner
CEILING WORK AND THEN CLEANED, SERVICED AS REQUIRED AND RELOCATED INTO NEW GRID
ONCE CEILING WORK IS COMPLETED. THIS MEANS THAT THE CEILING GRID IS NOT NECESSARILY Rose-Hulman Institute of Technology
CENTERED IN THE ROOM TO ALLOW FOR REUSE OF LIGHTING CONDUIT. IN NEW AREAS WITH 5500 Wabash Avenue
GRID THAT DID NOT PREVIOUSLY HAVE GRID CEILING, CENTER WITHIN SPACE AS SHOWN. Terre Haute, Indiana 47803
G. CENTER PENETRATIONS IN ACOUSTICAL CEILING SYSTEMS WITHIN INDIVIDUAL CEILING PANELS, 812-877-1511
B B SUCH AS SPRINKLER HEADS, DIFFUSERS, LIGHT FIXTURES, ETC., UNLESS OTHERWISE
INDICATED.
H. PAINT NEW GYPSUM BOARD CEILING SURFACES AS SHOWN ON RCP'S.
I. PROVIDE CONTROL JOINTS (C.J.) IN GYPSUM BOARD CEILING CONSTRUCTION AS INDICATED.
STORAGE WHERE NOT SHOWN, PROVIDE MAXIMUM SPACING BETWEEN JOINTS OF 30'-0”. VERIFY FINAL
FL206 STORAGE ELECTRICAL CONTROL JOINT LOCATIONS WITH ARCHITECT PRIOR TO STARTING WORK WHETHER OR NOT
FL205 SWITCH INDICATED ON THE DRAWINGS.
GEAR J. CEILING ACCESS PANELS INDICATED ARE NOT INTENDED TO LIMIT NUMBER OF PANELS
MECHANICAL REQUIRED. PANEL QUANTITY SHALL BE SUFFICIENT TO PROVIDE REQUIRED ACCESS WHETHER
FL203
FL201 OR NOT INDICATED ON THE DRAWINGS. VERIFY FINAL LOCATIONS WITH ARCHITECT PRIOR TO
STARTING WORK.
K. NEW EXPOSED DUCTS/ HVAC UNITS AT EXPOSED STAINED WOOD DECK CEILINGS TO BE BRUSH
PAINTED IN APPROPRIATE COATING TO MATCH PT-01, VERIFY COLOR OF PAINT AT ALL OTHER
Architect
LOCATIONS OF EXPOSED DUCTWORK AND HVAC UNITS. RATIO
C C 101 South Pennsylvania Street
Indianapolis, Indiana 46204
317-633-4040
CEILING LEGEND
MECHANICAL 1/8" = 1'-0" Structural Engineer
FL202
CEILING TAG Fink Roberts & Petrie, Inc.
CEILING TYPE 9449 Priority Way W Dr #200
XXX-01 Indianapolis, Indiana 46240
10'-10" A.F.F. CEILING HEIGHT 317-872-8400
CIRCULATION
9.8 8.9 7.9 - 6.9 5.9 5.5 5.1 4.1 3.1 2.1 1.2 (ABOVE FINISH FLOOR)
DW
MAIL DIST.
ELEVATOR CENTER DELIVERY PAINT NEW
MECHANICAL ANNEX
ELEV 1 CAGE DUCTWORK TO
EL203 EL204
- - MATCH EXISTING
ACT-01 ACT-01 STRUCTURE EXPOSED STRUCTURE TO REMAIN AS-
ACT-01 7'-3" A.F.F. 8'-5" A.F.F. IS UNLESS NOTED OTHERWISE. NEW BUILDING STANDARD 2'X2' GRID AND
8'-3" A.F.F. DUCTWORK AND HVAC EQUIPMENT TO CEILING TILES
E E
BE PREPPED AND DRYFALL PAINTED
FAB. LAB FAB. LAB TO MATCH EXISTING EXPOSED
STOCK STOCK PAINT NEW STRUCTURE WHERE APPLICABLE.
OFFICE STORAGE STORAGE DUCTWORK TO U.N.O. EXISTING LIGHTING TO BE
EL202A CL208 CL208 MATCH EXISTING REUSED, BUT MAY NEED TO BE
STRUCTURE RELOCATED DURING INSTALLATION OF
ACT-01
NEW HVAC AND DRYFALL PAINTING.
8'-0" A.F.F.
F MACHINE F
TOOL LAB FABRICATION
II LAB AREA N.I.C.
EL202 EL207
CIRCULATION
EL211 TOOL
ROOM
STAIR EL205
- GWB EX CEILING PLAN NOTES
A5 7'-8" A.F.F.
ACT-01 F
A-301
ACT-01
8'-3" A.F.F. 8'-0" A.F.F.
EXP
PAINT NEW
DUCTWORK TO
3 G
18 01 IF POSSIBLE, REUSE EXISTNG VERTICAL AND PORTION OF HORIZONTAL FACE OF EXISITNG
9'-0" A.F.F. MATCH EXISTING
STRUCTURE BULkHEAD TO CREATE PERIMETER OF NEW ACT CEILING AS SHOWN. REPAINT AS REQUIRED TO
E
2
MATCH EXISTING BUIDLING STANDARD. D
G GWB EX G
7'-2" A.F.F. 02 RECONSTRUCT PERIMETER BULKHEADS WHERE HVAC WORK REQUIRED REMOVAL TO REPLICATE
ORIGINAL CONSTRUCTION AND LIGHTING. C
03 PROVIDE NEW SURFACE MOUNTED LINEAR LIGHTING TO MATCH OTHER LINEAR LIGHTING ON THIS
ACT-01
8'-10" A.F.F.
FLOOR. PATCH AND PAINT EXPOED CEILING ELEMENTS AS REQUIRED. B 1
04
PAINT NEW A
DUCTWORK TO 05 NO HEADER AT THIS LOCATION . PROVIDE BLOCKING ABOVE CEIILNG TO SUPPORT DOOR FRAME
MATCH EXISTING INSERTED WITHINT FINISHED OPENING. DRYWALL CEILING IS CONTINUOUS.
STRUCTURE
08 PROVIDE ALTERNATE BID TO REPLACE EXISTING LIGHTING WITH NEW SURFACE MOUNTED LINEARS KEY PLAN
ACT-01 ACT-01 TO MATCH OTHER LINEAR LIGHITNG ON THIS FLOOR. INCLUDE POSSIBLE TOUCH UP THAT MAY BE
7'-6" A.F.F. 7'-8" A.F.F. MACHINE
TOOL REQUIRED TO CEILING AFTER CHANGE IN LIGHTING.
SEAL | DATE 04/01/21
H ACT-01 SHOP H 09 ACOUSTICAL LINEAR WOOD PLANK CEILING EQUAL TO ARMSTRONG WOODWORKS GRILLE WITH
8'-0" A.F.F. DL202
INSTRUCTIONAL NRC OF .90. WHERE SHOWN, ASSUME RECESSED LINEAR LIGHTING EQUAL TO FOCAL POINT SEEM
MENS R.R. TECHNOLOGY I.T. 2.
DL203 DL204 EQUIP./OFFICE
DL204A 11 DESIGN INTENT IS TO EXPOSED STRUCTURE CEILING - PAINT DRYFALL PAINT IF NOT WOOD TIMBER.
. PROVIDE SURFACE MOUNTED LED LINEAR FIXTURES TO MATCH NEW BUILDING STANDARD IN
QUANTITIES AND PLACEMENT TO ACHIEVE APPROPRIATE FOOTCANDLE LEVELS RECOMMENDED
FOR INDICATED ROOM FUNCTION PER IES STANDARDS IF EXPOSING THE EXISTING STRUCTURE IS
NOT POSSIBLE DUE TO UNFORESEEN CIRCUMSTANCES, PROVIDE STANDARD 2'X2' ACT TILE WITH
NEW RECESSED LIGHTING AS SHOWN.
12 EXPOSED STRUCTURE CEILING. RECONFIGURE DUCTS, PIPES AND CONDUIT AS REQUIRED TO
J J
MINIMIZE IN EXPOSED AREAS WHERE POSSIBLE, DRYFALL PAINT AND PROVIDE PROVIDE NEW
LIGHTING AS SHOWN IN ELECTRICAL PLANS. SHEET ISSUE
ACT-01 1 Construction Documents 04/01/21
MANAGER
7'-10" A.F.F. 14 REPAINT DRYWALL AND REPLACE EXISTING DOWNLIGHTS WITH NEW LED DOWNLIGHTS.
OFFICE OFFICE
DL204B DL205 17 PROVIDE MOTORIZED PROJECTION SCREEN AT FRONT OF ROOM AND PROJECTOR MOUNT TO
ACT-01 COORDINATE WITH PROJECTOR AND SPACED AS REQUIRED. COORDINATE STRUCTURAL SUPPORT
7'-6" A.F.F.
PAINT NEW AS REQUIRED.
ACT-01 CIRCULATION DUCTWORK TO 18 PROVIDE NEW CEILING WITH NEW LIGHTING AS SHOWN. IF NO NEW LIGHTING IS SHOWN, DESIGN
7'-8" A.F.F. - MATCH EXISTING
WORK
STRUCTURE INTENT IS TO REUSE EXISTING WALL SCONCES. COORDINATE WITH ELECTRICAL LIGHTING PLANS
SHOP OFFICE AS REQUIRED. PATCH TOP OF PERIMETER WALLS AS REQUIRED WHERE EXISTING CEILNGS WERE
DL206A DL206
REMOVED.
ACT-01
7'-8" A.F.F. MANUFACTURING 19 PROVIDE SOUND BOOTS AT HVAC ABOVE CEILING AND INSULATE AS REQUIRED ABOVE CEILING TO
K LAB K MITIGATE SOUND TRANSFER BETWEEN OFFICES.
DL201
21 IF POSSIBLE, EXISTING DRYWALL BULIKHEAD AND/OR CEILING AND LIGHTING ARE TO REMAIN;. iF
ACT-01
8'-10" A.F.F. CEILING MUST BE PARTIALLY DEMOLISHED TO ACCOMODATE NEW HVAC CONFIGURATION, PATCH
WITH NEW AS NEEDED AND REPAINT BULKHEAD. IF ADJACENT DRYWALL CEILING AT HIGHER
ELEVATION IS BEING REMOVED TO BE REPLACED BY ACT GRID CIELING, DEISGN INTENT IS FOR
NEW ACT CEILING TO BE 1" LOWER THAN REMOVED DRYWALL SUCH THAT MINIMAL TOUCH UP
ACT-01 WORK IS REQUIRED AT PERIMETER OF BULKHEAD TO REMIAN. REUSE LIGHTING IF POSSIBLE.
7'-8" A.F.F.
CONFIRM DESIGN INTENT WITH ARCHITECT PRIOR TO REPLACEMENT.
AREA 2
AREA 2 23 NEW SURFACE MOUNTED LINEAR LIGHTING TO MATCH OTHER FIXTURES ON THIS FLOOR. THESE
ROBOTICS ARE REPLACING FIXTURES WITH RED HOUSING THAT WERE REMOVED.
CLASSROOM
L DL207 L 25 DESIGN INTENT IS FOR NEWLY CONSTRUCTED CEIING AND LIGHTING TO REMAIN. IF MECHANICAL
AREA 1
AREA 1 WORK PROHIBITS THIS, SALVAGE REMOVED COMPONENTRY AND REINSTALL OR REPLACE WITH
GWB EX
NEW TO MATCH EXISTING.
7'-1" A.F.F. 26 REFERENCE ELECTRICAL DRAWINGS FOR NEW LIGHTING IN NEWLY CONSTRUCTED ROOMS.
PAINT NEW
ACT-01 ACT-01 DUCTWORK TO 27 ADDED FIXTURE FOR INCREASED LIGHT LEVEL
7'-1" A.F.F. 7'-8" A.F.F. MATCH EXISTING 29 ALIGN EXTENDED NEW GRID WITH EXISTING. GRID AND TILE MUST MATCH EXISTING ADJACENT
STRUCTURE. COPYRIGHT NOTICE: THIS ARCHITECTURAL AND ENGINEERING DRAWING IS GIVEN IN CONFIDENCE
CEILING AND EXTENSION TO APPEAR SEAMLESS. AND SHALL BE USED ONLY PURSUANT TO THE AGREEMENT WITH RATIO. NO OTHER USE,
DISSEMINATION OR DUPLICATION MAY BE MADE WITHOUT PRIOR WRITTEN CONSENT OF RATIO. ALL
GWB EX 30 EXISTING HARDLID CEILING AND SUSPENDED CLOUDS REQUIRE REMOVAL FOR HVAC WORK.. COMMON LAW RIGHTS OF COPYRIGHT AND OTHERWISE ARE HEREBY SPECIFICALLY RESERVED.
7'-1" A.F.F. PROVIDE NEW 2'X2' ACT GRID AND CEILING AS SHOWN. REUSE EXISTING LINEAR PENDANTS AND PROJECT NO. 19010.000
ADD ADDITIONAL LIGHTING FOR NEW LIVE VEGETATION WALL AND DECORATIVE PENDANTS AT
GWB EX ROBOTICS CAFE. AS SHOWN IN ELECTRICAL DRAWINGS.. SHEET TITLE
7'-1 1/2" A.F.F. WORKROOM/STORAGE
DL207A 31 PROVIDE NEW DRYWALL BULKHEAD AS SHOWN TO MATCH CONSTRUCTION ASSEMBLY OF OTHER
BULKHEADS IN ADJACENT AREA.
LOWER LEVEL 2
32 REMOVE HORIZONTAL PORTIONS OF HARDLID CEILINGS ON SOUTH ABOVE STAGE AND ALONG REFLECTED CEILING
EAST WALL. VERTICAL PORTION OF THESE BULKHEADS CAN REMAIN FOR EASE OF
RECONSTRUCITON AFTER HVAC WORK IS COMPLETED. DRYWALL WRAPPED TRUSSES AND PLAN - AREA 2
4/1/2021 12:07:11 PM
9.8 8.9 7.9 6.9 5.9 5.5 5.1 4.1 3.1 2.1 1.2
COFFERED CIELING AT NORTH END ARE TO REMAIN. REPLACE EXISTING WOOD SLAT CEILING WITH
NEW 2X2 ACT CEILING.
1 FIRST LEVEL RCP 33 REPAIR PORTION OF DEMOLISHED CEILING AND FLOOR ABOVE IF APPLICABLE TO MATCH EXISITNG SHEET NUMBER
A-131.2
1/8" = 1'-0" CONSTRUCTION ASSEMBLY AND MATERIALS SUCH THAT REPAIR IS VISIBLY SEAMLESS, INCLUDING
FLOORING FINISHES ON LEVEL ABOVE.
A-131.2
GENERAL CEILING PLAN NOTES
9.8 8.9 7.9 6.9 5.9 5.5 5.1 4.1 3.1 2.1 1.2
A. THESE GENERAL NOTES APPLY TO SERIES A-130 REFLECTED CEILING DRAWINGS.
RHIT MOENCH
B. INSTALL NEW ACT CEILINGS AT 1" LOWER THAN EXISTING HEIGHT UNLESS NOTED OTHERWISE.
G.C. TO COORDINATE PROVISION OF INFORMATION REGARDING EXISTING CEILING HEIGHTS.
CONFIRM ALL CEILING HEIGHTS INDICATED ON PLAN AND IMMEDIATELY REQUEST
CONFIRMATION FROM ARCHITECT IF THERE IS A CONFLICT BETWEEN HEIGHT SHOWN ON PLAN
OFFICE
AND ACHIEVING HEIGHT 1" LOWER THAN CURRENTLY IN FIELD.
C. UNLESS NOTED OR SHOWN OTHERWISE, EXISTING BULKHEADS ARE TO REMAIN, UNLESS
REMOVAL IS REQUIRED FOR HVAC INSTALLATION. IF REPAINTING IS REQUIRED, MATCH EXISTING
RENOVATION
ACT-01 GWB EX
GWB EX
7'-6" A.F.F.
7'-6 1/2" A.F.F. 7'-6 1/2" A.F.F.
CL109 FINISHES.
D. UNLESS NOTED OTHERWISE, ALL ROOMS SHOWN AS OPEN DECK TO REMAIN ARE TO ALSO 5500 Wabash Avenue
B1 ASSUME THAT EXISTING LIGHTING IS TO REMAIN AND EXISTING CEILING FINISHES ARE TO
ACT-01
7'-11" A.F.F.
WD BEAM
ACT-01
7'-11" A.F.F.
ACT-01
8'-0" A.F.F.
18 18 A-540 1'-6"
ACT-01
OPEN TO
LEVEL 1
REMAIN..
E. UNLESS NOTED OR SHOWN OTHERWISE, ALL ROOMS SHOWN WITH NEW GRID TO RECIEVE NEW
Terre Haute, Indiana
WD BEAM
7'-9" A.F.F. WD BEAM
7'-9" A.F.F.
7'-9" A.F.F. 1'-0"
01
GWB EX
7'-9" A.F.F.
B1
A-540
01
18 7'-10" A.F.F. 2'X2' ACOUSTICAL CEILING GRID (BASIS OF DESIGN IS ARMSTRONG 1732 WITH TEGULAR REVEAL
EDGE AND CORRESPONDING CHICAGO METALLIC 15/16" EXPOSED TEE GRID). GRID IS INTENDED 47803
M 01 M TO BE SHOWN IN THE PLANS AND INSTALLED
21 F. AT EXISTING LOCATION SUCH THAT EXISTING LIGHTING TO BE RAISED ABOVE GRID DURING Owner
WD BEAM WD BEAM ACT-01 B1 CEILING WORK AND THEN CLEANED, SERVICED AS REQUIRED AND RELOCATED INTO NEW GRID
7'-9" A.F.F. 7'-9" A.F.F. 8'-0" A.F.F. GWB EX
ACT-01 EXP A-540
21 ONCE CEILING WORK IS COMPLETED. THIS MEANS THAT THE CEILING GRID IS NOT NECESSARILY Rose-Hulman Institute of Technology
7'-6" A.F.F. 7'-9" A.F.F.
7'-11" A.F.F. GWB EX
H BAR
CENTERED IN THE ROOM TO ALLOW FOR REUSE OF LIGHTING CONDUIT. IN NEW AREAS WITH 5500 Wabash Avenue
M.T.F. 8'-0" A.F.F.
NON-LINEAR GRID THAT DID NOT PREVIOUSLY HAVE GRID CEILING, CENTER WITHIN SPACE AS SHOWN. Terre Haute, Indiana 47803
MEASUREMENT STAIR EL108
OPTICS CONFERENCE G. CENTER PENETRATIONS IN ACOUSTICAL CEILING SYSTEMS WITHIN INDIVIDUAL CEILING PANELS, 812-877-1511
LAB CIRCULATION -
A2 LAB ROOM SUCH AS SPRINKLER HEADS, DIFFUSERS, LIGHT FIXTURES, ETC., UNLESS OTHERWISE
A-301
CL114 - INDICATED.
CL115 CL116 OPEN TO
ACT-01 LEVEL 1 H. PAINT NEW GYPSUM BOARD CEILING SURFACES AS SHOWN ON RCP'S.
7'-11" A.F.F. I. PROVIDE CONTROL JOINTS (C.J.) IN GYPSUM BOARD CEILING CONSTRUCTION AS INDICATED.
WHERE NOT SHOWN, PROVIDE MAXIMUM SPACING BETWEEN JOINTS OF 30'-0”. VERIFY FINAL
GWB EX GWB EX B1 GWB EX GWB EX GWB EX CONTROL JOINT LOCATIONS WITH ARCHITECT PRIOR TO STARTING WORK WHETHER OR NOT
GWB EX EXP GWB EX 7'-6" A.F.F. 7'-6" A.F.F. 7'-6" A.F.F.
7'-6" A.F.F. 7'-6" A.F.F. A-540 INDICATED ON THE DRAWINGS.
7'-6" A.F.F. 7'-9" A.F.F. 7'-6 1/2" A.F.F.
ACT-03 21 J. CEILING ACCESS PANELS INDICATED ARE NOT INTENDED TO LIMIT NUMBER OF PANELS
N 7'-11" A.F.F. 01 N REQUIRED. PANEL QUANTITY SHALL BE SUFFICIENT TO PROVIDE REQUIRED ACCESS WHETHER
18 B1 OR NOT INDICATED ON THE DRAWINGS. VERIFY FINAL LOCATIONS WITH ARCHITECT PRIOR TO
18 01 18 ACT-01 ACT-01
1'-0" 1'-0" A-540 01 ACT-01 STARTING WORK.
GWB EX B1 ACT-01 7'-11" A.F.F. 7'-11" A.F.F.
7'-6" A.F.F. 1'-6" 7'-11" A.F.F. K. NEW EXPOSED DUCTS/ HVAC UNITS AT EXPOSED STAINED WOOD DECK CEILINGS TO BE BRUSH
A-540 7'-9" A.F.F. B1 Architect
PAINTED IN APPROPRIATE COATING TO MATCH PT-01, VERIFY COLOR OF PAINT AT ALL OTHER
A-540
GWB EX 01 ACT-01 ACT-01 ADMIN
LOCATIONS OF EXPOSED DUCTWORK AND HVAC UNITS. RATIO
7'-7" A.F.F. GWB EX 7'-6 1/2" A.F.F. 7'-11" A.F.F. 101 South Pennsylvania Street
OFFICE OFFICE OFFICE
7'-9" A.F.F. Indianapolis, Indiana 46204
CL108 CL106 CL105
EXP OFFICE CEILING LEGEND 317-633-4040
9'-8" A.F.F. CL107
ACT-03
7'-11" A.F.F. WD BEAM CEILING TAG Structural Engineer
EXP 7'-9" A.F.F.
7'-9" A.F.F. CEILING TYPE Fink Roberts & Petrie, Inc.
WD BEAM XXX-01
O 21 21 21 21 O 10'-10" A.F.F.
9449 Priority Way W Dr #200
7'-9" A.F.F. CEILING HEIGHT
PHYSICS GWB EX GWB EX WD BEAM Indianapolis, Indiana 46240
21 7'-9" A.F.F. (ABOVE FINISH FLOOR) 317-872-8400
LAB 3 7'-1 1/2" A.F.F. 7'-1 1/2" A.F.F.
CL117 ACT-01
CIRCULATION 7'-11" A.F.F. ACT-01
CLASSROOM - 7'-11" A.F.F. SPOT ELEVATION MARKER
CL119 Mechanical / Electrical Engineer
ACT-01 OFFICE
7'-7" A.F.F. EXP ELECTRICAL E.I.T. STORAGE R.E. Dimond & Associates, Inc.
ROOM CL102A CL102B CL104
9'-8" A.F.F.
CL101 48 SF 107 SF ACT-01 OPTICAL 184 SF 732 N Capitol Avenue
EXISTING PAINTED GYB BOARD CEILING NEW OR PATCHED PAINTED GYB BOARD
GWB EX 81 SF
EXP EXP 7'-11" A.F.F. COMMUNICATIONS Indianapolis, Indiana 46204
LAB OR BULKHEAD AS SHOWN ON PLAN CEILING OR BULKHEAD AS SHOWN ON
7'-6" A.F.F. 10'-0" A.F.F. 10'-0" A.F.F. 317-634-4672
EXP CL103 PLAN
10'-0" A.F.F.
P P
ACT-01
8'-0" A.F.F. EXPOSED STRUCTURE TO REMAIN AS-
IS UNLESS NOTED OTHERWISE. NEW BUILDING STANDARD 2'X2' GRID AND
ACT-01 OFFICE DUCTWORK AND HVAC EQUIPMENT TO CEILING TILES
ACT-01
8'-0" A.F.F. EXP 7'-11" A.F.F. BL103 BE PREPPED AND DRYFALL PAINTED
ACT-01 ENGINEERING OFFICE TO MATCH EXISTING EXPOSED
9'-8" A.F.F. ACT-01
7'-10" A.F.F. PHYSICS STRUCTURE WHERE APPLICABLE.
7'-11" A.F.F. ACT-01 ACT-01 BL102
LAB 1 U.N.O. EXISTING LIGHTING TO BE
MATERIALS 7'-11" A.F.F. 7'-11" A.F.F.
BL110 REUSED, BUT MAY NEED TO BE
PROCESSING
ACT-01 RELOCATED DURING INSTALLATION OF
LAB
7'-11" A.F.F. NEW HVAC AND DRYFALL PAINTING.
BL112 GWB EX GWB EX
7'-6" A.F.F. 7'-6" A.F.F.
PHYSICS GWB EX GWB EX
Q LAB 1 7'-7" A.F.F. 7'-6" A.F.F. Q
EXISTING EXPOSED WOOD BEAM ARMSTRONG WOODWORKS ACOUSTICAL
BL113 OFFICE
GWB EX GWB EX GWB-X1 ACT-01 PLANK CLOUD
ACT-01 7'-6" A.F.F. BL104 8'-0" A.F.F.
7'-7" A.F.F. 7'-6" A.F.F.
8'-0" A.F.F.
PHYSICS
STOCK OFFICE
ACT-01 ACT-01 ACT-01
7'-10" A.F.F. ROOM BL109 ACT-01 OFFICE AREA N.I.C.
7'-11" A.F.F. BL108 8'-0" A.F.F. 7'-11" A.F.F. BL101
ACT-01
GWB EX 7'-11" A.F.F. OFFICE
18 EXP
7'-9" A.F.F. 9'-8" A.F.F. BL105
GWB EX GWB EX
GWB EX 7'-6" A.F.F.
CIRCULATION 7'-6" A.F.F.
7'-6" A.F.F.
-
R GWB EX 21 R CEILING PLAN NOTES
7'-7" A.F.F.
F
GWB EX
7'-9" A.F.F.
18 GWB EX
7'-6" A.F.F.
GWB EX
7'-6" A.F.F.
GWB EX
7'-6" A.F.F. GWB EX 3 G
01 7'-6" A.F.F. 01 IF POSSIBLE, REUSE EXISTNG VERTICAL AND PORTION OF HORIZONTAL FACE OF EXISITNG
ACT-01
7'-9" A.F.F.
B1
A-540 BULkHEAD TO CREATE PERIMETER OF NEW ACT CEILING AS SHOWN. REPAINT AS REQUIRED TO
E
2
MATCH EXISTING BUIDLING STANDARD.
7'-11" A.F.F.
ACT-01 ACT-01 D
MACHINE
ACT-01
ACT-01 8'-0" A.F.F. 8'-0" A.F.F.
ELECTRICAL SHOP OFFICE 02 RECONSTRUCT PERIMETER BULKHEADS WHERE HVAC WORK REQUIRED REMOVAL TO REPLICATE
7'-10" A.F.F. ROOM GWB EX EXP
7'-9" A.F.F. 9'-8" A.F.F. BL107
OFFICE
BL100 ORIGINAL CONSTRUCTION AND LIGHTING. C
BL115
BL106 03 PROVIDE NEW SURFACE MOUNTED LINEAR LIGHTING TO MATCH OTHER LINEAR LIGHTING ON THIS
EXP
10'-0" A.F.F.
GWB EX
7'-2" A.F.F.
GWB EX
7'-6" A.F.F.
GWB EX
7'-6" A.F.F.
GWB EX ACT-01
FLOOR. PATCH AND PAINT EXPOED CEILING ELEMENTS AS REQUIRED. B 1
PHYSICS
7'-6" A.F.F. 8'-0" A.F.F. 04
LAB 2 21 A
S 21 S 05 NO HEADER AT THIS LOCATION . PROVIDE BLOCKING ABOVE CEIILNG TO SUPPORT DOOR FRAME
BL114 CIRCULATION ACT-01
GWB EX - 01 INSERTED WITHINT FINISHED OPENING. DRYWALL CEILING IS CONTINUOUS.
ACT-01 B1 8'-0" A.F.F.
7'-7" A.F.F. ELEV 2 8'-8" A.F.F. 21 08 PROVIDE ALTERNATE BID TO REPLACE EXISTING LIGHTING WITH NEW SURFACE MOUNTED LINEARS
21 A-540 KEY PLAN
- TO MATCH OTHER LINEAR LIGHITNG ON THIS FLOOR. INCLUDE POSSIBLE TOUCH UP THAT MAY BE
CUSTODIAL 1'-6" 21
STORAGE OPEN TO LEVEL REQUIRED TO CEILING AFTER CHANGE IN LIGHTING.
ACT-01 BL116 2 SKYLIGHT- SEAL | DATE 04/01/21
7'-10" A.F.F. ACT-01 ACT-01 ACT-01
09 ACOUSTICAL LINEAR WOOD PLANK CEILING EQUAL TO ARMSTRONG WOODWORKS GRILLE WITH
S10 S9 S8 S7 S6 21 7'-8" A.F.F. S5 7'-8" A.F.F. S4 S3 GWB EX S2 S1
EXP
7'-8" A.F.F. 8'-0" A.F.F. NRC OF .90. WHERE SHOWN, ASSUME RECESSED LINEAR LIGHTING EQUAL TO FOCAL POINT SEEM
8'-8" A.F.F. ELEVATOR OFFICE OFFICE OFFICE 2.
MECHANICAL AL104 AL103 AL102 11 DESIGN INTENT IS TO EXPOSED STRUCTURE CEILING - PAINT DRYFALL PAINT IF NOT WOOD TIMBER.
21
BL117 . PROVIDE SURFACE MOUNTED LED LINEAR FIXTURES TO MATCH NEW BUILDING STANDARD IN
QUANTITIES AND PLACEMENT TO ACHIEVE APPROPRIATE FOOTCANDLE LEVELS RECOMMENDED
T T
FOR INDICATED ROOM FUNCTION PER IES STANDARDS IF EXPOSING THE EXISTING STRUCTURE IS
GWB EX NOT POSSIBLE DUE TO UNFORESEEN CIRCUMSTANCES, PROVIDE STANDARD 2'X2' ACT TILE WITH
8'-0" A.F.F. ACT-01
8'-8" A.F.F. NEW RECESSED LIGHTING AS SHOWN.
STORAGE
ART AL101A
CURATOR 12 EXPOSED STRUCTURE CEILING. RECONFIGURE DUCTS, PIPES AND CONDUIT AS REQUIRED TO
9.8 8.9 7.9 6.9 5.9 5.5 5.1 4.1 3.1 AL101 2.1 1.2 MINIMIZE IN EXPOSED AREAS WHERE POSSIBLE, DRYFALL PAINT AND PROVIDE PROVIDE NEW
LIGHTING AS SHOWN IN ELECTRICAL PLANS. SHEET ISSUE
1 Construction Documents 04/01/21
14 REPAINT DRYWALL AND REPLACE EXISTING DOWNLIGHTS WITH NEW LED DOWNLIGHTS.
WATER ROOM 17 PROVIDE MOTORIZED PROJECTION SCREEN AT FRONT OF ROOM AND PROJECTOR MOUNT TO
AL106
50 SF COORDINATE WITH PROJECTOR AND SPACED AS REQUIRED. COORDINATE STRUCTURAL SUPPORT
AS REQUIRED.
U U 18 PROVIDE NEW CEILING WITH NEW LIGHTING AS SHOWN. IF NO NEW LIGHTING IS SHOWN, DESIGN
EXP
10'-0" A.F.F. INTENT IS TO REUSE EXISTING WALL SCONCES. COORDINATE WITH ELECTRICAL LIGHTING PLANS
AS REQUIRED. PATCH TOP OF PERIMETER WALLS AS REQUIRED WHERE EXISTING CEILNGS WERE
REMOVED.
19 PROVIDE SOUND BOOTS AT HVAC ABOVE CEILING AND INSULATE AS REQUIRED ABOVE CEILING TO
MITIGATE SOUND TRANSFER BETWEEN OFFICES.
21 IF POSSIBLE, EXISTING DRYWALL BULIKHEAD AND/OR CEILING AND LIGHTING ARE TO REMAIN;. iF
CEILING MUST BE PARTIALLY DEMOLISHED TO ACCOMODATE NEW HVAC CONFIGURATION, PATCH
WITH NEW AS NEEDED AND REPAINT BULKHEAD. IF ADJACENT DRYWALL CEILING AT HIGHER
ELEVATION IS BEING REMOVED TO BE REPLACED BY ACT GRID CIELING, DEISGN INTENT IS FOR
NEW ACT CEILING TO BE 1" LOWER THAN REMOVED DRYWALL SUCH THAT MINIMAL TOUCH UP
V V WORK IS REQUIRED AT PERIMETER OF BULKHEAD TO REMIAN. REUSE LIGHTING IF POSSIBLE.
CONFIRM DESIGN INTENT WITH ARCHITECT PRIOR TO REPLACEMENT.
23 NEW SURFACE MOUNTED LINEAR LIGHTING TO MATCH OTHER FIXTURES ON THIS FLOOR. THESE
ARE REPLACING FIXTURES WITH RED HOUSING THAT WERE REMOVED.
25 DESIGN INTENT IS FOR NEWLY CONSTRUCTED CEIING AND LIGHTING TO REMAIN. IF MECHANICAL
WORK PROHIBITS THIS, SALVAGE REMOVED COMPONENTRY AND REINSTALL OR REPLACE WITH
NEW TO MATCH EXISTING.
26 REFERENCE ELECTRICAL DRAWINGS FOR NEW LIGHTING IN NEWLY CONSTRUCTED ROOMS.
27 ADDED FIXTURE FOR INCREASED LIGHT LEVEL
29 ALIGN EXTENDED NEW GRID WITH EXISTING. GRID AND TILE MUST MATCH EXISTING ADJACENT COPYRIGHT NOTICE: THIS ARCHITECTURAL AND ENGINEERING DRAWING IS GIVEN IN CONFIDENCE
CEILING AND EXTENSION TO APPEAR SEAMLESS. AND SHALL BE USED ONLY PURSUANT TO THE AGREEMENT WITH RATIO. NO OTHER USE,
W W DISSEMINATION OR DUPLICATION MAY BE MADE WITHOUT PRIOR WRITTEN CONSENT OF RATIO. ALL
30 EXISTING HARDLID CEILING AND SUSPENDED CLOUDS REQUIRE REMOVAL FOR HVAC WORK.. COMMON LAW RIGHTS OF COPYRIGHT AND OTHERWISE ARE HEREBY SPECIFICALLY RESERVED.
PROVIDE NEW 2'X2' ACT GRID AND CEILING AS SHOWN. REUSE EXISTING LINEAR PENDANTS AND PROJECT NO. 19010.000
ADD ADDITIONAL LIGHTING FOR NEW LIVE VEGETATION WALL AND DECORATIVE PENDANTS AT
CAFE. AS SHOWN IN ELECTRICAL DRAWINGS.. SHEET TITLE
COFFERED CIELING AT NORTH END ARE TO REMAIN. REPLACE EXISTING WOOD SLAT CEILING WITH
NEW 2X2 ACT CEILING.
1 LOWER LEVEL 1 - AREA 1 33 REPAIR PORTION OF DEMOLISHED CEILING AND FLOOR ABOVE IF APPLICABLE TO MATCH EXISITNG SHEET NUMBER
A-132.1
1/8" = 1'-0" CONSTRUCTION ASSEMBLY AND MATERIALS SUCH THAT REPAIR IS VISIBLY SEAMLESS, INCLUDING
FLOORING FINISHES ON LEVEL ABOVE.
A-132.1
GENERAL CEILING PLAN NOTES
A. THESE GENERAL NOTES APPLY TO SERIES A-130 REFLECTED CEILING DRAWINGS.
B. INSTALL NEW ACT CEILINGS AT 1" LOWER THAN EXISTING HEIGHT UNLESS NOTED OTHERWISE.
N10 N9 N8 N7 N6 N5 N4 N3 N2 N1
G.C. TO COORDINATE PROVISION OF INFORMATION REGARDING EXISTING CEILING HEIGHTS.
CONFIRM ALL CEILING HEIGHTS INDICATED ON PLAN AND IMMEDIATELY REQUEST
CONFIRMATION FROM ARCHITECT IF THERE IS A CONFLICT BETWEEN HEIGHT SHOWN ON PLAN
RHIT MOENCH
AND ACHIEVING HEIGHT 1" LOWER THAN CURRENTLY IN FIELD.
C. UNLESS NOTED OR SHOWN OTHERWISE, EXISTING BULKHEADS ARE TO REMAIN, UNLESS
REMOVAL IS REQUIRED FOR HVAC INSTALLATION. IF REPAINTING IS REQUIRED, MATCH EXISTING
RENOVATION
FINISHES.
TYP.
A7 C5
D. UNLESS NOTED OTHERWISE, ALL ROOMS SHOWN AS OPEN DECK TO REMAIN ARE TO ALSO
ASSUME THAT EXISTING LIGHTING IS TO REMAIN AND EXISTING CEILING FINISHES ARE TO
5500 Wabash Avenue
A
TYP.
A-622 A-622
TYP.
A
REMAIN..
E. UNLESS NOTED OR SHOWN OTHERWISE, ALL ROOMS SHOWN WITH NEW GRID TO RECIEVE NEW
2'X2' ACOUSTICAL CEILING GRID (BASIS OF DESIGN IS ARMSTRONG 1732 WITH TEGULAR REVEAL
Terre Haute, Indiana
WT-01
WT-01 WT-01 WT-01 WT-01 EDGE AND CORRESPONDING CHICAGO METALLIC 15/16" EXPOSED TEE GRID). GRID IS INTENDED
TO BE SHOWN IN THE PLANS AND INSTALLED
47803
F. AT EXISTING LOCATION SUCH THAT EXISTING LIGHTING TO BE RAISED ABOVE GRID DURING
CEILING WORK AND THEN CLEANED, SERVICED AS REQUIRED AND RELOCATED INTO NEW GRID Owner
ONCE CEILING WORK IS COMPLETED. THIS MEANS THAT THE CEILING GRID IS NOT NECESSARILY
FACULTY FACULTY FACULTY FACULTY FACULTY FACULTY FACULTY FACULTY CENTERED IN THE ROOM TO ALLOW FOR REUSE OF LIGHTING CONDUIT. IN NEW AREAS WITH
Rose-Hulman Institute of Technology
WT-01 OFFICE OFFICE OFFICE OFFICE OFFICE OFFICE OFFICE OFFICE GRID THAT DID NOT PREVIOUSLY HAVE GRID CEILING, CENTER WITHIN SPACE AS SHOWN. 5500 Wabash Avenue
26 FL115 FL113 FL111 FL109 FL107 FL105 FL103 FL101 G. CENTER PENETRATIONS IN ACOUSTICAL CEILING SYSTEMS WITHIN INDIVIDUAL CEILING PANELS, Terre Haute, Indiana 47803
19
26 19 26 19 26 19 26 19 26 26 19 19 26 26 SUCH AS SPRINKLER HEADS, DIFFUSERS, LIGHT FIXTURES, ETC., UNLESS OTHERWISE 812-877-1511
ACT-01 19 19 INDICATED.
8'-0" A.F.F. ACT-01 ACT-01 ACT-01 ACT-01 ACT-01 ACT-01 ACT-01 ACT-01 H. PAINT NEW GYPSUM BOARD CEILING SURFACES AS SHOWN ON RCP'S.
8'-0" A.F.F. 8'-0" A.F.F. 8'-0" A.F.F. 8'-0" A.F.F. 8'-0" A.F.F. 8'-0" A.F.F. 8'-0" A.F.F. 8'-0" A.F.F. I. PROVIDE CONTROL JOINTS (C.J.) IN GYPSUM BOARD CEILING CONSTRUCTION AS INDICATED.
WHERE NOT SHOWN, PROVIDE MAXIMUM SPACING BETWEEN JOINTS OF 30'-0”. VERIFY FINAL
CONTROL JOINT LOCATIONS WITH ARCHITECT PRIOR TO STARTING WORK WHETHER OR NOT
B B INDICATED ON THE DRAWINGS.
J. CEILING ACCESS PANELS INDICATED ARE NOT INTENDED TO LIMIT NUMBER OF PANELS
CONC-01
D4 D4 REQUIRED. PANEL QUANTITY SHALL BE SUFFICIENT TO PROVIDE REQUIRED ACCESS WHETHER
7'-4" A.F.F. 18
A-540 18 A-540 CONC-01 OR NOT INDICATED ON THE DRAWINGS. VERIFY FINAL LOCATIONS WITH ARCHITECT PRIOR TO
26 7'-4" A.F.F. STARTING WORK.
ACT-01 19
8'-0" A.F.F. 18 K. NEW EXPOSED DUCTS/ HVAC UNITS AT EXPOSED STAINED WOOD DECK CEILINGS TO BE BRUSH
19 26 18 PAINTED IN APPROPRIATE COATING TO MATCH PT-01, VERIFY COLOR OF PAINT AT ALL OTHER
26
FACULTY 26 19 26 Architect
19 26 FACULTY LOCATIONS OF EXPOSED DUCTWORK AND HVAC UNITS.
19 19
FACULTY COLLISION
FACULTY OFFICE FACULTY
RATIO
WT-01 19 ACT-01 FL108 FL104 ACT-01
26 CONC-01
OFFICE OFFICE OFFICE 101 South Pennsylvania Street
ACT-01 FL112 8'-0" A.F.F. FL106 8'-0" A.F.F. Indianapolis, Indiana 46204
FACULTY 7'-4" A.F.F. ACT-01 FL102
8'-0" A.F.F. CONC-01 317-633-4040
OFFICE
FL114
ACT-01 7'-4" A.F.F. ACT-01 8'-0" A.F.F. ACT-01 CEILING LEGEND
8'-0" A.F.F. 8'-0" A.F.F. 8'-0" A.F.F.
C C Structural Engineer
CEILING TAG
ACT-01 ACT-01 ACT-01 D6 ACT-01 D6
Fink Roberts & Petrie, Inc.
GWB-X1 D6 8'-0" A.F.F. D6 8'-0" A.F.F. 8'-0" A.F.F. A-540 CEILING TYPE
7'-0" A.F.F. A-540 A-540
8'-0" A.F.F. A-540 XXX-01 9449 Priority Way W Dr #200
10'-10" A.F.F. CEILING HEIGHT Indianapolis, Indiana 46240
ACT-01 CONC-01
7'-1" A.F.F. 7'-4" A.F.F. (ABOVE FINISH FLOOR) 317-872-8400
11 11 11
11 EXP SPOT ELEVATION MARKER Mechanical / Electrical Engineer
9'-0" A.F.F.
R.E. Dimond & Associates, Inc.
GWB-X1 GWB-X2 732 N Capitol Avenue
9.8 8.9 7.9 8'-3" A.F.F. 6.9 7'-10" A.F.F.
5.9 5.5 5.1 4.1 3.1 2.1 1.2
ACT-01 EXISTING PAINTED GYB BOARD CEILING NEW OR PATCHED PAINTED GYB BOARD Indianapolis, Indiana 46204
3'-3" MIN.
7'-10" A.F.F. OR BULKHEAD AS SHOWN ON PLAN CEILING OR BULKHEAD AS SHOWN ON 317-634-4672
PLAN
D D
GWB-X1
6"
5'-0"
ALIGN 7'-11" A.F.F. 7'-9" A.F.F. BUILDING STANDARD 2'X2' GRID AND
D1 PT-01 F5 IS UNLESS NOTED OTHERWISE. NEW
A-540 GWB-X1 18 A-540 DUCTWORK AND HVAC EQUIPMENT TO CEILING TILES
8'-3" A.F.F. HOUSEKEEPING BE PREPPED AND DRYFALL PAINTED
A4 18 EQUIPMENT TO MATCH EXISTING EXPOSED
ACT-02
5'-0"
5'-0"
2'-10 1/4"
EL126 ACT-01
B4 B6 PT-05 1'-6"
GWB EX 7'-1" A.F.F.
A-540 A-540 ALIGN GWB-X1
7'-6 1/2" A.F.F.
7'-6 1/2" A.F.F. 31 EXISTING EXPOSED WOOD BEAM ARMSTRONG WOODWORKS ACOUSTICAL
GWB EX
A6 EXP MAIL SORT PLANK CLOUD
ACT-01 F3 7'-0" A.F.F. ACT-01
A-540 31 10'-0" A.F.F. EL103
PT-01 8'-4" A.F.F. A2 A-540 7'-6" A.F.F.
LOUNGE A-540 GWB-X1
EL112 GWB-X1 18 18 7'-9" A.F.F.
8'-3" A.F.F. GWB-X1
8'-3" A.F.F.
AREA N.I.C.
B2 GWB-X1 GWB EX ACT-01
A-540 ACT-01 7'-0" A.F.F. 7'-9" A.F.F. 7'-6" A.F.F.
ALIGN 31 27
8'-4" A.F.F. 21
18
F PT-05 GWB EX PT-01 F
OPEN TO 7'-6 1/2" A.F.F.
LEVEL 2 27 CEILING PLAN NOTES
A2 18
1'-6" ALIGN A-540
1'-6"
18 F
2'-0" GWB-X1
23
01 IF POSSIBLE, REUSE EXISTNG VERTICAL AND PORTION OF HORIZONTAL FACE OF EXISITNG
3 G
GWB-X1
8'-3" A.F.F. 18 GWB-X1
18
ACT-01
7'-9" A.F.F.
F3
WOMENS R.R.
EL105
ACT-01
7'-7" A.F.F.
BULkHEAD TO CREATE PERIMETER OF NEW ACT CEILING AS SHOWN. REPAINT AS REQUIRED TO
MATCH EXISTING BUIDLING STANDARD.
E
2
PT-01 8'-3" A.F.F.
A5 8'-4" A.F.F. A-540 D
A-301
ACT-01 MENS R.R.
02 RECONSTRUCT PERIMETER BULKHEADS WHERE HVAC WORK REQUIRED REMOVAL TO REPLICATE
31 18 7'-7" A.F.F. EL104 ORIGINAL CONSTRUCTION AND LIGHTING.
ACT-01 C
8'-4" A.F.F. A2 31 03 PROVIDE NEW SURFACE MOUNTED LINEAR LIGHTING TO MATCH OTHER LINEAR LIGHTING ON THIS
A-540
FLOOR. PATCH AND PAINT EXPOED CEILING ELEMENTS AS REQUIRED.
G G 04
B 1
ACT-01 ACT-01 05 NO HEADER AT THIS LOCATION . PROVIDE BLOCKING ABOVE CEIILNG TO SUPPORT DOOR FRAME A
7'-9" A.F.F. ACT-01 7'-11" A.F.F. INSERTED WITHINT FINISHED OPENING. DRYWALL CEILING IS CONTINUOUS.
7'-10" A.F.F. ACT-01 ACT-01
7'-10" A.F.F. 7'-10" A.F.F. EXPOSED PAINTED SEMICONDUCTOR 08 PROVIDE ALTERNATE BID TO REPLACE EXISTING LIGHTING WITH NEW SURFACE MOUNTED LINEARS
OFFICE WOOD DECK ACT-01 OPTICS LAB KEY PLAN
OFFICE DL110D OFFICE OFFICE OFFICE 7'-11" A.F.F. TO MATCH OTHER LINEAR LIGHITNG ON THIS FLOOR. INCLUDE POSSIBLE TOUCH UP THAT MAY BE
DL108
DL110C DL110E DL110F DL110G REQUIRED TO CEILING AFTER CHANGE IN LIGHTING.
OFFICE SEAL | DATE 04/01/21
DL107 09 ACOUSTICAL LINEAR WOOD PLANK CEILING EQUAL TO ARMSTRONG WOODWORKS GRILLE WITH
NRC OF .90. WHERE SHOWN, ASSUME RECESSED LINEAR LIGHTING EQUAL TO FOCAL POINT SEEM
ACT-01
2.
ACT-01
7'-10" A.F.F.
7'-8" A.F.F. WD BEAM 21 11 DESIGN INTENT IS TO EXPOSED STRUCTURE CEILING - PAINT DRYFALL PAINT IF NOT WOOD TIMBER.
7'-9" A.F.F. ACT-01 . PROVIDE SURFACE MOUNTED LED LINEAR FIXTURES TO MATCH NEW BUILDING STANDARD IN
H H
7'-9" A.F.F. GWB-X1 QUANTITIES AND PLACEMENT TO ACHIEVE APPROPRIATE FOOTCANDLE LEVELS RECOMMENDED
WD BEAM GWB EX
WD BEAM 7'-9" A.F.F. 7'-6" A.F.F. FOR INDICATED ROOM FUNCTION PER IES STANDARDS IF EXPOSING THE EXISTING STRUCTURE IS
7'-3" A.F.F.
7'-9" A.F.F.
NOT POSSIBLE DUE TO UNFORESEEN CIRCUMSTANCES, PROVIDE STANDARD 2'X2' ACT TILE WITH
OFFICE ADMIN OFFICE
OFFICE DL110A DL110 NEW RECESSED LIGHTING AS SHOWN.
ACT-01
DL110B 7'-11" A.F.F. 12 EXPOSED STRUCTURE CEILING. RECONFIGURE DUCTS, PIPES AND CONDUIT AS REQUIRED TO
ACT-01 ACT-01 ACT-01 NUCLEAR OFFICE MINIMIZE IN EXPOSED AREAS WHERE POSSIBLE, DRYFALL PAINT AND PROVIDE PROVIDE NEW
7'-11" A.F.F. ACT-01 7'-9" A.F.F. 7'-10" A.F.F. PHYSICS LAB DL106 LIGHTING AS SHOWN IN ELECTRICAL PLANS. SHEET ISSUE
7'-10" A.F.F. DL105
ACT-01 14 REPAINT DRYWALL AND REPLACE EXISTING DOWNLIGHTS WITH NEW LED DOWNLIGHTS. 1 Construction Documents 04/01/21
8'-0" A.F.F. ACT-01
GWB EX 7'-11" A.F.F.
GWB EX 17 PROVIDE MOTORIZED PROJECTION SCREEN AT FRONT OF ROOM AND PROJECTOR MOUNT TO
7'-6" A.F.F. 7'-6" A.F.F.
COORDINATE WITH PROJECTOR AND SPACED AS REQUIRED. COORDINATE STRUCTURAL SUPPORT
J GWB EX GWB EX J
7'-6" A.F.F. ACT-01 7'-9" A.F.F. AS REQUIRED.
GWB EX
7'-11" A.F.F. 7'-6" A.F.F. 18 PROVIDE NEW CEILING WITH NEW LIGHTING AS SHOWN. IF NO NEW LIGHTING IS SHOWN, DESIGN
OPTICAL GWB EX
ENGINEERING 7'-6" A.F.F. INTENT IS TO REUSE EXISTING WALL SCONCES. COORDINATE WITH ELECTRICAL LIGHTING PLANS
LAB 3 OPTICAL AS REQUIRED. PATCH TOP OF PERIMETER WALLS AS REQUIRED WHERE EXISTING CEILNGS WERE
ACT-01 ACT-01 EXPOSED PAINTED METROLOGY
DL115 8'-0" A.F.F. 8'-0" A.F.F. ACT-01 REMOVED.
WOOD DECK LAB
7'-11" A.F.F. OFFICE
DL104 19 PROVIDE SOUND BOOTS AT HVAC ABOVE CEILING AND INSULATE AS REQUIRED ABOVE CEILING TO
EXP DL103
ACT-01 10'-0" A.F.F. MITIGATE SOUND TRANSFER BETWEEN OFFICES.
7'-11" A.F.F. EXP
9'-8" A.F.F. 21 IF POSSIBLE, EXISTING DRYWALL BULIKHEAD AND/OR CEILING AND LIGHTING ARE TO REMAIN;. iF
GWB EX ACT-01
CEILING MUST BE PARTIALLY DEMOLISHED TO ACCOMODATE NEW HVAC CONFIGURATION, PATCH
WD BEAM 7'-3" A.F.F. 21 7'-11" A.F.F. WITH NEW AS NEEDED AND REPAINT BULKHEAD. IF ADJACENT DRYWALL CEILING AT HIGHER
7'-9" A.F.F. 21
ACT-01 GWB EX ELEVATION IS BEING REMOVED TO BE REPLACED BY ACT GRID CIELING, DEISGN INTENT IS FOR
K 7'-3" A.F.F. K
7'-9" A.F.F. NEW ACT CEILING TO BE 1" LOWER THAN REMOVED DRYWALL SUCH THAT MINIMAL TOUCH UP
WD BEAM
7'-9" A.F.F. ACT-01 WORK IS REQUIRED AT PERIMETER OF BULKHEAD TO REMIAN. REUSE LIGHTING IF POSSIBLE.
7'-9" A.F.F. ACT-01
7'-11" A.F.F. CONFIRM DESIGN INTENT WITH ARCHITECT PRIOR TO REPLACEMENT.
EXP
OPTICAL
ACT-01 ACT-01
7'-9" A.F.F. 23 NEW SURFACE MOUNTED LINEAR LIGHTING TO MATCH OTHER FIXTURES ON THIS FLOOR. THESE
ENGINEERING ARE REPLACING FIXTURES WITH RED HOUSING THAT WERE REMOVED.
ACT-01 7'-11" A.F.F. 7'-8" A.F.F.
LAB 1
7'-11" A.F.F. OFFICE
DL117 DARK ROOM CLASSROOM SENIOR
DL102
25 DESIGN INTENT IS FOR NEWLY CONSTRUCTED CEIING AND LIGHTING TO REMAIN. IF MECHANICAL
G112 DL119 EXP DESIGN LAB
WORK PROHIBITS THIS, SALVAGE REMOVED COMPONENTRY AND REINSTALL OR REPLACE WITH
9'-8" A.F.F. DL101
GWB EX ACT-01 NEW TO MATCH EXISTING.
GWB EX 7'-6" A.F.F. 7'-11" A.F.F. 26 REFERENCE ELECTRICAL DRAWINGS FOR NEW LIGHTING IN NEWLY CONSTRUCTED ROOMS.
7'-6" A.F.F.
ACT-01
7'-11" A.F.F. 27 ADDED FIXTURE FOR INCREASED LIGHT LEVEL
GWB EX
L L
7'-6" A.F.F. EXP 29 ALIGN EXTENDED NEW GRID WITH EXISTING. GRID AND TILE MUST MATCH EXISTING ADJACENT
OPTICAL CLASSROOM 7'-9" A.F.F. GWB EX GWB EX CEILING AND EXTENSION TO APPEAR SEAMLESS. COPYRIGHT NOTICE: THIS ARCHITECTURAL AND ENGINEERING DRAWING IS GIVEN IN CONFIDENCE
GWB EX ENGINEERING
GWB EX 7'-6" A.F.F. 7'-6" A.F.F. AND SHALL BE USED ONLY PURSUANT TO THE AGREEMENT WITH RATIO. NO OTHER USE,
7'-6" A.F.F. 7'-6" A.F.F. DL119 DISSEMINATION OR DUPLICATION MAY BE MADE WITHOUT PRIOR WRITTEN CONSENT OF RATIO. ALL
LAB 2 30 EXISTING HARDLID CEILING AND SUSPENDED CLOUDS REQUIRE REMOVAL FOR HVAC WORK.. COMMON LAW RIGHTS OF COPYRIGHT AND OTHERWISE ARE HEREBY SPECIFICALLY RESERVED.
ACOUSTICS
CL118 ACT-01
ACT-01 EXP PROJECTS ACT-01 PROVIDE NEW 2'X2' ACT GRID AND CEILING AS SHOWN. REUSE EXISTING LINEAR PENDANTS AND
8'-0" A.F.F. PROJECT NO. 19010.000
7'-8" A.F.F. 9'-8" A.F.F. LAB 7'-9" A.F.F. OFFICE ADD ADDITIONAL LIGHTING FOR NEW LIVE VEGETATION WALL AND DECORATIVE PENDANTS AT
GWB EX CL110 CL109 CAFE. AS SHOWN IN ELECTRICAL DRAWINGS.. SHEET TITLE
7'-6" A.F.F.
ACT-01
7'-11" A.F.F.
ACT-01
7'-11" A.F.F.
18 18
B1
A-540
31 PROVIDE NEW DRYWALL BULKHEAD AS SHOWN TO MATCH CONSTRUCTION ASSEMBLY OF OTHER
BULKHEADS IN ADJACENT AREA. LOWER LEVEL 1
01
32 REMOVE HORIZONTAL PORTIONS OF HARDLID CEILINGS ON SOUTH ABOVE STAGE AND ALONG
EAST WALL. VERTICAL PORTION OF THESE BULKHEADS CAN REMAIN FOR EASE OF
REFLECTED CEILING
9.8 8.9 7.9 6.9 5.9 5.5
C2 5.1 4.1 3.1 2.1 1.2 RECONSTRUCITON AFTER HVAC WORK IS COMPLETED. DRYWALL WRAPPED TRUSSES AND PLAN - AREA 2
4/1/2021 12:07:24 PM
A-301 COFFERED CIELING AT NORTH END ARE TO REMAIN. REPLACE EXISTING WOOD SLAT CEILING WITH
NEW 2X2 ACT CEILING.
1 LOWER LEVEL 1 - AREA 2 33 REPAIR PORTION OF DEMOLISHED CEILING AND FLOOR ABOVE IF APPLICABLE TO MATCH EXISITNG
A-132.2 SHEET NUMBER
1/8" = 1'-0" CONSTRUCTION ASSEMBLY AND MATERIALS SUCH THAT REPAIR IS VISIBLY SEAMLESS, INCLUDING
FLOORING FINISHES ON LEVEL ABOVE.
A-132.2
GENERAL CEILING PLAN NOTES
Structural Engineer
CEILING TAG
CLOSET Fink Roberts & Petrie, Inc.
G220A 17 CEILING TYPE
32 SF XXX-01 9449 Priority Way W Dr #200
10'-10" A.F.F. CEILING HEIGHT
Indianapolis, Indiana 46240
MENS R.R. 317-872-8400
G206 (ABOVE FINISH FLOOR)
165 SF
ACT-01
ACT-01 ACT-01 9'-0" A.F.F.
9'-0" A.F.F. 9'-0" A.F.F. EXISTING EXPOSED WOOD BEAM ARMSTRONG WOODWORKS ACOUSTICAL
PLANK CLOUD
18
STG.
G210A
STAIR
18 -
128 SF AREA N.I.C.
17
BULkHEAD TO CREATE PERIMETER OF NEW ACT CEILING AS SHOWN. REPAINT AS REQUIRED TO
E
2
MATCH EXISTING BUIDLING STANDARD.
D
02 RECONSTRUCT PERIMETER BULKHEADS WHERE HVAC WORK REQUIRED REMOVAL TO REPLICATE
ORIGINAL CONSTRUCTION AND LIGHTING.
C
03 PROVIDE NEW SURFACE MOUNTED LINEAR LIGHTING TO MATCH OTHER LINEAR LIGHTING ON THIS
04
FLOOR. PATCH AND PAINT EXPOED CEILING ELEMENTS AS REQUIRED. B 1
COOK 05 NO HEADER AT THIS LOCATION . PROVIDE BLOCKING ABOVE CEIILNG TO SUPPORT DOOR FRAME A
GREENHOUSE INSERTED WITHINT FINISHED OPENING. DRYWALL CEILING IS CONTINUOUS.
G219A
1266 SF 08 PROVIDE ALTERNATE BID TO REPLACE EXISTING LIGHTING WITH NEW SURFACE MOUNTED LINEARS
TO MATCH OTHER LINEAR LIGHITNG ON THIS FLOOR. INCLUDE POSSIBLE TOUCH UP THAT MAY BE KEY PLAN
REQUIRED TO CEILING AFTER CHANGE IN LIGHTING.
SEAL | DATE 04/01/21
09 ACOUSTICAL LINEAR WOOD PLANK CEILING EQUAL TO ARMSTRONG WOODWORKS GRILLE WITH
NRC OF .90. WHERE SHOWN, ASSUME RECESSED LINEAR LIGHTING EQUAL TO FOCAL POINT SEEM
2.
11 DESIGN INTENT IS TO EXPOSED STRUCTURE CEILING - PAINT DRYFALL PAINT IF NOT WOOD TIMBER.
. PROVIDE SURFACE MOUNTED LED LINEAR FIXTURES TO MATCH NEW BUILDING STANDARD IN
QUANTITIES AND PLACEMENT TO ACHIEVE APPROPRIATE FOOTCANDLE LEVELS RECOMMENDED
1 LOWER LEVEL 1 - AREA 3 FOR INDICATED ROOM FUNCTION PER IES STANDARDS IF EXPOSING THE EXISTING STRUCTURE IS
A-132.3
1/8" = 1'-0" NOT POSSIBLE DUE TO UNFORESEEN CIRCUMSTANCES, PROVIDE STANDARD 2'X2' ACT TILE WITH
NEW RECESSED LIGHTING AS SHOWN.
12 EXPOSED STRUCTURE CEILING. RECONFIGURE DUCTS, PIPES AND CONDUIT AS REQUIRED TO
MINIMIZE IN EXPOSED AREAS WHERE POSSIBLE, DRYFALL PAINT AND PROVIDE PROVIDE NEW
LIGHTING AS SHOWN IN ELECTRICAL PLANS. SHEET ISSUE
14 REPAINT DRYWALL AND REPLACE EXISTING DOWNLIGHTS WITH NEW LED DOWNLIGHTS. 1 Construction Documents 04/01/21
17 PROVIDE MOTORIZED PROJECTION SCREEN AT FRONT OF ROOM AND PROJECTOR MOUNT TO
COORDINATE WITH PROJECTOR AND SPACED AS REQUIRED. COORDINATE STRUCTURAL SUPPORT
AS REQUIRED.
18 PROVIDE NEW CEILING WITH NEW LIGHTING AS SHOWN. IF NO NEW LIGHTING IS SHOWN, DESIGN
INTENT IS TO REUSE EXISTING WALL SCONCES. COORDINATE WITH ELECTRICAL LIGHTING PLANS
AS REQUIRED. PATCH TOP OF PERIMETER WALLS AS REQUIRED WHERE EXISTING CEILNGS WERE
REMOVED.
19 PROVIDE SOUND BOOTS AT HVAC ABOVE CEILING AND INSULATE AS REQUIRED ABOVE CEILING TO
MITIGATE SOUND TRANSFER BETWEEN OFFICES.
21 IF POSSIBLE, EXISTING DRYWALL BULIKHEAD AND/OR CEILING AND LIGHTING ARE TO REMAIN;. iF
CEILING MUST BE PARTIALLY DEMOLISHED TO ACCOMODATE NEW HVAC CONFIGURATION, PATCH
WITH NEW AS NEEDED AND REPAINT BULKHEAD. IF ADJACENT DRYWALL CEILING AT HIGHER
ELEVATION IS BEING REMOVED TO BE REPLACED BY ACT GRID CIELING, DEISGN INTENT IS FOR
NEW ACT CEILING TO BE 1" LOWER THAN REMOVED DRYWALL SUCH THAT MINIMAL TOUCH UP
WORK IS REQUIRED AT PERIMETER OF BULKHEAD TO REMIAN. REUSE LIGHTING IF POSSIBLE.
CONFIRM DESIGN INTENT WITH ARCHITECT PRIOR TO REPLACEMENT.
23 NEW SURFACE MOUNTED LINEAR LIGHTING TO MATCH OTHER FIXTURES ON THIS FLOOR. THESE
ARE REPLACING FIXTURES WITH RED HOUSING THAT WERE REMOVED.
25 DESIGN INTENT IS FOR NEWLY CONSTRUCTED CEIING AND LIGHTING TO REMAIN. IF MECHANICAL
WORK PROHIBITS THIS, SALVAGE REMOVED COMPONENTRY AND REINSTALL OR REPLACE WITH
NEW TO MATCH EXISTING.
26 REFERENCE ELECTRICAL DRAWINGS FOR NEW LIGHTING IN NEWLY CONSTRUCTED ROOMS.
27 ADDED FIXTURE FOR INCREASED LIGHT LEVEL
29 ALIGN EXTENDED NEW GRID WITH EXISTING. GRID AND TILE MUST MATCH EXISTING ADJACENT
COPYRIGHT NOTICE: THIS ARCHITECTURAL AND ENGINEERING DRAWING IS GIVEN IN CONFIDENCE
CEILING AND EXTENSION TO APPEAR SEAMLESS. AND SHALL BE USED ONLY PURSUANT TO THE AGREEMENT WITH RATIO. NO OTHER USE,
DISSEMINATION OR DUPLICATION MAY BE MADE WITHOUT PRIOR WRITTEN CONSENT OF RATIO. ALL
30 EXISTING HARDLID CEILING AND SUSPENDED CLOUDS REQUIRE REMOVAL FOR HVAC WORK.. COMMON LAW RIGHTS OF COPYRIGHT AND OTHERWISE ARE HEREBY SPECIFICALLY RESERVED.
PROVIDE NEW 2'X2' ACT GRID AND CEILING AS SHOWN. REUSE EXISTING LINEAR PENDANTS AND
ADD ADDITIONAL LIGHTING FOR NEW LIVE VEGETATION WALL AND DECORATIVE PENDANTS AT PROJECT NO. 19010.000
CAFE. AS SHOWN IN ELECTRICAL DRAWINGS.. SHEET TITLE
31 PROVIDE NEW DRYWALL BULKHEAD AS SHOWN TO MATCH CONSTRUCTION ASSEMBLY OF OTHER
BULKHEADS IN ADJACENT AREA.
LOWER LEVEL 1
32 REMOVE HORIZONTAL PORTIONS OF HARDLID CEILINGS ON SOUTH ABOVE STAGE AND ALONG
EAST WALL. VERTICAL PORTION OF THESE BULKHEADS CAN REMAIN FOR EASE OF
REFLECTED CEILING
RECONSTRUCITON AFTER HVAC WORK IS COMPLETED. DRYWALL WRAPPED TRUSSES AND PLAN - AREA 3
4/1/2021 12:07:28 PM
COFFERED CIELING AT NORTH END ARE TO REMAIN. REPLACE EXISTING WOOD SLAT CEILING WITH
NEW 2X2 ACT CEILING.
33 REPAIR PORTION OF DEMOLISHED CEILING AND FLOOR ABOVE IF APPLICABLE TO MATCH EXISITNG SHEET NUMBER
CONSTRUCTION ASSEMBLY AND MATERIALS SUCH THAT REPAIR IS VISIBLY SEAMLESS, INCLUDING
FLOORING FINISHES ON LEVEL ABOVE.
A-132.3
9.8 8.9 7.9 6.9 5.9 5.5 5.1 4.1 3.1 2.1 1.2
GENERAL CEILING PLAN NOTES
STORAGE
D115A OFFICE
A. THESE GENERAL NOTES APPLY TO SERIES A-130 REFLECTED CEILING DRAWINGS.
CIRCULATION
D102
B. INSTALL NEW ACT CEILINGS AT 1" LOWER THAN EXISTING HEIGHT UNLESS NOTED OTHERWISE.
G.C. TO COORDINATE PROVISION OF INFORMATION REGARDING EXISTING CEILING HEIGHTS.
CONFIRM ALL CEILING HEIGHTS INDICATED ON PLAN AND IMMEDIATELY REQUEST
RHIT MOENCH
-
ACT-01
7'-1" A.F.F.
GWB-X1 GWB-X1
ACT-01
7'-10" A.F.F.
CONFIRMATION FROM ARCHITECT IF THERE IS A CONFLICT BETWEEN HEIGHT SHOWN ON PLAN
AND ACHIEVING HEIGHT 1" LOWER THAN CURRENTLY IN FIELD.
C. UNLESS NOTED OR SHOWN OTHERWISE, EXISTING BULKHEADS ARE TO REMAIN, UNLESS
RENOVATION
7'-1" A.F.F. 7'-1" A.F.F.
L
EQUIPMENT
INSTRUMENT
ROOM
L REMOVAL IS REQUIRED FOR HVAC INSTALLATION. IF REPAINTING IS REQUIRED, MATCH EXISTING
FINISHES. 5500 Wabash Avenue
C114 OFFICE D. UNLESS NOTED OTHERWISE, ALL ROOMS SHOWN AS OPEN DECK TO REMAIN ARE TO ALSO
STORAGE
C115A
WORKSHOP/STORAGE
C112
C110 ASSUME THAT EXISTING LIGHTING IS TO REMAIN AND EXISTING CEILING FINISHES ARE TO
REMAIN..
Terre Haute, Indiana
ACT-01
21
7'-9" A.F.F.
EXP
ACT-01
7'-9" A.F.F.
E. UNLESS NOTED OR SHOWN OTHERWISE, ALL ROOMS SHOWN WITH NEW GRID TO RECIEVE NEW
2'X2' ACOUSTICAL CEILING GRID (BASIS OF DESIGN IS ARMSTRONG 1732 WITH TEGULAR REVEAL
EDGE AND CORRESPONDING CHICAGO METALLIC 15/16" EXPOSED TEE GRID). GRID IS INTENDED
47803
9'-0" A.F.F. TO BE SHOWN IN THE PLANS AND INSTALLED
ACT-01 ACT-01 Owner
7'-2" A.F.F. 7'-9" A.F.F. F. AT EXISTING LOCATION SUCH THAT EXISTING LIGHTING TO BE RAISED ABOVE GRID DURING
CEILING WORK AND THEN CLEANED, SERVICED AS REQUIRED AND RELOCATED INTO NEW GRID Rose-Hulman Institute of Technology
ONCE CEILING WORK IS COMPLETED. THIS MEANS THAT THE CEILING GRID IS NOT NECESSARILY 5500 Wabash Avenue
OFFICE CENTERED IN THE ROOM TO ALLOW FOR REUSE OF LIGHTING CONDUIT. IN NEW AREAS WITH
OPEN TO LEVEL 2 MECHATRONICS Terre Haute, Indiana 47803
C109 GRID THAT DID NOT PREVIOUSLY HAVE GRID CEILING, CENTER WITHIN SPACE AS SHOWN.
C111 812-877-1511
G. CENTER PENETRATIONS IN ACOUSTICAL CEILING SYSTEMS WITHIN INDIVIDUAL CEILING PANELS,
M M SUCH AS SPRINKLER HEADS, DIFFUSERS, LIGHT FIXTURES, ETC., UNLESS OTHERWISE
ACT-01 INDICATED.
DIGITAL B1 7'-9" A.F.F.
18 A-540 H. PAINT NEW GYPSUM BOARD CEILING SURFACES AS SHOWN ON RCP'S.
ELECTRONIC I. PROVIDE CONTROL JOINTS (C.J.) IN GYPSUM BOARD CEILING CONSTRUCTION AS INDICATED.
MICROCOMPUTER 01
ACT-01 WHERE NOT SHOWN, PROVIDE MAXIMUM SPACING BETWEEN JOINTS OF 30'-0”. VERIFY FINAL
LABORATORY 7'-10" A.F.F. CONTROL JOINT LOCATIONS WITH ARCHITECT PRIOR TO STARTING WORK WHETHER OR NOT
1'-0"
C115 ACT-01 25
7'-1 1/2" A.F.F. 1'-0" INDICATED ON THE DRAWINGS.
A2 OFFICE J. CEILING ACCESS PANELS INDICATED ARE NOT INTENDED TO LIMIT NUMBER OF PANELS
B1 REQUIRED. PANEL QUANTITY SHALL BE SUFFICIENT TO PROVIDE REQUIRED ACCESS WHETHER
A-301 A-540 GWB EX C108
7'-9" A.F.F. OR NOT INDICATED ON THE DRAWINGS. VERIFY FINAL LOCATIONS WITH ARCHITECT PRIOR TO
CIRCULATION STARTING WORK.
21 Architect
1'-0"
01 - GWB EX ACT-01 K. NEW EXPOSED DUCTS/ HVAC UNITS AT EXPOSED STAINED WOOD DECK CEILINGS TO BE BRUSH
GWB EX 7'-1" A.F.F. 7'-9" A.F.F.
7'-9" A.F.F. 5589 SF PAINTED IN APPROPRIATE COATING TO MATCH PT-01, VERIFY COLOR OF PAINT AT ALL OTHER RATIO
LOCATIONS OF EXPOSED DUCTWORK AND HVAC UNITS.
101 South Pennsylvania Street
Indianapolis, Indiana 46204
N ACT-01 GWB EX N 317-633-4040
8'-0" A.F.F. 7'-9 1/2" A.F.F.
18
01 CEILING LEGEND Structural Engineer
B1
A-540 Fink Roberts & Petrie, Inc.
OPEN TO LEVEL 2 ACT-01
25 CEILING TAG 9449 Priority Way W Dr #200
7'-1 1/2" A.F.F. ACT-01 ACT-01 25 25 25
7'-9" A.F.F. 7'-9" A.F.F. Indianapolis, Indiana 46240
CEILING TYPE
XXX-01 317-872-8400
21 ACT-01 10'-10" A.F.F. CEILING HEIGHT
OFFICE 7'-10" A.F.F.
OFFICE ACT-01 (ABOVE FINISH FLOOR)
DYNAMIC C118
C117 7'-10" A.F.F.
SYSTEMS AND GWB EX Mechanical / Electrical Engineer
CONTROLS GWB EX GWB EX 7'-9" A.F.F.
LABORATORY R.E. Dimond & Associates, Inc.
O 7'-2" A.F.F. 7'-2" A.F.F. O SPOT ELEVATION MARKER
C116 MAIL ROOM 732 N Capitol Avenue
WORKROOM / C104 Indianapolis, Indiana 46204
BREAKROOM 317-634-4672
OFFICE ADMIN 25
C103A ACT-01
C103 EXISTING PAINTED GYB BOARD CEILING NEW OR PATCHED PAINTED GYB BOARD
7'-10" A.F.F. OR BULKHEAD AS SHOWN ON PLAN CEILING OR BULKHEAD AS SHOWN ON
ACT-01
7'-10" A.F.F. PLAN
ACT-01
SERVER
7'-8" A.F.F. ACT-01
ROOM
OFFICE 7'-10" A.F.F. OFFICE
B107B
C101A C105
ACT-01
GWB EX 7'-10" A.F.F. EXPOSED STRUCTURE TO REMAIN AS-
6'-10" A.F.F. IS UNLESS NOTED OTHERWISE. NEW BUILDING STANDARD 2'X2' GRID AND
DUCTWORK AND HVAC EQUIPMENT TO CEILING TILES
P P BE PREPPED AND DRYFALL PAINTED
TO MATCH EXISTING EXPOSED
ELECTRICAL ELECTRICAL
STAIR STRUCTURE WHERE APPLICABLE.
ROOM ROOM
- U.N.O. EXISTING LIGHTING TO BE
B107A B107 REUSED, BUT MAY NEED TO BE
171 SF 227 SF 33 SF ACT-01
RELOCATED DURING INSTALLATION OF
7'-10" A.F.F.
STORAGE NEW HVAC AND DRYFALL PAINTING.
B1 ACT-01 B105A
8'-0" A.F.F. 18 1'-4"
A-540
OPEN TO LEVEL 2
GWB EX 1'-4" GWB EX ACT-01 EXISTING EXPOSED WOOD BEAM ARMSTRONG WOODWORKS ACOUSTICAL
7'-9" A.F.F. 7'-9" A.F.F. 9'-1" A.F.F. PLANK CLOUD
01 CLASSROOM
GWB EX B1 01 B1 B106
7'-9" A.F.F. A-540 A-540
1'-4"
GWB EX
Q STUDY AREA 01 Q
7'-7" A.F.F.
144 ADVANCED
18 ACT-01
7'-8" A.F.F. CIRCUIT AREA N.I.C.
6'-0"
OFFICE LABORATORY
ACT-01 B108B ACT-01 B105
8'-0" A.F.F. ACT-01 7'-10" A.F.F. 1278 SF
A140
ACT-01 SERVER ADMIN OFFICE OFFICE 18 PROVIDE NEW CEILING WITH NEW LIGHTING AS SHOWN. IF NO NEW LIGHTING IS SHOWN, DESIGN
ACT-01 8'-11" A.F.F. ACT-01 ROOM A102 ACT-01 WORKROOM / A103 INTENT IS TO REUSE EXISTING WALL SCONCES. COORDINATE WITH ELECTRICAL LIGHTING PLANS
8'-11" A.F.F. 8'-11" A.F.F. 7'-4" A.F.F.
OFFICE OFFICE
A100A BREAKROOM 181 SF AS REQUIRED. PATCH TOP OF PERIMETER WALLS AS REQUIRED WHERE EXISTING CEILNGS WERE
97 SF A102B OFFICE
OFFICE OFFICE A136 A138 ACT-01 REMOVED.
A106
7'-4" A.F.F.
A124 A126 139 SF 19 PROVIDE SOUND BOOTS AT HVAC ABOVE CEILING AND INSULATE AS REQUIRED ABOVE CEILING TO
ACT-01 GWB-X1
MITIGATE SOUND TRANSFER BETWEEN OFFICES.
U 31 U
8'-11" A.F.F. 7'-0" A.F.F. 21 IF POSSIBLE, EXISTING DRYWALL BULIKHEAD AND/OR CEILING AND LIGHTING ARE TO REMAIN;. iF
GWB-X1
31 CIRCULATION CEILING MUST BE PARTIALLY DEMOLISHED TO ACCOMODATE NEW HVAC CONFIGURATION, PATCH
WORKROOM / 7'-0" A.F.F.
-
CIRCULATION BREAKROOM OFFICE WITH NEW AS NEEDED AND REPAINT BULKHEAD. IF ADJACENT DRYWALL CEILING AT HIGHER
ACT-01 A107
APPLICATIONS -
8'-11" A.F.F.
A122 ACT-01 STORAGE 138 SF
ELEVATION IS BEING REMOVED TO BE REPLACED BY ACT GRID CIELING, DEISGN INTENT IS FOR
READING 8'-6" A.F.F. A104B NEW ACT CEILING TO BE 1" LOWER THAN REMOVED DRYWALL SUCH THAT MINIMAL TOUCH UP
ROOM ACT-01 33 WORK IS REQUIRED AT PERIMETER OF BULKHEAD TO REMIAN. REUSE LIGHTING IF POSSIBLE.
A130 8'-0" A.F.F. OFFICE
A101
CONFIRM DESIGN INTENT WITH ARCHITECT PRIOR TO REPLACEMENT.
GWB-X1 OFFICE
OFFICE OFFICE SAFE
A128
6'-10" A.F.F.
A118 ELEC. AND A104A A104 OFFICE 23 NEW SURFACE MOUNTED LINEAR LIGHTING TO MATCH OTHER FIXTURES ON THIS FLOOR. THESE
ACT-01 ACT-01 ELEC. STORAGE A108 ARE REPLACING FIXTURES WITH RED HOUSING THAT WERE REMOVED.
9'-0" A.F.F. 8'-11" A.F.F. 141 SF
ACT-01 A118A A101A
STORAGE
ACT-01 8'-11" A.F.F. 25 DESIGN INTENT IS FOR NEWLY CONSTRUCTED CEIING AND LIGHTING TO REMAIN. IF MECHANICAL
A120A 8'-11" A.F.F. WORK PROHIBITS THIS, SALVAGE REMOVED COMPONENTRY AND REINSTALL OR REPLACE WITH
V V
ADMIN OFFICE NEW TO MATCH EXISTING.
GWB EX CIRCULATION STORAGE CIRCULATION A113
A120 A120B - CIRCULATION
8'-0" A.F.F. ACT-01 -
33 26 REFERENCE ELECTRICAL DRAWINGS FOR NEW LIGHTING IN NEWLY CONSTRUCTED ROOMS.
9'-3" A.F.F. 27 ADDED FIXTURE FOR INCREASED LIGHT LEVEL
OFFICE 29 ALIGN EXTENDED NEW GRID WITH EXISTING. GRID AND TILE MUST MATCH EXISTING ADJACENT COPYRIGHT NOTICE: THIS ARCHITECTURAL AND ENGINEERING DRAWING IS GIVEN IN CONFIDENCE
A109 CEILING AND EXTENSION TO APPEAR SEAMLESS. AND SHALL BE USED ONLY PURSUANT TO THE AGREEMENT WITH RATIO. NO OTHER USE,
OFFICE OFFICE 205 SF
DISSEMINATION OR DUPLICATION MAY BE MADE WITHOUT PRIOR WRITTEN CONSENT OF RATIO. ALL
ACT-01 COMMON LAW RIGHTS OF COPYRIGHT AND OTHERWISE ARE HEREBY SPECIFICALLY RESERVED.
A121 OFFICE OFFICE OFFICE OFFICE OFFICE A116 OFFICE OFFICE OFFICE OFFICE OFFICE 30 EXISTING HARDLID CEILING AND SUSPENDED CLOUDS REQUIRE REMOVAL FOR HVAC WORK..
9'-3" A.F.F.
A123 A125 A127 A129 A117 A115 A114 A112 A111 A110
PROVIDE NEW 2'X2' ACT GRID AND CEILING AS SHOWN. REUSE EXISTING LINEAR PENDANTS AND PROJECT NO. 19010.000
ADD ADDITIONAL LIGHTING FOR NEW LIVE VEGETATION WALL AND DECORATIVE PENDANTS AT
SHEET TITLE
CAFE. AS SHOWN IN ELECTRICAL DRAWINGS..
31 PROVIDE NEW DRYWALL BULKHEAD AS SHOWN TO MATCH CONSTRUCTION ASSEMBLY OF OTHER FIRST LEVEL
W W BULKHEADS IN ADJACENT AREA.
32 REMOVE HORIZONTAL PORTIONS OF HARDLID CEILINGS ON SOUTH ABOVE STAGE AND ALONG REFLECTED CEILING
EAST WALL. VERTICAL PORTION OF THESE BULKHEADS CAN REMAIN FOR EASE OF
PLAN - AREA 1
4/1/2021 12:07:34 PM
GWB-X1
8'-11" A.F.F.
GWB-X1
GWB-X1
11'-3" A.F.F. TYP.
A. THESE GENERAL NOTES APPLY TO SERIES A-130 REFLECTED CEILING DRAWINGS.
B. INSTALL NEW ACT CEILINGS AT 1" LOWER THAN EXISTING HEIGHT UNLESS NOTED OTHERWISE.
G.C. TO COORDINATE PROVISION OF INFORMATION REGARDING EXISTING CEILING HEIGHTS.
RHIT MOENCH
GWB-X1
11'-3" A.F.F. TYP.
TYP.
TYP.
C7
A-622
11'-3" A.F.F.
TYP. GWB-X1 TYP.
8'-11" A.F.F.
GWB-X1
8'-11" A.F.F. TYP.
CONFIRM ALL CEILING HEIGHTS INDICATED ON PLAN AND IMMEDIATELY REQUEST
CONFIRMATION FROM ARCHITECT IF THERE IS A CONFLICT BETWEEN HEIGHT SHOWN ON PLAN
AND ACHIEVING HEIGHT 1" LOWER THAN CURRENTLY IN FIELD.
RENOVATION
7"
6"
6"
7"
A A C. UNLESS NOTED OR SHOWN OTHERWISE, EXISTING BULKHEADS ARE TO REMAIN, UNLESS
REMOVAL IS REQUIRED FOR HVAC INSTALLATION. IF REPAINTING IS REQUIRED, MATCH EXISTING
FINISHES.
5500 Wabash Avenue
WT-01 WT-01 WT-01 WT-01 WT-01 WT-01 WT-01 WT-01 WT-01 WT-01 WT-01 WT-01 WT-01 WT-01 WT-01 WT-01 WT-01
D. UNLESS NOTED OTHERWISE, ALL ROOMS SHOWN AS OPEN DECK TO REMAIN ARE TO ALSO
ASSUME THAT EXISTING LIGHTING IS TO REMAIN AND EXISTING CEILING FINISHES ARE TO
Terre Haute, Indiana
REMAIN..
FACULTY
OFFICE
FACULTY
OFFICE
FACULTY
OFFICE
FACULTY
OFFICE
FACULTY
OFFICE
FACULTY
OFFICE
FACULTY
OFFICE
FACULTY
OFFICE
FACULTY
OFFICE
FACULTY
OFFICE
FACULTY
OFFICE
FACULTY
OFFICE
FACULTY
OFFICE
FACULTY
OFFICE
FACULTY
OFFICE
FACULTY
OFFICE
E. UNLESS NOTED OR SHOWN OTHERWISE, ALL ROOMS SHOWN WITH NEW GRID TO RECIEVE NEW
2'X2' ACOUSTICAL CEILING GRID (BASIS OF DESIGN IS ARMSTRONG 1732 WITH TEGULAR REVEAL
47803
F137 F135 F133 F131 F129 F127 F125 F123 F121 F119 F117 F115 F113 F111 F109 F107 DEPT. HEAD
6" EDGE AND CORRESPONDING CHICAGO METALLIC 15/16" EXPOSED TEE GRID). GRID IS INTENDED
F105A
TO BE SHOWN IN THE PLANS AND INSTALLED
Owner
7" 26 19 GWB-X1
ACT-01 ACT-01 ACT-01 ACT-01 ACT-01 ACT-01 ACT-01 ACT-01 ACT-01 ACT-01 ACT-01 ACT-01 ACT-01 ACT-01 ACT-01 ACT-01 ACT-01 8'-11" A.F.F. TYP.
F. AT EXISTING LOCATION SUCH THAT EXISTING LIGHTING TO BE RAISED ABOVE GRID DURING Rose-Hulman Institute of Technology
9'-0" A.F.F. 9'-0" A.F.F. 9'-0" A.F.F. 9'-0" A.F.F. 9'-0" A.F.F. 9'-0" A.F.F. 9'-0" A.F.F. 9'-0" A.F.F. 9'-0" A.F.F. 9'-0" A.F.F. 9'-0" A.F.F. 9'-0" A.F.F. 9'-0" A.F.F. 9'-0" A.F.F. 9'-0" A.F.F. 9'-0" A.F.F. CEILING WORK AND THEN CLEANED, SERVICED AS REQUIRED AND RELOCATED INTO NEW GRID 5500 Wabash Avenue
9'-0" A.F.F. GWB-X1 ONCE CEILING WORK IS COMPLETED. THIS MEANS THAT THE CEILING GRID IS NOT NECESSARILY
26 26 26 19 26 19 26 19 26 19 26 19 26 19 26 19 19 26 19 26 26 19 26 19 26 19 26 19 26 19 11'-3" A.F.F. TYP. CENTERED IN THE ROOM TO ALLOW FOR REUSE OF LIGHTING CONDUIT. IN NEW AREAS WITH
Terre Haute, Indiana 47803
19 19 812-877-1511
GRID THAT DID NOT PREVIOUSLY HAVE GRID CEILING, CENTER WITHIN SPACE AS SHOWN.
ACT-01
9'-0" A.F.F. G. CENTER PENETRATIONS IN ACOUSTICAL CEILING SYSTEMS WITHIN INDIVIDUAL CEILING PANELS,
B B SUCH AS SPRINKLER HEADS, DIFFUSERS, LIGHT FIXTURES, ETC., UNLESS OTHERWISE
18 18 26 19 WT-01 INDICATED.
H. PAINT NEW GYPSUM BOARD CEILING SURFACES AS SHOWN ON RCP'S.
ADMIN OFFICE
I. PROVIDE CONTROL JOINTS (C.J.) IN GYPSUM BOARD CEILING CONSTRUCTION AS INDICATED.
WT-01 18 F105 WHERE NOT SHOWN, PROVIDE MAXIMUM SPACING BETWEEN JOINTS OF 30'-0”. VERIFY FINAL
GWB-X1 19 26 ACT-01 CONTROL JOINT LOCATIONS WITH ARCHITECT PRIOR TO STARTING WORK WHETHER OR NOT
8'-11" A.F.F. 9'-0" A.F.F. ACT-01 ACT-01 ACT-01 ACT-01 ACT-01 ACT-01 INDICATED ON THE DRAWINGS.
ACT-01 ACT-01
9'-0" A.F.F. 7'-9" A.F.F. 7'-9" A.F.F. 7'-9" A.F.F. 7'-9" A.F.F. 7'-9" A.F.F. 7'-9" A.F.F. J. CEILING ACCESS PANELS INDICATED ARE NOT INTENDED TO LIMIT NUMBER OF PANELS
9'-0" A.F.F. FACULTY
GWB-X1 EXP WT-01 ACT-01 REQUIRED. PANEL QUANTITY SHALL BE SUFFICIENT TO PROVIDE REQUIRED ACCESS WHETHER
11'-3" A.F.F. OFFICE FACULTY FACULTY FACULTY FACULTY FACULTY FACULTY 8'-8" A.F.F. FACULTY FACULTY 9'-0" A.F.F. TYP. OR NOT INDICATED ON THE DRAWINGS. VERIFY FINAL LOCATIONS WITH ARCHITECT PRIOR TO
OFFICE FACULTY ACT-01
FACULTY F130 OFFICE OFFICE OFFICE OFFICE COLLISION FACULTY OFFICE OFFICE GWB-X1 STARTING WORK. Architect
DATA OFFICE FACULTY 9'-0" A.F.F.
OFFICE F128 F126 F124 F122 F120 F116 OFFICE F108 F106 11'-3" A.F.F. TYP. K. NEW EXPOSED DUCTS/ HVAC UNITS AT EXPOSED STAINED WOOD DECK CEILINGS TO BE BRUSH
19 26 ALIGN F114 F112
F110 OFFICE RATIO
F132 PAINTED IN APPROPRIATE COATING TO MATCH PT-01, VERIFY COLOR OF PAINT AT ALL OTHER
26 26 19 26 19 26 26 26 ALIGN F103 26 19 LOCATIONS OF EXPOSED DUCTWORK AND HVAC UNITS. 101 South Pennsylvania Street
18 19 19 19 19 26 19 26 19 26 19 26 19 Indianapolis, Indiana 46204
C PT-01 C
317-633-4040
CIRCULATION A2
GWB-X1
?
GWB-X1
7'-9" A.F.F. 18 FACULTY
ACT-01
9'-0" A.F.F.
CEILING LEGEND
ALIGN 7'-9" A.F.F. PT-01
- A-540 ? OFFICE
F101 JAN
128 SF
F100 Structural Engineer
ALIGN CEILING TAG
ACT-01 A2 19 26 EXP Fink Roberts & Petrie, Inc.
8'-8" A.F.F. A-540 8'-8" A.F.F. CEILING TYPE
18 XXX-01 9449 Priority Way W Dr #200
ACT-01 18 10'-10" A.F.F. Indianapolis, Indiana 46240
CEILING HEIGHT
8'-8" A.F.F. 317-872-8400
18 (ABOVE FINISH FLOOR)
STAIR
-
9.8 119 SF 8.9 7.9 6.9 5.9 5.5 5.1 4.1 3.1 2.1 1.2
GWB-X1 SPOT ELEVATION MARKER Mechanical / Electrical Engineer
7'-2" A.F.F.
R.E. Dimond & Associates, Inc.
D D 732 N Capitol Avenue
ACT-01 EXISTING PAINTED GYB BOARD CEILING NEW OR PATCHED PAINTED GYB BOARD Indianapolis, Indiana 46204
EQUIPMENT 8'-8" A.F.F. 18
REPAIR ROOM OR BULKHEAD AS SHOWN ON PLAN CEILING OR BULKHEAD AS SHOWN ON 317-634-4672
27 E107A PLAN
SERVER/EQUIP. 18
N10 N9 N8 N7 STORAGE
N6 N5 N4 ACT-01 N3 N2 N1
5'-0"
E107C 18 8'-0" A.F.F.
ACT-01 ACT-01 CLASSROOM
27 7'-9" A.F.F. 7'-9" A.F.F. EXP E104
ACT-01 1958 SF
GWB-X1 9'-0" A.F.F. ELEV 1 7'-7" A.F.F. EXPOSED STRUCTURE TO REMAIN AS-
5'-0"
2 1/4" 7'-1" A.F.F. 18 BUILDING STANDARD 2'X2' GRID AND
- IS UNLESS NOTED OTHERWISE. NEW
84 SF DUCTWORK AND HVAC EQUIPMENT TO CEILING TILES
27 ACT-01
18 BE PREPPED AND DRYFALL PAINTED
EQ.
7'-10" A.F.F.
WOMENS R.R. TO MATCH EXISTING EXPOSED
E E109 E STRUCTURE WHERE APPLICABLE.
GWB-X1
TECHNICIAN EXP U.N.O. EXISTING LIGHTING TO BE
7'-1" A.F.F.
OFFICE 7'-9" A.F.F. REUSED, BUT MAY NEED TO BE
ACT-01 E107B RELOCATED DURING INSTALLATION OF
7'-10" A.F.F. MENS R.R. NEW HVAC AND DRYFALL PAINTING.
EXP
OPEN TO LEVEL 2 9'-0" A.F.F. E108
21 OPEN TO LEVEL 2
ACT-01
WORKSHOP 18 7'-8" A.F.F. EXISTING EXPOSED WOOD BEAM ARMSTRONG WOODWORKS ACOUSTICAL
E107 PLANK CLOUD
GWB-X2 CIRCULATION
7'-3" A.F.F. -
GWB EX
8'-0" A.F.F.
GWB-X1 AREA N.I.C.
F 7'-3" A.F.F. F
OFFICE
E102
ACT-01
EXP
21 7'-10" A.F.F.
9'-0" A.F.F.
CEILING PLAN NOTES F
GWB-X1
7'-3" A.F.F. 3 G
GWB EX
04 04 7'-9" A.F.F.
OFFICE
E101 01 IF POSSIBLE, REUSE EXISTNG VERTICAL AND PORTION OF HORIZONTAL FACE OF EXISITNG
E
2
ACT-01 BULkHEAD TO CREATE PERIMETER OF NEW ACT CEILING AS SHOWN. REPAINT AS REQUIRED TO
7'-10" A.F.F. MATCH EXISTING BUIDLING STANDARD. D
G G 02 RECONSTRUCT PERIMETER BULKHEADS WHERE HVAC WORK REQUIRED REMOVAL TO REPLICATE
ORIGINAL CONSTRUCTION AND LIGHTING. C
OFFICE OFFICE OFFICE
D113 D108 D107 03 PROVIDE NEW SURFACE MOUNTED LINEAR LIGHTING TO MATCH OTHER LINEAR LIGHTING ON THIS
FLOOR. PATCH AND PAINT EXPOED CEILING ELEMENTS AS REQUIRED.
B 1
ACT-01
7'-9" A.F.F. ACT-01 ACT-01 04
EXP REFERENCE 7'-3" A.F.F. 7'-9" A.F.F. A
9'-0" A.F.F. (CONFERENCE) 05 NO HEADER AT THIS LOCATION . PROVIDE BLOCKING ABOVE CEIILNG TO SUPPORT DOOR FRAME
CLASSROOM ROOM
D112
INSERTED WITHINT FINISHED OPENING. DRYWALL CEILING IS CONTINUOUS.
D110
ENERGY 21 OFFICE OFFICE PT-01 08 PROVIDE ALTERNATE BID TO REPLACE EXISTING LIGHTING WITH NEW SURFACE MOUNTED LINEARS KEY PLAN
OFFICE
CONVERSION D111-1 D111 TO MATCH OTHER LINEAR LIGHITNG ON THIS FLOOR. INCLUDE POSSIBLE TOUCH UP THAT MAY BE
ACT-01 ACT-01 D106
AND POWER EXP
132 SF 149 SF ACT-01 SEAL | DATE 04/01/21
SYSTEMS
7'-10" A.F.F. 7'-11" A.F.F.
7'-3" A.F.F. REQUIRED TO CEILING AFTER CHANGE IN LIGHTING.
7'-9" A.F.F.
LABORATORY 09 ACOUSTICAL LINEAR WOOD PLANK CEILING EQUAL TO ARMSTRONG WOODWORKS GRILLE WITH
H GWB-X1 ACT-01 H
D114 ACT-01
EXP ACT-01 ACT-01 7'-2" A.F.F. OFFICE 7'-10" A.F.F. NRC OF .90. WHERE SHOWN, ASSUME RECESSED LINEAR LIGHTING EQUAL TO FOCAL POINT SEEM
7'-1 1/2" A.F.F.
9'-0" A.F.F. 7'-10" A.F.F. 7'-9" A.F.F. D109 2.
11 DESIGN INTENT IS TO EXPOSED STRUCTURE CEILING - PAINT DRYFALL PAINT IF NOT WOOD TIMBER.
GWB-X1 GWB-X1 . PROVIDE SURFACE MOUNTED LED LINEAR FIXTURES TO MATCH NEW BUILDING STANDARD IN
7'-1" A.F.F. 7'-1" A.F.F. OFFICE QUANTITIES AND PLACEMENT TO ACHIEVE APPROPRIATE FOOTCANDLE LEVELS RECOMMENDED
21 D105 FOR INDICATED ROOM FUNCTION PER IES STANDARDS IF EXPOSING THE EXISTING STRUCTURE IS
OPEN TO LEVEL 2 21 GWB EX
EXP 7'-9" A.F.F. ACT-01 NOT POSSIBLE DUE TO UNFORESEEN CIRCUMSTANCES, PROVIDE STANDARD 2'X2' ACT TILE WITH
9'-0" A.F.F. 7'-10" A.F.F.
ACT-01 NEW RECESSED LIGHTING AS SHOWN.
21 GWB EX 7'-10" A.F.F.
7'-9" A.F.F. 12 EXPOSED STRUCTURE CEILING. RECONFIGURE DUCTS, PIPES AND CONDUIT AS REQUIRED TO
MINIMIZE IN EXPOSED AREAS WHERE POSSIBLE, DRYFALL PAINT AND PROVIDE PROVIDE NEW SHEET ISSUE
J ACT-01 GWB EX GWB-X1 J LIGHTING AS SHOWN IN ELECTRICAL PLANS. 1 Construction Documents 04/01/21
7'-9" A.F.F. 7'-1" A.F.F. 7'-1" A.F.F.
OFFICE 14 REPAINT DRYWALL AND REPLACE EXISTING DOWNLIGHTS WITH NEW LED DOWNLIGHTS.
D104 17 PROVIDE MOTORIZED PROJECTION SCREEN AT FRONT OF ROOM AND PROJECTOR MOUNT TO
EXP
9'-0" A.F.F. ACT-01
COORDINATE WITH PROJECTOR AND SPACED AS REQUIRED. COORDINATE STRUCTURAL SUPPORT
ACT-01 7'-10" A.F.F. AS REQUIRED.
GWB-X1 GWB-X1 7'-10" A.F.F. 18 PROVIDE NEW CEILING WITH NEW LIGHTING AS SHOWN. IF NO NEW LIGHTING IS SHOWN, DESIGN
7'-1" A.F.F. 7'-1" A.F.F. INTENT IS TO REUSE EXISTING WALL SCONCES. COORDINATE WITH ELECTRICAL LIGHTING PLANS
21 EXP
ACT-01 9'-0" A.F.F. AS REQUIRED. PATCH TOP OF PERIMETER WALLS AS REQUIRED WHERE EXISTING CEILNGS WERE
7'-2" A.F.F. OFFICE
ELECTRONIC D103 REMOVED.
CIRCUITS CALIBRATION EXP
LABORATORY ECE LAB TECH LEARNING 19 PROVIDE SOUND BOOTS AT HVAC ABOVE CEILING AND INSULATE AS REQUIRED ABOVE CEILING TO
LABORATORY 7'-9" A.F.F. CENTER DESIGN LAB
K D115 D116 D117
D101-A D101 K MITIGATE SOUND TRANSFER BETWEEN OFFICES.
ACT-01 ACT-01
7'-1 1/2" A.F.F. 7'-10" A.F.F. 21 IF POSSIBLE, EXISTING DRYWALL BULIKHEAD AND/OR CEILING AND LIGHTING ARE TO REMAIN;. iF
GWB-X1 CEILING MUST BE PARTIALLY DEMOLISHED TO ACCOMODATE NEW HVAC CONFIGURATION, PATCH
ACT-01 OFFICE 7'-1" A.F.F. WITH NEW AS NEEDED AND REPAINT BULKHEAD. IF ADJACENT DRYWALL CEILING AT HIGHER
7'-11" A.F.F. D118 EXP
ACT-01
ACT-01 ELEVATION IS BEING REMOVED TO BE REPLACED BY ACT GRID CIELING, DEISGN INTENT IS FOR
9'-0" A.F.F. 7'-10" A.F.F.
OPEN TO LEVEL 2 STORAGE 7'-11" A.F.F. ACT-01
OFFICE
NEW ACT CEILING TO BE 1" LOWER THAN REMOVED DRYWALL SUCH THAT MINIMAL TOUCH UP
D115A 7'-10" A.F.F.
PT-01 D102 WORK IS REQUIRED AT PERIMETER OF BULKHEAD TO REMIAN. REUSE LIGHTING IF POSSIBLE.
CONFIRM DESIGN INTENT WITH ARCHITECT PRIOR TO REPLACEMENT.
21 CIRCULATION
ACT-01
-
ACT-01
23 NEW SURFACE MOUNTED LINEAR LIGHTING TO MATCH OTHER FIXTURES ON THIS FLOOR. THESE
7'-1" A.F.F. 7'-10" A.F.F. ARE REPLACING FIXTURES WITH RED HOUSING THAT WERE REMOVED.
GWB-X1 GWB-X1
7'-1" A.F.F. PT-01 PT-01 7'-1" A.F.F. 25 DESIGN INTENT IS FOR NEWLY CONSTRUCTED CEIING AND LIGHTING TO REMAIN. IF MECHANICAL
L INSTRUMENT L
ROOM WORK PROHIBITS THIS, SALVAGE REMOVED COMPONENTRY AND REINSTALL OR REPLACE WITH
EQUIPMENT NEW TO MATCH EXISTING.
C114 OFFICE
STORAGE
WORKSHOP/STORAGE C110
C115A
C112
26 REFERENCE ELECTRICAL DRAWINGS FOR NEW LIGHTING IN NEWLY CONSTRUCTED ROOMS.
ACT-01 27 ADDED FIXTURE FOR INCREASED LIGHT LEVEL
7'-9" A.F.F. ACT-01
7'-9" A.F.F. COPYRIGHT NOTICE: THIS ARCHITECTURAL AND ENGINEERING DRAWING IS GIVEN IN CONFIDENCE
21 EXP 29 ALIGN EXTENDED NEW GRID WITH EXISTING. GRID AND TILE MUST MATCH EXISTING ADJACENT AND SHALL BE USED ONLY PURSUANT TO THE AGREEMENT WITH RATIO. NO OTHER USE,
9'-0" A.F.F. CEILING AND EXTENSION TO APPEAR SEAMLESS. DISSEMINATION OR DUPLICATION MAY BE MADE WITHOUT PRIOR WRITTEN CONSENT OF RATIO. ALL
ACT-01 ACT-01 COMMON LAW RIGHTS OF COPYRIGHT AND OTHERWISE ARE HEREBY SPECIFICALLY RESERVED.
7'-2" A.F.F. 7'-9" A.F.F. 30 EXISTING HARDLID CEILING AND SUSPENDED CLOUDS REQUIRE REMOVAL FOR HVAC WORK..
PROVIDE NEW 2'X2' ACT GRID AND CEILING AS SHOWN. REUSE EXISTING LINEAR PENDANTS AND PROJECT NO. 19010.000
OFFICE
OPEN TO LEVEL 2 MECHATRONICS C109
ADD ADDITIONAL LIGHTING FOR NEW LIVE VEGETATION WALL AND DECORATIVE PENDANTS AT SHEET TITLE
CAFE. AS SHOWN IN ELECTRICAL DRAWINGS..
C111
31 PROVIDE NEW DRYWALL BULKHEAD AS SHOWN TO MATCH CONSTRUCTION ASSEMBLY OF OTHER
FIRST LEVEL
ACT-01
18
B1
A-540
7'-9" A.F.F.
32
BULKHEADS IN ADJACENT AREA.
REMOVE HORIZONTAL PORTIONS OF HARDLID CEILINGS ON SOUTH ABOVE STAGE AND ALONG
REFLECTED CEILING
EAST WALL. VERTICAL PORTION OF THESE BULKHEADS CAN REMAIN FOR EASE OF PLAN - AREA 2
4/1/2021 12:07:36 PM
9.8 8.9 7.9 6.9 5.9 5.5 5.1 4.1 3.1 2.1 1.2
RECONSTRUCITON AFTER HVAC WORK IS COMPLETED. DRYWALL WRAPPED TRUSSES AND
COFFERED CIELING AT NORTH END ARE TO REMAIN. REPLACE EXISTING WOOD SLAT CEILING WITH
NEW 2X2 ACT CEILING.
1 FIRST LEVEL - AREA 2 33 REPAIR PORTION OF DEMOLISHED CEILING AND FLOOR ABOVE IF APPLICABLE TO MATCH EXISITNG
SHEET NUMBER
A-133.2
1/8" = 1'-0"
CONSTRUCTION ASSEMBLY AND MATERIALS SUCH THAT REPAIR IS VISIBLY SEAMLESS, INCLUDING
FLOORING FINISHES ON LEVEL ABOVE. A-133.2
GENERAL CEILING PLAN NOTES
A. THESE GENERAL NOTES APPLY TO SERIES A-130 REFLECTED CEILING DRAWINGS.
B. INSTALL NEW ACT CEILINGS AT 1" LOWER THAN EXISTING HEIGHT UNLESS NOTED OTHERWISE.
G.C. TO COORDINATE PROVISION OF INFORMATION REGARDING EXISTING CEILING HEIGHTS.
RHIT MOENCH
CONFIRM ALL CEILING HEIGHTS INDICATED ON PLAN AND IMMEDIATELY REQUEST
CONFIRMATION FROM ARCHITECT IF THERE IS A CONFLICT BETWEEN HEIGHT SHOWN ON PLAN
AND ACHIEVING HEIGHT 1" LOWER THAN CURRENTLY IN FIELD.
C. UNLESS NOTED OR SHOWN OTHERWISE, EXISTING BULKHEADS ARE TO REMAIN, UNLESS
RENOVATION
REMOVAL IS REQUIRED FOR HVAC INSTALLATION. IF REPAINTING IS REQUIRED, MATCH EXISTING
FINISHES.
5500 Wabash Avenue
D. UNLESS NOTED OTHERWISE, ALL ROOMS SHOWN AS OPEN DECK TO REMAIN ARE TO ALSO
ASSUME THAT EXISTING LIGHTING IS TO REMAIN AND EXISTING CEILING FINISHES ARE TO
REMAIN..
Terre Haute, Indiana
E. UNLESS NOTED OR SHOWN OTHERWISE, ALL ROOMS SHOWN WITH NEW GRID TO RECIEVE NEW
2'X2' ACOUSTICAL CEILING GRID (BASIS OF DESIGN IS ARMSTRONG 1732 WITH TEGULAR REVEAL 47803
EDGE AND CORRESPONDING CHICAGO METALLIC 15/16" EXPOSED TEE GRID). GRID IS INTENDED
TO BE SHOWN IN THE PLANS AND INSTALLED Owner
F. AT EXISTING LOCATION SUCH THAT EXISTING LIGHTING TO BE RAISED ABOVE GRID DURING
CEILING WORK AND THEN CLEANED, SERVICED AS REQUIRED AND RELOCATED INTO NEW GRID Rose-Hulman Institute of Technology
ONCE CEILING WORK IS COMPLETED. THIS MEANS THAT THE CEILING GRID IS NOT NECESSARILY 5500 Wabash Avenue
CENTERED IN THE ROOM TO ALLOW FOR REUSE OF LIGHTING CONDUIT. IN NEW AREAS WITH Terre Haute, Indiana 47803
GRID THAT DID NOT PREVIOUSLY HAVE GRID CEILING, CENTER WITHIN SPACE AS SHOWN. 812-877-1511
G. CENTER PENETRATIONS IN ACOUSTICAL CEILING SYSTEMS WITHIN INDIVIDUAL CEILING PANELS,
SUCH AS SPRINKLER HEADS, DIFFUSERS, LIGHT FIXTURES, ETC., UNLESS OTHERWISE
INDICATED.
H. PAINT NEW GYPSUM BOARD CEILING SURFACES AS SHOWN ON RCP'S.
I. PROVIDE CONTROL JOINTS (C.J.) IN GYPSUM BOARD CEILING CONSTRUCTION AS INDICATED.
WHERE NOT SHOWN, PROVIDE MAXIMUM SPACING BETWEEN JOINTS OF 30'-0”. VERIFY FINAL
CONTROL JOINT LOCATIONS WITH ARCHITECT PRIOR TO STARTING WORK WHETHER OR NOT
INDICATED ON THE DRAWINGS.
J. CEILING ACCESS PANELS INDICATED ARE NOT INTENDED TO LIMIT NUMBER OF PANELS
REQUIRED. PANEL QUANTITY SHALL BE SUFFICIENT TO PROVIDE REQUIRED ACCESS WHETHER
OR NOT INDICATED ON THE DRAWINGS. VERIFY FINAL LOCATIONS WITH ARCHITECT PRIOR TO
STARTING WORK. Architect
CLASSROOM CLASSROOM K. NEW EXPOSED DUCTS/ HVAC UNITS AT EXPOSED STAINED WOOD DECK CEILINGS TO BE BRUSH
G308 G306
STUDENT PAINTED IN APPROPRIATE COATING TO MATCH PT-01, VERIFY COLOR OF PAINT AT ALL OTHER RATIO
WORK AREA LOCATIONS OF EXPOSED DUCTWORK AND HVAC UNITS. 101 South Pennsylvania Street
G304 Indianapolis, Indiana 46204
CLASSROOM
317-633-4040
G310
940 SF
17 ACT-01
9'-0" A.F.F.
17 CEILING LEGEND
18 CEILING TAG
18 Structural Engineer
CEILING TYPE
18 XXX-01 Fink Roberts & Petrie, Inc.
ACT-01 A7 ACT-01
9'-0" A.F.F. 9'-0" A.F.F. 10'-10" A.F.F.
A-351 CEILING HEIGHT 9449 Priority Way W Dr #200
(ABOVE FINISH FLOOR) Indianapolis, Indiana 46240
CLOSET 317-872-8400
G304A
8 SF SPOT ELEVATION MARKER
Mechanical / Electrical Engineer
CIRCULATION R.E. Dimond & Associates, Inc.
STAIR - EXISTING PAINTED GYB BOARD CEILING NEW OR PATCHED PAINTED GYB BOARD 732 N Capitol Avenue
1390 SF OR BULKHEAD AS SHOWN ON PLAN CEILING OR BULKHEAD AS SHOWN ON
- Indianapolis, Indiana 46204
178 SF PLAN
317-634-4672
ACT-01
9'-0" A.F.F.
AREA N.I.C.
F
01 IF POSSIBLE, REUSE EXISTNG VERTICAL AND PORTION OF HORIZONTAL FACE OF EXISITNG 3 G
BULkHEAD TO CREATE PERIMETER OF NEW ACT CEILING AS SHOWN. REPAINT AS REQUIRED TO
1
A-133.3
FIRST LEVEL - AREA 3 MATCH EXISTING BUIDLING STANDARD.
E
2
1/8" = 1'-0"
02 RECONSTRUCT PERIMETER BULKHEADS WHERE HVAC WORK REQUIRED REMOVAL TO REPLICATE D
ORIGINAL CONSTRUCTION AND LIGHTING.
03 PROVIDE NEW SURFACE MOUNTED LINEAR LIGHTING TO MATCH OTHER LINEAR LIGHTING ON THIS C
FLOOR. PATCH AND PAINT EXPOED CEILING ELEMENTS AS REQUIRED.
04 B 1
05 NO HEADER AT THIS LOCATION . PROVIDE BLOCKING ABOVE CEIILNG TO SUPPORT DOOR FRAME
INSERTED WITHINT FINISHED OPENING. DRYWALL CEILING IS CONTINUOUS. A
08 PROVIDE ALTERNATE BID TO REPLACE EXISTING LIGHTING WITH NEW SURFACE MOUNTED LINEARS
TO MATCH OTHER LINEAR LIGHITNG ON THIS FLOOR. INCLUDE POSSIBLE TOUCH UP THAT MAY BE KEY PLAN
REQUIRED TO CEILING AFTER CHANGE IN LIGHTING.
09 ACOUSTICAL LINEAR WOOD PLANK CEILING EQUAL TO ARMSTRONG WOODWORKS GRILLE WITH SEAL | DATE 04/01/21
NRC OF .90. WHERE SHOWN, ASSUME RECESSED LINEAR LIGHTING EQUAL TO FOCAL POINT SEEM
2.
11 DESIGN INTENT IS TO EXPOSED STRUCTURE CEILING - PAINT DRYFALL PAINT IF NOT WOOD TIMBER.
. PROVIDE SURFACE MOUNTED LED LINEAR FIXTURES TO MATCH NEW BUILDING STANDARD IN
QUANTITIES AND PLACEMENT TO ACHIEVE APPROPRIATE FOOTCANDLE LEVELS RECOMMENDED
FOR INDICATED ROOM FUNCTION PER IES STANDARDS IF EXPOSING THE EXISTING STRUCTURE IS
NOT POSSIBLE DUE TO UNFORESEEN CIRCUMSTANCES, PROVIDE STANDARD 2'X2' ACT TILE WITH
NEW RECESSED LIGHTING AS SHOWN.
12 EXPOSED STRUCTURE CEILING. RECONFIGURE DUCTS, PIPES AND CONDUIT AS REQUIRED TO
MINIMIZE IN EXPOSED AREAS WHERE POSSIBLE, DRYFALL PAINT AND PROVIDE PROVIDE NEW
LIGHTING AS SHOWN IN ELECTRICAL PLANS.
SHEET ISSUE
14 REPAINT DRYWALL AND REPLACE EXISTING DOWNLIGHTS WITH NEW LED DOWNLIGHTS.
1 Construction Documents 04/01/21
17 PROVIDE MOTORIZED PROJECTION SCREEN AT FRONT OF ROOM AND PROJECTOR MOUNT TO
COORDINATE WITH PROJECTOR AND SPACED AS REQUIRED. COORDINATE STRUCTURAL SUPPORT
AS REQUIRED.
18 PROVIDE NEW CEILING WITH NEW LIGHTING AS SHOWN. IF NO NEW LIGHTING IS SHOWN, DESIGN
INTENT IS TO REUSE EXISTING WALL SCONCES. COORDINATE WITH ELECTRICAL LIGHTING PLANS
AS REQUIRED. PATCH TOP OF PERIMETER WALLS AS REQUIRED WHERE EXISTING CEILNGS WERE
REMOVED.
19 PROVIDE SOUND BOOTS AT HVAC ABOVE CEILING AND INSULATE AS REQUIRED ABOVE CEILING TO
MITIGATE SOUND TRANSFER BETWEEN OFFICES.
21 IF POSSIBLE, EXISTING DRYWALL BULIKHEAD AND/OR CEILING AND LIGHTING ARE TO REMAIN;. iF
CEILING MUST BE PARTIALLY DEMOLISHED TO ACCOMODATE NEW HVAC CONFIGURATION, PATCH
WITH NEW AS NEEDED AND REPAINT BULKHEAD. IF ADJACENT DRYWALL CEILING AT HIGHER
ELEVATION IS BEING REMOVED TO BE REPLACED BY ACT GRID CIELING, DEISGN INTENT IS FOR
NEW ACT CEILING TO BE 1" LOWER THAN REMOVED DRYWALL SUCH THAT MINIMAL TOUCH UP
WORK IS REQUIRED AT PERIMETER OF BULKHEAD TO REMIAN. REUSE LIGHTING IF POSSIBLE.
CONFIRM DESIGN INTENT WITH ARCHITECT PRIOR TO REPLACEMENT.
23 NEW SURFACE MOUNTED LINEAR LIGHTING TO MATCH OTHER FIXTURES ON THIS FLOOR. THESE
ARE REPLACING FIXTURES WITH RED HOUSING THAT WERE REMOVED.
25 DESIGN INTENT IS FOR NEWLY CONSTRUCTED CEIING AND LIGHTING TO REMAIN. IF MECHANICAL
WORK PROHIBITS THIS, SALVAGE REMOVED COMPONENTRY AND REINSTALL OR REPLACE WITH
NEW TO MATCH EXISTING.
26 REFERENCE ELECTRICAL DRAWINGS FOR NEW LIGHTING IN NEWLY CONSTRUCTED ROOMS.
27 ADDED FIXTURE FOR INCREASED LIGHT LEVEL
29 ALIGN EXTENDED NEW GRID WITH EXISTING. GRID AND TILE MUST MATCH EXISTING ADJACENT
CEILING AND EXTENSION TO APPEAR SEAMLESS. COPYRIGHT NOTICE: THIS ARCHITECTURAL AND ENGINEERING DRAWING IS GIVEN IN CONFIDENCE
AND SHALL BE USED ONLY PURSUANT TO THE AGREEMENT WITH RATIO. NO OTHER USE,
30 EXISTING HARDLID CEILING AND SUSPENDED CLOUDS REQUIRE REMOVAL FOR HVAC WORK.. DISSEMINATION OR DUPLICATION MAY BE MADE WITHOUT PRIOR WRITTEN CONSENT OF RATIO. ALL
PROVIDE NEW 2'X2' ACT GRID AND CEILING AS SHOWN. REUSE EXISTING LINEAR PENDANTS AND COMMON LAW RIGHTS OF COPYRIGHT AND OTHERWISE ARE HEREBY SPECIFICALLY RESERVED.
ADD ADDITIONAL LIGHTING FOR NEW LIVE VEGETATION WALL AND DECORATIVE PENDANTS AT PROJECT NO. 19010.000
CAFE. AS SHOWN IN ELECTRICAL DRAWINGS..
SHEET TITLE
31 PROVIDE NEW DRYWALL BULKHEAD AS SHOWN TO MATCH CONSTRUCTION ASSEMBLY OF OTHER
BULKHEADS IN ADJACENT AREA. FIRST LEVEL
32 REMOVE HORIZONTAL PORTIONS OF HARDLID CEILINGS ON SOUTH ABOVE STAGE AND ALONG
EAST WALL. VERTICAL PORTION OF THESE BULKHEADS CAN REMAIN FOR EASE OF REFLECTED CEILING
RECONSTRUCITON AFTER HVAC WORK IS COMPLETED. DRYWALL WRAPPED TRUSSES AND
COFFERED CIELING AT NORTH END ARE TO REMAIN. REPLACE EXISTING WOOD SLAT CEILING WITH PLAN - AREA 3
4/1/2021 12:07:39 PM
A-133.3
GENERAL CEILING PLAN NOTES
9.8 8.9 7.9 6.9 5.9 5.5 5.1 4.1 3.1 2.1 1.2
1'-0"
C.J. GWB EX 01 ACT-01
01 7'-10" A.F.F. INDICATED ON THE DRAWINGS.
7'-9" A.F.F. 1'-0" J. CEILING ACCESS PANELS INDICATED ARE NOT INTENDED TO LIMIT NUMBER OF PANELS
1'-0"
STUDY AREA 1'-0" STAFF
A2 - D6 RESOURCES ACT-01 REQUIRED. PANEL QUANTITY SHALL BE SUFFICIENT TO PROVIDE REQUIRED ACCESS WHETHER
CIRCULATION B1
A-301 A-322 C200 ACT-01 8'-6" A.F.F. OR NOT INDICATED ON THE DRAWINGS. VERIFY FINAL LOCATIONS WITH ARCHITECT PRIOR TO
SKYLIGHT - SKYLIGHT A-540
STARTING WORK.
8'-6" A.F.F. OFFICE
C.J. 5103 SF
1'-0"
ACT-01
1'-0"
01 01 01 01 ACT-01 C208 K. NEW EXPOSED DUCTS/ HVAC UNITS AT EXPOSED STAINED WOOD DECK CEILINGS TO BE BRUSH Architect
8'-6" A.F.F. 18 1'-6" 8'-6" A.F.F. PAINTED IN APPROPRIATE COATING TO MATCH PT-01, VERIFY COLOR OF PAINT AT ALL OTHER
GWB EX C.J. ACT-01 RATIO
C.J. B1 LOCATIONS OF EXPOSED DUCTWORK AND HVAC UNITS.
B1 A-540 7'-10" A.F.F. 1'-6" D3 18 C.J. STORAGE 7'-10" A.F.F. 101 South Pennsylvania Street
A-540 A-322 C200A Indianapolis, Indiana 46204
N N CEILING LEGEND 317-633-4040
CIRCULATION
GWB EX CIRCULATION
ACT-01 7'-9" A.F.F. -
7'-10" A.F.F. Structural Engineer
CEILING TAG
Fink Roberts & Petrie, Inc.
CEILING TYPE
OFFICE 25 25 XXX-01 9449 Priority Way W Dr #200
ACT-01
C216 8'-0" A.F.F. 10'-10" A.F.F. CEILING HEIGHT
Indianapolis, Indiana 46240
EXPOSED 21 317-872-8400
OFFICE (ABOVE FINISH FLOOR)
WOOD DECK
ACT-01 C217 ABOVE
7'-10" A.F.F.
ACT-01 ALIGN ALIGN SPOT ELEVATION MARKER Mechanical / Electrical Engineer
7'-10" A.F.F.
R.E. Dimond & Associates, Inc.
O MECHANICAL O
ROOM
732 N Capitol Avenue
GWB-X1 ADMIN EXISTING PAINTED GYB BOARD CEILING NEW OR PATCHED PAINTED GYB BOARD Indianapolis, Indiana 46204
C201
8'-7 1/2" A.F.F. C205 OR BULKHEAD AS SHOWN ON PLAN CEILING OR BULKHEAD AS SHOWN ON 317-634-4672
OFFICE
C206 PLAN
MECHANICAL MECHANICAL
ROOM ROOM
C218 C201 ACT-01 ACT-01
8'-0" A.F.F. 7'-10" A.F.F.
EXPOSED STRUCTURE TO REMAIN AS-
IS UNLESS NOTED OTHERWISE. NEW BUILDING STANDARD 2'X2' GRID AND
DUCTWORK AND HVAC EQUIPMENT TO CEILING TILES
ALIGN ALIGN STORAGE BE PREPPED AND DRYFALL PAINTED
C205B TO MATCH EXISTING EXPOSED
P P STRUCTURE WHERE APPLICABLE.
U.N.O. EXISTING LIGHTING TO BE
REUSED, BUT MAY NEED TO BE
RELOCATED DURING INSTALLATION OF
21 GWB EX 21 NEW HVAC AND DRYFALL PAINTING.
8'-7" A.F.F.
GWB EX MECHANICAL
7'-1" A.F.F. ROOM
B202 EXISTING EXPOSED WOOD BEAM ARMSTRONG WOODWORKS ACOUSTICAL
25 W9NAA ROSE 335 SF
PLANK CLOUD
MECHANICAL TECH RADIO
GWB EX
21 ROOM CLUB
8'-7" A.F.F.
B203 B204
PT-01 ALIGN ALIGN
ACT-01
7'-7" A.F.F. AREA N.I.C.
Q 32 Q
PROJECTION ADVANCED
ROOM EXISTING CIRCUIT
B111A VERTICAL ACT-01 LABORATORY
ACT-01 CONSTRU 7'-11" A.F.F. B105
8'-0" A.F.F. CTION OF OFFICE 1278 SF CEILING PLAN NOTES
BULKHEAD STUDENT BBE HIVE B201
TO CONFERENCE 229 SF
EXISTING TO REMAIN ROOM B205 F
REMAIN -
REBUILD B205A 01 IF POSSIBLE, REUSE EXISTNG VERTICAL AND PORTION OF HORIZONTAL FACE OF EXISITNG
BULkHEAD TO CREATE PERIMETER OF NEW ACT CEILING AS SHOWN. REPAINT AS REQUIRED TO
3 G
32 NEW ACT
HORIZONT
AL AS
REQUIRED
ACT-01 ACT-01
ACT-01
7'-9" A.F.F.
STAIR
MATCH EXISTING BUIDLING STANDARD.
E
2
.
7'-10" A.F.F. 7'-8" A.F.F. CIRCULATION
ALIGN ALIGN 300-1 02 RECONSTRUCT PERIMETER BULKHEADS WHERE HVAC WORK REQUIRED REMOVAL TO REPLICATE D
PT-01 -
EXISTING TO REMAIN 111 SF ORIGINAL CONSTRUCTION AND LIGHTING.
R 32 32 R 03 PROVIDE NEW SURFACE MOUNTED LINEAR LIGHTING TO MATCH OTHER LINEAR LIGHTING ON THIS C
EXISTING FLOOR. PATCH AND PAINT EXPOED CEILING ELEMENTS AS REQUIRED.
VERTICAL
CONSTRU
CTION OF
ACT-01
8'-0" A.F.F. DIGITAL
04
05 NO HEADER AT THIS LOCATION . PROVIDE BLOCKING ABOVE CEIILNG TO SUPPORT DOOR FRAME
B 1
SYNTHETIC SIGNAL
BULKHEAD INSERTED WITHINT FINISHED OPENING. DRYWALL CEILING IS CONTINUOUS.
32 NEW ACT TO
BIOLOGY PROCESSING A
LABORATORY LAB
REMAIN - B206 B200 08 PROVIDE ALTERNATE BID TO REPLACE EXISTING LIGHTING WITH NEW SURFACE MOUNTED LINEARS
REBUILD ACT-01 TO MATCH OTHER LINEAR LIGHITNG ON THIS FLOOR. INCLUDE POSSIBLE TOUCH UP THAT MAY BE
HORIZONT 7'-11" A.F.F. KEY PLAN
AL AS
REQUIRED TO CEILING AFTER CHANGE IN LIGHTING.
REQUIRED 09 ACOUSTICAL LINEAR WOOD PLANK CEILING EQUAL TO ARMSTRONG WOODWORKS GRILLE WITH
. PT-01 ALIGN ALIGN SEAL | DATE 04/01/21
32 NRC OF .90. WHERE SHOWN, ASSUME RECESSED LINEAR LIGHTING EQUAL TO FOCAL POINT SEEM
S 32 EXISTING TO REMAIN 32 S 2.
21 GWB EX GWB EX 11 DESIGN INTENT IS TO EXPOSED STRUCTURE CEILING - PAINT DRYFALL PAINT IF NOT WOOD TIMBER.
32 NEW ACT 8'-8" A.F.F. 8'-8" A.F.F.
ELEV 2 GWB EX CLERESTORY GLAZING ABOVE . PROVIDE SURFACE MOUNTED LED LINEAR FIXTURES TO MATCH NEW BUILDING STANDARD IN
- 7'-9" A.F.F. QUANTITIES AND PLACEMENT TO ACHIEVE APPROPRIATE FOOTCANDLE LEVELS RECOMMENDED
42 SF
GM ROOM 21 E5 FOR INDICATED ROOM FUNCTION PER IES STANDARDS IF EXPOSING THE EXISTING STRUCTURE IS
EXISTING A-321
32 B111 MECHANICAL NOT POSSIBLE DUE TO UNFORESEEN CIRCUMSTANCES, PROVIDE STANDARD 2'X2' ACT TILE WITH
VERTICAL ROOM
S10 S9 CONSTRUCTION S8 S7 S6 S5 21 S4 S3 S2 S1 NEW RECESSED LIGHTING AS SHOWN.
B207
PT-01 OF BULKHEAD TO 469 SF 12 EXPOSED STRUCTURE CEILING. RECONFIGURE DUCTS, PIPES AND CONDUIT AS REQUIRED TO
REMAIN - REBUILD
HORIZONTAL AS
21
GWB EX
CIRCULATION 21 MINIMIZE IN EXPOSED AREAS WHERE POSSIBLE, DRYFALL PAINT AND PROVIDE PROVIDE NEW
REQUIRED. 21 - GWB EX LIGHTING AS SHOWN IN ELECTRICAL PLANS.
GWB EX 11'-2" A.F.F. 8'-8" A.F.F.
8'-8" A.F.F. E1 SHEET ISSUE
14 REPAINT DRYWALL AND REPLACE EXISTING DOWNLIGHTS WITH NEW LED DOWNLIGHTS.
T A-321 T 1 Construction Documents 04/01/21
17 PROVIDE MOTORIZED PROJECTION SCREEN AT FRONT OF ROOM AND PROJECTOR MOUNT TO
4'-11" 6'-4" 4'-11" GWB EX COORDINATE WITH PROJECTOR AND SPACED AS REQUIRED. COORDINATE STRUCTURAL SUPPORT
10" 2" 24'-0" 2" 10" 7'-2" A.F.F.
CIRCULATION AS REQUIRED.
10"
ACT-01
- 7'-4" A.F.F. 18 PROVIDE NEW CEILING WITH NEW LIGHTING AS SHOWN. IF NO NEW LIGHTING IS SHOWN, DESIGN
9.8 8.9 7.9 6.9 5.9 5.5 5.1 4.1 3.1 2.1 ACT-01
1.2 INTENT IS TO REUSE EXISTING WALL SCONCES. COORDINATE WITH ELECTRICAL LIGHTING PLANS
2"
ADMIN OFFICE OFFICE MENS R.R. 11'-4" A.F.F. AS REQUIRED. PATCH TOP OF PERIMETER WALLS AS REQUIRED WHERE EXISTING CEILNGS WERE
ACT-01
A218 A218A AWP-01 7'-4" A.F.F. CIRCULATION
11'-0" A.F.F. E1 A223
-
REMOVED.
A-540
ACT-01 CUSTODIAL CLASSROOM 19 PROVIDE SOUND BOOTS AT HVAC ABOVE CEILING AND INSULATE AS REQUIRED ABOVE CEILING TO
11'-3" A.F.F. ACT-01 WOMENS R.R.
11'-3" A.F.F. A222 STORAGE A202 MITIGATE SOUND TRANSFER BETWEEN OFFICES.
20'-0"
A223A
ACT-01
21 IF POSSIBLE, EXISTING DRYWALL BULIKHEAD AND/OR CEILING AND LIGHTING ARE TO REMAIN;. iF
11'-4" A.F.F. CEILING MUST BE PARTIALLY DEMOLISHED TO ACCOMODATE NEW HVAC CONFIGURATION, PATCH
U 29 25 U
WITH NEW AS NEEDED AND REPAINT BULKHEAD. IF ADJACENT DRYWALL CEILING AT HIGHER
09
29 A2 ELEVATION IS BEING REMOVED TO BE REPLACED BY ACT GRID CIELING, DEISGN INTENT IS FOR
PT-01b
ABOVE 4'-10" A-351
ELECTRICAL NEW ACT CEILING TO BE 1" LOWER THAN REMOVED DRYWALL SUCH THAT MINIMAL TOUCH UP
OFFICE OFFICE BREAKROOM ROOM OFFICE WORK IS REQUIRED AT PERIMETER OF BULKHEAD TO REMIAN. REUSE LIGHTING IF POSSIBLE.
GWB-X1 STORAGE /
A218C A218B A200
10" 2"
18 11'-3" A.F.F. A200A A201 PROJECTOR CONFIRM DESIGN INTENT WITH ARCHITECT PRIOR TO REPLACEMENT.
ACT-01 ACT-01 PT-01 ACT-01 ACT-01 A202A OFFICE
GWB EX 11'-3" A.F.F. 11'-3" A.F.F. 11'-4" A.F.F. 11'-4" A.F.F. A203A
23 NEW SURFACE MOUNTED LINEAR LIGHTING TO MATCH OTHER FIXTURES ON THIS FLOOR. THESE
10'-0" A.F.F. ACT-01 WORK AREA / ARE REPLACING FIXTURES WITH RED HOUSING THAT WERE REMOVED.
29 STORAGE
11'-4" A.F.F.
A203 ACT-01 25 DESIGN INTENT IS FOR NEWLY CONSTRUCTED CEIING AND LIGHTING TO REMAIN. IF MECHANICAL
CIRCULATION 11'-4" A.F.F. WORK PROHIBITS THIS, SALVAGE REMOVED COMPONENTRY AND REINSTALL OR REPLACE WITH
25 25 - 25 ACT-01 NEW TO MATCH EXISTING.
V 11'-3" A.F.F. V 26 REFERENCE ELECTRICAL DRAWINGS FOR NEW LIGHTING IN NEWLY CONSTRUCTED ROOMS.
CIRCULATION
GWB EX GWB EX OFFICE 27 ADDED FIXTURE FOR INCREASED LIGHT LEVEL
2'-1"
32
BULKHEADS IN ADJACENT AREA.
REMOVE HORIZONTAL PORTIONS OF HARDLID CEILINGS ON SOUTH ABOVE STAGE AND ALONG
SECOND LEVEL
W W EAST WALL. VERTICAL PORTION OF THESE BULKHEADS CAN REMAIN FOR EASE OF
RECONSTRUCITON AFTER HVAC WORK IS COMPLETED. DRYWALL WRAPPED TRUSSES AND
REFLECTED CEILING
COFFERED CIELING AT NORTH END ARE TO REMAIN. REPLACE EXISTING WOOD SLAT CEILING WITH PLAN - AREA 1
4/1/2021 12:07:45 PM
A A
G.C. TO COORDINATE PROVISION OF INFORMATION REGARDING EXISTING CEILING HEIGHTS.
CONFIRM ALL CEILING HEIGHTS INDICATED ON PLAN AND IMMEDIATELY REQUEST
CONFIRMATION FROM ARCHITECT IF THERE IS A CONFLICT BETWEEN HEIGHT SHOWN ON PLAN
RHIT MOENCH
AND ACHIEVING HEIGHT 1" LOWER THAN CURRENTLY IN FIELD.
C. UNLESS NOTED OR SHOWN OTHERWISE, EXISTING BULKHEADS ARE TO REMAIN, UNLESS
REMOVAL IS REQUIRED FOR HVAC INSTALLATION. IF REPAINTING IS REQUIRED, MATCH EXISTING
RENOVATION
CONFERENCE FINISHES.
ROOM
F230
OFFICE
F228
OFFICE
F226
OFFICE
F224
OFFICE
F222
OFFICE
F220
OFFICE
F218
OFFICE
F216
OFFICE
F214
OFFICE
F212
OFFICE
F210
D. UNLESS NOTED OTHERWISE, ALL ROOMS SHOWN AS OPEN DECK TO REMAIN ARE TO ALSO
ASSUME THAT EXISTING LIGHTING IS TO REMAIN AND EXISTING CEILING FINISHES ARE TO
5500 Wabash Avenue
REMAIN..
E. UNLESS NOTED OR SHOWN OTHERWISE, ALL ROOMS SHOWN WITH NEW GRID TO RECIEVE NEW
2'X2' ACOUSTICAL CEILING GRID (BASIS OF DESIGN IS ARMSTRONG 1732 WITH TEGULAR REVEAL
Terre Haute, Indiana
EDGE AND CORRESPONDING CHICAGO METALLIC 15/16" EXPOSED TEE GRID). GRID IS INTENDED
TO BE SHOWN IN THE PLANS AND INSTALLED
47803
F. AT EXISTING LOCATION SUCH THAT EXISTING LIGHTING TO BE RAISED ABOVE GRID DURING
CIRCULATION CEILING WORK AND THEN CLEANED, SERVICED AS REQUIRED AND RELOCATED INTO NEW GRID Owner
- STORAGE ONCE CEILING WORK IS COMPLETED. THIS MEANS THAT THE CEILING GRID IS NOT NECESSARILY
F208 CENTERED IN THE ROOM TO ALLOW FOR REUSE OF LIGHTING CONDUIT. IN NEW AREAS WITH
Rose-Hulman Institute of Technology
B ADMIN OFFICE B 5500 Wabash Avenue
GRID THAT DID NOT PREVIOUSLY HAVE GRID CEILING, CENTER WITHIN SPACE AS SHOWN.
F231 G. CENTER PENETRATIONS IN ACOUSTICAL CEILING SYSTEMS WITHIN INDIVIDUAL CEILING PANELS, Terre Haute, Indiana 47803
BREAK AREA SUCH AS SPRINKLER HEADS, DIFFUSERS, LIGHT FIXTURES, ETC., UNLESS OTHERWISE 812-877-1511
F207 INDICATED.
USABILITY H. PAINT NEW GYPSUM BOARD CEILING SURFACES AS SHOWN ON RCP'S.
LAB I. PROVIDE CONTROL JOINTS (C.J.) IN GYPSUM BOARD CEILING CONSTRUCTION AS INDICATED.
OFFICE
F225A WHERE NOT SHOWN, PROVIDE MAXIMUM SPACING BETWEEN JOINTS OF 30'-0”. VERIFY FINAL
F206 CONTROL JOINT LOCATIONS WITH ARCHITECT PRIOR TO STARTING WORK WHETHER OR NOT
WORKROOM /
BREAKROOM INDICATED ON THE DRAWINGS.
F233 J. CEILING ACCESS PANELS INDICATED ARE NOT INTENDED TO LIMIT NUMBER OF PANELS
REQUIRED. PANEL QUANTITY SHALL BE SUFFICIENT TO PROVIDE REQUIRED ACCESS WHETHER
OFFICE
OR NOT INDICATED ON THE DRAWINGS. VERIFY FINAL LOCATIONS WITH ARCHITECT PRIOR TO
F205 STARTING WORK.
USABILITY
LAB CONTROL CSSE LAB CSSE LAB K. NEW EXPOSED DUCTS/ HVAC UNITS AT EXPOSED STAINED WOOD DECK CEILINGS TO BE BRUSH
C ROOM F225 F217 C PAINTED IN APPROPRIATE COATING TO MATCH PT-01, VERIFY COLOR OF PAINT AT ALL OTHER Architect
F225B LOCATIONS OF EXPOSED DUCTWORK AND HVAC UNITS.
OFFICE RATIO
F204 101 South Pennsylvania Street
CEILING LEGEND Indianapolis, Indiana 46204
317-633-4040
STAIRWELL
- CEILING TAG
OFFICE
CUSTODIAL Structural Engineer
F203
- CEILING TYPE Fink Roberts & Petrie, Inc.
XXX-01
10'-10" A.F.F. CEILING HEIGHT 9449 Priority Way W Dr #200
9.8 8.9 7.9 6.9 5.9 5.5 5.1 4.1 3.1 2.1 1.2
(ABOVE FINISH FLOOR) Indianapolis, Indiana 46240
317-872-8400
D ACT-01 D
8'-0" A.F.F. SPOT ELEVATION MARKER
2'-0"
PT-01
PT-01
R.E. Dimond & Associates, Inc.
N10 N9 N8 N7 N6 GWB-X1 N5 N3 02 N2 N1 EXISTING PAINTED GYB BOARD CEILING NEW OR PATCHED PAINTED GYB BOARD 732 N Capitol Avenue
MECHANICAL 7'-6" A.F.F. 18
ROOM
OR BULKHEAD AS SHOWN ON PLAN CEILING OR BULKHEAD AS SHOWN ON Indianapolis, Indiana 46204
CLASSROOM PLAN 317-634-4672
G116 WOMENS R.R.
GWB-X1 E104
30 E202 1958 SF
7'-6" A.F.F. ELEV 1
-
84 SF
ALIGN ALIGN
1'-6" 2'-0"
PT-01
PT-01
AWP-01 GWB-X1 REUSED, BUT MAY NEED TO BE
9'-3" A.F.F. 9'-5" A.F.F. MECHANICAL
RELOCATED DURING INSTALLATION OF
ROOM 02 02
NEW HVAC AND DRYFALL PAINTING.
E201
30 PT-01 EXP
E1
12 12'-0" A.F.F.
A-540
12
F ACT-01 F
ACT-01 C.J 8'-9" A.F.F.
8'-1" A.F.F. CIRCULATION
.
- C.J
1838 SF 21 1'-0" AREA N.I.C.
PT-01 .
18
PT-01
PT-01
E7 01 SKYLIGHT
10'-0 1/8"
01 GWB EX A-540 SEATING 21
30 8'-0" A.F.F. 01 A6
E200 A-322
A5 GWB EX
A-301 SKYLIGHT 21 8'-0" A.F.F.
GWB EX GWB EX C.J CEILING PLAN NOTES
PT-01 8'-0" A.F.F. 8'-0" A.F.F. C.J .01
E6 . F
04
18
A-351 21
A3
02
01 IF POSSIBLE, REUSE EXISTNG VERTICAL AND PORTION OF HORIZONTAL FACE OF EXISITNG
3 G
G A-322 G BULkHEAD TO CREATE PERIMETER OF NEW ACT CEILING AS SHOWN. REPAINT AS REQUIRED TO
MATCH EXISTING BUIDLING STANDARD.
E
2
CIRCULATION 21 21
- GWB EX GWB EX ACT-01 OFFICE
02 RECONSTRUCT PERIMETER BULKHEADS WHERE HVAC WORK REQUIRED REMOVAL TO REPLICATE D
OFFICE ACT-01 7'-9" A.F.F. 7'-9" A.F.F. 7'-11" A.F.F. D208
D222 ACT-01 7'-10" A.F.F. ORIGINAL CONSTRUCTION AND LIGHTING.
7'-10" A.F.F. ACT-01
03 PROVIDE NEW SURFACE MOUNTED LINEAR LIGHTING TO MATCH OTHER LINEAR LIGHTING ON THIS C
ACT-01 7'-10" A.F.F.
PT-01
PT-01
7'-10" A.F.F. FLOOR. PATCH AND PAINT EXPOED CEILING ELEMENTS AS REQUIRED.
OFFICE OFFICE
OFFICE
D220
OFFICE OFFICE OFFICE
D207
04
B 1
D223 D224 D221 D209
05 NO HEADER AT THIS LOCATION . PROVIDE BLOCKING ABOVE CEIILNG TO SUPPORT DOOR FRAME A
ACT-01 INSERTED WITHINT FINISHED OPENING. DRYWALL CEILING IS CONTINUOUS.
7'-10" A.F.F. STORAGE ALIGN ALIGN ACT-01 ACT-01 ACT-01 ACT-01
D223A
7'-10" A.F.F. 7'-11" A.F.F. 7'-10" A.F.F. 7'-10" A.F.F. 08 PROVIDE ALTERNATE BID TO REPLACE EXISTING LIGHTING WITH NEW SURFACE MOUNTED LINEARS
H H TO MATCH OTHER LINEAR LIGHITNG ON THIS FLOOR. INCLUDE POSSIBLE TOUCH UP THAT MAY BE KEY PLAN
9"
PT-01
7'-10" A.F.F.
A-321 ACT-01 ACT-01
11 DESIGN INTENT IS TO EXPOSED STRUCTURE CEILING - PAINT DRYFALL PAINT IF NOT WOOD TIMBER.
OFFICE OFFICE 7'-10" A.F.F. 7'-10" A.F.F. OFFICE . PROVIDE SURFACE MOUNTED LED LINEAR FIXTURES TO MATCH NEW BUILDING STANDARD IN
D226 D227 OFFICE D205 QUANTITIES AND PLACEMENT TO ACHIEVE APPROPRIATE FOOTCANDLE LEVELS RECOMMENDED
ACT-01 D219V ACT-01 ACT-01 FOR INDICATED ROOM FUNCTION PER IES STANDARDS IF EXPOSING THE EXISTING STRUCTURE IS
7'-10" A.F.F. ACT-01 7'-10" A.F.F. 7'-11" A.F.F. NOT POSSIBLE DUE TO UNFORESEEN CIRCUMSTANCES, PROVIDE STANDARD 2'X2' ACT TILE WITH
STORAGE 7'-10" A.F.F. ALIGN ALIGN
D226A NEW RECESSED LIGHTING AS SHOWN.
J 10 SF J
STORAGE / OFFICE
12 EXPOSED STRUCTURE CEILING. RECONFIGURE DUCTS, PIPES AND CONDUIT AS REQUIRED TO
OFFICE
WORKROOM
21
CIRCULATION D218 D204 MINIMIZE IN EXPOSED AREAS WHERE POSSIBLE, DRYFALL PAINT AND PROVIDE PROVIDE NEW
ACT-01 D226C D217 ACT-01 ACT-01
7'-10" A.F.F. 7'-10" A.F.F. 7'-10" A.F.F. LIGHTING AS SHOWN IN ELECTRICAL PLANS. SHEET ISSUE
ACT-01
14 REPAINT DRYWALL AND REPLACE EXISTING DOWNLIGHTS WITH NEW LED DOWNLIGHTS. 1 Construction Documents 04/01/21
PT-01
PT-01
PT-01
D230
145 SF ROOM ACT-01 21 IF POSSIBLE, EXISTING DRYWALL BULIKHEAD AND/OR CEILING AND LIGHTING ARE TO REMAIN;. iF
7'-10" A.F.F.
OFFICE
D212 CEILING MUST BE PARTIALLY DEMOLISHED TO ACCOMODATE NEW HVAC CONFIGURATION, PATCH
OFFICE
ACT-01 D214 ACT-01 WITH NEW AS NEEDED AND REPAINT BULKHEAD. IF ADJACENT DRYWALL CEILING AT HIGHER
7'-10" A.F.F. D215A ACT-01 7'-11" A.F.F.
ACT-01 7'-10" A.F.F. ELEVATION IS BEING REMOVED TO BE REPLACED BY ACT GRID CIELING, DEISGN INTENT IS FOR
7'-10" A.F.F. OFFICE OFFICE NEW ACT CEILING TO BE 1" LOWER THAN REMOVED DRYWALL SUCH THAT MINIMAL TOUCH UP
D232 ACT-01 D201
OFFICE
7'-10" A.F.F.
WORK IS REQUIRED AT PERIMETER OF BULKHEAD TO REMIAN. REUSE LIGHTING IF POSSIBLE.
D231 ACT-01 ACT-01 ACT-01
7'-10" A.F.F. CONFIRM DESIGN INTENT WITH ARCHITECT PRIOR TO REPLACEMENT.
STORAGE 7'-10" A.F.F. 7'-10" A.F.F.
D226D 23 NEW SURFACE MOUNTED LINEAR LIGHTING TO MATCH OTHER FIXTURES ON THIS FLOOR. THESE
L L ARE REPLACING FIXTURES WITH RED HOUSING THAT WERE REMOVED.
OFFICE 25 DESIGN INTENT IS FOR NEWLY CONSTRUCTED CEIING AND LIGHTING TO REMAIN. IF MECHANICAL
ALIGN ALIGN OFFICE
C211
C212 WORK PROHIBITS THIS, SALVAGE REMOVED COMPONENTRY AND REINSTALL OR REPLACE WITH
EXPOSED ACT-01 NEW TO MATCH EXISTING.
MECHANICAL
PT-01
PT-01
08-G1
ADMIN OFFICE
FL116
FL120
W PT-03
MATCH SURROUNDING SURFACES UNLESS OTHERWISE
INDICATED.
47803
W PT-02 CG-01 CG-01 B RB-01 CG-01 CG-01 F. IN STAIRWELLS, PAINT STEEL STAIR AND LANDING PARTS
09-N1
B RB-01 F CPT-03 CG-01 EXPOSED TO VIEW INCLUDING RISERS AND TREADS, Owner
F CPT-01 STRINGERS, UNDERSIDE OF STAIR STRUCTURE,
HANDRAILS, WALL BRACKETS, COMPONENTS VISIBLE FROM
Rose-Hulman Institute of Technology
EXTERIOR, ETC., UNLESS OTHERWISE INDICATED. 5500 Wabash Avenue
FACULTY G. DO NOT APPLY FINISHES BEHIND FIXED EQUIPMENT SUCH Terre Haute, Indiana 47803
FACULTY OFFICE COLLISION AS CABINETRY, CASEWORK, CHALK AND TACKBOARDS, 812-877-1511
FACULTY OFFICE FACULTY OFFICEFACULTY OFFICE
FACULTY OFFICE
FL112 FL108 LOCKERS, ETC.
08-G1 FL114 FL106 FL104 FL102
W PT-02 W PT-03 H. ALIGN FLOOR FINISH TRANSITIONS AT DOOR LOCATIONS
09-N1 W PT-02 W PT-02 W PT-02 W PT-02 WITH CENTERLINE OF DOOR SUCH THAT TRANSITION
CG-01 B RB-01 B RB-01 B RB-01 B RB-01 B RB-01
B RB-01 F CPT-01 F LVT-01 MATERIALS ARE NOT VISIBLE FROM EITHER SIDE WHEN
F CPT-01 F CPT-01 F CPT-01 F CPT-01
DOOR IS IN CLOSED POSITION. TRANSITIONS MUST BE 1/8"
ZINC TERRAZZO STRIP WITH LEVELING LATEX USED AS
REQUIRED TO INSURE SURFACES ARE LEVEL.
I. REFER TO REFLECTED CEILING PLANS AND INTERIOR
PT-03 CG-01 CG-01 ELEVATIONS FOR ADDITIONAL FINISH INFORMATION.
CG-01 J. REFER TO PROJECT MANUAL DIVISION 9 FOR FINISH LEVEL
CPT-03 REQUIREMENTS FOR GYPSUM BOARD SURFACES UNLESS
RB-01 OTHERWISE INDICATED. Architect
CG-01 K. REFERENCE FINISH PLANS FOR CORNER GUARD
EQ
PT-03 CENTER CARPET CORRIDOR LOCATIONS AND PREP CORNER AS NEEDED. RATIO
CG-01 ACROSS CORRIDOR FL120 L. PROVIDE SOLID SURFACE WINDOW SILL SSM-02 AT NEW 101 South Pennsylvania Street
WIDTH W PT-03 OPENINGS. MILLWORKER MUST PROVIDE DETAIL FOR FINAL Indianapolis, Indiana 46204
B RB-01 APPROVAL PRIOR TO FABRICATION. 317-633-4040
EQ
CG-01 F CPT-03 CG-01 M. EXPOSED BRICK TO BE CLEANED AND PAINTED PT-01.
A5 / A-650 N. ALL WALLS WITH PT-04, PT-05, PT-06 INDICATED AS FINISH
ARE TO RECEIVE LEVEL 5 DRYWALL FINISH,
O. REFERENCE ALL DEMOLITION AND ARCHITECTURAL PLANS Structural Engineer
FOR AREAS SHOWN WITH SHAFT WORK. THESE AFFECTED Fink Roberts & Petrie, Inc.
WALLS WILL REQUIRED PAINTING FROM CORNER TO
PT-07 CTB-02 KITCHEN CORNER.NOT ALL LOCATIONS ARE VISIBLE IN FINISH PLANS. 9449 Priority Way W Dr #200
EL125 P. REFERENCE ALL DEMOLITION PLANS FOR REMOVAL OF Indianapolis, Indiana 46240
CPT-03
W FRP-01 PERIMETER DRYWALL BULKHEADS. ALL ADJACENT WALLS 317-872-8400
CT-04
CG-01 B QTB-01 WILL REQUIRE PAINTING FROM CORNER TO CORNER. NOT
CAFE F QT-01 ALL LOCATIONS ARE VISIBLE IN FINISH PLANS.
EL127 HOUSEKEEPING
DW
W PT-07 EQUIPMENT Mechanical / Electrical Engineer
B RB-01 F5 ROOM CPT CON
4'-11" CT-03 F QT-01 A-402 ELEV 1 EL102
R.E. Dimond & Associates, Inc.
FULL TILE STORAGE - W PT-07 732 N Capitol Avenue
EL126 W ETR B RB-01 Indianapolis, Indiana 46204
W FRP-01 B ETR F SC-01
PT-05 F ETR 317-634-4672
B QTB-01
ALIGN F QT-01 CON VINYL
CT-04
C5 / A-650 C6 / A-650
CTB-01
2 FULL TILES
45.
MAIL SORT
00°
LOUNGE EL103
C1 CT-01 W PT-07
A-152.2
EL112 A5 / A-650 CG-01
W PT-07 B RB-01 CPT CPT
B RB-02 ALIGN CG-01 F VCT-01
00°
45. F CT-01
7" CT-04
ALIGN CORRIDOR
A5 / A-650 CG-01 CG-01
--
PT-06 CT-02 W PT-03 CT VINYL
CT-04
CT-04
ALTERNATE A-5 ALTERNATE A-5
B2
A-152.2 Room name
XXXXX
W Wall Fin ROOM NAME AND
45. A5 / A-650 A5 / A-650 B Base Fin ROOM FINISHES
00°
CT-04 EQ EQ F Floor Fin
FULL TILE
150 SF
4'-11"
45.
2'-0"
00°
F
59" FULL TILE
FLOORING DIRECTION
3 G
INSTALL THESE
E
2
FULL TILES FIRST ACCENT WALL FINISH
PT-XX D
DESIGNATION
45.
C
59" FULL TILE
00°
ALIGN EACH
PLANK AT MITRE
EXISTING CARPET B 1
INSTALLED OVER THE
SUMMER, N.I.C. A
3 1/2"
KEY PLAN
3 3/8"
SEAL | DATE 04/01/21
59" FULL TILE
AREA N.I.C.
EXISTING BUILDING
INSTALL THESE QUARRY TILE, N.I.C.
FULL TILES FIRST
00°
45.
C1 ENLARGED FINISH PLAN - TILE TRANSITION 08-G1 PROVIDE SOLID SURFACE WINDOW SILL AT NEW
OPENINGS WITH SSM-02. MILLWORKER MUST
A-152.2
3/8" = 1'-0" PROVIDE DETAIL FOR FINAL APPROVAL.
09-N1 WHERE FLOOR MOUNTED HVAC UNITS EXIST,
EXTEND CARPET UNDER BASE OF UNIT, SUCH
THAT NO EXPOSED SUBFLOOR IS VISIBLE FROM
ANY LOCATION IN THE ROOM. PROVIDE RUBBER
BASE AS NEEDED WHERE CARPET MEETS
EXPOSED BRICK WALL.
CT-05 CTB-03
CT-05
CT-06
PT-03
B2 ENLARGED FINISH PLAN - MEN'S RESTROOM COPYRIGHT NOTICE: THIS ARCHITECTURAL AND ENGINEERING DRAWING IS GIVEN IN CONFIDENCE
AND SHALL BE USED ONLY PURSUANT TO THE AGREEMENT WITH RATIO. NO OTHER USE,
DISSEMINATION OR DUPLICATION MAY BE MADE WITHOUT PRIOR WRITTEN CONSENT OF RATIO. ALL
A-152.2 ALTERNATE A-5 COMMON LAW RIGHTS OF COPYRIGHT AND OTHERWISE ARE HEREBY SPECIFICALLY RESERVED.
1/4" = 1'-0"
PROJECT NO. 19010.000
SHEET TITLE
LOWER LEVEL 1
FINISH PLAN - AREA
2
4/1/2021 11:44:28 AM
SHEET NUMBER
EQ.
INDICATED. 812-877-1511
F. IN STAIRWELLS, PAINT STEEL STAIR AND LANDING PARTS
EXPOSED TO VIEW INCLUDING RISERS AND TREADS,
STRINGERS, UNDERSIDE OF STAIR STRUCTURE,
HANDRAILS, WALL BRACKETS, COMPONENTS VISIBLE FROM
EXTERIOR, ETC., UNLESS OTHERWISE INDICATED.
G. DO NOT APPLY FINISHES BEHIND FIXED EQUIPMENT SUCH
AS CABINETRY, CASEWORK, CHALK AND TACKBOARDS,
CLASSROOM
LOCKERS, ETC.
G203
H. ALIGN FLOOR FINISH TRANSITIONS AT DOOR LOCATIONS
W PT-02 WITH CENTERLINE OF DOOR SUCH THAT TRANSITION
B RB-01
F CPT-04 MATERIALS ARE NOT VISIBLE FROM EITHER SIDE WHEN
DOOR IS IN CLOSED POSITION. TRANSITIONS MUST BE 1/8" Architect
ZINC TERRAZZO STRIP WITH LEVELING LATEX USED AS
EQ. EQ. REQUIRED TO INSURE SURFACES ARE LEVEL. RATIO
I. REFER TO REFLECTED CEILING PLANS AND INTERIOR 101 South Pennsylvania Street
ELEVATIONS FOR ADDITIONAL FINISH INFORMATION. Indianapolis, Indiana 46204
J. REFER TO PROJECT MANUAL DIVISION 9 FOR FINISH LEVEL 317-633-4040
REQUIREMENTS FOR GYPSUM BOARD SURFACES UNLESS
EQ.
OTHERWISE INDICATED.
K. REFERENCE FINISH PLANS FOR CORNER GUARD
LOCATIONS AND PREP CORNER AS NEEDED.
Structural Engineer
L. PROVIDE SOLID SURFACE WINDOW SILL SSM-02 AT NEW Fink Roberts & Petrie, Inc.
OPENINGS. MILLWORKER MUST PROVIDE DETAIL FOR FINAL
PT-03
APPROVAL PRIOR TO FABRICATION.
9449 Priority Way W Dr #200
A1/A-650
PT-XX Indianapolis, Indiana 46240
M. EXPOSED BRICK TO BE CLEANED AND PAINTED PT-01.
CPT-03 N. ALL WALLS WITH PT-04, PT-05, PT-06 INDICATED AS FINISH 317-872-8400
RB-01 ARE TO RECEIVE LEVEL 5 DRYWALL FINISH,
O. REFERENCE ALL DEMOLITION AND ARCHITECTURAL PLANS
PT-03 FOR AREAS SHOWN WITH SHAFT WORK. THESE AFFECTED
Mechanical / Electrical Engineer
WALLS WILL REQUIRED PAINTING FROM CORNER TO
CORNER.NOT ALL LOCATIONS ARE VISIBLE IN FINISH PLANS. R.E. Dimond & Associates, Inc.
P. REFERENCE ALL DEMOLITION PLANS FOR REMOVAL OF 732 N Capitol Avenue
PERIMETER DRYWALL BULKHEADS. ALL ADJACENT WALLS
WILL REQUIRE PAINTING FROM CORNER TO CORNER. NOT Indianapolis, Indiana 46204
STG. ALL LOCATIONS ARE VISIBLE IN FINISH PLANS. 317-634-4672
G210A
W PT-02
B RB-01
F CPT-04 CPT CON
CLASSROOM
G208 CON VINYL
W PT-02 STUDENT AREA
B RB-01 G210 C5 / A-650 C6 / A-650
F CPT-04 W PT-02
B RB-01
F CPT-04
CPT CPT
CT VINYL
A5 / A-650 A1 / A-650
Room name
XXXXX
W Wall Fin ROOM NAME AND
B Base Fin ROOM FINISHES
F Floor Fin
150 SF F
3 G
XX-01 FLOORING MATERIAL
TRANSITION
E
2
D
FLOORING DIRECTION
C
B 1
ACCENT WALL FINISH
PT-XX DESIGNATION A
1 LOWER LEVEL 1 - FINISH - AREA 3
A-152.3
1/8" = 1'-0"
KEY PLAN
EXISTING CARPET
INSTALLED OVER THE
SUMMER, N.I.C. SEAL | DATE 04/01/21
AREA N.I.C.
EXISTING BUILDING
QUARRY TILE, N.I.C. SHEET ISSUE
1 Construction Documents 04/01/21
KEYNOTE LEGEND
LOWER LEVEL 1
FINISH PLAN - AREA
3
4/1/2021 11:44:32 AM
SHEET NUMBER
A-152.3
08-G1 08-G1 08-G1 08-G1 08-G1 08-G1 08-G1 08-G1 08-G1 08-G1 08-G1 08-G1 08-G1 08-G1 08-G1 08-G1 GENERAL FINISH PLAN NOTES
08-G1
09-N1
09-N1 09-N1 09-N1 09-N1 09-N1 09-N1 09-N1 09-N1 09-N1 09-N1 09-N1 09-N1 09-N1 09-N1 09-N1 09-N1
DEPT. HEAD
RHIT MOENCH
A. THESE GENERAL NOTES APPLY TO SERIES A150 PLANS.
FACULTY OFFICE
F137
W PT-02
FACULTY OFFICE FACULTY OFFICE
F135
W PT-02
F133
FACULTY OFFICEFACULTY OFFICE FACULTY OFFICEFACULTY OFFICEFACULTY OFFICE
F131 F129 F127 F125 F123 F121 F119
FACULTY OFFICEFACULTY OFFICE FACULTY OFFICE
FACULTY OFFICE FACULTY OFFICE
F117
W PT-02
F115 F113
FACULTY OFFICEFACULTY OFFICEFACULTY OFFICE
F111 F109 F107
F105A
W PT-02
B RB-01
B. PAINT NEW AND EXISTING HOLLOW METAL DOORS, DOOR
FRAMES, AND LINTELS EXPOSED TO VIEW IN FINISHED
AREAS AND AT EXTERIOR LOCATIONS UNLESS OTHERWISE
RENOVATION
W PT-02 W PT-02 W PT-02 W PT-02 W PT-02 W PT-02 W PT-02 W PT-02 W PT-02 W PT-02 W PT-02 W PT-02 W PT-02
B RB-01
F CPT-01
B RB-01
F CPT-01
B RB-01
F CPT-01
B RB-01
F CPT-01
B RB-01
F CPT-01
B RB-01
F CPT-01
B RB-01
F CPT-01
B RB-01
F CPT-01
B RB-01
F CPT-01
B RB-01
F CPT-01
B RB-01
F CPT-01
B RB-01
F CPT-01
B RB-01
F CPT-01
B RB-01
F CPT-01
B RB-01
F CPT-01
B RB-01
F CPT-01
F CPT-01
INDICATED.
C. PAINT STEEL COLUMNS, BEAMS, STRUCTURE, ETC.,
5500 Wabash Avenue
EXPOSED TO VIEW IN FINISHED AREAS UNLESS OTHERWISE
INDICATED.
D. PAINT EXISTING FIRE EXTINGUISHER CABINETS, METAL
Terre Haute, Indiana
CORRIDOR
F132
ADMIN OFFICE
F105
ACCESS PANELS, LOUVERS, UNIT VENTILATORS, AND
OTHER PAINTABLE SURFACES IN ROOMS TO BE FINISHED 47803
CG-01 W PT-03 UNLESS OTHERWISE INDICATED.
CG-01 CG-01 CG-01 CG-01 CG-01 CG-01 CG-01 W PT-02 08-G1
B RB-01 B RB-01 E. FINISH SOFFITS, BULKHEADS, AND SIMILAR CONDITIONS TO Owner
F CPT-03 F CPT-01 09-N1 MATCH SURROUNDING SURFACES UNLESS OTHERWISE
INDICATED. Rose-Hulman Institute of Technology
F. IN STAIRWELLS, PAINT STEEL STAIR AND LANDING PARTS 5500 Wabash Avenue
FACULTY OFFICE FACULTY OFFICE
EXPOSED TO VIEW INCLUDING RISERS AND TREADS, Terre Haute, Indiana 47803
FACULTY STRINGERS, UNDERSIDE OF STAIR STRUCTURE, 812-877-1511
F132 F130 FACULTY OFFICEFACULTY OFFICE FACULTY OFFICE
FACULTY OFFICEFACULTY OFFICE FACULTY OFFICE
FACULTY OFFICE FACULTY OFFICE FACULTY OFFICE HANDRAILS, WALL BRACKETS, COMPONENTS VISIBLE FROM
W PT-02 W PT-02 FACULTY OFFICE COLLISION
F126 F124 F122 F120 DATA F112 F110 F108 F106 F103 EXTERIOR, ETC., UNLESS OTHERWISE INDICATED.
B RB-01 B RB-01 F128 F116 08-G1
F CPT-01 F CPT-01 W PT-02 W PT-02 W PT-02 W PT-02 F114 W PT-02 W PT-02 W PT-02 W PT-02 G. DO NOT APPLY FINISHES BEHIND FIXED EQUIPMENT SUCH
W PT-03 W PT-02 09-N1
W PT-02 B RB-01 B RB-01 B RB-01 B RB-01 B RB-01 B RB-01 B RB-01 B RB-01 B RB-01 AS CABINETRY, CASEWORK, CHALK AND TACKBOARDS,
B RB-01 W PT-01 F CPT-01 F CPT-01
B RB-01 F CPT-01 F CPT-01 F CPT-01 F CPT-01 B RB-01 F CPT-01 F CPT-01 F CPT-01 LOCKERS, ETC.
F CPT-01 F LVT-01
F SDT-01 H. ALIGN FLOOR FINISH TRANSITIONS AT DOOR LOCATIONS
WITH CENTERLINE OF DOOR SUCH THAT TRANSITION
MATERIALS ARE NOT VISIBLE FROM EITHER SIDE WHEN
CG-01 2'-0" DOOR IS IN CLOSED POSITION. TRANSITIONS MUST BE 1/8"
FACULTY OFFICE
JAN ZINC TERRAZZO STRIP WITH LEVELING LATEX USED AS
F101 08-G1
F100 REQUIRED TO INSURE SURFACES ARE LEVEL.
EQ.
W PT-01 09-N1
CG-01 B RB-01 W PT-01 I. REFER TO REFLECTED CEILING PLANS AND INTERIOR Architect
CG-01 F CPT-01 B RB-01 ELEVATIONS FOR ADDITIONAL FINISH INFORMATION.
CORRIDOR F SC-01 RATIO
J. REFER TO PROJECT MANUAL DIVISION 9 FOR FINISH LEVEL
CENTER CARPET F132
REQUIREMENTS FOR GYPSUM BOARD SURFACES UNLESS 101 South Pennsylvania Street
ACROSS CORRIDOR W PT-03 CG-01 OTHERWISE INDICATED.
B RB-01 Indianapolis, Indiana 46204
WIDTH K. REFERENCE FINISH PLANS FOR CORNER GUARD
F CPT-03 317-633-4040
LOCATIONS AND PREP CORNER AS NEEDED.
L. PROVIDE SOLID SURFACE WINDOW SILL SSM-02 AT NEW
OPENINGS. MILLWORKER MUST PROVIDE DETAIL FOR FINAL
EQ.
APPROVAL PRIOR TO FABRICATION. Structural Engineer
M. EXPOSED BRICK TO BE CLEANED AND PAINTED PT-01. Fink Roberts & Petrie, Inc.
N. ALL WALLS WITH PT-04, PT-05, PT-06 INDICATED AS FINISH
ARE TO RECEIVE LEVEL 5 DRYWALL FINISH, 9449 Priority Way W Dr #200
O. REFERENCE ALL DEMOLITION AND ARCHITECTURAL PLANS Indianapolis, Indiana 46240
FOR AREAS SHOWN WITH SHAFT WORK. THESE AFFECTED 317-872-8400
PT-03 WALLS WILL REQUIRED PAINTING FROM CORNER TO
PT-XX REFINISH RESTROOM CORNER.NOT ALL LOCATIONS ARE VISIBLE IN FINISH PLANS.
WALLS AS REQUIRED P. REFERENCE ALL DEMOLITION PLANS FOR REMOVAL OF
PERIMETER DRYWALL BULKHEADS. ALL ADJACENT WALLS Mechanical / Electrical Engineer
AFTER PATCHING OF TWO
WALLS AND REPLACEMENT WILL REQUIRE PAINTING FROM CORNER TO CORNER. NOT R.E. Dimond & Associates, Inc.
OF CEILING. ALL LOCATIONS ARE VISIBLE IN FINISH PLANS.
WALL FINISHES INDICATED 732 N Capitol Avenue
IN LL1 FINISH PLAN AND Indianapolis, Indiana 46204
ELEVATION PT-XX
317-634-4672
CPT CON
PT-XX
PAINT ALL WALLS AS
REQUIRED TO MATCH
EXISTING COLOR.
REPAINTING IS REQUIRED
AFTER REPLACEMENT OF CON VINYL
ALL BULKHEADS.
C5 / A-650 C6 / A-650
PT-03
PT-03
CPT CPT
ALTERNATE A-5
INCLUDES REMOVAL OF PEDESTALS CT VINYL
ALTERNATE A-5 AND ADDING PLATFORM TO MATCH
LL1 PLATFORM UNDER STAIRS A5 / A-650 A1 / A-650
Room name
XXXXX
W Wall Fin ROOM NAME AND
B Base Fin ROOM FINISHES
EXISTING WALL
F Floor Fin
FINISHES TO REMAIN
150 SF
PT-XX
B 1
A
EXISTING CARPET
INSTALLED OVER THE
SUMMER, N.I.C.
KEY PLAN
AREA N.I.C.
EXISTING BUILDING
QUARRY TILE, N.I.C.
SHEET ISSUE
1 Construction Documents 04/01/21
KEYNOTE LEGEND
PT-XX
PT-XX
PT-XX
PT-03
SHEET NUMBER
1 FIRST LEVEL FINISH - AREA 2
A-153.2
1/8" = 1'-0" A-153.2
GENERAL FINISH PLAN NOTES
RHIT MOENCH
A. THESE GENERAL NOTES APPLY TO SERIES A150 PLANS.
RENOVATION
B. PAINT NEW AND EXISTING HOLLOW METAL DOORS, DOOR
FRAMES, AND LINTELS EXPOSED TO VIEW IN FINISHED
AREAS AND AT EXTERIOR LOCATIONS UNLESS OTHERWISE
5500 Wabash Avenue
INDICATED.
C. PAINT STEEL COLUMNS, BEAMS, STRUCTURE, ETC., Terre Haute, Indiana
EXPOSED TO VIEW IN FINISHED AREAS UNLESS OTHERWISE
INDICATED.
D. PAINT EXISTING FIRE EXTINGUISHER CABINETS, METAL
47803
ACCESS PANELS, LOUVERS, UNIT VENTILATORS, AND
OTHER PAINTABLE SURFACES IN ROOMS TO BE FINISHED Owner
UNLESS OTHERWISE INDICATED. Rose-Hulman Institute of Technology
E. FINISH SOFFITS, BULKHEADS, AND SIMILAR CONDITIONS TO
MATCH SURROUNDING SURFACES UNLESS OTHERWISE 5500 Wabash Avenue
INDICATED. Terre Haute, Indiana 47803
F. IN STAIRWELLS, PAINT STEEL STAIR AND LANDING PARTS 812-877-1511
EXPOSED TO VIEW INCLUDING RISERS AND TREADS,
STRINGERS, UNDERSIDE OF STAIR STRUCTURE,
HANDRAILS, WALL BRACKETS, COMPONENTS VISIBLE FROM
EXTERIOR, ETC., UNLESS OTHERWISE INDICATED.
G. DO NOT APPLY FINISHES BEHIND FIXED EQUIPMENT SUCH
AS CABINETRY, CASEWORK, CHALK AND TACKBOARDS,
LOCKERS, ETC.
H. ALIGN FLOOR FINISH TRANSITIONS AT DOOR LOCATIONS
WITH CENTERLINE OF DOOR SUCH THAT TRANSITION
MATERIALS ARE NOT VISIBLE FROM EITHER SIDE WHEN
DOOR IS IN CLOSED POSITION. TRANSITIONS MUST BE 1/8"
ZINC TERRAZZO STRIP WITH LEVELING LATEX USED AS Architect
REQUIRED TO INSURE SURFACES ARE LEVEL.
I. REFER TO REFLECTED CEILING PLANS AND INTERIOR RATIO
ELEVATIONS FOR ADDITIONAL FINISH INFORMATION. 101 South Pennsylvania Street
J. REFER TO PROJECT MANUAL DIVISION 9 FOR FINISH LEVEL Indianapolis, Indiana 46204
REQUIREMENTS FOR GYPSUM BOARD SURFACES UNLESS 317-633-4040
OTHERWISE INDICATED.
K. REFERENCE FINISH PLANS FOR CORNER GUARD
LOCATIONS AND PREP CORNER AS NEEDED.
L. PROVIDE SOLID SURFACE WINDOW SILL SSM-02 AT NEW
Structural Engineer
OPENINGS. MILLWORKER MUST PROVIDE DETAIL FOR FINAL Fink Roberts & Petrie, Inc.
APPROVAL PRIOR TO FABRICATION.
9449 Priority Way W Dr #200
M. EXPOSED BRICK TO BE CLEANED AND PAINTED PT-01.
N. ALL WALLS WITH PT-04, PT-05, PT-06 INDICATED AS FINISH Indianapolis, Indiana 46240
ARE TO RECEIVE LEVEL 5 DRYWALL FINISH, 317-872-8400
O. REFERENCE ALL DEMOLITION AND ARCHITECTURAL PLANS
FOR AREAS SHOWN WITH SHAFT WORK. THESE AFFECTED
EQ EQ EQ EQ WALLS WILL REQUIRED PAINTING FROM CORNER TO Mechanical / Electrical Engineer
CORNER.NOT ALL LOCATIONS ARE VISIBLE IN FINISH PLANS.
P. REFERENCE ALL DEMOLITION PLANS FOR REMOVAL OF R.E. Dimond & Associates, Inc.
PERIMETER DRYWALL BULKHEADS. ALL ADJACENT WALLS 732 N Capitol Avenue
WILL REQUIRE PAINTING FROM CORNER TO CORNER. NOT
CLASSROOM
STUDENT WORK
ALL LOCATIONS ARE VISIBLE IN FINISH PLANS.
Indianapolis, Indiana 46204
CLASSROOM AREA 317-634-4672
G308
G306 G304
W PT-02
B RB-01 W PT-02 W PT-02
F CPT-04 B RB-01 ROOF ACCESS B RB-01
F CPT-04 F CPT-04 CPT CON
G304B
W PT-02 CLOSET
B RB-01 G304A
F SC-01 W PT-02
CG-01 B RB-01
F CPT-04
CON VINYL
C5 / A-650 C6 / A-650
CPT CPT
PT-XX
CT VINYL
A5 / A-650 A1 / A-650
Room name
XXXXX F
13 SEAT CONF.
W Wall Fin
B Base Fin
ROOM NAME AND
ROOM FINISHES
3 G
G305
W PT-02
STORAGE
F Floor Fin
150 SF
E
2
G305A
B RB-01 W PT-02 D
F CPT-04 XX-01 FLOORING MATERIAL
B RB-01
F CPT-04 TRANSITION
C
FLOORING DIRECTION
B 1
A
EXISTING CARPET
INSTALLED OVER THE
SUMMER, N.I.C.
AREA N.I.C.
KEYNOTE LEGEND
SHEET NUMBER
A-153.3
GENERAL FINISH PLAN NOTES
RHIT MOENCH
PT-XX
A. THESE GENERAL NOTES APPLY TO SERIES A150 PLANS.
B. PAINT NEW AND EXISTING HOLLOW METAL DOORS, DOOR
FRAMES, AND LINTELS EXPOSED TO VIEW IN FINISHED
RENOVATION
PT-03
RB-01 PT-XX
AREAS AND AT EXTERIOR LOCATIONS UNLESS OTHERWISE
INDICATED.
5500 Wabash Avenue
PT-XX
C. PAINT STEEL COLUMNS, BEAMS, STRUCTURE, ETC.,
EXPOSED TO VIEW IN FINISHED AREAS UNLESS OTHERWISE
INDICATED.
Terre Haute, Indiana
PT-XX PT-03
D. PAINT EXISTING FIRE EXTINGUISHER CABINETS, METAL
ACCESS PANELS, LOUVERS, UNIT VENTILATORS, AND 47803
RB-01 OTHER PAINTABLE SURFACES IN ROOMS TO BE FINISHED
PT-XX UNLESS OTHERWISE INDICATED. Owner
E. FINISH SOFFITS, BULKHEADS, AND SIMILAR CONDITIONS TO
MATCH SURROUNDING SURFACES UNLESS OTHERWISE
Rose-Hulman Institute of Technology
INDICATED. 5500 Wabash Avenue
F. IN STAIRWELLS, PAINT STEEL STAIR AND LANDING PARTS Terre Haute, Indiana 47803
EXPOSED TO VIEW INCLUDING RISERS AND TREADS, 812-877-1511
PT-XX PT-XX PT-XX STRINGERS, UNDERSIDE OF STAIR STRUCTURE,
PT-03 HANDRAILS, WALL BRACKETS, COMPONENTS VISIBLE FROM
PT-03 ALTERNATE A-5 PT-03
RB-01 EXTERIOR, ETC., UNLESS OTHERWISE INDICATED.
G. DO NOT APPLY FINISHES BEHIND FIXED EQUIPMENT SUCH
AS CABINETRY, CASEWORK, CHALK AND TACKBOARDS,
LOCKERS, ETC.
PT-03 PT-03
H. ALIGN FLOOR FINISH TRANSITIONS AT DOOR LOCATIONS
WITH CENTERLINE OF DOOR SUCH THAT TRANSITION
MATERIALS ARE NOT VISIBLE FROM EITHER SIDE WHEN
DOOR IS IN CLOSED POSITION. TRANSITIONS MUST BE 1/8"
PT-03 ZINC TERRAZZO STRIP WITH LEVELING LATEX USED AS
PT-03 PT-XX REQUIRED TO INSURE SURFACES ARE LEVEL.
PT-XX Architect
PT-XX I. REFER TO REFLECTED CEILING PLANS AND INTERIOR
ELEVATIONS FOR ADDITIONAL FINISH INFORMATION. RATIO
J. REFER TO PROJECT MANUAL DIVISION 9 FOR FINISH LEVEL 101 South Pennsylvania Street
REQUIREMENTS FOR GYPSUM BOARD SURFACES UNLESS Indianapolis, Indiana 46204
PT-03 OTHERWISE INDICATED. 317-633-4040
RB-01 K. REFERENCE FINISH PLANS FOR CORNER GUARD
LOCATIONS AND PREP CORNER AS NEEDED.
L. PROVIDE SOLID SURFACE WINDOW SILL SSM-02 AT NEW
OPENINGS. MILLWORKER MUST PROVIDE DETAIL FOR FINAL Structural Engineer
APPROVAL PRIOR TO FABRICATION. Fink Roberts & Petrie, Inc.
M. EXPOSED BRICK TO BE CLEANED AND PAINTED PT-01.
N. ALL WALLS WITH PT-04, PT-05, PT-06 INDICATED AS FINISH 9449 Priority Way W Dr #200
ARE TO RECEIVE LEVEL 5 DRYWALL FINISH, Indianapolis, Indiana 46240
O. REFERENCE ALL DEMOLITION AND ARCHITECTURAL PLANS 317-872-8400
FOR AREAS SHOWN WITH SHAFT WORK. THESE AFFECTED
WALLS WILL REQUIRED PAINTING FROM CORNER TO
CORNER.NOT ALL LOCATIONS ARE VISIBLE IN FINISH PLANS.
P. REFERENCE ALL DEMOLITION PLANS FOR REMOVAL OF Mechanical / Electrical Engineer
PERIMETER DRYWALL BULKHEADS. ALL ADJACENT WALLS R.E. Dimond & Associates, Inc.
PT-03 WILL REQUIRE PAINTING FROM CORNER TO CORNER. NOT
RB-01
PT-XX ALL LOCATIONS ARE VISIBLE IN FINISH PLANS. 732 N Capitol Avenue
Indianapolis, Indiana 46204
317-634-4672
CPT CON
PT-03
PT-XX RB-01
PT-XX
CON VINYL
ALTERNATE A-5
C5 / A-650 C6 / A-650
PT-03
RB-01
CPT CPT
CT VINYL
PT-03
RB-01 PT-XX A5 / A-650 A1 / A-650
Room name
PT-03 XXXXX
W Wall Fin ROOM NAME AND
RB-01 ROOM FINISHES
B Base Fin
F Floor Fin
150 SF
THESE WALLS SHOULD PT-XX
NOT REQUIRE PAINT
XX-01 FLOORING MATERIAL
PT-XX TRANSITION F
3 G
FLOORING DIRECTION
E
2
D
PT-03
RB-01 ACCENT WALL FINISH
C
PAINT ALL WALLS AS PT-XX
REQUIRED TO MATCH DESIGNATION
EXISTING COLOR.
REPAINTING REQUIRED
B 1
AFTER BULKHEADS ARE
REBUILT AFTER HVAC WORK.
A
EXISTING CARPET
INSTALLED OVER THE
SUMMER, N.I.C. KEY PLAN
PT-03
RB-01
PT-XX
EXISTING BUILDING
QUARRY TILE, N.I.C.
SHEET ISSUE
CPT-01 PT-03 1 Construction Documents 04/01/21
2'-0"
PT-XX
SECOND LEVEL
FINISH PLAN - AREA
1
4/1/2021 12:07:56 PM
A-154.1
GENERAL FINISH PLAN NOTES
RHIT MOENCH
A. THESE GENERAL NOTES APPLY TO SERIES A150 PLANS.
B. PAINT NEW AND EXISTING HOLLOW METAL DOORS, DOOR
FRAMES, AND LINTELS EXPOSED TO VIEW IN FINISHED
RENOVATION
AREAS AND AT EXTERIOR LOCATIONS UNLESS OTHERWISE
INDICATED. 5500 Wabash Avenue
C. PAINT STEEL COLUMNS, BEAMS, STRUCTURE, ETC.,
EXPOSED TO VIEW IN FINISHED AREAS UNLESS OTHERWISE
INDICATED.
Terre Haute, Indiana
D. PAINT EXISTING FIRE EXTINGUISHER CABINETS, METAL
ACCESS PANELS, LOUVERS, UNIT VENTILATORS, AND 47803
OTHER PAINTABLE SURFACES IN ROOMS TO BE FINISHED
UNLESS OTHERWISE INDICATED. Owner
E. FINISH SOFFITS, BULKHEADS, AND SIMILAR CONDITIONS TO
MATCH SURROUNDING SURFACES UNLESS OTHERWISE Rose-Hulman Institute of Technology
INDICATED. 5500 Wabash Avenue
F. IN STAIRWELLS, PAINT STEEL STAIR AND LANDING PARTS Terre Haute, Indiana 47803
EXPOSED TO VIEW INCLUDING RISERS AND TREADS, 812-877-1511
STRINGERS, UNDERSIDE OF STAIR STRUCTURE,
HANDRAILS, WALL BRACKETS, COMPONENTS VISIBLE FROM
EXTERIOR, ETC., UNLESS OTHERWISE INDICATED.
G. DO NOT APPLY FINISHES BEHIND FIXED EQUIPMENT SUCH
AS CABINETRY, CASEWORK, CHALK AND TACKBOARDS,
LOCKERS, ETC.
H. ALIGN FLOOR FINISH TRANSITIONS AT DOOR LOCATIONS
WITH CENTERLINE OF DOOR SUCH THAT TRANSITION
MATERIALS ARE NOT VISIBLE FROM EITHER SIDE WHEN
DOOR IS IN CLOSED POSITION. TRANSITIONS MUST BE 1/8"
ZINC TERRAZZO STRIP WITH LEVELING LATEX USED AS
REQUIRED TO INSURE SURFACES ARE LEVEL.
Architect
I. REFER TO REFLECTED CEILING PLANS AND INTERIOR
ELEVATIONS FOR ADDITIONAL FINISH INFORMATION. RATIO
J. REFER TO PROJECT MANUAL DIVISION 9 FOR FINISH LEVEL 101 South Pennsylvania Street
REQUIREMENTS FOR GYPSUM BOARD SURFACES UNLESS
REFINISH RESTROOM Indianapolis, Indiana 46204
OTHERWISE INDICATED.
WALLS AS REQUIRED K. REFERENCE FINISH PLANS FOR CORNER GUARD 317-633-4040
AFTER PATCHING OF TWO LOCATIONS AND PREP CORNER AS NEEDED.
WALLS AND REPLACEMENT L. PROVIDE SOLID SURFACE WINDOW SILL SSM-02 AT NEW
OF CEILING. OPENINGS. MILLWORKER MUST PROVIDE DETAIL FOR FINAL Structural Engineer
APPROVAL PRIOR TO FABRICATION. Fink Roberts & Petrie, Inc.
M. EXPOSED BRICK TO BE CLEANED AND PAINTED PT-01.
N. ALL WALLS WITH PT-04, PT-05, PT-06 INDICATED AS FINISH 9449 Priority Way W Dr #200
ARE TO RECEIVE LEVEL 5 DRYWALL FINISH, Indianapolis, Indiana 46240
A1 / A-650 O. REFERENCE ALL DEMOLITION AND ARCHITECTURAL PLANS 317-872-8400
FOR AREAS SHOWN WITH SHAFT WORK. THESE AFFECTED
CT-05 WALLS WILL REQUIRED PAINTING FROM CORNER TO
PT-03
RB-01 CORNER.NOT ALL LOCATIONS ARE VISIBLE IN FINISH PLANS.
PT-XX Mechanical / Electrical Engineer
P. REFERENCE ALL DEMOLITION PLANS FOR REMOVAL OF
PERIMETER DRYWALL BULKHEADS. ALL ADJACENT WALLS R.E. Dimond & Associates, Inc.
PT-03 WILL REQUIRE PAINTING FROM CORNER TO CORNER. NOT
RB-01 ALL LOCATIONS ARE VISIBLE IN FINISH PLANS. 732 N Capitol Avenue
Indianapolis, Indiana 46204
CT-05 317-634-4672
CPT CON
PT-03
RB-01 PAINT ALL WALLS AS
CPT-01 REQUIRED TO MATCH
EXISTING COLOR.
CIRCULATION REPAINTING IS REQUIRED CON VINYL
- PAINT EXISTING RA-01 AFTER REPLACEMENT OF
W PT-03 HANDRAILS ALL BULKHEADS. C5 / A-650 C6 / A-650
CPT-01 B RB-01
F CPT-03
PT-XX
CPT CPT
PT-03
CPT-01
PT-03 QZ-01
RB-01 CT VINYL
ALTERNATE A-5 PT-03
A5 / A-650 A1 / A-650
PT-03 PAINT EXTG
HANDRAILS RA-01 CPT-03
SEATING
E200
W PT-03 PT-03
B RB-01 Room name
F CPT-03 XXXXX
W Wall Fin ROOM NAME AND
PT-03 QZ-01
B Base Fin ROOM FINISHES
F Floor Fin
150 SF
F
PT-XX
PT-XX 3 G
XX-01 FLOORING MATERIAL
TRANSITION
E
2
PT-XX D
PT-XX PT-XX FLOORING DIRECTION
PT-XX C
PT-XX
PT-XX
PT-XX
AREA N.I.C.
PT-XX PT-XX
PT-03
RB-01 PT-XX
EXISTING BUILDING
PT-XX PT-XX QUARRY TILE, N.I.C. SHEET ISSUE
PT-XX 1 Construction Documents 04/01/21
PT-XX
PT-XX
PT-03
RB-01
KEYNOTE LEGEND
PT-XX
PT-XX
PT-XX
PT-XX PT-XX
PT-XX
PT-03
RB-01 PT-XX
PT-XX
PT-XX PT-03
RB-01
PT-XX
PT-XX
PT-XX
SHEET NUMBER
PT-03
RB-01
1
A-154.2
SECOND LEVEL FINISH - AREA 2 A-154.2
1/8" = 1'-0"
RHIT MOENCH
RENOVATION
FACULTY FACULTYFACULTYFACULTYFACULTYFACULTYFACULTY
FACULTY
OFFICE OFFICE OFFICE OFFICE OFFICE OFFICE OFFICE OFFICE
5500 Wabash Avenue
FL115 FL113 FL111 FL109 FL107 FL105 FL103 FL101
FURNITURE SHOWN FOR Terre Haute, Indiana
REFERENCE ONLY. FINAL 47803
LAYOUT AND COORDINATION OF Owner
CLOSET DEPT. HEAD ELECTRICAL/ DATA MUST OCCUR Rose-Hulman Institute of Technology
G220A FL116B
CLASSROOM
G203 MENS R.R.
STUDY AREA
G204
DIRECTLY THROUGH FURNITURE 5500 Wabash Avenue
G206 Terre Haute, Indiana 47803
DEALERSHIP. 812-877-1511
5'-11"
CLASSROOM ADMIN OFFICE
G222 CLASSROOM FL116
G220
FACULTY
WOMENS R.R.
OFFICE
G202
FL114
FACULTY
COLLISION
FL108 Architect
STG.
G210A RATIO
101 South Pennsylvania Street
Indianapolis, Indiana 46204
317-633-4040
CLASSROOM CLASSROOM HOUSEKEEPING
DW
G221 G219 EQUIPMENT
ELEV 1
- ROOM Structural Engineer
CLASSROOM EL102
Fink Roberts & Petrie, Inc.
G208
9449 Priority Way W Dr #200
LOUNGE MAIL SORT
Indianapolis, Indiana 46240
EL112 EL103
STUDENT 317-872-8400
COOK AREA
GREENHOUSE G210
G219A
Mechanical / Electrical Engineer
R.E. Dimond & Associates, Inc.
732 N Capitol Avenue
WOMENS R.R. MENS R.R.
Indianapolis, Indiana 46204
EL105 EL104
317-634-4672
SEMICONDUCTOR
OPTICS LAB
DL108
OFFICE
DL107
?
?
?
NUCLEAR
PHYSICS LAB OFFICE
DL105 DL106
OPTICAL
ENGINEERING
LAB 3 OPTICAL
DL115 METROLOGY
LAB OFFICE
DL104 DL103
OPTICAL
ENGINEERING
LAB 1 SENIOR OFFICE
DARK ROOM DESIGN LAB
DL117 DL102
G112 DL101
CLASSROOM
DL119
OPTICAL ACOUSTICS
ENGINEERING PROJECTS
LAB OFFICE
LAB 2 CL109
CL118 CL110
M.T.F.
MEASUREMENT NON-LINEAR CONFERENCE
LAB OPTICS LAB ROOM H BAR
CL114 CL115 CL116 EL108
ENGINEERING OFFICE
PHYSICS LAB BL103 OFFICE
MATERIALS 1 BL102
PROCESSING BL110
PHYSICS LAB LAB
1 BL112 OFFICE
BL113 BL104 SHEET ISSUE
PHYSICS 1 Construction Documents 04/01/21
STOCK ROOM OFFICE OFFICE
BL108 BL109 OFFICE BL101
BL105
MACHINE
ELECTRICAL SHOP OFFICE OFFICE
ROOM BL107 BL106 BL100
PHYSICS LAB BL115
2
BL114 ELEV 2
CUSTODIAL -
STORAGE
BL116
OFFICE OFFICE OFFICE
AL104 AL103 AL102
ELEVATOR STORAGE
MECHANICAL ART CURATOR AL101A
BL117 AL101
WATER ROOM
AL106
LOWER LEVEL 1
FURNITURE PLAN
A5 LOWER LEVEL 1 FURNITURE PLAN
4/1/2021 11:45:06 AM
A-172
1/16" = 1'-0"
SHEET NUMBER
A-172
RHIT MOENCH
RENOVATION
FACULTYFACULTYFACULTYFACULTY
FACULTYFACULTYFACULTY FACULTYFACULTYFACULTYFACULTY
FACULTYFACULTYFACULTYFACULTY
FACULTY
OFFICE OFFICE OFFICE OFFICE OFFICE OFFICE OFFICE OFFICE OFFICE OFFICE OFFICEOFFICE OFFICE OFFICE OFFICEOFFICE
5500 Wabash Avenue
F137 F135 F133 F131 F129 F127 F125 F123 F121 F119 F117 F115 F113 F111 F109 F107
FURNITURE SHOWN FOR Terre Haute, Indiana
CLASSROOM CLASSROOM
STUDENT
WORK AREA DEPT. HEAD
REFERENCE ONLY. FINAL 47803
G308 G306 G304 F105A LAYOUT AND COORDINATION OF Owner
ELECTRICAL/ DATA MUST OCCUR Rose-Hulman Institute of Technology
DIRECTLY THROUGH FURNITURE 5500 Wabash Avenue
4'-5 1/8"
CLASSROOM Terre Haute, Indiana 47803
G310
ADMIN OFFICE
F105
DEALERSHIP. 812-877-1511
FACULTY
OFFICE
FACULTY 5'-0" F103
OFFICE DATA
JAN
8'-10"
CLOSET F132 F114
G304A F100
8'-10"
ROOF
ACCESS
G304B
FACULTY FACULTY
COLLISION OFFICE Architect
F116 F101 RATIO
101 South Pennsylvania Street
EQUIPMENT SERVER/EQUIP. Indianapolis, Indiana 46204
CLASSROOM CLASSROOM CLASSROOM REPAIR ROOM STORAGE 317-633-4040
G317 G315 G313 E107A E107C CLASSROOM
E104
ELEV 1
TECHNICIAN Structural Engineer
- WOMENS R.R.
STORAGE OFFICE
E109 Fink Roberts & Petrie, Inc.
G305A E107B
9449 Priority Way W Dr #200
WORKSHOP MENS R.R. Indianapolis, Indiana 46240
13 SEAT
CONF. E107 E108 317-872-8400
G305
OFFICE
REFERENCE OFFICE OFFICE
D113
ENERGY (CONFERENCE) D108 D107
CONVERSION ROOM
AND POWER CLASSROOM D110
SYSTEMS D112
LABORATORY OFFICE
OFFICE OFFICE OFFICE
D114 D106
D111-1 D111 D109
OFFICE
D105
OFFICE
ELECTRONIC D104
CALIBRATION
LABORATORY ECE LAB TECH
CIRCUITS LEARNING
LABORATORY D116 D117
CENTER DESIGN LAB OFFICE
D115 D101-A D101 D103
OFFICE
D118
STORAGE OFFICE
D115A D102
INSTRUMENT
ROOM OFFICE
EQUIPMENT C114 C110
WORKSHOP/STORAGE
STORAGE
C112
C115A
DIGITAL
ELECTRONIC
MECHATRONICS OFFICE
MICROCOMPUTER C111 C109
LABORATORY
C115
OFFICE
C108
DYNAMIC
SYSTEMS AND OFFICE MAIL ROOM
OFFICE
CONTROLS C118 C104
C117
LABORATORY
SEAL | DATE 04/01/21
C116
OFFICE ADMIN
SERVER WORKROOM / C103
ROOM BREAKROOM
OFFICE C103A OFFICE
B107B
C101A C105
ELECTRICAL
ELECTRICAL ROOM
ROOM B107
B107A STORAGE
B105A
CLASSROOM
B106 ADVANCED
STUDY AREA CIRCUIT
144 OFFICE LABORATORY SHEET ISSUE
B108B B105 1 Construction Documents 04/01/21
OFFICE
B108C
OFFICE E.I.T.
B108A B103C
TEST OFFICE
BUSINESS SOLDERING OFFICE
AND FINANCE ENGINEERING B103A
LAB LAB B101 OFFICE
CONFERENCE
B104 B102 B100
ROOM
OFFICE
B109
B103B
CUSTODIAL ELEV 2
STORAGE -
GM ROOM B110
B111
WORKROOM / OFFICE
OFFICE A105
OFFICE BREAKROOM
A140 SERVER A102B OFFICE
A102A
OFFICE OFFICE ROOM A103 OFFICE
OFFICE OFFICE ADMIN OFFICE
A136 A138 A100A A106
A124 A126 A102
WORKROOM / STORAGE
OFFICE A104B OFFICE
BREAKROOM
ELEC. A101 A107
A122
APPLICATIONS A118A
READING OFFICE STORAGE OFFICE ELEC. AND SAFE OFFICE
ROOM OFFICE
A128 A120B A118 STORAGE A104A A104
A130 A108
A101A
CIRCULATION ADMIN OFFICE COPYRIGHT NOTICE: THIS ARCHITECTURAL AND ENGINEERING DRAWING IS GIVEN IN CONFIDENCE
STORAGE A120 A113
AND SHALL BE USED ONLY PURSUANT TO THE AGREEMENT WITH RATIO. NO OTHER USE,
DISSEMINATION OR DUPLICATION MAY BE MADE WITHOUT PRIOR WRITTEN CONSENT OF RATIO. ALL
A120A OFFICE COMMON LAW RIGHTS OF COPYRIGHT AND OTHERWISE ARE HEREBY SPECIFICALLY RESERVED.
OFFICE A109
OFFICE OFFICE OFFICE OFFICE OFFICE OFFICE OFFICE OFFICE OFFICE OFFICE OFFICE
A121 PROJECT NO. 19010.000
A123 A125 A127 A129 A117 A116 A115 A114 A112 A111 A110
SHEET TITLE
FIRST LEVEL
FURNITURE PLAN
FIRST LEVEL FURNITURE PLAN
4/1/2021 11:45:21 AM
A5
A-173
1/16" = 1'-0"
SHEET NUMBER
A-173
RHIT MOENCH
RENOVATION
5500 Wabash Avenue
FURNITURE SHOWN FOR Terre Haute, Indiana
CONFERENCE
REFERENCE ONLY. FINAL 47803
ROOM OFFICE OFFICE OFFICE OFFICE OFFICE OFFICE OFFICE OFFICE OFFICE OFFICE LAYOUT AND COORDINATION OF Owner
F230 F228 F226 F224 F222 F220 F218 F216 F214 F212 F210 ELECTRICAL/ DATA MUST OCCUR Rose-Hulman Institute of Technology
DIRECTLY THROUGH FURNITURE 5500 Wabash Avenue
CIRCULATION STORAGE Terre Haute, Indiana 47803
ADMIN OFFICE - F208 DEALERSHIP. 812-877-1511
F231 1224 SF
BREAK AREA
F207 OFFICE
USABILITY
WORKROOM / LAB F206
BREAKROOM F225A OFFICE
F233
USABILITY CSSE LAB CSSE LAB F205
LAB CONTROL F225 F217 OFFICE
ROOM F204
F225B
STAIRWELL
- CUSTODIAL OFFICE
275 SF - F203 Architect
RATIO
101 South Pennsylvania Street
CIRCULATION
Indianapolis, Indiana 46204
MECHANICAL -
545 SF 317-633-4040
ROOM CLASSROOM
G116 E104
ELEV 1 WOMENS R.R.
- E202 Structural Engineer
Fink Roberts & Petrie, Inc.
9449 Priority Way W Dr #200
MECHANICAL Indianapolis, Indiana 46240
ROOM 317-872-8400
E201
CIRCULATION
STORAGE OFFICE
OFFICE
D223A- D208
D222 131 SF
CIRCULATION
OFFICE STORAGE - STUDENT OFFICE
D225 CONFERENCE D206
D226A
138 SF STUDY AREA
D219A
OFFICE 134 SF D210
263 SF OFFICE
OFFICE D227
D226 D205
CIRCULATION FACULTY
OFFICE OFFICE OFFICE
- CONFERENCE
D230 D202
138 SF D215B ROOM CIRCULATION
145 SF
D212 -
OFFICE 287 SF 836 SF
OFFICE
OFFICE D232 D201
D231 STORAGE
D226D
MECHANICAL OFFICE
ROOM MECHANICAL C211
ROOM OFFICE
C215
C214 C212
OFFICE
C210
IT CLOSET
C200B OFFICE
STAFF C209
STUDY AREA RESOURCES
- CIRCULATION
OPEN TO C200
- BELOW OFFICE
5103 SF
STORAGE C208
C200A
CIRCULATION
62 SF
OFFICE
C216 OFFICE
C217
ELEV 2
GM ROOM -
MECHANICAL
B111 ROOM
B207
CIRCULATION
-
80 SF
CUSTODIAL
CIRCULATION MECHANICAL
STORAGE
- ROOM CLASSROOM
OFFICE A223A
ADMIN OFFICE 151 SF MENS R.R. A301
A218A A202
A218 A223
WOMENS R.R. CIRCULATION
- STORAGE /
A222
92 SF PROJECTOR
A202A
ELECTRICAL
OFFICE OFFICE BREAKROOM ROOM OFFICE
A218C A218B A200 A200A A201
OFFICE
WORK AREA /
CIRCULATION A203A
STORAGE
- A203
1304 SF CIRCULATIONOFFICE COPYRIGHT NOTICE: THIS ARCHITECTURAL AND ENGINEERING DRAWING IS GIVEN IN CONFIDENCE
- A203B AND SHALL BE USED ONLY PURSUANT TO THE AGREEMENT WITH RATIO. NO OTHER USE,
58 SF DISSEMINATION OR DUPLICATION MAY BE MADE WITHOUT PRIOR WRITTEN CONSENT OF RATIO. ALL
WORKROOM COMMON LAW RIGHTS OF COPYRIGHT AND OTHERWISE ARE HEREBY SPECIFICALLY RESERVED.
OFFICE A207 OFFICE OFFICE OFFICE
OFFICE OFFICE OFFICE OFFICE OFFICE OFFICE OFFICE OFFICE A209 OFFICE A203D
A217 A216 A215 A214 A213 A212 A211 A210 ADMIN OFFICE A206 A205 A204 OFFICE PROJECT NO. 19010.000
A208 A203C
SHEET TITLE
SECOND LEVEL
FURNITURE PLAN
A5 SECOND LEVEL FURNITURE PLAN
4/1/2021 11:45:35 AM
A-174
1/16" = 1'-0"
SHEET NUMBER
A-174
GLAZING SCHEDULE NOTE: ALL EXISTING CONDITIONS AND OPENING
DIMENSIONS SHOWN FOR REFERENCE ONLY.
FINAL DIMENSIONS TO BE VERIFIED IN THE FIELD.
GL-01 CLEAR INSULATING GLASS, LOW-E COATED - EXTERIOR
APPLICATIONS
GL-02 CERAMIC COATED SPANDREL GLASS - EXTERIOR
APPLICATIONS
EXTERIOR ELEVATION NOTES
RHIT MOENCH
GL-03 INSULATING, CERAMIC COATED VISION GLASS -
EXTERIOR APPLICATIONS
GL-04 CLEAR INSULATING GLASS, LOW-E COATED, LAMINATED
01 NEW CURTAIN WALL FRAMED WINDOW
TO MATCH EXISTING WINDOWS IN KIND,
FLASH INTO EXISITNG CONSTRUCTION
RENOVATION
- EXTERIOR APPLICATIONS, FIRE RATED 03 NEW METAL PANEL WALL
GL-11 CLEAR TEMPERED GLASS - INTERIOR APPLICATIONS,
WINDOWS AND DOORS
CONSTRUCTION WITH RIGID
INSULATION OVER METAL STUDS
5500 Wabash Avenue
GL-12 DECORATIVE GLASS, FILM OVERLAY - INTERIOR
APPLICATIONS
04 NEW MECHANICAL LOUVER IN
EXISTING STOREFRONT OPENING,
Terre Haute, Indiana
COORDINATE WITH MECHANICAL
GL-13 CLEAR, LAMINATED - INTERIOR APPLICATIONS, FIRE
RATED DRAWINGS. 47803
GL-15 CLEAR TEMPERED LAMINATED GLASS - INTERIOR 05 INCREASE EXISTING MASONRY
APPLICATIONS, RAILINGS SEPARATION WALL UP AND AROUND Owner
NEW LIGHT MONITOR CONSTRUCTION.
Rose-Hulman Institute of Technology
5500 Wabash Avenue
Terre Haute, Indiana 47803
812-877-1511
Architect
RATIO
101 South Pennsylvania Street
Indianapolis, Indiana 46204
E D C B A A B C D 317-633-4040
Structural Engineer
T/O NORTH GABLE T/O NORTH GABLE
163'-5 13/16" 163'-5 13/16" Fink Roberts & Petrie, Inc.
9449 Priority Way W Dr #200
Indianapolis, Indiana 46240
317-872-8400
01 01 01 01
01 01
N1 N2 N3 N4 N5 N6 N7 N8 N9 N10
SHEET ISSUE
1 Construction Documents 04/01/21
T/O PARAPET
142'-8"
C7
TYP. A-622 GL-01 TYP. N SECOND LEVEL
133'-6 13/16"
01 01 01 01 01 01 01 01 01
A7
A-622
FIRST LEVEL
C5 120'-11 13/16"
TYP. A-622
04 01 01 01 01 01
A5
A-622
LOWER LEVEL
110'-7 1/16"
COPYRIGHT NOTICE: THIS ARCHITECTURAL AND ENGINEERING DRAWING IS GIVEN IN CONFIDENCE
AND SHALL BE USED ONLY PURSUANT TO THE AGREEMENT WITH RATIO. NO OTHER USE,
DISSEMINATION OR DUPLICATION MAY BE MADE WITHOUT PRIOR WRITTEN CONSENT OF RATIO. ALL
COMMON LAW RIGHTS OF COPYRIGHT AND OTHERWISE ARE HEREBY SPECIFICALLY RESERVED.
A3 NORTH ELEVATION
A-201
1/8" = 1'-0"
SHEET NUMBER
A-201
GLAZING SCHEDULE NOTE: ALL EXISTING CONDITIONS AND OPENING
DIMENSIONS SHOWN FOR REFERENCE ONLY.
FINAL DIMENSIONS TO BE VERIFIED IN THE FIELD.
GL-01 CLEAR INSULATING GLASS, LOW-E COATED - EXTERIOR
APPLICATIONS
GL-02 CERAMIC COATED SPANDREL GLASS - EXTERIOR
APPLICATIONS
EXTERIOR ELEVATION NOTES
RHIT MOENCH
GL-03 INSULATING, CERAMIC COATED VISION GLASS -
EXTERIOR APPLICATIONS
GL-04 CLEAR INSULATING GLASS, LOW-E COATED, LAMINATED
01 NEW CURTAIN WALL FRAMED WINDOW
TO MATCH EXISTING WINDOWS IN KIND,
FLASH INTO EXISITNG CONSTRUCTION
RENOVATION
- EXTERIOR APPLICATIONS, FIRE RATED 03 NEW METAL PANEL WALL
GL-11 CLEAR TEMPERED GLASS - INTERIOR APPLICATIONS,
WINDOWS AND DOORS
CONSTRUCTION WITH RIGID
INSULATION OVER METAL STUDS
5500 Wabash Avenue
GL-12 DECORATIVE GLASS, FILM OVERLAY - INTERIOR
APPLICATIONS
04 NEW MECHANICAL LOUVER IN
EXISTING STOREFRONT OPENING,
Terre Haute, Indiana
COORDINATE WITH MECHANICAL
GL-13 CLEAR, LAMINATED - INTERIOR APPLICATIONS, FIRE
RATED DRAWINGS. 47803
GL-15 CLEAR TEMPERED LAMINATED GLASS - INTERIOR 05 INCREASE EXISTING MASONRY
APPLICATIONS, RAILINGS SEPARATION WALL UP AND AROUND Owner
NEW LIGHT MONITOR CONSTRUCTION.
Rose-Hulman Institute of Technology
5500 Wabash Avenue
Terre Haute, Indiana 47803
812-877-1511
Architect
RATIO
101 South Pennsylvania Street
Indianapolis, Indiana 46204
317-633-4040
Structural Engineer
Fink Roberts & Petrie, Inc.
9449 Priority Way W Dr #200
Indianapolis, Indiana 46240
317-872-8400
E5
A-321
E1
A3 D3 A-321
A-322
A-322
03 03 03 03
D E F G H J K L M N O P Q R S T
A5 A3 A2
A-301 A-321 A-301
05
GL-01 TYP.
SHEET ISSUE
1 Construction Documents 04/01/21
A5
T E5 S R Q P O N M L K J A3 H G A-301 F E D
A-321 D6 A-321
18'-0" A-322 05
GL-01 TYP.
EXTERIOR
A1 CENTRAL MONITOR EAST ELEVATION ELEVATIONS
A-202
1/8" = 1'-0"
4/1/2021 11:33:08 AM
SHEET NUMBER
A-202
KEYNOTE LEGEND
RHIT MOENCH
RENOVATION
5500 Wabash Avenue
Terre Haute, Indiana
47803
Owner
Rose-Hulman Institute of Technology
5500 Wabash Avenue
Terre Haute, Indiana 47803
812-877-1511
Architect
RATIO
101 South Pennsylvania Street
Indianapolis, Indiana 46204
317-633-4040
Structural Engineer
Fink Roberts & Petrie, Inc.
9449 Priority Way W Dr #200
Indianapolis, Indiana 46240
317-872-8400
W V U T S R Q P O N M L K J H G F E D C B A
A5
A3 A-301
A2 A-321
A-301
N SECOND LEVEL
S SECOND LEVEL 133'-6 13/16"
134'-3 13/16"
SECOND LEVEL
130'-6 13/32"
FIRST LEVEL
120'-11 13/16"
LOWER LEVEL
110'-7 1/16"
LOWER LEVEL 2
100'-0"
SHEET ISSUE
1 Construction Documents 04/01/21
9.8 8.9 7.9 6.9 5.9 5.5 5.1 4.1 3.1 2.1 1.2 9.8 8.9 7.9 6.9 5.9 5.5 5.1 4.1 3.1 2.1 1.2
C2 C2
A-301 A-301
D3 A3
A-322 A-322
D6 A6
A-322 A-322
T/O PARAPET T/O PARAPET
142'-8" 142'-8"
A2 MID TRANSVERSE BUILDING SECTION A5 NORTH TRANSVERSE BUILDING SECTION COPYRIGHT NOTICE: THIS ARCHITECTURAL AND ENGINEERING DRAWING IS GIVEN IN CONFIDENCE
AND SHALL BE USED ONLY PURSUANT TO THE AGREEMENT WITH RATIO. NO OTHER USE,
DISSEMINATION OR DUPLICATION MAY BE MADE WITHOUT PRIOR WRITTEN CONSENT OF RATIO. ALL
A-301 A-301 COMMON LAW RIGHTS OF COPYRIGHT AND OTHERWISE ARE HEREBY SPECIFICALLY RESERVED.
1/16" = 1'-0" 1/16" = 1'-0"
BUILDING SECTIONS
4/1/2021 11:33:14 AM
SHEET NUMBER
A-301
KEYNOTE LEGEND
RHIT MOENCH
RENOVATION
5500 Wabash Avenue
Terre Haute, Indiana
47803
Owner
Rose-Hulman Institute of Technology
S SIM 1 1/2" STANDING SEAM METAL E1 5500 Wabash Avenue
C1 ROOF, 5/8" COVER BOARD, 5"
A-350
A-321 Terre Haute, Indiana 47803
RIGID INSULATION, 1 1/2" 812-877-1511
METAL DECK
E5 5/8" GYPSUM CEILING
A-321
C7
A-351
3" / 1
2 " SIM
A3
A-350
STANDING SEAM
E6 METAL GABLE
A-351 E6
A-350 FLASHING
5.9 5.5 5.1
METAL COPING
PREFINISHED STANDING SEAM METAL ROOF PANELS
ACM PANELS ON
PARAPET BEYOND SELF-ADHERING WATERPROOF MEMBRANE
UNDERLAYMENT OVER 5/8" COVER BOARD AND 5"
RIGID INSULATION
NOMINAL 4X6 STRUCTURAL WOOD DECKING
STAINED TO MATCH EXPOSED DECKING ON
FLOORS BELOW
2"
/1
7" 7"
1'-
/1
0"
2"
4'-11 5/16"
SNOW GUARDS
TREATED WOOD
BLOCKING AS REQ.
LEVEL 5 FINISH
LEVEL 5 FINISH
6'-4" 6'-4"
ROOF MONITOR
SECTIONS
4/1/2021 11:33:20 AM
A-321
KEYNOTE LEGEND
RHIT MOENCH
RENOVATION
5500 Wabash Avenue
Terre Haute, Indiana
47803
Owner
Rose-Hulman Institute of Technology
5500 Wabash Avenue
Terre Haute, Indiana 47803
812-877-1511
Architect
RATIO
101 South Pennsylvania Street
Indianapolis, Indiana 46204
317-633-4040
Structural Engineer
Fink Roberts & Petrie, Inc.
9449 Priority Way W Dr #200
Indianapolis, Indiana 46240
317-872-8400
D6
A-322
A3
A-350
A3
A-322 SHEET ISSUE
C1 1 Construction Documents 04/01/21
A-350
A6
A-322
1 1/2" STANDING SEAM METAL
ROOF, 5/8" COVER BOARD, 5"
A4
+/- 7'-0 19/32"
A-350
1'-0"
+/- 10'-1 1/4" +/- 20'-0"
5'-0"
ROOF MONITOR
SECTIONS
A3 NORTH MONITOR SECTION A6 NORTH MONITOR LONGITUDINAL SECTION
4/1/2021 11:33:25 AM
A-322 A-322
1/2" = 1'-0" 1/2" = 1'-0"
SHEET NUMBER
A-322
KEYNOTE LEGEND
8"
FLASHING ZEE CLOSURE, 074113.16.B01
SET IN SEALANT 075323.D01 3” RIGID INSULATION
076200.D06 074113.16.E01 075323.E01 COVER BOARD
REMOVE & REINSTALL EXISTING 076200.C01 HANGING GUTTER
ASPHALT SHINGLES AS REQUIRED 074113.16.D01
TO EXTEND MEMBRANE ROOFING 076200.D01 BASE FLASHING
074113.16.D02
3'-0" UNDER SHINGLE ROOFING. 076200.D02 COUNTERFLASHING
061053.F05 076200.D06 FASCIA, METAL
077253.A00 SNOW GUARDS
075323.D01 075323.A01
079200.C01 BACKER ROD AND SEALANT Architect
075323.E01 075323.E01 084413.A00 GLAZED ALUMINUM CURTAIN WALLS RATIO
054000.A02 075323.D01 092216.A01 1 5/8" METAL STUD FRAMING, NON-STRUCTURAL
101 South Pennsylvania Street
092216.B01 2 1/2" METAL STUD FRAMING, NON-STRUCTURAL Indianapolis, Indiana 46204
061053.F05
051200.A00 092216.C01 3 5/8" METAL STUD FRAMING, NON-STRUCTURAL 317-633-4040
N6 5.9
092900.B04 GYPSUM BOARD, 5/8"
Structural Engineer
061053.F05 Fink Roberts & Petrie, Inc.
061516.A01 9449 Priority Way W Dr #200
Indianapolis, Indiana 46240
317-872-8400
051200.A00
Mechanical / Electrical Engineer
R.E. Dimond & Associates, Inc.
E6 MONITOR RIDGE 732 N Capitol Avenue
A-350 Indianapolis, Indiana 46204
1 1/2" = 1'-0" 317-634-4672
D D
5.9
074113.16.A00 077253.A00
074113.16.B01
5.9
WRAP ROOF
UNDERLAYMENT 3" CAP @ BASE EXTEND ROOF MEMBRANE
ZEE CLOSURE, SET IN
MEMBRANE 8" MIN BEHIND SEALANT JOINT
SEALANT
DOWN VERTICAL LINEAR BAR GRILLE
FACE AND LAP OVER 074113.16.A00 074113.16.A00 084413.A00
MEMBRANE FLASHING 074113.16.B01 074113.16.B01
ZEE CHANNEL SET 079200.C01 LINEAR BAR GRILLE
074113.16.E01 IN SEALANT 074113.16.E01
061053.B01 076200.D01
074113.16.D01 074113.16.D01
076200.D06 RAKE FLASHING 092900.B04
074113.16.D02 074113.16.D02
075323.A01 092216.C01
061053.F05 061053.F05
SET PANEL EDGE 075323.E01
074113.16.E01
IN CONT. BEAD 075323.D01
072100.C7 OF SEALANT SEAL | DATE 04/01/21
LINE PLYWOOD
074113.16.E01 TROUGH WITH
SHEET METAL
054000.A03 061053.B01
WRAP MEMBRANE T/O PARAPET
FLASHING AROUND 074213.23.B01 142'-8"
INSULATION AND
TERMINATE AT MULLION 074213.23.C02
061053.F05 4"X12" VENTS @16"
075323.A01 061053.F05 O.C. BETWEEN
CLEAT & DRIP EDGE 075323.E01 STUDS, VERIFY WITH
061053.F05 054000.A01 MECHANICAL
079200.C01 079200.C01 074113.16.A00
054000.A02 @16" O.C. MIN ALIGN WITH FACE OF
092900.B04 074113.16.B01 075323.D01
084413.A00 EXISTING COLUMN
054000.A02 074113.16.E01 WRAP BELOW
SHEET ISSUE
077253.A00 061600.B05 8 1/2" VIF 1 Construction Documents 04/01/21
074113.16.D01
C1 MONITOR HEAD DETAIL 074113.16.D02
2 SectionDtl- Clerestory SIll
A-350 A-350
1 1/2" = 1'-0" 061053.F05 054000.A02 1 1/2" = 1'-0"
EXTEND METAL
MEMBRANE ROOF SYSTEM
ROOFING
TO EXTEND UP BEHIND
UNDERLAYMENT
ACM WALL PANELS AND
OVER MEMBRANE
TERMINATE AT STANDING 092900.B04
ROOFING SYSTEM
084413.A00 SEAM METAL ROOF. SET
ATTACHMENT GIRTS IN EXISTING STONE 9.8
076200.D06
CONTINUOUS BEAD OF COPING
061053.B01
3" CAP @ SILL SEALANT AND FASTEN
092216.A01 T/O PARAPET
INTO PLYWOOD, SEAL
054000.A02 HEADS OF ALL FASTENERS 142'-8"
EXISTING STEEL TO 075323.A01 REPLACE EXISTING SEALANT
REMAIN, REMOVE ALL 092900.B04 JOINT AND SET NEW
079200.C01 EXISTING FINISH COUNTERFLASHING IN JOINT
061053.F05
MATERIALS, ROOFING
MATERIALS AND 076200.D02
075323.D01
5 1/2"
ASSOCIATED SUPPORT
SYSTEMS DOWN TO ROOF DRAIN
075323.A01
075323.A01 ROOF DECK PRIOR TO
092900.B04 075323.E01 075323.E01
075323.E01 INSTALLING NEW WORK TERMINATION BAR EXISTING MASONRY
054000.A01 CRICKET 075323.D01
075323.D01 092216.C01 PARAPET
T/O PARAPET T/O PARAPET T/O PARAPET
142'-8" 142'-8" 142'-8"
075323.E01 EXISTING STEEL TO INFILL EXISTING
REMAIN, REMOVE ALL 061053.F05 SCUPPER WITH
EXISTING FINISH MASONRY - 3-5/8"
092900.B04 MATERIALS, ROOFING 054000.A01 LIMESTONE ON
075323.A01 MATERIALS AND 075323.A01 SALVAGED BRICK
092216.C01 ASSOCIATED SUPPORT WITH METAL COPYRIGHT NOTICE: THIS ARCHITECTURAL AND ENGINEERING DRAWING IS GIVEN IN CONFIDENCE
SYSTEMS DOWN TO COPING. AND SHALL BE USED ONLY PURSUANT TO THE AGREEMENT WITH RATIO. NO OTHER USE,
075323.A01 DISSEMINATION OR DUPLICATION MAY BE MADE WITHOUT PRIOR WRITTEN CONSENT OF RATIO. ALL
ROOF DECK PRIOR TO COMMON LAW RIGHTS OF COPYRIGHT AND OTHERWISE ARE HEREBY SPECIFICALLY RESERVED.
INSTALLING NEW WORK
PROJECT NO. 19010.000
EXISTING ROOF DECK
ALIGN FINISH FACE SHEET TITLE
TO SOFFIT BELOW EXISTING WOOD DECK
EXTERIOR DETAILS
SHEET NUMBER
A1 SECTION DETAIL - MONITOR SILL A3 SECTION DETAIL - MONITOR BASE A4 SECTION DETAIL - MONITOR SIDES A6 TYP SECTION DETAIL @ EXIST PARAPET
A-350
1 1/2" = 1'-0"
A-350
1 1/2" = 1'-0"
A-350
1 1/2" = 1'-0"
A-350
1 1/2" = 1'-0"
A-350
G
METAL COPING
075323.A01
074213.23.B01
RHIT MOENCH
074213.23.C02
RENOVATION
054000.A02
5.9
061053.F05 5500 Wabash Avenue
075323.D01
074113.16.E01 Terre Haute, Indiana
3 LAYERS TYPE X
47803
2'-6"
BOTH SIDES
074113.16.A00 Owner
092900.B04
074113.16.B01 Rose-Hulman Institute of Technology
4"
092216.C01 5500 Wabash Avenue
074113.16.E01
Terre Haute, Indiana 47803
074113.16.D01 812-877-1511
054000.A03
074113.16.D02
8"
3 LAYERS
084413.A00 BOTH SIDES 061053.F05
076200.C04
G
074213.23.B01
Architect
075323.A01
RATIO
101 South Pennsylvania Street
061053.F05 Indianapolis, Indiana 46204
092900.B04
075323.D01 2" 3 1/2" 3 1/2" 2" CONTINUE 317-633-4040
3 LAYERS
075323.E01 OF GYP 092216.C01
ACROSS TO
Structural Engineer
EXTERIOR
SHEATHING Fink Roberts & Petrie, Inc.
ABOVE 9449 Priority Way W Dr #200
COLUMN
Indianapolis, Indiana 46240
317-872-8400
3 LAYERS 5/8" GYP BD TYPE X
INSET AT COLUMN. EXTEND 2"
ABOVE ROOF DECK Mechanical / Electrical Engineer
R.E. Dimond & Associates, Inc.
732 N Capitol Avenue
TERMINATE RATED
PARTITION AT BACK SIDE OF Indianapolis, Indiana 46204
EXTERIOR SHEATHING 317-634-4672
074113.16.A00
061053.B01
074113.16.E01
072100.C7
074113.16.E01
WRAP MEMBRANE FLASHING
AROUND INSULATION AND
TERMINATE AT MULLION
1'-4"
SAFETY GATE TO ALLOW FOR
FUTURE RE-ROOFING
3-5/8" METAL
STUDS MEMBRANE
ROOFING
SYSTEM
ACCESS
PANEL
TO FLOOR
4/1/2021 11:33:40 AM
SHEET NUMBER
A2 MECH ROOM LADDER A3 ATTIC MECH WALL SECTION A5 ROOF HATCH DETAIL A7 CRAPO ROOF HATCH
A-351
1/2" = 1'-0"
A-351
1 1/2" = 1'-0"
A-351
1 1/2" = 1'-0"
A-351
1/2" = 1'-0" A-351
KEYNOTE LEGEND
1/32"
1'-0"
Toilet Room Accessories (Internal)
5500 Wabash Avenue
1'-0" Type Mark Description Manufacturer Model Assembly Code
1'-6"
1'-6"
MICROWAVE BROOM
HOLDER
1'-0"
1'-0" Owner
Rose-Hulman Institute of Technology
5500 Wabash Avenue
11'-3 3/16"
2'-0"
6"
2'-0" Terre Haute, Indiana 47803
812-877-1511
1'-6" CLEAR
16'-1 27/32"
D7 A-502 D6
D1
16'-3 5/8"
E2 A-502 G6
1'-5 1/4" Architect
A5 A5 A5
00-A1 00-A1 A5 E1 RATIO
A-532 A-532 A-532
00-A1 00-A1
11'-1 5/8"
A-532
C C C C 1'-6" 101 South Pennsylvania Street
PAPER SHREDDER
PAPER SHREDDER BY OWNER
Indianapolis, Indiana 46204
BY OWNER 317-633-4040
2'-0"
3'-3 5/16"
1'-6"
1'-0" 9449 Priority Way W Dr #200
Indianapolis, Indiana 46240
317-872-8400
8'-0 1/8"
E1 ENLARGED PLAN - FACULTY COLLISION LL1 E4 ENLARGED PLAN - FACULTY COLLISION LEVEL 1 E7 ENLARGED PLAN - FIRST LEVEL CONF. ROOM STORAGE
A-401 A-401 A-401
3/8" = 1'-0" 3/8" = 1'-0" 1/4" = 1'-0"
N1
12C
3'-0"
1'-3"
B4
A-502
6"
N1
6"
1'-6"
1'-6" CLEAR
E3 A-501 E1
SHEET ISSUE
11'-10 1/2"
E2
1 Construction Documents 04/01/21
6'-10 1/2"
1'-6"
1'-6"
7'-6"
B1 FACULTY COLLISION - LOWER LEVEL 1 B4 FACULTY COLLISION - FIRST LEVEL B7 ENPLARGED PLAN - LOWER LEVEL 1 STORAGE
A-401 A-401 A-401
1/4" = 1'-0"
ENLARGED PLANS
4/1/2021 11:34:00 AM
SHEET NUMBER
A-401
N9 N8 N7 N6
KEYNOTE LEGEND
8.9 7.9 6.9 5.9
RHIT MOENCH
101419.A00
105113.A00
DIMENSIONAL LETTER SIGNAGE
METAL LOCKER
123623.13.D01 COUNTER TOP FLIP-UP COUNTERBALANCE
RENOVATION
D D
SYSTEM
5500 Wabash Avenue
S3C.C
1'-6" 9'-10" 1'-6"
S3C.C
Terre Haute, Indiana
2'-3"
S3C
REACH-IN FRIG. REACH-IN FRIG.
A7 2'-0"
123623.13.D01 CT-02
KITCHEN
CG-01 Toilet Room Accessories (Internal) 47803
2'-3"
A-530 C5 A-402 B1 A1 START OF QUARRY TILE CG-01 EL125
S3C S3C PT-05 Type Mark Description Manufacturer Model Assembly Code
A2 KITCHEN Owner
1'-0"
EL125 CG-01 W FRP-01
A-602 S3A.C
N9 N8 N7 N6
1'-0"
C4
B QTB-01 Rose-Hulman Institute of Technology
B3 A-402 A5 F QT-01 12C MOP AND BOBRICK B-223x24 C1090.40
1'-0" 4'-1 3/16" BROOM 5500 Wabash Avenue
CG-01 HOLDER Terre Haute, Indiana 47803
3-COMPARTMENT B5 105113.A00 812-877-1511
DISHWASHER SINK S3A.C
C5 CAFE
EL127
DW
DW
FREEZER FRIG. W PT-07
A-403 C1 B RB-01
1'-0" 1'-6" F QT-01
ICE
CT-02
S3A.C CG-01
A-402 A4
7'-11"
EL126
12C STORAGE W FRP-01
W FRP-01
MOP SINK EL126 B QTB-01
B QTB-01 RATIO
F QT-01
2'-6"
10 SF
F QT-01 101 South Pennsylvania Street
Indianapolis, Indiana 46204
1'-6"
1'-0" 1'-8"
1'-0"
317-633-4040
2'-0"
2'-8"
E S3A.C E CG-01
2'-0"
S3C.D.A CT-02 CT-02
9 31/32"
1'-2"
S3C PT-05
3"
2'-10 1/2" 1'-1 3/4" 1'-1 3/4" PT-05 Structural Engineer
1 1/2"
ALIGN PT-05
2"
B7 PT-06 RB-02
C4 A-532
RB-03 Fink Roberts & Petrie, Inc.
B5
A-532
A-530 9449 Priority Way W Dr #200
ALIGN TILE TRANSITION WITH VERTICAL Indianapolis, Indiana 46240
FACE OF RECESSED TOEKICK SHOWN 317-872-8400
WITH DASHED LINE 3" FROM VERTICAL
FACE OF CASEWORK
10'-10"
CENTER TILE
BETWEEN
WING WALLS, TYP
8'-0" 4'-6"
PT-05 PT-05
1 1/2"
PL-04 F1
1'-10 1/4"
8"
8"
MERCHANDISER
1'-10 1/4"
4'-0"
3'-6"
ALIGN
2'-10"
2'-10"
2'-10"
2'-10"
PL-02
2'-6"
2'-6"
PL-02 PL-02 PL-02
RB-03
5'-5" 9'-10 7/16" 2'-8" 2'-7 1/2"1'-1 1/4" RB-02 2'-0" 3'-3" 3'-3" 1'-3" PL-02 5'-1" 1'-10" 3'-6" 1'-6" 3'-0"
A1 F1
A-531 A-531 SEAL | DATE 04/01/21
5 1/4" F5 D5 PROVIDE A1 D1 PROVIDE CAMLOCKS 5 1/4" 1 1/2"
A-531 A-531 A-531 A-531
CAMLOCKS ON ON ALL DRAWERS
ALL DRAWERS AND CABINETS
AND CABINETS
SHEET ISSUE
1 Construction Documents 04/01/21
A4 A3
PT-05 A-540 101419.A00 FULL HEIGHT FRP FULL HEIGHT FRP FULL HEIGHT FRP
A-531
PT-06 BEYOND
2'-0 3/4"
PT-05
TILE STARTS AT PL-01
COUNTERTOP
1'-0"
CT-02
3'-4 1/4"
1'-0" EQ EQ 1'-0"
E1
8'-6"
8'-6"
8'-3"
A-530
PL-03
QZ-01 D6
SSM-01 A-531
4'-8"
6"
2'-10"
A8 A8
2'-6"
A-530
CAFE
4'-8"
A8 A8
2'-10"
2'-10"
4'-0"
4/1/2021 11:34:15 AM
TABLES BY OTHERS A8
A-650
A1 INTERIOR ELEVATION A3 INTERIOR ELEVATION A4 INTERIOR ELEVATION A5 INTERIOR ELEVATION SHEET NUMBER
A-402
A-402
A-402 A-402 1/4" = 1'-0" A-402
1/4" = 1'-0" 1/4" = 1'-0" 1/4" = 1'-0"
RHIT MOENCH
RENOVATION
5500 Wabash Avenue
Terre Haute, Indiana
47803
Owner
Rose-Hulman Institute of Technology
5500 Wabash Avenue
Terre Haute, Indiana 47803
812-877-1511
Architect
RATIO
101 South Pennsylvania Street
Indianapolis, Indiana 46204
317-633-4040
Structural Engineer
Fink Roberts & Petrie, Inc.
9449 Priority Way W Dr #200
Indianapolis, Indiana 46240
317-872-8400
E1 AXON-CAFE
A-403
WALLCOVERING CONTINUES BEHIND COLUMN 34'-10 1/2" ALTERNATE A-4. SEAMING DIAGRAM IF ALTERNATE APPROVED 38'-1 7/8"
WALLCOVERING STOPPING
POINT BEHIND COLUMN
8'-0 1/2"
1'-1 1/2"
8'-3"
WC-01
10'-10"
WC-01 WC-01
101419.A00 D1
A-540
10"
1'-10 1/2"
2'-1 1/2"
EXISTING DRYWALL REVEALS
PT-07
PT-07 PT-07 PT-05 PT-07 PT-05 PT-07
10'-4 3/4"
10'-4 3/4"
D3 8"
F6 PL-04 PT-05
A-531
1'-3 3/4"
8'-3 1/4"
A-531
123623.13.D01 QZ-01 QZ-01
7'-2"
PL-04
1'-0"
PL-02 PL-02
2'-6"
PL-03 PL-03
PL-02
C5 INTERIOR ELEVATION
C1 INTERIOR ELEVATION A-403
1/4" = 1'-0"
A-403 SHEET ISSUE
1/4" = 1'-0"
1 Construction Documents 04/01/21
CLEAR HEAD HEIGHT BELOW STAIRS
SELF REVEAL
6'-9 3/4"
QZ-01
SEATING PLATFORM
A6
A-530 SEATING PLATFORM A6 QZ-01
A-530 COPYRIGHT NOTICE: THIS ARCHITECTURAL AND ENGINEERING DRAWING IS GIVEN IN CONFIDENCE
AND SHALL BE USED ONLY PURSUANT TO THE AGREEMENT WITH RATIO. NO OTHER USE,
1'-6"
DISSEMINATION OR DUPLICATION MAY BE MADE WITHOUT PRIOR WRITTEN CONSENT OF RATIO. ALL
1'-6"
WD-01 WD-01
COMMON LAW RIGHTS OF COPYRIGHT AND OTHERWISE ARE HEREBY SPECIFICALLY RESERVED.
2"
2"
6'-0"
1/2" 4'-0" 1/2" 4'-0" 1/2" 4'-0"
PROJECT NO. 19010.000
SHEET TITLE
WIDTH TO MATCH WIDTH
BETWEEN INTERIOR
FACES OF STRINGERS
14'-6" +/- CAFE
A1 INTERIOR ELEVATION A3 INTERIOR ELEVATION
A-403 A-403
4/1/2021 11:35:08 AM
SHEET NUMBER
A-403
KEYNOTE LEGEND
RHIT MOENCH
051200.A00 STRUCTURAL STEEL FRAMING
092900.B03
092900.B04
GYPSUM BOARD, 1/2"
GYPSUM BOARD, 5/8"
RENOVATION
097553.A01 VEGETATIVE WALL SYSTEM
5500 Wabash Avenue
Terre Haute, Indiana
47803
Owner
Rose-Hulman Institute of Technology
5500 Wabash Avenue
Terre Haute, Indiana 47803
812-877-1511
Architect
EXISTING DRYWALL REVEALS
RATIO
101 South Pennsylvania Street
SEATING PLATFORM BELOW B4
Indianapolis, Indiana 46204
2" TRIM
A-404 317-633-4040
WD-01
2" TRIM 29'-6" 2" TRIM
Structural Engineer
A-404
Fink Roberts & Petrie, Inc.
6'-3"
ALIGN
9449 Priority Way W Dr #200
E4 A1 1'-0 13/32"
A-403 Indianapolis, Indiana 46240
317-872-8400
8 1/4" PLANTING DPETH
A5
B6
1'-3" CABINET DEPTH
A-301
A-404
16'-11"
097553.A01 317-634-4672
2" 2"
GREENERY
1'-3"
29'-10" WD-01 WD-01
G G
1'-3 1/2"
WD-01
9.8 8.9 7.9 BASE CABINET
097553.A01
VERSA DRIPLINE
4 3/4"
PLANTS BY GSKY
051200.A00
092900.B04
092900.B03
VERSA BACKING
SHEET ISSUE
REMOVABLE VERSA 4" WD-01
BOTTOM EDGE TRIM 1 Construction Documents 04/01/21
4 3/4" TYP
1/4" REVEAL
1'-3 1/2"
7 1/4"
VERSA 7" MULTIP-
PURPOSE EDGE TRIM
BASE CABINET BY GSKY OR MILLWORKER.
VERSA 2" RETURN
3/4"
EDGE TRIM
VERSA TRAY WITH
HONEYWELL WATER DEFENSE SELECTED PLANTS BY
1/2"
GSKY
BOTTOM TRIM BELOW
MANDATORY GAP 3/4" 2"
10 1/2" ADJUSTABLE FEET, PART OF CABINET. MANDATORY GAP 3/4"
3/4" 3/4"
LIVING WALL
4/1/2021 11:35:54 AM
SHEET NUMBER
A-404
KEYNOTE LEGEND
RHIT MOENCH
7.9 6.9 5.9
D6
A-421 RENOVATION
D2
A-421 T/O PARAPET
142'-8"
5500 Wabash Avenue
7.9 6.9 5.9 5.5 5.1 Terre Haute, Indiana
10"
D6
F7
A-540
A-421
47803
WALL MOUNTED HANDRAIL Owner
6'-8" MIN.
Rose-Hulman Institute of Technology
F6
A-423 5500 Wabash Avenue
Terre Haute, Indiana 47803
812-877-1511
S6A.A
N SECOND LEVEL 2'-4 3/8" 3'-0" A1 A-502 A5
133'-6 13/16"
1" / 12"
+/- 8"
4'-6 1/2"
SECOND LEVEL D5
130'-6 13/32" A-421
13'-5 3/4"
D2
A-421
G116
1'-8"
(2X) LAYERS 3/4" PLYWOOD ON 1 1/2" METAL DECK
Architect
COLD FORMED METAL FRAMING AS REQUIRED TO SUPPORT RAMP E E RATIO
F2 NORTH RAMP - N SECTION 101 South Pennsylvania Street
A-421 S2C Indianapolis, Indiana 46204
3'-9 1/4"
1/4" = 1'-0" 1'-0" 1'-0"
F2 317-633-4040
A-421 5'-0" 28'-6 1/8"
1'-0"
Structural Engineer
2 3/4"
D2
Fink Roberts & Petrie, Inc.
A-421 A1 9449 Priority Way W Dr #200
5.9 6.9 7.9 A-423 D6 Indianapolis, Indiana 46240
S3A A-423
below 317-872-8400
2 3/4"
8'-4 1/4"
GLASS GUARDRAIL C6
A1
A-423 WRAP HANDRAIL WRAP HANDRAIL INFILL WITH LIKE WALL
11"
EXPOSED EXISTING TRUSS AROUND AROUND CONSTRUCTION, Mechanical / Electrical Engineer
C5 A-422
BEYOND, PREPPED AND S3A GUARDRAIL GUARDRAIL
5'-0" 2 3/4" 13'-6" ALIGN TO EXISTING R.E. Dimond & Associates, Inc.
2 3/4"
D5 PERFORMANCE PAINT TO CLEAR C3
A-621 MATCH PT-01 Indianapolis, Indiana 46204
317-634-4672
D5
METAL HANDRAIL 5'-0" 8'-0" A-621
3'-10 3/4"
W01 ATTACHED TO E201
STOREFRONT
SYSTEM STOREFRONT E2
W02 MULLIONS A-421 +/- 11 1/2" 15'-7 3/8" +/- 1'-0 1/4" 15'-7 3/8"
+/- 8"
1" / 12" F F
D3 A-423
SECOND LEVEL W01 W02
130'-6 13/32" 1'-0" 1'-0"
NEW PIPE
RAILING, FINISH
F6 (2X) LAYERS 3/4" PLYWOOD TO MATCH ADJ.
E2 NORTH RAMP - S SECTION A-422
ON 1 1/2" METAL DECK E5 NORTH RAMP PLAN RAILING
A-421 A-421
1/4" = 1'-0" COLD FORMED METAL FRAMING AS 1/4" = 1'-0"
REQUIRED TO SUPPORT RAMP
F2 E D5
A-421 A-421
5.9
E2 F2
F A-421 A-421 E
E6
EQ
RAILING
EXISTING TRUSS,
3'-6"
DOOR AS
PREPPED AND C6
SELF SUPPORTING SCHEDULED
PAINTED
EQ
INFILL OPENINGS FROM A-423
METAL PLATFORM
STOREFRONT REMOVED WINDOWS AND ALTERNATING N SECOND LEVEL N SECOND LEVEL
133'-6 13/16" 133'-6 13/16"
U
GLASS GUARDRAIL S8 B2
S7 S6
SYSTEM A-421
A2 A3
A-421 A-423 METAL HANDRAIL S3C
T SHEET ISSUE
1 Construction Documents 04/01/21
+/- 1'-7 3/8"
5'-0"
5'-0" 26'-1 1/2" +/- 3'-1 5/8" VIF CUT BACK
S SECOND LEVEL A2
134'-3 13/16" GUARDRAIL AND
E1 1" / 12" A-421
A5 E3 STRINGER AT NEW
5'-0"
SECOND LEVEL
130'-6 13/32"
A3
19'-4 3/4"
A-423
A3
B2 A-423
S3C
A-421
S6 S7 S8 SIM. O.H.
GLASS GUARDRAIL
U
EXISTING STAIR METAL HANDRAIL, ATTACHED TO A5 NEW RAMP
AND RAILING TO STUD WALL AND GLASS GUARDRAIL A-423 BETWEEN
REMAIN AS REQUIRED ALONG RAMP EXISTING BEAMS
BEYOND
A2
A-421
SOUTH RAMP SECTION - E/W
1/4" = 1'-0"
A5
A-421
SOUTH RAMP PLAN
1/4" = 1'-0"
A-421
GLAZING SCHEDULE KEYNOTE LEGEND
GL-01 CLEAR INSULATING GLASS, LOW-E COATED - EXTERIOR
APPLICATIONS 02-A1 EXISTING WALL CONSTRUCTION
GL-02 CERAMIC COATED SPANDREL GLASS - EXTERIOR
APPLICATIONS
02-A3
02-B1
EXISTING FLOOR CONSTRUCTION
EXISTING STRUCTURAL FRAMING
RHIT MOENCH
GL-03 INSULATING, CERAMIC COATED VISION GLASS -
EXTERIOR APPLICATIONS
GL-04 CLEAR INSULATING GLASS, LOW-E COATED, LAMINATED
09-A1
09-A3
WALL BASE, REFER TO FINISH PLAN FOR TYPE
FLOOR FINISH, REFER TO FINISH PLAN FOR
TYPE
RENOVATION
- EXTERIOR APPLICATIONS, FIRE RATED
GL-11 CLEAR TEMPERED GLASS - INTERIOR APPLICATIONS,
WINDOWS AND DOORS
033000.A02
051200.A00
CAST-IN-PLACE CONCRETE SLAB
STRUCTURAL STEEL FRAMING 5500 Wabash Avenue
GL-12 DECORATIVE GLASS, FILM OVERLAY - INTERIOR
APPLICATIONS
051200.B01
051200.C01
STRUCTURAL STEEL FRAMING, COLUMN
STRUCTURAL STEEL FRAMING, BEAM Terre Haute, Indiana
053100.A01 STEEL DECKING
GL-13 CLEAR, LAMINATED - INTERIOR APPLICATIONS, FIRE
RATED 055113.A02 METAL PAN STAIR WITH CONCRETE FILLED
TREADS, PAINTED
47803
GL-15 CLEAR TEMPERED LAMINATED GLASS - INTERIOR
APPLICATIONS, RAILINGS 055213.A00 PIPE AND TUBE RAILING Owner
057313.C01 SHOE MOUNTED GLASS RAIL
Rose-Hulman Institute of Technology
061053.B01 WOOD BLOCKING
5500 Wabash Avenue
061053.F03 MISCELLANEOUS ROUGH CARPENTRY,
PLYWOOD, 1/2" Terre Haute, Indiana 47803
061053.F05 MISCELLANEOUS ROUGH CARPENTRY,
812-877-1511
PLYWOOD, 3/4"
079200.A01 SEALANT
092216.B02 2 1/2" METAL STUD FRAMING, NON-STRUCTURAL,
WITH SOUND ATTENUATION
092216.C01 3 5/8" METAL STUD FRAMING, NON-STRUCTURAL
092216.C02 3 5/8" METAL STUD FRAMING, NON-STRUCTURAL,
WITH SOUND ATTENUATION
092216.F02 7/8" METAL FURRING
092900.B04 GYPSUM BOARD, 5/8"
3/4"
MAINTAIN SMOOTH
3/4"
053100.A01 101 South Pennsylvania Street
TRANSITION FROM
061053.F05 Indianapolis, Indiana 46204
PLYWOOD TO EXISTING
FLOOR TO RECEIVE 1" / 12" MIN. 317-633-4040
FLOOR FINISH
SECOND LEVEL
130'-6 13/32"
1 1/2"
Structural Engineer
S8
Fink Roberts & Petrie, Inc.
+/- 5 1/16" 9449 Priority Way W Dr #200
V.I.F. 02-A3
Indianapolis, Indiana 46240
02-A1 317-872-8400
092216.C01 092216.C02 02-A3
051200.C01 092216.C02
051200.C01
+/- 1 7/16"
092216.C01 09-A1 033000.A02
092216.C01 061053.F05
051200.A00 079200.A01 1'-6"
061053.F05 053100.A01 02-B1
1" MIN.
SEE STRUCTURAL 09-A3
053100.A01 1" / 12" MIN.
FOR BEARING
DETAIL 061053.F05 051200.A00
SEE STRUCTURAL
BEYOND TO SUPPORT BEYOND TO 053100.A01 FOR FRAMING
WOOD CEILING SUPPORT WOOD
DETAILS
CEILING 02-A3
061053.F03 V.I.F.
061053.F03
02-A1 WOOD CEILING WOOD
REPAIR FINISH AWP-02 CEILING
AS REQUIRED AWP-02 E6 CRAPO RAMP DETAIL
A-422
1 1/2" = 1'-0"
E1 RAMP BEARING WALL DETAIL E3 RAMP WALL DETAIL E5 RAMP BEAM DETAIL
A-422 A-422 A-422
1 1/2" = 1'-0" 1 1/2" = 1'-0" 1 1/2" = 1'-0"
N10
N10
FIRST LEVEL
120'-11 13/16" C
S7FA
4" 1'-0" 1'-0"
092216.F02 1'-0 1/4"
10'-1" V.I.F.
092216.B02 EXISTING ACT
EQ EQ +/- 11'-4 1/2"
CEILING
092900.B04
+/- 16'-6 1/8" V.I.F. EXISTING STRUCTURE, REMOVED
051200.B01 F6
+/- 7'-0"
TO HEIGHT OF EXISTING DOOR D5
055213.A00
4 1/4"
+/- 11"
ON METAL FINISH AFTER
FURRING 1" / 12" LOWER LEVEL REMOVAL OF
3'-4"
1'-0" 1'-0"
BEYOND WING WALL S7FA S3C
110'-7 1/16"
S7FA
092900.B04
ALIGN THIS SIDE +/- 6'-2 1/4" VIF
092216.C02 WITH EXISTING
CONCRETE RAMP SEAL | DATE 04/01/21
092216.F02 FINISH FACE BEYOND 057313.C01
02-A1
02-A3 E6
A-422
3'-6"
+/- 9 1/8"
A1 A-423
A-423
3'-6"
3'-6"
055213.A00 055213.A00
3'-6"
057313.C01 055213.A00
057313.C01
092900.B04 057313.C01 055113.A02
092216.C02
092216.F02
092216.C02
092216.F02
051200.B01
S6
ALIGN WITH
EXISTING FINISH 10"
FACE BEYOND
A5 057313.C01 COMMON LAW RIGHTS OF COPYRIGHT AND OTHERWISE ARE HEREBY SPECIFICALLY RESERVED.
BEYOND +/- 19'-4 13/16" V.I.F. 057313.C01 A-423 057313.C01 A-423 O.H.
+/- 29'-7 3/16" V.I.F. +/- 11'-8 1/4" V.I.F.
PROJECT NO. 19010.000
4 1/4"
EQ EQ EQ EQ EQ SHEET TITLE
EQ EQ EQ EQ EQ EQ EQ EQ EQ EQ
STAIR AND RAMP
3'-6"
3'-6"
3'-6"
092900.B04
1'-2 7/8"
092216.B02
PLANS, SECTIONS,
092216.F02 055213.A00
ALIGN WITH
02-A3
BEYOND 02-A3 02-A3 EXISTING
AND DETAILS
4/1/2021 11:36:15 AM
GUARDRAIL BEYOND
EXISTING FINISH TO REMAIN, PAINTED
FACE BEYOND
COLUMN WRAP DETAIL SOUTH RAMP - SOUTH RAMP - SOUTH RAMP -
SHEET NUMBER
A1 A138 A3 W RAILING ELEVATION A5 N RAILING ELEVATION A7 E RAILING ELEVATION
A-422
1 1/2" = 1'-0"
A-422
1/4" = 1'-0"
A-422
1/4" = 1'-0"
A-422
1/4" = 1'-0"
A-422
KEYNOTE LEGEND
Architect
RATIO
LOW PROFILE METAL
CAP RAIL, FINISH TO 101 South Pennsylvania Street
MATCH GLAZING SHOE Indianapolis, Indiana 46204
317-633-4040
055213.A00
Structural Engineer
GLASS
SUPPORTED
Fink Roberts & Petrie, Inc.
METAL RAILING 9449 Priority Way W Dr #200
BRACKET Indianapolis, Indiana 46240
317-872-8400
5.1
3 3/4" MAX PIPE
+/- 2 3/4" 5" 2" LOW PROFILE METAL
SPACING
CAP RAIL, FINISH TO
MATCH GLAZING SHOE
2 3/4"
PRE-FINISHED METAL
1 1/2" SHOE CLADDING
1 1/2" 2"
084113.C02
4 1/4"
057313.C01 LOW PROFILE
ALUMINUM BASE SHOE
055213.A01
09-K2
STEEL CHANNEL
EXISTING STRINGER
RAILING TO
REMAIN
3'-6"
3'-6"
COPE S.S. SILL
AND PLYWOOD
D6 STAIR GUARD RAILING DETAIL
A-423
AROUND PIPES 1 1/2" = 1'-0"
MATCH EXISTING
2 3/4"
PRE-FINISHED METAL
SHOE CLADDING
LOW PROFILE
4 1/4"
ALUMINUM BASE SHOE GLAZING BEYOND
RAILING SHOE
SECOND LEVEL 02-A3 SECOND LEVEL
130'-6 13/32" 130'-6 13/32" (2)X 3/4" PLYWOOD ON
1 1/2" METAL DECK
051200.A00
DELEGATED COLD
FORMED METAL STUD
FRAMING
D3 RAILING INFILL DETAIL D5 BRIDGE INFILL RAILING DETAIL SEAL | DATE 04/01/21
A-423 A-423
1 1/2" = 1'-0" 1 1/2" = 1'-0" CONCRETE FILL
GLAZING BEYOND
3'-6"
GLASS
SUPPORTED
3'-0"
METAL RAILING
3'-6"
3'-6"
RAILING SHOE
BRACKET
09-A3 SUPPORTED
SHOE CLADDING
2 3/4" METAL RAILING
LOW PROFILE 061053.F03 PRE-FINISHED METAL BRACKET 2 3/4"
4 1/4"
4 1/4"
ALUMINUM BASE
LOW PROFILE 02-A3
3/8"
SHOE
3/8"
092900.F04 054000.A01
079200.C01 CONCRETE FILL
092900.F04 COPYRIGHT NOTICE: THIS ARCHITECTURAL AND ENGINEERING DRAWING IS GIVEN IN CONFIDENCE
092900.B04 AND SHALL BE USED ONLY PURSUANT TO THE AGREEMENT WITH RATIO. NO OTHER USE,
092900.B04 02-A3 092900.F04 FORMED STEEL SHEET DISSEMINATION OR DUPLICATION MAY BE MADE WITHOUT PRIOR WRITTEN CONSENT OF RATIO. ALL
EXISTING WOOD TREAD AND RISER COMMON LAW RIGHTS OF COPYRIGHT AND OTHERWISE ARE HEREBY SPECIFICALLY RESERVED.
051200.A00 ADHERED TIGHT 3" WOOD DECKING 1" TYPICAL
TO EXISTING 092900.B04 BEAM BEYOND
SEE STRUCTURAL PROJECT NO. 19010.000
WOOD BEAM 02-B1
092216.B01 051200.C01 SHEET TITLE
TREAD WIDTH 3"x3"x 1/4" STEEL CLIP
BEYOND
SECOND LEVEL 092216.C02 6" (REFER TO PLAN) ANGLE. ANCHORED TO
CONCRETE AND WELDED
STAIR AND RAMP
130'-6 13/32" TO INSIDE FACE OF BOTH
STRINGERS DETAILS
4/1/2021 11:36:20 AM
A1 NORTH RAMP RAILING DETAIL A3 SOUTH RAMP RAILING DETAIL A5 SOUTH RAMP RAILING DETAIL A6 STAIR RISER/TREAD DETAIL AT FLOOR
A-423 A-423 A-423 A-423
1 1/2" = 1'-0" 1 1/2" = 1'-0" 1 1/2" = 1'-0" 1 1/2" = 1'-0"
SHEET NUMBER
A-423
KEYNOTE LEGEND
4'-0"
Owner
Rose-Hulman Institute of Technology
5'-0"
101100.A00 101100.A00
5500 Wabash Avenue
3'-6"
3'-0"
Terre Haute, Indiana 47803
812-877-1511
Architect
RATIO
101 South Pennsylvania Street
Indianapolis, Indiana 46204
317-633-4040
Structural Engineer
8'-0" 8'-0" 8'-0"
Fink Roberts & Petrie, Inc.
F3 EXPOSED CONCRETE BEAM 9449 Priority Way W Dr #200
A6 A-530 COLUMN Indianapolis, Indiana 46240
A-531 317-872-8400
A3 F6 F3
PL-02 A3 A-531 A3 A-530
A-531 PL-02 A-530
PL-02 A-531
1'-11"
1'-8"
PL-01 PL-01 Mechanical / Electrical Engineer
1'-6" EQ EQ EQ EQ
1'-6" EQ EQ EQ EQ
4'-0"
9" CLEAR
1'-6" EQ EQ EQ EQ
VD-01 VD-01 VD-01 R.E. Dimond & Associates, Inc.
PL-04
2'-0"
732 N Capitol Avenue
1'-9"
SSM-01 SSM-01
6'-6 1/4"
6'-6 1/4"
Indianapolis, Indiana 46204
6'-6 1/4"
317-634-4672
101100.A00
2'-10"
2'-10"
3'-6"
PL-01 PL-01
E1 INTERIOR ELEVATION E2 INTERIOR ELEVATION E3 INTERIOR ELEVATION E5 INTERIOR ELEVATION E7 INTERIOR ELEVATION
A-501 A-501 A-501 A-501
1/4" = 1'-0" 1/4" = 1'-0" A-501 1/4" = 1'-0" 1/4" = 1'-0"
1/4" = 1'-0"
VD-01
PL-04
E6 C6
1'-9"
COUNTER CONTINUES
1'-8"
SSM-01 D6
72" AFF
A-530 A-530
A-531
SSM-01 IN FRONT OF COLUMN
48" AFF
1'-0"
2'-10"
3'-0"
PL-01
D6
A-531 SHEET ISSUE
CORRIDOR BEYOND
SSM-01 CORRIDOR BEYOND 1 Construction Documents 04/01/21
6" 6"
MANUFACTURER
4'-0"
STAINLESS STEEL FINISH COPYRIGHT NOTICE: THIS ARCHITECTURAL AND ENGINEERING DRAWING IS GIVEN IN CONFIDENCE
VD-01 AND SHALL BE USED ONLY PURSUANT TO THE AGREEMENT WITH RATIO. NO OTHER USE,
DISSEMINATION OR DUPLICATION MAY BE MADE WITHOUT PRIOR WRITTEN CONSENT OF RATIO. ALL
72" AFF
COMMON LAW RIGHTS OF COPYRIGHT AND OTHERWISE ARE HEREBY SPECIFICALLY RESERVED.
3'-0"
1 3/16" SHEET TITLE
INTERIOR
RECOMMENDED HEIGHT PER
MANUFACTURER ELEVATIONS
4/1/2021 11:36:33 AM
A-501
KEYNOTE LEGEND
REFER TO AV FOR
MONITOR SIZE
RHIT MOENCH
101100.A00 VISUAL DISPLAY UNIT
8'-9" ALIGN 2'-2 1/8" 8'-0" 101100.A00 8'-0" 8'-0" 2'-2 1/8" A3
A-531
RENOVATION
PL-02 TYP
101100.A00 5500 Wabash Avenue
1'-6" EQ EQ EQ EQ
Terre Haute, Indiana
4'-0"
E6 VD-01 VD-01 VD-01
A-530
QZ-01
47803
4"
6'-6"
5'-3"
2'-10"
PL-04 Owner
3'-3"
Rose-Hulman Institute of Technology
3'-6" 3'-6" 3'-6"
5500 Wabash Avenue
Terre Haute, Indiana 47803
812-877-1511
Architect
RATIO
101 South Pennsylvania Street
Indianapolis, Indiana 46204
317-633-4040
DOOR SWING
5" 8'-0" EQ EQ 8'-0" 5 1/2" 8'-0" 8'-0" REFER TO AV FOR Structural Engineer
A3 MONITOR SIZE PROVIDE BLOCKING AND WALL
A3 PL-02 TYP
1'-6" CLEAR
MOUNTED PRAGUE SINGLE Fink Roberts & Petrie, Inc.
A-531 PL-02 TYP A-531
EQ EQ
ROBE HOOK 353655 IN BRUSHED 9449 Priority Way W Dr #200
EQ EQ STAINLESS STEEL FINISH Indianapolis, Indiana 46240
1'-6" EQ EQ EQ EQ
1'-6" EQ EQ EQ EQ
EQ
EQ
317-872-8400
4'-0"
4'-0"
4'-0"
VD-01 VD-01 VD-01 VD-01 1'-6" VD-01
6'-6 1/4"
EQ
EQ
6'-6"
72" AFF
R.E. Dimond & Associates, Inc.
5'-0"
5'-0"
101100.A00 101100.A00 8'-0" 732 N Capitol Avenue
3'-0"
3'-0"
3'-0"
REFER TO AV FOR Indianapolis, Indiana 46204
MONITOR SIZE 317-634-4672
1'-11"
1'-8"
1'-0"
PL-01 PL-01 9" CLEAR, TYP
4'-0"
1'-11"
4'-0"
4'-0"
PL-01
VD-01
2'-0"
1'-9"
SSM-01 PL-04 PL-04
E6 C6
1'-9"
SSM-01
1'-0"
1'-6" CLEAR
A-530 A-530
8'-0"
2'-10"
2'-10"
3'-3"
3'-0"
PL-01 PL-01
3'-0"
2'-10"
PL-01
D1 INTERIOR ELEVATION D3 INTERIOR ELEVATION D5 INTERIOR ELEVATION D6 INTERIOR ELEVATION D7 INTERIOR ELEVATION
A-502 A-502 A-502 A-502 A-502
1/4" = 1'-0" 1/4" = 1'-0" 1/4" = 1'-0" 1/4" = 1'-0" 1/4" = 1'-0"
EQ EQ
4'-0"
72" AFF
QZ-01 A1 A1 QZ-01
5'-0"
A-530 A-530
4'-0"
4'-0"
WD-01 WD-01
3'-0"
3'-0"
1'-8 1/4"
1'-8 1/4"
WD-01 WD-01
FLOOR MOUNTED HVAC UNIT MOP SINK S.S. TRIM V.I.F. REPAIR DRYWALL WHERE 1'-11" S.S. TRIM V.I.F. V.I.F.
TILE WAS REMOVED
REPAIR DRYWALL WHERE
TILE WAS REMOVED SHEET ISSUE
1 Construction Documents 04/01/21
B1 INTERIOR ELEVATION B3 INTERIOR ELEVATION B4 INTERIOR ELEVATION B5 INTERIOR ELEVATION B7 INTERIOR ELEVATION
A-502 A-502 A-502 A-502 A-502
1/4" = 1'-0" 1/4" = 1'-0" 1/4" = 1'-0" 1/4" = 1'-0" 1/4" = 1'-0"
A5
A-301
A5
A-301
F2 D5
A-421 A-421
F7
LEVEL 5 FINISH E7 A-540 LEVEL 5 FINISH
A-540
LEVEL 5 FINISH COPYRIGHT NOTICE: THIS ARCHITECTURAL AND ENGINEERING DRAWING IS GIVEN IN CONFIDENCE
AND SHALL BE USED ONLY PURSUANT TO THE AGREEMENT WITH RATIO. NO OTHER USE,
DISSEMINATION OR DUPLICATION MAY BE MADE WITHOUT PRIOR WRITTEN CONSENT OF RATIO. ALL
COMMON LAW RIGHTS OF COPYRIGHT AND OTHERWISE ARE HEREBY SPECIFICALLY RESERVED.
INTERIOR
ELEVATIONS
4/1/2021 11:36:48 AM
SHEET NUMBER
VARIES
5500 Wabash Avenue
CEILING, REF. REFLECTED WOOD BLOCKING, PAINT 1'-0" 6"
CEILING PLAN FOR HEIGHT TO MATCH SOFFIT
MELAMINE INTERIOR
PER ELEVATION
1/2" BACK PANEL ON CLEATS
PER ELEVATION
1/2" BACK PANEL ON CLEATS 1/2" BACK PANEL ON CLEATS PL-01
PER ELEVATION FINISH EXPOSED WOOD BLOCKING AND
FRAMING TO MATCH CABINET DOOR ABOVE 47803
PL-04
CABINET INTERIOR, PLASTIC Owner
LAMINATE ON ALL EXPOSED REF. ENLARGED PLAN
MELAMINE INTERIOR Rose-Hulman Institute of Technology
SURFACES CABINET ABOVE
GENERAL CASEWORK NOTES
PER ELEVATION
5500 Wabash Avenue
EQ
ALL AXPOSED WOOD
Terre Haute, Indiana 47803
812-877-1511
2 1/2"
2 1/2"
ADJUSTABLE SHELVES, ADJUSTABLE SHELVES MICROWAVE BLOCKING TO MATCH
EQ EQ EQ EQ EQ EQ EQ
LINE OF FRAME BEYOND CABINET ABOVE A. PROVIDE FINISHED END PANELS AT ALL EXPOSED CABINET
PLASTIC LAMINATE
ENDS.
EQ
1/4" BACK PANEL B. PROVIDE FILLER PANELS BETWEEN CORNER CABINETS AND
CUTOUT FOR OUTLET, TYP. BETWEEN CABINETS AND WALLS, UNLESS NOTED
REFER TO ELECTRICAL SHELVES - RECESSED IN
OTHERWISE
SIDES. REFER TO
24"
LIGHTING, REFER TO RCP AND LIGHTING, REFER TO RCP AND C. PROVIDE SEALANT BETWEEN BACKSPLASH AND COUNTER
ELECTRICAL DRAWINGS ELECTRICAL DRAWINGS ELEVATION FOR COUNT.
PL-04 AT PERIMETER WALLS.
BASE CABINET AND D. ▐►PROVIDE EASED EDGES AT ALL SOLID SURFACE AND
1'-0"
BASE CABINET AND
BASE PANEL, PLASTIC BASE PANEL, PLASTIC 1'-0" CLEAR COUNTER WHERE QUARTZ SURFACES.◄▌
COUNTER WHERE
LAMINATE VENEER LAMINATE VENEER INDICATED ON ELEVATIONS E. PROVIDE COUNTERTOP SUPPORT BRACKETS AS REQUIRED
INDICATED ON ELEVATIONS
UNLESS NOTED OTHERWISE ON ELEVATIONS. BRACKETS
TO BE SPACED 48" ON CENTER, MINIMUM. Architect
BASE CABINET AND BASE CABINET AND
F. COORDINATE FINAL ELECTRICAL AND DATA OUTLET RATIO
COUNTER WHERE COUNTER WHERE
LOCATIONS IN CASEWORK/MILLWORK WITH ▐►OWNER,
INDICATED ON ELEVATIONS INDICATED ON ELEVATIONS 101 South Pennsylvania Street
ARCHITECT ◄▌PRIOR TO INSTALLATION.
Indianapolis, Indiana 46204
317-633-4040
F1 UPPER CABINET F3 TYP. KITCHEN UPPER CABINET F5 MICROWAVE CABINET F6 CABINET WITH MAIL SLOTS Structural Engineer
A-530 A-530 A-530 A-530
1" = 1'-0" 1" = 1'-0" 1" = 1'-0" 1" = 1'-0"
Fink Roberts & Petrie, Inc.
9449 Priority Way W Dr #200
Indianapolis, Indiana 46240
317-872-8400
PER ELEVATION
PER ELEVATION
PER ELEVATION
Indianapolis, Indiana 46204
PER ELEVATION
EQ
DRAWER
EQ
FACE OF APRON PANEL TO MELAMINE ON STD'S & BRACKETS
DRAWER
EQ
ALIGN WITH FACE OF (RECESSED IN SIDES)
ADJACENT CABINET FRAME. PULL, REFERENCE PLANS, TYPICAL PULL, REFERENCE PLANS, TYPICAL
1/2" BACK PANEL ON CLEATS
PER ELEVATION
PER ELEVATION
PER ELEVATION
PER ELEVATION
EQ
DRAWER
3/4" PANEL, PLASTIC LAMINATE
EQ
VENEER. SHAPE TOP OF MELAMINE INTERIOR
DRAWER
PANEL WITH 1/8" TOLERANCE
27" min.
EQ
AROUND SINK DRAWER
EQ
1/2" BACK PANEL ON CLEATS 1/2" BACK PANEL ON CLEATS
1/2" BACK PANEL ON CLEATS
EQ
GLIDEWALL CLEAT WITH DRAWER DRAWER
EQ
ROLLER CATCH
9" min.
6" min.
BASE BASE BASE BASE
11" min. SCRIBE TO FLOOR, TYP. SCRIBE TO FLOOR, TYP. SCRIBE TO FLOOR, TYP. SCRIBE TO FLOOR, TYP.
E1 TYP. KITCHEN SINK BASE ADA E3 DRAWER BASE CABINET E4 DRAWER BASE CABINET E6 BASE CABINET
A-530 A-530 A-530 A-530
1" = 1'-0" 1" = 1'-0" 1" = 1'-0" 1" = 1'-0"
PER ELEVATION
PER ELEVATION
SCRIBE TO WALL W/ SILICONE
BEAD AT LOC. OF NO SPLASH
ROUTE 1/4" FROM S.S. TOP
ROUTE 1/4" FROM S.S. TOP
SCRIBE TO WALL W/ SILICONE COUNTERTOP PER
REFER TO ENLARGED PLAN SCRIBE TO WALL W/ SILICONE
25" BEAD AT LOC. OF NO SPLASH REFER TO ENLARGED PLAN ELEVATIONS
BEAD AT LOC. OF NO SPLASH CABINET DOOR
EQ EQ
SOLID SURFACE FINISH ALL EXPOSED WOOD
COUNTERTOP FINISH PER
COUNTERTOP AND BACK BLOCKING AND FRAMING TO MATCH
ELEVATION.
SPLASH SAME FINISH AS CABINET DOOR
BELOW
EASED SUPPORT EDGE PULL
TRASH GROMMET EDGE (BOTH SIDES)
INLCUDE MAGNETIC PUSH LATCH
PULL, REFERENCE PLANS
SEAL | DATE 04/01/21
PER ELEVATION
PER ELEVATION
SLIDING TRASH
PER ELEVATION
C1 BASE CABINET W/ TRASH C3 BASE CABINET - TRASH DRAWER C4 PLAN DETAIL - TRASH GROMMET C6 BASE CABINET
A-530 A-530 A-530 A-530
1" = 1'-0" 1" = 1'-0" 1 1/2" = 1'-0" 1" = 1'-0"
3'-5 1/2"
BELOW.
1/2"
MERCHANDISER
3/4"
ALIGN QZ-01
1 1/2"
EXISTING METAL SHALE EDGE
EXISTING MILLWORK ALIGN
FRAME DECK. REFER TO WALL TILE PER COPYRIGHT NOTICE: THIS ARCHITECTURAL AND ENGINEERING DRAWING IS GIVEN IN CONFIDENCE
STRUCTURAL ELEVATION AND SHALL BE USED ONLY PURSUANT TO THE AGREEMENT WITH RATIO. NO OTHER USE,
PL-02 DISSEMINATION OR DUPLICATION MAY BE MADE WITHOUT PRIOR WRITTEN CONSENT OF RATIO. ALL
6"
3/4"
COMMON LAW RIGHTS OF COPYRIGHT AND OTHERWISE ARE HEREBY SPECIFICALLY RESERVED.
WD-01 PL-04
PL-03
1'-3"
SHEET NUMBER
A1 INTERIOR DETAIL A3 INTERIOR DETAIL A4 INTERIOR DETAIL A6 INTERIOR DETAIL A7 PLAN DETAIL - COUNTER EDGE
A-530
1" = 1'-0"
A-530
6" = 1'-0"
A-530
1 1/2" = 1'-0"
A-530
1" = 1'-0"
A-530
3" = 1'-0"
A-530
KEYNOTE LEGEND
1 1/2"
1'-2" 1'-6"
1 1/2"
47803
PL-04 PL-03
PLAM PRIVACY PANEL
REFER TO ELEV.
Owner
10"
PL-03
REFER TO ELEV.
CONCEALED SUIPPORT BRACKET Rose-Hulman Institute of Technology
PL-03 TILE BACKSPLASH 1'-0" 1'-10" GENERAL CASEWORK NOTES
MORTAR BED 5500 Wabash Avenue
Terre Haute, Indiana 47803
POWER/DATA FOR 812-877-1511
5" SOUP
2"
PL-03 REFER TO ENLARGED PLAN CONVENIENCE, COORD. W/ A. PROVIDE FINISHED END PANELS AT ALL EXPOSED CABINET
10"
LINE OF SURROUNDING QZ-01 KETTLES ELECTRICAL ENDS.
COUNTER FINISH PER QZ-01
PANEL BEYOND 2" 1'-0" 2" MITRED CORNER, B. PROVIDE FILLER PANELS BETWEEN CORNER CABINETS AND
ELEVATION 2'-8"
PL-04 EDGE PULL FINISH PER ELEVATION EASED EDGE. EDGE PULL BETWEEN CABINETS AND WALLS, UNLESS NOTED
PL-04 COUNTER
PLAM EDGE PULL
DOOR PANEL, PLAM OTHERWISE
ROUTE 2" DIAMETER 3/4" DOOR PANEL, FINISH
1" FINISH PER ELEVATION C. PROVIDE SEALANT BETWEEN BACKSPLASH AND COUNTER
FINISHED PLAM 5" 2'-0" 1" IN RIBBING TO FEED PER ELEVATION
CUTOUT FOR OUTLET. AT PERIMETER WALLS.
PANEL 3/4" MDF ADJ. SHELF CLAD IN CABLES
D. ▐►PROVIDE EASED EDGES AT ALL SOLID SURFACE AND
EQ
MELAMINE ON STD'S & BRACKETS REFER TO ELEC. FINISHED PLAM PANEL DRAWER 3/4" MDF ADJ. SHELF CLAD IN
EQ
QUARTZ SURFACES.◄▌
EQ
(RECESSED IN SIDES) MELAMINE ON STD'S & BRACKETS
E. PROVIDE COUNTERTOP SUPPORT BRACKETS AS REQUIRED
1'-6"
MICROWAVE 2'-0" (RECESSED IN SIDES)
UNLESS NOTED OTHERWISE ON ELEVATIONS. BRACKETS
REFER TO ELEV.