Vacon NXP Grid Converter Arfiff03v164 Manual Dpd01599c Uk v001

The document provides information about error codes F91, F92, and F93 that could occur on a Vacon grid converter. F91 indicates a short circuit was detected by current or voltage measurements exceeding limits. F92 means the measured grid voltage is outside the set protection limits, possibly due to a short circuit, low supply or reference voltage, or unconnected voltage monitoring equipment. F93 refers to the measured grid frequency being outside the set limits, potentially because frequency monitoring is not connected or the actual frequency is out of range.

Uploaded by

Mohamed Elsayed
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
138 views1 page

Vacon NXP Grid Converter Arfiff03v164 Manual Dpd01599c Uk v001

The document provides information about error codes F91, F92, and F93 that could occur on a Vacon grid converter. F91 indicates a short circuit was detected by current or voltage measurements exceeding limits. F92 means the measured grid voltage is outside the set protection limits, possibly due to a short circuit, low supply or reference voltage, or unconnected voltage monitoring equipment. F93 refers to the measured grid frequency being outside the set limits, potentially because frequency monitoring is not connected or the actual frequency is out of range.

Uploaded by

Mohamed Elsayed
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

184 · VACON® arfiff03 Grid Converter

F91 Short Circuit


Drive has operated against current limit for more than short circuit time.
By phase fault detection has seen low voltage for more than short circuit time.
Warning comes immediately when current is at current limit, fault comes after the short circuit time.

A1: Code given by V089 and older versions.


A2: Bi Phase
A3: Three Phase

Possible cause:
- There is a short circuit in the grid.

Correcting measures:

F92 D7 Voltage
Measured voltage is not within limits set in the protection group Grid Voltage D7
Possible cause:
- Voltage reference is below set limit.
- Supply Voltage is below set limit.
- There is a short circuit in the grid.
- OPT-D7 is installed but not connected.
• Monitoring can be disabled with Control Options.

F93 D7 Frequency
Measured frequency is not within limits set in protection group Grid Frequency.
Possible cause:
- OPT-D7 is installed but measurements are not connected.
• Monitoring can be disabled with Control Options.
- Grid frequency has gone outside the set limits.

F97 Signal Trip


Freely selectable signal monitoring value has exceeded set limit levels.

Local contacts: [Link]