SWD-TS-500-2000 (R 2018)
SWD-TS-500-2000 (R 2018)
The CSI Logo®, SAP2000®, ETABS®, and SAFE® are registered trademarks of
Computers & Structures, Inc. Watch & LearnTM is a trademark of Computers &
Structures, Inc.
The computer programs SAP2000® and ETABS® and all associated documentation are
proprietary and copyrighted products. Worldwide rights of ownership rest with Computers
& Structures, Inc. Unlicensed use of these programs or reproduction of documentation in
any form, without prior written authorization from Computers & Structures, Inc., is
explicitly prohibited.
No part of this publication may be reproduced or distributed in any form or by any means,
or stored in a database or retrieval system, without the prior explicit written permission of
the publisher.
1 Introduction
1.1 Notation 1-2
1.2 Design Station Locations 1-7
1.3 Default Design Load Combinations 1-7
1.3.1 Dead Load Component 1-8
1.3.2 Live Load Component 1-8
1.3.3 Wind Load Component 1-8
1.3.4 Earthquake Load Component 1-9
1.3.5 Combinations that Include a Response Spectrum 1-9
1.3.6 Combinations that Include Time History Results 1-10
1.3.7 Combinations that Include Static Nonlinear
Results 1-11
1.4 Shear Wall Design Preferences 1-11
1.5 Shear Wall Design Overwrites 1-11
1.6 Choice of Units 1-12
2 Pier Design
2.1 Wall Pier Shear Design 2-1
2.1.1 Determine the Concrete Shear Capacity 2-2
2.1.2 Determine the Require Shear Reinforcing 2-2
2.2 Wall Pier End Zones 2-3
2.2.1 Details of Check for Wall End Zone Requirements 2-3
i
Shear Wall Design TS 500-2000(R2018)
3 Spandrel Design
3.1 Spandrel Flexural Design 3-1
3.1.1 Determine the Maximum Factored Moments 3-2
3.1.2 Determine the Required Flexural Reinforcing 3-2
3.2 Spandrel Shear Design 3-10
3.2.1 Determine the Concrete Shear Capacity 3-10
3.2.2 Determine the Required Shear Reinforcing 3-11
Bibliography
ii
Chapter 1
Introduction
This manual describes the details of the shear wall design and stress check
algorithms used by the program when the user selects the TS 500-2000(R2018)
design code. The various notations used in this manual are described in Section
1.1.
Design and check of concrete wall piers for flexural and axial loads (Chapter
2)
Consideration of the wall end zones requirements for concrete wall piers us-
ing an approach based on the requirements of Turkish Earthquake code 2018
Section 7.6.2 in TS 500-2000(R2018) (Chapter 3)
1-1
Shear Wall Design TS 500-2000(R2018)
1.1. Notation
Following is the notation used in this manual.
1-2 Notation
Chapter 1 Introduction
DB2 Width of a user-defined wall pier edge member, mm. This can
be different on the left and right sides of the pier, and it also
can be different at the top and the bottom of the pier.
LL Live load
Notation 1-3
Shear Wall Design TS 500-2000(R2018)
N left Equivalent axial force in the left edge member of a wall pier
used for design, N. This may be different at the top and the
bottom of the wall pier.
N right Equivalent axial force in the right edge member of a wall pier
used for design, pounds. This may be different at the top and
the bottom of the wall pier.
1-4 Notation
Chapter 1 Introduction
WL Wind load
d r-top Distance from top of spandrel beam to centroid of the top re-
inforcing steel, mm. This can be different on the left and right
ends of the beam.
Notation 1-5
Shear Wall Design TS 500-2000(R2018)
1-6 Notation
Chapter 1 Introduction
γm Material factor
The program designs wall spandrels at stations located at the left and right ends
of the spandrel only. To design at the mid-length of a spandrel, break the span-
drel into two separate "half-length" piers. Note that if a spandrel is into broken
into pieces, the program will calculate the seismic diagonal shear reinforcing
separately for each piece. The angle used to calculate the seismic diagonal
shear reinforcing for each piece is based on the length of the piece, not the
length of the entire spandrel. This can cause the required area of diagonal re-
inforcing to be significantly underestimated. Thus, if you break a spandrel into
pieces, calculate the seismic diagonal shear reinforcing separately by hand.
These also are the default design load combinations in the program whenever
the TS 500-2000 code is used. The user should use other appropriate design
load combinations if roof live load is separately treated, or if other types of
loads are present.
Live load reduction factors can be applied to the member forces of the live
load case on a member-by-member basis to reduce the contribution of the live
load to the factored loading.
See the description of the earthquake load component later in this chapter for
additional information.
The earthquake load cases considered when creating the default design load
combinations include all static load cases that are defined as earthquake loads
and all response spectrum cases. Default design load combinations are not cre-
ated for time history cases or for static nonlinear cases.
The output from a response spectrum is all positive. Any program shear wall
design load combination that includes a response spectrum load case is
checked for all possible combinations of signs on the response spectrum val-
ues. Thus, when checking shear in a wall pier or a wall spandrel, the response
spectrum contribution of shear to the design load combination is considered
once as a positive shear and then a second time as a negative shear. Similarly,
when checking moment in a wall spandrel, the response spectrum contribution
of moment to the design load combination is considered once as a positive
moment and then a second time as a negative moment. When checking the
flexural behavior of a two-dimensional wall pier or spandrel, four possible
combinations are considered for the contribution of response spectrum load to
the design load combination. They are:
+N and +M
+N and −M
−N and +M
−n and −M
where N is the axial load in the pier and M is the moment in the pier. Similarly,
eight possible combinations of N, M2 and M3 are considered for three-dimen-
sional wall piers.
Note that based on the preceding, TS 6.8a and TS 6.8b are redundant for a load
combination with a response spectrum, and similarly, TS 6.7a and TS 6.7b are
redundant for a load combination with a response spectrum. For this reason,
the program creates default design load combinations based on TS 6.8a and
TS 6.7a only for response spectra. Default design load combinations using TS
6.8b and TS 6.7b are not created for response spectra.
When a design load combination includes time history results, the design can
be for the envelope of those results or for each step of the time history. The
type of time history design can be specified in the shear wall design
preferences.
When envelopes are used, the design is for the maximum of each response
quantity (axial load, moment, and the like) as if they occurred simultaneously.
Typically, this is not the realistic case, and in some instances, it may be un-
conservative. Designing for each step of a time history gives the correct corre-
spondence between different response quantities, but designing for each step
can be very time consuming.
When the program gets the envelope results for a time history, it gets a
maximum and a minimum value for each response quantity. Thus, for wall
piers it gets maximum and minimum values of axial load, shear and moment;
and for wall spandrels, it gets maximum and minimum values of shear and
moment. For a design load combination in the program shear wall design
module, any load combination that includes a time history load case in it is
checked for all possible combinations of maximum and minimum time history
design values. Thus, when checking shear in a wall pier or a wall spandrel, the
time history contribution of shear to the design load combination is considered
once as a maximum shear and then a second time as a minimum shear.
Similarly, when checking moment in a wall spandrel, the time history
contribution of moment to the design load combination is considered once as
a maximum moment and then a second time as a minimum moment. When
checking the flexural behavior of a wall pier, four possible combinations are
considered for the contribution of time history load to the design load
combination. They are:
where N is the axial load in the pier and M is the moment in the pier.
If a single design load combination has more than one time history case in it,
that design load combination is designed for the envelopes of the time histo-
ries, regardless of what is specified for the Time History Design item in the
preferences.
If a design load combination includes a single static nonlinear case and nothing
else, the design is performed for each step of the static nonlinear analysis. Oth-
erwise, the design is performed for the last step of the static nonlinear analysis
only.
change any of the overwrites. How-ever, at least review the default values for
the overwrite items to make sure they are acceptable. When changes are made
to overwrite items, the program applies the changes only to the elements to
which they are specifically assigned; that is, to the elements that are selected
when the overwrites are changed. Please consult the program-specific on-line
Help for information about reviewing and updating preferences.
The shear wall design preferences allow the user to specify special units for
concentrated and distributed areas of reinforcing. These units are then used for
reinforcing in the model, regardless of the current model units displayed in the
drop-down list on the status bar (or within a specific form). The special units
specified for concentrated and distributed areas of reinforcing can only be
changed in the shear wall design preferences.
The choices available in the shear wall design preferences for the units associ-
ated with an area of concentrated reinforcing are in2, cm2, mm2, and current
units. The choices available for the units associated with an area per unit length
of distributed reinforcing are in2/ft, cm2/m. mm2/m, and current units.
The current units option uses whatever units are currently displayed in the
drop-down list on the status bar (or within a specific form). If the current length
units are m, this option means concentrated areas of reinforcing are in m2 and
distributed areas of reinforcing are in m2/m. Note that when using the "current"
option, areas of distributed reinforcing are specified in Length2/Length units,
where Length is the currently active length unit. For example, if you are work-
ing in kN and m units, the area of distributed reinforcing is specified in m2/m.
If you are in Newton and mm, the area of distributed reinforcing is specified
in mm2/mm.
This chapter describes how the program designs each leg of concrete wall piers
for shear using TS 500-2000(R2018). Note that in this program shear reinforcing
cannot be specified and then checked by the program. The program only designs
the pier for shear and reports how much shear reinforcing is required. The shear
design is performed at stations at the top and bottom of the pier.
This chapter also describes how the program designs and checks concrete wall
piers for flexural and axial loads using TS 500-2000(R2018). The menu option
“TS 500-2000(R2018)” also covers the “Seismic Design Code” (TCS 2018).
First we describe how the program designs piers that are specified by a Simpli-
fied Section. Next we describe how the program checks piers that are specified
by a Section Designer Section. Then we describe how the program designs piers
that are specified by a Section Designer Section.
Determine the design factored forces Nd, Md and Vd that are acting on the wall
pier section.
Determine the shear force, Vc, that can be carried by the concrete.
2-1
Shear Wall Design TS 500-2000(R2018)
Determine the required shear reinforcing to carry the balance of the shear
force.
Step 1 needs no further explanation. The following two sections describe in de-
tail the algorithms associated with the Steps 2 and 3.
Vmax = 0.85 f ck Ach for flexural wall (TCS 7.6.6.3, Eqn. 7.18)
Vmax = 0.65 f ck Ach for coupled wall (TCS 7.6.6.3, Eqn. 7.18)
Vd − Vc
Ash = (TS 8.1.4, TCS 3.6.7.2)
f yd (0.8 Lw )
where,
=Vr 0.65 f ctd Ach + Ash f yd must not exceed 0.85 f ck Ach in accordance with TCS
Section 7.6.6.3, Eqn. 7.18.
For walls H w ≥ 2.0 , A sh shall be 0.0025 of the gross section area of the wall
lw
web remaining in between the wall end zones. In cases where H w ≤ 2.0 , the
lw
wall web section is the full section of the wall.
Note that the wall end zones requirements are considered separately for each
design load case that includes seismic load.
The height of the entire wall, H w , length of the wall pier, l w , and the gross area
of the pier, A g . (Refer to Figure 2-5 later in this chapter for an illustration of
the dimensions l w and b w, the thickness of the wall pier.)
The area of steel in the pier, A st . This area of steel is calculated by the program,
or it is provided by the user.
The symmetry of the wall pier (i.e., is the left side of the pier the same as the
right side of the pier). Only the geometry of the pier is considered, not the
reinforcing, when determining if the pier is symmetrical. Figure 2-1 shows
some examples of symmetrical and unsymmetrical wall piers. Note that a pier
defined using Section Designer is assumed to be unsymmetrical, unless it is
made up of a single rectangular shape.
Figure 2-1 Example Plan Views of Symmetrical and Unsymmetrical Wall Piers
The critical wall height is measured from the foundation or Base level in ETABS
using the following criteria:
l
H cr ≥ w (TCS 7.6.2.2, Eqn. 7.15)
H w / 6
In structural walls with rectangular cross-sections, the wall end zone length lu is
computed as follows:
2bw
lu ≥ along the critical wall height, and
0.2lw
bw
lu ≥ outside the critical wall height (TCS 3.6.2.3)
0.1lw
If wall end zones are required, the program calculates the minimum required
length of the wall end zone at each end of the wall, l u , in accordance with the
requirements of TCS Section 7.6.5.2 Figure 2-2 illustrates the boundary zone
length l u .
Figure 2-3 Typical Wall Pier Dimensions Used for Simplified Design
The length of the wall pier is designated l w . This is the horizontal length of the
wall pier in plan.
The thickness of the wall pier is designated b w . The thickness specified for left
and right edge members (DB2 left and DB2 right ) may be different from this wall
thickness.
DB1 represents the horizontal length of the pier end zone. DB1 can be different
at the left and right sides of the pier.
DB2 represents the horizontal width (or thickness) of the pier end zone. DB2
can be different at the left and right sides of the pier.
The dimensions illustrated are specified in the shear wall overwrites (Appendix
B) and can be specified differently at the top and bottom of the wall pier.
If no specific end zone dimensions have been specified by the user, the program
assumes that the end zone is the same width as the wall, and the program
determines the required length of the end zone. In all cases, whether the end zone
size is user-specified or program-determined, the program reports the required
area of reinforcing steel at the center of the end zone. This section describes how
the program-determined length of the end zone is determined and how the
program calculates the required reinforcing at the center of the end zone.
Three design conditions are possible for a simplified wall pier. These conditions,
illustrated in Figure 2-4, are as follows:
The wall pier has program-determined (variable length and fixed width) end
zones on each end.
The wall pier has user-defined (fixed length and width) end zones on each end.
The wall pier has a program-determined (variable length and fixed width) end
zone on one end and a user-defined (fixed length and width) end zone on the
other end.
the shear wall design preferences and the pier design overwrites as Edge Design
PC-Max and Edge Design PT-Max.
Consider the wall pier shown in Figure 2-5. For a given design section, say the
top of the wall pier, the wall pier for a given design load combination is designed
for a factored axial force N d-top and a factored moment M d-top .
The program initiates the design procedure by assuming an end zone at the left
end of the wall of thickness b w and width B 1-left , and an end zone at the right end
of the wall of thickness b w and width B 1-right . Initially B 1-left = B 1-right = b w .
The moment and axial force are converted to an equivalent force set N left-top and
N right-top using the relationships shown below. (Similar equations apply at the bot-
tom of the pier.)
N d -top M d -top
N= +
left-top
2 ( lw − 0.5B1-left − 0.5B1-right )
N d -top M d -top
=
N right-top −
2 ( lw − 0.5B1-left − 0.5B1-right )
For any given loading combination, the net values for N left-top and N right-top could
be tension or compression.
0.5Lp
0.5tp 0.5tp
tp tp
tp
B1-left B1-right
B2-left B2-right
B3-left B3-right
Lp
CL
Wall Pier Plan
Bottom
of pier
Mu-bot
Note that for dynamic loads, N left-top and N right-top are obtained at the modal level
and the modal combinations are made before combining with other loads. Also
for design loading combinations involving SRSS, the N left-top and N right-top forces
are obtained first for each load case before the combinations are made.
If any value of N left-top or N right-top is tension, the area of steel required for tension,
A st , is calculated as:
N
Ast = .
f yd
If any value of N left-top or N right-top is compression, for section adequacy, the area
of steel required for compression, A sc , must satisfy the following relationship.
Abs ( N )
− 0.85 f cd Ag
( N max Factor)
Asc = .
f yd − 0.85 f cd
If A st is less than or equal to A st-max and A sc is less than or equal to A sc-max , the
program will proceed to check the next loading combination; otherwise the pro-
gram will increment the appropriate B 1 dimension (left, right or both, depending
on which end zone is inadequate) by one-half of the wall thickness to B 2 (i.e.,
1.5b w ) and calculate new values for N left-top and N right-top resulting in new values
of A st and A sc . This iterative procedure continues until A st and A sc are within the
allowed steel ratios for all design load combinations.
If the value of the width of the end zone B increments to where it reaches a value
larger than or equal to l w /2, the iteration is terminated and a failure condition is
reported.
The design is similar to that which has previously been described for design con-
ditions 1 and 2. The size of the user-specified end zone is not changed. Iteration
occurs on the size of the variable length end zone only.
C
3 3
T
Pier section Pier section
2 2
45°
a) Angle is 0 degrees b) Angle is 45 degrees
2 2
C T 225°
T
Figure 2-6 Orientation of the Pier Neutral Axis for Various Angles
Note that the orientation of the neutral axis is the same for an angle of θ and
θ+180°. Only the side of the neutral axis where the section is in tension or com-
pression changes. We recommend use of 24 interaction curves (or more) to de-
fine a three-dimensional interaction surface.
Each PMM interaction curve that makes up the interaction surface is numerically
described by a series of discrete points connected by straight lines. The coordi-
nates of these points are determined by rotating a plane of linear strain about the
neutral axis on the section of the pier. Details of this process are described later
in the section entitled "Details of the Strain Compatibility Analysis."
By default, 11 points are used to define a PMM interaction curve. This number
can be changed in the preferences; any odd number of points greater than or
equal to 11 can be specified, to be used in creating the interaction curve. If an
even number is specified for this item in the preferences, the program will incre-
ment up to the next higher odd number.
Note that when creating an interaction surface for a two-dimensional wall pier,
the program considers only two interaction curvesthe 0° curve and the 180°
curveregardless of the number of curves specified in the preferences. Further-
more, only moments about the M3 axis are considered for two-dimensional
walls.
(N d , M 2d , M 3d ) ≤ (N r , M 2r , M 3r )
The design strength for concrete and steel is obtained by dividing the character-
istic strength of the material by a partial factor of safety, γ mc and γ ms . The values
used in the program are as follows:
These factors are already incorporated in the design equations and tables in the
code. Although not recommended, the program allows them to be overwritten.
If they are overwritten, the program uses them consistently by modifying the
code-mandated equations in every relevant place.
The theoretical maximum compressive force that the wall pier can carry is des-
ignated N oc and is given by:
N oc = [0.85f cd (A g − A st ) + f yd A st ].
The theoretical maximum tension force that the wall pier can carry is designated
N ot and is given by:
N ot = f yd A st .
If the wall pier geometry and reinforcing is symmetrical in plan, the moments
associated with both N oc and N ot are zero. Otherwise, a moment associated will
be with both N oc and N ot .
Figure 2-7 shows a plan view of an example two-dimensional wall pier. Notice
that the concrete is symmetrical but the reinforcing is not symmetrical in this
example. Figure 2-8 shows several interaction surfaces for the wall pier illus-
trated in Figure 2-7.
# 5@12” o.c.,
12'-6"
each face, except
3" 12 spaces at 1'-0" = 12'-0" 3" as noted
1'
f’c = 4 ksi
2-#9
2-#9
2-#6
fy = 60 ksi
Figure 2-8 Interaction Curves for Example Wall Pier Shown in Figure 2-7
The 0° and 180° interaction curves are not symmetric because the wall pier
reinforcing is not symmetric.
The smaller interaction surface (drawn with a heavier line) has the strength
reduction factor, as specified by TS 500-2000(R2018).
The dashed line shows the effect of setting the N max Factor to 1.0.
The larger interaction surface has both the strength reduction factor and the
N max Factor set to 1.0.
The interaction surfaces shown are created using the default value of 11 points
for each interaction curve.
Figure 2-9 shows the 0° interaction curves for the wall pier illustrated in Figure
2-7. Additional interaction curves are also added to Figure 2-9.
Figure 2-9 Interaction Curves for Example Wall Pier Shown in Figure 2-7
The smaller, heavier curve in Figure 2-9 has the strength reduction factor as
specified in TS 500-2000(R2018).
Figure 2-10 illustrates varying planes of linear strain such as those that the pro-
gram considers on a wall pier section for a neutral axis orientation angle of 0
degrees.
Varying
neutral axis
locations
+ε
0.000
-0.003
Varying Linear Strain Diagram -ε
In these planes, the maximum concrete strain is always taken as −0.003 and the
maximum steel strain is varied from −0.003 to plus infinity. (Recall that in this
program compression is negative and tension is positive.) When the steel strain
is −0.003, the maximum compressive force in the wall pier, N oc , is obtained from
the strain compatibility analysis. When the steel strain is plus infinity, the maxi-
mum tensile force in the wall pier, N ot , is obtained. When the maximum steel
strain is equal to the yield strain for the reinforcing (e.g., 0.00207 for f yk = 460
MPa), N b is obtained.
Figure 2-11 illustrates the concrete wall pier stress-strain relationship that is ob-
tained from a strain compatibility analysis of a typical plane of linear strain
shown in Figure 2-10. In Figure 2-11 the compressive stress in the concrete, C c ,
is calculated using section 7.2 of TS 500-2000(R2018).
In Figure 2-10, the value for maximum strain in the reinforcing steel is assumed.
Then the strain in all other reinforcing steel is determined based on the assumed
plane of linear strain. Next the stress in the reinforcing steel is calculated using
the following equation, where ε s is the strain, E s is the modulus of elasticity, σ s
is the stress, and f ys is the yield stress of the reinforcing steel.
13 12 11 10 9 8 7 6 5 4 3 2 1
Ts Ts Ts Ts Ts Ts Ts Ts Ts Cs Cs Cs Cs
0.85f'c
Cc
a = β1c
Stress Diagram
ε13s
ε12s
ε11s ε10
s
ε9s ε8 c
s
ε7s ε6 5
s ε
s
ε = 0.003
ε4s ε3
s
ε2s ε1
s
Linear Strain Diagram
tp
Plan View of Wall Pier
σ s = ε s E s ≤ f ys
The force in the reinforcing steel (T s for tension or C s for compression) is calcu-
lated by:
T s or C s = σ s A s
N r = (ΣT s − C c − ΣC s ) ≤ N max
In the preceding equation , the tensile force T s and the compressive forces C c
and C s are all positive. If N r is positive, it is tension, and if it is negative, it is
compression.
The value of M 2r is calculated by summing the moments due to all of the forces
about the pier local 2 axis. Similarly, the value of M 3r is calculated by summing
the moments due to all of the forces about the pier local 3 axis. The forces whose
moments are summed to determine M 2r and M 3r are N r , C c , all of the T s forces
and all of the C s forces.
When one interaction curve is complete, the next orientation of the neutral axis
is assumed and the points for the associated new interaction curve are calculated.
This process continues until the points for all of the specified curves have been
calculated.
As a measure of the stress condition in the wall pier, the program calculates a
stress ratio. The ratio is achieved by plotting the point L and determining the
location of point C. The point C is defined as the point where the line OL (ex-
tended outward if needed) intersects the interaction curve. The demand/capacity
ratio, D/C, is given by D/C = OL / OC where OL is the "distance" from point O
(the origin) to point L, and OC is the "distance" from point O to point C. Note
the following about the demand/capacity ratio:
If OL = OC (or D/C = 1), the point (N d , M 3d ) lies on the interaction curve and
the wall pier is stressed to capacity.
If OL < OC (or D/C < 1), the point (N d , M 3d ) lies within the interaction curve
and the wall pier capacity is adequate.
φPn
Pu L
Axial
Compression
Axial O M3u φM3n
Tension
If OL > OC (or D/C > 1), the point (N d , M 3d ) lies outside of the interaction
curve and the wall pier is overstressed.
The wall pier demand/capacity ratio is a factor that gives an indication of the
stress condition of the wall with respect to the capacity of the wall.
The size of each reinforcing bar specified in Section Designer relative to the
size of the other bars.
The interaction surfaces are developed for eight different ratios of reinforcing-
steel-area-to-pier-area. The pier area is held constant and the rebar area is mod-
ified to obtain these different ratios; however, the relative size (area) of each
rebar compared to the other bars is always kept constant.
The smallest of the eight reinforcing ratios used is that specified in the shear wall
design preferences as Section Design IP-Min. Similarly, the largest of the eight
reinforcing ratios used is that specified in the shear wall design preferences as
Section Design IP-Max.
The eight reinforcing ratios used are the maximum and the minimum ratios plus
six more ratios. The spacing between the reinforcing ratios is calculated as an
increasing arithmetic series in which the space between the first two ratios is
equal to one-third of the space between the last two ratios. Table 1 illustrates the
spacing, both in general terms and for a specific example, when the minimum
reinforcing ratio, IPmin, is 0.0025 and the maximum, IPmax, is 0.02.
After the eight reinforcing ratios have been determined, the program develops
interaction surfaces for all eight of the ratios using the process described earlier
in the section entitled "Checking a General or Uniform Reinforcing Pier Sec-
tion."
Next, for a given design load combination, the program generates a demand/ca-
pacity ratio associated with each of the eight interaction surfaces. The program
then uses linear interpolation between the eight interaction surfaces to determine
the reinforcing ratio that gives a demand/capacity ratio of 1 (actually the program
uses 0.99 instead of 1). This process is repeated for all design load combinations
and the largest required reinforcing ratio is reported.
This chapter describes how the program designs concrete shear wall spandrels
for flexure and shear when TS 500-2000(R2018) is the selected design code.
The program allows consideration of rectangular sections and T-beam sections
for shear wall spandrels. Note that the program designs spandrels at stations
located at the ends of the spandrel. No design is performed at the center (mid-
length) of the spandrel. The program does not allow shear reinforcing to be
specified and then checked. The program only designs the spandrel for shear and
reports how much shear reinforcing is required.
The following steps are involved in designing the flexural reinforcing for a par-
ticular wall spandrel section for a particular design loading combination at a par-
ticular station.
3-1
Shear Wall Design TS 500-2000(R2018)
The beam section is then designed for the maximum positive and the maximum
negative factored moments obtained from all of the design load combinations.
In this program, positive beam moments produce bottom steel. In such cases, the
beam may be designed as a rectangular section, or as a T-beam section. Indicate
that a spandrel is to be designed as a T-beam by specifying the appro-priate slab
width and depth dimensions are provided in the spandrel design overwrites
(Appendix B).
εcu Es
cb = d (TS 7.1)
εcu Es + f yd
It is assumed that the compression depth carried by the concrete is less than or
equal to amax. When the applied moment exceeds the moment capacity at amax,
the program calculates an area of compression reinforcement assuming that the
additional moment is carried by compression reinforcing and additional tension
reinforcing.
The procedure used by the program for both rectangular and T-beam sections is
given in the subsections that follow.
a
=M d Cc dspandrel − (TS 7.1)
2
where Cc = 0.85 f cd a ts and dspandrel is equal to hs − dr-bot for positive bending and
hs − dr-top for negative bending.
2M d
a =dspandrel − dspandrel
2
−
0.85 f cd ts
The program uses the preceding equation to determine the depth of the compres-
sion block, a. The depth of the compression block, a, is compared with amax.
Md
As =
a
f yd dspandrel −
2
The steel is placed at the bottom for positive moment and at the top for negative
moment.
Note: The program reports the ratio of top and bottom steel required in the web area.
When compression steel is required, those ratios may be large because there is no limit
on them. However, the program reports an overstress when the ratio exceeds 4%.
The depth of the concrete compression block, a, is set equal to a = amax. The
compressive force developed in the concrete alone is given by
The moment resisted by the couple between the concrete in compression and the
tension steel, Mdc, is given by
a
=M dc Cc dspandrel − max
2
Therefore, the additional moment to be resisted by the couple between the com-
pression steel and the additional tension steel, Mds, is given by
M=
ds M d − M dc
M ds
Cs =
dspandrel − d r
Referring to Figure 3-1, the strain in the compression steel, ε's, is given by.
0.003 ( c − d r )
ε s′ =
c
c − d′
σ′s Es εcu max ≤ f yd .
cmax
The term dr in the preceding equations is equal to dr-top for positive bending and
equal to dr-bot for negative bending. The term c is equal to amax k1.
The total required area of compression steel, A's, is calculated using the following
equation.
Cs
As′ =
(σ s′ − 0.85 f cd )
The required area of tension steel for balancing the compression in the concrete
web, Asw, is:
M dc
Asw =
a
f yd dspandrel − max
2
The required area of tension steel for balancing the compression steel, Asc, is:
M ds
Asc =
f yd ( dspandrel − d r )
In the preceding equations, dspandrel is equal to hs − dr-bot for positive bending and
hs − dr-top for negative bending. In the preceding equations, dr is equal to dr-top for
positive bending and dr-bot for negative bending.
=
As Asw + Asc
Thus, the total tension reinforcement, As, and the total compression reinforce-
ment, As'. As is to be placed at the bottom of the beam, and As' at the top for
positive bending and vice versa for negative bending.
2M d
a =−
d d2 − .
0.85 f cd b f
If a ≤ ds, the subsequent calculations for the reinforcing steel are exactly the
same as previously defined for rectangular section design. However, in that
case, the width of the compression block is taken to be equal to the width of
the compression flange, bs. Compression reinforcement is provided when the
dimension "a" exceeds amax.
If a > ds, the subsequent calculations for the required area of reinforcing steel
are performed in two parts. First, the tension steel required to balance the com-
pressive force in the flange is determined, and second, the tension steel re-
quired to balance the compressive force in the web is determined. If necessary,
compression steel is added to help resist the design moment.
The remainder of this section describes in detail the design process used by the
program for T-beam spandrels when a > ds.
Refer to Figure 3-2. The compression force in the protruding portion of the
flange, Cf, is given. The protruding portion of the flange is shown cross-hatched.
=C f 0.85 f cd ( bs − ts ) d s
Figure 3-2 Design of a Wall Spandrel with a T-Beam Section, Positive Moment
The required area of tension steel for balancing the compression force in the
concrete flange, Asf, is:
Cf
Asf =
f yd
The portion of the total moment, Md, that is resisted by the flange, Mdf, is given
by
d
=M df C f dspandrel − s .
2
Therefore, the balance of the moment to be carried by the web, Mdw, is given by
M=
dw M d − M df .
The web is a rectangular section of width ts and depth hs for which the design
depth of the compression block, a1, is recalculated as:
2 M dw
a1 =dspandrel − dspandrel
2
−
0.85 f cd ts
M dw
Asw =
a
f yd d spandrel − 1
2
=
As Asf + Asw
The total tension reinforcement, As, is to be placed at the bottom of the beam for
positive bending.
The depth of the concrete compression block, a, is set equal to amax, a = amax. The
compressive force developed in the web concrete alone is given by
Cw = 0.85 f cd ats .
The moment resisted by the couple between the concrete web in compression
and the tension steel, Mdc, is given by
a
=M dc Cw dspandrel − .
2
Therefore, the additional moment to be resisted by the couple between the com-
pression steel and the tension steel, Mds, is given by
=
M ds M dw − M dc
Referring to Figure 3-2, the force carried by the compression steel, Cs, is given
by
M ds
Cs = .
dspandrel − d r -top
0.003 ( c − d r -top )
ε s′ = .
c
0.003Es ( c − d r -top )
f s′ = Es ε s′ = .
c
Cs
As′ = .
σ s′
The required area of tension steel for balancing the compression in the concrete
web, Asw, is
M dc
Asw = .
a
f yd dspandrel −
2
The required area of tension steel for balancing the compression steel, Asc, is
M ds
Asc = .
f yd ( dspandrel − d r -top )
As is to be placed at the bottom of the beam, and As' at the top of the beam.
The wall spandrel shear reinforcing is designed for each of the design load com-
binations. The required area of reinforcing for vertical shear is calculated only at
the ends of the spandrel beam.
In this program, wall spandrels are designed for major direction flexure and shear
forces only. Effects caused by any axial forces, minor direction bending, torsion
or minor direction shear that may exist in the spandrels must be investigated by
the user independent of the program.
The following steps are involved in designing the shear reinforcing for a partic-
ular wall spandrel section for a particular design loading combination at a par-
ticular station.
Determine the shear force, Vc, that can be carried by the concrete.
Determine the required shear reinforcing to carry the balance of the shear
force.
Step 1 needs no further explanation. The following two sections describe in de-
tail the algorithms associated with Steps 2 and 3.
The required shear reinforcement per unit spacing, Asw /s, is calculated as fol-
lows:
If Vd ≤ Vcr ,
Asw f
= 0.3 ctd bw , (TS 8.1.5, Eqn. 8.6)
s f ywd
Asw (Vd − Vc )
= , (TS 8.1.4, Eqn. 8.5)
s f ywd d
Asw f
≥ 0.3 ctd bw (TS 8.1.5, Eqn. 8.6)
s f ywd
If Vd exceeds its maximum permitted value Vmax, the concrete section size should
be increased (TS 8.1.5b).
If Vds exceeds 1.5 f ctd ts dspandrel , a failure condition is reported in accordance with
TCS Section 7.6.8.2.
Given Vds, the preceding equation initially calculates the required vertical shear
reinforcing in area per unit length (e.g., square mm per meter) for both seismic
and nonseismic wall spandrels (as indicated in the preferences). Note that addi-
tional requirements that are checked for both seismic and nonseismic wall span-
drels are given as.
Vds
Av =
f yd dspandrel
Note: The output units for the distributed shear reinforcing can be set in the
shear wall design preferences.
Vd
Avd = , (TCS 7.6.8.2(b))
2 f yd sin γ
where,
0.8hs
sin γ = ,
L2s + (0.8hs ) 2
where hs is the height of the spandrel and Ls is the length of the spandrel.
In the output, the program reports the diagonal shear reinforcing as required or
not required (i.e., optional). The diagonal shear reinforcing is reported as re-
quired when Vd > 1.5f ctd dbspandrel .
CSI, 2019. CSI Analysis Reference Manual. Computers and Structures, Inc.,
Walnut Creek, California.
TCS, 2018. Specification for Turkish Seismic Code. Official Gazette No. 26454
and 26511. Ministry of Public Works and Settlement. Government of the
Republic of Turkey.
Bibliography - i