NTDC-merged Data
NTDC-merged Data
WAPDA/NTDC Junior
Engineer/JE Interview
Preparation
Prepared by:
Group Admin
Engr.Mehran Marwat
Assistant Engineer (Operations) 220KV G/S,
NTDC Loralai, Quetta
What is anti-fog insulator?
They are most likely Called Fog Type insulators. They are same as insulators but a little higher insulation
value. Taken into account these factors Location, voltage, ph of the water, pollution levels,
temperatures ranges, Flash over voltage, seismic loads, mechanical loads, wind loads etc.
Why power transformers are designed to have maximum efficiency near full load while
distributors’ transformers near half load?
Due to the continuous changing load on a distribution transformer, they are designed for giving
maximum efficiency at 50% of loading because efficiency is maximum when cu losses= iron losses but in
distribution t/f cu losses vary according to demand.
(10) Polarity Test: This test on a transformer is either additive or subtractive. When voltage
is applied between the primary bushings and the resultant voltage between the secondary
bushings is greater, then it means that the transformer has additive polarity. Polarity is a vital
concern if transformers are to be paralleled or bank connected. Three-phase transformers are
also checked for polarity by the same means.
An oil sample will detect several things on a transformer. The following tests can be performed
with the oil sample.
Acid number
Dielectric breakdown
Power factor
Moisture content
Interfacial tension
Oil tests are really useful to determine the condition of the insulation and the oil so based on
these results a maintenance program can be established.
The breakdown of electrical insulating materials and related components inside a transformer
generates gases within the transformer. The identity of the gases being generated can be very useful
information in any preventive maintenance program. There are several techniques for detecting
those gases and DGA is recognized as the most informative method. This method involves sampling
the oil and testing the sample to measure the concentration of the dissolved gases. It is
recommended that DGA of the transformer oil be performed at least on an annual basis with results
compared from year to year.
BDV Test is a very important testing procedure for the insulation oils in transformer. When the
testing result shows a very low value, the oil has to be replaced or purified.
For mineral oil, a generally accepted minimum dielectric strength is 30 kV for transformers with a
high-voltage rating of 230 kV and above and 27 kV for transformers with a high-voltage rating below
230 kV. New oil should have a minimum dielectric strength of 35 kV by ASTM methods of testing.
Buchholz relay:
Buchholz relay is a type of oil and gas actuated protection relay universally used on all oil immersed
transformers having rating more than 500 kVA. Buchholz relay is not provided in relays having rating
below 500 kVA from the point of view of economic considerations.
Working: Buchholz relay is used for the protection of transformers from the faults occurring inside
the transformer. Short circuit faults such as inter turn faults, incipient winding faults, and core faults
may occur due to the impulse breakdown of the insulating oil or simply the transformer oil.
It’s a gas actuated relay and it works for internal faults when temperature of T/F rise, breakdown of
oil occurs which will produce gas to operate the relay.
Construction: Buchholz relay can be used in the transformers having the conservators only. It is
placed in the pipe connecting the conservator tank and the transformer tank. It consists of an oil
filled chamber. Two hinged floats, one at the top of the chamber and the other at the bottom of the
chamber which accompanies a mercury switch each is present in the oil filled chamber. The mercury
switch on the upper float is connected to an external alarm circuit and the mercury switch on the
lower is connected to an external trip circuit.
When does a buchholz relay operate? Buchholz relay operates during three conditions:
1. Whenever gas bubbles are formed inside the transformer due to severe fault.
2. Whenever the level of transformer oil falls.
3. Whenever transformer oil flows rapidly from the conservation tank to the main or from the main
tank to the conservation tank.
Limitations: It can sense the faults occurring below the oil level only. The relay is slow and has a
minimum operating range of 0.1second and an average operating range of 0.2 seconds.
W(hys) =B^(1.6)*f
B=V/f
W(edd)=B^(2)*f^2
(In eddy current formulae, effect of frequency is cancelled when u put B=V/f)
Auto-Transformer:
Transformer in which primary and secondary windings are interrelated. Both primary and secondary
share common single winding. The main advantage of this type of transformer design is that it can
be made a lot cheaper for the same VA rating, but the biggest disadvantage of an autotransformer is
that it does not have the primary/secondary winding isolation of a conventional double wound
transformer. Uses of Auto-transformers are
1. Voltage regulator
It stabilizes circuit potentials with respect to ground and limits the overall potential rise.
It protects life and property from over voltage.
It provides low impedance path to fault currents to ensure prompt and consistent operation of
protective devices during ground faults.
It keeps the maximum voltage gradient along the surface inside and around the substation
within safe limits during ground fault.
Transformer Types:
On the basis of voltage level
(i) Step-up and (ii) Step-down
Depending upon uses
(i) Power T/F (ii) Distribution T/F (iii) Instrument T/F (CT & PT)
On the basis of design
(i) Two winding T/F and (ii) Auto (single winding transformer)
On the basis of operation
(i) Single phase T/F and (ii) Three phase T/F
On the basis of insulation
(i) Oil immersed T/F and (ii) Dry type T/F
Step potential (E-Step): It is the potential developed between the two feet on the ground of a
man or animal when short circuit occurs. This results in flow of current in the body leads to
electrical shock.
Touch potential (E-Touch): It is the potential that is developed between the ground and the
body of the equipment when a person touches the body during fault condition. When operating
personnel touch an electrical equipment during short circuit condition, fault current flows
through the human body. This is defined as touch potential.
What is the need of batteries at the substation?
To provide an uninterrupted & reliable power supply to control the switch gears & monitor the
status of feeders in case of power failure.
In a Substation DC power is supplied in following feeders of a panel:
Tripping and Closing circuit of Circuit breaker
Protection Relay
Isolator control circuit
Indication lamp, Alarm, Facia
PLC Control panel
Emergency lamps in Control room
All of the above are minimum requirements and supply to the above circuits should be available in any
condition. Suppose the Station Transformer is failed, in that case supply should be available for the
panels of line and Power Transformer, Busbar protection etc., which are still in service. Hence battery
set is provided for backup purpose. Nowadays in EHV Substations, it is a practice to provide two battery
sets each with a Battery charger.
Bundled conductors are used in electrical transmission system above 220 kV to get better voltage
regulation. Up to 220 kV, single stranded conductors are used. But it is not possible to use single
stranded conductor above 220 kV systems. In bundled conductors two or more stranded conductors are
used per phase.
The transposition arrangement of high voltage lines also helps to reduce the system power loss.
Transposition arrangement of power line also helps to reduce the effect of inductive
coupling.
It also reduces radio interference with other communication lines, as in case of three
phase system, electrical flux linkage between conductors produces imbalance in the
system.
Power outage: A power outage (also called a power cut, a power out, a power blackout,
power failure or a blackout) is a short-term or a long-term loss of the electric power to a
particular area.
Grounding: Grounding means connecting the live part (it means the part which carries current
under normal condition) to the earth, for example neutral of power transformer. It is done for
the protections of power system equipment and to provide an effective return path from the
machine to the power source. Black wire is used for it as nomenclature.
Earthing: Earthing means connecting the dead part (it means the part which does not carries
current under normal condition) to the earth, for example electrical equipment’s frames,
enclosures, supports etc. The purpose of earthing is to minimize the risk of receiving an electric
shock if touching metal parts when a fault is present. Generally green wire is used for this as a
nomenclature.
Main Points:
When we take out the neutral for a three phase unbalanced connection and send it to
ground, it is called grounding. Grounding is done to balance unbalanced load. While
earthing is used between the equipment and earth pit so as to avoid electrical shock
and equipment damage.
Earthing is used for the safety of the human body in fault conditions while Grounding
(As neutral earth) is used for the protection of equipment. Earthing is a preventive
measure as it provides low resistance path to the fault current while Grounding is just
a return path.
Why secondary of potential transformer should not be short circuited?
Since, the power (P=VI) in a transformer (input and output) is same, the current rises to a
very high level. Thus, a very high resistance is maintained at the secondary terminal to limit
the current (which appears as open circuit)... Short circuiting the secondary would burn out
the windings.
If a step down Transformer is connected with its output and Input interchanged,
does it work as a step up transformer?
Sure why not,
Step down voltage transformer is nothing but current step up transformer.
If we give supply to secondary of the step up transformer then we get output which is greater than
input.
But drawback is that rating is fixed,
Means if Transformer is of 11KV/440V,
Then we get only 11KV to the secondary side when we energies the 440V side.
Not more than 11 KV so this is the limitation.
1) Differential Protection of Transformer:
Generally Differential protection is provided in the electrical power transformer rated more than 5MVA.
The Differential Protection of Transformer has many advantages over other schemes of protection.
The faults occur in the transformer inside the insulating oil can be detected by Buchholz
relay. But if any fault occurs in the transformer but not in oil then it cannot be detected by
Buchholz relay. Any flash over at the bushings are not adequately covered by Buchholz
relay. Differential relays can detect such type of faults. Moreover Buchholz relay is provided
in transformer for detecting any internal fault in the transformer but Differential Protection
scheme detects the same in more faster way.
The differential relays normally response to those faults which occur in side the differential
protection zone of transformer.
A relay is automatic device which senses an abnormal condition of electrical circuit and closes its
contacts. These contacts in turns close and complete the circuit breaker trip coil circuit hence make the
circuit breaker tripped for disconnecting the faulty portion of the electrical circuit from rest of the
healthy circuit.
Pickup Level of Actuating Signal: The value of actuating quantity (voltage or current) which is on
threshold above which the relay initiates to be operated. If the value of actuating quantity is increased,
the electromagnetic effect of the relay coil is increased, and above a certain level of actuating quantity,
the moving mechanism of the relay just starts to move.
Reset Level: The value of current or voltage below which a relay opens its contacts and comes in
original position.
Operating Time of Relay: The time which elapses between the instant when actuating quantity
exceeds the pickup value to the instant when the relay contacts close.
Reset Time of Relay: The time which elapses between the instant when the actuating quantity
becomes less than the reset value to the instant when the relay contacts return to its normal position.
Reach of Relay: A distance relay operates whenever the distance seen by the relay is less than the pre-
specified impedance. The actuating impedance in the relay is the function of distance in a distance
protection relay. This impedance or corresponding distance is called the reach of relay (from fault
location to relay location).
Power system protection relays can be categorized into different types of relays:
Types of protection relays are mainly based on their characteristic, logic, on actuating parameter and
operation mechanism.
Based on operation mechanism protection relay can be categorized as electromagnetic
relay, static relay and mechanical relay.
1. In an electromagnetic relay, these closing and opening of relay contacts are done by the
electromagnetic action of a solenoid.
2. In the mechanical relay, these closing and opening of relay contacts are done by mechanical
displacement of different gear level system.
3. In static relay it is mainly done by semiconductor switches like thyristor.
4. In digital relay on and off state can be referred as 1 and 0 state.
Electromagnetic Relays:
Electromagnetic relays are those relays which are operated by electromagnetic action. Modern
electrical protection relays are mainly microprocessor based, but still electromagnetic relay holds
its place. It will take much longer time to replace all electromagnetic relays by microprocessor
based static relays.
Electromagnetic Relay Working: Practically all the relaying device is based on either one or more
of the following types of electromagnetic relays.
1. Magnitude measurement
2. Comparison
3. Ratio measurement
Principle of electromagnetic relay working is on some basic principles. Depending upon
working principle these can be divided into following types of electromagnetic relays.
1. Attracted Armature type relay,
2. Induction Disc type relay
3. Induction Cup type relay
4. Balanced Beam type relay
5. Moving coil type relay
6. Polarized Moving Iron type relay
Important terms of Relay:
2. Definite Time Over Current Relay (DTOC): This relay is created by applying intentional time delay
after crossing pick up the value of the current. A definite time overcurrent relay can be adjusted to issue
a trip output at an exact amount of time after it picks up. Thus, it has a time setting adjustment and
pickup adjustment.
3. Inverse Time Over Current Relay (ITOC):
Inverse time is a natural character of any induction type rotating device. Here, the speed of rotation of
rotating part of the device is faster if the input current is more. In other words, time of operation
inversely varies with input current. This natural characteristic of electromechanical induction disc relay
is very suitable for overcurrent protection. If the fault is severe, it will clear the fault faster.
Inverse Definite Minimum Time Over Current Relay or IDMT O/C Relay:
Ideal inverse time characteristics cannot be achieved, in an overcurrent relay. As the current in the
system increases, the secondary current of the current transformer is increased proportionally. The
secondary current enters the relay current coil. But when the CT becomes saturated, there would not
be a further proportional increase of CT secondary current with increased system current. From this
phenomenon, it is clear that from trick value to certain range of faulty level, an inverse time relay shows
specific inverse characteristic. But after this level of fault, the CT becomes saturated and relay current
does not increase further with increasing faulty level of the system. As the relay current does not
increase further, there would not be any further reduction in time of operation in the relay. We define
this time as the minimum time of operation. Hence, the characteristic is inverse in the initial part, which
tends to a definite minimum operating time as the current becomes very high. That is why the relay is
referred as inverse definite minimum time over current relay or simply IDMT relay.
Hall Effect Transducer: The Hall Effect element is a type of transducer used
for measuring the magnetic field by converting it into an emf. The direct measurement of the magnetic
field is not possible. Thus the Hall Effect Transducer is used. The transducer converts the magnetic
field into an electric quantity which is easily measured by the analogue and digital meters.
Over flux Relay/Over-Excitation Relay of Transformer: Transformer Overflux Protection is
provided to protect the Transformer core from over fluxing. A Transformer is designed to operate at a
particular flux level. In case the flux in the core of Transformer exceeds a certain level, the core loss
increases which may lead to overheating of components which in turn may result into internal fault.
Therefore, over flux protection is provided.
The flux in the core increases with either increasing voltage or decreasing frequency. During
start-up or shutdown of generator-connected transformers, or following a load rejection, the
transformer may experience an excessive ratio of Volts to Hertz (V/f), that is, become
overexcited. When a transformer core is overexcited, the core is operating in a non-linear
magnetic region, and creates harmonic components in the exciting current.
Let us assume that Transformer Primary is connected with 220 kV. Thus normal voltage of
primary of Transformer will be 220 kV at a frequency of 50 Hz. Also assume that the PT ratio is
220 kV/110 V.
Therefore,
Normally the setting of over fluxing is kept 110% of nominal value or 1.1 Pu. This means at a flux level
of 1.1×2.2 = 2.42, the Transformer will operate safely but above 2.42, the Transformer core will be
subjected to over flux and over-flux relay will trip.
Why MHO relay is preferred for long transmission lines, reactance relay in case of short
transmission lines and impedance relay in case of medium transmission lines?
These major factors determine the relay usage for transmission lines
1. Power swing
3. fault resistance
4. directional property
5. cost
Mho relay (Used for Long T/L) Reason is explained on next Page :
1) Long transmission lines:
Since Long lines are highly subjected to power swings (Load shedding cumulative effect adds on and
effects the long transmission lines majorly).
Mho relay can protect from power swing better than simple impedance relay.
Mho relay has the directional property also which is essential in transmission lines.
Ground faults are highly subjected here because of the trees falling down during the heavy winds. So
fault resistance can effect in estimating the reach of the distance relay.
Reactance relay is immune to the fault resistance but isn’t directional and also unstable at normal load.
So the mho relay is used in conjunction with the reactance relay here.
Here simple impedance relay with added directional property element is used rather than the mho relay
due to the cost factor.
The scheme of busbar protection, involves, Kirchhoff’s current law, which states that, total current
entering an electrical node is exactly equal to total current leaving the node. Hence, total current
entering into a bus section is equal to total current leaving the bus section. The principle of differential
busbar protection is very simple. Here, secondaries of all CTs are connected parallel. That means, S1
terminals of all CTs connected together and forms a bus wire. Similarly S2 terminals of all CTs connected
together to form another bus wire. A tripping relay is connected across these two bus wires.
At external faulty condition, there is no current flows through relay. Now consider a situation when fault
is occurred on the bus itself. At this condition, also the faulty current is contributed by all feeders
connected to the bus. Hence, at this condition, sum of all contributed fault current is equal to total
faulty current. Now, at faulty path there is no CT. (in external fault, both fault current and contributed
current to the fault by different feeder get CT in their path of flowing). The sum of all secondary currents
is no longer zero. It is equal to secondary equivalent of faulty current. So at this condition current starts
flowing through relay and it makes trip the circuit breaker corresponding to all the feeders connected to
this section of the busbar and the bus becomes dead.
Overvoltage Protection:
There are always a chance of suffering an electrical power system from abnormal over voltages. These
abnormal over voltages may be caused due to various reason such as, sudden interruption of heavy
load, lightening impulses, switching impulses etc. These over voltage stresses may damage insulation of
various equipment’s and insulators of the power system. Although, all the over voltage stresses are not
strong enough to damage insulation of system, but still these over voltages also to be avoided to ensure
the smooth operation of electrical power system. These all types of destructive and non-destructive
abnormal over voltages are eliminated from the system by means of over voltage protection.
Voltage Surge:
The over voltage stresses applied upon the power system, are generally transient in nature. Transient
voltage or voltage surge is defined as sudden sizing of voltage to a high peak in very short duration. The
voltage surges are transient in nature that means they exist for very short duration. The main cause of
these voltage surges in power system are due to lightning impulses and switching impulses of the
system. But over voltage in the power system may also be caused by, insulation failure, arcing ground
and resonance etc.
The voltage surges appear in the electrical power system due to switching surge, insulation failure,
arcing ground and resonance are not very large in magnitude. These over voltages hardly cross the twice
of the normal voltage level. Generally, proper insulation to the different equipment of power system is
sufficient to prevent any damage due to these over voltages. But over voltages occur in the power
system due to lightning is very high. If over voltage protection is not provided to the power system,
there may be high chance of severe damage. Hence all over voltage protection devices used in power
system mainly due to lightning surges.
When a no load transmission line is suddenly switched on, the voltage on the line becomes twice of
normal system voltage. This voltage is transient in nature. When a loaded line is suddenly switched off
or interrupted, voltage across the line also becomes high enough current chopping in the system mainly
during opening operation of air blast circuit breaker, causes over voltage in the system. During insulation
failure, a live conductor is suddenly earthed. This may also cause sudden over voltage in the system.
Resonance:
If emf wave produced by alternator is distorted, the trouble of resonance may occur due to 5th or higher
harmonics. Actually for frequencies of 5th or higher harmonics, a critical situation in the system so
appears, that inductive reactance of the system becomes just equal to capacitive reactance of the
system. As these both reactance cancel each other the system becomes purely resistive. This
phenomenon is called resonance and at resonance the system voltage may be increased enough.
These are mainly three main methods generally used for protection against lightning. They are
1. Earthing screen.
Earthing screen is generally used over electrical substation. In this arrangement a net of GI wire is
mounted over the sub-station. The GI wires, used for earthing screen are properly grounded through
different sub-station structures. This network of grounded GI wire over electrical sub-station, provides
very low resistance path to the ground for lightning strokes. This method of high voltage protection is
very simple and economic but the main drawback is, it cannot protect the system from travelling wave
which may reach to the sub-station via different feeders.
This method of over voltage protection is similar as earthing screen. The only difference is, an earthing
screen is placed over an electrical sub-station, whereas, overhead earth wire is placed over electrical
transmission network. One or two stranded GI wires of suitable cross-section are placed over the
transmission conductors. These GI wires are properly grounded at each transmission tower. These
overhead ground wires or earth wire divert all the lightning strokes to the ground instead of allowing
them to strike directly on the transmission conductors.
3. Lightning Arrester:
The previously discussed two methods, i.e. earthing screen and over-head earth wire are very suitable
for protecting an electrical power system from directed lightning strokes but these methods cannot
provide any protection against high voltage travelling wave which may propagate through the line to the
equipment of the sub-station. The lightning arrester is a devices which provides very low impedance
path to the ground for high voltage travelling waves. The concept of a lightning arrester is very simple.
This device behaves like a nonlinear electrical resistance. The resistance decreases as voltage increases
and vice-versa, after a certain level of voltage.
1. Under normal voltage level, these devices withstand easily the system voltage as electrical
insulator and provide no conducting path to the system current.
2. On occurrence of voltage surge in the system, these devices provide very low impedance path
for the excess charge of the surge to the ground.
3. After conducting the charges of surge, to the ground, the voltage becomes to its normal level.
Then lightning arrester regains its insulation properly and prevents further conduction of
current, to the ground.
There are different types of lightning arresters used in power system, such as rod gap arrester,
horn gap arrester, multi-gap arrester, expulsion type LA, value type LA.
In addition to these the most commonly used lightning arrester for over voltage protection
now-a-days gapless ZnO lightning arrester is also used.
Zinc Oxide Lightning Arrester: (used nowadays)
This type of arrester comprises of numbers of solid zinc oxide disc. This discs are arranged one
by one to form a cylindrical stack. The number of zinc oxide discs used per lightning arrester
depends upon the voltage rating of the system. This stack is kept inside a cylindrical housing of
polymer or porcelain. Then the stack is placed inside the housing and highly pressed by heavy
spring load attached to end cap at top. The equipment connection terminal for line is projected
from top cap and connection terminal for earth is projected from the bottom cap.
Arcing Horns:
Arcing horns form a spark gap across the insulator with a lower breakdown voltage than the air path
along the insulator surface, so an overvoltage will cause the air to break down and the arc to form
between the arcing horns, diverting it away from the surface of the insulator preventing it from flash-
over.
Surge Arrestors:
A surge arrester is a device that protects electrical power systems from damages caused by lightning.
When a powerful electric surge travels from the power system to the surge arrester, the high voltage
current is sent directly to the insulation or to the ground to avoid damaging the system. OR A surge
arrester is a device to protect electrical equipment from over-voltage transients caused by external
(lightning) or internal (switching) events.
Surge Diverters:
Surge diverters work by capturing the excess electricity that would otherwise be absorbed into the
house's electrical circuit. They will help protect the property by diverting this power away from the
house by “shunting” it to the earth. Any electricity over 260 volts will automatically be diverted to the
ground.
POWER TRANSFORMER: Power Transformer is a static electrical device .By electromagnetic
induction, it transforms electrical power from one or more circuits to one or more other circuits at the
same frequency usually with a change in voltage and current levels. Specially designed transformers can
also affect a change in phase angle between input and output voltages/currents.
The invention of transformer had made it possible to efficiently transmit large amounts of
electrical power over long distances. In the transmission of electric power, the function of the
Transformer is to raise or step-up the voltage at the generator to a much higher value and to
step down the voltage to the utilization value at the load center where the power is used. This
reduces the size of transmission conductor and hence installation and maintenance costs are
reduced.
Thus in transmitting power from generators to load centers transformers play a vital part. Power
transformer are of higher KVA ratings (more than 500KVA) and are operated at high KV ratings.
These are used to step up and step down the voltage at Grid Stations.
Voltage ratings of power transformers installed in WAPDA power System are
500/220KV,220KV/132KV,132KV/11.5KV,132KV/66KV, 66KV/11KV, 132KV/11KV whereas
generated voltages of 6KV to 30KV are also stepped up, through power Transformers to EHV &
HV transmission levels at generating stations.
E= 4(1.11) Øm N f = 4.44 Øm N f
V1/V2 = N1/N2 = I2/I1 (RELATION OF TURNS RATIO WITH VOLTAGE & CURRENT RATIOS)
Following analogy holds between magnetic & electric circuits; (on next page)
Electric circuit Magnetic circuit
Electromotive force EMF Magneto motive force MMF=NI
Current, I Flux, Ø
Impedance, Z Reluctance (Ψ)
(iii) Breather:
As we know moisture weakens the dielectric strength of oil .Breather is filled with silicon gel or
other moisture absorbing compounds. The transformer exhales and in hales through the
breather when oil expands or contracts in main tank. Breather absorbs moisture and prevents it
to enter into transformer and mix with oil.
(iv) Thermometer:
Two temperature gauges are installed on transformer showing the oil and winding temperature.
Temperatures of Power Transformer are recorded on log sheet half hourly and those must not
increase beyond the maximum limits.
Bucholz relay is connected in between the main tank and conservator tank. It detects the incipient fault
inside the transformer. It is a very important protection of transformer which saves it from internal
faults.
(vi) H.V, L.V BUSHINGS AND ARC-GAP: External terminals of transformer are connected to
the windings inside the transformer H.V & L.V bushings provide insulation between terminals and top
plate transformer body. Arc Gaps or Arcing horns protect transformer from high voltage surges. The gap
between the forks of an Arc gap is adjustable. It is kept about 1CM/KV. It may vary depending upon
atmospheric conditions e.g. humidity & pollution in air.
(vii) TOP PLATE AND GASKETS: In main tank which is filled with transformer oil (Insulating Oil) core
and winding is immersed, top plate and gaskets seal the main tank.
(ix) FANS & PUMPS: Forced cooling is provided by fans and pumps. By fanning air incident on
transformers/tubes temperature of transformer is lowered. Pumps do the forceful speedy circulation of
oil enhancing the cooling rate.
The life of a transformer depends on the life of its insulation which in turn depends on the
temperature developed inside it. Increase in temperature results in deterioration of insulation.
The extent of over-load that a transformer can take depends upon various factors viz. The
winding or oil temperatures, surrounding air temperature. Duration of the over load in 24 hours,
and general loading conditions during the remaining day.
EFFECTS OF OVERLOADING
Overloading: As the load on a transformer is increased i.e. secondary current as well as primary
current increase resulting an increase in Power Losses in windings which are also called
as Cu losses and equal to I^2R Losses.
As the Cu-losses are directly proportional to square of current i.e. that if current is increased
twice, the Cu-losses are increased by 4 times as of the previous. The overloading increases
power losses inside a transformer and hence the temperature of power transformer is increased
affects the physical life time span of transformer.
Temperature rise also decides KVA rating of transformer. By lowering working temperature of a
transformer, its KVA/MVA capacity can be enhanced.
* By employing forced cooling i.e. fanning and pumping etc. The transformers capacity can be
increased.
e.g.
Cooling Mode Capacity of 1-phase, Auto Transformer
500KV/220KV at Gatti Grid Station NTDC
ONAN (Oil natural, Air Natural) 90MVA (oil immersed natural cooling)
ONAF (Oil natural, Air Forced) 120MVA (oil immersed forced air)
OFAF (Oil Forced, Air Forced) 150MVA (oil forced air forced)
TRANSFORMER LOSSES
There are two types of losses inside the Transformer:-
a) Cu-Losses
b) Core Losses
a) Cu-LOSSES
Power losses inside the windings of a transformer are called Cu-losses and equal to I^2R Losses.
These losses depends upon load and are proportional to square of the load current.
b) CORE LOSSES
Power losses in core are called Iron losses or core losses. These are independent of load. There
are further divided into:
–Eddy current losses
–Hysteretic losses
Relaying Time= Time start from when a relay circuit sense a fault current & up to closing of
the trip circuit of the circuit breaker.
Breaker Opening time = Time start from closing of the circuit breaker trip circuit to the
opening of the circuit breaker contacts.
Arching Time = Time start from opening of the contacts of the circuit breaker to the final arc
extinction.
• Duplicate Protection
Nowadays, relay schemes have backup relaying as such. The new standard to protect a power
system consists of two independent relay scheme where neither of them has intentional time
delay. In addition breaker failure protection is provided on all high voltage and some low
voltage breakers.
• Zone Protection: Power system is divided into zones which can be protected by a
specialized group of relays and which can also be separated from the rest of the system.
Z1 = in this zone 85 % area of protected line is included. In this zone tripping occurred
speedily.
Z2 = in this zone 50% area of next line is included.
CT CORES:
•There are different cores in a CT. metering core, over-current CT core, differential CT core
provided that if it is CT of power transformer.
•Metering core has 15VA burden.
•Over current core has 30 VA burden.
•Differential CT core has 60 VA burden.
The characteristics of protection core and metering core are different; have different designs
and cannot be interchanged with each other. When more fault current occurs then mechanical
system of meter pivot, jewel etc damages and hence metering core is made smaller and should
saturate earlier therefore. But protection
core should give exact replica of system
current at fault condition. So protection core
would saturate later.
CT Saturation:
CT saturation is point where the excitation
impendence collapses and whole of the
primary current is utilized in exciting the core
of CT i.e. the Ip becomes the Iexe and
secondary output of the CT out ceases. The
cause of CT saturation is fault current which flows on fault or if CT is opened accidentally at
secondary side. DC transients are present in the fault current which superimpose on AC quantity
having less time but high magnitude. These transients saturate the CT core.
Ankle Point:
Ankle point is a point where Ve and Ie are linear i.e. Ve and Ie are directly proportional.
Operating point of CT should be in linear portion.
Knee Point : It is a point where an increase of 10% in Vexc causes an increase of 50% in Iexc
and this is the point of saturation of CT. Measuring CT operates between zero and ankle point
and saturation level is low. Protection CT operates satisfactory up to knee point and saturation
level is high. Protection CT cannot be used instead of measuring CT and vice versa.
Numeric relays:
These relays are digital relays having two over current and one earth fault and three
instantaneous elements. These relays have a number of LED, s that indicates the fault. These
relays also record the fault / date and time. The plug setting and operating time can be adjusted
on operating panel given on the relay. These relays can be operated both on AC and DC. They
also indicate the load of each phase. This relay is now widely used in WAPDA.
DC SUPERVISION RELAY:
This relay supervise the trip circuit of C.breaker and brings up an alarm if the supply or
operation of mechanism is faulty.
This relay has three units a,b,c. In normal condition when breaker is in closed position “a” and
“c” units are picked up. If the trip circuit becomes open circuited or if the supply fails unit “a” is
no longer held picked up, contact opens causing “c” to drop out.
In open position unit “b” is supplied through breaker auxiliary contact NC and it detects the
control circuit in open position in similar way as “a” in closed position.
CT Burden (VA): Current transformer burden is defined as the load connected across its
secondary. ... The burden in a CT metering circuit is the largely resistive impedance presented to
its secondary winding. Typical burden ratings for IEC CTs are 1.5 VA, 3 VA, 5 VA, 10 VA, 15 VA,
20 VA, 30 VA, 45 VA and 60 VA.
Capacitor voltage transformer:
A capacitor voltage transformer (CVT or CCVT), is a transformer used in power systems to step
down extra high voltage signals and provide a low voltage signal, for metering or operating
a protective relay.
Other applications:
The CVT is also useful in communication systems. CVTs in combination with wave traps are used
for filtering high-frequency communication signals from power frequency. This forms a carrier
communication network throughout the transmission network, to communicate between
substations. The CVT is installed at a point after Lightning Arrester and before Wave trap.
What are the reasons that Over-current relays are not used for Long lengths but for
only short lengths (sub transmission/distribution) lines only?
We know that in transmission line LG, LLG, LLL fault takes place.
Fault impedance of different fault is follow like this LG>LLG>LLL
So LG fault has maximum impedance over other faults.
Suppose we set relay current setting such that it can protect 50% transmission line of LLG fault.
So relay will function accurately for LLG fault.
But for LG Fault (Impedance is high) relay is under reach i.e. it cannot provide protection to 50%
transmission line and able to protect only say 35% of transmission line.
For LLL Fault (Impedance is low compared to LLG) relay over reach i.e. it cannot provide
protection to 50% transmission line but able to protect only say 60% of transmission line.
So overcurrent relay will malfunction under such conditions.
And usually Long transmission line are EHV lines, so relay malfunction is threat to stability of
power system.
Inrush current of transformer: Inrush Current is a form of over current that occurs during
energisation of a transformer and is a large transient current which is caused by part cycle
saturation of the magnetic core of the transformer. For power transformers, the magnitude
of inrush current is initially 6 – 10 times the rated load current.
If turn-on occurs when the AC voltage wave is at its peak value, there will be no inrush
current drawn by the transformer.
Power Swing and its effect on Protection System:
Power swings refer to oscillation in active and reactive power flows on a transmission line
consequent to a large disturbance like a fault. The oscillation in the apparent power and bus
voltages is seen by the relay as an impedance swing on the R-X plane. If the impedance
trajectory enters a relay zone and if stays there for sufficiently long time, then the relay will
issue a trip decision on power swing. Tripping on power swings is not desirable.
A distance relay may classify power swing as a phase fault (L-G) if the impedance trajectory
enters operating characteristic of the relay.
Surge Impedance:
If the line is lossless, i.e. the resistance and conductance are zero, then the characteristic
impedance reduces to √ (L/C), a pure resistance. When dealing with high frequencies or with
surges due to lightening, losses are often neglected and surge impedance becomes important.
SIL is also called natural power of the line. Sometimes it is convenient to express the power
transmitted by a line in terms of per unit of SIL which is the ratio of the power transmitted to
the surge impedance loading.
The permissible loading of a transmission line may be expressed as a fraction of its SIL and SIL
provides a comparison of load carrying capabilities of lines.
Load encroachment:
Load encroachment occurs when the impedance crosses the loadability limit of the operating
characteristic. The loadability of an impedance relay is normally stated in MVA, at nominal
operating voltage and a specific power factor.
Three-Stepped Distance Relaying Scheme:
Distance relays are the preferred choice for the protection of High Voltage lines. In three
stepped distance protection, the relay is set for protection of line in three steps in different
zones with suitable time delay between each step for back up.
Shunt Reactor:
A shunt reactor is an absorber of reactive power, thus increasing the energy efficiency of the system. It
is the most compact device commonly used for reactive power compensation in long high-voltage
transmission lines and in cable systems. The shunt reactor can be directly connected to the power line
or to a tertiary winding of a three-winding transformer. The shunt reactor could be permanently
connected or switched via a circuit breaker. To improve the adjustment of the consumed reactive power
the reactor can also have a variable rating. If the load variation is slow, which it normally is (seasonal,
daily or hourly), a variable shunt reactor (VSR) could be an economical solution for some customer
applications.
Series reactors: Series reactors are used as current limiting reactors to increase the impedance of a
system. Such reactors are also used to limit the starting currents of synchronous electric motors and to
compensate reactive power in order to improve the transmission capacity of power lines.
PHASE SEQUENCE
It is the order or sequence in which the current or voltage in different phases attain their
maximum values. The phase sequence is usually denoted by R, Y, B or A, B, C or 1,2,3.
Inductive reactance
An opposition to current flow created by the inductance. This type of opposition is called
inductive reactance.
Or The effect of inductance is called inductive reactance. XL denotes it.
Capacitive reactance
In capacitor an opposition to the flow of current due to electrostatic field is called capacitive
reactance .It is denoted by Xc.
Impedance
It is the total opposition to the flow of current .It is denoted by Z.
Phase angle.
The angular separation between current and voltage is called phase angle.
Apparent power
It is the product of current and voltage. It is expressed in VA, KVA, and MVA.
True power
It is the watt of an A.C circuit. It is the product of current, voltage and cosine of the phase angle.
It is expressed in W, KW, and MW.
Reactive power
It is the magnetizing power of an A.C circuit. It gives rise to phase angle. It is expressed in
KVAR.
Types of isolator
Horizontal break (center break) 220 / 132 kV
Vertical break (side break) 500 kV
Interlocking of isolator
1- Electrical interlocking with breaker
The isolator cannot be open when the breaker is closed.
2-Mechanical interlocking: This system is used in hand operated mechanism.
3-Interlocking of earth switch with isolator: The earth switch cannot be close yet isolator is
open.
WAVE TRAP OR LMU
This equipment is installed at the grid station for telecom purpose. Usually it is installed at end
of line before line isolator on one or more phases. It is a combination of number of capacitors
that reduces the voltage for telecom purpose (PLC). It is filled with oil. Some time it is also used
for tripping purpose.
SHUNT REACTOR
This equipment is installed on very high voltage transmission lines like 500kv in parallel. It is an
inductive load and used to ground extra voltage of long 500kv lines generated due to
capacitance. Its one end is connected to line and other is grounded.
Shunt reactor reduces the extra voltage according to its capacity. It is used on 200 km or 250
km longer lines at one end or both ends .one unit is used for each phase and three units make a set.
Its capacity is in MVAR.
Laying of earthling mesh in GRID Station:
The earthling mesh is laid in the ground up to depth of 3 ft. .A 3 ft long copper rod is pierce into ground
up to the wet soil. If wet soil is at more depth then long copper rods up to twenty meters may be used.
Tap changer:
Tap changer is used to increase / decrease voltage. In power transformer on load tap
changer is mostly used. It is usually installed on primary side.
Tap changer is used to step up or step down system voltage with variation of load. This is
installed usually on primary side, as load on primary side is less then secondary.
Types of tap changer
1- On load tap changer
The tap position of this tap changer can be changed on load. This tap changer is used in power
transformer.
2- Off load tap changer
The tap position of this transformer cannot be changed on load position. It can be changed by
switching off the transformer. This type of tap changer is used in distribution transformer.
Operation of tap changer
1- Automatic
In this method required voltage are adjusted on voltage regulator, which automatically changes
the tap position.
2- Remote
Tap position can also be changed from control panel in the control room. The position
Indicator indicates the tap position of power transformer.
3- Manual
If tap position cannot be changed by remote operation due to any fault. It can be changed by
hand using handle provided by manufacturer.
Parts of tap changer
Tap changer consists of following parts; -
1- Selector switches 2- Diverter switch
3- Reversing switch 4- Motor drive unit.
1- Selector switch
Its function is to select required tap. It has some moving and fixed contacts. The leads from tap
winding which is 10 % of main winding are joined with the contacts of selector switch.
2- Diverter switch
This switch is fixed in main winding in a separate tank .It provides the path for current from one
tap to another. This switch is dipped in oil. Due to sparking this oil must be tested as per routine
maintenance and this sparking may also damage main winding. Therefore it is mounted in a
separate tank.
3- Reversing switch
The function of this switch is to reverse the polarity of winding. This switch is attached with
selector switch.
4- Motor drive unit
This unit is used to operate the whole parts of tap changer. All above parts are attached
together with a shaft or gearbox, which is coupled with the pulley of a three-phase motor.
This motor is attached with main shaft either with gearbox or belt. If a gearbox is provided in the drive
unit lubricate it with special Mobile oil.
The electrical bus bar is available in rectangular, cross-sectional, round and many other shapes. The
rectangular bus bar is mostly used in the power system. The copper and aluminium are used for the
manufacturing of the electrical bus bar.
The various types of busbar arrangement are used in the power system. The selection of the bus bar is
depended on the different factor likes reliability, flexibility, cost etc. The following are the electrical
considerations governing the selection of any one particular arrangement.
The small substation where continuity of the supply is not essential uses the single bus bar. But in a large
substation, the additional busbar is used in the system so that the interruption does not occur in their
supply. The different type of electrical busbar arrangement is shown in the figure below.
The only disadvantage of such type of arrangement is that the complete supply is disturbed on the
occurrence of the fault.
The arrangement provides the less flexibility and hence used in the small substation where continuity of
supply is not essential.
The faulty section is removed without affecting the continuity of the supply.
The maintenance of the individual section can be done without disturbing the system supply.
The system has a current limiting reactor which decreases the occurrence of the fault.
The system uses the additional circuit breaker and isolator which increases the cost of the system.
Main and Transfer Bus Arrangement
Such type of arrangement uses two type of busbar namely, main busbar and the auxiliary bus bar. The
busbar arrangement uses bus coupler which connects the isolating switches and circuit breaker to the
busbar. The bus coupler is also used for transferring the load from one bus to another in case of
overloading. The following are the steps of transferring the load from one bus to another.
1. The potential of both the bus bar kept same by closing the bus coupler.
2. The bus bar on which the load is transferred is kept close.
3. Open the main bus bar
Thus, the load is transferred from the main bus
to reserve bus.
Advantages of Main & Transfer Bus
Arrangement:
In such type of arrangements, two bus bars are used which increases the cost of the system.
The fault on any of the bus would cause the complete shutdown on the whole substation.
Double Bus Double Breaker Arrangement
This type of arrangement requires two bus bar and two circuit breakers. It does not require any
additional equipment like bus coupler and switch.
Disadvantages of One and a Half Breaker Arrangement: The circuit becomes complicated because of
the relaying system and their maintenance cost is very high.
Ring Main Arrangement: In such type of arrangement, the end of the bus bar is connected back to the
starting point of the bus to form a ring.
National Transmission & Dispatch Company (NTDC) was incorporated on 6th November, 1998 and
commenced commercial operation on 24th December, 1998. It was organized to take over all the
properties, rights and assets obligations and liabilities of 220 KV and 500KV Grid Stations and
Transmission Lines/Network owned by Pakistan Water and Power Development Authority
(WAPDA). NTDC operates and maintains sixteen 500 KV and forty three 220 KV Grid Stations, 5893 km
of 500 KV transmission line and 10963 km of 220 KV transmission line in Pakistan.
MAIN FUNCTIONS
System Operator
i) System Operator: For secure, safe and reliable operation, control and dispatch of generation facilities.
ii) Transmission Network Operator: For Operation & Maintenance, Planning, Design and expansion of
the 500 kV and 220 kV transmission network.
iii) Contract Registrar and Power Exchange Administrator (CRPEA): As CRPEA, to record and monitor
contracts relating to bilateral trading system.
(i) settlement, (ii) power procurement on behalf of DISCOs, (iii) finance, (iv) legal and corporate affairs,
(v) strategy and market development, (vi) monitoring and coordination. The support functions include
(vii) human resource management and (viii) information technology.
The main tasks performed by the company are as follows:
Vision: "To become a world-class power market operator by providing the optimum environment for
trading electricity in the Pakistani power market"
National Power Control Center (NPCC) was established in 1985 in Islamabad to control 500kV and 220kV
transmission system throughout the country but with the passage of time, most of the equipment has
become obsolete and its capacity is not sufficient to control expanding power grid system and require
up-gradation.
Project Summary
This project is aimed at Modernization & Up-gradation of Load Dispatch Center at National Power
Control Center (NPCC) Islamabad by converting it from current analogue system to digital system. Main
components include Digital Processing System (DPS), Supervisory Control & Data Acquisition (SCADA),
Energy Management Sysetm (EMS), 8 Remote Terminal Units (RTUs), and telecom system: Optical Fiber
Ground Wire (OPGW), equipment for 8 Regional Control Centers (RCCs).
Project Highlights
Under this project, Data Processing System is being up-graded by installing latest servers, workstations
and Local Area Network to ensure proper functioning of SCADA for real time power network operation,
EMS for automated frequency control, load forecast, unit commitment, economic dispatch, optimal
power flow etc. Remote terminal units are also being installed at all 500kV & 220kV substations, all
GENCO thermal power stations and some WAPDA owned hydropower stations. In telecommunication
system, the backbone telecommunication system is being replaced by laying OPGW (Optical fibers
ground wires) on existing 500, 220 and 132 kV transmission lines. The existing NTDC’s old telephone
system will be replaced by a new system to meet the requirements of traffic, quality, redundancy and
reliability. For RCCs, painted mimic boards with hotline telephone link with NPCC are being provided in
this project.
The strategy going to be adopted by NEECA for promoting energy efficiency and conservation shall
cover whole spectrum of activities starting from identification of energy efficiency and conservation
opportunities and including technology demonstration, undertaking pilot projects, information and
outreach, training and education, and development of plans and policies for promoting mitigation,
energy efficiency and conservation best practices.
Private Power and Infrastructure Board (PPIB): It was created in 1994 as a "One-Window
Facilitator" on behalf of the Government of Pakistan (GOP) to promote private investments in
power sector. In 2012 PPIB was made a statutory organization through Private Power and
Infrastructure Board Act 2012 (Act VI of 2012). The role of PPIB has been further expanded by
the GOP (Govt of Pakistan) by allowing it to facilitate public sector power and related
infrastructure projects in IPP mode, for which PPIB's Act has been amended in November
2015. PPIB approves IPPs, issues LOIs & LOSs (including Tripartite LOSs), approves Feasibility
Studies, executes Implementation Agreements (IAs) and provides GOP guarantees.
NESPAK (National Engineering Services Pakistan):
NESPAK enjoys the reputation of being one of the top engineering consultancy organizations in Asia and
Africa. NESPAK was established in 1973 as a private limited company by the Government of Pakistan.
The objective of its creation was to create a pool of talented engineers, attain self-reliance in
engineering consultancy and replace foreign consultants. Currently, NESPAK has total strength of over
5100 employees, 3490 completed projects and 381 ongoing projects.
The Total estimated turnover for the year 2016-2017 is Rs. 8.8 Billion with the total cumulative cost of
the projects undertaken by NESPAK is US $ 288 Billion.
CASA (Central Asia, South Asia) : (1.16 billion $ project)
High voltage direct current (HVDC) converter stations will also be included as part of the project, as well
as a 477 kilometer long, 500 kilovolt alternating current transmission line between Datka, Kyrgyzstan
and Khujand, Tajikistan. A 1,300 MW AC/DC converter station will be constructed in the city of
Sangtuda, Tajikistan, as well as a 300 MW converter station in Kabul, Afghanistan. A 750km HVDV line
will be constructed between Sangtuda, and the city of Peshawar, Pakistan, via the Salang Pass and
Kabul. In Peshawar, a 1,300 MW converter station will be built and connected to Pakistan's electric grid
> Transmission lines are designed to transmit 1,300 MW of electricity, with Afghanistan allotted 300
MW of electricity and Pakistan 1000 MW of electricity. Initially, however, Pakistan will receive 700 MW,
while Afghanistan will be supplied 300 MW. Due to lack of power, Afghanistan will not be provided with
300 Mw. All 1300MW will be delivered to Pakistan now.
o WAPDA is now fully responsible for the development of Hydel Power and Water Sector Projects.
o PEPCO has been fully empowered and is responsible for the management of all the affairs of
corporatized nine Distribution Companies (DISCOs), four Generation Companies (GENCOs) and
a National Transmission Dispatch Company (NTDC). These companies are working under
independent Board of Directors (Chairman and some Directors are from Private Sectors).
o The Companies are administratively autonomous and leading to financial autonomy by
restructuring their balance sheets by bringing their equity position to at least 20 percent,
required to meet the prudential regulations and to facilitate financing from commercial sector
(approved by ECC).
o The Loan Liability Transfer Agreements (LLTA) has been signed with Corporate Entities and
execution of loan transfer is complete.
o All Entities have the physical possessions of all their operational assets.
o On 24th Feb. 2007 Ministry of Water & Power notified NEPRA approved Tariff for all Distribution
Companies replacing unified WAPDA Tariff.
o Regulatory instruments like Grid Code, Distribution Codes, Performance Standard for
Distribution Companies and Transmission Companies were drafted and got approved from
(www.nepra.org.pk) in 2007.
o All major lenders gave their consent for transfer of their loan from WAPDA to Corporate Entities,
thus 326 loan assumption agreements were signed amongst respective Companies, WAPDA and
EAD (Economic Affairs Division) GOP.
o CPPA is established under the coverage of NTDC for payments from DISCOs to IPPs, GENCOs and
NTDC. Ultimately, it will function independently under Federal Govt. and all forthcoming IPPs
will be under CPPA.
The Charter of Duties of WAPDA is to investigate, plan and execute schemes for the following fields:
o Flood Management.
o Inland Navigation.
The Authority comprises of a Chairman and three (3) Members working through a Secretary.
WAPDA is one of the largest employers of human resources in Pakistan. Over the years WAPDA has
built-up a reservoir of Technical know-how and expertise which has made it a modern and progressive
organization.
To achieve energy autarky in Pakistan, the country needs massive investment in power
generation and associated infrastructure. The vision statement of National Energy Policy
2013 outlines that: “Pakistan will develop the most efficient and consumer-centric
power generation, transmission, and distribution system that meets the needs of its
population and boosts its economy in a sustainable and affordable manner.”
In line with its policy, the Government of Pakistan took an unprecedented initiative to
inject 2400 MW into the national system through its own resources. National Power
Parks Management Company Private Limited was established and entrusted with the
task to give shape to this resolve of the Government under the auspices of Ministry of
Water & Power. The company immediately took up the task and now is in the Process of
establishing two state of the art Re-gasified Liquid Natural Gas (RLNG) based Combined
Cycle Power Plants; 1223 MW CCPP at Balloki, District Kasur and 1230 MW CCPP at
Haveli Bahadur Shah, Jhang. These state of the art plants are providing cheap electricity
to the national grid owing to their unparalleled latest technology and high efficiency.
Engineering Procurement & Construction (EPC) contracts for both the projects were
awarded in the last quarter of 2015 and Operation and Maintenance (O &M) contracts
for both plants were awarded within 18 month of ground breaking.Haveli Bahadur Shah
began combined cycle commercial operations on 9th May, 2018 and Balloki achieved
Combined cycle COD on July 29th 2018.The company has its offices in Lahore and
Islamabad.
Water Apportionment Accord (WAA) was signed amongst the Provinces on 16.03.1991
and approved by the Council of Common Interests (CCI) on 21.03.1991. Under Clause 13
of the WAA ’91, the need to establish an Indus River System Authority was recognized
and accepted for the implementation of the Accord. The Authority would have its HQs
at Lahore (shifted to Islamabad) and having representation from all the Provinces. IRSA
was established for regulating and monitoring the distribution of water sources of Indus
Rivers in accordance with the Accord amongst the Provinces and to provide matters
connected therewith and ancillary thereto. IRSA was established vide Act No. XXII of
1992 passed by the Parliament and approved by the President of Pakistan on, the 6th
December 1992.
Pakistan Power Park Management Company Limited (PPPMCL) : Comes under Ministry of Water
and Power Government of Pakistan .
SCADA: SCADA stands for supervisory control and data acquisition. It is a type of software
application program for process control. SCADA is a central control system which consist of
controllers network interfaces, input/output, communication equipments and software.
SCADA systems are used to monitor and control the equipments in the industrial process
which include manufacturing, production, development and fabrication. The infrastructural
processes include gas and oil distribution, electrical power, water distribution. Public utilities
include bus traffic system, airport. The SCADA system takes the reading of the meters and
checks the status of sensors in regular interval so that it requires minimal interference of
human. A large number of processes occur in large industrial establishment. Every process you
need to monitor is very complex because each machine gives different output. The SCADA
system used to gather the data from sensors and instruments located at remote area. The
computer then processes this data and presents in a timely manner. The SCADA system
gathers the information (like leak on a pipeline occurred) and transfer the information back to
the system while giving the alerts that leakage has occurred and displays the information in a
logical and organized fashion. The SCADA system used to run on DOS and UNIX operating
systems.
On-Load Tap-Changing Transformer: (in explained way)
Definition: The transformer which is not disconnected from the main supply when the tap
setting is to be changed such type of transformer in known as on-load tap changing transformer.
The tap setting arrangement is mainly used for changing the turn ratio of the transformer to
regulate the system voltage while the transformer is delivering the load. The main feature of an
on-load tap changer is that during its operation the main circuit of the switch should not be
opened. Thus, no part of the switch should get the short circuit.
In tap changing transformer different types of an impedance circuit are used for limiting the
current during the operation of a tap changing. The impedance circuit may be resistor or reactor
type, and by the impedance circuit, the tap changer can be classified as the resistor and reactor
type. Nowadays the current limiting is carried out by using a pair of resistors.
Difference between power transformer and auto transformer:
In an autotransformer, portions of the same winding act as both the primary and secondary
sides of the transformer. In contrast, an ordinary transformer has separate primary and
secondary windings which are not electrically connected. The winding has at least three taps
where electrical connections are made.
An autotransformer can also be used to step the supply voltage up or down by reversing the
connections. The autotransformer has many uses and applications including the starting of
induction motors, used to regulate the voltage of transmission lines, and can be used to
transform voltages when the primary to secondary ratio is close to unity.
Prepared by :
Engr. Mehran Marwat
What is the use of wave trap?
Wave Traps are used at sub-stations using Power Line Carrier Communication (PLCC). PLCC is used to
transmit communication and control information at a high frequency over the power lines. This reduces
need for a separate infra for communication between sub-stations.
There are three basic types of current transformers: wound, toroidal and bar.
Wound Current Transformer – The transformers primary winding is physically connected in series
with the conductor that carries the measured current flowing in the circuit. The magnitude of the
secondary current is dependent on the turns ratio of the transformer.
Toroidal Current Transformer – These do not contain a primary winding. Instead, the line that
carries the current flowing in the network is threaded through a window or hole in the toroidal
transformer. Some current transformers have a “split core” which allows it to be opened,
installed, and closed, without disconnecting the circuit to which they are attached.
Bar-type Current Transformer – This type of current transformer uses the actual cable or bus-bar
of the main circuit as the primary winding, which is equivalent to a single turn. They are fully
insulated from the high operating voltage of the system and are usually bolted to the current
carrying device.
Characteristics
Characteristics
A 300/500 mA RCCB may be used where only fire protection is required. eg., on lighting circuits,
where the risk of electric shock is small.
Litz wire:
Litz wire is a type of specialized multistrand wire or cable used in electronics to carry alternating current
(AC) at radio frequencies. The wire is designed to reduce the skin effect and proximity effect losses in
conductors used at frequencies up to about 1 MHz.
Ceiling fan uses a single phase induction motor to run it. That’s why; P.f of a ceiling fan is lagging. To
overcome this drawback, a capacitor is used. It is connected across a part of the winding in the
fan motor. This creates a phase difference between the windings (one part with the capacitor connected
and other part without the capacitor).
Transformer Types:
As per construction, transformers are classified as,
1. Core type
2. Shell type
3. Berry type: These types of transformer are generally kept in tightly fitted sheet metal tanks. The tanks
are constructed of specific high quality steel plate cut formed and welded into the rigid structures. The
tanks are filled with the special insulating oil. The entire transformer assembly is immersed in the oil.
The oil served two functions, keep the coils cool by circulation and provides the transformers an
additional insulation
Difference: One of the major difference between the core type and the shell type transformers
is that in core type transformer, the winding encircles the core (P & S windings wrapped
around each side leg), whereas, in shell type transformer, the core encircles the winding of the
transformer ( windings wrapped around the center leg).
1. Core Type: The H.V. & L.V. both are placed on same limb
concentrically. L.V. is placed near to core.
It’s also known that 230 V AC is 325 volts peak, 650 peak to peak. So an AC supply can actually
apply greater voltage than 230 volts DC.
Renewable Energy
There are many forms of renewable energy. Most of these renewable energies depend in one
way or another on sunlight. Wind and hydroelectric power are the direct result of differential
heating of the Earth's surface which leads to air moving about (wind) and precipitation forming
as the air is lifted. Solar energy is the direct conversion of sunlight using panels or collectors.
Biomass energy is stored sunlight contained in plants. Other renewable energies that do not
depend on sunlight are geothermal energy, which is a result of radioactive decay in the crust
combined with the original heat of accreting the Earth, and tidal energy, which is a conversion of
gravitational energy.
Difference
between
Manual
Switch and smart switch (home automation):
The Manual Switch block is a toggle switch that selects one of its two inputs to pass through
to the output.
A smart switch is still a light switch, but with advanced features that help automate your home.
They resemble traditional switches and plug into the same spaces that traditional outlets are
found, except:
1. They have radio wave capabilities that allow the switches to connect to a nearby wireless
network and become part of the Internet of Things. This makes the devices “smart” and gives
them an array of capabilities, including app or voice control.
2. Their design tends to be a bit more complicated. Some may have extra buttons for more specific
light control, while others may come with additional sensors or light indicators.
A Stock bridge damper is a tuned mass damper used to suppress wind-induced vibrations on
slender structures such as overhead power lines . The dumbbell-shaped device consists of two
masses at the ends of a short length of cable or flexible rod, which is clamped at its middle to
the main cable. The damper is designed to dissipate the energy of oscillations in the main cable
to an acceptable level. Its distinctive shape gives it the nickname "dog-bone damper".
How the relays know to trip the circuit? (Due to electromagnet (heart) of the relay)
Relay Design: A relay is an electromagnetic switch that is used to turn on and turn off a circuit
by a low power signal, or where several circuits must be controlled by one signal.
There are only four main parts in a relay. They are
Electromagnet
Movable Armature
Switch point contacts
Spring
When current starts flowing through the control coil (wrapped around electromagnet),
the electromagnet starts energizing and thus intensifies the magnetic field. Thus the upper
contact arm starts to be attracted to the lower fixed arm and thus closes the contacts causing a short
circuit for the power to the load. On the other hand, if the relay was already de-energized when the
contacts were closed, then the contact move oppositely and make an open circuit.
The portion above the top cross arm is called peak of transmission
tower. Generally earth shield wire connected to the tip of this
peak.
Cross arms of transmission tower hold the transmission conductor. The dimension of cross arm depends
on the level of transmission voltage, configuration and minimum forming angle for stress distribution.
The portion between tower body and peak is known as cage of transmission tower. This portion of the
tower holds the cross arms.
The portion from bottom cross arms up to the ground level is called
transmission tower body. This portion of the tower plays a vital role for
maintaining required ground clearance of the bottom conductor of the
transmission line.
The minimum ground clearance of the lowest conductor point above the ground level.
The minimum clearance to be maintained between conductors and between conductor and
tower.
The mid span clearance required from considerations of the dynamic behavior of conductor and
lightening protection of the line.
To determine the actual transmission tower height by considering the above points, we have
divided the total height of tower in four parts,
According to different considerations, there are different types of transmission towers. The transmission
line goes as per available corridors. Due to unavailability of shortest distance straight corridor
transmission line has to deviate from its straight way when obstruction comes. In total length of a long
transmission line there may be several deviation points. According to the angle of deviation there are
four types of transmission tower,
As per the force applied by the conductor on the cross arms, the transmission towers can be
categorized in another way-
2. Angle tower or tension tower or sometime it is called section tower. All B, C and D types of
transmission towers come under this category.
Apart from the above customized type of tower, the tower is designed to meet special usages
listed below, these are called special type towers,
3. Transposition tower
Transmission towers relay electric current, and come in several major types.
To keep up with the world's trend towards a cleaner, greener future Pakistan needs to invest heavily in
Solar, wind, tidal, and Biomass energy.
Biomass: Being an agricultural economy Pakistan has a huge potential in leading the Biomass
Energy revolution. Pakistan has about 26,000,000 hectares of agricultural land which produces
wheat straw, rice straw, cane husks, cotton stalks, bagasse and other plant residue as a
byproduct which can be used as bio fuel. Animal manure produced by the 67,000,000 cattle and
municipal solid waste produced by sprawling major cities, is a very good bio fuel for energy
production at low costs. Currently there is little to no work being done in Pakistan towards a bio
energy powered future.
Tidal: Pakistan has a coastline which is 1,045 km-long and is ripe for harnessing tidal wave
energy. The Indus river delta in Sindh which is 170 km-long has a vast amount of potential to be
used for production of electricity from tidal energy. Currently there is no work being done on
harnessing tidal wave energy in Pakistan and there are no plans for this in the near future.
Wind : The government of Pakistan with assistance of China, has implemented wind power
energy generation plants in areas such as Bin Qasim, Keti Bandar, Jhimpir and Gharo where
electricity production has been a problem before.
Punjab on the other hand, being the most populous province of Pakistan with 111,000,000
residents does not have a single operational wind farm to date.
Pakistan has a mind blowing potential to produce 50,000 megawatts of energy using wind
power alone as reported by the Pakistan meteorological department.
Solar: Last, but maybe the most important production method of clean renewable energy with
the highest potential in Pakistan. With the prices dropping at an exponential rate for the
production of solar panels, it is ripe time that Pakistan dips its toes into solar power production
and doubles down on renewable energy investments. To date, Pakistan is producing 2000 MW
of solar energy from two Photovoltaic installations, whereas the total potential of Pakistan is
close to 10 GW.
Thal, Kharan, Thar and Cholistan deserts are vast areas of unused land where sunlight shines for
approximately 8.5 hours throughout the day and 300 days of consistent sunshine throughout
the year, giving an average solar irradiance of 5.3 kwh/m²/day which puts Pakistan in the top
50 Solar Insolation Nations as reported by the NASA Surface Meteorology and Solar Energy (SSE)
Data.
Quaid-E-Azam Solar Park : The flagship solar installation of Pakistan which was supposed to
reach a fully operational capacity of 1 GW in 2017 has been struggling to maintain an output of
100 GW as of 2018. Like every other government project in Pakistan, this project has been facing
delays due to operational difficulties, corruption, tariff conflicts and plans of privatization. The
project which had a cost $131 million has been behind its completion date by a year and will be
delayed for the upcoming few years due to the ongoing corruption probe by the NAB.
What is the main difference between surge impedance and characteristics impedance of a
transmission line?
In a power system network the characteristics impedance is given by the ratio of square root of series
impedance of transmission line (Z) to the shunt admittance of transmission line(Y).
Characteristics impedance = sq rt(Z/Y).
Z=R+jX , Y=G+jB
The characteristics impedance is calculated for the transmission line with losses.
The term Surge impedance is reserved for the special case of loss less line.
For the loss less line the resistance(R) and conductance(G) are zero.
Now the characteristics impedance of the transmission line is reduced to pure resistance in terms of
dimensions. Surge impedance = sqrt(L/C)
where, L -> inductance of transmission line
C ->capacitance of transmission line.
What type of connection is used at transformers used at generation side and distribution side
(start, delta)? Why?
Generator side: The transformers are generally step up transformers with LV winding (i.e. primary)
connected in Delta and HV winding (i.e. secondary) connected in Star.
The advantages of using transformer's primary in delta are:
1) The line current gets divided by √3 and hence the cross-sectional area of the conductor to be used in
each of the three phases of the primary winding will be reduced. Thus saving in copper.
2) Delta connection provides a path for the third order harmonic current and hence no distortion
because of it.
The advantage of using transformer's secondary in star is:
1) On the secondary side, the line voltage is high and thus using star connection, the phase voltage will
be 1/√3 times line voltage. Thus the cost of insulation is saved. Also, the cost of insulation throughout
the transmission line is reduced.
Distribution Side: The transformers in distribution side are step down transformers. The HV winding is
connected to source and LV winding is connected to load. Here the LV winding (i.e. secondary) is always
star connected to provide a neutral point to consumers by which 3-phase can be converted to 1-phase.
The HV winding (i.e. primary) may be delta or star based upon the KVA rating of transformers and
economical aspects of insulation and cross-sectional area of conductor to be used.
From phaser diagram it is clear that primary current Ip is not exactly equal to the secondary current
multiplied by turns ratio, i.e. KTIs. This difference is due to the primary current is contributed by the core
excitation current. The error in current transformer introduced due to this difference is called current
error of CT or sometimes ratio error in current transformer.
For an ideal CT, the angle between the primary and reversed secondary current vector
is zero. But for an actual CT there is always a difference in phase between two
currents due to the fact that primary current has to supply the component of the
exiting current. The angle between the above two phases in termed as phase angle
error in current transformer or CT. Here in the pharos diagram it is β the phase
angle error is usually expressed in minutes.
It is desirable to reduce these errors, for better performance. For achieving minimum error in current
transformer, one can follow the following,
1. Using a core of high permeability and low hysteresis loss magnetic materials.
2. Keeping the rated burden to the nearer value of the actual burden.
3. Ensuring minimum length of flux path and increasing cross-sectional area of the core, minimizing
joint of the core.
Reflection coefficient: The reflection coefficient is a parameter that describes how much of an
electromagnetic wave is reflected by an impedance discontinuity in the transmission medium.
The reflection coefficient is a very useful quality when determining VSWR or investigating the
match between, for example, a feeder and a load.
Reflection coefficient is a parameter closely associated with VSWR indicating the portion of the
signal that is reflected at the end of a feeder, etc.
Where do we use the Fourier, Laplace and Z transforms, and why? What are the differences
among them?
Laplace transform: A mathematical transformation from one domain to another. A time domain
analog signal is transformed to the Laplace domain by using a kernel, e^(−st), where t stands for
time and s is a complex number further represented as: s=σ+jω. As defined, the s-plane is a 2D
plane with a real and imaginary axis.
Fourier transform: The kernel for the Fourier transform is : e^(−jω).It is a special case of the
Laplace transform evaluated along the imaginary axis.
Z transform: This is the most useful since it is a digitization of the Laplace transform, and in
reality all DSP chips work with digital signals. Conformal mapping yields: z=e^s = e^ (σ+jω). This
mapping maps the imaginary axis of the s-plane to the unit circle on the z-plane. DC (ω=0) maps
to z = (1,0) and Nyquist (ω=π) maps to z = (-1,0).
Discrete Fourier Transform: Special case of the Z-transform, evaluated at discrete points along
the unit circle (just like Fourier transform was a special case of the Laplace transform evaluated
on the imaginary axis).
What causes galloping power lines? The most common cause of galloping lines is ice
that builds up on one side of a power line as a result of strong winds. Storms at any time
of the year can pack damaging winds, which can knock down power lines and blow trees
and limbs on to power lines, which can cause power outages.
The conductors of transmission lines are subjected to a variety of motions caused by the wind.
The most common motions are Aeolian vibration, sub-conductor oscillation (bundled
conductors), galloping (generally associated with a light ice coating) and wind sway. Unless
controlled, motions of conductors can produce damage to the conductor and other elements of
the transmission system that will negatively affect the reliability and serviceability of the system.
Sub-conductor oscillations, galloping and wind sway are associated with higher wind velocities,
and in the case of galloping a light to moderate ice coating is required to initiate the motion.
These motions are generally characterized as low frequency, high amplitude. Aeolian vibration,
which is the subject of this paper, is associated with smooth (non-turbulent) winds in the range
of 2 MPH to 15 MPH, and can occur on a daily basis. In contrast to galloping and sub-conductor
oscillations, Aeolian vibration is characterized as high frequency, low amplitude motion.
Demand: 12300MW
Generation: 14000MW
DISCO, S are drawing only: 11500MW (They are taking 11500MW only from NTDC)
Shortfall: 800MW
Generation Capacity: 28000MW
Transmission Capacity: Upto 22000MW
DISCO,S are drawing only 11500MW (hydel:2762MW ,GENCO,S: 1421MW, IPPs: 7160MW ,
nuclear: 951MW and the shortfall of 800MW is due to load shedding by DISCO,s advisedly in
those areas where people don't pay the bill. The less demand is due to the winters only, as in
summer, demand increased upto 24000/25000MW and generation was 20500MW due to the
old infrastructure of DISCO,s. So was shortfall of 4500MW. By the way installed capacity of
Pakistan is 28000MW. Pakistan is going to export 1000MW to Tajikistan and Afghanistan in
winter, 2018 currently, says Express Tribune and DAWN.
Energy Mix:
Hydel: 29% , Nuclear: 4.5% , Thermal: 65.5% Others (Solar,Wind,etc): 1%
Shut
Reactor
compensation at the receiving end might help to reduce the effect of Ferranti Effect. Shunt
Reactor absorbs the excess reactive power generation during no load / light load condition and
thus helps in stabilizing the voltage of Transmission Line.
Geothermal:
Most power plants need steam to generate electricity. The steam rotates a turbine that
activates a generator, which produces electricity. Many power plants still use fossil fuels to boil
water for steam. Geothermal power plants, however, use steam produced from reservoirs of
hot water found a couple of miles or more below the Earth's surface. There are three types of
geothermal power plants: dry steam, flash steam, and binary cycle
Dry steam power plants draw from underground resources of steam. The steam is piped
directly from underground wells to the power plant, where it is directed into a
turbine/generator unit. There are only two known underground resources of steam in the
United States: The Geysers in northern California and Yellowstone National Park in Wyoming,
where there's a well-known geyser called Old Faithful. Since Yellowstone is protected from
development, the only dry steam plants in the country are at The Geysers.
Flash steam power plants are the most common. They use geothermal reservoirs of water with
temperatures greater than 360°F (182°C). This very hot water flows up through wells in the
ground under its own pressure. As it flows upward, the pressure decreases and some of the hot
water boils into steam. The steam is then separated from the water and used to power a
turbine/generator. Any leftover water and condensed steam are injected back into the
reservoir, making this a sustainable resource.
Binary cycle power plants operate on water at lower temperatures of about 225°-360°F (107°-
182°C). These plants use the heat from the hot water to boil a working fluid, usually an organic
compound with a low boiling point. The working fluid is vaporized in a heat exchanger and used
to turn a turbine. The water is then injected back into the ground to be reheated. The water and
the working fluid are kept separated during the whole process, so there are little or no air
emissions.
It also has higher overloading capacity under emergency conditions. XLPE Cables are ideal for
transmission and distribution of power because it has high
corrosion resistance under polluted atmosphere along with better resistance power against
chemicals and corrosive alkalis. Not only this, it can withstand vibration and hot impacts. It also
has 100 times more moisture resistance capacity compared to PVC. XLPE cables are used from
low voltage (600/1000 V) to 132 kV applications.
PVC Cables:
PVC (Polyvinyl chloride) is widely used in electrical cable construction for insulation, bedding and
sheathing. It was the 1950s when PVC started to replace rubber insulated and sheathed cables
in general household wiring due to its ease of processing. PVC is cost-effective and also has
excellent ageing properties and typically exceeds a 25 to 30 year service life.
It’s considered to be one of the most versatile of the common thermoplastics due to the fact
that its properties can be easily modified - although PVC is inherently hard and rigid it is easily
modified with plasticizers, stabilizers, lubricants and various other ingredients .
Cable with a PVC insulation or sheathing is flame retardant, which is an important consideration
for electric cables in most applications. PVC can be made resistant to a wide range of chemicals
including oils, acids and alkalis, and is tough, durable and resistant to abrasion. The addition of
various additives can improve its temperature range, typically from -40 to 105°C, as well as the
resistance to sunlight, reduced smoke emission and improved water resistance.
Voltage: 6350/11000v as main power distribution cable
Power sent from sending end - line losses = Power delivered at receiving end.
Extra High Voltage 110 kV, 132 kV, 220 kV, 400 kV
Ultra-High Voltage 765kV
High Voltage Direct Current ±500kV
Tower Spotting
NORMAL SPAN:
It is the design span
ACTUAL SPAN:
It is the actual distance between two adjacent towers
NULL POINT:
It is a point in a span where the position of the conductor is lowest (or) it is a point in a span where the
sag is maximum.
WEIGHT SPAN:
The distance between two adjacent null points
WIND SPAN:
It is the distance between two center points of adjacent spans.
Post insulator
Post insulator is more or less similar to Pin insulator, but former is suitable for
higher voltage application. Post insulator has higher numbers of petticoats and
has greater height. We can mount this type of insulator on supporting structure
horizontally as well as vertically. The insulator is made of one piece of porcelain
and it has clamp arrangement are in both top and bottom end for fixing.
Suspension Insulator:
In higher voltage, beyond 33KV, it becomes uneconomical to use pin insulator because size,
weight of the insulator become more. Handling and replacing bigger size single unit insulator are
quite difficult task. For overcoming these difficulties, suspension insulator was developed.
In suspension insulator numbers of insulators are connected in series to form a string and the
line conductor is carried by the bottom most insulator. Each insulator of a suspension string is
called disc insulator because of their disc like shape.
Advantages of Suspension Insulator
1. Each suspension disc is designed for normal voltage rating 11KV (Higher
voltage rating 15KV), so by using different no. of discs, a suspension string
can be made suitable for any voltage level.
2. If any one of the disc insulators in a suspension string is damaged, it can be
replaced easily.
3. Mechanical stresses on the suspension insulator are less since the line
hanged on a flexible suspension string.
4. As the current carrying conductors are suspended from supporting structure
by suspension string, the height of the conductor position is always less than
the total height of the supporting structure. Therefore, the conductors may
be safe from lightening.
Disadvantages of Suspension Insulator
1. Suspension insulator string costlier than pin and post type insulator.
2. Suspension string requires more height of supporting structure than that for pin or post
insulator to maintain same ground clearance of current conductor.
3. The amplitude of free swing of conductors is larger in suspension insulator system,
hence, more spacing between conductors should be provided.
Three types are cemented cap, interlinking suspension, and core suspension insulators.
Strain Insulator
When suspension string is used to sustain extraordinary tensile load
of conductor it is referred as string insulator. When there is a dead
end or there is a sharp corner in transmission line, the line has to
sustain a great tensile load of conductor or strain. A strain insulator
must have considerable mechanical strength as well as the
necessary electrical insulating properties.
Stay Insulator
For low voltage lines, the stays are to be insulated from
ground at a height. The insulator used in the stay wire is
called as the stay insulator and is usually of porcelain and is
so designed that in case of breakage of the insulator the
guy-wire will not fall to the ground.
Electrical Insulator is a very high resistive path through which practically no current can flow. In
transmission and distribution system, the overhead conductors are generally supported by
supporting towers or poles. The towers and poles both are properly grounded. So there must be
insulator between tower or pole body and current carrying conductors to prevent the flow of
current from conductor to earth through the grounded supporting towers or poles.
Properties of Insulating Material
1. It must be mechanically strong enough to carry tension and weight of conductors.
2. It must have very high dielectric strength to withstand the voltage stresses in High Voltage
system.
3. It must possess high Insulation Resistance to prevent leakage current to the earth.
4. The insulating material must be free from unwanted impurities.
5. It should not be porous.
6. There must not be any entrance on the surface of electrical insulator so that the moisture or
gases can enter in it.
7. There physical as well as electrical properties must be less affected by changing temperature.
Is relay work on DC voltage? Is there working principal of AC relay and DC relay are different?
DC or AC? Relays may be of any type: AC or DC. However, in general, DC relays are widely
preferred to AC relays in control systems of HT switchgear.
Why? HT switchgears require a reliable power source for operation, which shall work even in
the event of power failures. We have battery banks as power backup for tackling such an event.
These battery banks inherently provide a DC output. If we use AC relays, we require an
additional inverter connected to the battery banks. The more equipment we add, higher is the
probability of failure. We therefore prefer DC relays that can directly work on output from the
battery bank.
What is the difference between AC and DC relays?
AC relays require higher margin of safety in terms of insulation resistance with respect to RMS
voltage.
AC relays have a shading coil to overcome the problem of intermittent nature of alternating
voltages.
DC relays have freewheeling diodes across them for faster commutation and dropping. This is
because DC does not have natural zero crossing unlike AC.
Generation Code: The Generation Code covers the guiding principles, operating procedures and
Technical standards governing operation of the Electrical Power System Grid and all
interconnected generating facilities.
What is diaphragm in transformer?
The rubber diaphragm and capsule for the large power transformer is a protective device to
prevent degradation of the transformer oil and ageing of insulation materials to prolong service
life of the transformer. It can be used in a fully sealed oil reservoir tank on the 110 kv, 220 kv
and 500kv transformers.
It represents the shortest distance along the surface of the insulator between the conductive
ends of the insulator. The objective in insulator design is to create an insulator shape that will
prevent current from “leaking” along the surface of the insulator from live electrical circuits to
ground. Current leakage is bad and will cause damage and eventually failure of the insulator.
Insulator geometry is critical to maintaining good creep distance. Engineers add “sheds” to the
insulator to maximize the creep distance. This helps in two ways. First, the geometry of a shed
increases the surface distance on the insulator from end to end. This increases the creep
distance. Second, the sheds are engineered in way to remove environmental contaminants
(salt, pollution, dust, etc.) from the insulator in rainy weather.
Environmental contaminants have a strong effect on insulator performance. The more surface
contaminants on the insulator, the more likely you will have leakage current since many of the
contaminants are conductive. In general, areas of high contaminants require more than
31mm/kV of creep distance whereas clean areas need only 16mm/kV.Creep distance is a
critical aspect of insulator design. The higher the voltage level and the higher the contaminant
level, the more creep distance you will need.
Improving the PF can maximize current-carrying capacity, improve voltage to equipment, reduce
power losses, and lower electric bills. The simplest way to improve power factor is to add PF
correction capacitors to the electrical system. PF correction capacitors act as reactive current
generators. Improving power factor means reducing the phase difference between voltage and
current.
Why an over excited synchronous generator generates reactive power and an under
excited synchronous generator absorbs reactive power?
Let us consider that the stator winding of synchronous generator is being excited by a DC source
and the rotor (Armature ) of synchronous generator carries 3-phase winding on it and supplies
power at output terminals with the help of slip rings, than:-
1) An over excited synchronous generator generates reactive power as its excitation is
increased (over excited ) means the magnetic field strength of the stator winding of the
synchronous generator is now increased more by increase in DC excitation , so in such a case
more flux will induce in stator winding and when this induced flux will interact with the rotor
(Armature ) 3-phase winding than more power (reactive power) will get developed. Thus the
over excited synchronous generator generates more reactive power on this principle.
2) Similarly Under excited synchronous generator absorbs reactive power as when it is under
excited means the DC excitation of the synchronous generator has been reduced, which results
in decrease in magnetic flux of stator. Thus when this less/low flux interact with rotor than it will
generate lagging reactive power i.e., it will absorbs reactive power. Thus the under excited
synchronous generator absorbs the reactive power on this principle.
Types of Generator Protection: The various forms of protection applied to the generator can be
categorized into two manners,
Other than protective relays, associated directly with the generator and its associated
transformer, there are lightning arrestors, over speed safe guards, oil flow devices and
temperature measuring devices for shaft bearing, stator winding, transformer winding and
transformer oil etc. Some of these protective arrangement are of non-trip type i.e. they only
generate alarm during abnormalities.
But the other protective schemes ultimately operate master tripping relay of the generator. This
should be noted that no protective relay can prevent fault, it only indicates and minimizes the
duration of the fault to prevent high temperature rise in the generator otherwise there may be
permanent damage in it. It is desirable to avoid any undue tresses in the generator, and for that
it is usual practice to install surge capacitor or surge diverter or both to reduce the effects of
lightning and other voltage surges on the machine. The protection schemes usually applied to
the generator are discussed here below in brief.
Protection against Insulation Failure
The main protection provided in the stator winding against phase to phase or phase to earth
fault, is longitudinal differential protection of generator. Second most important protection
scheme for stator winding is inter turn fault protection. This type of protection was considered
unnecessary in previous days because breakdown of insulation between points in the same
phase winding, contained in the same slot, and between which a potential difference exists, very
rapidly changes into an earth fault, and then it is detected by either the stator differential
protection or the stator earth fault protection. A generator is designed to produce relatively
high voltage in comparison to its output and which therefore contains a large number of
conductors per slot. With increasing size and voltage of the generator, this form of protection is
becoming essential for all large generating units.
Stator Earth Fault Protection:
When the stator neutral is earthed through a resistor, a current transformer is mounted in the
neutral to earth connection. Inverse Time Relay is used across the CT secondary when the
generator is connected directly to the bus bar. In case of generator feeds power via a delta star
transformer, an Instantaneous Relay is used for the same purpose. In the former case, the earth
faults relay is required to be graded with other fault relays in the system. This is the reason why
Inverse Time Relay is used in this case. But in the latter case, the earth fault loop is restricted to
the stator winding and primary winding of the transformer, hence, there is no need of grading
or discrimination with other earth fault relays in the system. That is why Instantaneous Relay is
preferable in the case.
Rotor Earth Fault Protection
A single earth fault does not create any major problem in the generator but if the second earth
fault is occurred, however, part of the field winding will become short-circuited and resulting
and unbalanced magnetic field in the system and consequently there may be major mechanical
damage to the bearings of the generator. There are three methods available to detect the types
of fault in the rotor. The methods are,
Potentiometer method
AC injection method
DC injection method
Unbalanced Stator Loading Protection:
Unbalancing in loading produces negative sequence currents in the stator circuit. This negative
sequence current produces a reaction field rotating at twice of synchronous speed with respect
to the rotor and hence induce double frequency current in the rotor. This current is quite large
and causes overheating in the rotor circuit, especially in the alternator. If any unbalancing
occurred due to fault in the stator winding itself, that would be cleared instantaneously by the
differential protection provided in the generator. If the unbalancing is occurred due to any
external fault or unbalanced loading in the system, it may remain undetected or may persist for
a significant period of time depending on the protection coordination of the system. These
faults then be cleared by installing a negative phase sequence relay with the characteristics to
match the withstand curve of the machine.
Protection against Stator Overheating:
Overloading can causes overheating in the stator winding of the generator. Not only
overloading, failure of cooling systems and insulation failure of stator laminations also cause
overheating of the stator winding. The overheating is detected by embedded temperature
detectors at various points in the stator winding. The temperature detector coils are normally
resistance elements which form one arm of the Wheatstone bridge circuit. In the case of smaller
generator normally below 30 MW, the generators are not equipped with embedded
temperature coil but are usually fitted with thermal relay and they are arranged to measure the
current flowing in the stator winding. This arrangement only detects overheating caused by
overloading and does not provide any protection against overheating due to failure of cooling
systems or short circuited stator laminations. Although over current relays, negative phase
sequence relays, and devises for monitoring constant flow are also used to provide a certain
degree of thermal overload protection.
Low Vacuum Protection: This protection usually is in the form of a regulator which compares
the vacuum against atmospheric pressure, it is normally fitted to the generator set above 30
MW. The modern practice is for the regulator to unload the set via the secondary governor until
normal vacuum conditions are restored. If the vacuum conditions do not improve below 21 inch
the stop valves are closed and the main circuit breaker is tripped.
Protection against Lubrication Oil Failure: This protection is not considered essential since the
lubrication oil is normally obtained from the same pump as governor oil and a failure of the
governor oil will automatically make stop valve to close.
Protection against Loss of Boiler Firing: Two methods are available for detecting the loss of
boiler firing. In the first method, normally opened (NO) contacts are provided with the fan
motors which may trip the generator if more than two motors fail. The second methods use a
boiler pressure contacts which unload the generator if boiler pressure falls below approximately
90%.
Protection against Prime Mover Failure: If the prime mover fails to supply mechanical energy
to the generator, the generator will continue to rotate in motoring mode that means it takes
electrical energy from the system instead of supplying it to the system. In steam turbine set the
steam acts as a coolant maintaining the turbine blades at a constant temperature. Failure of the
supply will therefore result in overheating due to friction, with subsequent distortion of turbine
blades. The, failure of steam supply can cause severe mechanical damage in addition of
imposing a heavy motoring load on the generator. Reverse power relay is used for this purpose.
As soon as the generator starts rotating in motoring mode, the reverse power relay will trip the
generator set.
Over Speed Protection: While it is the general practice to provide mechanical over speed
devices on both steam and hydro turbine, which operate directly on the steam throttle valve or
main step valve, it is not usual to backup this devises by an over speed relay on steam driven
sets. It is, however, considered good practice on hydroelectric units, as the response of the
governor is comparatively slow and the set is more prone to over-speed. The relay when fitted is
usually supplied from the permanent magnet generator used for the control of governor.
Protection against Rotor Distortion: The cooling rates following shutdown, at the top and
bottom of the turbine casing, are different and this uneven temperature distribution tends to
cause destruction of the rotor. To minimize the disruption, it is common practice to turn the
rotor at low speed during the cooling down period. In the view of the forces involved with large
modern rotor, it is now standard practice to fit shaft eccentricity detectors.
Protection against Difference in Expansion between Rotating and Stationary parts: During the
running up period, the rate of heating of the rotor differs from that of the casing, due to the
difference in mass. As a result, the rotor expands at a different rate to the casing and it is
necessary to overcome this unequal expansion. To this end, proposition is made on the larger
machine for independent supplies of steam to be set to certain joints on the casing. It is
desirable therefore to provide a means of measuring the axial expansion to assist the operator
to feed the steam to the correct points and also to provide indication of any dangerous
expansion. The shaft axial expansion detector is basically similar to the equipment described for
rotor distortion equipment, except that the detector magnets are fixed to the turbine casing.
Protection against Vibration: Vibration detectors are usually mounted on the bearing pedestals.
The detector consists of a coil mounted on springs between U shaped permanent magnets. The
voltage output from the coil, which is proportional to the degree of vibration, is passed from the
coil into integrating circuits and then into interval indicating instrument.
Back up Protection of Generator: Back up protection should always be given in highly rated
machine like synchronous generator or alternator. If faults occurred had not been cleared by the
appropriate protection scheme then back up protection relays should be operated to clear the
fault. Over current relays are generally used for this purpose. Because the synchronous
reactance of modern machine is often greater than hundred percent, the sustained fault current
fed from the machine into an external fault is invariably below the normal full load current. The
normal IDMT relays would not prove satisfactory because their current settings must be close to
the full load and their time sitting short if operation is to be obtained, resulting in probable lack
of discrimination with other over current relays in the system. Further, the over current relay
would most probably operate for loss of field on the machine, disconnecting it prematurely. To
overcome this problem, it has become customary to apply an over current relay in combination
with under voltage relay, the latter relay controlling the fault settings of the former.
Differential Protection of a Generator: Differential
protection for a generator is mainly employed for
the protection of stator windings
of generator against earth faults and phase-to-
phase faults. The stator winding faults are very
dangerous, and it causes considerable damage to
the generator.
Neutral Grounding: In neutral grounding system, the neutral of the system or rotating system or
transformer is connected to the ground. The neutral grounding is an important aspect of power
system design because the performance of the system regarding short circuits, stability,
protection, etc., is greatly affected by the condition of the neutral. A three phase system can be
operated in two possible ways,
1. With ungrounded neutral
2. With a grounded neutral
The selection of the type of grounding depends on the size of the unit, system voltage and
protection scheme to be used.
Thevenin’s Theorem:
A more general statement of Thevenin’s Theorem is that any linear active network consisting of
independent or dependent voltage and current source and the network elements can be
replaced by an equivalent circuit having a voltage source in series with a resistance, that voltage
source being the open circuited voltage across the open circuited load terminals and the
resistance being the internal resistance of the source.
In other words, the current flowing through a resistor connected across any two terminals of a
network by an equivalent circuit having a voltage source Eth in series with a resistor Rth. Where
Eth is the open circuit voltage between the required two terminals called the Thevenin voltage
and the Rth is the equivalent resistance of the network as seen from the two terminals with all
other sources replaced by their internal resistances called Thevenin resistance.
Zig-Zag Transformer:
A zig-zag transformer is used for providing grounding on the transformer. It provides insulation between
the ground and the component so that the system component may not be affected by the fault
currents. Zigzag transformer terminates the harmonics of the power system. It also protects the power
system by reducing the stress of the voltage under a fault
condition.
The zig-zag transformer has no secondary winding. It is a three-
limbed (branched) transformer. Each limbed has got two
identical windings. One set of windings is connected in the star
to provide the neutral point. The other ends of this set of
windings are connected to the second set of windings as shown
in the figure below. The direction of current in the two windings
on each limb is opposite to each other.
Under normal operating conditions the total flux in each limb is
negligibly small. Therefore, the transformer draws very small
magnetizing current. Under fault conditions, the impedance of
the grounding transformer is very low.
In order to limit the fault current, a resistor is connected in series
with the neutral grounding. It is designed for a short-time kVA
rating and for carrying the rated current for a very short time of
10 seconds.
Resistance grounding:
In this type of neutral grounding, the neutral of the system is connected to ground through one or more
resistance. Resistance grounding limits the fault currents. It protects the system from transient
overvoltages. Resistance grounding decreases the arcing grounding risk and permits ground-fault
protection. The value of resistance used in the neutral grounding system should
neither be very high nor be very low shown in the figure below.
A very low resistance makes the system to the solidity grounded, whereas a very high
resistance makes the system ungrounded. The value of resistance is chosen such that
the ground-fault current is limited, but still sufficient ground current flows permit the
operation of ground faults protections. In general, the ground fault may be limited up
to 5% to 20% of that which occur with a three-phase line.
Reactance Grounding
In reactance grounded system, a reactance is inserted between the neutral and
ground to limit the fault current as shown in the figure below.
To minimize transient overvoltages, the ground fault current in a reactance
grounded system should not be less than 25% of the three phase fault current. This
is considerably more than the minimum current desirable in resistance grounded
systems.
If IC is equal to IL there will be no current through the ground, and there will
be no tendency of the arcing grounds to occur. With the help of Peterson
coil neutral grounding, arc resistance is reduced to such a small value that
it is usually self-extinguishing. Therefore, Peterson coil is also known as a
ground fault neutralizer or arc suppression coil. Peterson coil is rated for a
short time of about 5 minutes, or it is designed to carry its rated current
continuously. It reduces the transient faults which occur due to lightning
and also minimized the single line-to-ground voltage drops.
Reciprocity Theorem:
Reciprocity Theorem states that – In any branch of a network or circuit, the current due to a
single source of voltage (V) in the network is equal to the current through that branch in which
the source was originally placed when the source is again put in the branch in which the current
was originally obtained. This theorem is used in the bilateral linear network which consists
bilateral components.
Superposition Theorem:
Superposition theorem states that in any linear, active, bilateral network having more than one source,
the response across any element is the sum of the responses obtained from each source considered
separately and all other sources are replaced by their internal resistance. The superposition theorem is
used to solve the network where two or more sources are present and connected.
In other words, it can be stated as if a number of voltage or current sources are acting in a linear
network, the resulting current in any branch is the algebraic sum of all the currents that would be
produced in it, when each source acts alone, all the other independent sources are replaced by their
internal resistances. It is only applicable to the circuit which is valid for the ohm’s law (i.e., for the linear
circuit).
Compensation Theorem
Compensation Theorem states that in a linear time invariant network when the resistance (R) of
an uncoupled branch, carrying a current (I), is changed by (ΔR). The currents in all the branches
would change and can be obtained by assuming that an ideal voltage source of (VC) has been
connected such that VC= I (ΔR) in series with (R + ΔR) when all other sources in the network are
replaced by their internal resistances.
Norton’s Theorem:
Norton’s Theorem states that – A linear active network consisting of independent or dependent voltage
source and current sources and the various circuit elements can be substituted by an equivalent circuit
consisting of a current source in parallel with a resistance. The current source being the short-circuited
current across the load terminal and the resistance being the internal resistance of the source network.
The Norton’s theorems reduce the networks equivalent to the circuit having one current source, parallel
resistance and load. Norton’s theorem is the converse of Thevenin’s Theorem. It consists of the
equivalent current source instead of an equivalent voltage source as in Thevenin’s theorem. The
determination of internal resistance of the source network is identical in both the theorems.
In the final stage that is in the equivalent circuit, the current is placed in parallel to the internal
resistance in Norton’s Theorem whereas in Thevenin’s Theorem the equivalent voltage source is placed
in series with the internal resistance.
Maximum Power Transfer Theorem:
Maximum Power Transfer Theorem can be stated as – A resistive load, being connected to a DC
network, receives maximum power when the load resistance is equal to the internal resistance
known as (Thevenin’s equivalent resistance) of the source network as seen from the load
terminals. The Maximum Power Transfer theorem is used to find the load resistance for which
there would be the maximum amount of power transfer from the source to the load.
The maximum power transfer theorem is applied to both the DC and AC circuit. The only
difference is that in AC circuit the resistance is substituted by the impedance. The maximum
power transfer theorem finds their applications in communication systems which receive low
strength signal. It is also used in speaker for transferring the maximum power from an amplifier
to the speaker.
Millman’s Theorem
The Millman’s Theorem states that – when a number of voltage sources (V1, V2, V3……… Vn) are in
parallel having internal resistance (R1, R2, R3………….Rn) respectively, the arrangement can replace by a
single equivalent voltage source V in series with an equivalent series resistance R. In other words; it
determines the voltage across the parallel branches of the circuit, which have more than one voltage
sources, i.e., reduces the complexity of the electrical circuit.
This Theorem is given by Jacob Millman. The utility of Millman’s Theorem is that the number of parallel
voltage sources can be reduced to one equivalent source. It is applicable only to solve the parallel
branch with one resistance connected to one voltage source or current source. It is also used in solving
network having an unbalanced bridge circuit.
Tellegen’s Theorem
Tellegen’s Theorem states that the summation of power delivered is zero for each branch of any
electrical network at any instant of time. It is mainly applicable for designing the filters in signal
processing. It is also used in complex operation systems for regulating the stability. It is mostly used in
the chemical and biological system and for finding the dynamic behavior of the physical network.
Tellegen’s theorem is independent of the network elements. Thus, it is applicable for any lump system
that has linear, active, passive and time-variant elements. Also, the theorem is convenient for the
network which follows Kirchhoff’s current law and Kirchhoff’s voltage law.
Conductance:
The base of the Admittance triangle is known as Conductance, shown in the figure above.
Susceptance:
Susceptance is positive for capacitive reactance and is negative for inductive reactance.
Peak Value
Definition: The maximum value attained by an alternating
quantity during one cycle is called its Peak value. It is also
known as the maximum value or amplitude or crest value.
The sinusoidal alternating quantity obtains its peak value at
90 degrees as shown in the figure below. The peak values of
alternating voltage and current is represented by Em and Im
respectively.
Average Value
Definition: The average of all the instantaneous values of an alternating voltage and currents
over one complete cycle is called Average Value.
If we consider symmetrical waves like sinusoidal current or voltage waveform, the positive half
cycle will be exactly equal to negative half cycle. Therefore, the average value over a complete
cycle will be zero. The work is done by both, positive and negative cycle and hence the average
value is determined without considering the signs. So the only positive half cycle is considered
to determine the average value of alternating
quantities of sinusoidal waves.
R.M.S Value
Definition: That steady current which, when flows through a resistor of known resistance for a given
period of time than as a result the same quantity of heat is produced by the alternating current when
flows through the same resistor for the same period of time is called R.M.S or effective value of the
alternating current.
In other words, the R.M.S value is defined as the square root of means of squares of instantaneous
values.
Ieff = square root of mean of squares of instantaneous values = R.M.S value
Root Mean Square is the actual value of an alternating quantity which tells us an energy transfer
capability of an AC source. The ammeter records the RMS value of alternating current and voltmeter
record’s the root mean square (R.M.S) value of alternating voltage. The domestic single phase AC supply
is 230 V, 50 hertz, where 230 V is the R.M.S value of alternating voltage.
The values of voltage and the current system in a DC circuit is constant, so there is no issue in evaluating
their magnitudes, but in an AC system, the alternating voltage and current vary from time to time and
hence it is necessary to evaluate their magnitudes. The following three ways (peak value, Average value
and R.M.S value) given above are adopted to express the magnitude of the voltage and current.
Parallel Resonance:
Parallel Resonance means when the circuit current is in phase with the applied voltage of an AC
circuit containing an Inductor and a Capacitor connected together in parallel.
Synchronous Machine:
Synchronous Machine constitutes of both synchronous motors as well as synchronous
generators. An AC system has some advantages over DC system. Therefore, the AC system is
exclusively used for generation, transmission and distribution of electric power. The machine
which converts mechanical power into AC electrical power is called as Synchronous Generator
or Alternator. However, if the same machine can be operated as a motor is known as
Synchronous Motor.
A synchronous machine is an AC machine whose satisfactory operation depends upon the
maintenance of the following relationship.
…………..> Eq-1
Where,
When connected to an electric power system, a synchronous machine always maintains the
above relationship shown in the equation (1).
If the synchronous machine working as a motor fails to maintain the average speed (Ns) the
machine will not develop sufficient torque to maintain its rotation and will stop. Then the motor
is said to be Pulled Out of Step.
In case, when the synchronous machine is operating as a generator, it has to run at a fixed
speed called Synchronous speed to generate the power at a particular frequency. As all the
appliances or machines are designed to operate at this frequency. In some countries, the value
of the frequency is 50 hertz.
Lightning is a natural phenomenon that occurs in the atmosphere when two neighboring clouds
of opposite charges strike each other or between a negative cloud and a grounded object on
earth. It is associated with an electrical discharge and huge sound during a thunderstorm. The
phenomenon of Lightning introduces lightning surges in transmission network. The Lightning
strokes on transmission lines are of two type direct strokes and induced strokes. When a
thunder cloud directly discharges on a transmission line tower or line wire it is called a direct
stroke. It is the most severe form of lightning stroke and is rare on transmission systems and
only induced strokes occurs.
When a thunderstorm generates negative charges at its ground end, the earthed objects
develop induced positive charge. The earthed objects of interest are transmission lines and
towers. Normally, it is expected that the lines are unaffected because they are insulated by
strings of insulators.
However because of high field gradients involved the positive charges leak from the tower along
the insulator surfaces to the line conductors. This process may take considerable time in the
order of some hundreds of seconds. When the cloud discharges to some earthed object other
than the line conductor, the transmission line conductor is left with a high concentration of
positive charge which cannot leak suddenly. The transmission line and the ground will act as a
huge capacitor carrying a positive charge and hence over voltages occur due to these induced
charges. This would result in a stroke which is commonly known as an “induced” lightning
stroke.
As a result of a direct stroke or an induced stroke, a large current impulse is injected into the
line conductor which produces a voltage surge in the line as high as 5,000kV. However on an
average most of the lightning strokes give rise to voltage surges of less than 1000kV on
overhead lines.
What is Impulse?
An impulse is defined as a unidirectional voltage (or current) rising quickly to its peak value and then
decaying slowly to zero. An impulse voltage is characterized by its peak value Vp, its front time “tf” and
its tail time or time to half “tt”. Thus an impulse has 2 parts i.e. a rising part which is usually realized by
charging a capacitor and a decaying part which is realized by discharging a capacitor.
Impulse voltages are used to simulate the stresses imposed on high voltage apparatus due to lightning
or switching surges.
Insulation is recognized as one of the most important constructional elements of a transformer. Its chief
function is to confine the current to useful paths, preventing it flow into harmful channels. Any
weakness of insulation may result in failure of the transformer. A measure of the effectiveness with
which insulation performs is the dielectric strength of transformer. The purpose of the impulse test is to
determine the ability of the transformer insulation to withstand the transient voltages due to lightning.
It is well known that power system components are subjected to severe over voltage due to internal
switching or external lightning surges. Consequently the integrity of the individual components, devices,
and subsystems must be checked through high voltage surge testing.
Lightning Impulse Test on Transformer (400KV/15KV, 160MVA) (ABB)
System disturbances from lightning can be represented by three basic wave shapes- full wave,
chopped wave and front-of-waves.
Lightning Impulse is generated using an Impulse Generator in impulse test.
Max. Test voltage amplitudes:
> 2.1 MV lightning impulse
> 1.6 MV switching impulse
The relay module includes four frequency stages. Each frequency stage can
be set to operate as an over-frequency (f>) stage or an under frequency (f<)
stage with definite time characteristic.
Further, each stage can be set to function as a rate of change of frequency (df/dt) stage. When the start
frequency of a stage is set below the rated frequency, the stage operates as an under-frequency stage.
Correspondingly, the stage has the function of an over-frequency stage, when the start frequency is set
above the rated frequency. The frequency setting cannot be the same as the rated frequency.
The operation of the df/dt function of a protection stage is based on the same principle as the frequency
function, which means that if a stage operates as an under-frequency stage, the sign of the df/dt
function is negative.
Then the df/dt function starts once the absolute value of the rate of frequency drop exceeds the
set df/dt value. When required by the application, the definite time principle and the rate of
change principle can be combined so that the criteria for operation of both functions have to be
fulfilled at the same time to enable operation of the stage. Once a preset condition is fulfilled,
the stage starts and, at the same time, it activates a timing circuit. No start signal can be
assigned for the output relays. When the stage times out, the relay produces a trip signal. The
trip signal can be assigned to the desired output relay.
The main application of the HVDC circuit breaker is to interrupt the high voltage direct current
flows in the network. AC circuit breaker easily interrupts the arc at natural current zero in the AC
wave. At zero current, the energy to be interrupted is also zero. The contact gap has to recover
the dielectric strength to withstand natural transient recovery voltage.
With DC circuit breakers, the problem is more complex as the DC waveform does not have
natural current zeros. Forced arc interruption would produce high transient recovery voltage
and restrike without arc interruption and ultimate destruction of the breaker contacts. In
designing of HVDC circuit breakers, there are three main problems to be overcome. These
problems are;
> Creation of artificial current zero
> Prevention of restrikes arc
> Dissipation of stored energy
The artificial current zero principles are used in HVDC circuit breakers
for arc extinction. By introducing a parallel L-C circuit, the arc current
is subjected to oscillations. These oscillations are severe and have
several artificial current zeros. The breaker extinguishes the arc at
one of the artificial current zeros. The crest current of the oscillation
must be greater than the direct current to be interrupted.
Phase Failure Relay: monitors three phase AC supplies for
Phase failure
Phase Imbalance
Incorrect Phase Sequence
The Phase Failure Relay is a phase-voltage-balance monitoring device designed for use with magnetic
controls to automatically prevent three phase motors or other equipment from operating or attempting
to start up under open phase or single-phase conditions, thereby eliminating burnouts and consequent
down-time frequently incurred by phase failure.
Phase Failure Relay is not a thermal device. It operates on the principle of phase voltage unbalance
which may occur in a three phase system. It also protects against phase loss.
Operation:
Phase Failure Relay is a self-contained power sensing device. In normal operation the incoming phases
of the three phase voltage applied to our power-sensing network are in balance. When any phase
becomes more than 12% unbalanced from the other two (either low or high), or a phase loss occurs, the
sensing network will deliver an output voltage to activate the transistor circuit. This will cause the
master output relay on the Phase Failure Relay to trip (either dropout or pickup depending upon model).
A time delay of approximately 1 ½ seconds is incorporated to eliminate the possibility of nuisance
tripping.
Applications:
Phase Failure Relay can be used to protect any magnetically controlled three phase equipment that
would be damaged if subjected to abnormal phase conditions such as single phasing. It is designed to
monitor any three phase supply line, and can be used with any type of actuating controls such as push
button stations, thermostats, pressure or float switches. It may also be used in a trip circuit utilizing
manually operated starters in conjunction with shunt or capacitive trip devices. Typical applications are
as follows:
Any three phase motor.
Unattended motors, such as ventilation fans.
Pumps, refrigeration equipment, air conditioning units, welders, and computers.
Tz1=instantaneous time= <100ms=less than 0.1 sec,,,,, Tz2 = 450,300ms msec = 0.45 sec
HVDC:
Line-Commutated Current Sourced Converters
The invention of mercury arc rectifiers in the nineteen-thirties made the design of line-
commutated current sourced converters possible.
In 1941, the first contract for a commercial HVDC system was signed in
Germany: 60 MW were to be supplied to the city of Berlin via an underground cable of 115 km
length. The system with ±200 kV and 150 A was ready for energizing in 1945. It was never put
into operation. Since then, several large HVDC systems have been realized with mercury arc
valves.
The replacement of mercury arc valves by thyristor valves was the next major development. The
first thyristor valves were put into operation in the late Nineteen-seventies. The outdoor valves
for Cahora Bassa were designed with oil-immersed thyristors with parallel/series connection of
thyristors and an electromagnetic firing system. Further development went via air insulated air-
cooled valves to the air insulated water-cooled design, which is still state of the art in HVDC
valve design.
The development of thyristors with higher current and voltage ratings has eliminated the need
for parallel connection and reduced the number of series-connected thyristors per valve. The
development of light-triggered thyristors has further reduced the overall no. of components and
thus contributed to increased reliability. Innovations in almost every other area of HVDC have
been constantly adding to the reliability of this technology with economic benefits for users
throughout the world.
Self-Commutated Voltage Sourced Converters:
Voltage sourced converters require semiconductor devices with turn-off capability. The
development of Insulated Gate Bipolar Transistors (IGBT) with high voltage ratings have
accelerated the development of voltage sourced converters for HVDC applications in the
lower power range. The main characteristics of the voltage sourced converters are a compact
design, four-quadrant operation capability and high losses.
Siemens is offering voltage sourced converters for HVDC applications with ratings up to 250 MW
under the trade name HVDC plus Power Link Universal Systems.
Main components of HVDC are are:
Thyristor valves
AC,DC and active Harmonic filters
Converter transformers
Smoothing reactors
Surge Arrestors
DC transmission circuits
DC transmission lines
High speed Dc switches
Earthing /Grounding Electrodes
Booster Transformer:
Booster transformer is one which is often used towards the end of a power line to raise the
voltage to the desired value. It is used for controlling the voltage of a feeder at a point far away
from the main transformer.
The secondary of the booster transformer is connected in series with the line, and its primary is
supplied from the secondary of the regulating transformer. The output winding of the regulating
transformer is so connected to the primary of the booster transformer that the voltage injected
in the line VB is in phase with the supply VS.
By changing taps on the regulating transformer, the magnitude of VB can be changed and thus
feeder voltage VF can be regulated. The rating of regulating transformer is only the fraction of
that the main transformer. It is given by the expression.
The advantage of the above system is that the regulating equipment is independent of the main
transformer so that a failure in the former will not throw the latter out of service.
Booster transformer is used in railways for eliminating the flow of stray current. The stray
current disturbs the communication system and also damages the electronic devices of the
trains passing through them.
Regulating Transformer:
Definition: The transformer which changes the
magnitude and phase angle at the certain point in
the power system is known as the regulating
transformer. It is mainly used for controlling the
magnitude of bus voltage and for controlling the
power flow, which is controlled by the phase angle of
the transformer. They provide the small component
of voltage between the line or phase voltage.
The main function of the regulating transformer is to
control the magnitude of voltage and power flow of
the transmission line. The regulating transformer is of
two types. One is used for changing the magnitude of
voltage which is called online tap changing
transformer and the other is called phase shifting
transformer. The regulating transformer compensates
the fluctuation of voltage and current.
What is the difference between smart meters and power metering using powerline
communication?
Smart meters allow bidirectional flow of power and communication. In simple words, under the
smart grid, companies can control the power flow of an individual consumer (shut down the
supply or restore it) and consumer and company can communicate back to back as well via
smart metering. Company can send tariff and pricing signals to consumer to which the later
responds. Smart Grid - Advanced Metering Infrastructure - Advanced Meter Reading (AMR)
Power meter using PLC is a technology of AMR. The mode of communication under PLC, as the
name suggests, is Power Line_the pre exiting transmission lines. Doesn’t require additional
infrastructure or communication lines.
What will happen to the size of conductors and insulators If transmission frequency is tripled?
If frequency increases, overall impedance increases; means more inductive reactance, skin
effect, corona etc. So in order to reduce that, we have to increase the size of conductor.
While I think Insulator size remains same as voltage is not increased.
Characteristic impedance value for overhead line is about 400ohm and for underground cables
value is 40 ohm.
How CPEC is important Related to Power Projects?
10400 MW energy capacity will be added in the system through CPEC and shortfall of electricity
will be eradicate.
The proximity effect mainly depends on the factors like conductors’ material, conductor diameter,
frequency and conductor structure. The factors are explained below in details Frequency – The
proximity increases with the increases in the frequency.
Diameter – The proximity effect increases with the increase in the conductor.
Structure – This effect is more on the solid conductor as compared to the stranded conductor (i.e.,
ASCR) because the surface area of the stranded conductor is smaller than the solid conductor.
Material – If the material is made up of high ferromagnetic material then the proximity effect is more on
their surface.
How is reactive power produced? What are the effects of reactive power in the grid?
In case of purely resistive load like incandescent lamp, electrical energy is directly
converted into useful work (light and heat energy in this particular case), no
intermediate electric or magnetic field is required in between. And hence no any power
is wasted in creating electrical or magnetic field. Therefore the total Power is entirely
Active Power that does useful work and there's no any requirement of Reactive Power.
However in case of inductive loads like motors, electrical energy can't directly be
converted into useful work (rotation of motor in this particular case). This is because, to
convert electrical energy into rotational energy, magnetic field has to be created in
between the gaps of stator and rotor of Motor. Hence, some amount of energy has to
be used in creating magnetic field. The portion of power that contributes in creating
magnetic field is known as Reactive Power. From view point of efficiency, reactive
power may be seen as power loss because its role is limited to creating magnetic field
and does not contribute in driving load. Nevertheless, reactive power isn't actually a loss
because it creates magnetic field without which electrical energy in stator could not
have been converted to rotational energy in rotor.
My posting is at GBHP : Hmaare hann 290MW k generators installed hen unko jb
chalaaty hn jese hi woh busbar k sath sync hojata hai to automatically 20MW ki
commamd le leta hai ... uss k bad humein khud se usko 290MW ki command deni hoti
hai ... agr sync hone k bad hm usko koi command naa dein to kuch tym (30, 40 seconds)
k bad wo khud e reverse power pe trip hojata hai ... reverse power relay usko trip
krwaa deti ha .q k uss tym generator as a motor kaam krna shuru krdeta ha mtlb bajae
system ko power dene k woh system se power lenaa shuru krdeta ha which is too much
dangerous situation.
How Load management on different generators is done ? Agr aik trip kr jaye incase to
baqi generators pe to load ziada hojata hai then frequency disturb hoti hai. How it is
controlled?
Yes 290MW ka generator agar trip hojae to frequency distrub hojati hai ... tou NPCC baqi plants se
generation ko increase kraaa dety hn ... taa k frequency control me rhy. For example ... system ki
frequency 49.5HZ chal rhi ho aur uss tym 290MW ka ek generator trip hojata hai kisi b reason ki wja se
... to frequency 49hz se b nechy chali jaegi aur lines trip hojaengi khud se hi aur black out hone ka b
chances hen ... aur agr 50.5hz frequency chal rhi ho uss tym 290MW ka ek generator trip hota hai ... to
frequency 49.5 tk aaskti hai us tym itni dangerous situation nahin ... it all depends k uss tym system ki
frequency kia chal rhi hy jis tym generator trip hota ha.
Hmaare hann jo generators installed hen uski designing aesi hai sync hone k bad wo 20mw khud se
generate krna shuru krdeta ha issiliye sync hone k foran bad hm 290mw ki command dete hn generator
ko ... hr plant ki apni designing hoti hy hr generator ki apni designing hoti h ... I'm talking about
generators installed at Ghazi Bharota Power House (GBPH).
A switch is a device which is designed to interrupt the current flow in a circuit, in other words, it can
make or break an electrical circuit. Every electrical and electronics application uses at least one switch to
perform ON and OFF operation of the device. So the switches are the part of a control system and
without it, control operation cannot be achieved. A switch can perform two functions, namely fully ON
(by closing its contacts) or fully OFF (by opening its contacts).
When the contacts of a switch are closed, the switch creates the closed path for current flow and hence
load consumes the power from source. When the contacts of a switch are open, no power will be
consumed by the load as shown in below figure.
Electronic switches do not require any physical contact in order to control a circuit.
These are activated by semiconductor action.
Mechanical Switches
o Single Pole Single Throw Switch (SPST)
o Single Pole Double Throw Switch (SPDT)
o Double Pole Single Throw Switch (DPST)
o Double Pole Double Throw Switch (DPDT)
o Push Button Switch
o Toggle Switch
o Limit Switch
o Float Switches
o Flow Switches
o Pressure Switches
o Temperature Switches
o Joystick Switch
o Rotary Switches
Electronic Switches
o Bipolar Transistors
o Power Diode
o MOSFET
o IGBT
o SCR
o TRIAC
o DIAC
o Gate Turn-Off Thyristors
Mechanical Switches
Mechanical switches can be classified into different types based on several factors such as method of
actuation (manual, limit and process switches), number of contacts (single contact and multi contact
switches), number of poles and throws (SPST, DPDT, SPDT, etc.), operation and construction (push
button, toggle, rotary, joystick, etc.), based on state (momentary and locked switches), etc.
Based on the number of poles and throws, switches are classified into following types.
The pole represents the number of individual power circuits that can be switched.
Most of the switches are designed have one, two or three poles and are designated as
single pole, double pole and triple pole.
The number of throws represents the number of states to which current can pass
through the switch. Most of the switches are designed to have either one or two
throws which are designated as single throw and double throw switches.
This is the basic ON and OFF switch consisting of one input contact and one output contact.
It switches a single circuit and it can either make (ON) or break (OFF) the load.
The contacts of SPST can be either normally open or normally closed configurations .
This switch has three terminals, one is input contact and remaining two are output contacts.
This means it consist two ON positions and one OFF position.
In most of the circuits, these switches are used as changeover to connect the input between two
choices of outputs.
The contact which is connected to the input by default is referred as normally closed contact and
contact which will be connected during ON operation is a normally open contact.
Limit Switch
Float Switches
These are mainly used to detect the movement of liquid or air flow
through a pipe or duct. The air flow switch (or a micro switch) is
constructed by a snap-action.
This micro switch is attached to a metal arm .To this metal arm, a
thin plastic or metal piece is connected.
When a large amount of air passes through the metal or plastic
piece, it causes the movement of metal arm and thus operates the
contacts of the switch.
Liquid flow switches are designed with a paddle that inserted across the flow of liquid in a pipe.
When liquid flows through the pipe, force exerted against the paddle changes the position of the
contacts.
The above figure shows the switch symbol used for both air flow and liquid flow. The flag symbol
on the switch indicates the paddle which senses the flow or movement of liquid.
These switches again normally open or normally closed type configurations.
Pressure Switches
Temperature Switches
The most common heat sensing element is the bimetallic strip that operates on the principle of
thermal expansion.
The bimetallic strips are made with two dissimilar metals (that
are having different thermal expansion rates) and are bonded
with each other.
The switch contacts are operated when the temperature causes
the strip to bend or wrap. Another method of operating the
temperature switch is to use mercury glass tube.
When the bulb is heated, mercury in the tube will expand and
then generates pressure to operate the contacts.
Joystick Switch
Rotary Switches
Electronic Switches
The electronic switches are generally called as solid state switches because there are no physical
moving parts and hence absence of physical contacts. Most of the appliances are controlled by
semiconductor switches such as motor drives and HVAC equipment’s.
There are different types of solid state switches are available in today market with different sizes and
ratings. Some of these solid state switches include transistors, SCRs, MOSFETs, TRIACs and IGBTs.
Bipolar Transistors
A transistor either allows the current to pass or it blocks the current as similar to
working of normal switch.
In switching circuits, transistor operates in cut-off mode for OFF or current blocking
condition and in saturation mode for ON condition. The active region of the
transistor is not used for switching applications.
Both NPN and PNP transistors are operated or switched ON when a sufficient base
current is supplied to it. When a small current flows though the base terminal
supplied by a driving circuit (connected between the base and emitter), it causes to
turns ON the collector-emitter path.
And it is turned OFF when the base current is removed and base voltage is reduced
to a slight negative value. Even though it utilizes small base current, it is capable to
carry much higher currents through the collector- emitter path.
Power Diode
A diode can perform switching operations between its high and low state
impedance states. Semiconductor materials like silicon and germanium are used
for constructing the diodes.
Usually, power diodes are constructed using silicon in order to operate the device
at higher currents and higher junction temperatures. These are constructed by
joining p and n type semiconductor materials together to form PN junction. It has
two terminals namely anode and cathode.
When the anode is made positive with respect to cathode and by the application of voltage greater than
the threshold level, PN junction is forward biased and starts conducting (like ON switch). When the
cathode terminal is made positive with respect to anode, PN junction reverse biased and its blocks the
current flow (like OFF switch).
MOSFET
P-channel MOSFET operates in a similar manner of N-channel MOSFET but it uses reverse polarity of
voltages. Both VGS and VDD are negative with respect the source to switch ON the P- channel MOSFET.
IGBT
IGBT (Insulated Gate Bipolar Transistor) combines the several advantages of bipolar
junction power transistor and power MOSFET. Like a MOSFET, it is a voltage controlled
device and has lower ON state voltage drop (less than that of MOSFET and closer to power
transistor).
It is a three terminal semiconductor high speed switching device. These terminals are
emitter, collector and gate.
Similar to the MOSFET, IGBT can be turned ON by applying a positive voltage (greater than
the threshold voltage) between the gate and emitter. IGBT can be turned by reducing the
voltage across the gate-emitter to zero. In most of the case it needs negative voltage to
reduce turn OFF losses and safely turn OFF the IGBT.
SCR
TRIAC
DIAC
A DIAC (or Diode AC switch) is bidirectional switching device and it consists
of two terminals which are not named as anode and cathode. It means that a
DIAC can be operated in either direction regardless of the terminal
identification. This indicates that the DIAC can be used in either direction.
When a voltage is applied across a DIAC, it either operates in forward
blocking or reverse blocking mode unless the applied voltage is less than the
breakover voltage. Once the voltage is increased more than breakover
voltage, avalanche breakover occurs and device starts conducting.
A GTO (Gate Turn off Thyristor) is a bipolar semiconductor switching device. It has
three terminals as anode, cathode and gate. As the name implies, this switching
device is capable to turn OFF through gate terminal.
A GTO is turned ON by applying a small positive gate current triggers the
conduction mode and turned OFF by a negative pulse to the gate. GTO symbol
consists of double arrows on the gate terminal which represents the bidirectional
flow of current through gate terminal.
Solar Energy Technologies
Solutions for Today’s Energy Needs
Overview
Solar energy is the cleanest, most abundant renewable energy source available. The U.S. has some of
the world’s richest solar resources. Today's technology allows us to harness this resource in several
ways, giving the public and commercial entities flexible ways to employ both the light and heat of
the sun.
There are three primary technologies by which solar energy is commonly harnessed: photovoltaics (PV),
which directly convert light to electricity; concentrating solar power (CSP), which uses heat from the sun
(thermal energy) to drive utility-scale, electric turbines; and heating and cooling systems, which collect
thermal energy to provide hot water and air conditioning.
Solar energy can be deployed through distributed generation, whereby the equipment is located on
rooftops or ground-mounted arrays close to where the energy is used. Some technologies can be further
expanded into utility-scale applications to produce energy as a central power plant.
Photovoltaic Technology
Photovoltaic (PV) technologies directly convert energy from sunlight into electricity. When sunlight
strikes the PV module, made of a semiconductor material, electrons are stripped from their atomic
bonds. This flow of electrons produces an electric current. PV modules contain no moving parts and
generally last thirty years or more with minimal maintenance.
PV electricity output peaks mid-day when the sun is at its highest point in the sky, and can offset the
most expensive electricity when daily demand is greatest. Homeowners can install a few dozen PV
panels to reduce or eliminate their monthly electricity bills, and utilities can build large “farms” of PV
panels to provide pollution-free electricity to their customers.
Semiconductors are used in most electronic products, including computer chips, audio amplifiers,
temperature sensors and solar cells. Traditionally, PV modules are made using various forms of silicon,
but many companies are also manufacturing modules that employ other semiconductor materials often
referred to as thin-film PV. Each of the various PV technologies have unique cost and performance
characteristics that drive competition within the industry. Cost and performance can be further affected
by the PV application and specific configuration of a PV system.
Concentrating solar power (CSP) plants use mirrors to concentrate the sun’s thermal energy to drive a
conventional steam turbine to make electricity. The thermal energy concentrated in a CSP plant can be
stored and used to produce electricity when it is needed, day or night. Today, over 1,400 MW of CSP
plants operate in the U.S., and another 340 MW of CSP projects will be placed in service within the
next year.
The two commercialized CSP technologies are Power Towers and Parabolic Troughs. Other CSP
technologies include Compact Linear Fresnel Reflector (CLFR) and Dish Engine. CSP specific conditions to
produce power, such as areas where direct sunlight is most intense (e.g., the U.S. Southwest) and
contiguous parcels of dry, flat land.
Solar Heating and Cooling
Solar heating and cooling technologies collect thermal energy from the sun and use this heat to provide
hot water and space heating and cooling for residential, commercial and industrial applications. There
are several types of collectors: flat plate, evacuated tube, Integral Collector Storage (ICS), thermosiphon
and concentrating. These technologies provide a return on investment in 3-6 years.
Water heating, space heating and space cooling accounted for 69 percent of the energy used in an
average U.S. household in 2005 – representing significant market potential for solar heating and cooling
technologies. For example, solar water heating systems can be installed on every home in the U.S., and a
properly designed and installed system can provide 40 to 80 percent of a building’s hot water needs.
Similarly, solar space heating and cooling systems circulate conditioned air or liquid throughout a
building using existing HVAC systems, without using electricity.
1. Needs large amount of Coal and Water so have to be placed a large water sources and coal
mine. Else the logistics cost will be too high. A Power plant of 3000MW typically requires 35,000
to 45,000 tonnes of coal.
2. It is the prime contributor to CO2 emissions all over the world. With the Climate change a
restriction is now placed on all countries in this regard.
3. Nearly 20% to 30% of coal is rejected as Ash, which is a waste and needs to be
dumped. Unutilized ash is collected in Ash dykes that form the largest land usage in a typical
thermal power plant. It is also detrimental to environment.
4. Apart from CO2, other harmful gases like NOx and SOx are also generated lead to Acid Rain.
Though with advanced combustion and other techniques these are lowered and also captured.
5. Some liquid effluents are also discharged as the byproduct of water / chemical treatment and
runoff of various oil / chemicals.
6. Thermal power plant take a lot of time to start up (generally 4–8 hrs) and don’t do well in cycling
that is large up and down in power generation and mostly designed for constant load. Therefore
any fluctuation is power demand can be detrimental to it life cycle.
7. A large quantity of ash is released from the Chimney and the coal dust that lead to a high
particulate matter in the surrounding areas. Though nearly 99% is captured using ESP still a
significant amount escapes.
Ice storage air conditioning (ICE):
Ice storage air conditioning is the process of using ice for thermal energy storage. This is practical
because of water's large heat of fusion: one metric ton of water (one cubic meter) can store 334 mega
joules (MJ) (317,000 BTU) of energy, equivalent to 93 kWh (26.4 ton-hours).
Ice was originally obtained from mountains or cut from frozen lakes and transported to cities for use as
a coolant. The original definition of a "ton of cooling capacity" (heat flow) was the heat needed to melt
one ton of ice in a 24-hour period. This heat flow is what one would expect in a 3,000-square-foot
(280 m2) house in Boston in the summer. This definition has since been replaced by less archaic units:
one ton HVAC capacity is equal to 12,000 BTU per hour. A small storage facility can hold enough ice to
cool a large building from one day to one week, whether that ice is produced by anhydrous
ammonia chillers or hauled in by horse-drawn carts.
1. The plant has high running charges as the fuel (i.e., diesel) used is costly.
2. The plant does not operate satisfactorily under overload conditions for a longer period.
3. The plant can only generate small power.
4. The cost of lubrication is generally high.
5. The maintenance charges are generally high.
What are advantages of nuclear power plants over thermal or hydroelectric power plants?
Geographical limitations - nuclear power plants don't require a lot of space; they do not
need a large plot like a wind farm. But they have to be built near a large body of
water for cooling purposes - using the water as a heat sink. They are usually found on
the coast so there is no risk to drinking water sources.
Nuclear power stations do not contribute to carbon emissions - no CO2 is given out - it
therefore does not contribute to global warming.
Nuclear power stations do not produce smoke particles to pollute the atmosphere or
emit gases that contribute to acid rain.
Nuclear energy is by far the most concentrated form of energy - a lot of energy is
produced from a small mass of fuel. This reduces transport costs - (although the fuel is
radioactive and therefore each transport that does occur is expensive because of
security implications).
Nuclear power is reliable. It does not depend on the weather.
We can control the output from a nuclear power station to fit our needs.
It is relatively easy to control the output - although the time factor for altering power
output is not as small as for fossil fuel stations. It is said to have a long 'start up' time. It
cannot respond immediately to demand. That is why electricity companies try to 'even
out' demand by using tariffs that encourage use at off peak time prides.
Nuclear power produces a small volume of waste (although that waste is radioactive).
Low Fuel Cost - The main reason behind the low fuel cost is that it requires little amount
of uranium to produce energy. When a nuclear reaction happens, it releases million
times more energy as compared to traditional sources of energy. Only about 28 gram of
uranium releases as much energy as produced from 100 metric tons of coal.
Smart Grid:
The electric grid which is smart compare to traditional grid is known as smart grid. It
detects local changes in power usage and reacts automatically without the need of
human intervention.
• It allows two way communication between grid and consumers. It allows real time
communication between consumer and utility so that consumers can tailor their energy
consumption based on individual preferences such as price and/or environmental
concerns.
• Smart grid is developed using modern digital communication technologies. Grid
communicates with cellular tower in order to push vital parameters such as
instantaneous power usage, cumulative power usage, maximum demand etc.
In short, the digital technology that allows for two-way communication between the
utility and its customers, and the sensing along the transmission lines is what makes the
grid smart. Like the Internet, the Smart Grid will consist of controls, computers,
automation, and new technologies and equipment working together, but in this case,
these technologies will work with the electrical grid to respond digitally to our quickly
changing electric demand.
A smart grid is an electrical grid which includes a variety of operational and energy measures
including smart meters, smart appliances, renewable energy resources, and energy efficient
resources. Electronic power conditioning and control of the production and distribution of
electricity are important aspects of the smart grid.
Features:
Load Handling: The sum/total of
the power grid load is not stable
and it varies over time. In case of
heavy load, a smart grid system can
advise consumers to temporarily
minimize energy consumption.
Demand Response Support:
Provides users with an automated
way to reduce their electricity bills
by guiding them to use low-priority
electronic devices when rates are
lower.
Decentralization of Power Generation: A distributed or decentralized grid system
allows the individual user to generate onsite power by employing any appropriate
method at his or her discretion.
And yes it can be used in ntdc and Discos for proper handling of load and electricity
theft which will directly help generation section and transmission losses etc.
Micro-grid:
A micro grid is a small-scale power production and delivery system comprising
distributed generation facilities co-located with the loads they serve. Microgrids
encompass multiple types of energy generation resources, storage systems, and
efficiency programs, allowing for optimal utilization of renewable energy resources and
facilitating advanced energy management, demand response, and load reduction
solutions.
Micro grids are able to be connected to the utility grid to purchase power from the grid
or sell power back to the grid as conditions dictate. Micro grids can be designed to
operate “islanded”, when the utility grid is not available.
Benefits:
Economic: Improved efficiency and long term predictable energy cost
Resiliency: Field-proven reliability improvement over grid-only interconnections
Environmental: Reduction in harmful emissions resulting from optimal use of renewable
resources and energy efficiency programs.
Why are Micro grids important to the World?
They improve the efficiency of the larger power grid. They offer power resilience
against natural disasters such as earthquakes, tsunamis and storms. They can power
disaster relief centers during regional and national crises. They are secure against cyber
and physical attacks. They are great for the environment because they use renewables
resources. They create jobs and education opportunities.
Types of microgrids:
Campus Environment/Institutional Microgrids:
The focus of campus microgrids is aggregating existing on-site generation with multiple
loads that located in tight geography in which owner easily manage them.
Community Microgrids:
Community Microgrids can serve a few up to thousands of customers and support the
penetration of local energy (electricity, heating, and cooling). In a community microgrid,
some houses may have some renewable sources that can supply their demand as well
as that of their neighbors within the same community. The community microgrid may
also have a centralized or several distributed energy storages. Such microgrids can be in
the form of an AC and DC microgrid coupled together through a bi-directional power
electronic converter.
Remote Off-grid Microgrids: These microgrids never connect to the Macrogrid and
instead operate in an island mode at all times because of economic issues or
geographical position. Typically, an "off-grid" microgrid is built in areas that are far
distant from any transmission and distribution infrastructure and, therefore, have no
connection to the utility grid. Studies have demonstrated that operating a remote area
or islands' off-grid microgrids, that are dominated by renewable sources, will reduce the
levelized cost of electricity production over the life of such microgrid projects.
Large remote areas may be supplied by several independent microgrids, each with a
different owner (operator). Although such microgrids are traditionally designed to be
energy self-sufficient, intermittent renewable sources and their unexpected and sharp
variations can cause unexpected power shortfall or excessive generation in those
microgrids. This will immediately cause unacceptable voltage or frequency deviation in
the microgrids. To remedy such situations, it is possible to interconnect such microgrids
provisionally to a suitable neighboring microgrid to exchange power and improve the
voltage and frequency deviations. This can be achieved through a power electronics-
based switch after a proper synchronization or a back to back connection of two power
electronic converters and after confirming the stability of the new system. The
determination of a need to interconnect neighboring microgrids and finding the suitable
microgrid to couple with can be achieved through optimization or decision making
approaches.
Military Base Microgrids:
These microgrids are being actively deployed with focus on both physical and cyber
security for military facilities in order to assure reliable power without relying on
the Macrogrid.
Commercial and Industrial (C&I) Microgrids:
These types of microgrids are maturing quickly in North America and Asia Pacific;
however, the lack of well –known standards for these types of microgrids limits them
globally. Main reasons for the installation of an industrial microgrid are power supply
security and its reliability. There are many manufacturing processes in which an
interruption of the power supply may cause high revenue losses and long start-up time.
Rupee value decreases or increase due to the difference in demand and supply of
dollars into and out of country. If a dollars are coming into the country are more,
through external remittances, exports and other investments in your country then
rupee will be increased because number of dollars in the country will be more but if the
dollar going out of the country will be more due to payments of debts, dollars paid as a
result of imports and dollars etc., then the value of rupee will be decreased.
Symmetrical faults give rise to symmetrical fault currents and the fault current can be
calculated by single phase solution of balanced 3-Φ system.
Unsymmetrical faults like L-N, L-L or L-L-N give rise to unsymmetrical fault currents and for
their analysis, the method of sequence components is used. In this method, A 3-Φ
Unsymmetrical fault current can be represented as the sum of two balanced components i.e.
+ve & -ve sequence components & a zero sequence component.
Positive sequence components have equal magnitude and their phase sequence is same
as that of original unsymmetrical fault current. The circuit impedance that resists the
flow of +ve sequence current is known as +ve sequence impedance.
Negative sequence components have equal magnitude but their phase sequence is
opposite to that of original unsymmetrical fault current. The circuit impedance that
resists the flow of -ve sequence current is known as -ve sequence impedance.
The zero sequence components are of equal magnitude and they are in phase with each
other. Neutral current is equal to sum of zero sequence currents flowing through each
phase. In case of delta connection or in case of ungrounded star connection, neutral
current will be zero; hence zero sequence currents will not flow.
Ratio of rated
power should not be greater
than 3:1 in transformers to be
connected in parallel.
EARTHING AT GRID STATION:
For the safety of equipment and worker the whole equipment installed in Grid station is
properly earthed. If they are not grounded the possibility Of fatal accidents arise.
Normally the potential of some parts of equipment remains zero but in case of fault or
insulation failure they become dangerously charged now if a person comes in contact with
these parts the possibility of electrical shock arise. Due to this the metal parts are properly
earthed.
Role of earthling
To provide earthling to power transformer and neutral of capacitor bank.
To connect every structure, body of transformers and other equipment’s body to earth
mesh.
To provide easy path for lightening and extra voltage through rod gaps, surge arrester
and sky wire to ground.
To discharge trapped charge through less resistance path for maintenance purpose.
To provide a grounding mat below ground surface and around the grid station which will
have uniformly zero potential w.r.t ground and the lowest earth resistance.