EPAS – Design & Configuration

Basic Modules configuration


EcoStruxureTM Power Automation System
Power Solutions Global Training
2023

Confidential Property of Schneider Electric


Internal
Safety Information
This is training presentation, reference information is in Official Technical Guides.

▪ It is advisable to read all the Safety


Information, all the time before trying to
Install, Operate, Service or Maintain it.
▪ Electrical equipment should be installed,
operated, serviced and maintained only by
qualified personnel.
▪ Work with facility IT System
Administrators to ensure that the system
adheres to the site-specific cybersecurity
policies.

Failure to follow these instructions can result


in death, serious injury, or equipment damage.

Confidential Property of Schneider Electric | Page 2


Internal
Chapter Objectives
By the completion of this chapter, you will be able to:

• Configure Primary devices in SCE Typed


devices:
Circuit breaker
Switchgear
Transformer
Generic device

Confidential Property of Schneider Electric | Page 3


Internal
• Content

▪ Circuit Breaker
▪ Disconnector Switch
▪ Transformer
▪ Generic Module

Confidential Property of Schneider Electric | Page 4


Internal
• Add / Configure a CB
1) Circuit Breaker can be added at Bay level in Electric hierarchy.
CB 3 phases (1 DPS for global position) / CB 1 phase (single phase acq.)

2) CB attributes
Short Name :
SCE Key + appears in viewers + printers

CB Type :
3-ph = 3 phases together,
1-ph = 3 separated phases
Other : do not use
(Think about AutoRecloser 1P 3P 3P)

Nodes definition :
For ATCC, AVR, IEC topological model in SCD
(iFLS)

Confidential Property of Schneider Electric | Page 5


Internal
• CB-1ph Configuration (1)
1) CB 1 phase basic configuration
1.1) Type 1
Typed Switch Ctrl DPC :
DPC Open/Close

Typed CB Computed Position DPS :


- Global CB Position, computed by C264
- is feedback of DPC command
- is animated on PACiS HMI / C264 LCD

Typed Switchgear ph A,B,C wired DPS/SPS :


CB single phase position, acquired by C264
(DI/CCU or IED)

1.2) Type 2
Position can be computed by :
- typed Switch ph A DPS
- typed Phases Not Together SPS

Note : Positions can be SPS


Confidential Property of Schneider Electric | Page 6
Internal
• CB-1ph Configuration (2)
2) CB enhanced configuration => possible sons
Typed Sync CB Close :
Synchrocheck

Typed Lock Control SPC :


Operator lock
Typed Selection SPC :
when SBO, activated at selection

Typed Lock SPS :


Lock status

Typed Phase Not Together SPS :


- Indicates if all phases are in same position
- holds a timer for CB trip

Typed withdrawn SPS :


brushable devices (for HMI brushable position
info )

Confidential Property of Schneider Electric | Page 7


Internal
• CB-3ph Configuration
1) CB 3 phases basic configuration (most common)
1.1) Type 1
Typed Switch Ctrl DPC :
DPC Open/Close

Typed CB Computed Position DPS :


- Global CB Position, computed by C264
- is feedback of DPC command
-is animated on PACiS HMI / C264 LCD
-is used in Interlock FBDs
Typed Switchgear position wired DPS :
CB Position, acquired by C264 (DI/CCU or IED)
Today always profile without HMI archive (no IEC
1.2) Type 2 adrs)
Typed Switch Ctrl DPC can be replaced by :
- typed Switch Ctrl SPC for CLOSE
- typed Switch ph A SPC for OPEN

Note : Positions can be SPS


Confidential Property of Schneider Electric | Page 8
Internal
• Content

▪ Circuit Breaker
▪ Disconnector Switch
▪ Transformer
▪ Generic Module

Confidential Property of Schneider Electric | Page 9


Internal
• Add / Configure a Disconnector Switch
1) Disconnector switch is a Switchgear, it can be added at Bay level in
Electric hierarchy.

2) DS attributes
Short Name :
SCE Key + appears in viewers + printers

Nodes definition :
AVR

Confidential Property of Schneider Electric | Page 10


Internal
• Switchgear Configuration (1)
1) Switchgear basic configuration
Typed Switch Ctrl DPC :
DPC Open/Close

Typed Switchgear position DPS :


Switchgear Position, acquired by C264
(DI/CCU or IED)

Q1 is a Switchgear object with position status


Wired to DI board in this example

Note : Position can be SPS


Confidential Property of Schneider Electric | Page 11
Internal
• Switchgear Configuration (2)
2) Switchgear enhanced configuration => possible sons
Typed Lock Control SPC :
Operator lock

Typed Selection SPC :


when SBO, activated at selection

Typed Lock SPS :


Lock status

Typed withdrawn SPS :


brushable devices

Confidential Property of Schneider Electric | Page 12


Internal
• Content

▪ Circuit Breaker
▪ Disconnector Switch
▪ Transformer
▪ Generic Module

Confidential Property of Schneider Electric | Page 13


Internal
• Add / Configure a Transformer
1) Transformer module can be added at Transformer or Generic Bay level in
Electric hierarchy.

2) Transformer attributes
Short Name :
SCE Key + appears in viewers + printers

Transformer Type :
- Auto wound : no galvanic isolation between HV
and LV sides, tap changer acts simultaneously in
primary and secondary : TAP RAISE = LV LOWER
- Double wound : galvanic isolation between HV
and LV sides, tap changer acts in primary : TAP
RAISE = LV RAISE

Power value / impedance :


AVR

Nodes definition :
AVR
Confidential Property of Schneider Electric | Page 14
Internal
• Transformer Configuration (1)
1) Transformer basic configuration

Tap Changer built-in function:


cf. DATAPOINTS CONFIGURATION course

Typed Raise/Lower DPC :


Tap Change control

Typed TPI MV :
cf. DATAPOINTS CONFIGURATION course

Confidential Property of Schneider Electric | Page 15


Internal
• Transformer Configuration (2)
2) Transformer enhanced configuration => possible sons
Typed MCB Open SPC :
- AVR
- In case of invalid tap changing, it will stop
supplying tap changer (power cutting)

Typed TAP Select SPC :


when SBO, activated at selection
Typed Higher Position / Lower Position SPS
:
- SET when max tap and min tap are reached
Typed Tap in progress SPS :
- physically acquired by C264
- impact on control sequence

Typed Goto min/max DPC :


DPC doing raise until max tap / lower until min
tap

Confidential Property of Schneider Electric | Page 16


Internal
• Content

▪ Circuit Breaker
▪ Disconnector Switch
▪ Transformer
▪ Generic Module

Confidential Property of Schneider Electric | Page 17


Internal
• Features
1) Generic Modules are :
- non typed modules
- contains generic datapoints
- huge range of use => non particular context

Example for switching device

- ADVICE : DON’T USE GENERIC MODULES but TYPED MODULES for CB


and disconnector if you have :
- Built-in automation (AVR, Synchrocheck, Autorecloser)
- lock, hardware selection, withdrawn

Confidential Property of Schneider Electric | Page 18


Internal
Internal
Internal