Full Voltage Conversion From 120V To 220V at House Type 3Tr3S (Internal Works)
Full Voltage Conversion From 120V To 220V at House Type 3Tr3S (Internal Works)
NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
PMT OPRNS
SAUDI ARABIAN OIL COMPANY
AG-0012
ENGG CERT
DESCRIPTION
JO/EWO
SCOPE OF WORK
NO. DATE
REV
DISCIPLINE
ENGINEER
BOS
FULL VOLTAGE CONVERSION FROM
120V TO 220V AT HOUSE TYPE 3TR3S
DATE: 8-23-17
PROJECT
ENGINEER
(INTERNAL WORKS)
AFB
DATE:
8-24-17
CERTIFIED
00-00-16
HAK
DATE:
8-24-17
CONSTRUCTION
AGENCY
SIM
9-20-17
DATE:
OPERATIONS
ASB
DATE:
9-25-17
RAS TANURA
CONTROL NUMBER
VERIFICATION
EDSD
DATE:
BY:
SCOPE OF WORK DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION
This Project shall be carried out in accordance with the Contract Terms
and Conditions, Scope of Work, Drawings, Standards, Specifications
DATE
DISCIPLINE
ENGINEER
BOS PART I - SOLICITATION PROVISIONS
DATE: 8-23-17
PROJECT
ENGINEER PART II - GENERAL REQUIREMENTS
AFB
DATE:
8-24-17 PART III - DETAILED WORK DESCRIPTIONS
CERTIFIED
00-00-16
HAK
PART IV - CONSTRUCTION SPECIFICATION
DATE:
8-24-17
CONSTRUCTION
AGENCY PART V - DRAWING COMPLETION CERTIFICATE
SIM
9-20-17
DATE:
OPERATIONS
ASB
DATE:
9-25-17
CONTROL NUMBER
VERIFICATION
EDSD
DATE:
BY:
REVISIONCERTIFICATION
APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
CERTIFICATE
SCOPE OF WORK DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION
DATE:
DATE:
DATE:
DATE:
DATE:
THIS INDICATES THAT REV. NO.__________
OF THIS DRAWING IS COVERED, FOR ALL
CONTROL NUMBER
SIM
ASB
APPROVAL/CERTIFICATION REQUIREMENTS,
AFB
HAK
BOS
AGENCY
BY:
PROJECT
BY DRAWING COMPLETION CERTIFICATE
ENGINEER
ENGINEER
DISCIPLINE
8-24-17
CERTIFIED
9-20-17
8-24-17
8-23-17
9-25-17
OPERATIONS
00-00-16
CONSTRUCTION
(DCC) NO. _____________________ 17U092-092 DATE:
RAS TANURA
(AG-0012 EGG/CBP) ISSUE DATE: 10-08-2017
100%
RESIDENTIAL AREA
SCOPE OF WORK
3.0
2.0
1.0
SAUDI ARABIA
MATERIALS
S65
TABLE OF CONTENTS
BID SUBMISSSION
A
DWG.TYPE PLANT NO. INDEX
JO/EWO: 17U092
SAUDI ARABIAN OIL COMPANY
SPECIFIC INSTRUCTIONS
PART- I: SOLICITATION PROVISIONS
RE-778890
DRAWING NO.
3
of
105
SHT.NO.
00
REV.NO.
THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
PMT OPRNS
SAUDI ARABIAN OIL COMPANY
1.1 CONTRACTOR shall submit a Lump Sum Bid to supply all labor, permanent,
temporary and expendable materials and equipment including spare parts
required for the completion of the WORK as shown on the Bid Drawings and/or
described in the Scope of Work.
1.3 CONTRACTOR acknowledge that (1) it has fully understood all requirements to
satisfactorily complete the WORK, (2) it had the opportunity to request
clarification prior to submitting the Bid as described in Paragraph 1.2 above, and
(3) that the Bid include all the cost of completing the project and all incidental
JO/EWO
1.4 Any failure of the CONTRACTOR to take the actions required and acknowledged
in this Solicitation Provision will not relieve the CONTRACTOR from
NO.
REV
APPROVAL/CERTIFICATION REQUIREMENTS,
approval from the SAUDI ARAMCO Project Engineer to any deviation from
THIS INDICATES THAT REV. NO.__________
CERTIFICATE
SCOPE OF WORK DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION
2.4 Materials will be taken to site only as required and will not be stockpiled at the
DESCRIPTION
site.
3.1.1 This Specific Instructions must be read in conjunction with the drawings as
listed in Drawing Control Sheet No. RD-778891, Sheet No. 1 of 1, Rev.
DATE
3.1.2 It is the intent of the Scope of Work to generally describe the major
NO.
REV
3.2 Site Investigation, Field Dimensions and Conditions Affecting the WORK
DATE:
BY:
REVISIONCERTIFICATION
ascertain the nature and location of the WORK and it has thoroughly
(DCC) NO. _____________________
inspected and investigated the work site and satisfied itself regarding all
17U092-092
general and local conditions and its surrounding areas, which can affect
SCOPE OF WORK DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION
3.2.3 Field dimensions shall prevail over those in the drawings. CONTRACTOR
shall check and verify all measurements and dimensions at the
construction area for their accuracy prior to submission of bid and shall
immediately report any discrepancies to Saudi ARAMCO Project Engineer
for resolution within the bid clarification period. Following award, no extra
charge or compensation will be allowed on account of differences in actual
JO/EWO
3.3.1 CONTRACTOR shall preserve and protect all structures, equipment and
DISCIPLINE
ENGINEER vegetation (plants, trees, shrubs and grass) on and adjacent to the work
BOS
sites, which are not to be removed and which do not unreasonably
DATE: 8-23-17
PROJECT interfere with the WORK. Any item that is damaged or marred as a direct
ENGINEER
AFB or indirect result of the WORK shall be restored to its original state by the
DATE:
8-24-17 CONTRACTOR at no expense to SAUDI ARAMCO.
CERTIFIED
00-00-16
HAK
8-24-17 3.4 Workmanship
DATE:
CONSTRUCTION
AGENCY
SIM 3.4.1 All WORK shall be performed in skillful, workmanlike and safely manner in
DATE:
9-20-17 accordance with SAUDI ARAMCO Construction Safety Manual, the
OPERATIONS relevant General Instructions and SAUDI ARAMCO Codes and Standards.
ASB
9-25-17
DATE: 3.4.2 CONTRACTOR is held responsible to complete the project in accordance
CONTROL NUMBER
VERIFICATION
with the details and requirements of the Scope of Work as shown in the
EDSD
with the drawing(s), Scope of Work and all SAUDI ARAMCO Codes,
(DCC) NO. _____________________
SCOPE OF WORK DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION
3.5.1 Keep the area of WORK and surrounding premises free from accumulation
of waste materials or rubbish caused by the WORK at all times. Each day,
CONTRACTOR shall remove from the Work Site all waste materials, and
leave the Work Site in a neat and broom-clean condition. Upon completion
of WORK, CONTRACTOR shall remove from the Work Site waste
materials, rubbish, tools, construction equipment, machinery and surplus
material, and thoroughly clean the Work Site, leaving it in a neat and
broom-clean condition.
DESCRIPTION
DISCIPLINE
ENGINEER
BOS
DATE: 8-23-17
PROJECT
ENGINEER
AFB
DATE:
8-24-17
CERTIFIED
00-00-16
HAK
DATE:
8-24-17
CONSTRUCTION
AGENCY
SIM
9-20-17
DATE:
OPERATIONS
ASB
DATE:
9-25-17
CONTROL NUMBER
VERIFICATION
EDSD
DATE:
BY:
REVISIONCERTIFICATION
APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
CERTIFICATE
SCOPE OF WORK DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION
DATE:
DATE:
DATE:
DATE:
THIS INDICATES THAT REV. NO.__________
OF THIS DRAWING IS COVERED, FOR ALL
CONTROL NUMBER
SIM
ASB
APPROVAL/CERTIFICATION REQUIREMENTS,
AFB
HAK
BOS
AGENCY
BY:
PROJECT
BY DRAWING COMPLETION CERTIFICATE
ENGINEER
ENGINEER
DISCIPLINE
8-24-17
CERTIFIED
9-20-17
8-24-17
DATE: 8-23-17
9-25-17
OPERATIONS
00-00-16
CONSTRUCTION
(DCC) NO. _____________________ 17U092-092 DATE:
RAS TANURA
(AG-0012 EGG/CBP) ISSUE DATE: 10-08-2017
100%
RESIDENTIAL AREA
SCOPE OF WORK
2.0
1.0
SAUDI ARABIA
WORK SCHEDULE
TABLE OF CONTENTS
S65
SAFETY REQUIREMENTS
A
DWG.TYPE PLANT NO. INDEX
JO/EWO: 17U092
PART – II: GENERAL REQUIREMENTS
SAUDI ARABIAN OIL COMPANY
RE-778890
DRAWING NO.
8
of
105
SHT.NO.
00
REV.NO.
THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
PMT OPRNS
SAUDI ARABIAN OIL COMPANY
1.1 The area of WORK is within the residential areas; thus, WORK will be done with
minimal disturbance to residents, which will be agreed by the Saudi ARAMCO
Project Engineer and CONTRACTOR during the project kick-off meeting.
1.1.1 Saudi ARAMCO Project Engineer shall coordinate with the Proponent to
establish sequence of the WORK, schedule of work and/or working
time.
1.1.2 CONTRACTOR shall meet with the Saudi ARAMCO Project Engineer to
DESCRIPTION
2.1 Introduction
APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
CERTIFICATE
SCOPE OF WORK DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION
SAUDI ARAMCO reserves the right to monitor and inspect any WORK
site, laydown yard, fabrication yard, clinic, camp and dining facility (On
or Off SAUDI ARAMCO property) for compliance with the above
references Safety, Health and Environmental Requirements. SAUDI
ARAMCO reserves the right to reject, remove from site, or have
CONTRACTOR destroy any tools or equipment found to be defective or
of substandard quality. “Homemade”, including “shop-made”, tools are
strictly prohibited.
DESCRIPTION
2.3.1 CONTRACTOR has overall responsibility for a full time safety in and out
BY:
APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
CERTIFICATE
(WSSM).
17U092-092
SCOPE OF WORK DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION
CONTRACTOR shall provide full time and qualified site safety staff in
accordance to the requirements of Volume I Paragraph 4.5 of the
SAUDI ARAMCO CSM or as otherwise required by the SAUDI
ARAMCO Project Engineer during Job Explanation Meeting.
DISCIPLINE
ENGINEER
A. CONTRACTOR shall provide all required Safety Harness and
BOS proper PPE that meets SAUDI ARAMCO specification to its
DATE: 8-23-17 employees in accordance with Volume I Paragraph 4.8 and
PROJECT
ENGINEER Volume II Paragraph 3.0 of the SAUDI ARAMCO CSM.
AFB
DATE:
8-24-17 2.3.5 Work Permit
CERTIFIED
00-00-16
HAK
A. CONTRACTOR shall obtain and complete all required Work
8-24-17
DATE: Permits in accordance with Volume I Paragraph 4.12 and Volume
CONSTRUCTION
AGENCY II, Part I Paragraph 4. of the SAUDI ARAMCO CSM as per the
SIM minimum guidelines and responsibilities set forth in SAUDI
DATE:
9-20-17
ARAMCO General Instruction manual, GI 2.100 “Work Permit
OPERATIONS System”.
ASB
DATE:
9-25-17 B. CONTRACTOR Work Permit Receiver shall have a valid SAUDI
CONTROL NUMBER
SCOPE OF WORK DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION
APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
CERTIFICATE
SCOPE OF WORK DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION
2.3.9 Medical
attendant(s).
VERIFICATION
EDSD
APPROVAL/CERTIFICATION REQUIREMENTS,
at the Work Site who are trained and certified in First Aid and
THIS INDICATES THAT REV. NO.__________
CERTIFICATE
SCOPE OF WORK DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION
SAPO name
JO/EWO
Project title
DATE
NO.
REV
APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
CERTIFICATE
SCOPE OF WORK DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION
2.3.13 Asbestos
APPROVAL/CERTIFICATION REQUIREMENTS,
public.
(DCC) NO. _____________________
SCOPE OF WORK DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION
TABLE OF CONTENTS
2.0 ARCHITECTURAL
6.0 ELECTRICAL
DISCIPLINE
ENGINEER
BOS 7.0 PROVISIONAL QUANTITIES
DATE: 8-23-17
PROJECT
ENGINEER 8.0 DRAWINGS
AFB
DATE:
8-24-17
CERTIFIED
00-00-16
HAK
DATE:
8-24-17
CONSTRUCTION
AGENCY
SIM
9-20-17
DATE:
OPERATIONS
ASB
DATE:
9-25-17
CONTROL NUMBER
VERIFICATION
EDSD
DATE:
BY:
REVISIONCERTIFICATION
APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
CERTIFICATE
SCOPE OF WORK DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION
1.1 This Scope of Work describes the voltage conversion from existing 208/120 Volts
to 400/230 Volts and upgrading all electrical installations including kitchen
equipment and HVAC equipment suit new voltage at House Type 3TR3S, Ras
Tanura:
1.2 The WORK includes but not necessarily limited to the following:-
1.2.2 Replacement of existing NEMA type power outlets with new BS-1363
Type, 13A, 250 Volts (RCD for wet areas).
1.2.4 Provision of new 250 Volts switches of new garbage disposer, water
heaters, washing machine and clothes drier, and range.
DATE
DISCIPLINE
ENGINEER
1.2.6 Replacement of fluorescent tubes and starter of the two lighting fixtures
BOS at the kitchen with new T-8 LED tubes and new electronic energy
DATE: 8-23-17 miser/universal voltage ballast respectively.
PROJECT
ENGINEER
AFB 1.2.7 Megger testing of all existing power and lighting wires prior to re-use,
DATE:
8-24-17 inclusive of replacement of wires with damaged insulations.
CERTIFIED
00-00-16
HAK
1.2.8 Provision of neutral lines directly from the outlets and lighting luminaires
8-24-17
DATE: to the panel board and rectifying circuits with common neutral.
CONSTRUCTION
AGENCY
SIM 1.2.9 Replacement of branch circuits, including conduits and wires to suit new
9-20-17
DATE: service.
OPERATIONS
ASB 1.2.10 Replacement of existing garbage disposer, sweet water heater, range
DATE:
9-25-17 hood and exhaust fans.
CONTROL NUMBER
VERIFICATION
1.2.12 Complete replacement of existing smoke alarm including new 220 Volts
REVISIONCERTIFICATION
multi station photoelectric smoke alarm at hallways (1st and 2nd floor) and
APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
CERTIFICATE
transformer.
17U092-092
SCOPE OF WORK DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION
1.3 SAUDI ARAMCO will replace all single phase appliances rated 208/120 volts
with new appliances rated not less than 220 volts.
ENGG CERT
1.5 Project Engineer shall coordinate with proponent for the provision of tags and
asset numbers for all new equipment installed.
CONTRACTOR shall:
2.1 Cut portion of existing floors, interior wall and ceiling linings affected by the
WORK.
2.2 All conduit and pipe penetrations in fire walls shall be sealed with UL listed
ARAMCO approved fire stop materials and shall be equal or greater than the fire
rated wall.
JO/EWO
2.3 Make good floors exterior and interior walls, and ceiling directly or indirectly
affected by the WORK to match adjacent existing surfaces.
DATE
3.1 General
DISCIPLINE
ENGINEER
BOS CONTRACTOR shall
DATE: 8-23-17
PROJECT
ENGINEER 3.1.1 Verify existing site condition, dimension and coordinate with the
AFB “Authority Having Jurisdiction” prior to start of any works.
DATE:
8-24-17
CERTIFIED
00-00-16
3.2 Removal/Demolition Works (Refer to Drawing No. RA-778889, Sheet No. 001-
HAK
Revision No. 00)
DATE:
8-24-17
CONSTRUCTION
AGENCY CONTRACTOR shall
SIM
9-20-17
DATE: 3.2.1 Remove existing ACCU and AHU.
OPERATIONS
APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
CERTIFICATE
SCOPE OF WORK DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION
3.3 New Works - Equipment Installation (Refer to Drawing No. RA-778889, Sheet
No. 001 & 002-Revision 00).
CONTRACTOR shall:
3.3.3 Fabricate and install new duct take-off with flexible machine connection
between new AHU and existing main ducts.
3.3.4 Install new condensate drain pipe complete with P-Trap from the new
AHU to the existing drain pipe.
3.3.5 Install new exhaust fans inclusive of required duct and connect to
existing exhaust duct.
JO/EWO
3.4 Refrigerant Lines New Works (Refer to Drawing No. RA-778889, Sheet No.
NO.
REV
3.5.1 Perform pressure test on the refrigerant pipe lines in accordance with
VERIFICATION
STD 15. The required test pressure shall be maintained for a minimum
of 10 minutes.
DATE:
BY:
REVISIONCERTIFICATION
3.5.2 Leak test and vacuum test refrigerant pipe lines in accordance with
APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
CERTIFICATE
SCOPE OF WORK DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION
4.1 General
CONTRACTOR shall:
DESCRIPTION
4.1.1 Shut-off isolation valves serving the area prior to start of any plumbing
work.
CONTRACTOR shall
DISCIPLINE
ENGINEER
BOS 4.2.1 Remove existing electric sweet water heater.
DATE: 8-23-17
PROJECT
ENGINEER 4.2.2 Remove existing garbage disposer.
AFB
DATE:
8-24-17 4.3 New Works
CERTIFIED
00-00-16
HAK
4.3.1 Install new 20 gallons electric sweet water heater complete with ball
8-24-17
DATE: valves, fittings and fiberglass grating.
CONSTRUCTION
AGENCY
SIM 4.3.2 Install new garbage disposer.
9-20-17
DATE:
OPERATIONS 5.0 FIRE ALARM
ASB
DATE:
9-25-17 5.1 General
CONTROL NUMBER
VERIFICATION
5.1.1 Conduct site survey and verify existing detection alarm installation in
EDSD
APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
CERTIFICATE
SCOPE OF WORK DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION
5.2 Option 1 (As per Item No. 4 of Section 7.0 “Provisional Quantities”)
ENGG CERT
CONTRACTOR shall:
5.2.2 New Work (Refer to Drawing No. HA-003315, Sheet No. 001 & 002-
DESCRIPTION
CONTRACTOR shall:
DISCIPLINE
ENGINEER
5.2.2.4 Connect/tap the new circuit wires to the new panelboard.
BOS
DATE: 8-23-17 5.3 Option 2 (As per Item No. 5 of Section 7.0 “Provisional Quantities”)
PROJECT
ENGINEER
AFB 5.3.1 New Work (Refer to Drawing No. HA-003315, Sheet No. 002-Revision
DATE:
8-24-17 No. 00)
CERTIFIED
00-00-16
HAK
CONTRACTOR shall:
DATE:
8-24-17
CONSTRUCTION
AGENCY 5.3.1.1 Install new enclosed step down transformer complete with
SIM required fixing supports.
9-20-17
DATE:
OPERATIONS 5.3.1.2 Connect/tap the new circuit wires to the new panelboard.
ASB
DATE:
9-25-17 5.4 Testing & Commissioning
CONTROL NUMBER
VERIFICATION
CONTRACTOR shall:
EDSD
5.4.1 Conduct insulation resistance test and continuity test for new wirings
DATE:
BY:
APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
CERTIFICATE
5.4.2 Conduct test and commission the newly installed fire detection devices
(DCC) NO. _____________________
SCOPE OF WORK DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION
6.0 ELECTRICAL
6.1 General
6.1.1 Conduct site visit to thoroughly familiarize with all details of the work
and working conditions, check location of electrical distribution system
and advice the SAUDI ARAMCO Project Engineer of any discrepancy.
DESCRIPTION
6.1.4 All conduit and pipe penetrations in fire walls shall be sealed with UL
listed SAUDI ARAMCO approved fire stop materials and shall be equal
or greater than the fire rated wall.
DATE
ASB 6.1.6.3 Range Hood: 220V, 60Hz. variable speed fan, under cabinet
DATE:
9-25-17 type with integral lights, aluminum mesh filter, 280 CFM min.
CONTROL NUMBER
VERIFICATION
Phase.
DATE:
BY:
APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
CERTIFICATE
SCOPE OF WORK DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION
CONTRACTOR shall:
6.2.2 Disconnect and remove existing duplex receptacle outlets (120V) and
boxes.
6.2.5 Disconnect and remove existing washing machine, clothes dryer and
range outlets including boxes.
6.2.6 Disconnect and remove existing outlet for garbage disposal with switch,
dishwasher, refrigerator and freezer including wires and conduits.
JO/EWO
6.2.7 Disconnect and remove existing junction box of existing sweet and raw
water heater.
DATE
DISCIPLINE
ENGINEER
6.2.9 Disconnect and remove existing disconnect switches of duct heater
BOS including wires and conduits.
DATE: 8-23-17
PROJECT
ENGINEER 6.2.10 Disconnect and remove existing dimmer switch.
AFB
DATE:
8-24-17 6.3 New Work (Refer to Drawing No. RA-778884, Sheet No. 001-Revision No. 00;
CERTIFIED
00-00-16
RA-778885, Sheet No. 001-Revision No. 00; RA-778886, Sheet No. 001-
HAK
Revision No. 00; RA-778887, Sheet No. 001-Revision No. 00)
DATE:
8-24-17
CONSTRUCTION
AGENCY CONTRACTOR shall:
SIM
9-20-17
DATE: 6.3.1 Install new panelboard complete with fixing supports and fittings.
OPERATIONS
ASB 6.3.2 Install new disconnect switches for new ACCU & AHU.
DATE:
9-25-17
CONTROL NUMBER
6.3.3 Install new disconnect switches for existing duct heaters including
VERIFICATION
6.3.5 Install new duplex receptacle outlets with faceplate and boxes.
APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
CERTIFICATE
6.3.6 Install new RCD receptacle outlet with switch for garbage disposer
(DCC) NO. _____________________
SCOPE OF WORK DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION
6.3.7 Install new RCD receptacle outlet for dishwasher including conduit,
wires, boxes, supports and fittings.
ENGG CERT
6.3.8 Install new receptacle outlet for freezer and refrigerator including
conduit, wires, boxes, supports and fittings.
6.3.9 Install new duplex receptacle outlets with residual current devices
(RCD) with faceplate.
6.3.10 Install new duplex receptacle outlets with residual current devices
(RCD) weatherproof cover.
DESCRIPTION
6.3.11 Install new receptacle outlet with residual current devices (RCD) for
washing machine with faceplate.
6.3.12 Install new switches for washing machine and clothes dryer.
6.3.14 Install new switches for sweet and raw water heaters including supports
JO/EWO
and fittings.
6.3.16 Replace incandescent bulbs with new 230 Volts LED bulbs as per item
1 of Section 7.0 “Provisional Quantities”.
NO.
REV
DISCIPLINE
ENGINEER
BOS 6.3.17 Replace existing fluorescent tubes and ballasts of existing fluorescent
DATE: 8-23-17 fixtures at Kitchen Area with new T-8 LED tubes and electronic energy
PROJECT miser/universal voltage (120-240V) ballast, respectively (applicable to
ENGINEER
AFB
units where kitchen has fluorescent fixtures) as per item 2 of Section 7.0
8-24-17 “Provisional Quantities”.
DATE:
CERTIFIED
00-00-16
HAK 6.3.18 Conduct insulation resistance test and continuity test of all existing
DATE:
8-24-17 power and lighting cables; replace wires with damaged insulations as
CONSTRUCTION
AGENCY
per Item 3 of Section 7.0 “Provisional Quantities”.
SIM
DATE:
9-20-17 6.3.19 Provide neutral lines to all power and lighting luminaire circuits. Rectify
OPERATIONS circuits with common neutral.
ASB
9-25-17 6.3.20 All outlets boxes shall be provided with cable entrance protection and
DATE:
cable restraint appropriate for the existing cables.
CONTROL NUMBER
VERIFICATION
EDSD
6.3.21 Install Arc Flash and Shock Hazard Warning Labels on all new electrical
distribution equipment in accordance with current version of SAUDI
DATE:
APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
CERTIFICATE
6.4.1 Connect/tap all new power outlets and new circuit wires to the new
17U092-092
SCOPE OF WORK DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION
6.4.3 Conduct Panel board circuit breaker test (Trip test, contact resistance
and insulation resistance).
6.4.4 Conduct operational tests and Energize the system to ensure that
requirements are satisfactorily met in the presence of SAUDI ARAMCO
Project Engineer.
DESCRIPTION
7.1.2 CONTRACTOR shall allow for the following quantities in his Lump Sum
price.
DATE
2 number 10
miser/universal voltage (120-240V)
EDSD
of bulbs
ballast, respectively (applicable to
per
DATE:
House
fixtures) as per Paragraph 6.3.17.
REVISIONCERTIFICATION
APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
CERTIFICATE
SCOPE OF WORK DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION
Percent
of the
Fire Alarm Option No. 2 as per total
5 50
Section 5.3 above. number
of
Houses
ASB 8.1.1 Refer to Drawing Control Sheet No. RD-778891, Sheet No. 1 of 1, Rev.
9-25-17
DATE: No. 00.
CONTROL NUMBER
VERIFICATION
DATE:
8.2.1 Upon completion of all works, the CONTRACTOR shall submit one set
BY:
APPROVAL/CERTIFICATION REQUIREMENTS,
indicate all deviations from the contract Drawings and Scope of Work,
THIS INDICATES THAT REV. NO.__________
CERTIFICATE
SCOPE OF WORK DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION
DISCIPLINE
ENGINEER
BOS
DATE: 8-23-17
PROJECT
ENGINEER
AFB
DATE:
8-24-17
CERTIFIED
00-00-16
HAK
DATE:
8-24-17
CONSTRUCTION
AGENCY
SIM
9-20-17
DATE:
OPERATIONS
ASB
DATE:
9-25-17
CONTROL NUMBER
VERIFICATION
EDSD
DATE:
BY:
REVISIONCERTIFICATION
APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
CERTIFICATE
SCOPE OF WORK DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION
TABLE OF CONTENT
DIVISION 15 – MECHANICAL
DATE
DISCIPLINE
ENGINEER SECTION 15781 – AIR CONDITIONING UNIT
BOS
DATE: 8-23-17 SECTION 15870 – EXHAUST FANS
PROJECT
ENGINEER
AFB DIVISION 16 – ELECTRICAL
DATE:
8-24-17
CERTIFIED
00-00-16 SECTION 16010 - BASIC ELECTRICAL REQUIREMENTS
HAK
8-24-17
DATE:
SECTION 16111 – RACEWAY
CONSTRUCTION
AGENCY
SIM
SECTION 16123 – WIRES AND CABLES
9-20-17
DATE:
OPERATIONS
SECTION 16135 – CABINETS & BOXES
ASB
9-25-17
DATE: SECTION 16140 – WIRING DEVICES
CONTROL NUMBER
VERIFICATION
SCOPE OF WORK DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION
PART 1 - GENERAL
A. Products.
DESCRIPTION
E. Manufacturers
F. Conflicts.
JO/EWO
1.02 REFERENCES
DATE
SCOPE OF WORK DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION
each other.
E. Where available and complying with requirements, provide standard
products which have been used previously and successfully in similar
applications, and which are recommended by manufacturers for
applications indicated.
F. Product Selection Limitations. Comply with the following for the
selection of Products:
DESCRIPTION
DISCIPLINE
4. Prescriptive Requirements: Selection of product which has
ENGINEER been certified and tested by the manufacturer to comply with
BOS
requirements, including prescriptive requirements, is
DATE: 8-23-17
PROJECT
CONTRACTOR’s option where no names are indicated.
ENGINEER
AFB 5. Visual Requirements: Where indicated to be selected from
DATE:
8-24-17 manufacturer’s standard options, selection is SAUDI ARAMCO
CERTIFIED
00-00-16 Representative’s option, subsequent to determination or
HAK
8-24-17
selection of manufacturer (CONTRACTOR’s option). Where
DATE:
indicated to be selected from among standard options
CONSTRUCTION
AGENCY available within the industry, selection is SAUDI ARAMCO
SIM
Representative’s option prior to determination or selection of
9-20-17
DATE: manufacturer.
OPERATIONS
723 and shall have a flame spread index not greater than that
VERIFICATION
APPROVAL/CERTIFICATION REQUIREMENTS,
otherwise specified).
SCOPE OF WORK DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION
B. All shop fabrications and assemblies delivered at the job site shall be
DISCIPLINE
ENGINEER
inspected for proper identification, completeness, and free from
BOS damage by a qualified person on behalf of the CONTRACTOR. Any
DATE: 8-23-17 conflict noted between project material selection or specification and
PROJECT
ENGINEER SAES or SAMSS shall be brought to the attention of the SAUDI
AFB ARAMCO Representative in writing.
DATE:
8-24-17
CERTIFIED
00-00-16
C. Utility piping and piping materials, including fittings and welding
HAK
solvents, etc., shall be inspected prior to use in accordance with Para.
8-24-17
DATE: 7 of SAES-S-070.
CONSTRUCTION
AGENCY
SIM D. All equipment shipped with protective covers or plugs over openings,
9-20-17
DATE: and with rust preventive coatings applied to exterior machined and
OPERATIONS threaded surfaces, shall be treated upon arrival at the job site, as
ASB follows:
DATE:
9-25-17
CONTROL NUMBER
A. General
(DCC) NO. _____________________
17U092-092
DISCIPLINE
ENGINEER 8. All materials (soil materials excepted), stored outdoors shall be
BOS positioned off the ground and above ground water pooling by
DATE: 8-23-17 use of timbers, pallets, or other appropriate means.
PROJECT
ENGINEER
AFB 9. Arrange storage for accessibility to Products as needed for the
DATE:
8-24-17 Work to avoid unnecessary handling.
CERTIFIED
00-00-16
HAK 10. Protect and maintain installed Products and Work safe from
DATE:
8-24-17 damage or deterioration at all times prior to Mechanical
CONSTRUCTION Completion.
AGENCY
SIM
9-20-17
11. Assure that the designated shelf life of paints and other similar
DATE:
Products will not be exceeded before use. Approval to use
OPERATIONS
any Product which has exceeded its specified shelf life must
ASB
be obtained in writing from the SAUDI ARAMCO
9-25-17
DATE: Representative prior to use.
CONTROL NUMBER
VERIFICATION
APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
CERTIFICATE
SCOPE OF WORK DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION
DISCIPLINE
4. Piping and Conduit:
ENGINEER
BOS a. Utility piping and piping materials, including fittings and
DATE: 8-23-17 welding solvents, etc., shall be handled, transported,
PROJECT
ENGINEER and stored in accordance with SAES-S-070.
AFB
8-24-17 b. All ends of piping shall be closed with temporary caps
DATE:
CERTIFIED or covers to prevent intrusion of debris, sand, water,
00-00-16
HAK etc.
DATE:
8-24-17
CONSTRUCTION
c. Avoid overstacking of PVC piping or conduit to prevent
AGENCY distortion.
SIM
9-20-17
DATE: d. Keep PVC and conduit out of direct sunlight by cover
OPERATIONS or inside storage.
ASB
DATE:
9-25-17 5. Cables:
CONTROL NUMBER
VERIFICATION
sunlight.
DATE:
BY:
moisture.
17U092-092
SCOPE OF WORK DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION
6. Welding electrodes:
ENGG CERT
7. Paint Materials:
PART 2 PRODUCTS
EDSD
DATE:
Not Used.
BY:
REVISIONCERTIFICATION
APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
CERTIFICATE
PART 3 EXECUTION
OF THIS DRAWING IS COVERED, FOR ALL
Not Used.
17U092-092
PART 1 - GENERAL
1.02 REFERENCES
connecting wiring of entire fire alarm system. Include wiring and riser diagrams.
Submittal shall be certified by a SAUDI ARAMCO approved registered
DATE:
BY:
APPROVAL/CERTIFICATION REQUIREMENTS,
(sealed/stamped review letter) from said engineer stating that all requisite
THIS INDICATES THAT REV. NO.__________
CERTIFICATE
SCOPE OF WORK DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION
(sealed/stamped review letter) from said engineer stating that all requisite
drawings/documents/calculations have been satisfactorily reviewed.
C. Maintenance Data: Submit maintenance data and parts lists for each type of fire
alarm, emergency voice evacuation and gas leak detection equipment installed,
including furnished specialties and accessories. Include this data, product data,
and shop drawings in maintenance manual; in accordance with requirements of
Division 1.
DESCRIPTION
D. Fire layout drawings detailing fire zones, alarm zones and all fire devices shall be
provided by CONTRACTOR for approval by Company.
A. System Installers.
2. Qualified personnel shall include, but not limited to, one or more of the
following:
NO.
REV
DISCIPLINE
ENGINEER
a. Personnel who are factory trained and certified for fire alarm system
BOS installation of the specific type and brand of system being installed.
DATE: 8-23-17
PROJECT
ENGINEER b. Personnel who are certified by recognized certification organization
AFB acceptable to SAUDI ARAMCO.
DATE:
8-24-17
CERTIFIED
00-00-16
B. Codes and Standards
HAK
8-24-17
DATE: 1. NEC Compliance: Comply with applicable requirements of NEC standards
CONSTRUCTION
AGENCY pertaining to fire alarm system.
SIM
9-20-17
DATE: 2. UL Compliance and Labeling: Comply with provisions of UL safety
OPERATIONS standards pertaining to fire alarm system; and provide products and
ASB components which are UL-listed and labeled.
DATE:
9-25-17
CONTROL NUMBER
FM-approved.
EDSD
A. Handle fire alarm equipment carefully to prevent damage, breaking, and scoring.
APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
CERTIFICATE
SCOPE OF WORK DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION
B. Store fire alarm equipment’s in clean, dry place. Protect from weather, dirt,
fumes, water, construction debris, and physical damage.
ENGG CERT
B. Upon Completion of the work the CONTRACTOR shall submit to the SAUDI
ARAMCO Project Engineer “As Built” drawings and supply operating manuals for
the systems/ Equipment used in the installation.
PART 2 - PRODUCTS
JO/EWO
A. Manufacturer(s) Reference(s):
NO.
REV
Website: www.honeywell.com
APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
CERTIFICATE
B. Recommended Vendor(s)/Supplier(s):
(DCC) NO. _____________________
17U092-092
SCOPE OF WORK DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION
Honeywell DTV
Dhahran Techno Valley (DTV) – Dhahran
ENGG CERT
DISCIPLINE
ENGINEER 2.02 GENERAL
BOS
DATE: 8-23-17
PROJECT
A. All equipment and materials to be used shall be of standard components,
ENGINEER
regularly manufactured, by only one manufacturer.
AFB
8-24-17
DATE: B. All systems and components shall have been thoroughly tested and proven in
CERTIFIED
00-00-16
HAK
actual size.
8-24-17
DATE:
CONSTRUCTION
C. All equipment shall be listed and labeled by Underwriter’s Laboratories and
AGENCY must be mutually compatible.
SIM
9-20-17
DATE:
2.03 FIRE ALARM SYSTEM
OPERATIONS
ASB
A. Fire Alarm Devices
DATE:
9-25-17
CONTROL NUMBER
1. Smoke Alarm: Photo Electric Type - Multi Station Smoke Alarm, Model
VERIFICATION
APPROVAL/CERTIFICATION REQUIREMENTS,
indicator, 60Hz. In compliance with NFPA 72, 2016 Edition and UL 217-
(DCC) NO. _____________________
PART 3 – EXECUTION
3.01 EXAMINATION
A. Examine areas and conditions under which fire alarm and gas leak detection
system are to be installed. Do not proceed with work until unsatisfactory
conditions have been corrected in manner acceptable to Installer.
JO/EWO
DISCIPLINE
ENGINEER
B. Wiring: Wiring of fire alarm system is work of this section, but is not specifically
BOS detailed on drawings.
DATE: 8-23-17
PROJECT
ENGINEER 1. Complete wiring in accordance with manufacturer's requirements. Color
AFB code wiring and install per manufacturer's point-to-point wiring diagram.
DATE:
8-24-17 Determine exact number of wires for each fire area zone from number
CERTIFIED
00-00-16
and types of devices installed. Connect each device with sufficient wiring
HAK
to complete its intended operation.
DATE:
8-24-17
CONSTRUCTION
AGENCY 2. Where there are a number of power requiring devices such as smoke
SIM detectors and smoke damper operators installed in a circuit, group in
9-20-17
DATE: numbers so power required does not exceed 80% of manufacturer's
OPERATIONS power supply rating. Provide extra wiring, or extra power supplies
ASB required to fulfill that requirement. In addition, provide extra or larger size
DATE:
9-25-17 wiring to alleviate voltage drops which makes device operate beyond
CONTROL NUMBER
respect to HVAC diffuser and building features to insure that devices will
REVISIONCERTIFICATION
operate properly.
APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
CERTIFICATE
devices shall be monitored for integrity. Low voltage (600V and below)
17U092-092
SCOPE OF WORK DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION
DISCIPLINE
ENGINEER
BOS
DATE: 8-23-17
PROJECT
ENGINEER
AFB
DATE:
8-24-17
CERTIFIED
00-00-16
HAK
DATE:
8-24-17
CONSTRUCTION
AGENCY
SIM
9-20-17
DATE:
OPERATIONS
ASB
DATE:
9-25-17
CONTROL NUMBER
VERIFICATION
EDSD
DATE:
BY:
REVISIONCERTIFICATION
APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
CERTIFICATE
SCOPE OF WORK DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION
DIVISION 15 – MECHANICAL
ENGG CERT
PART 1 - GENERAL
A. Plumbing Equipment
1.02 REFERENCES
DISCIPLINE
ENGINEER SAES-S-060 Saudi ARAMCO Plumbing Code
BOS
8-23-17
DATE:
Floor-Affixed Supports For Off-The-Floor Plumbing
PROJECT ASME A112.6.1 M-12
ENGINEER Fixtures For Public Use
AFB
DATE:
8-24-17
CERTIFIED
ASME A112.18.1-12 Finished and Rough Brass Plumbing Fixture Fittings.
00-00-16
HAK
8-24-17
DATE: ASME A112.19.1-13 Enameled Cast Iron Plumbing Fixtures.
CONSTRUCTION
AGENCY
SIM
9-20-17 ASME A112.19.2 -13 Ceramic Plumbing Fixtures -
DATE:
OPERATIONS
DATE:
APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
CERTIFICATE
SCOPE OF WORK DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION
1.03 SUBMITTALS
A. Maintenance Data: Include fixture trim exploded view and replacement parts
lists.
DATE
A. Electric Water Heater: 20 gallons capacity, vertical 150 psi working pressure
EDSD
glass lined tank; incoloy immersion heating elements; thermostats & high
temperature cut-off; T & P relief valve; magnesium anode; foam insulation
DATE:
BY:
per NAECAS. 90; baked enamel sheet metal jacket; drain valve; ANSI/UL-
REVISIONCERTIFICATION
Energy factor, 3/4” NPT inlet & outlet. Manufacturer Reference– AO Smith
OF THIS DRAWING IS COVERED, FOR ALL
or approved equal.
(DCC) NO. _____________________
17U092-092
SCOPE OF WORK DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION
safety 1:2.
B. Garbage Disposal (Sink Erator): with 2-stage grind and auto reverse grind
system stainless steel grind chamber, grinding element, 0.70Hp, 220-240V,
60Hz, 380Watts, 1725RPM. Manufacturer Reference Model: Evolution 100.
A. BINEX
P.O. Box 2194, Al Khobar 31952, KSA
NO.
REV
E-mail: [email protected]
DATE:
BY:
SCOPE OF WORK DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION
E-mail: [email protected]
PART 3 - EXECUTION
NO.
REV
DISCIPLINE
ENGINEER
3.01 EXAMINATION
BOS
DATE: 8-23-17 A. Verify that walls and floor finishes are prepared and ready for installation of
PROJECT
ENGINEER fixtures.
AFB
DATE:
8-24-17 B. Verify that electric power is available and of the correct characteristics.
CERTIFIED
00-00-16
HAK
3.02 PREPARATION
DATE:
8-24-17
CONSTRUCTION
AGENCY A. Rough-in fixture piping connections in accordance with minimum sizes indicated
SIM in fixture rough-in schedule for particular fixtures.
9-20-17
DATE:
OPERATIONS 3.03 INSTALLATION
ASB
DATE:
9-25-17 A. Install in accordance with Saudi Aramco Sanitary Code.
CONTROL NUMBER
VERIFICATION
C. Install each fixture with a trap which shall be easily removable for servicing and
DATE:
BY:
cleaning.
REVISIONCERTIFICATION
APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
CERTIFICATE
E. Install and secure fixtures in place with wall supports and bolts.
17U092-092
SCOPE OF WORK DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION
F. Seal fixtures to wall and floor surfaces with sealant as specified in Section 07900,
color to match fixture.
ENGG CERT
G. Solidly attach water closets to floor with lag screws. Lead flashing is not
intended to hold fixture in place.
H. All piping penetrating a fire rated wall shall be installed in a metal sleeve which
shall be one size larger than the pipe. Escutcheons shall cover the wall opening
and sleeve.
(Fiberglass Reinforced Plastic Manhole and Access Cover with Frame) and
tested in accordance with SAES-S-070.
A. Confirm location and size of fixtures and openings before rough in and
installation.
3.05 ADJUSTING
JO/EWO
A. Adjust stops or valves to the intended water flow rate for plumbing fixtures to
prevent splashing, noise or overflow.
DATE
3.06 CLEANING
NO.
REV
DISCIPLINE
ENGINEER
A. At completion clean plumbing fixtures and equipment.
BOS
DATE: 8-23-17 3.07 PROTECTION AND FINISHED WORK
PROJECT
ENGINEER
AFB A. Do not permit use of fixtures until building is handed over to the proponent.
DATE:
8-24-17
CERTIFIED
00-00-16
HAK
DATE:
8-24-17
CONSTRUCTION
AGENCY
SIM - END OF SECTION 15440 - PLUMBING EQUIPMENT -
9-20-17
DATE:
OPERATIONS
ASB
DATE:
9-25-17
CONTROL NUMBER
VERIFICATION
EDSD
DATE:
BY:
REVISIONCERTIFICATION
APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
CERTIFICATE
SCOPE OF WORK DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION
DIVISION 15 – MECHANICAL
ENGG CERT
PART 1 – GENERAL
B. Refrigerant line
DESCRIPTION
D. Accessories
DISCIPLINE
ENGINEER
SAES-L-105 Piping Material Specifications
BOS
DATE: 8-23-17
PROJECT
SAES-L-108 Selection of Valves
ENGINEER
AFB
DATE:
8-24-17 SAES-S-040 Saudi ARAMCO Water System
CERTIFIED
00-00-16
HAK
DATE:
8-24-17 SAES-S-060 Saudi ARAMCO Plumbing Code
CONSTRUCTION
AGENCY
SIM SAMSS Saudi ARAMCO Material Systems Specifications
9-20-17
DATE:
OPERATIONS Saudi ARAMCO Heating, Ventilation and Air
SAES-K-001
ASB Conditioning (HVAC)
DATE:
9-25-17
SAES-K-100 SAUDI ARAMCO Mechanical (HVAC) Code.
CONTROL NUMBER
VERIFICATION
EDSD
APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
CERTIFICATE
AMCA 210-16
Aerodynamic Performance Rating
(DCC) NO. _____________________
17U092-092
SCOPE OF WORK DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION
ASHRAE Handbooks
Fundamentals and Refrigeration
ASHRAE STD 62.1-16 Ventilation for Acceptable Indoor Air Quality
design, external static pressure and sound rating. Fan curve shall be provided with
VERIFICATION
F. Description of heat exchangers including the cooling coil and condenser coil.
DATE:
BY:
REVISIONCERTIFICATION
SCOPE OF WORK DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION
K. Submit recommended spare parts list for each unit under this section. List shall
include part numbers, and description of each part, and the price of each part.
L. System Drawings
A. Units shall ship fully assembled on factory installed base rails/mounting legs up
REVISIONCERTIFICATION
to practical shipping and rigging limitations. Unit not shipped fully assembled
APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
CERTIFICATE
shall have tags and airflow arrows on each direction of airflow. Each section shall
have lifting lugs or shipping skid to allow for field rigging and final placement of
(DCC) NO. _____________________
section.
17U092-092
SCOPE OF WORK DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION
B. Deliver units to site with fan motors, sheaves, and belts completely assembled
and mounted in units.
ENGG CERT
C. Store units in clean dry place and protect from weather and construction traffic.
Handle unit carefully to avoid damage to components, enclosure and finish.
PART 2 - PRODUCTS
A. Air Cooled Condensing Unit (ACCU) unit Direct Expansion type: Model No.CX-
DESCRIPTION
B. Air Handling Unit (AHU): Model BY-10, vertical type discharge, 81,824 BTU/H
total cooling capacity, at 116°F outdoor temperature , 1 external static pressure
(Inches of H2O), Air flow capacity: 2,800 CFM; 400VAC, 3Phase, 60Hz. Blower
JO/EWO
Drive 2Hp, 710 RPM. EER 11.2; AHRI certified, Washable filter. Manufacturer
Reference- ZAMIL Air Conditioners or approved equal.
DATE
A. Sight Glass: Liquid/moisture indicator, wet/dry scale, glass with copper plate steel
DISCIPLINE
ENGINEER
body, UL, glass-in cap type, single port`
BOS
DATE: 8-23-17 B. Filter Drier: Refrigerant service, sealed, standard activated, UL and CSA listed.
PROJECT
ENGINEER Manufacturer Reference – Sporlan Valve Company or approved equal.
AFB
DATE:
8-24-17 C. Insulation (Refrigerant Pipe): 19 mm (3/4”) thick, elastomer cellular, flexible, Meet
CERTIFIED
00-00-16
ASTM 411, C534 Type 1, D 1056-00-2C1 and E84, density 48-96 kg/m3, 0.0353
HAK
W/M-K thermal conductivity @ 75ºF (24ºC) mean temperature. Manufacturer
8-24-17
DATE: Reference – K-FLEX USA or approved equal.
CONSTRUCTION
AGENCY
SIM D. Copper Tube with Flare Joints: liquid line size outside diameter and vapor line
9-20-17
DATE: outside diameter tube as per model; ASTM B280, type ACR, hard or annealed
OPERATIONS temper seamless copper tube, sealed ends, refrigeration tube, dehydrated, scale
ASB ad dirt free and sizes as shown on the drawing. Manufacturer Reference –
DATE:
9-25-17 Cambridge-Lee Industries Incorporated of approved equal.
CONTROL NUMBER
VERIFICATION
E. Refrigerant Pipe Cladding: 0.016” thick; sheet metal aluminum; GR Alloy 3003,
EDSD
ASTM B209; non-heat treatable; moderate strength and high corrosion resistant;
riveted and sealed water tight. Elbows shall be mitered.
DATE:
BY:
REVISIONCERTIFICATION
2.03 ACCESSORIES
APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
CERTIFICATE
A. Neoprene Isolators: Provide molded neoprene isolators having steel base plates
(DCC) NO. _____________________
with mounting holes and, at the top, steel mounting plates with mounting holes or
17U092-092
SCOPE OF WORK DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION
coded with molded letters or numbers or color coded for capacity identification.
Metal parts of neoprene elements shall be completely embedded in neoprene.
A. PVC, rigid, ASTM D-1785, schedule 40, plain ends, 60°C maximum
temperature 20 feet joints. Fittings: PVC, ASTM D-2467/pattern for solvent
cement joints, socket to male thread, 60°C maximum service temperature.
Solvent Cement: PVC to PVC pipe and fitting joints- ASTM D-2564, ABS to
ABS-D2235, ABS to PVC-D3138.
JO/EWO
A. Saudi Aircon
P.O. Box 1658 , Al-Ahsa 31982, K.S.A
NO.
REV
ASB D. PETRA
DATE:
9-25-17 Contact Person: Hussam Qattash
CONTROL NUMBER
SCOPE OF WORK DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION
3.01 INSPECTION
ENGG CERT
A. The unit shall have factory installed internal piping and wiring; refrigerant circuit
tested, dehydrated, sealed and shipped with holding charge of refrigerant.
C. The CONTRACTOR shall check the air conditioning unit for damage and/or
wrapping which may have occurred during transit.
DESCRIPTION
3.02 INSTALLATION
DATE
ASB
DATE:
9-25-17
CONTROL NUMBER
VERIFICATION
EDSD
DATE:
BY:
REVISIONCERTIFICATION
APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
CERTIFICATE
SCOPE OF WORK DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION
DIVISION 15 – MECHANICAL
ENGG CERT
PART 1 - GENERAL
A. Exhaust Fans
ASHRAE Handbooks
Fundamentals and Refrigeration
REVISIONCERTIFICATION
APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
CERTIFICATE
Systems
SCOPE OF WORK DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION
D. Seals: All fans must bear the AMCA certified rating seal.
1.04 SUBMITTALS
DATE
A. Test Reports: Submit 4 sets of data showing test reading and calculated results
of factory tests of fans. The data shall include:
NO.
REV
DISCIPLINE
ENGINEER
BOS 1. Description of Fan and Drive - (Make - size - type - arrangement).
DATE: 8-23-17
PROJECT 2. Motor nameplate data - (Volts - phase - Hertz - FLA - LRA - synchronous
ENGINEER
AFB
and full load speeds).
DATE:
8-24-17
CERTIFIED 3. Calculated results - m3/hr. (CMH) head pressures, efficiency at design
00-00-16
HAK conditions.
DATE:
8-24-17
CONSTRUCTION
AGENCY
B. Shop Drawings
SIM
DATE:
9-20-17 1. Submit shop drawings showing fan layout, housing, materials, gauges,
OPERATIONS dimensions, weights and installation details.
ASB
DATE:
9-25-17 2. Product Data
CONTROL NUMBER
VERIFICATION
SCOPE OF WORK DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION
5. UL Listing
a. Submit manuals.
PART 2 - PRODUCTS
NO.
REV
B. Warranty
EDSD
material and workmanship for a period of one (1) year from the purchase
REVISIONCERTIFICATION
date. Any units or parts which prove defective during the warranty period
APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
CERTIFICATE
2. The motor manufacturer shall warrant motors for a period of one (1) year.
17U092-092
SCOPE OF WORK DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION
2.03 IDENTIFICATION
A. Equipment Number
JO/EWO
APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
CERTIFICATE
SCOPE OF WORK DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION
DIVISION 16 - ELECTRICAL
ENGG CERT
PART 1 - GENERAL
A. General Provisions
DESCRIPTION
1. Electrical Services
2. Distribution Equipment.
3. Raceways
5. Conductors/Wires/Cables.
JO/EWO
6. Conduits.
DATE
7. Grounding.
NO.
REV
8. Wiring Devices.
DISCIPLINE
ENGINEER
BOS 9. Indoor Lighting System.
DATE: 8-23-17
PROJECT
ENGINEER 10. Self-Contained Smoke & CO Alarm
AFB
DATE:
8-24-17 1.02 REFERENCES
CERTIFIED
00-00-16
HAK
A. SAUDI ARAMCO STANDARDS
DATE:
8-24-17
CONSTRUCTION
AGENCY SAES SAUDI ARAMCO Engineering Standards
SIM
9-20-17
DATE: a. SAES-P-123 Lighting
OPERATIONS
c. SAES-P-111 Grounding
VERIFICATION
EDSD
APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
CERTIFICATE
SCOPE OF WORK DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION
UL Underwriters Laboratories.
DISCIPLINE
ENGINEER
1.03 DESCRIPTION OF SYSTEM
BOS
DATE: 8-23-17 A. Primary Power is 13.8 kV, 3Phase, 4wires, 60 Hz.
PROJECT
ENGINEER
AFB B. Secondary Power is 400Y/230V, 3Phase, 4wires, 60 Hz.
DATE:
8-24-17
CERTIFIED
00-00-16
C. Power for Three Phase motors is 400/230V, 60Hz or as shown on the drawings.
HAK
8-24-17
DATE: D. Power for equipment:
CONSTRUCTION
AGENCY
SIM 1. 230V, Single Phase, 60Hz
9-20-17
DATE:
OPERATIONS
2. 400V, 3Phase, 60Hz
ASB
DATE:
9-25-17 E. Indoor Lighting, 230V, unless otherwise shown on the drawings.
CONTROL NUMBER
VERIFICATION
1.04 DRAWINGS
EDSD
A. The drawings show the location and general arrangement of all electrical work
DATE:
BY:
and shall be followed as closely as actual building construction and work of other
REVISIONCERTIFICATION
APPROVAL/CERTIFICATION REQUIREMENTS,
B. The CONTRACTOR shall examine the drawings of other trades and shall verify
the conditions governing his work at the job site. He shall arrange his work
17U092-092
SCOPE OF WORK DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION
C. Verify the dimensions governing this work at the building site. No extra
compensation will be claimed or allowed on account of differences between
actual dimensions and those indicated on the drawings. Examine adjoining work,
on which this work is dependent for perfect efficiency and report any work which
must be corrected. No waiver of responsibility for defective work shall be claimed
or allowed due to the failure to report unfavorable conditions affecting this work.
Generally, the Architectural drawings take precedence in all matters pertaining to
electrical trades’ installation; however, all conflicts shall be reported to the SAUDI
ARAMCO Representative for review.
DESCRIPTION
A. The CONTRACTOR shall visit the site, examine and verify the conditions under
which his work must be conducted before submitting a proposal.
DATE
B. The submitting of a proposal implies that the CONTRACTOR has visited the site
and is conversant with the conditions under which his work must be conducted.
NO.
REV
DISCIPLINE
ENGINEER
C. The CONTRACTOR shall adequately protect and preserve all newly installed
BOS work.
DATE: 8-23-17
PROJECT
ENGINEER D. The Electrical CONTRACTOR shall consult with the SAUDI ARAMCO
AFB Representative as to the methods of carrying on the work so as not to interfere
DATE:
8-24-17 with any operations more than necessary; accordingly, all services lines shall be
CERTIFIED
00-00-16
kept in operation as directed and the services shall be interrupted or
HAK
disconnected at such times as will be designated by the SAUDI ARAMCO
8-24-17
DATE: Representative.
CONSTRUCTION
AGENCY
SIM E. The CONTRACTOR shall take all necessary precautions to protect the
9-20-17 equipment and personnel from damage or injury due to his carrying on of the
DATE:
OPERATIONS work and the area in which the CONTRACTOR is working must be kept as clean
ASB as possible at all times, with only a minimum amount of construction material at
DATE:
9-25-17 the site at one time.
CONTROL NUMBER
VERIFICATION
A. Carefully examine the drawings and specifications, visit the site of the work, and
(DCC) NO. _____________________
SCOPE OF WORK DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION
having jurisdiction over conduits, wires, pipes or other equipment, which are not
needed or which interfere in any manner with the execution of this work and
remove or protect such utilities or equipment as required by the parties having
jurisdiction over same.
C. If existing active or non-active services (which are not shown on plans) are
encountered that require location or disconnecting, provide proper handling of
these services, and do not proceed with the work until so authorized by the
SAUDI ARAMCO Representative.
DESCRIPTION
enclosed with fire restrained materials adequate to restore the fire rating of the
wall.
DATE
1. Distribution Panels.
DATE:
BY:
APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
CERTIFICATE
3. Disconnecting Switches
OF THIS DRAWING IS COVERED, FOR ALL
4. Lighting Switches
17U092-092
SCOPE OF WORK DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION
5. Outlets – Power
ENGG CERT
7. Lighting Fixtures
9. Wires/Cables
12. Floor and Wall Conduit Entrances Seals including Fire Stop Materials.
13. Grounding
and the equipment's feeder name and location and any special operational
notes, such as voltage, number of wires, phase etc.
NO.
REV
DISCIPLINE
ENGINEER
B. Nameplates shall be engraved laminated phenolic plastic with black letters on
BOS white background, unless specified to the contrary. The size of the nameplates
DATE: 8-23-17 shall be compatible with the application but not less than 1/4" letters.
PROJECT
ENGINEER Nameplates shall be attached by pop rivets or screws. When screws are used,
AFB length will be considered to ensure required spacing away from energized parts.
DATE:
8-24-17
CERTIFIED
00-00-16
C. Equipment identification shall be visible after installation without the need for
HAK
disturbing or being exposed to the interior parts or wiring. Titles and method
8-24-17
DATE: shall conform to equipment identification, as shown on the Drawings.
CONSTRUCTION
AGENCY
SIM D. Equipment identification nameplate titles and methods shall be submitted as
9-20-17
DATE: shop drawings for approval.
OPERATIONS
ASB E. Special tools required for any electrical equipment shall be clearly identified with
DATE:
9-25-17 that equipment.
CONTROL NUMBER
VERIFICATION
A. Determine the work to be performed by all other trades throughout the Contract
DATE:
BY:
to facilitate the electrical installation. Provide the type and amount of electrical
REVISIONCERTIFICATION
completely wired, tested, and ready for use. This shall include all conduits, wires,
motor starters, disconnects, relays, and all other devices for the required
(DCC) NO. _____________________
operation and control sequences of all electrical, mechanical, and other systems
17U092-092
SCOPE OF WORK DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION
B. Provide conduits and wires for all controls and other devices, for both high and
low voltage, described in this and other parts of the Construction Specification.
Install all control housing and junction boxes required for installing conduits and
wires to the controls except for controls such as solenoid valves, pressure
switches, damper motors, and other items which are to be installed in piping,
ducts, machinery, or other equipment supplied and fitted by others. Items shall
be installed by skilled workmen, thoroughly trained in the necessary crafts and
experienced in the work.
DESCRIPTION
C. Install control wiring in separate conduit between all heating, ventilating and air
conditioning sensing devices, control panels, and motor controls. Before
installing any conduit for heating, ventilating, and air conditioning control wiring,
verify from the control manufacturer's shop drawings where these separate
conduit runs are required and determine exact termination points for the specific
items to be wired, including but not limited to the following:
D. A "package system" is defined as any combination of equipment with all local and
DISCIPLINE
ENGINEER
remote instruments and controls required to perform a specialized function. In all
BOS "package systems" the responsibility for the electrical work shall remain with the
DATE: 8-23-17 "system" installer but the electrical work performed shall comply with the
PROJECT
ENGINEER provisions of Division 16. Work under this Division shall include bringing
AFB power to the main switch or panel of the "package system" at voltages available
DATE:
8-24-17 on site (see Item 1.04). Where other voltages or D.C are required, the
CERTIFIED
00-00-16
transformation or rectification of current shall be provided with the "package
HAK
system".
DATE:
8-24-17
CONSTRUCTION
AGENCY E. Install and connect all room thermostats, as required for the AC system
SIM
9-20-17
DATE: F. Install and connect all fan shutdown circuits as required for the fire alarm system.
OPERATIONS
A. All temporary lighting and power facilities shall be in accordance with the
VERIFICATION
purpose for which the wiring was installed. All circuits shall originate in an
approved power outlet or panel board. All cables shall be listed for hard or extra
(DCC) NO. _____________________
SCOPE OF WORK DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION
A. In general, mounting heights above finished floor to the centerline of outlet boxes
DESCRIPTION
A. Install all equipment in strict accordance with all directions and recommendations
BY:
furnished by the manufacturer. Where such directions are in conflict with the
REVISIONCERTIFICATION
APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
CERTIFICATE
Representative who shall determine the method or design criteria under which
(DCC) NO. _____________________
SCOPE OF WORK DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION
PART 2 - PRODUCTS
ENGG CERT
2.01 All products will comply as required by the SAUDI ARAMCO Material Specification
System (SAMSS).
PART 3 - EXECUTION
3.01 Electrical equipment shall be installed in a neat and workmanlike manner. Unused
openings in boxes, raceways, auxiliary gutters, cabinets, equipment case or housing
shall be effectively closed to afford proper protection, equivalent to the enclosure of the
DESCRIPTION
equipment. Conductors and conduits shall be racked to provide ready and safe
access at all openings into which persons enter for installation and maintenance with a
minimum 1M dead front distance in front of these openings and devices.
DISCIPLINE
ENGINEER
BOS
DATE: 8-23-17
PROJECT
ENGINEER
AFB
DATE:
8-24-17
CERTIFIED
00-00-16
HAK
DATE:
8-24-17
CONSTRUCTION
AGENCY
SIM
9-20-17
DATE:
OPERATIONS
ASB
DATE:
9-25-17
CONTROL NUMBER
VERIFICATION
EDSD
DATE:
BY:
REVISIONCERTIFICATION
APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
CERTIFICATE
SCOPE OF WORK DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION
DIVISION 16 - ELECTRICAL
ENGG CERT
PART 1 - GENERAL
B. Conduit support
1.02 REFERENCES
NEMA TC6 & 8-13 Extra-Strength PVC Plastic Utilities Duct for
APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
CERTIFICATE
Underground Installation
(DCC) NO. _____________________
SCOPE OF WORK DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION
b. NFPA70 Table 344.30 (B) (2): Support for Rigid Metal Conduit
UL Underwriters Laboratories
DISCIPLINE
ENGINEER
1.03 SUBMITTALS
BOS
DATE: 8-23-17 A. Before starting any installation of any materials or equipment, submit for approval
PROJECT
ENGINEER a complete list incorporated in the work. This list shall include catalog numbers;
AFB cuts, data sheets, and such other descriptive information as may be required.
DATE:
8-24-17
CERTIFIED
00-00-16
No consideration shall be given in partial list submitted. Approval of materials will
HAK
be based on manufacturer's published data, installation and roughing-in data
8-24-17
DATE: sheets and drawings indicating compliance with the Contract documents.
CONSTRUCTION
AGENCY
SIM B. All metric substitutes for Schedule 40 and 80 conduit and fittings shall be
9-20-17
DATE: submitted for approval.
OPERATIONS
ASB C. Listed/ Mark and labelled Compliance: Provide and comply Raceway and
DATE:
9-25-17 components which are UL/TUV/ENEC/BSI/ KEMA/KEUR-listed and labeled or
CONTROL NUMBER
approved equal.
VERIFICATION
EDSD
A. Protect all materials and equipment from damage or corrosion during handling
REVISIONCERTIFICATION
Requirements" for complete work scope. Provide appropriate covering for all
stored materials.
(DCC) NO. _____________________
17U092-092
SCOPE OF WORK DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION
PART 2 – PRODUCTS
2.01 MANUFACTURER
the following:
1. Conduit Bodies:
Appleton Electric Co. (NA 6106-01)
EGS-OZ Gedney/EGS Electrical Group (NN 1440-06)
Crouse-Hinds Divisions/Cooper Indust. (NC 6828-03)
ASCO (Japan) Co. Ltd. (TA 5505-01)
Saudi Conduit & Cabling Co. DS 3800-01)
Zamil Indust. Coatings (ZINCDO) (DZ6377-05)
JO/EWO
Square D Co.
Saudi Electric Industries Co; Ltd. (SEICO)
NO.
REV
WESCOSA
DISCIPLINE
ENGINEER
Other Approved Manufacturers
BOS
DATE: 8-23-17 2.02 CONDUITS
PROJECT
ENGINEER
AFB A. Galvanized Rigid Steel Conduit/ Electrical Metallic Tubing
DATE:
8-24-17
CERTIFIED
00-00-16
1. Shall be hot-dipped galvanized threads and their fittings, it can be installed at
HAK
exterior, interior area.
DATE:
8-24-17
CONSTRUCTION
AGENCY 2. Rigid Steel Conduit/Electrical Metallic Tubing: NEMA C80.1 and ASTM
SIM A123/A123M.
9-20-17
DATE:
OPERATIONS 3. Fittings and Conduit Bodies: NEMA FB 1; conduit fittings and supports shall
ASB be cast or forged steel, cast-iron or malleable iron, either hot-dipped
DATE:
9-25-17 galvanized (preferably) or zinc electroplated. No aluminum fittings shall be
CONTROL NUMBER
used.
VERIFICATION
EDSD
1. Shall be zinc coated, electrically metallic tube and their fitting shall be
REVISIONCERTIFICATION
SCOPE OF WORK DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION
2. Description: NEMA RN 1; rigid steel conduit with external PVC coating, 0.1
ENGG CERT
3. Fittings and Conduit Bodies: NEMA FB 1; steel fittings with external PVC
coating, 0.1 mm (40 mil) thick, to match conduit.
4. All PVC-coated conduit and fittings shall be furnished from one manufacturer
for uniform appearance and interchangeability of parts.
6. Only Strap Wrenches are allowed for installing PVC coated rigid steel
conduit.
3. Fittings : NEMA FB 1.
NO.
REV
E. PVC Conduit
DISCIPLINE
ENGINEER
BOS 1. Description: NEMA TC 6 & 8; Suitable for direct burial (type DB) and 90
DATE: 8-23-17 degree C (194 degree F) cable operation.
PROJECT
ENGINEER
AFB 2. Fittings and Conduit Bodies: NEMA - TC 9.
DATE:
8-24-17
CERTIFIED
00-00-16
F. Conduit Support
HAK
8-24-17
DATE: 1. Steel channel
CONSTRUCTION
AGENCY
SIM 2. Steel spring clips
9-20-17
DATE:
OPERATIONS
3. Clamp with bolt and nut
ASB
DATE:
9-25-17 2.03 CONDUIT FITTINGS & ACCESSORIES
CONTROL NUMBER
VERIFICATION
A. Steel Fittings
EDSD
1. For rigid steel conduit provide zinc-coated, cast malleable, ferrous metal,
DATE:
BY:
APPROVAL/CERTIFICATION REQUIREMENTS,
galvanized threads.
17U092-092
SCOPE OF WORK DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION
1. 19mm (¾") through 51 mm (2") shall be compression type. EMT fittings shall
ENGG CERT
C. Grounding Bushing
1. Provide Appleton Type "GIB" Grouse-Hinds Type "GB" or Thomas & Betts
3800 series threaded, grounding type insulated, metallic bushing, in
combination with one exterior and one interior locknut, on each rigid conduit
terminating in sheet metal box, cabinet, trough, gutter or wireway.
DESCRIPTION
D. Expansion Fittings
1. Provide O.Z. Type “AX” or “EX” expansion fitting with bonding jumper in each
exposed conduit crossing a building expansion joint. Provide O.Z. Type “DX”
at each concrete embedded run crossing a building expansion joint.
E. Hubs
1. Provide Appleton “HUB” or “HUB-U” Series or Thomas and Betts “370” series
JO/EWO
F. Unions
NO.
REV
1. Where conduit unions are necessary, provide Appleton Type “EC” or Thomas
DISCIPLINE
ENGINEER
and Betts “Erikson coupling” or equal.
BOS
DATE: 8-23-17 G. Conduit Seals (If detailed on Contract drawings)
PROJECT
ENGINEER
AFB 1. Manufacturers : Crouse-Hinds Type EYS or approved equal
DATE:
8-24-17
CERTIFIED
00-00-16
2. Classification : Explosion proof.
HAK
DATE:
8-24-17 3. Size : Wire fill of standard conduit sealing fittings shall not
CONSTRUCTION
AGENCY
exceed 25% based on the conduit size. Oversized
SIM sealing fittings with reducers may be used in order to
9-20-17 utilize the higher permissible wire fill of the conduit.
DATE:
OPERATIONS
SCOPE OF WORK DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION
PART 3- EXECUTION
3.01 COORDINATION
trades throughout. Provide the type and amount of materials and equipment
necessary to completely installed and ready for use.
C. Support conduit using galvanized iron, zinc plated steel or malleable iron straps,
DATE
lay-in adjustable hangers, clevis hangers, and split hangers. Group related
conduits by using conduit rack support. Construct rack using steel channel; and
NO.
REV
J. Maintain 300mm (12 inch) clearance between conduit and surfaces with
(DCC) NO. _____________________
SCOPE OF WORK DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION
K. Cut metallic conduit square using saw or pipe-cutter, de-burrs cut ends. Threads
must be tapered in accordance with ANSI/ASMI B.1.20.1 and remaining threads
ENGG CERT
exposed after make-up shall be coated with rust preventing grease such as
Crouse Hinds thread lubricant (SAUDI ARAMCO Material Stock No. 14-839-050)
or approved equal.
to entire area inserted in fitting. Allow joint to cure for 20 minutes, minimum.
N. Use conduit hubs with ground lugs to fasten metallic conduit to sheet metal
boxes in damp or wet locations.
O. Install no more than the equivalent of three 90-degree bends between boxes.
Sizes pull boxes per NFPA 70-370-6. Use conduit bodies to make sharp changes
in direction, as around beams. Use factory elbows or hydraulic one-shot bender
to fabricate bends in metal conduit. The minimum bending radius shall be in
JO/EWO
P. Avoid moisture traps; provide junction box or conduit body with stainless steel
DISCIPLINE
ENGINEER
drain fitting at low points in conduit system. Install breathers at high points on
BOS conduit system. 5 mm hole acceptable in bottom of sheet metal boxes.
DATE: 8-23-17
PROJECT
ENGINEER Q. Provide suitable fittings to accommodate expansion and deflection where
AFB necessary.
DATE:
8-24-17
CERTIFIED
00-00-16
R. Expansion fittings shall be installed in each straight conduit run exceeding 45
HAK
meters (150 feet). When expansion fittings are installed, oversized conduit
8-24-17
DATE: clamps shall be used to allow the conduits to move.
CONSTRUCTION
AGENCY
SIM S. Provide suitable pull-wire or nylon rope of adequate strength in each conduit
9-20-17
DATE: except sleeves and nipples.
OPERATIONS
ASB T. All conduit systems shall be swabbed clean before installation of wires or cables.
DATE:
9-25-17 PVC conduits must be checked for internal clearance using mandrel or SAUDI
CONTROL NUMBER
freely pass the mandrel in either direction shall constitute the failure of the
EDSD
U. Use suitable caps to protect installed conduit against entrance of dirt and
REVISIONCERTIFICATION
installation drawings.
17U092-092
SCOPE OF WORK DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION
W. Identify conduit.
ENGG CERT
Y. Arc emitting devices contained within enclosure located in classified areas (Class
1, Division 1 and 2 shall be factory sealed, or conduit seal fittings shall be
installed within 450 mm (18") or such enclosures.
A. Conduit fittings and supports shall be cast or forged steel, cast iron or malleable
iron, either hot-dip galvanized (preferably), or zinc electroplated as supplied by
the manufacturer. No aluminum fittings shall be used. Only malleable iron sealing
fittings shall be used. Gray cast iron split type (EYSR) retrofit sealing fittings may
be used if required for repair purposes.
C. Rigid conduit must be standard taper and lengths, threads shall be completely
covered by the couplings or fittings. Used proper tools in tightening threaded
connections.
DATE
cement specifically manufactured for the purpose. Not to be used for power
DISCIPLINE
ENGINEER
distribution inside buildings.
BOS
DATE: 8-23-17 E. Locknuts & Bushings shall be put on threaded metal conduits end that penetrate
PROJECT
ENGINEER
in metal boxes, cabinets, equipment, etc., except cast thick-walled bodies and
AFB boxes equipped with threaded hubs.
DATE:
8-24-17
CERTIFIED F. Threaded conduit connections to outdoor, weatherproof boxes, cabinets, etc.,
00-00-16
HAK shall be made using watertight, insulated throat, conduit hubs, unless otherwise
DATE:
8-24-17 indicated.
CONSTRUCTION
AGENCY
SIM G. Electric metallic tubing (EMT) connections to boxes, cabinets, etc., shall be made
9-20-17 using watertight, steel on malleable iron, compression ring type conduit
DATE:
OPERATIONS connectors, complete with locknut and insulated bushing. Setscrew conduit
ASB connectors and couplings will not be permitted.
DATE:
9-25-17
H. Flexible metallic conduit and liquid tight conduit connections shall be made using
CONTROL NUMBER
VERIFICATION
insulated steel cast or malleable iron connectors with ridges that thread into the
EDSD
I. Keep bends and offsets in conduit runs to an absolute minimum. For the serving
REVISIONCERTIFICATION
utilities, make large radius bends to meet their requirements. Replace deformed,
APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
CERTIFICATE
flattened, or kinked conduit. Not more than the equivalent of four quarter-bends
00
shall be used in any run between terminals and cabinets, or between outlet and
(DCC) NO. _____________________
SCOPE OF WORK DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION
J. Rigid steel conduit bends, 1-1/2 inch (40 mm) trade size or larger shall be
factory-made bends, or field bend with a power bender designed for the purpose,
ENGG CERT
utilizing bending shoes sized for the conduit used. All bends shall be free of
dents or flattening. Bending manually is not permitted.
K. Plastic conduit (PVC) bends shall be factory-made bends, or field bend using
approved heatbox bender and conduit mandrels to assure full inside diameter
and prevent deforming or discolor conduit.
L. All bends shall have a radius not less than that required by the NFPA 70 -
Chapter 9 Table 2.
DESCRIPTION
A. Use rigid steel conduit and elbows from non-metallic conduits for stub-ups and
risers to grade unless otherwise shown. Approved adapter fittings from steel to
non-metallic conduits shall be used.
in threads of sealing plugs to prevent sticking. For entries above grade, joint with
plugged couplings set flush with building exterior finish.
DATE
purpose. Caulking and sealing compound shall not be used for plugging empty
conduits.
EDSD
DATE:
APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
CERTIFICATE
fastened in place. Conduit shall be firmly supported within 3 feet (910 mm) of
(DCC) NO. _____________________
each outlet box, junction box, cabinet, or fitting. Conduit shall be supported at
17U092-092
least every 10 feet (3 meter) in straight runs. Provide additional supports where
SCOPE OF WORK DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION
B. In steel stud construction, rigidly tie conduit at maximum 4 feet (1.2 m) intervals
ENGG CERT
with No.16 gauge double annealed galvanized wire to prevent conduit movement
from vibration or other causes.
carried. Minimum 3/8 inch diameter (10 mm) where rods are more than 2 feet
(0.6 meter) long provide rigid sway bracing. Conduits shall be securely fastened
to hangers using one-hole malleable straps or steel, factory made split-hinged
pipe clamps.
E. Use one-hole malleable iron straps and spacers with metallic expansion anchors
and screws or preset inserts for conduit run exposed on concrete. Use preset
inserts in concrete when possible.
JO/EWO
ASB
DATE:
9-25-17
CONTROL NUMBER
VERIFICATION
EDSD
DATE:
BY:
REVISIONCERTIFICATION
APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
CERTIFICATE
SCOPE OF WORK DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION
DIVISION 16 – ELECTRICAL
ENGG CERT
PART 1 - GENERAL
B. Connectors
C. Wire marker
1.02 REFERENCES
DISCIPLINE
ENGINEER B. CODES AND INDUSTRY STANDARDS
BOS
8-23-17
DATE: SBC 401 SAUDI Building Code
PROJECT
ENGINEER
AFB NEMA National Electrical Manufacturers Association
DATE:
8-24-17
CERTIFIED
00-00-16
HAK
a. NEMA WC-71 Non-shielded Cables Rated 2001-5000V for use in
8-24-17
the Distribution of electric energy.
DATE:
CONSTRUCTION
AGENCY b. NEMA WC-74 Cross Linked Thermosetting Polyethylene-
SIM
9-20-17
Insulated Wire and Cable for the Transmission
DATE:
and Distribution of Electrical Energy
OPERATIONS
ASB
NFPA National Fire Protection Association
DATE:
9-25-17
CONTROL NUMBER
APPROVAL/CERTIFICATION REQUIREMENTS,
UL Underwriters Laboratory
17U092-092
SCOPE OF WORK DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION
DISCIPLINE
IEEE Institute of Electrical & Electronics Engineers
ENGINEER
BOS
OSHA Occupational Safety & Health Act
DATE: 8-23-17
PROJECT
ENGINEER SAMSS SAUDI ARAMCO Material System Specification
AFB
8-24-17
DATE: BS7671-11 Requirement for electrical installation
CERTIFIED
00-00-16
HAK
8-24-17 1.03 SUBMITTALS
DATE:
CONSTRUCTION
AGENCY A. Before starting any installation of any materials or equipment submit for approval
SIM
9-20-17 a complete list to be incorporated in the work. This list shall include catalog
DATE:
OPERATIONS
numbers; cuts, data sheets, and such other descriptive information as may be
required. No consideration will be given to partial lists submitted. Approval of
ASB
9-25-17
materials will be based on manufacturer's published data, installation and
DATE:
roughing-in data sheets and drawings indicating compliance with the Contract
CONTROL NUMBER
VERIFICATION
documents.
EDSD
A. Protect all materials and equipment from damage during handling and storage.
REVISIONCERTIFICATION
APPROVAL/CERTIFICATION REQUIREMENTS,
work scope.
(DCC) NO. _____________________
17U092-092
SCOPE OF WORK DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION
PART 2 - PRODUCTS
ENGG CERT
2.01 MANUFACTURERS:
Brintec Corp.
Carol Cable Co. Inc.
Senator Wire and Cable Co.
Southwire Company
Saudi Cable Company
Other Approved Manufacturers
Square D Company
Burndy Co.
Thomas and Betts
DATE
by colors other than green, green with yellow stripes, white or gray.
17U092-092
SCOPE OF WORK DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION
F. Low voltage jacketed cables shall comply with NFPA 70 or IEC 502.
ENGG CERT
Use connectors with temperature ratings equal to or greater than those of the
wires upon which used.
DESCRIPTION
B. Copper compression (crimped) type connectors shall be used for splicing and
terminating stranded conductors, except as noted below:
1. Spring pressure type twist-on connectors and pressure set screw connectors
with insulating caps are permitted for:
b. In non-industrial applications.
permitted.
DISCIPLINE
ENGINEER
BOS C. The use of solder lugs is prohibited. Compression connectors for 120mm2 (4/0
DATE: 8-23-17 AWG) and larger conductors shall be two hole NEMA design.
PROJECT
ENGINEER
AFB D. All compression connectors for 10mm2 (8 AWG) and larger conductors shall have
DATE:
8-24-17 a manufacturer’s reference die number and conductor size printed or stamped on
CERTIFIED
00-00-16
the connector.
HAK
8-24-17
DATE: Exception: The use of die less compression tools is acceptable, provided that the
CONSTRUCTION
AGENCY tool is suitable for the connector and (for 8 AWG and larger
SIM conductor connectors) the tool ram embosses the tool
DATE:
9-20-17 manufacturer’s logo on the crimp.
OPERATIONS
ASB E. Insulated ring tongue, locking fork tongue compression (crimped) terminals shall
DATE:
9-25-17 be used for control wiring.
CONTROL NUMBER
VERIFICATION
Exception: Only ring tongue compression (crimped) terminals shall be used for
EDSD
APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
CERTIFICATE
shown on the drawings. Wires at termination points shall be identified by the use
17U092-092
SCOPE OF WORK DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION
A. Color code secondary service, feeder, and branch circuit conductors with factory
applied color as follows:
A Brown
B Black
DESCRIPTION
C Grey
Neutral White
Ground Green
B. Except for ground conductor in which green is mandatory, use conductors with
black insulation or jacket and color-code with Scotch No.35 color-coding tape or
equivalent for specified insulations and jackets not manufactured by the selected
vendor with integral colors. Color-code each conductor entering every box,
cabinet, panelboard, through and wire way. In wire ways and other locations
JO/EWO
PART 3- EXECUTION
NO.
REV
3.01 COORDINATION
DISCIPLINE
ENGINEER
BOS A. Obtain and review shop drawing, products data and manufacturer’s instructions
DATE: 8-23-17 for equipment furnished.
PROJECT
ENGINEER
AFB B. Determine the work to be performed by the building contractors and other trades
DATE:
8-24-17 throughout. Provide the type and amount of materials and equipment necessary
CERTIFIED
00-00-16
to place this work in proper operation, completely installed, wired, tested, and
HAK
ready for use.
DATE:
8-24-17
CONSTRUCTION
AGENCY 3.02 INSTALLATION OF WIRES AND CABLES
SIM
9-20-17
DATE: A. Visual inspection of the wires and cables, before any installation, will be carried
OPERATIONS out by SAUDI ARAMCO Representative.
ASB
DATE:
9-25-17 B. Installation of wires and cables shall conform to SAES and NFPA 70.
CONTRACTOR shall check and increase conduit sizes if required so that correct
CONTROL NUMBER
VERIFICATION
C. Identify each wire in junction boxes, terminal blocks, cabinets, and terminal
DATE:
BY:
APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
CERTIFICATE
D. Conductors shall be continuous between outlets, boxes, devices etc. There shall
OF THIS DRAWING IS COVERED, FOR ALL
SCOPE OF WORK DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION
F. Pull conductors simultaneously where more than one is being installed in the
ENGG CERT
G. Use pulling means including, fish tape, cable rope, and basket weave wire/cable
grips which will not damage cables or raceways. Do not use rope hitches for
pulling attachment to wire or cable.
K. Each circuit shall correspond to the branch circuit number or control circuit
number as indicated. All control wiring shall conform to the certified wiring
diagrams submitted, and the manufacturer's wiring diagrams, and shall control
the equipment in the manner specified.
JO/EWO
M. Do not pull wire or cable through any box, fitting or enclosure where change or
NO.
REV
raceway alignment or direction occurs; do not cut strands from conductors to fit
DISCIPLINE lugs or terminals; and do not bend conductors to less than recommended radius
ENGINEER
BOS as set forth in NFPA 70.
DATE: 8-23-17
PROJECT
ENGINEER
N. Install splice and tap connectors which possess equivalent or better mechanical
AFB strength and insulation rating than conductors being spliced.
DATE:
8-24-17
CERTIFIED O. Use splice and tap connectors which are compatible with conductor material.
00-00-16
HAK
DATE:
8-24-17 P. Provide adequate length of conductors within electrical enclosures and train the
CONSTRUCTION
AGENCY
conductors to terminal points with no excess. Bundle multiple conductors, with
SIM conductors larger than 6mm2 (10 AWG) cabled in individual circuits. Make
9-20-17 terminations so there is no bare conductor at the terminal.
DATE:
OPERATIONS
ASB Q. Tighten electrical connectors and terminals, including screws and bolts, in
DATE:
9-25-17 accordance with manufacturer’s published torque tightening values. Where
manufacturer’s torqued requirements are not indicated, tighten connectors and
CONTROL NUMBER
VERIFICATION
manufacturer's instructions.
00
SCOPE OF WORK DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION
C. Prepare wiring connections using wire and cable with insulation suitable for
ENGG CERT
E. Provide suitable strain-relief clamps and fittings for cord connections at outlet
boxes and equipment connection boxes.
indicated.
A. Cables shall be 500V DC megger tested after installation and prior to placing in
service.
JO/EWO
compliance.
DISCIPLINE
ENGINEER
BOS D. Written result shall submit to SAUDI ARAMCO Representative for interpretation
DATE: 8-23-17 and approval.
PROJECT
ENGINEER
AFB E. Correct the deficiencies found at no cost to SAUDI ARAMCO.
DATE:
8-24-17
CERTIFIED
00-00-16
HAK
DATE:
8-24-17 - END OF SECTION 16123 – WIRES AND CABLES -
CONSTRUCTION
AGENCY
SIM
9-20-17
DATE:
OPERATIONS
ASB
DATE:
9-25-17
CONTROL NUMBER
VERIFICATION
EDSD
DATE:
BY:
REVISIONCERTIFICATION
APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
CERTIFICATE
SCOPE OF WORK DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION
DIVISION 16 - ELECTRICAL
ENGG CERT
PART 1 - GENERAL
A. Panelboard cabinet
DESCRIPTION
1.02 REFERENCES
DISCIPLINE
ENGINEER
B. CODES AND INDUSTRY STANDARDS
BOS
DATE: 8-23-17 SASO SSA775 Fiber glass reinforced polyester meter boxes
PROJECT
ENGINEER
AFB NEMA National Electrical Manufacturers Association
DATE:
8-24-17
CERTIFIED
00-00-16
a. NEMA 250-15 Enclosures for Electrical Equipment
HAK
(1000 Volts Maximum)
DATE:
8-24-17
CONSTRUCTION
AGENCY b. NEMA ICS 6-11 Enclosures for Industrial Control and Systems
SIM
9-20-17
DATE: NFPA National Fire protection Association
OPERATIONS
Steel hardware
APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
CERTIFICATE
UL Underwriters Laboratories
(DCC) NO. _____________________
17U092-092
SCOPE OF WORK DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION
1.03 SUBMITTALS
A. Product data for cabinets and enclosures with classification higher than NEMA 1.
B. Shop drawings for enclosures and cabinets that are to be shop fabricated,
(nonstock items). For shop fabricated junction and pull boxes, show accurately
scaled views and spatial relationships to adjacent equipment. Show box types,
dimensions, and finishes.
JO/EWO
D. Detailed drawings of cover, locking device, meter window and protective cover,
DISCIPLINE
ENGINEER
breaker access window, bill pocket, enclosure bottom plate, and terminals.
BOS
DATE: 8-23-17 E. Diagram for the internal wiring indicating color codes or numbers for each wires
PROJECT
ENGINEER and terminals.
AFB
DATE:
8-24-17 1.04 DELIVERY, STORAGE AND HANDLING
CERTIFIED
00-00-16
HAK
A. Protect all materials and equipment from damage during handling and storage.
8-24-17
DATE: Refer to specifications Section 16010 - "Basic Electrical Requirements" for
CONSTRUCTION
AGENCY complete work scope.
SIM
9-20-17
DATE: PART 2 - PRODUCTS
OPERATIONS
following:
EDSD
DATE:
MK electric
REVISIONCERTIFICATION
APPROVAL/CERTIFICATION REQUIREMENTS,
MK 878 ZIC & MK 861 ZIC steel box with adjustable lug
THIS INDICATES THAT REV. NO.__________
CERTIFICATE
OZ/ Gedney
Robroy Industries, Inc.
Spring City Electrical Mfg. Co.
Woodhead Industries, Inc.
Other Approved Manufacturers
3. Cabinets:
Electric Panelboard, Inc.
Erickson Electrical Equipment Co.
DESCRIPTION
4. Approved Manufacturer(s)
A. Cabinet constructions shall of code gauge sheet steel, each items with a hinged
gasket door, for surface or flush mounting as indicated on the drawings, use
dead-front type, coated with a rust inhibiting primer and finished in baked
DATE
B. Panel board Cabinet trims equipped with a hinged door shall have a semi-flush
DISCIPLINE
ENGINEER
cylinder lock and catch assembly.
BOS
DATE: 8-23-17 2.03 BOXES
PROJECT
ENGINEER
AFB A. Materials shall conform to all requirements as to size for conduit entry and
DATE:
8-24-17 thickness of metal used, and shall be constructed of code-gauge steel of the type
CERTIFIED
00-00-16
as hereinafter specified, and shall be rated for the use and area of installation.
HAK
8-24-17
DATE: B. All boxes 4 11/16" and below shall be equipped with 10/32 - 3/8 inch slotted
CONSTRUCTION
AGENCY hexagon head washer face screw, colored green, where grounded devices are
SIM part of the wiring within the box. All boxes larger than 4 11/16" shall be
9-20-17
DATE: grounded.
OPERATIONS
ASB C. Flush Mounted Boxes, serving exterior equipment and surface mounted lighting
DATE:
9-25-17 fixtures shall be equipped with neoprene gaskets.
CONTROL NUMBER
VERIFICATION
with knockouts, minimum 4 inch (100 mm.) square by 2 inch (55 mm.) deep,
unless otherwise indicated, and shall be of sufficient size to provide free space
DATE:
BY:
for all conductors, wire connectors, wiring devices, etc., and shall be of the type
REVISIONCERTIFICATION
1. Masonry - Interior
(DCC) NO. _____________________
17U092-092
SCOPE OF WORK DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION
2. Masonry - Exterior
Covers shall be in accordance with Section 16140 for the type of wiring
devices served.
3. Exposed Work
In areas where conduit work and wiring devices are run exposed, surface
mounted, cast feraloy, hot-dip galvanized boxes, with minimum 3/4 inch
(20mm) hubs shall be used. Boxes shall be manufactured by "Crouse-
Hinds Company” Cat. No. FD-2 (single conduit feed) and Cat. No. FDC-2
JO/EWO
(through feed).
Boxes shall be securely and rigidly installed to the conduit. Conduits shall
DATE
DISCIPLINE
ENGINEER
4” x 4” junction box with knock out provision may be used where
BOS installation is indoor, in a non-classified area and not subject to any
DATE: 8-23-17 physical damage.
PROJECT
ENGINEER
AFB E. Use manufactured or field fabricated pull and junction boxes where required to
DATE:
8-24-17 facilitate pulling of cables and to meet NFPA 70 requirements for maximum
CERTIFIED
00-00-16
conduit bends.
HAK
DATE:
8-24-17
CONSTRUCTION
AGENCY PART 3 – EXECUTION
SIM
9-20-17 3.01 COORDINATION
DATE:
OPERATIONS
ASB A. Determine the work to be performed by the building contractors and others
DATE:
9-25-17 throughout. Provide the type and amount of materials and equipment necessary
to place this work in proper operation, completely installed, tested, and ready for
CONTROL NUMBER
VERIFICATION
use.
EDSD
A. Locations in Special Finish Materials: For outlet boxes for receptacles and
APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
CERTIFICATE
corners and straight sides. Install such boxes without plaster rings. Saw cut all
17U092-092
SCOPE OF WORK DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION
B. Gasketed Boxes: At the following locations use cast metal, threaded hub type
ENGG CERT
1. Exterior locations.
2. Where surface mounted on unfinished walls, columns or pilasters. (Cover
gaskets may be omitted in dry locations).
3. Where exposed to moisture laden atmosphere.
4. At food preparation equipment within four ft. of steam connections.
5. Where indicated.
DESCRIPTION
C. Mounting: Mount outlet boxes for switches with the long axis vertical or as
indicated. Mount boxes for receptacles either vertically or horizontally but
consistently either way. Locate box covers or device plates so they will not span
different types of building finishes either vertically or horizontally. Locate boxes
for switches near doors on the side opposite the hinges and close to door trim,
even though electrical floor plans may show them on hinge side.
D. Ceiling Outlets: For fixtures, where wiring is concealed, use outlet boxes 4-inches
square by 1-1/2-inches deep, minimum, unless otherwise indicated.
JO/EWO
E. Cover Plates for Surface Boxes: Use plates sized to box front without overlap.
DATE
F. Protect outlet boxes to prevent entrance of plaster, and debris. Thoroughly clean
foreign material from boxes before conductors are installed.
NO.
REV
DISCIPLINE
ENGINEER
3.03 INSTALLATION OF PULL AND JUNCTION BOXES
BOS
DATE: 8-23-17 A. Box Selection: For boxes in main feeder conduit runs, use sizes not smaller than
PROJECT
ENGINEER 8-inches square by 4-inches deep. Do not exceed 6 entering and 6 leaving
AFB raceways in a single box. Quantities of conductors (including equipment
DATE:
8-24-17 grounding conductors) in pull or junction box shall not exceed the following:
CERTIFIED
00-00-16
HAK Size of Maximum no. of
8-24-17
DATE: Largest Conductors Conductors in Box
CONSTRUCTION
AGENCY in Box
SIM
DATE:
9-20-17 No. 4/0 AWG 30
OPERATIONS 250 MCM 20
ASB
9-25-17 B. Cable Supports: Install clamps, grids, or devices to which cables may be
DATE:
secured. Arrange cables so they may be readily identified. Support cable at least
CONTROL NUMBER
VERIFICATION
C. Mount pull boxes in inaccessible ceilings with the covers flush with the finished
DATE:
ceiling.
BY:
REVISIONCERTIFICATION
APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
CERTIFICATE
D. Size: Provide pull and junction boxes for telephone, signal, and other systems at
OF THIS DRAWING IS COVERED, FOR ALL
indicated. Locate boxes strategically and provide shapes to permit easy pulling of
17U092-092
SCOPE OF WORK DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION
C. Set cabinets in finished spaces flush with walls, unless indicated shown
otherwise.
3.05 GROUNDING
DESCRIPTION
tray manufacturer.
NO.
REV
ASB
DATE:
9-25-17
CONTROL NUMBER
VERIFICATION
EDSD
DATE:
BY:
REVISIONCERTIFICATION
APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
CERTIFICATE
SCOPE OF WORK DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION
DIVISION 16 - ELECTRICAL
ENGG CERT
PART 1 - GENERAL
A. Socket outlets.
DESCRIPTION
B. Device Plates
1.02 REFERENCES
a. SAES-123 Lighting
JO/EWO
UL Underwriters Laboratory
NO.
REV
1.04 QUALIFICATIONS
REVISIONCERTIFICATION
APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
CERTIFICATE
SCOPE OF WORK DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION
A. Protect all materials and equipment from damage during handling and
storage. Refer to specifications Section 16010 - “Basic Electrical
DESCRIPTION
1.07 TESTING
A. The type test certificate for each type of outlet box may be accepted in lieu of the
actual tests on the boxes being supplied on this project.
PART 2 - PRODUCTS
JO/EWO
2.01 GENERAL
DATE
A. Provide factory packaged wiring devices, in type, color, and electrical rating for
the service required and as indicated hereinafter. Where type and grade are not
NO.
REV
E.
VERIFICATION
5215” or equivalent.
EDSD
F. New recessed wall mounted dimmer switch, 230V, 60Hz, up to 500W maximum,
DATE:
BY:
40W slide up and down Cat. # Lyneo, white, By: Lutron control or approved
REVISIONCERTIFICATION
equal.
APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
CERTIFICATE
SCOPE OF WORK DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION
A. MK Electric
B. G. E. Wiring Devices
C. Wiring Device Div./Hubbell
D. Leviton Manufacturing Company
E. Pass and Seymour/Legrand
F. Other Approved Manufacturers
B. Recommended Vendor(s)/Supplier(s)
DESCRIPTION
A. Al-Fanar Trading
Tel. No.: 859-3832
Fax No.: 859-3812
B. Abdul Karim Trading
Tel. No.: 833-7110
Fax No.: 833-8242
C. Saudi Electric Supply Co. (SESCO)
Tel. No. 882-6739
JO/EWO
Fax No.882-5768
ASB B. Verify that wall openings are neatly cut and will be completely covered by wall
DATE:
9-25-17 plates.
CONTROL NUMBER
VERIFICATION
3.02 PREPARATION
EDSD
A. Provide extension rings to bring outlet boxes flush with finished surface.
DATE:
BY:
REVISIONCERTIFICATION
APPROVAL/CERTIFICATION REQUIREMENTS,
3.03 INSTALLATION
17U092-092
SCOPE OF WORK DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION
B. Install wiring devices only in electrical boxes which are clean; free from excess
building materials, dirt, and debris.
DISCIPLINE
ENGINEER
A. Inspect each wiring device for defects.
BOS
DATE: 8-23-17 B. Operate each wall switch with circuit energized and verify proper operation.
PROJECT
ENGINEER
AFB C. Verify that each receptacle device is energized.
DATE:
8-24-17
CERTIFIED
00-00-16
D. Test each receptacle device for proper polarity.
HAK
8-24-17
DATE: E. Test each Residual Current Devices (RCD) type receptacles or devices for
CONSTRUCTION
AGENCY proper operation.
SIM
9-20-17
DATE: 3.05 ADJUSTING
OPERATIONS
3.06 CLEANING
VERIFICATION
EDSD
SCOPE OF WORK DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION
DIVISION 16 - ELECTRICAL
ENGG CERT
PART 1 - GENERAL
C. Conduit markers
1.02 REFERENCES
PART 2 – PRODUCTS
DATE:
BY:
APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
CERTIFICATE
background.
(DCC) NO. _____________________
17U092-092
SCOPE OF WORK DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION
C. Letter size:
1. Use 5mm high letters for identifying individual equipment and loads
DESCRIPTION
2. Use 6mm high letters for identifying individual equipment and loads
A. Manufacturers:
4. Rychem
NO.
REV
ASB A. Manufacturers:
DATE:
9-25-17
CONTROL NUMBER
APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
CERTIFICATE
SCOPE OF WORK DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION
A. Install Arc Flash and Shock Hazard Warning Labels on all new electrical
distribution equipment in accordance with current version of SAUDI ARAMCO G.I.
2.721.
B. Labels shall be thermal transfer type label of high adhesion polyester for each
location analyzed and shall be machine printed, with no field markings. Labels
shall meet the requirements of SAES-B-067 Paragraph 4.1.7. Refer to standard
label layout on ARC FLASH 2.721.
DESCRIPTION
PART 3 – EXECUTION
3.01 INSTALLATION
JO/EWO
Ground Green
VERIFICATION
EDSD
code each conductor entering every box, cabinet, panelboard, though, and
APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
CERTIFICATE
wire way. In wire ways and other locations where conductors are
accessible, color-code conductors every 1500mm (5 FT).
(DCC) NO. _____________________
17U092-092
SCOPE OF WORK DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION
b. The label should be placed close to the operating handle, cover latch, or in
DISCIPLINE
ENGINEER
another readily visible location.
BOS
DATE: 8-23-17
PROJECT
ENGINEER -END OF SECTION 16195 – ELECTRICAL IDENTIFICATION-
AFB
DATE:
8-24-17
CERTIFIED
00-00-16
HAK
DATE:
8-24-17
CONSTRUCTION
AGENCY
SIM
9-20-17
DATE:
OPERATIONS
ASB
DATE:
9-25-17
CONTROL NUMBER
VERIFICATION
EDSD
DATE:
BY:
REVISIONCERTIFICATION
APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
CERTIFICATE
SCOPE OF WORK DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION
DIVISION 16 - ELECTRICAL
ENGG CERT
PART 1 - GENERAL
1.07 REFERENCES
DISCIPLINE
ENGINEER
a. NEMA KS 1-13 Heavy Duty Enclosed and Dead-front
BOS Switches (600V maximum)
DATE: 8-23-17
PROJECT
ENGINEER NFPA 70-17 National Fire Protection Association
AFB
DATE:
8-24-17 ANSI American National Standards Institute
CERTIFIED
00-00-16
HAK UL Underwriters Laboratories
DATE:
8-24-17
CONSTRUCTION
AGENCY a. UL 98-16 Standard for Safety Enclosed and Dead-front
SIM Switches
9-20-17
DATE:
OPERATIONS IEEE Institute of Electrical & Electronics Engineers
ASB
DATE:
9-25-17 SAMMS SAUDI ARAMCO Material System Specification
CONTROL NUMBER
VERIFICATION
1.01 SUBMITTALS
(DCC) NO. _____________________
17U092-092
SCOPE OF WORK DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION
A. Protect all materials and equipment from damage during handling and storage.
Refer to specification Section 16010 - "Basic Electrical Requirements" for
DESCRIPTION
PART 2 – PRODUCTS
2.01 MANUFACTURERS
Crouse-Hinds Co.
Cutler-Hammer Inc.
DATE
enclosure.
DATE:
BY:
APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
CERTIFICATE
PART 3 EXECUTION
3.01 INSTALLATION
DATE
A. Mount all individually Disconnect switch rigidly and align properly. Install
disconnect switch on fabricate free standing switch rack with 1.7M high above
NO.
REV
opening/closing cycles with circuit unloaded. Open each switch enclosure for
BY:
APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
CERTIFICATE
then retest to demonstrate compliance. Remove and replace defective units with
OF THIS DRAWING IS COVERED, FOR ALL
SCOPE OF WORK DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION
DIVISION 16 - ELECTRICAL
ENGG CERT
PART 1 - GENERAL
1.02 REFERENCES
DISCIPLINE
ENGINEER
NECA National Electrical Contractors Association)
BOS “Standard of Installation.”
DATE: 8-23-17
PROJECT
ENGINEER NEMA National Electrical Manufacturers Association
AFB
DATE:
8-24-17 a. NEMA KS 1-13 Heavy Duty Enclosed and dead-Front Switches.
CERTIFIED
00-00-16
HAK
b. NEMA PB 1-11 Panelboards
DATE:
8-24-17
CONSTRUCTION
AGENCY c. NEMA PB 1.1 General Instructions for Proper Handling,
SIM Installation, Operation & Maintenance of Panelboard
9-20-17
DATE: Rated 600 Volts or Less
OPERATIONS
ASB W-C- 375/15B Circuit Breakers Molded Case, branch circuit and
DATE:
9-25-17 service.
CONTROL NUMBER
VERIFICATION
UL Underwriter laboratory
EDSD
SCOPE OF WORK DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION
A. Maintenance Data: Include spare parts data listing; source and current prices of
replacement parts and supplies; and recommended maintenance program
including procedures and intervals.
B. Codes and Standards: Comply with the provisions of the latest edition of the
following:-
DATE
1.06 QUALIFICATIONS
NO.
REV
APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
CERTIFICATE
SCOPE OF WORK DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION
PART 2 - PRODUCTS
JO/EWO
2.01 MANUFACTURER
DATE
DISCIPLINE
ENGINEER 1. Eaton Corp.
BOS 2. General Electric Co.
DATE: 8-23-17 3. JEDAC
PROJECT
ENGINEER 4. Siemens Energy & Automation, Inc.
AFB 5. Square D Co.
DATE:
8-24-17 6. WESCOSA
CERTIFIED
00-00-16 7. Middle East Electric Factory co.
HAK
8. Other approved vendor
DATE:
8-24-17
CONSTRUCTION
AGENCY 2.02 LIGHTING AND POWER PANELBOARD ASSEMBLY.
SIM
9-20-17
DATE: A. The panels shall be designed for sequence connection of branch circuit devices,
OPERATIONS
interior adjustable if for flush mounting. Main lugs shall be mechanical solderless
ASB type, and approved for CU conductors. Main lugs shall be secured in line with
DATE:
9-25-17 UL/TUV/ENEC/BSI standards to prevent lugs from turning or loosening when
CONTROL NUMBER
B. The panel chassis assembly shall be rigid to assure accurate alignment of interior
with panel front. Boxes are code gauge galvanized steel. Liberal gutter space
DATE:
BY:
APPROVAL/CERTIFICATION REQUIREMENTS,
for panels shall be modernistic in appearance having light gray finish, and shall
THIS INDICATES THAT REV. NO.__________
CERTIFICATE
SCOPE OF WORK DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION
D. Panel Bus: Copper, ratings as indicated. Provide copper ground bus in each
panel. Provide insulated ground bus where scheduled. The panel shall have a
neutral bus.
E. Fully rated minimum short circuit interrupting rating: 10,000 amperes rms.
Symmetrical for volt AC panels unless otherwise shown on the drawings.
DESCRIPTION
A. Molded Case Circuit Breakers: Bolt-on type thermal magnetic trip circuit
breakers, with common trip handle for all poles. Provide circuit breakers UL listed
as Type C for lighting circuits. Provide UL/TUV/ENEC/BSI Class A residual
current circuit breaker with overcurrent protection (RCBO) circuit breakers where
scheduled. Do not use tandem circuit breakers.
2.04 PANELBOARD
JO/EWO
DISCIPLINE
ENGINEER
2.05 CABLE BUSHING AND CABLE CLAMP:
BOS
DATE: 8-23-17 A. Cable bushings shall be dust, temper and temperature proof, UV stabilized rigid
PROJECT
ENGINEER
PVC and provided in the base of the boxes to accommodate 50mm inside
AFB diameter conduit, for single meter box only and 80mm inside diameter conduit
DATE:
8-24-17 for the rest of meter boxes.
CERTIFIED
00-00-16
HAK B. Galvanized metallic cable clamp fittings 2mm thick shall be provided inside the
8-24-17
DATE: box to support the incoming and outgoing conduits up to 70 mm. Cable entry
CONSTRUCTION
AGENCY plate shall not be removable unless door is opened.
SIM
9-20-17 2.06 BREAKER AND METER MOUNTING RAIL:
DATE:
OPERATIONS
ASB A. Hot-dip galvanized steel rails equipped with sliding spring-loaded steel nuts size
DATE:
9-25-17 M4, suitable for a range of MCCB’s and KWH meters of various sizes, shall be
provided.
CONTROL NUMBER
VERIFICATION
EDSD
PART 3 - EXECUTION
DATE:
BY:
REVISIONCERTIFICATION
3.01 INSTALLATION
APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
CERTIFICATE
SCOPE OF WORK DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION
instructions.
D. Use secured support and anchorage for all individually mounted breakers
required.
E. Mount individually Panelboards 1" off the wall, with top of enclosure not to
exceed 6'-6" above finished floor.
DESCRIPTION
G. Provide typed circuit directory for each branch circuit panelboard. Revise
directory to reflect circuiting changes required to balance phase loads.
location above ceiling or below floor. Minimum spare conduits: 5 empty 25mm (1
inch.) Identify each as SPARE.
DATE
J. Provide Arc Flash and Shock Hazard Warning Labels in accordance with G.I.
7.21
NO.
REV
DISCIPLINE
ENGINEER
3.02 FIELD QUALITY CONTROL
BOS
DATE: 8-23-17 A. Measure steady state load currents at each panelboard feeder, rearrange circuits
PROJECT
ENGINEER in the panelboard to balance the phase loads to within 20 percent of each other.
AFB Maintain proper phasing for multi-wire branch circuits.
DATE:
8-24-17
CERTIFIED
00-00-16
B. Visual and Mechanical Inspection: Inspect for physical damage, proper
HAK
alignment, anchorage, and grounding. Check proper installation and tightness of
8-24-17
DATE: connections for circuit breakers.
CONSTRUCTION
AGENCY
SIM
9-20-17
DATE:
OPERATIONS - END OF SECTION 16470 - DISTRIBUTION PANEL-
ASB
DATE:
9-25-17
CONTROL NUMBER
VERIFICATION
EDSD
DATE:
BY:
REVISIONCERTIFICATION
APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
CERTIFICATE
SCOPE OF WORK DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION
TABLE OF CONTENTS
JO/EWO
DISCIPLINE
ENGINEER
BOS
DATE: 8-23-17
PROJECT
ENGINEER
AFB
DATE:
8-24-17
CERTIFIED
00-00-16
HAK
DATE:
8-24-17
CONSTRUCTION
AGENCY
SIM
9-20-17
DATE:
OPERATIONS
ASB
DATE:
9-25-17
CONTROL NUMBER
VERIFICATION
EDSD
DATE:
BY:
REVISIONCERTIFICATION
APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
CERTIFICATE
SCOPE OF WORK DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION
DATE:
DATE:
DATE:
DATE:
THIS INDICATES THAT REV. NO.__________
OF THIS DRAWING IS COVERED, FOR ALL
CONTROL NUMBER
SIM
ASB
APPROVAL/CERTIFICATION REQUIREMENTS,
AFB
HAK
BOS
AGENCY
BY:
PROJECT
BY DRAWING COMPLETION CERTIFICATE
ENGINEER
ENGINEER
DISCIPLINE
8-24-17
CERTIFIED
9-20-17
8-24-17
DATE: 8-23-17
9-25-17
OPERATIONS
00-00-16
CONSTRUCTION
(DCC) NO. _____________________ 17U092-092 DATE:
1.0
RAS TANURA
(AG-0012 EGG/CBP) ISSUE DATE: 10-08-2017
100%
RESIDENTIAL AREA
SCOPE OF WORK
FULL VOLTAGE CONV. HOUSE TYPE 3TR3S
DOC
SAUDI ARABIA
SIGNED DRAWING COMPLETION CERTIFICATE
S65
A
DWG.TYPE PLANT NO. INDEX
JO/EWO: 17U092
SAUDI ARABIAN OIL COMPANY
RE-778890
DRAWING NO.
of
105
105
SHT.NO.
00
REV.NO.
THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.