INSTALLATION INSTRUCTIONS

HT1R Select Series PWR

Room RH & RH/T Transmitters


RH/TRANSMITTER GND
RTN1 COMMON/RH 2-WIRE
V1 RH 3-WIRE V

RTN1
RTN2

PWR
GND
V1
V2
I1
I2
POS 1 I1 RH 3-WIRE mA
UP 3-wire
DN 2-wire V2 TEMP 3-WIRE V
RH/THERMISTOR
I2 TEMP 3-WIRE mA

RTN1

PWR
TH+

GND
TH-

V1
I1
RH ONLY
RTN2 TEMP 2-WIRE

RTN1

PWR
GND
V1
I1
TH- THERMISTOR OUT
TH+ THERMISTOR OUT

2. Wire sensor as shown above.


IMPORTANT WARNINGS 3. Set the slide selector position (on back of device) to
accommodate either 2-wire or 3-wire outputs. This selector
• Only qualified trade installers should install this product must be ‘up’ for a voltage output.
• This product is not intended for life-safety applications 4. Set DIP switch positions to accommodate your application.
• Do not install in hazardous or classified locations DIP switch 2 only applies to units with transmitter temperature
• The installer is responsible for all applicable codes output selected.
• De-energize power supply prior to installation or service

PRODUCT APPLICATION LIMITATION: BUTTONS DIP 1 2

Senva products are not designed for life or safety applications. DOWN, MENU, UP UP 0-10V 10-35C
DN 0-5V 0-50C
Senva products are not intended for use in critical applications
such as nuclear facilities, human implantable device or life DIP SWITCHES ON

support. Senva is not liable, in whole or in part, for any claims MENU 1 2

or damages arising from such uses. 5. See mounting section.

INSTALLATION 6. Apply power to sensor.

 . IMPORTANT! Locate sensor in an area away from ventilation


1
sources and heat generating equipment and appliances.
Sensor should be mounted at light switch height in a vertical OPERATION
orientation. Use insulating material behind sensor to ensure
reading accuracy.  ress center MENU button to cycle between (1) the sensor
P
readouts, (2) %RH offset, (3) temperature offset (transmitter
NOTE: Do not install sensor in multi-gang electrical boxes with version only), and (4) ºF/ºC display settings (LCD version only).
line voltage or other electrical devices. The next press will return to the readout menu.
OUTSIDE
WALL OR WINDOW
TOO HOT/COLD
The lower arrow and upper arrow can be used to decrease
or increase offset values in 0.1 increments up to ±5 (% or o) or
choose between ºC and ºF.
INSIDE WALL
GOOD TOO HOT/COLD

If no LCD is present, the same menu structure applies except


LOCATION

TOO NEAR
EQUIPMENT OR DOORWAY the oF/oC setting will not be accessible. A red LED will blink
COPIER COMPUTER to indicate %RH offset setting and glow solid to indicate
ROOM
temperature offset setting in oF.

GOOD GOOD
LOCATION LOCATION

senvainc.com 1-866-660-8864 (F)1-503-296-2529 9290 SW Nimbus Ave. Beaverton Oregon 97008


MOUNTING TROUBLESHOOTING
IF MOUNTING INTO A JUNCTION BOX: Symptom Solution
1. Remove drywall clamps by turning screw counter clockwise. Check wiring. Ensure power supply meets
No output
requirements.
Verify control panel software is configured for
correct output scaling.
Verify accuracy of test instrument. Observe
installation and calibration guidelines
Temp or Verify unit is located away from sources of hot/
RH reading cold.
IF MOUNTING INTO DRYWALL: error Verify RH / T sensing element is inserted prop-
1. Turn both mounting clamps all the way counter clockwise. erly
Install insulation foam gasket provided to pre-
vent thermal conduction from inside wall.
Perform calibration only if necessary.

CALIBRATION
Senva RH sensors are factory calibrated to NIST traceable
standards. No field calibration is necessary or recommended.
However, to facilitate compliance with job requirements and
commissioning procedures, provisions for field calibration are
provided:

1. Locate calibration instrument and sensor in close proximity


to each other in a controlled environment free of drafts, people,
2. Insert into drywall cutout. and equipment to reduce influence on RH and temperature.

2. Compare output of sensor to calibration instrument, and


note difference. (In 0-10v mode, 1v = 10%RH)

3. Using the buttons on front of unit, adjust offset value for


%RH as needed. Factory calibration may be restored by setting
offset back to 0.
DIMENSIONS

3. Turn screw clockwise to tighten drywall mounts until tight to


wall.
SPECIFICATIONS
Power supply 12-30VDC/24VAC (1)
Outputs RH and Temperature (option) 3-wire 0-5V/10V(4), 3-wire or 2-wire 4-20mA (Selectable)
RH 0-100%RH
Output scaling
Temperature 50-95oF (10-35oC) or 32-122oF (0-50oC) (selectable)
Thermistor/RTD options Yes, see ordering table in catalog
2% models: ±2% max 0 to 100% RH
Accuracy
3% models: ±3% max 0 to 100% RH
Resolution 0.01%RH
Hysteresis ±0.8%RH
Repeatability 0.08% RH
Non-linearity Factory linearized <1%RH
Relative Humidity Temperature coefficient Fully compensated by on-board sensor
Response time (2) 8s
Output update rate 0.5s
Operating range 0 to 100%RH (non-condensing)
Long term drift <0.25%RH per year
Element Recommended Operating 41 to 140oF (5 to 60oC )@ 20% to 80% RH
conditions (3)
2% RH models, <±0.25oC
Accuracy
3% RH models, <±0.3oC
Resolution 0.01oC
Temperature Transmitter Repeatability 0.04oC
Response time (2) 2s
Output update rate 0.5s
Element Operating range -40 to 140oF (-40 to 60oC)
Enclosure Rating IP20/NEMA 1
Environmental
Unit Temp Rating -40oF to 158oF (-40 to 70oC)
(1) One side of transformer secondary is connected to signal common. Dedicated transformer is recommended.
(2) Time for reaching 63% of reading at 25oC and 1 m/s airflow.
(3) Long term exposures to conditions outside normal range or high humidity may temporarily offset the RH reading (+3%RH after 60 hours.)
(4) 15-30VDC/24VAC power supply voltage required for 10 Volt output. Power consumption 100mA max AC, 50mA max DC

Revised 1/6/2020 Document #152-0071-0D