3/73 Page 73 Monday, October 29, 2001 11:36 AM

References TeSys circuit-breakers


Thermal-magnetic motor circuit-breakers
type GV7-R

Thermal magnetic circuit-breakers GV7-R with screw clamp terminals

Control by rocker lever


Standard power ratings of 3-phase Setting range Reference Weight
motors 50/60 Hz in category AC-3 of thermal
400/415 V 500 V 660/690 V trips
P Icu Ics (1) P Icu Ics (1) P Icu Ics (1)
kW kA kW kA kW kA A kg

7.5 25 100 9 18 100 11 8 100 12…20 GV7-RE20 2.010


9 25 100 11 18 100 15 8 100

GV7-RE
7.5 70 100 9 50 100 11 10 100 12…20 GV7-RS20 2.010
9 70 100 11 50 100 15 10 100
3
9 25 100 11 18 100 15 8 100 15…25 GV7-RE25 2.010
11 25 100 15 18 100 18.5 8 100

9 70 100 11 50 100 15 10 100 15…25 GV7-RS25 2.010


11 70 100 15 50 100 18.5 10 100

18.5 25 100 18.5 18 100 22 8 100 25…40 GV7-RE40 2.010


22 18 100

18.5 70 100 18.5 50 100 22 10 100 25…40 GV7-RS40 2.010


3.3
GV7-RS
22 25 100 30 18 100 30 8 100 30…50 GV7-RE50 2.015

22 70 100 30 50 100 30 10 100 30…50 GV7-RS50 2.015

37 25 100 45 18 100 55 8 100 48…80 GV7-RE80 2.040


55 18 100

37 70 100 45 50 100 55 10 100 48…80 GV7-RS80 2.040


55 50 100

45 25 100 – 18 100 75 8 100 60…100 GV7-RE100 2.040

45 70 100 – 50 100 75 10 100 60…100 GV7-RS100 2.040

55 35 100 75 30 100 90 8 100 90…150 GV7-RE150 2.020


75 35 100 90 30 100 110 8 100

55 70 100 75 50 100 90 10 100 90…150 GV7-RS150 2.020


75 70 100 90 50 100 110 10 100

90 35 100 110 30 100 160 8 100 132…220 GV7-RE220 2.350


110 35 100 132 30 100 200 8 100
160 30 100

90 70 100 110 50 100 160 10 100 132…220 GV7-RS220 2.350


110 70 100 132 50 100 200 10 100
160 50 100
(1) As % of Icu.

Characteristics: Dimensions: Schemes:


pages 3/63 to 3/72 pages 3/78 to 3/80 page 3/81
Schneider Electric 3/73
3/74-75 Page 74 Monday, October 29, 2001 11:37 AM

4
3
3 2
1

GV7-AE11, AB11

3.3 GV7-RE, RS

GV7-AU, AS

3/74 Schneider Electric


3/74-75 Page 75 Monday, October 29, 2001 11:37 AM

References TeSys circuit-breakers


Thermal-magnetic motor circuit-breakers
type GV7-R with screw clamp terminals
Accessories

Add-on auxiliary contact blocks

They allow remote indication of the circuit-breaker contact states. They can be used for signalling, electrical locking,
relaying, etc. Two versions are available: standard and low level. They include a terminal block and the auxiliary circuits
leave the circuit-breaker through a hole provided for this purpose.
They perform the following functions, depending on where they are located in the circuit-breaker:

Location Function Application

1 and/or 4 C/O contact Indicates the position of the circuit-breaker poles

2 Trip Indicates that the circuit-breaker has tripped due to an overload, a short-circuit,
indication a differential faul or the operation of a voltage trip (undervoltage or shunt trip
or of the “push to trip” test button.
It resets when the circuit-break is reset.
3
3 Electrical fault Indicates that the circuit-breaker has tripped due to an overload, a short-circuit or
indication a differential fault. It resets when the circuit-breaker is reset.

Type Reference Weight


kg

Standard GV7-AE11 0.015

Low level GV7-AB11 0.015

Fault discrimination devices

They make it possible to: 3.3


- either differentiate a thermal fault from a magnetic fault,
- or open the contactor only in the event of a thermal fault.

Voltage Reference Weight


kg

a 24...48 and c 24…72 V GV7-AD111 (1) 0.100

z 110…240 V GV7-AD112 (1) 0.100

Electric trips

These allow the circuit-breaker to be tripped via an electrical control signal.

p Undervoltage trip GV7-AU


- Trips the circuit-breaker when the control voltage drops below the tripping threshold, which is between 0.35 and 0.7
times the rated voltage.
- Circuit-breaker closing is only possible if the voltage exceeds 0.85 times the rated voltage.
Circuit-breaker tripping by a GV7-AU trip meets the requirements of IEC/EN 60947-2.
p Shunt trip GV7-AS
Trips the circuit-breaker when the control voltage rises above 0.7 times the rated voltage.
p Operation (GV7-AU or GV7-AS)
- When the circuit-breaker has been tripped by a GV7-AU or AS, it must be reset either locally or by remote control.
(For remote control, please call our Customer information centre on 0870 608 8 608).
- Tripping has priority over manual closing: if a tripping instruction is present, manual action does not result in closing,
even temporarily, of the contacts.
- Durability: 50 % of the mechanical life of the circuit-breaker.

Type Voltage Reference Weight


kg

Undervoltage 48 V, 50/60 Hz GV7-AU055 (1) 0.105


trip 110…130 V, 50/60 Hz GV7-AU107 (1) 0.110
200…240 V, 50/60 Hz GV7-AU207 (1) 0.110
380…440 V, 50/60 Hz GV7-AU387 (1) 0.105
525 V, 50 Hz GV7-AU525 (1) 0.100

Shunt 48 V, 50/60 Hz GV7-AS055 (1) 0.105


trip 110…130 V, 50/60 Hz GV7-AS107 (1) 0.110
200…240 V, 50/60 Hz GV7-AS207 (1) 0.110
380…440 V, 50/60 Hz GV7-AS387 (1) 0.105
525 V, 50 Hz GV7-AS525 (1) 0.100
(1) For mounting of a GV7-AD or a GV7-AU or AS.
Characteristics: Dimensions: Schemes:
pages 3/63 to 3/72 pages 3/78 to 3/80 page 3/81
Schneider Electric 3/75
3/76-77 Page 76 Monday, October 29, 2001 11:38 AM

ON

O
ON OFF

GV7AP04

O
OFF

ON

GV7AP01, AP02

3 GV7RE, RS O
OFF
ON

GV7AP03
ON
O
OFF

ON

O
OFF

O
OFF

GV7AP05

3.3

GV7AC04

GV7AC01

GV7V01

GV7RE, RS GV7-AC04

GV7AC03 GV7AC01

3/76 Schneider Electric


3/76-77 Page 77 Monday, October 29, 2001 11:39 AM

References TeSys circuit-breakers


Thermal-magnetic motor circuit-breakers
type GV7-R with screw clamp terminals
Accessories

Cabling accessories
Description Application For Sold Unit Weight
contactor in reference kg
lots of

Clip-on Up to 150 A, 1.5…95 mm2 – 3 GV7-AC021 0.300


connectors
for GV7-R Up to 220 A, 1.5…185 mm2 – 3 GV7-AC022 0.350

3-pole To increase the – 1 GV7-AC03 0.180


spreader (1) pitch to 45 mm

Terminal shields Supplied with the – 1 GV7-AC01 0.125


IP 405 (1) sealing accessory

Phase Safety accessories used – 2 GV7-AC04 0.075


barriers when fitting of shields
is impossible 3
Insulating screens Ensure insulation between – 2 GV7-AC05 0.075
the connections and the
backplate

Kit for combination Allowing link between the LC1-F185 1 GV7-AC06 0.550
with contactor circuit-breaker and the
(2) contactor. The cover
provides protection against LC1-F225 1 GV7-AC07 0.550
direct finger contact. and F265

LC1-D115 1 GV7-AC08 0.550


and D150

Direct rotary handle 3.3


Replaces the circuit-breaker front cover; secured by screws. It includes a device for locking the circuit-breaker in the O
(Off) position by means of up to 3 padlocks with a shank diameter of 5 to 8 mm (padlocks not supplied). A conversion
accessory allows the direct rotary handle to be mounted on the enclosure door. In this case, the door cannot be opened
if the circuit-breaker is in the “tripped” position. Circuit-breaker closing is inhibited if the enclosure door is open
Description Type Degree of Reference Weight
protection kg

Direct Black handle, black legend plate IP 40 GV7-AP03 0.205


rotary handle
Red handle, yellow legend plate IP 40 GV7-AP04 0.205

Conversion For mounting direct rotary IP 43 GV7-AP05 0.100


accessory (3) handle on enclosure door

Extended rotary handle


Allows a circuit-breaker installed in the back of an enclosure to be operated from the front of the enclosure. It comprises:
- a unit which screws onto the front cover of the circuit-breaker,
- an assembly (handle and front plate) to be fitted on the enclosure door,
- an extension shaft which must be adjusted (distance between the mounting surface and the door: 185 mm minimum,
600 mm maximum). It includes a device for locking the circuit-breaker in the O (Off) position by means of up to 3 padlocks
with shank diameter of 5 to 8 mm (padlocks not supplied). This prevents the enclosure door from being opened.
Description Type Degree of Reference Weight
protection kg

Extended Black handle, black legend plate IP 55 GV7-AP01 0.775


rotary
handle Red handle, yellow legend plate IP 55 GV7-AP02 0.775

Locking device
Allows circuit-breakers not fitted with a rotary handle to be locked in the O (Off) position by means of up to 3 padlocks
with a shank diameter of 5 to 8 mm (padlocks not supplied).
Description Application Reference Weight
kg

Locking device For circuit-breaker not fitted GV7-V01 0.100


with a rotary handle
(1) Terminal shields cannot be used together with spreaders.
(2) The kit comprises links, a protective shield and a depth adjustable metal bracket for the breaker.
(3) This conversion accessory makes it impossible to open the door if the device is closed and prevents the device from
being closed if the door is open.

Characteristics: Dimensions: Schemes:


pages 3/63 to 3/72 pages 3/78 to 3/80 page 3/81
Schneider Electric 3/77