GENERAL ELECTRICAL NOTES AND

SPECIFICATIONS
ALL ELECTRICAL WORKS HEREIN SHALL BE DONE IN ACCORDANCE WITH
APPLICABLE PROVISIONS OF THE LATEST EDITION OF THE PHILIPPINE
ELECTRICAL CODE, REQUIREMENTS OF THE LOCAL AUTHORITIES ENFORCING
A4
THE CODE, AND THE REQUIREMENTS OF THE POWER SERVICE COMPANY
C3
B4

ALL WIRES SHAL BE COPPER TYPE T.W. INTERMIDIATE PVC CONDUIT


B4

(IMC) OR UNLESS OTHERWISE SPECIFIED.


A4

C3
ALL JUNCTION UTILITY, SQUARE AND PULL BOXES SHALL BE GAUGE # 18
B4
B4 OR APPROVED EQUIVALENT AND SHALL BE PAINTED WITH ONE COAT
B4
60 A PRIMER PRIOR TO INSTALLATION.
C3

A4

ALL MATERIALS TO BE USED SHALL BE BRAND NEW AND OF THE APPROVED


2-14.0 sqmm THHN Cu.
SW3 SW4
A4

B3
TYPE, APPROPRIATE WITH THE LOCATION AND INTENDED USE.
A3

A3 A3
Wire in 25 mm Ø Conduit
POWER SUPPLY SHALLBE 220 VOLTS, SINGLE PHASE, 60 HERTS, TWO WIRE

ALL WORKS HEREIN SHALL BE DONE UNDER THE DIRECT SUPERVISION OF A


1 20 A 20 A
A3

2 DULY QUALIFIED AND LICENSED ELECTRICAL ENGINEER OR MASTER

MINIMUM SIZE OF CONDUCTORS SHALL BE 2.0 mm T.W. IN 15 mm TRADE SIZE.


3 20 A 20 A
4
A3 A3

ALL WALL OUTLETS SHALL BE INSTALLED AT THE FOLLOWING


HEIGHT ABOVE FINISHED FLOOR LEVEL UNLESS OTHERWISE NOTED.
A2 A2

5 30 A 30 A
6 A. WALL SWITCHES 1.50 mts.
B. CONVENIENCE OUTLET 0.30 mts.
C. PANEL BOARD 1.80 mts.
30 A
A2 7 30 A 4 D. ELECTRIC METER 1.50 mts
B2
B2 E. SERVICE ENTRANCE 5.40 mts.

ALL VERTICAL AND HORIZONTAL CONDUIT SHALL BE CONCEALED OR


EMBEDDED ON CONCRETE WALLS AND FLOORS.
A2 A2

B2

A2
ALL CONDUITS SHALL BE PROPERLY REAMED PRIOR TO INSTALLATION TO
DAMGES TO THE SKIN OF THE WIRE.
SW2
SW1
B1

A1
WORKMANSHIP OF THE WORK THROUGHOUT SHALL BE EXECUTED IN THE
B1
BEST AND MOST THOROUGH MANNER KNOWN TO THE TRADE AND TO THE
SATISFACTION OF THE ARCHITECT AND THE ENGINEER.
A1
C2

A1
A1
C1

B1

Riser
Schedule Diagram
Of Loads
PROTECTION PER CIRCUIT
A1 CKT. LOAD DESCRIPTION No. OF VOLTS POWER AMPERES
A1
SIZE OF WIRES AND CONDUITS
NO. OUTLETS AT P
A1 A1
2 2
1 LIGHTING OUTLET 19 230 1900 8.26 2 - 3.5 mm THHN Cu. Wire + 3.5 mm THHN Y/G 20 AT 2
2 2
2 LIGHTING OUTLET 22 230 2200 9.57 2 - 3.5 mm THHN Cu. Wire + 3.5 mm THHN Y/G 20 AT 2
2 2
3 CONVENIENCE OUTLET 9 230 1620 7.04 2 - 3.5 mm THHN Cu. Wire + 3.5 mm THHN Y/G 20 AT 2
2 2
4 CONVENIENCE OUTLET 6 230 1080 4.70 2 - 3.5 mm THHN Cu. Wire + 3.5 mm THHN Y/G 20 AT 2
2 2
5 ACU 1 230 1200 5.22 2 - 5.5 mm THHN Cu. Wire + 3.5 mm THHN Y/G 30 AT 2
2 2
6 ACU 1 230 1200 5.22 2 - 5.5 mm THHN Cu. Wire + 3.5 mm THHN Y/G 30 AT 2
2 2
7 ACU 1 230 1200 5.22 2 - 5.5 mm THHN Cu. Wire + 3.5 mm THHN Y/G 30 AT 2

Lighting Layout Plan Power Layout Plan 8 SPARE

E Scale 1:75M
E Scale 1:75M
TOTAL 10400 45.22

I = 45.22 x 0.85DF Use 2-14.0 sqmm THHN Cu. Wire in 25 mm Ø Conduit


= 38.43 A & 60AT main Ckt. Bkr.

Engineer: Date: Owner: Project Title: Cadd By: Sheet COntent/s: No. Revision Date Sheet No.:
This drawing or prints is
property of the architect and
such not be copied, reproduced, Date:
and used as an instrument for
construction or exhibited Mofil Corporation / Proposed nterior Renovation
without their prior notice and
[Link] drawings are not
be returned upon request. Ptr No.: Tin: erome Lalamunan Mofil itchen - Closet - Curtain Checked By: As Shown E-1
Prc No.: Place: Address: Designed By:
RA 5 5 Location: Lipa Town Center, Brgy. Tambo, Lipa City